Greenheck ESJ-150 Installation Manual

Thin-line Louver
J Style Blade
Application and Design
ESJ-150 is a thin-line stationary louver commonly used for interior or exterior applications where high free area and low airflow resistance is required. The narrow depth makes this product ideal for installation into curtainwalls, windows, doors, or as air conditioning grilles.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063T5 aluminum,
1 ½ in. x 0.063 in. nominal wall thickness
0.063 in. nominal wall thickness, positioned at 30.5º angles on approximately 1
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 10 in. W x 10 in. H (without fl ange)
12 in. W x 12 in. H (with fl ange)
Maximum Single Section Size . . .48 in. W x 60 in. H
7
/
in. centers
8
ESJ-150
Options (at additional cost)
• A variety of bird and insect screens
• Anchor brackets
• Captivated frame
• Extended sill
• Flanged frame
• Glazing adaptor
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver Height Inches
10 12 18 24 30 36 42 48
10 0.23 0.29 0.45 0.60 0.76 0.92 1.06 1.22
12 0.29 0.36 0.56 0.76 0.95 1.15 1.33 1.53
15 0.39 0.48 0.74 1.01 1.27 1.54 1.77 2.04
18 0.46 0.57 0.88 1.20 1.52 1.83 2.11 2.43
21 0.58 0.71 1.11 1.51 1.90 2.30 2.65 3.04
24 0.65 0.80 1.25 1.70 2.15 2.59 2.99 3.43
27 0.75 0.92 1.44 1.96 2.47 2.99 3.44 3.95
30 0.85 1.04 1.62 2.20 2.78 3.36 3.87 4.45
33 0.92 1.14 1.77 2.40 3.03 3.67 4.22 4.86
36 1.04 1.28 1.99 2.71 3.42 4.13 4.76 5.47
39 1.11 1.37 2.13 2.90 3.66 4.42 5.09 5.85
42 1.22 1.49 2.33 3.16 3.99 4.82 5.55 6.38
45 1.31 1.61 2.51 3.41 4.30 5.20 5.98 6.88
48 1.39 1.70 2.65 3.61 2.55 5.50 6.34 7.29
51 1.50 1.85 2.88 3.91 4.94 5.97 6.87 7.90
54 1.58 1.94 3.02 4.10 5.17 6.25 7.20 8.28
57 1.68 2.06 3.21 4.36 5.51 6.66 7.66 8.81
60 1.77 2.18 3.39 4.60 5.81 7.03 8.09 9.30
Louver Width in Inches
ESJ-150PERFORMANCE DATA
Thin-line Louver
Extruded Aluminum
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Model ESJ-150 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 900 1000 2000 3000
3
Exhaust
Intake
2345678910
Free Air Velocity
3
)
This half intentionally left blank.
Loading...
+ 3 hidden pages