GreenBrook M22SW, M22SM Installation Instructions

Page 1
Installation Instructions for
SafetySure Twin RCD Socket
22W, M22M & Switched versions
M
M22SW, M22SM
IMPORTANT
This product should be installed by a competent person and in accordance with the current IET Wiring Regulations. If in doubt, consult a qualified electrician.
Electricity is dangerous and an RCD must not be used as a substitute for
ormal precautionary measures.
n Always disconnect from mains supply before any inspection or repair to equipment is carried out. Do not
llow children to tamper with
a electrical devices. This device will protect against live and neutral leakage faults to earth, it will not protect against electric shock due to contact with both
conductors, short circuits between live and neutral, or a fault in the wiring supplying this device.
TO FIT THIS SAFETYSURE RCD SOCKET –
Switch off the power supply at the mains in order to isolate the existing socket. Remove the old socket, then for the Unswitched models M22W
and M22M simply connect using the wiring diagram below.
Green/Yellow(E)
Brown(L)
Blue(N)
Or for switched sockets M22SW and M22SM follow the diagram below.
E
E
L N
Green/Yellow(E)
Brown(L)
Blue(N)
If earth conductors are bare, they must be sleeved with appropriate green/yellow sleeving. If you are in any doubt about
connecting this product consult a qualified electrician.
N.B. Green/yellow earth wire may be connected to either earth terminal. Wiring insulation tests should be completed before setting the SafetySure RCD Socket to avoid misleading instrument readings and possible internal damage to the unit.
Page 2
PLEASE CARRY OUT THIS SIMPLE TEST PROCEDURE PRIOR TO EACH USE.
1. Press green (R) ON button.
2. Indicator window will turn red*.
3. Press white Test button (T).
4. Red window indicator will disappear*. This means the RCD has tripped successfully.
5. To reset – press green (R) ON button and use as a normal socket.
* If indicator fails to work, do not use
and return to place of purchase.
NOTE 1:
f the red window indicator
I disappears once the socket has been
reset and appliance is firmly plugged in the socket, this may mean that the
appliance or the cable lead is faulty,
nd should be checked by a
a qualified electrician. NOTE 2:
Remove this RCD from circuit before performing any high voltage
insulation tests.
TECHNICAL DATA
Rated voltage: 230V AC 50Hz Maximum operating current: 13A
Rated trip current: 30mA Trip speed: 30mS RCD contact break: Double pole Test/Reset buttons: Responsive to
both positive and
Dimensions: 145mm x 85mm
Conforms to BS7288:1990 & BS1363
(3A inductive)
negative cycles
x 35mm
GUARANTEE
Your GreenBrook Twin RCD Socket
is guaranteed for 12 months
from the date of purchase.
This does not affect your
statutory rights.
Please keep these instructions
for future reference.
- Please pass instruction manual onto the
INSTALLER
owner of the unit
WEST ROAD . HARLOW ESSEX . CM20 2BG . UK
WW W.G R EE NB RO OK .CO .UK
Issue no: 704467