Greenheck DFD User Manual

Part # 462100
®
24 in. O.C. Maximum
I-Studs
J-Track Headers (Slot ends to fit into I-Studs as shown in Detail ‘A’)
J-Track folded as shown in Detail ‘B’. Attach to J­Track header
Detail ‘B’
Detail ‘A’
24 in. O.C.
Maximum
J-Runner
1 1⁄2 in. x 1 1⁄2 in. x 2 in. Min. angle attached with 5⁄8 in. type #12 screws (min.)
Installation Instruction Supplement for
Refer to: ‘Installation Instructions for FD, DFD, SSFD, SSDFD, & KFD Series Curtain Fire Dampers’ (Part #452763) or ‘Installation Instructions for FD and DFD 150X Series Curtain Fire Dampers’ (Part #453946) or ‘Installation Instructions for FSD and SSFSD Series Combination Fire Smoke Dampers’ (Part #461336) for additional details.
Notes
1. Gypsum panels must be screwed 12 in. (305mm) on center
maximum to all stud and runner flanges surrounding opening. (See Figure 1 and Figure 2 for Opening Preparation Details).
2. Fire damper and sleeve assemblies 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), or 40 in. W x 100 in. H (1016mm x 2540mm) and smaller only require retaining angles on one side of the partition (See Figure 3 and Figure 4). Retaining angles must be attached to the sleeve and the partition. Larger damper assemblies require retaining angles on both sides of the partition. Retaining angles must be attached to the sleeve.
• Retaining angles must be a minimum of 16 gauge
(1.5mm) steel and have a minimum of 11/2 in. x 11/2 in. (38mm x 38mm) legs. For metal stud partitions only, the single-side mounting angle may be directly attached to the metal stud prior to the installation of the drywall.
• Retaining angles must be attached to the partition and
sleeve using one of the methods shown below.
• tack or spot welds
• #10 sheet metal screws and bolts
• Drywall screws of a length such that the screw
engages the stud/track by a minimum of 1/2 in. (13mm)
• A minimum of two connections per side, top, and
bottom, 12 in. on center maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in. (152mm) on center for openings 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), and 40 in. W x 100 in. H (1016mm x 2540mm) or less.
• Retaining angles must overlap the partition a minimum of 1 in. (25mm)
Grille Installations (Dampers up to 36 in. x 36 in.
[914mm x 914mm] maximum)
• Angle legs may be reversed and one leg inserted into the wall opening. Retaining angles used in conjunction with grille installations must be a minimum of 16 gauge steel and have a minimum of 5/8 x 1 in. (16mm x 25mm) legs (See Figure 5 and Figure 6).
OR
Using #10 sheet metal screws, screw from inside of
sleeve into the studs. Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side) (See
Figure 7 and Figure 8).
3. These installation instructions apply to the following wall
design numbers as detailed in the UL Fire Resistance Directory: U438, U469, U497,U499
FD & DFD Series
11⁄2 Hour Curtain Fire Dampers and
FSD Series
11⁄2 Hour Combination Fire Smoke Dampers Vertical Mount
Metal Stud Framing for Fire Dampers In Cavity Shaftwall Partitions
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555 (Listing #R13317) Standard 555S (Listing #R13447)
Figure #1: Opening Preparation Detail
Figure #2: Optional Opening Preparation
Detail for I-Stud Assembly
Detail ‘A’: J-Track to I-Stud Connection
Fasten J-Trac
k
in this manner
I-Stud
Cut here and bend down
5
/8 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
J-Runner C-H Stud I-Stud
Damper Sleeve
A
ngle Fastener
(see Note 2)
1 1⁄2 in. x 1 1⁄2 in. 16 ga. angle minimum
J-Runner C-H Stud I-Stud
Damper Sleeve
Two layers of 5/8 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design fo
r
Additional Details)
ngle Fastener
1 1⁄2 in. x 1 1⁄2 in. 16 ga. angle minimum
5
8 in. x 1 in. 16 ga.
angle minimum
5
/8 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
J-Runner C-H Stud I-Stud
Damper Sleeve
Angle Fastener (see Note 2)
Grille (supplied by others)
1 1⁄2 in. x 1 1⁄2 in. 16 ga. angle minimum
J-Runner C-H Stud I-Stud
Damper Sleeve
1 1⁄2 in. x 1 1⁄2 in. 16 ga. angle minimum
5
8 in. x 1 in. 16 ga.
angle minimum
Two layers of 5⁄8 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design fo
r
Additional Details)
Angle Fastener (see Note 2)
Grille (supplied by others)
5
8 in. x 1 in. 16 ga.
angle minimum
5
/8 in. UL Classified Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
J-Runner C-H Stud I-Stud
Damper Sleeve
Angle Fastener (see Note 2)
Grille (supplied by others)
#10 sheet metal screws spaced 6 in. on center and a maximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille assembly.
J-Runner C-H Stud I-Stud
Damper Sleeve
5
8 in. x 1 in. 16 ga.
angle minimum
Two layers of 5⁄8 in. UL
Classified Gypsum Wallboard
(see UL Rated Wall Design
for Additional Details)
Angle Fastener (see Note 2)
Grille (supplied by others)
#10 sheet metal screws spaced 6 in. on center and a maximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conflicts with the grille assembly.
Detail ‘B’: Forming J-Track
Figure #3: 1 Hour Shaftwall Rating
Figure #5: 1 Hour Shaftwall Rating
Figure #4: 2 Hour Shaftwall Rating
Figure #6: 2 Hour Shaftwall Rating
Figure #7: 1 Hour Shaftwall Rating
Figure #8: 2 Hour Shaftwall Rating
Copyright © 2008 Greenheck Fan Corporation.
462100 Metal Stud in Cavity Shaftwall
Rev. 7 March 2008