Model CUE Direct Drive
Upblast Centrifugal
Roof Exhaust Fan
Pre-Starting Checks
Check all fasteners for
tightness. The wheel
should rotate freely
and be aligned as
shown at right. Wheel
position is preset and
the unit tested at the
factory. However,
movement may occur
during shipment, and
realignment may be
necessary. Centering (height
alignment) may be
accomplished by loosening
the set screws in the wheel
and moving the wheel to
desired position.
Installation
Upon receiving unit, check for any damage and report it immediately to the shipper. Also check to see that all accessory items
are accounted for.
Move fan to desired location and fasten securely through mounting holes in base. Shims may be necessary depending upon
roofing material thickness. The diagram below shows dimensions for Model CUE.
Access to the motor compartment is accomplished by removing the screws designated “R” in the drawing below. The cover
can then be removed and placed on a flat surface in an area protected from strong winds that could blow it off the roof.
The voltage rating of the motor must be checked for compatibility to supply voltage prior to final electrical connection. For
NFPA - restaurant applications, the electrical supply must enter the motor compartment through the breather tube. For other
non-flammable applications, the electrical supply can be routed through the conduit chase between the curb cap and the
bottom of the motor compartment. Consult local code authorities for your specific requirements.
IMPORTANT: UL/cUL 762 Installations are for Restaurant Applications.
A, B, and C motor RPMs are only approved for this installation. All must include the suffix “G”.
A drain trough is provided on all CUE fans for one point drainage of residue. Some means of collection of this residue must be
provided by either placing a container directly under the trough or by utilizing an adapter to direct the residue to another
location.
R
Dimension “A” is the inside dimension of the curb cap.
The roof curb should be 1-1/2" less than the curb cap to allow for
roofing and flashing.
*May vary depending on motor size.
Dimensional Data
Wheel Rotation
Direction of rotation is very critical. Improper
rotation will result in loss of performance,
excessive horsepower and possible motor
burnout. Check
rotation by
energizing the unit
only momentarily.
The rotation should
be as shown in the
diagram at right and
should be in the
same direction as
the rotation decals
affixed to the unit.
CUE Models 060-161
Roof Approx.
Model A B C D Damper
Opening Unit Wt.
CUE-060,065,070,075 17 18
3
/8 131/2 113/8 8x8 101/2x101/2 26
CUE-080,085,090 19 21 133/8 111/2 10x10 121/2x121/2 33
CUE-095 19 21 151/4 137/16 10x10 121/2x121/2 36
CUE-098,101,121,131 19 247/8 233/4 173/8 12x12 141/2x141/2 67
CUE-141,161 22 287/8 243/4 193/8 16x16 181/2x181/2 85
MODEL G H
060-095 - 3/32 in.
098-161 1/4 in. -
READ AND SAVE THESE INSTRUCTIONS
PN 457692
Installation, Operation and Maintenance Manual
G
H
Cl
o
c
e
s
i
k
w
IOM CUE FS
Rev. 3 February 2001
NOTE: Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information
will assist the local Greenheck representative and the factory in providing service and replacement parts.
CAUSE CORRECTIVE ACTION
System resistance too high. Check system: Proper operation of
backdraft or control dampers,
obstruction in ductwork, etc.
Unit running backwards. Correct as shown in Fig. 2.
Excessive dirt buildup on wheel. Clean wheel.
Improper wheel alignment. See Fig. 1 and Pre-Starting Checks.
Wheel improperly aligned and rubbing. See Fig. 1 and Pre-Starting Checks.
Foreign objects in wheel or housing. Remove objects, check for damage.
Unbalance of wheel caused by excessive Remove buildup.
dirt and grease buildup.
REDUCED
AIRFLOW
PROBLEM
EXCESSIVE
NOISE OR
VIBRATION
Maintenance
Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited to exterior
surfaces only. Removing dust buildup on motor housing ensures proper motor cooling. Greasing of motors is only intended
when fittings are provided. Many fractional motors are permanently lubricated and should not be lubricated after installation.
Motors supplied with grease fittings should be greased in accordance with manufacturers’ recommendations. With motor
temperatures under 104°F (40°C), the grease should be replaced after 2000 hours of running time as a general rule.
Wheels require very little attention when moving clean air. Occasionally, oil and dust may accumulate causing imbalance.
When this occurs, the wheel and housing should be cleaned to ensure smooth and safe operation.
All fasteners should be checked for tightness each time maintenance checks are performed prior to restarting unit.
A proper maintenance program will help these units deliver years of dependable service.
Troubleshooting
NOTE: Before taking any corrective action, make certain unit is not capable of operation during repairs.
Replacement
Parts
MOTOR
SHOCK
MOUNTS
WHEEL
BREATHER
TUBE
BIRDGUARD
*CURB CAP /
VENTURI
CONDUIT
CHASE
HOOD
*WINDBAND
*VERTICAL
SUPPORTS
*DRAIN
TROUGH
*For replacement, the windband, vertical supports, drain trough and curb
cap/venturi come as one complete assembly.
GREENHECK
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410
PH. 715-359-6171
www.greenheck.com
®
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase
date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our
factory, transportation prepaid.
Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective
during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for
any removal or installation costs.
Copyright © 2001 Greenheck Fan Corp.