Greenheck ESD-202 Installation Manual

Stationary Louver
Drainable Blade
Application and Design
ESD-202 is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to channel water to the jambs which guides the water through vertical downspouts for escape at the sill. The ESD-202 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
2 in. x 0.063 in. nominal wall thickness
Blades . . . . . . . .Drainable design, heavy gauge extruded 6063-
T5 aluminum, 0.063 in. nominal wall thickness, positioned at 45º angles on approximately 3 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 6 in. W x 6 in. H
Maximum Single Section Size . . . 120 in. W or 120 in. H (limited to 70 ft. sq.)
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Glazing adaptor
• Hinged frame
• Security bars
• Welded construction
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
ESD-202
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
*Width and height dimensions furnished
approximately ¼ inch under size.
Stationary Louver Drainable Blade
Free Area Chart (Sq. ft.)
Height
in
Inches
6 121824303642485460667278849096102108114120
6 0.02 0.05 0.09 0.12 0.16 0.19 0.23 0.26 0.29 0.32 0.36 0.39 0.43 0.46 0.50 0.53 0.56 0.59 0.63 0.66
12 0.08 0.22 0.37 0.51 0.66 0.80 0.95 1.09 1.02 1.35 1.49 1.64 1.78 1.93 2.07 2.22 2.33 2.47 2.62 2.76
18 0.14 0.41 0.67 0.94 1.20 1.47 1.74 2.00 2.20 2.47 2.73 3.00 3.26 3.53 3.79 4.06 4.26 4.52 4.79 5.05
24 0.20 0.58 0.95 1.33 1.70 2.07 2.45 2.82 3.10 3.48 3.85 4.22 4.60 4.97 5.35 5.72 6.00 6.38 6.75 7.12
30 0.26 0.74 1.22 1.70 2.18 2.66 3.14 3.62 3.98 4.46 4.94 5.42 5.90 6.38 6.86 7.35 7.71 8.19 8.67 9.15
36 0.31 0.88 1.45 2.02 2.59 3.16 3.73 4.30 4.72 5.29 5.86 6.43 7.00 18.27 8.14 8.71 9.14 9.71 10.28 10.85
42 0.37 1.04 1.72 2.39 3.07 3.75 4.42 5.10 5.60 6.28 6.96 7.63 8.31 8.98 9.66 10.34 10.84 11.52 12.20 12.87
48 0.43 1.23 2.02 2.82 3.62 4.42 5.21 6.01 6.61 7.40 8.20 9.00 9.79 10.59 11.39 12.18 12.78 13.58 14.37 15.17
54 0.49 1.40 2.30 3.21 4.12 5.02 5.93 6.84 7.52 8.42 9.33 10.24 11.14 12.05 12.96 13.86 14.54 15.45 16.36 17.26
60 0.55 1.56 2.57 3.59 4.60 5.61 6.63 7.64 8.40 9.41 10.42 11.44 12.45 13.46 14.48 15.49 16.25 17.26 18.27 19.29
66 0.61 1.73 2.85 3.89 5.10 6.22 7.35 8.47 9.31 10.44 11.56 12.68 13.81 14.93 16.05 17.18 18.02 19.14 20.27 21.39
72 0.65 1.86 3.07 4.28 5.49 6.70 7.91 9.11 10.02 11.23 12.44 13.65 14.86 16.06 17.27 18.48 19.39 20.60 21.80 23.01
78 0.71 2.03 3.35 4.67 5.99 7.31 8.63 9.95 10.94 12.25 13.57 14.89 16.21 17.53 18.85 20.17 21.16 22.48 23.80 25.11
84 0.78 2.22 3.66 5.10 6.54 7.98 9.41 10.85 11.93 13.37 14.81 16.25 17.69 19.13 20.57 22.01 23.09 24.53 25.96 27.40
90 0.84 2.39 3.93 5.48 7.03 8.58 10.13 11.67 12.84 14.38 15.93 17.48 19.03 20.58 22.12 23.67 24.83 26.38 27.93 29.48
96 0.90 2.55 4.20 5.86 7.51 9.17 10.82 12.48 13.72 15.37 17.02 18.68 20.33 21.99 23.64 25.30 26.54 28.19 29.84 31.50
102 0.94 2.69 4.43 6.18 7.92 9.66 11.41 13.15 14.46 16.20 17.94 19.69 21.43 23.18 24.92 26.66 27.97 29.71 31.64 33.20
108 1.00 2.85 4.70 6.55 8.40 10.25 12.10 13.95 15.34 17.19 19.04 20.89 22.74 24.59 26.44 28.29 29.67 31.52 33.37 35.22
114 1.07 3.04 5.01 6.98 8.95 10.92 12.89 14.69 16.34 18.31 20.28 22.25 24.22 26.19 28.14 30.13 31.61 33.58 35.55 37.52
120 1.13 3.21 5.29 7.37 9.45 11.53 13.61 15.69 17.25 19.33 21.41 23.49 25.57 27.65 29.73 31.81 33.37 35.45 37.53 39.61
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Model ESD-202 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 900 1000 2000 3000
3
Exhaust
Intake
2345678910
Free Air Velocity
Width in Inches
3
) Water Penetration (Standard Air - .075 lb/ft3)
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
Water Penetration per Unit Free Area
0.30
Test Size 48 in. x 48 in.
80
60
40
20
0
ft/min:
m/s:
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
900 950 1000 1050 1100 1150 1200 1250 1300
4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 5.8 5.9 6.0 6.1 6.2 6.3 6.4 6.5 6.6
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model ESD-202 is 1058 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
ESD-202PERFORMANCE DATA
Extruded Aluminum
Greenheck Fan Corporation
WATER
AIR
®
certifies that the ESD­202 louvers shown herein are licensed to
PENETRATION
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.