CRD-60
W*
H*
2 in.
H*
311/16 in.
11/8
in.
Ceiling Radiation Damper
Application and Design
The CRD-60 has been UL tested and labeled for protection of ceiling openings in fire rated floor/ceiling assemblies with fire resistance ratings of 3 hours or less.
Curtain Type
Standard Construction
Frame/Blades: Galvanized steel
(in gauges required by UL listing R13446).
Fusible Link: Replaceable 165°F (74ºC) UL listed link is standard, 212°F (100ºC) is optional.
Finish: Mill galvanized.
Size Limitations
Minimum Size: 6 in. x 4 in.
(152mm x 101mm)
Maximum Panel Size:
CRD-60 24 in. x 24 in. (610mm x 610mm) CRD-60B 24 in. x 22 in. (610mm x 559mm)
Thermal Blanket Option
Ceramic fiber or mineral wool thermal blanket available.
CSFM California State Fire Marshal Fire Damper Listing (#3226-0981:111)
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555C (Listing #R13446)
National Fire Protection Association: NFPA Standards 90A and 101
BOCA, ICBO, SBCCI, & IBC Building Codes
New York City MEA Listing #260-91-M
CRD-60
CRD-60B
High Free Area
*W & H dimensions furnished approximately 1/4 in. (6mm) under size.
Installation instructions available at www.greenheck.com.