Greenheck DG0H10 Installation Manual

Part # 464043
**WARNING**
Disconnect and secure all electrical power to the
“OFF” position prior to inspection or servicing.
Failure to comply with this safety precaution
could result in serious injury or death.
**IMPORTANT**
precaution could result in property damage, serious injury or death.
FOR YOUR SAFETY
If you smell gas
1. Open windows
2. Don’t touch electrical switches
3. Extinguish any open flames
4. Immediately call your gas supplier
Report any damaged equipment to the shipper immediately!
All units are shipped on a skid or packaged to minimize damage during shipment. The transporting carrier has the responsibility of delivering all items in their original condition as received from Greenheck. The individual receiving the equipment is responsible for inspecting the unit for obvious or hidden damage, recording any damage on the bill of lading before acceptance and filing a claim (if required) with the final carrier. Some accessory items are stored inside the unit during shipping. Care must be taken during installation to prevent damage to units.
FOR YOUR SAFETY
The use and storage of gasoline or other
flammable vapors and liquids in open
containers in the vicinity of this appliance
is hazardous.
**WARNING**
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death. Read the installation,
operating, and maintenance instructions
thoroughly before installing or servicing this
equipment.
MaintenanceTroubleshootingOperation
Start-UpInstallation
Reference
MODEL DG / DGX (Direct Spark Ignition)
Make-Up Air Unit
Installation, Operation and Maintenance Manual
®
2
TABLE OF CONTENTS
Installation
Clearance to Combustibles &
Service Clearances . . . . . . . . . . . . . . . .2
Unit - Indoor . . . . . . . . . . . . . . . . . . . . . . .3
Unit - Arrangement DB/HZ . . . . . . . . . . . .4
Unit - Arrangement DBC . . . . . . . . . . . .5-6
Evaporative Module . . . . . . . . . . . . . . . . . .7
Electrical Wiring . . . . . . . . . . . . . . . . . . .8-9
Direct Gas Piping . . . . . . . . . . . . . . . .10-11
Evaporative Cooler Piping . . . . . . . . .12-13
Water Wizard™ . . . . . . . . . . . . . . . . . . . .14
Direct Expansion (DX) Coil Piping . . .15-16
Chilled Water Coil Piping . . . . . . . . . . . .17
Building Pressure Control . . . . . . . . . . . .18
I
Start-Up
Blower . . . . . . . . . . . . . . . . . . . . . . . . .19-20
Direct Gas . . . . . . . . . . . . . . . . . . . . . .21-25
Evaporative Cooling . . . . . . . . . . . . . . . .26
Water Wizard™ . . . . . . . . . . . . . . . . .27-28
S
Operation
VAV and Recirculation Units . . . . . . .29-30
Electrical . . . . . . . . . . . . . . . . . . . . . . . . .31
Water Wizard™ . . . . . . . . . . . . . . . . . . . .32
O
Troubleshooting
Blower . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Heater . . . . . . . . . . . . . . . . . . . . . . . . .34-35
Evaporative Cooling . . . . . . . . . . . . . . . .36
Water Wizard™ . . . . . . . . . . . . . . . . . . . .37
Vibration . . . . . . . . . . . . . . . . . . . . . . . . . .38
T
Reference
Gas Train Layout . . . . . . . . . . . . . . . . . . .44
Control Center Layout . . . . . . . . . . . . . . .45
Dirty Filter Switch . . . . . . . . . . . . . . . . . .45
Start-Up Checklist . . . . . . . . . . . . . . . . . .46
Maintenance Log . . . . . . . . . . . . . . . . . . .47
Warranty . . . . . . . . . . . . . . . . . .Backcover
Maintenance
Routine . . . . . . . . . . . . . . . . . . . . . . . .39-41
Fall . . . . . . . . . . . . . . . . . . . . . . . . .42-43
M
R
STORAGE
When a unit is not going to be in service for an extended period of time, certain procedures should be followed to keep the unit in proper operating condition:
• Plug all piping
• Rotate fan wheel monthly and purge bearings once every one to three months (depending on environment).
• Energize fan motor once every three months
• Store belts flat to keep them from warping and stretching
• Store unit in location without vibration
• Cover unit with tarp to protect from dirt and moisture
• After storage period, purge grease before putting fan into service
NOTE!
Do not cover unit with a black tarp, this would
promote condensation.
NOTE!
Improper storage which results in damage to the
unit will void the warranty.
Clearance to Combustibles / Service Clearances
Floor Top Sides Ends
Insulated Units
0 inches 0 inches 0 inches 0 inches
Non Insulated Units
0 inches 6 inches 6 inches 6 inches
Clearance to combustibles is defined as the minimum distance required between the heater and adjacent combustible surfaces to ensure the adjacent surface’s temperature does not exceed 90 degrees above the ambient temperature.
Recommended Minimum Service Clearances
Housing 32 and less
42 inches on the controls side of the unit
Housing 35 and higher
48 inches on the controls side of the unit
Clearances for component removal may be greater than the service clearances listed.
3
Installation - Indoor Installation
Installation
Step 1 Install Hangers
Install threaded hangers from ceiling supports. When locating hangers, allow enough room to open access panel(s). Two nuts must be used on the end of each threaded hanger. Ceiling supports are supplied by others.
Step 2 Install Unit
Using sheet metal screws, attach the weatherhood/thru-wall/filter section to the blower/burner section. The flange on the weatherhood/thru-wall/filter section should overlap the flange on the blower/burner section.
Raise the assembled unit into place.
Using two nuts per hanger, fasten the unit supports to the hangers under the unit. Appropriate unit supports, such as the optional Greenheck hanging bracket kit or c-channel and angle iron (supplied by others) should be used.
Using self-tapping screws, attach ductwork to unit.
In order to prevent the unit from swinging and to provide a safe environment for service and maintenance, additional measures must be taken to secure the unit in all directions.
Step 3 Seal Wall Opening
Apply sealant around the perimeter of the weatherhood to prevent water penetration and drafts into the building.
NOTE!
Two nuts must be used on each end of each
threaded hanging rod for proper support.
NOTE!
Good duct practices should be followed for all ductwork. Ductwork should be installed in accordance with SMACNA and AMCA guidelines, NFPA 96 and any local codes. Reference the CAPS submittal for
duct sizes.
Sealant
Unit
Supports
Ceiling
Supports
Hangers
Ductwork
Indoor Mounting
Sealing Wall Opening
4
Step 6 Seal Weatherhood Seam
Using an appropriate sealant, seal the seam between the weatherhood and the unit.
Step 3 Apply Sealant
Apply an appropriate sealant around the perimeter of the curb and duct adapter(s) to isolate fan vibration and prevent water penetration.
Step 1 Install Curb and/or Equipment
Support(s)
Position curb/equipment support(s) on the roof (reference the CAPS submittal for placement of curb/equipment support(s) in relation to the unit). Verify that unit supports are level, shim if necessary. Attach curb to roof and flash into place. Attach the equipment support(s) to the roof, remove metal cover, flash to wooden nailer and reinstall cover.
Step 2 Install Ductwork
Good duct practices should be followed for all ductwork. All ductwork should be installed in accordance with SMACNA and AMCA guidelines, NFPA 96 and all local codes. Reference the CAPS submittal for ductwork sizes.
Step 4 Install Unit
Use a crane and a set of spreader bars hooked to the factory lifting lugs to lift and center the unit on the curb/equipment support(s).
Use self-tapping sheet metal screws to fasten the unit to the curb/equipment support(s).
Step 5 Assemble and Attach
Weatherhood
The weatherhood can now be assembled and attached to the unit. Detailed assembly instructions can be found with the weatherhood. If the optional evaporative cooling module was selected, this step does not apply, refer to the installation instructions for the optional evaporative cooling module.
Supply Air Ductwork (Arrangement DB only)
Optional Return Air Duct (Arrangement HZ and DB)
Sealant
Installation - Arrangement DB / HZ
Installation
NOTE!
The use of all lifting lugs and a set of spreader
bars is mandatory when lifting the unit.
NOTE!
Some units come with the weatherhood attached
and step 5 may not apply.
NOTE!
The use of a duct adapter is recommended on a
downblast (DB) arrangement to align the
ductwork with the supply unit. The duct adapter
is only a guide and is not to be used as support
for the ductwork.
Metal Cover
Equipment Support
Roof Curb
Roof Curb
Ductwork
Setting Unit
Complete Rooftop Installation
5
Step 1 Install Curb/Equipment
Support(s)
Position curb/equipment support(s) on the roof (reference the CAPS submittal for placement of curb/equipment support(s) in relation to the unit). Verify that all unit supports are level, shim if necessary. Attach curb to roof and flash into place. Attach the equipment support(s) to the roof, remove metal cover, flash to wooden nailer and reinstall cover.
Step 2 Install Combination Extension
Install combination extension over curb. Lag into place using wood screws. Locate the extension so the tall vented side is over the exhaust opening.
Installation - Roof Mounted Unit Arrangement DBC
Installation
Step 4 Apply Sealant
Apply an appropriate sealant around the perimeter of the curb and duct adapter(s) to isolate fan vibration and prevent water penetration.
NOTE!
The use of a duct adapter is recommended on a
downblast (DBC) arrangement to align the
ductwork with the supply unit. The duct adapter
is only a guide and is not to be used as support
for the ductwork.
Step 3 Install Ductwork
Good duct practices should be followed for all ductwork. All ductwork should be installed in accordance with SMACNA and AMCA guidelines, NFPA 96 and any local codes. Reference the CAPS submittal for ductwork size and location.
Curb and Equipment Support
Combination Extension
Ductwork
Sealing Ductwork
Roof Curb
Metal Cover
Equipment Support
Exhaust
Supply
1 inch Inside Flange
Supply Ductwork by Others
Exhaust Duct Installed
Sealant
Supply Duct with Duct Adapter Installed
Exhaust Ductwork by Others
6
Model CUBE Exhaust Fan
Step 5 Install Exhaust Fan
Fasten exhaust fan to curb extension with self­tapping sheet metal screws.
Step 6 Install Exhaust Options
Install optional Greenheck hinge kit with restraining cables and grease trap with drain connection.
Step 7 Install Supply Unit
Use a crane and a set of spreader bars hooked to the factory lifting lugs to lift and center the unit on the extension/equipment support(s).
Use self-tapping sheet metal screws to fasten the unit to the extension/equipment support(s).
Installation - Roof Mounted Unit Arrangement DBC
Step 8 Assemble and Attach
Weatherhood
The weatherhood can now be assembled and/or attached to the unit. Detailed assembly instructions can be found with the weatherhood. If the optional evaporative cooling module was selected, this step does not apply, refer to the installation instructions for the optional evaporative cooling module.
Installation
NOTE!
Installing the exhaust fan prior to the supply unit
will allow for easier installation of options.
NOTE!
The use of all lifting lugs and a set of spreader
bars is mandatory when lifting unit.
Step 9 Seal Weatherhood Seam
Using an appropriate sealant, seal the seam between the weatherhood and the unit.
NOTE!
Some units come with the weatherhood attached
and step 8 may not apply.
Installing Exhaust Fan
Installing Supply Unit
Complete Combination Installation
7
NOTE!
When mounting the evaporative cooler, it is important that it is
level to ensure proper operation and water drainage.
Installation - Evaporative Module (Optional)
Installation
Step 1 Locate Equipment Support(s)
Position equipment support(s) on the roof (reference the CAPS submittal for placement of equipment support(s) in relation to the unit). Verify that all unit supports are level, shim if necessary. Attach equipment support to the roof, remove metal cover, flash to wooden nailer and reinstall cover.
Step 2 Apply Sealant
Apply an appropriate sealant around the airstream opening to create an air tight seal.
Step 3 Set Evaporative Cooling Module
Use a crane and a set of spreader bars hooked to the factory lifting lugs to lift and center the module on the equipment support(s). The flange on the evaporative cooler should overlap the flange on the unit.
Step 4 Secure Cooling Module to Unit
Use self-tapping screws to fasten the cooling module to the base unit along the top and down both sides. Fasten at the top through the flanges. To fasten the sides, the media must be removed. To remove the media, first remove the access panel on the evaporative module and disconnect the evaporative pump(s). The media will now slide out. With the media removed, you can access the side fastening points inside the evaporative module. With all the screws in place, reinstall the media, reconnect the pumps and reinstall the access panel.
NOTE!
Small evaporative coolers ship attached to the base unit and require no additional mounting.
NOTE!
The use of all lifting lugs and a set of spreader bars is mandatory when lifting the evaporative
cooling module.
Metal Cover
Equipment Support
Sealant
Equipment Support
Sealant
Placing Evaporative Module
Securing Evaporative Module
8
Step 4 Wire the Optional Convenience Outlet
The convenience outlet requires a separate 115V power supply circuit. The circuit must include short circuit protection which may need to be supplied by others.
Step 3 Connect the Main Power
Connect the main power lines to the disconnect switch and main grounding lug(s). Torque field connections to 20 in-lbs. See the control center layout in the reference section for main disconnect and grounding lug(s) locations.
Installation - Electrical Wiring
CAUTION!
If replacement wire is required, it must have a
temperature rating of at least 105°C, except for
energy cut-off or sensor lead wire which must be
rated to 150°C.
CAUTION!
Any wiring deviations may result in personal injury or property damage. Greenheck is not responsible
for any damage to, or failure of the unit caused by incorrect final wiring.
Installation
DANGER!
High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.
IMPORTANT!
All wiring should be done in accordance with the
latest edition of the National Electrical Code
ANSI/NFPA-70 and any local codes that may
apply. In Canada, wiring should be done in
accordance with the Canadian Electrical Code.
IMPORTANT!
The equipment must be properly grounded.
Any wiring running through the unit in the
airstream must be protected by metal conduit,
metal clad cable or raceways.
Step 1 Determine the Size of the Main
Power Lines
The units nameplate states the voltage and the unit’s MCA. The main power lines to the unit should be sized accordingly. The nameplate is located on the outside of the unit on the control panel side.
Step 2 Provide the Opening(s) for the
Electrical Connections
Electrical openings vary by unit size and arrangement and are field supplied.
Voltage, Hertz,
and Phase
Unit’s MCA
IMPORTANT!
Before connecting power to the unit, read and understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached to the inside of the control center door(s).
IMPORTANT!
Greenheck’s standard control voltage is 24 VAC.
Control wire resistance should not exceed 0.75 ohms (approximately 285 feet total length for 14 gauge
wire; 455 feet total length for 12 gauge wire). If the resistance exceeds 0.75 ohms an industrial-style,
plug-in relay should be wired in place of the remote switch. The relay must be rated for at least 5
amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to
chatter or not pull in, resulting in contactor failures and/or motor failures.
Electrical Nameplate
SUP HP
MCA
EXH HP
MOP
VOLTS HZ PH
9
Step 5 Wire the Accessories
Reference the ladder diagram on the inside of the control center door for correct wiring of the following accessories:
Step 6 Wire the Optional Evaporative
Cooler
Reference the ladder diagram on the inside of the control center door for correct wiring of the pump and the optional auto-drain and flush.
Step 7 Check Recirculation / VAV
Operation
Two Position Damper Control
Turn the recirculating switch on the remote control panel to each position and confirm that the return air damper adjusts accordingly. The damper actuator may take a few minutes to open or close.
Two Speed
Turn the fan speed switch on the remote control panel to each positions and confirm that the fan speed adjusts accordingly.
Potentiometer Control
To test potentiometer operation, turn the potentiometer to the two extremes. With 80/20 recirculation, confirm that the return air damper fully opens and fully closes. The damper actuator may take a few minutes to open or close. With variable volume, make sure the fan goes to maximum and minimum speed.
Building Pressure Control
See Installation - Building Pressure control for building pressure set-up and operation check.
External Signal Control
See Operation-VAV and Recirculating units for additional information. External 2-10 VDC / 4-20 mA signal required.
NOTE!
Large evaporative coolers may require a
separate power supply.
NOTE!
TSCP has number-to-number wiring.
NOTE!
Wiring to the Selectra Stat should be in separate
conduit or run with shielded cable.
Installation - Electrical Wiring
Installation
NOTE!
For maintenance issues associated with variable
frequency drives, consult the drive’s manual
supplied with the unit. The drives are
programmed at the factory and should not need
any adjustment during installation and start-up.
For kitchen applications, the drive may be
located in the kitchen or in the unit.
NOTE!
Blower Start-Up, steps 1-4 should be performed
before the blower is run.
• Selectra Stat
• Room Override
• Blower Switch
• Heat Switch
• Indicating Lights
• Dirty Filter Indicator
• TSCP
• KSCP
70
65
75
80
85
90
60
55
(OPTIONAL)
BLOWER
DIRTY FILTERS
MAIN VALVES
EXHAUST
SUPPLY
HEAT
(OPTIONAL)
GREENHECK
®
PHOTOHELIC
70
65
75
80
85
90
60
55
(OPTIONAL)
BLOWER
DIRTY FILTERS
MAIN VALVES
EXHAUST
SUPPLY
HEAT
(OPTIONAL)
GREENHECK
®
70
65
75
80
85
90
60
55
GREENHECK
®
(OPTIONAL)
BLOWER
DIRTY FILTERS
MAIN VALVES
RECIRCULATION
EXHAUST
SUPPLY
HEAT
(OPTIONAL)
2-Position Damper Control
Potentiometer Control
Building Pressure Control
10
Installation - Direct Gas Piping
Installation
Step 1 Determine the Supply Gas Requirements
The unit’s direct gas nameplate states the requirements for the gas being supplied to the unit. The direct gas nameplate is located on the outside of the unit on the control center side.
IMPORTANT!
All gas piping must be installed in accordance with the latest edition of the National Fuel Gas Code
ANSI/Z223.1 and any local codes that may apply. In Canada, the equipment shall be installed in
accordance with the Installation Code for Gas Burning Appliances and Equipment (CGA B149) and
Provincial Regulations for the class. Authorities having jurisdiction should be consulted before
installations are made.
WARNING!
All components of this or any other gas fired heating unit must be leak tested prior to placing the unit
into operation. A soap and water solution should be used to perform this test. NEVER test for gas
leaks with an open flame.
WARNING!
If pressure testing in excess of 1/2 psig (3.5
kPa), the heater and manual shutoff valve must
be disconnected from the supply gas line.
WARNING!
If pressure testing at or below 1/2 psig (3.5 kPa),
the heater must be isolated from the supply gas
line by closing its manual shutoff valve.
IMPORTANT!
All piping should be clean and free of any foreign
matter. Foreign material entering the gas train
can damage the valves, regulators and burner.
“W.C.
“W.C.
“W.C.
F
PSI
“W.C.
“W.C.
MAX BTU/HR BTU/H MAX
NORMAL MANIFOLD PRESSURE PRESSION D’ADMISSION NORMALE
MIN GAS PRESSURE PRESSION DE GAZ
MIN BURNER PRESSURE DROP PERTE MIN DE PRESSION DANS LE BRULEUR
TYPE OF GAS NATURE DU GAZ
MIN BTU/HR BTU/H MIN
MIN GAS PRESSURE FOR MAX OUTPUT PRESSION DE GAZ MIN POUR PUISSANCE MAX
MAX BURNER PRESSURE DROP PERTE MAX DE PRESSION DANS LE BRULEUR
MAX GAS PRESSURE PRESSION DE GAZ MAX
DESIGN ∆T T NORMALE
EQUIPPED FOR
CONCU POUR
SCFM
“W.C.
EXTERNAL STATIC PRESSURE
PRESSION STATIQUE EXTERIEURE
AGAINST
CONTE
Maximum gas
pressures
Minimum gas
pressure for
maximum output
Type of Gas
IMPORTANT!
Do NOT connect the unit to gas types other than
what is specified and do NOT connect the unit to
gas pressures that are outside of the pressure
range shown on the label.
Direct Gas Nameplate
11
Installation - Direct Gas Piping
Installation
To
Controls
Gas Cock
From
Gas
Supply
6 in. Trap
1/8 in. Plugged Tap
Ground Joint Union
Step 3 Connect the Supply Gas Line
A manual shut off valve (gas cock), 1/8 in. plugged test port and 6 in. drip leg must be installed prior to the gas train. The valve and the test port must be accessible for the connection of a test gauge. Supply gas connections must be made by a qualified installer and are not furnished by Greenheck.
Step 2 Install Additional Regulator if
Required
When the supply gas pressure exceeds the maximum gas pressure shown on the direct gas nameplate, an additional regulator (by others) is required to reduce the pressure. The regulator must have a listed leak limiting device or it must be vented to the outdoors.
Step 4 Test the System for Leaks
Check both the supply lines and the factory piping for leaks. Apply a soap and water solution to all piping and watch for bubbling which indicates a leak.
WARNING!
The factory piping has been checked for leaks,
but should be rechecked due to shipping and installation.
WARNING!
NEVER test for a gas leak with an open flame.
NOTE!
The regulator located inside the unit is used to
adjust the unit’s maximum output temperature.
Supply Gas Line
12
Installation - Evaporative Cooling Piping (Optional)
Evaporative Cooling with Recirculating Pump
Installation
IMPORTANT!
The supply line should be of adequate size and pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be the same size or larger than the supply line.
Step 1 Install the Water Supply Line
Supply line opening requirements vary by unit size and arrangement and are field supplied. Connect the water supply line to the float valve through the supply line opening in the evaporative cooling unit. Install a manual shutoff valve in the supply line as shown above.
Step 2 Install the Drain Line
Connect an unobstructed drain line to the drain and overflow connections on the evaporative cooler. A manual shut off valve (by others) is required for the evaporative cooler drain line. A trap should be used to prevent sewer gas from being drawn into the unit. Refer to piping diagram above.
Step 3 Check/Adjust Water Level
Check the water level in the sump tank. The water level should be above the pump intake and below the overflow. Adjust the float as needed to achieve the proper water level.
CAUTION!
Provisions must be taken to prevent damage to the evaporative cooling section during freezing
conditions. The sump, drain lines and supply lines must be drained prior to freezing conditions or an
alternate method must be used to protect the lines and media.
IMPORTANT!
All supply solenoids, valves and all traps must be below the roofline or be otherwise protected from
freezing.
6 in. min.
6 in. min.
Supply Line
Overflow
Trap
Drain Line Valve (Normally Open)
Drain Line
Supply Line Valve (Normally Closed)
Recirculating Evaporative Piping
Drain Trap
13
Installation - Evaporative Cooler Piping (Optional)
Installation
IMPORTANT!
The supply line should be of adequate size and pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be the same size or larger than the supply line.
CAUTION!
All solenoids valves and traps must be installed
below the roof to protect the supply water line
from freezing. If they cannot be installed below
the roof, an alternative method must be used to
protect the lines from freezing
IMPORTANT!
The supply solenoid (Valve A) is NOT the same as
the drain solenoids (Valve B and Valve C). Make
sure to use the proper solenoid for each
location. Check you local code requirements for
proper installation of this type of system.
Step 1 Install the Water Supply Line
Supply line opening requirements vary by unit size and arrangement and are field supplied. Connect the water supply line to the float valve through the supply line opening in the evaporative cooling unit. Install the 1/2 in. normally closed solenoid (Valve A) in the supply line as shown above. Install the 1/4 in. normally open solenoid (Valve B) between the supply line and the drain line as shown above.
Step 2 Install the Drain Line
Connect an unobstructed drain line to the sump drain overflow connection. Install the 3/4 in. normally open solenoid (Valve C) between the sump drain connection and the drain line. A trap should be used to prevent sewer gas from being drawn into the unit. Refer to piping drawing above.
Evaporative Cooling with Auto Drain and Fill
Step 3 Check/Adjust Water Level
Check the water level in the sump tank. The water level should be above the pump intake and below the overflow. Adjust the float as needed to achieve the proper water level.
6 in. min.
6 in. min.
Auto-Drain and Fill Evaporative Piping
Drain Trap
Auto Drain & Flush Valves (when provided by Greenheck)
Assembly
Number
GFC
Part Number
ASCO
Part Number
Solenoid Type
De-Energized
Position
Diameter Quantity
852178
461262 8210G2 Supply Closed 1/2 inch 1
461263 8262G62 Supply Line Drain Open 1/4 inch 1
461264 8210G35 Sump Drain Open 3/4 inch 1
Supply Line
VALVE B
Supply Line Drain Solenoid
(Normally Open)
Sump Overflow
Sump Drain
VALVE C
Sump Drain Solenoid
(Normally Open)
VALVE A
Supply Solenoid
(Normally Closed)
Drain Line
Part numbers subject to change.
14
Installation
Evaporative Cooling with the Water Wizard
Installation - Water Wizard™ (Optional)
Step 3 Wire the Solenoid(s)
Wire the supply line solenoid and drain solenoid as shown on the unit’s wiring diagram in the control center.
Step 4 Wire the Temperature Sensor
If the evaporative cooler shipped separate from the unit, the temperature sensor must be wired. The sensor wire is bundled inside the discharge end of the evaporative cooler. Wire the sensor wire to terminals AI2 and AIC on the terminal strip in the unit’s control center.
Step 1 Install Normally Closed Supply Line/Solenoid
Connect the water supply line to the manual supply valve in the unit. Install the supply solenoid in the supply line, upstream of the manual supply valve and below the roofline.
Step 2 Install Normally Open Drain Line/Solenoid
Connect the drain line to the supply line between the manual supply valve and the supply solenoid. Install a drain solenoid in the drain line, below the roof line. A trap should be installed in the drain line.
CAUTION!
Any wiring deviations may result in personal injury or property damage. Greenheck is not
responsible for any damage to, or failure of the
unit caused by incorrect final wiring.
NOTE!
The Water Wizard start-up must be completed for proper performance.
NOTE!
Solenoid(s) may be provided by Greenheck (if ordered) or by others.
WARNING!
Disconnect and lock-out all power and gas
before performing any maintenance or service to
the unit. Failure to do so could result in serious
injury or death and damage to equipment.
NOTE!
The following instructions are provided for
evaporative coolers equipped with the Water
Wizard only. Additional instructions are provided
for evaporative coolers equipped with the auto-
drain and fill or bleed-off.
Water Wizard Valves (when provided by Greenheck)
Unit
Model
Assembly
Number
GFC
Part Number
ASCO
Part Number
Solenoid
Type
De-Energized
Position
Diameter Quantity
DG0H10/H20
DGX-H12/H22
DGX-H30 (<9000 cfm)
852370
461262 8210G2 Supply Closed 1/2 inch 1
383086 8210G34
Supply Line
Drain
Open 1/2 inch 1
DG-H30
DGX-H32 (9000 cfm)
852371
383088 8210G9 Supply Closed 3/4 inch 1
383086 8210G34
Supply Line
Drain
Open 1/2 inch 1
Supply Line Drain Solenoid
(Normally Open)
Supply Solenoid
(Normally Closed)
Manual
Supply Valve
Pressure
Gauge
To Media
Sump
Drain
Roof
Line
Trap
Water Wizard Installation
Factory
Installed
Field
Installed
Part numbers subject to change.
15
Installation - Direct Expansion (DX) Coil Piping (Optional)
Installation
IMPORTANT!
Guidelines for the installation of direct expansion cooling coils have been provided to insure proper
performance and longevity of the coils. These are general guidelines that may have to be tailored to
meet the specific requirements of any one job. As always, a qualified party or individual should
perform the installation and maintenance of any coil. Protective equipment such as safety glasses,
steel toe boots and gloves are recommended during the installation and maintenance of the coil.
IMPORTANT!
All field brazing and welding should be
performed using high quality materials and an
inert gas purge (such as nitrogen) to reduce
oxidation of the internal surface of the coil.
IMPORTANT!
All field piping must be self supporting and
flexible enough to allow for the thermal
expansion of the coil.
Hot Gas Bypass
(by others)
Step 1 Locate the Distributor(s) by Removing the Distributor Access Panel
(by others)
Installation with Hot Gas Bypass
Step 2 Verify Nozzle Placement
Inspect the refrigerant distributor and verify that the nozzle is in place. The nozzle is generally held in place by a retaining ring or is an integral part of the distributor itself.
NOTE!
If a hot gas bypass kit was provided by others,
refer to the manufacturer’s instructions
Nozzle Placement
Step 3 Install Suction Line
Install suction line(s) from the compressor to the suction connection(s) which are stubbed through the side of the cabinet.
Distributor Access Panel
Retainer Ring
Nozzle Distributor
Loading...
+ 33 hidden pages