Greenheck EDD-601 Installation Manual

Stationary Louver
Dual Drainable Blade
Application and Design
EDD-601 is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head member and stationary horizontal blades to channel water to the jambs which guides the water through vertical downspouts for escape at the sill. The EDD-601 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
6 in. x 0.081 in. nominal wall thickness
Blades . . . . . . . .Dual drainable design, heavy gauge extruded
6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned at 37º and 45º angles on approximately 6 in. centers
Construction . . Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum
in removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 16 in. H
Maximum Single
Section Size . . .120 in. W or 120 in. H (limited to 70 ft. sq.)
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Glazing adaptor
• Hinged frame
• Security bars
• Welded construction
• 0.125 in. nominal wall thickness
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
EDD-601
*Width and height dimensions furnished
approximately ¼ inch under size.
Stationary Louver Dual Drainable Blade
Free Area Chart (Sq. ft.)
Louver Height
in
12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120
Inches
16 0.44 0.72 1.01 1.29 1.57 1.86 2.14 2.35 2.64 2.92 3.21 3.49 3.77 4.06 4.34 4.55 4.84 5.12 5.41
18 0.50 0.83 1.15 1.47 1.80 2.12 2.45 2.69 3.02 3.34 3.67 3.99 4.32 4.64 4.97 5.21 5.53 5.86 6.18
24 0.70 1.16 1.61 2.07 2.52 2.98 3.43 3.77 4.23 4.68 5.14 5.59 6.05 6.50 6.96 7.30 7.75 8.21 8.66
30 0.94 1.55 2.16 2.77 3.38 3.99 4.60 5.06 5.67 6.28 6.89 7.50 8.11 8.73 9.34 9.79 10.40 11.01 11.63
36 1.19 1.95 2.72 3.49 4.26 5.03 5.80 6.38 7.15 7.92 8.68 9.45 10.22 10.99 11.76 12.34 13.11 13.88 14.64
42 1.43 2.36 3.29 4.22 5.15 6.07 7.00 7.70 8.63 9.56 10.49 11.41 12.34 13.27 14.20 14.90 15.83 16.75 17.68
48 1.68 2.77 3.86 4.94 6.03 7.12 8.21 9.03 10.12 11.20 12.29 13.38 14.47 15.56 16.65 17.46 18.55 19.64 20.73
54 1.93 3.17 4.42 5.67 6.92 8.17 9.42 10.36 11.60 12.85 14.10 15.35 16.60 17.85 19.10 20.03 21.28 22.53 23.78
60 2.17 3.58 4.99 6.40 7.81 9.22 10.62 11.68 13.09 14.50 15.91 17.32 18.73 20.13 21.54 22.60 24.01 25.42 26.83
66 2.42 3.98 5.55 7.12 8.68 10.25 11.82 12.99 14.56 16.13 17.70 19.26 20.83 22.40 23.97 25.14 26.71 28.27 29.84
72 2.66 4.39 6.11 7.84 9.57 11.29 13.02 14.31 16.04 17.77 19.49 21.22 22.94 24.67 26.40 27.69 29.42 31.14 32.87
78 2.91 4.79 6.68 8.56 10.45 12.33 14.22 15.63 17.52 19.40 21.29 23.18 25.06 26.95 28.83 30.25 32.13 34.02 35.90
84 3.15 5.20 7.24 9.29 11.33 13.38 15.42 16.96 19.00 21.05 23.09 25.14 27.18 29.23 31.27 32.81 34.85 36.90 38.94
90 3.40 5.60 7.81 10.01 12.22 14.42 16.63 18.28 20.49 22.69 24.90 27.10 29.31 31.51 33.72 35.37 37.57 39.78 41.98
96 3.65 6.01 8.38 10.74 13.10 15.47 17.83 19.61 21.97 24.34 26.70 29.07 31.43 33.80 36.16 37.94 40.30 42.66 45.03
102 3.89 6.42 8.94 11.47 13.99 16.52 19.04 20.93 23.46 25.98 28.51 31.03 33.56 36.08 38.61 40.50 43.03 45.55 48.08
108 4.14 6.82 9.51 12.19 14.88 17.56 20.25 22.26 24.95 27.63 30.32 33.00 35.69 38.37 41.06 43.07 45.76 48.44 51.13
114 4.39 7.23 10.08 12.92 15.77 18.61 21.46 23.59 26.44 29.28 32.13 34.97 37.82 40.66 43.51 45.64 48.49 51.33 54.18
120 4.63 7.64 10.64 13.65 16.65 19.66 22.67 24.92 27.92 30.93 33.94 36.94 39.95 42.95 45.96 48.21 51.22 54.22 57.23
Louver Width in Inches
EDD-601PERFORMANCE DATA
Extruded Aluminum
Greenheck Fan Corporation certifies that the EDD­601 louvers shown
herein are licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 8009001000 2000 3000
3
Intake
Exhaust
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model EDD-601 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test size 48 in. x 48 in. Test duration of 15 min.
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model EDD-601 is 1107 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather­proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.