Greenheck EVH-201 Installation Manual

Wind-Driven Rain Louver
Vertical Blade
Application and Design
EVH-201 is a Wind-Driven Rain louver designed to protect air intake and exhaust openings in building exterior walls that are sensitive to direct water penetration. Design incorporates a drainable head member and vertical rain resistant blades to provide maximum resistance to wind driven rain in even the most extreme weather conditions. The EVH-201 is an AMCA CERTIFIED LOUVER enabling designers to select and apply with confidence.
Standard Construction
Frame � � � � � � � � �Heavy gauge extruded 6063-T5 aluminum,
2 in. x 0.063 in. nominal wall thickness
Blades � � � � � � � � �Vertical rain resistant style, heavy gauge
extruded 6063-T5 aluminum, 0.063 in. nominal wall thickness, positioned on approximately 1 in. blade spacing
Construction . . . .Mechanically fastened
Birdscreen � � � � � �3/4 in. x 0.051 in. flattened expanded
aluminum in removable frame, inside mount (rear)
Finish � � � � � � � � � �Mill
Sill Pan � � � � � � � �0.063 formed aluminum
Minimum Size � � �6 in. W x 12 in. H
Maximum Single Section Size � � � �60 in. W x 96 in. H
EVH-201
WATER
PENETRATION
AIR
PERFORMANCE
WIND
DRIVEN RAIN
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panel
• Clip angles
• Filter rack
• Flanged frame (head and jamb only)
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel
Kynar
*Width and height dimensions furnished
approximately ¼ inch under size.
Static Pressure Drop
Wind-Driven Rain Performance
ORMANCE
DRIVEN RAIN
75 mm/h (3 in./hr) Rainfall &
13 m/s (29 mph) Wind Velocity
Free Area
Velocity
Ventilation Air
Core Velocity
Water
Penetration
(fpm) (m/s) (fpm) (m/s) Class Effective (fpm) (m/s) (fpm) (m/s) Class Effective
0 0 0 0 0 0 0 0
247 1.3 98 0.5 247 1.3 98 0.5
497 2.5 197 1.0 497 2.5 197 1.0
744 3.8 295 1.5 744 3.8 295 1.5
994 5.0 394 2.0 994 5.0 394 2.0
1241 6.3 492 2.5 1241 6.3 492 2.5
1491 7.6 591 3.0 1471 7.5 583 3.0 A 100.0
1718 8.7 681 3.5 A 100.0 1688 8.6 669 3.4 A 99.8
Discharge Loss Coefficient Class (Intake) = 3
Weather louvers shall be classified by their ability to reject simulated rain. The table shows different classifications based on the maximum simulated rain
penetration per square meter (square feet) of louver. Water penetration rating
at a given louver face velocity is determined by the water penetration while the louver is subjected to a selected simulated rainfall rate and wind velocity.
202 mm/h (8 in./hr) Rainfall &
22 m/s (50 mph) Wind Velocity
Free Area
Velocity
Ventilation Air
Core Velocity
Water
Penetration
EVH-201PERFORMANCE DATA
Wind-Driven Rain Louver
Extruded Aluminum
Discharge Loss Coefcient Classications
Class Discharge Loss Coefcient
1 0.4 and Above Class Effectiveness
2 0.3 to 0.399 A 1 to 0.99
3 0.2 to 0.299 B 0.989 to 0.95
4 0.199 and Below C 0.949 to 0.80
Greenheck Fan Corporation certifies
that the EVH-201 louvers shown herein are licensed to bear the
WATER
AMCA Seal. The ratings shown are
PENETRATION
AIR
PERF
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
based on tests and procedures
WIND
performed in accordance with
AMCA Publication 511 and comply with the requirements of the AMCA
®
Certified Ratings Program. The AMCA Certified Ratings Seal applies
to air performance, water penetration, and wind­driven rain ratings.
Wind-driven Rain
Penetration Classes
D Below 0.80
Airflow Resistance (Standard Air - �075 lb/ft
Pa
in. wg
1
0.9
200
100
90 80
70
60
50
40
30
0.09
20
0.08
0.07
0.06
0.05
10
0.04
9 8
0.03
7
6
5
0.02
ft/min:
m/s:
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
200 300 400 500 600 700 800 900 1000 2000 3000
3
Intake
Exhaust
2345678910
3
)
Free Air Velocity
Model EVH-201 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection
information.
Water Penetration
Test Size 48 in� x 48 in� Test Duration of 15 min
ml/m2
oz/ft2
0.30
Test Size 48 in. x 48 in.
80
0.25
0.20
60
0.15
40
0.10
20
0.05
Water Penetration per Unit Free Area
0.00
0
ft/min:
m/s:
The AMCA Water Penetration Test provides a method for
comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through
0.01 oz. of water (penetration) per sq. ft. of louver free area. *The beginning point of water penetration for Model EVH-201 is above 1250 fpm free area velocity. These performance ratings
do not guarantee a louver to be weather-proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
Test Period 15 minutes
Standard Air - .075 lb/ft
1100 1150 1200 1250 1300
6.5 7.0 7.5
3
Free Area Velocity