CRD-2
Application and Design
The CRD-2 has been UL tested and labeled for protection of
ceiling openings in fire-rated floor/ceiling assemblies with fire
resistance ratings of 3 hours or less. This product can also be
applied to steel lay-in style diffusers up to 24 in. (610mm) diameter
maximum size when installed with an approved thermal blanket.
Construction Standard Optional
Frame
Frame Type
Blades
Fusible Link
Temperature
Under 115.46 sq. in.
Blade
Insulation
(10 3/4 in. diameter)
Over 115.46 sq. in.
(10 3/4 in. diameter)
* in gauges required by UL listing R13446
W & H
Minimum
Size
Inches 5 24
mm 127 610
Galvanized
Steel*
Standard Top, Bottom,
Galvanized
Steel*
165°F (74°C) 212°F (100°C)
Not required -
Non-asbestos
UL classified
Maximum
Size
-
or Top/Bottom
Extension
-
-
Ceiling Radiation Damper
Round
“UL CLASSIFIED
(see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555C (Listing #R13446)
National Fire Protection Association:
NFPA Standards 90A and 101
New York City MEA Listing #260-91-M
CSFM California State Fire Marshal
Fire Damper Listing (#3226-0987:101)
Damper Model
CRD-2 Standard
Frame
CRD-2B Bottom
Extension
CRD-2T
Top Extension
CRD-2BT Bottom
and Top Extension
Frame Option Dimensions
Diameter
(in.)
5 - 24 3
A B C D
7
⁄16 - - -
5 - 24 - 4 ¾ - -
5 - 11¼ - - 7 ½ -
11½ - 17¼ - - 10 ½ -
17½ - 24 - - 13 ½
5 - 11¼ - - - 9
11½ - 17¼ - - - 12 15⁄16
15
⁄16
17½ - 24 - - - 15 7⁄8
*D dimension is actual O.D. of damper. Specify “ 1/4 in.
(6mm) under size” for dampers to be installed inside steel
ducts.
Volume Controller Option
A volume controller is used to manually set the
blades at a given angle to regulate the airflow (24
in. [610mm] maximum). Adjusting the cap screw will
open and close the blades.
Thermal Blanket Option
Ceramic fiber or mineral wool thermal blanket
available.
Installation instructions available at www.greenheck.com
Copyright © 2009 Greenheck Fan Corporation
CRD-2 Rev. 7 April 2009