Greenheck ESJ-401LT Installation Manual

Stationary Louver
J Blade
Application and Design
ESJ-401LT is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates J style blades, sloped sill and high free area to provide maximum resistance to rain and weather while providing minimum resistance to airflow. The ESJ-401LT is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.063 in. nominal wall thickness
Blades . . . . . . . .J style, heavy gauge extruded 6063-T5
aluminum, 0.063 in. nominal wall thickness, positioned at 37º and 45º angles on approximately 4 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 10 in. H
Maximum Single Section Size . . . 60 in. W x 60 in. H.
ESJ-401LT
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Hinged frame
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
ESJ-401LTPERFORMANCE DATA
Stationary Louver J Blade
Extruded Aluminum
Width in Inches
Height in
Inches
12 18 24 30 36 42 48 54 60
12 0.29 0.49 0.68 0.87 1.06 1.25 1.44 1.58 1.77
18 0.54 0.89 1.24 1.59 1.94 2.29 2.64 2.91 3.26
24 0.75 1.24 1.73 2.22 2.71 3.20 3.69 4.05 4.54
30 1.01 1.67 2.32 2.98 3.63 4.29 4.94 5.43 6.09
36 1.26 2.07 2.89 3.70 4.51 5.33 6.14 6.76 7.57
42 1.47 2.42 3.38 4.33 5.28 6.23 7.19 7.90 8.85
48 1.73 2.85 3.96 5.08 6.20 7.32 8.44 9.28 10.40
54 1.97 3.25 4.53 5.81 7.09 8.37 9.64 10.60 11.88
60 2.18 3.60 5.02 6.44 7.85 9.27 10.69 11.75 13.17
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 900 1000 2000 3000
3
Intake
Exhaust
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model ESJ-401LT resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Greenheck Fan Corporation certifies that
AIR
®
the ESJ­401LT louvers shown herein are licensed to bear the AMCA
WATER
PENETRATION
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
Water Penetration per Unit Free Area
0.30
Test Size 48 in. x 48 in.
80
60
40
20
0
ft/min:
m/s:
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
600 650 700 750 800 850 900
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model ESJ-401LT is 691 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.