Application and Design
The CRD-1 has been UL tested and labeled for protection of ceiling
openings in fire rated floor/ceiling assemblies with fire resistance
ratings of 3 hours or less. This product can also be applied to steel
lay-in style ceiling diffusers up to 24 in. x 24 in. (610mm x 610mm)
maximum size when installed with an approved thermal blanket.
Construction Standard Optional
Frame Galvanized
Steel*
Frame Type Standard Top, Bottom,
Blades Galvanized
Steel*
Fusible Link
165°F (74°C) 212°F (100°C)
Temperature
Blade
Insulation
Under 115.46
sq. in.
Not required -
(74,490 sq. mm)
Over 115.46
sq. in.
Non-asbestos
UL classified
(74,490 sq. mm)
* in gauges required by UL listing R13446
-
or Top/Bottom
Extension
-
-
CRD-1
Ceiling Radiation Damper
Rectangular
“UL CLASSIFIED
(see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555C (Listing #R13446)
National Fire Protection Association:
NFPA Standards 90A and 101
CSFM California State Fire Marshal
Fire Damper Listing (#3226-0987:101)
New York City MEA Listing #260-91-M
W & H
Minimum
Size
Inches 4 x 6 24 x 24
Maximum Size
*W & H dimensions furnished approximately 1/4 in. (6mm) under size.
mm 101 x 152 610 x 610
Frame Option Dimensions
Damper Model Height (in.) A B C D
CRD-1 Standard Frame 6 - 24 2
11
⁄16 - - -
CRD-1B Bottom Extension 6 - 24 - 4 ¾ - -
6 - 10¼ - - 6 ¾ -
CRD-1T Top Extension
10½ - 16¼ - - 9 ¾ -
16½ - 24 - - 12 ¾ -
CRD-1BT Bottom and Top
Extension
6 - 10¼ - - - 8
10½ - 16¼ - - - 11 7⁄8
16½ - 24 - - - 14 7⁄8
Volume Controller Option
A volume controller is used to manually set the
blades at a given angle to regulate the airflow (24
in. x 16 in.[610mm x 406mm] maximum). Adjusting
the cap screw will open and close the blades.
Thermal Blanket Option
Ceramic fiber or mineral wool thermal blanket
available.
7
⁄8
Installation instructions available at www.greenheck.com.
Copyright © 2009 Greenheck Fan Corporation
CRD-1 Rev 7 April 2009