Greenheck DFD-M350 User Manual

APPLICATION
Model DFD-M350 is approved for use in walls, floors and partitions with fire resistance ratings of 3 hours or more. This model carries a 3 hour UL fire damper label. UL 555 classifies dynamic rated fire dampers for use in HVAC systems that are operational in the event of fire .
CONSTRUCTION
Galvanized steel (in gauges required by UL listing R-13317)
Model DFD-M350
Dynamic Rated Fire Dampers
Model DFD-M350 meets the requirements for fire dampers established by:
National Fire Protection Association
(NFPA Standards 80, 90A & 101)
Underwriters Laboratories Standard 555 (Listing #R-13317) IBC International Building Codes
INSTALLATION
All fire damper installations require the use of sleeves, angles and methods described in Greenheck Fire Damper Installation Instructions #464089, included with every damper shipment. Sleeves can be field fabricated or factory furnished
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555 (Listing #R13317)
as a complete damper/sleeve assembly. See Factory Sleeve Option below for details.
W*
H*
94mm
94mm
FACTORY SLEEVE OPTION
DFD-350 Fire Dampers are available in factory furnished sleeves. Sleeves are galvanized steel and are available in 1.0mm - 1.5mm thicknesses and lengths up to 914mm.
“K” dimension specifies location of damper within the sleeve. Minimum is 102mm, maximum is “L” less 102mm, which allows for mounting angle installation and duct connection at each end of sleeve. If “K” dimension is not specified, it will be provided as one half of “L” dimension (damper centered in sleeve).
TYPE A TYPE B
W*
H*
Features:
• Stainless steel closure springs
• Fusible links (74°C standard, 100°C
available)
• Vertical or horizontal mount
• Grille tabs
*O
These dimensions are furnished approximately 6mm
*
undersize.
Sleeve
Damper
H*
Type B with sleeve
Type B corner profile
Installation instructions available at www.greenheck.com
K
Damper
Location
CL Damper Frame
Overall Sleeve Length
L
W*
When sealed option is selected, B transitions will need to be field sealed in the area where duct to sleeve connection is made.
DFD-M350 Types A&B
Three hour rated dampers are normally furnished in single section sizes only. Multi-section assembly is allowable with some limitations. Consult Greenheck for specific information.
SIZE LIMITATIONS TYPE A
Vertical or Horizontal
Single Section
Minimum 102mm x 102mm
Maximum 914mm x 914mm
SIZE LIMITATIONS TYPE B
Vertical or Horizontal
Single Section
Minimum 102mm x 76mm
Maximum 914mm x 813mm
Maximum Single Section Dimensions
Type A
914mm max.
914mm max.
Type B
914mm max.
813mm max.
Overall Damper Dimensions
H* O*
76 127
H*
102 152
127 178
152 203
178 229
W*
Type A
H*
W*
Type B
O*
203 254
229 279
254 305
279 330
305 356
330 381
356 406
381 457
406 483
432 508
457 533
483 559
508 584
533 610
559 660
584 686
610 711
635 737
660 762
686 787
711 813
737 838
762 864
787 889
813 915
DFD-M350 Type R
Sizing and Assembly Data
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size.
Transition is centered on damper frame (or frame assembly for multiple section dampers).
SIZE LIMITATIONS
Vertical or Horizontal
Minimum 76mm diameter
Maximum 864mm diameter
GREENHECK
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410
PH. 715-359-6171
www.greenheck.com
These dimensions are furnished
*
approximately 6mm undersize. (Dimensions in mm)
76mm min.
864mm max.
Copyright © 2009 Greenheck Fan Corporation
DFD-M350 Rev. 5 Sept 2009