GREE COMMERCIAL AIR CONDITIONER DC INVERTER MULTI VRF
PRODUCT
1
DC INVERTER MULTI VRF PRODUCT
PRODUCT
1 MODELS LIST
1.1 Outdoor Unit
Capacity
Units
Series
Model
Cooling
(Btu/h)
Heating
(Btu/h)
Ref.
Power
Supply
Appearance
220-240V
~50Hz
220-240V
~50Hz
220-240V
~50Hz
220-240V
~50Hz
DC
Inverter
Multi VRF
GMV(L)-Pd100W/NaB-K 34120 37532
GMV(L)-Pd120W/NaB-K 40944 47768
GMV(L)-Pd140W/NaB-K 47768 52545
GMV(L)-Pd160W/NaB-K 54592 60051
R410A
R410A
R410A
R410A
Note:1Ton =12000Btu/h = 3.517kW
Notes: a. Cooling only unit (GMVL type) has no items on heating;
b. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient;
c. The charge amount of R410A in the list is only the sealed amount when outdoor unit outgoing. When installing,
calculate the additional charge amount according to actual length of pipe and the matched indoor units;
d. Nominal capacities are based on the following conditions:
Notes: a. Cooling only unit (GMVL type) has no items on heating;
b. Noise was tested in semi-silenced room, so the actual noise value will be a little higher for change of ambient;
c. Nominal capacities are based on the following conditions:
Capacity
Cooling
(Btu/h)
9554
12284
17061
24226
30709
38216
42652
Cooling Heating
Heating
(Btu/h)
/
/
/
/
/
/
/
Ref
R410A
Power
Supply
220-240V
~50Hz
Appearance
Conversion Formula: Btu/h=kW×3412
Indoor :27℃(80.6℉)/19℃(66.2℉)
Outdoor: 35℃(95℉)/-
Indoor: 20℃(68℉)/-
Outdoor : 7℃(44.6℉)/6℃(42.8℉)
7
DC INVERTER MULTI VRF PRODUCT
2 NOMENCLATURE
2.1 Nomenclature of outdoor unit
GMV □L - Pd 120 W / Na B - K
1 2 3
NO. Description Options
1 Code for type GMV=Gree Multi Variable
2 Code for weather Default:T1 T2:T2 weather T3:T3 weather
3 Code for model
4 Units Series Pd: DC inverter VRF
5 Nominal cooling capacity
6 W: outdoor unit
7 Refrigerant Na: R410A
8 Series number B: The second generation
9 Power supply K: 220-240V 50Hz
4 5 6 7 8 9
L: Cooling Only
Default: Heat pump
120 represents 12kW
Btu/h=kW×3412
2.2 Nomenclature of indoor unit
GMV □L -R 36 P / Na B □
1 2 3 4 5 6 7 8 9
NO. Description Options
1 Code for type GMV=Gree Multi Variable
2 Code for weather Default:T1 T2:T2 weather T3:T3 weather
3 Code for model
4 Code for function R: R-R series
5 Nominal cooling capacity
6 Code for unit type
7 Refrigerant Na: R410A
8 Series number B: The second generation
9 Power supply K: 220-240V 50Hz
Example: GMV-R22G/NaB-K. A wall mounted indoor unit of GREE, and the nominal cooling capacity is 2.2kw. It's the
second generation product, and it could connect the outdoor unit with digital scroll, the power supply is 220V-240V, 50Hz.
L: Cooling Only
Default: Heat pump
36 represents 3.6kW
Btu/h=kW×3412
P=Duct type
T=Cassette type
G=Wall mounted
Zd=Floor ceiling
8
DC INVERTER MULTI VRF PRODUCT
3 FUNCTION
Auto Restart
Fan Operation Mode
LCD Remote Controller (Option)
Auto Swing Function
For
Comfortable
Air Conditioning
For Easy
Construction and
Maintenance
Ceiling Soiling Prevention
Program Dry
High Fan Speed Mode
High Ceiling Application
Two Select Thermo Sensor
Hot Start
Timer Selector
Fresh Return air inlet Directly from The Unit
Drain Pump
Long Life Filter
Ultra-Long life Filter (Option)
Mold Resistant Treatment for Filter
Filter Sign
Mold Resistant Drain Pan
Emergency Operation
Self Diagnoses Function
Set Back Time Clock
For Flexible
Control
Double Remote Control
Group Control By 1 Remote Controller
Control By External Command
Remote/Centralized Control
9
DC INVERTER MUL TI VRF PRODUCT
4 PRODUCT DATA
4.1 Product data of outdoor
Model GM V(L) -Pd10 0 W/N a B-K GM V (L) - P d120 W/Na B-K
Cooling①
Capacity
Heating②
Sound Pressure Level dB(A) 48 48
R410A Filling Amount kg 5.0 5.0
Power Supply V , Ph, Hz 220V-240V~,1Ph,50Hz 220V-240V~,1Ph,50Hz
Power input
Rated current
Moisture protection IP×4 IP×4
Connection Pipes
Cooling kW 3.1 3.8
Heating kW 2.9 3.6
Cooling A 14.2 17.3
Heating A 13.2 16.4
Compressor DC inverter dual-rotor type compressor×1
W e i g h t ( N e t / G r o s s ) kg 135/140 135/140
Notes:
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
Air Fl o w R ate
Step 3 3
W i d t h mm 950 950
Depth mm 340 340
Height mm 1250 1250
W i d t h mm 1 1 1 0 1 1 1 0
Depth mm 450 450
Height mm 1280 1280
m3/h 6000 6800
CFM 3538 4010
10.0×3 10.0×3
1650×590× 1700 1650×590× 1700
1 1
DC INVERTER MULTI VRF PRODUCT
4.2 Product data of indoor
4.2.1 Duct Type
Model GMV(L)-R22P/Na-K GMV(L)-R25P/Na-K GMV(L)-R28P/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
12
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R32P/Na-K GMV(L)-R36P/Na-K GMV(L)-R40P/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
13
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R45P/Na-K GMV(L)-R50P/Na-K GMV(L)-R56P/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
14
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R63P/Na-K GMV(L)-R71P/Na-K GMV(L)-R80P/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
15
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R90P/Na-K GMV(L)-R100P/Na-K GMV(L)-R112P/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling
only units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
mm 875×680×260 875×680×260
mm 1012×780×315 1012×780×315
kg 27/31 27/31
18
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R28P/NaB-K GMV(L)-R36P/NaB-K GMV(L)-R45P/NaB-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
mm 875×680×260 875×680×260 980×736×266
mm 1012×780×315 1012×780×315 1068×766×320
kg 27/31 27/31 34/37
19
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R56P/NaB-K GMV(L)-R71P/NaB-K GMV(L)-R90P/NaB-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
22
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R28T/Na-K GMV(L)-R36T/Na-K GMV(L)-R45T/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
23
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R50T/Na-K GMV(L)-R56T/Na-K GMV(L)-R63T/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
24
DC INVERTER MULTI VRF PRODUCT
Model GMV(L)-R71T/Na-K GMV(L)-R80T/Na-K GMV(L)-R90T/Na-K
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
① Refer to the product nameplate for parameters and specification of the unit;
② The model with GMVL code is cooling only unit; while the model with GMV code is heat pump unit; the cooling only
units dose not have any parameters of performing heating;
③ The sound level was tested under circumstance of semi-anechoic chamber; the value of noise could be a little higher in
actual operation.
27