Stationary Louver
Dual Drainable Blade
Application and Design
EDD-601 is a weather louver designed to protect air intake and
exhaust openings in building exterior walls. Design incorporates
a drainable head member and stationary horizontal blades to
channel water to the jambs which guides the water through vertical
downspouts for escape at the sill. The EDD-601 is an extremely
efficient louver with AMCA LICENSED PERFORMANCE DATA
enabling designers to select and apply with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
6 in. x 0.081 in. nominal wall thickness
Blades . . . . . . . .Dual drainable design, heavy gauge extruded
6063-T5 aluminum, 0.081 in. nominal wall
thickness, positioned at 37º and 45º angles on
approximately
6 in. centers
Construction . . Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum
in removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 16 in. H
Maximum Single
Section Size . . .120 in. W or 120 in. H (limited to 70 ft. sq.)
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Glazing adaptor
• Hinged frame
• Security bars
• Welded construction
• 0.125 in. nominal wall thickness
• A variety of architectural finishes including:
Clear anodize
Integral color anodize
Baked enamel paint
Kynar paint
EDD-601
*Width and height dimensions furnished
approximately ¼ inch under size.
Stationary Louver Dual Drainable Blade
Free Area Chart (Sq. ft.)
Louver
Height
in
12 18 24 30 36 42 48 54 60 66 72 78 84 90 96 102 108 114 120
Inches
16 0.44 0.72 1.01 1.29 1.57 1.86 2.14 2.35 2.64 2.92 3.21 3.49 3.77 4.06 4.34 4.55 4.84 5.12 5.41
18 0.50 0.83 1.15 1.47 1.80 2.12 2.45 2.69 3.02 3.34 3.67 3.99 4.32 4.64 4.97 5.21 5.53 5.86 6.18
24 0.70 1.16 1.61 2.07 2.52 2.98 3.43 3.77 4.23 4.68 5.14 5.59 6.05 6.50 6.96 7.30 7.75 8.21 8.66
30 0.94 1.55 2.16 2.77 3.38 3.99 4.60 5.06 5.67 6.28 6.89 7.50 8.11 8.73 9.34 9.79 10.40 11.01 11.63
36 1.19 1.95 2.72 3.49 4.26 5.03 5.80 6.38 7.15 7.92 8.68 9.45 10.22 10.99 11.76 12.34 13.11 13.88 14.64
42 1.43 2.36 3.29 4.22 5.15 6.07 7.00 7.70 8.63 9.56 10.49 11.41 12.34 13.27 14.20 14.90 15.83 16.75 17.68
48 1.68 2.77 3.86 4.94 6.03 7.12 8.21 9.03 10.12 11.20 12.29 13.38 14.47 15.56 16.65 17.46 18.55 19.64 20.73
54 1.93 3.17 4.42 5.67 6.92 8.17 9.42 10.36 11.60 12.85 14.10 15.35 16.60 17.85 19.10 20.03 21.28 22.53 23.78
60 2.17 3.58 4.99 6.40 7.81 9.22 10.62 11.68 13.09 14.50 15.91 17.32 18.73 20.13 21.54 22.60 24.01 25.42 26.83
66 2.42 3.98 5.55 7.12 8.68 10.25 11.82 12.99 14.56 16.13 17.70 19.26 20.83 22.40 23.97 25.14 26.71 28.27 29.84
72 2.66 4.39 6.11 7.84 9.57 11.29 13.02 14.31 16.04 17.77 19.49 21.22 22.94 24.67 26.40 27.69 29.42 31.14 32.87
78 2.91 4.79 6.68 8.56 10.45 12.33 14.22 15.63 17.52 19.40 21.29 23.18 25.06 26.95 28.83 30.25 32.13 34.02 35.90
84 3.15 5.20 7.24 9.29 11.33 13.38 15.42 16.96 19.00 21.05 23.09 25.14 27.18 29.23 31.27 32.81 34.85 36.90 38.94
90 3.40 5.60 7.81 10.01 12.22 14.42 16.63 18.28 20.49 22.69 24.90 27.10 29.31 31.51 33.72 35.37 37.57 39.78 41.98
96 3.65 6.01 8.38 10.74 13.10 15.47 17.83 19.61 21.97 24.34 26.70 29.07 31.43 33.80 36.16 37.94 40.30 42.66 45.03
102 3.89 6.42 8.94 11.47 13.99 16.52 19.04 20.93 23.46 25.98 28.51 31.03 33.56 36.08 38.61 40.50 43.03 45.55 48.08
108 4.14 6.82 9.51 12.19 14.88 17.56 20.25 22.26 24.95 27.63 30.32 33.00 35.69 38.37 41.06 43.07 45.76 48.44 51.13
114 4.39 7.23 10.08 12.92 15.77 18.61 21.46 23.59 26.44 29.28 32.13 34.97 37.82 40.66 43.51 45.64 48.49 51.33 54.18
120 4.63 7.64 10.64 13.65 16.65 19.66 22.67 24.92 27.92 30.93 33.94 36.94 39.95 42.95 45.96 48.21 51.22 54.22 57.23
Louver Width in Inches
EDD-601PERFORMANCE DATA
Extruded Aluminum
Greenheck
Fan
Corporation
certifies that
the EDD601 louvers
shown
herein
are licensed to bear the
AMCA Seal. The ratings
shown are based on
tests and procedures
performed in accordance
with AMCA Publication
511 and comply with
the requirements of the
AMCA Certified Ratings
Program. The AMCA
Certified Ratings Seal
applies to air performance
and water penetration
ratings.
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 8009001000 2000 3000
3
Intake
Exhaust
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model EDD-601 resistance to airflow (pressure drop) varies
depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average
velocity through the overall louver size. See louver selection
information.
Test size 48 in. x 48 in. Test duration of 15 min.
The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting
the penetration of rainfall under specific laboratory test conditions. The
beginning point of water penetration is defined as that velocity where the
water penetration curve projects through .01 oz. of water (penetration)
per sq. ft. of louver free area.
penetration for Model EDD-601 is 1107 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weatherproof or stormproof and should be used in combination with other factors
including good engineering judgement in selecting louvers.