EVH-602D is an extruded aluminum stationary louver designed
to protect air intake and exhaust openings in building exteriors
specifically for applications requiring extremely high structural
design loadings. Design characteristics meet the performance
criteria established by the Florida Building Code and MiamiDade County. Tested in accordance with and passes TAS 201
(Large Missile Impact), TAS 202 (Uniform Static Air Pressure),
TAS 203 (Cyclic Wind Loading) and TAS 100A (Wind-Driven Rain)
with optiononal VCD-40 damper. EVH-602D may be installed
in a location where the space behind the louver is designed to
accept water penetration and houses water resistant/water proof
equipment, components or supplies. Qualified for installation within
concrete/masonry, steel stud, structural steel or wood framed
building conditions.
Maximum
Nominal Size � � � �Unlimited W x 96 ¼ in. H
Maximum Nominal Single
Section Size � � � �48 ¼ in. W x 96 ¼ in. H
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panels
• Extended sill
• Filter racks
• Flanged frame
• Security bars
• A variety of architectural finishes including:
Clear anodize
Integral color anodize
Baked enamel
Kynar
Optional factory attached VCD-40 damper
Minimum
Nominal Size � � � �12 in. W x 16 in. H
Maximum
Nominal Size � � � �Unlimited in. W x 96 ¼ in. H
Maximum Nominal Single
Section Size � � � �48 ¼ in. W x 96 ¼ in. H
EVH-602D
Florida Product Approval No: FL8042.1
Miami-Dade NOA No.: 06-0711.11
Maximum Wind-load: 150 PSF
*Width and height dimensions furnished
approximately ¼ inch under size.
• May be installed in locations up to 33 ft. above grade
where the space behind the louver is not designed
to accept water penetration and houses non-water
resistant/water proof equipment, components or
supplies.
• Parallel blade action
• Plated steel blade linkage
• Silicone blade seals
• Stainless steel compression jamb seals
• ½ in. diameter plated steel axles
• Synthetic (acetal) sleeve bearings
• Manual quadrant actuator (in airstream)
• Mill nish only
Wind-Driven Rain Performance
75mm/h (3 in/hr) Rainfall & 13 m/s
(29 mph) Wind Velocity
Ventilation Air
Core Velocity
m/s (fpm)
0.0 (0)A0.0 (0)A
0.5 (98)A0.5 (98)A
1.0 (197)A1.0 (197)A
1.5 (295)A1.5 (295)A
2.0 (394)A2.0 (394)A
2.5 (492)A2.5 (492)A
3.0 (591)A2.9 (591)A
3.5 (689)A3.5 (689)A
4.0 (787)A4.0 (787)A
4.5 (886)100.0A4.5 (886)A
5.0 (984)99.9A5.0 (984)100.0A
Water Penetration
Effectiveness%Water Penetration
Classification
Ventilation Air
Core Velocity
m/s (fpm)
Discharge Loss Coefficient Class (Intake) = 2
Weather louvers shall be classified by their ability to reject simulated rain. The
table shows different classifications based on the maximum simulated rain
penetration per square meter (square feet) of louver. Water penetration rating
at a given louver face velocity is determined by the water penetration while
the louver is subjected to a selected simulated rainfall rate and wind velocity.
200mm/h (8 in/hr) Rainfall & 22 m/s
(50 mph) Wind Velocity
Water Penetration
Effectiveness%Water Penetration
Classification
EVH-602DPERFORMANCE DATA
Florida Product Approval No.: FL8042.1
Miami-Dade NOA No.: 06-0711.11
Maximum Wind-load: 150 PSF
Discharge Loss Coefficient Classifications
10.4 and AboveClass Effectiveness
20.3 to 0.399A1 to 0.99
30.2 to 0.299B0.989 to 0.95
40.199 and BelowC0.949 to 0.80
Greenheck Fan Corporation certifies
that the EVH-602D louvers shown
herein are licensed to bear the AMCA
Seal. The ratings shown are based on
tests and procedures performed in
accordance with AMCA Publication 511
and comply with the requirements of the
AMCA Certified Ratings Program. The
AMCA Certified Ratings Seal applies to
air performance, water penetration, and
wind-driven rain ratings.
Wind-driven Rain
Penetration ClassesClassDischarge Loss Coefficient
DBelow 0.80
Airflow Resistance (Standard Air - �075 lb/ft
3
)
Model EVH-602D resistance to airflow (pressure drop)
varies depending on louver application (air intake or air
exhaust). Free area velocities (shown) are higher than average
velocity through the overall louver size. See louver selection
information.
Water Penetration
Test Size 48 in� x 48 in� Test Duration of 15 min�
ml/m2
oz/ft2
0.30
Test Size 48 in. x 48 in.
80
0.25
0.20
60
0.15
40
0.10
20
0.05
Water Penetration per Unit Free Area
0.00
0
ft/min:
m/s:
The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting
the penetration of rainfall under specific laboratory test conditions.
The beginning point of water penetration is defined as that velocity
where the water penetration curve projects through 0.01 oz. of water
(penetration) per sq. ft. of louver free area. *The beginning point of
water penetration for Model EVH-602D is above 1250 fpm free
area velocity. These performance ratings do not guarantee a louver
to be weather-proof or stormproof and should be used in combination
with other factors including good engineering judgement in selecting
louvers.
Test Period 15 minutes
Standard Air - .075 lb/ft
11001150120012501300
6.57.07.5
3
Free Area Velocity
Florida Product Approval No.: FL8042.1
Free Area Chart (sq. ft.)
Louver
Height
Inches
160.230.390.610.770.911.071.231.451.61
180.290.480.760.951.131.331.521.801.99
240.450.761.191.501.782.092.392.833.13
300.611.031.622.042.432.853.263.864.27
360.781.312.062.593.083.614.144.895.41
420.941.582.493.133.724.375.015.926.55
481.111.862.933.674.375.135.886.957.69
541.272.143.364.225.025.896.757.988.84
601.432.413.794.765.676.657.629.019.98
661.602.694.235.316.327.418.5010.0411.12
721.762.964.665.856.978.179.3711.0712.26
781.933.245.106.407.618.9310.2412.1013.40
842.093.525.536.948.269.6911.1113.1314.54
902.263.795.967.498.9110.4511.9814.1615.68
962.424.076.408.039.5611.2112.8615.1916.82
121824303642485460
Louver Width in Inches
EVH-602DPERFORMANCE DATA
Miami-Dade NOA No.: 06-0711.11
Maximum Wind-load: 150 PSF
Core Area Chart (sq. ft.)
Louver
Height
Inches
160.420.771.131.481.832.182.542.893.24
180.520.961.391.832.262.703.143.574.01
240.821.512.192.883.564.254.945.626.31
301.122.052.993.934.865.806.737.678.61
361.422.603.794.986.167.358.539.7210.91
421.723.154.596.027.468.9010.3311.7713.20
482.023.705.397.078.7610.4512.1313.8215.50
542.314.256.198.1210.0611.9913.9315.8717.80
602.614.806.999.1711.3613.5415.7317.9220.10
662.915.357.7810.2212.6615.0917.5319.9622.40
723.215.908.5811.2713.9616.6419.3322.0124.70
783.516.459.3812.3215.2518.1921.1324.0627.00
843.817.0010.1813.3716.5519.7422.9226.1129.30
904.117.5410.9814.4217.8521.2924.7228.1631.60
964.418.0911.7815.4619.1522.8426.5230.2133.89
121824303642485460
Louver Width in Inches
EVH-602DINSTALLATION DETAILS
Florida Product Approval No.: FL8042.1
Miami-Dade NOA No.: 06-0711.11
Maximum Size and Installation Information
Model EVH-602D is a Miami-Dade Qualified and Florida Product Approved louver and must be installed in accordance with the installation instructions shown herein.
Model EVH-602D is qualified for installation within concrete/masonry, steel stud, structural steel or wood framed building conditions. Model EVH-602D is structurally
calculated to withstand positive and negative wind-loads up to 150 PSF. The maximum single section width is 48 in. The maximum single section height is 96 in. While
the maximum section height is limited to 96 in., the width may be unlimited as multiple sections may be installed side by side in accordance with installation instructions.
Maximum Wind-load: 150 PSF
12 in� W x 16 in� H
Wood Opening
Concrete/Masonry Opening
Minimum
Nominal Size
Maximum Nominal Single
Section Size
48 ¼ in� W x 96 ¼ in� H