Standard: Two-single pole, double
throw type (SPDT) with an option
for 2 or 4 additional.
Ratings: UL and CSA listed.
15 amp & 1/2 H.P. at 125 or
250 VAC; 1/2 amp at 125 VDC;
1/4 amp at 250 VDC; 5 amp at 120 VAC
Optional: All double pole,
double throw type (DPDT).
Ratings: UL and CSA listed.
10 amp at 125/250 VAC (form ZZ);
1/2 H.P. at 125 VDC; 3/4 H.P. at 250 VAC
Limit Switches (MAR Models)
Ratings: UL and CSA listed.
MIL-PRF-8805 Qualified Listing
25 amp at 277 VAC; 1 H.P. at 125 VAC;
2 H.P. at 250 VAC
Limit Switches (DCR Models)
* (N.L.A.) — No Load Ampere (L.R.A.) — Locked Rotor Ampere (1) — Open/Close Service (2) — Open/Close or Modulating Service
Model
Output Torque Type Speed of Operation Duty Cycle Rating
Inch Pounds (N.m) 60 Hz. (50 Hz.) 24 VAC
MAR10-2 120 (13.5) Part Turn 2 seconds/90° 25% (1)
MAR10-2MT 120 (13.5) Multi-Turn 7.5 RPM 25% (1)
MAR10-10 350 (40) Part Turn 10 seconds/90° 25% (1)
MAR10-30 425 (48) Part Turn 30 seconds/90° 25% (1)
MAR10-60 400 (45) Part Turn 60 seconds/90° 25% (1)
MAR50-10 600 (67) Part Turn 10 seconds/90° 25% (1)
MAR50-30 700 (79) Part Turn 30 seconds/90° 25% (1)
MAR90-15 1,000 (112) Part Turn 15 seconds/90° 25% (1)
24 VAC
MAR
Current Ratings
24 VAC
N.L.A.* L.R.A.*
2.8 3.50
2.8 3.50
1.90 2.70
1.70 2.40
1.80 2.50
3.80 4.70
1.90 2.70
2.40 4.00
Model
Output Torque Type No Load Duty Cycle Rating Duty Cycle Rating
Inch Pounds (N.m)
Speed of Operation
12 VDC 24 VDC
DCR10-2 250 (28) Part Turn .6 seconds/90° 50% (1) 50% (1)
DCR10-2MT 250 (28) Multi-Turn 25 RPM 50% (2) 50% (2)
DCR10-10 400 (45) Part Turn 6.4 seconds/90° 50% (1) 50% (1)
DCR50-2 600 (67) Part Turn .7 seconds/90° 50% (1) 50% (1)
DCR50-2MT 600 (67) Multi-Turn 21 RPM 50% (2) 50% (2)
DCR50-10 600 (67) Part Turn 5.6 seconds/90° 50% (1) 50% (1)
DCR50-30 700 (79) Part Turn 21 seconds/90° 50% (2) 50% (2)
DCR50-60 750 (84) Part Turn 42 seconds/90° 50% (2) 50% (2)
DCR90-5 900 (101) Part Turn 2.2 seconds/90° 50% (1) 50% (1)
DCR90-5MT 900 (101) Multi-Turn 7 RPM 50% (2) 50% (2)
DCR90-15 900 (101) Part Turn 5.6 seconds/90° 50% (2) 50% (2)
12 & 24 VDC
DCR
Current Ratings Current Ratings
12 VDC 24 VDC
N.L.A.* L.R.A.* N.L.A.* L.R.A.*
1.00 12.50 0.75 6.80
1.00 12.50 0.75 6.80
0.19 3.90 0.08 2.10
1.00 22.00 0.75 12.00
1.00 22.00 0.75 12.00
0.90 5.80 0.50 2.40
0.15 2.65 0.06 1.15
0.15 2.65 0.06 1.15
1.00 12.50 0.75 6.80
1.00 12.50 0.75 6.80
0.90 5.80 0.50 2.40
Note — Multi-turn models are available with the following
number of turns: 1.4, 5, 8, 13, 18, 26 or 50.
Must be specified when the order is placed.
To operate multiple actuators in parallel from
a single signal requires isolating relays in the
field wiring. Consult factory.
Isolation Relays