Greenheck ESS-502D Installation Manual

Miami-Dade Qualified
Sightproof Louver
Application and Design
ESS-502D is an extruded aluminum sightproof louver designed to protect air intake and exhaust openings in building exteriors specifically for applications requiring extremely high structural design loadings. Design characteristics meet the performance criteria established by the Florida Building Code and Miami-Dade County. Tested in accordance with and passes TAS 201 (Large Missile Impact), TAS 202 (Uniform Static Air Pressure) and TAS 203 (Cyclic Wind Loading). The ESS-502D may be installed in a location where the space behind the louver is designed to accept water penetration and houses water resistant/water proof equipment, components or supplies.
Standard Construction
Frame � � � � � � � � �Heavy gauge extruded 6063-T5 (head, sill) and
6105-T5 (jamb) aluminum, 5 in. x 0.081 in. nominal wall thickness
Blades � � � � � � � � �Chevron style, heavy gauge 6105-T5 extruded
aluminum, 0.081 in. nominal wall thickness, positioned on approximately 2 in. centers
Construction . . . .Welded and mechanically fastened
Birdscreen � � � � � �3/4 in. x 0.051 flattened expanded aluminum
in removable frame, inside mount (rear)
Finish � � � � � � � � � �Mill
Continuous Perimeter Angles � � � � � � � � �Ship loose, heavy gauge extruded aluminum, mill
finish
Minimum Rough Opening Size � � �8 in. W x 7 in. H
Maximum Single Section Rough Opening Size � � �144.5 in. W or 144.5 in. H (limited to 72 sq. ft.)
ESS-502D
Florida Product Approval No: FL12941.1
Miami-Dade NOA No.: 09-0519.14
Maximum Wind-load: 110 PSF
Options (at additional cost)
• A variety of bird and insect screens
• Blank-off panels
• Extended sill
• Filter racks
• Flanged frame
• A variety of architectural finishes including:
Clear anodize Integral color anodize Baked enamel Kynar
*Width and height dimensions furnished
approximately ½ inch under size.
Free Area Chart *Based on actual sizing
ml/m2 oz/ft2
Louver Height
in
Inches
12 24 36 48 60 72 84 96 108 120 132 144
12 0.26 0.60 0.94 1.28 1.63 1.97 2.31 2.65 2.99 3.34 3.68 4.02
24 0.72 1.67 2.63 3.59 4.54 5.50 6.45 7.41 8.37 9.32 10.28 11.23
36 1.18 2.75 4.32 5.89 7.46 9.03 10.60 12.17 13.74 15.31 16.88 18.45
48 1.64 3.82 6.01 8.19 10.37 12.56 14.74 16.93 19.11 21.30 23.48 25.66
60 2.10 4.90 7.69 10.49 13.29 16.09 18.89 21.69 24.48 27.28 30.08 32.88
72 2.56 5.97 9.38 12.80 16.21 19.62 23.03 26.44 29.86 33.27 36.68 40.09
84 3.02 7.05 11.07 15.10 19.12 23.15
96 3.48 8.12 12.76 17.40 22.04 26.68
108 3.94 9.19 14.45 19.70 24.96 30.21
120 4.40 10.27 16.14 22.01 27.87 33.74
132 4.86 11.34 17.83 24.31 30.79 37.27
144 5.32 12.42 19.51 26.61 33.71 40.80
Lourver Width in Inches
ESS-502DPERFORMANCE DATA
Florida Product Approval No: FL12941.1
Miami-Dade NOA No.: 09-0519.14
Maximum Wind-load: 110 PSF
Greenheck Fan Corporation certifies that the ESS-502D louvers shown herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and
comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
Airflow Resistance (Standard Air - �075 lb/ft
3
Water Penetration (Standard Air - �075 lb�/ft�3)
)
Test size 48 in. x 48 in. Test duration of 15 min.
0.30
Test Size 48 in. x 48 in.
80
0.25
0.20
60
0.15
40
0.10
20
Water Penetration per Unit Free Area
0.05
0
0.00
ft/min:
m/s:
Test Period 15 minutes
Standard Air - .075 lb/ft
900 950 1000 1050 1100 1150 1200
3
5.0 6.0
Free Area Velocity
Model ESS-502D resistance to airflow (pressure drop) varies de12941.1 on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area. *The beginning point of water penetration for Model ESS- 502D is 1057 fpm free area velocity. These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
ESS-502DPRODUCT/INSTALLATION DETAILS
SINGLE SECTION
Model ESS-502D is a Miami-Dade Qualified louver and must be installed in accordance with the installation instructions shown herein� Model ESS-502D is qualified for installation within concrete/masonry, structural steel, steel stud or wood framed building conditions� Model ESS-502D is structurally calculated to withstand positive and negative wind-loads up to 110 PSF� The maximum single section rough opening width is 144�5 in� The maximum single section rough opening height is 144�5 in� In accordance with installation instructions, the maximum opening width can be unlimited if there is only one section high and the maximum opening height can be unlimited if there is only one section wide�
Florida Product Approval No: FL12941.1
Miami-Dade NOA No.: 09-0519.14
Maximum Wind-load: 110 PSF