CRD-60X
Ceiling Radiation Damper
Curtain Type With Insulation Skirt
Application and Design
The CRD-60X, which is manufactured with an attached insulation skirt, has been UL tested and labeled for protection of ceiling
openings in fire rated floor/ceiling assemblies with fire resistance ratings of 3 hours or less.
Standard Construction
Frame/Blades: Galvanized steel
(in gauges required
by UL listing R13446).
Fusible Link: Replaceable 165°F (74ºC)
UL listed link is standard,
212°F (100ºC) is optional.
Finish: Mill galvanized.
Blade Insulation: Non-asbestos UL classified.
Size Limitations
Minimum Size: 6 in. x 4 in.
(152mm x 101mm)
Maximum Size: 24 in. x 24 in.
(610mm x 610mm)
Thermal Blanket Option
Ceramic fiber or mineral wool thermal blanket
available.
CSFM California State Fire Marshal
Fire Damper Listing (#3226-0981:111)
“UL CLASSIFIED
(see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555C (Listing #R13446)
National Fire Protection Association:
NFPA Standards 90A and 101
BOCA, ICBO, SBCCI, & IBC Building Codes
New York City MEA Listing #260-91-M
Installation instructions available at www.greenheck.com.
*W & H dimensions furnished approximately 1/4 in. (6mm) under size.
Copyright ©2008 Greenheck Fan Corporation
CRD-60X Rev. 4 June 2008