Stationary Louver
Drainable Blade
Application and Design
ESD-403LT is a weather louver designed to protect air intake and
exhaust openings in building exterior walls. Design incorporates
a drainable head member and stationary horizontal blades to
channel water to the jambs which guides the water through vertical
downspouts for escape at the sill. The ESD-403LT is an extremely
efficient louver with AMCA LICENSED PERFORMANCE DATA
enabling designers to select and apply with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.063 in. nominal wall thickness
Blades . . . . . . . .Drainable design, heavy gauge extruded
6063-T5 aluminum, 0.063 in. nominal wall
thickness, positioned at 37º and 45º angles on
approximately 4 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 12 in. H
Maximum Single
Section Size . . . 60 in. W x 60 in. H
ESD-403LT
WATER
PENETRATION
AIR
PERFORMANCE
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Hinged frame
• Security bars
• A variety of architectural finishes including:
Clear anodize
Integral color anodize
Baked enamel paint
Kynar paint
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Width in Inches
Height in
Inches
12 18 24 30 36 42 48 54 60
12 0.30 0.50 0.70 0.89 1.09 1.28 1.48 1.63 1.83
18 0.50 0.83 1.15 1.48 1.81 2.13 2.46 2.70 3.03
24 0.77 1.28 1.78 2.28 2.78 3.28 3.78 4.16 4.67
30 0.97 1.59 2.22 2.85 3.48 4.10 4.73 5.20 5.83
36 1.17 1.93 2.69 3.45 4.21 4.97 5.73 6.31 7.07
42 1.44 2.37 3.30 4.23 5.16 6.09 7.02 7.73 8.66
48 1.64 2.70 3.76 4.82 5.88 6.94 8.00 8.80 9.86
54 1.91 3.14 4.38 5.61 6.85 8.08 9.32 10.26 11.49
60 2.10 3.47 4.83 6.20 7.56 8.93 10.29 11.33 12.69
ESD-403LTPERFORMANCE DATA
Stationary Louver Drainable Blade
Extruded Aluminum
Greenheck
Fan
Corporation
AIR
®
certifies
that the
ESD-403LT
louvers
shown
herein are
WATER
PENETRATION
PERFORMANCE
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
licensed to bear the AMCA
Seal. The ratings shown
are based on tests and
procedures performed in
accordance with AMCA
Publication 511 and comply
with the requirements of
the AMCA Certified Ratings
Program. The AMCA
Certified Ratings Seal
applies to air performance
and water penetration
ratings.
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 900 1000 2000 3000
3
Intake
Exhaust
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model ESD-403LT resistance to airflow (pressure drop)
varies depending on louver application (air intake or air
exhaust). Free area velocities (shown) are higher than average
velocity through the overall louver size. See louver selection
information.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
Water Penetration per Unit Free Area
0.30
Test Size 48 in. x 48 in.
80
60
40
20
0
ft/min:
m/s:
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
900 950 1000 1050 1100 1150 1200 1250 1300
4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.2 6.3 6.4 6.5 6.6
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting
the penetration of rainfall under specific laboratory test conditions. The
beginning point of water penetration is defined as that velocity where the
water penetration curve projects through .01 oz. of water (penetration)
per sq. ft. of louver free area.
penetration for Model ESD-403LT is 1007 fpm free area
The beginning point of water
*
velocity. These perfor mance ratings do not guarantee a louver to be
weather proof or stormproof and should be used in combination with other
factors including good engineering judgement in selecting louvers.