Greenheck EVH-401 Installation Manual

Wind-Driven Rain Louver
Vertical Blade
Application and Design
EVH-401 is a Wind-Driven Rain louver designed to protect air intake and exhaust openings in building exterior walls that are sensitive to direct water penetration. Design incorporates a drainable head member and vertical rain resistant blades to provide maximum resistance to wind driven rain in even the most extreme weather conditions. The EVH-401 is an AMCA CERTIFIED LOUVER enabling designers to select and apply with confidence.
Standard Construction
Frame � � � � � � � � �Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.081 in. nominal wall thickness
Blades � � � � � � � � �Vertical rain resistant style, heavy gauge
extruded 6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned on approximately 1.5 in. blade spacing
Construction . . . .Mechanically fastened
Birdscreen � � � � � �3/4 in. x 0.051 in. flattened expanded
aluminum in removable frame, inside mount (rear)
Finish � � � � � � � � � �Mill
Sill Pan � � � � � � � �0.063 formed aluminum
Minimum Size � � �12 in. W x 12 in. H
Maximum Single Section Size � � � �60 in. W x 96 in. H
EVH-401
WATER
PENETRATION
AIR
PERFORMANCE
WIND
DRIVEN RAIN
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panel
• Clip angles
• Filter rack
• Flanged frame (head and jamb only)
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel
Kynar
*Width and height dimensions furnished
approximately ¼ inch under size.
Static Pressure Drop
Wind-Driven Rain Performance
EVH-401PERFORMANCE DATA
Wind-Driven Rain Louver
Extruded Aluminum
75mm/h (3 in/hr) Rainfall & 13 m/s
(29 mph) Wind Velocity
Ventilation Air
Core Velocity
m/s (fpm)
0.0 (0) A 0.0 (0) A
0.5 (98) A 0.5 (98) A
1.0 (197) A 1.0 (197) A
1.5 (295) A 1.5 (295) A
2.0 (394) A 1.9 (365) 99.9 A
2.5 (492) A 2.4 (473) 99.9 A
3.0 (591) A 2.9 (570) 99.7 A
3.4 (673) 100.0 A 3.5 (694) 98.8 B
Water Penetration
Effectiveness
%
Water Penetration
Classification
Ventilation Air
Core Velocity
m/s (fpm)
200mm/h (8 in/hr) Rainfall & 22 m/s
(50 mph) Wind Velocity
Water Penetration
Effectiveness
%
Water Penetration
Classification
Discharge Loss Coefficient Class (Intake) = 3
Weather louvers shall be classified by their ability to reject simulated rain. The table shows different classifications based on the maximum simulated rain penetration per square meter (square feet) of louver. Water penetration rating at a given louver face velocity is determined by the water penetration while the louver is subjected to a selected simulated rainfall rate and wind velocity.
Airflow Resistance (Standard Air - �075 lb/ft
Pa
in. wg
1
0.9
200
100
90 80
70
60
50
40
30
0.09
20
0.08
0.07
0.06
0.05
10
0.04
9 8
0.03
7
6
5
0.02
ft/min:
m/s:
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
200 300 400 500 600 700 800 900 1000 2000 3000
3
Intake
Exhaust
2345678910
Free Air Velocity
3
)
Water Penetration
Test Size 48 in� x 48 in� Test Duration of 15 min�
ml/m2
80
60
40
20
Water Penetration per Unit Free Area
0
ft/min:
m/s:
The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity
where the water penetration curve projects through 0.01 oz. of water
Model EVH-401 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection
information.
(penetration) per sq. ft. of louver free area. *The beginning point of
water penetration for Model EVH-401 is above 1250 fpm free area velocity. These performance ratings do not guarantee a louver
to be weather-proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
Discharge Loss Coefcient Classications
Class Discharge Loss Coefcient
1 0.4 and Above Class Effectiveness
2 0.3 to 0.399 A 1 to 0.99
3 0.2 to 0.299 B 0.989 to 0.95
4 0.199 and Below C 0.949 to 0.80
Wind-driven Rain
Penetration Classes
D Below 0.80
Greenheck Fan Corporation certifies that
the EVH-401 louvers shown herein are
licensed to bear the AMCA Seal. The
ratings shown are based on tests and
WATER
PENETRATION
PERFORMANCE
DRIVEN RAIN
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
procedures performed in accordance
AIR
with AMCA Publication 511 and comply
WIND
with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air
®
performance, water penetration, and wind-driven rain ratings.
oz/ft2
0.30
Test Size 48 in. x 48 in.
0.25
0.20
0.15
0.10
0.05
0.00
Test Period 15 minutes
Standard Air - .075 lb/ft
1100 1150 1200 1250 1300
6.5 7.0 7.5
3
Free Area Velocity
Loading...