Graymills Osep-2 User Manual

OSEP-2
Fluid Conditioning System
Operation and Maintenance Instructions
Do not install or operate until you have read all warnings and instructions and understand the operation of this equipment.
• The OSEP-2 is not intended for and will not function with solvent-based fluids. Using flammable or com­bustible fluids will create a safety hazard.
• Read and follow all safety instructions supplied with the coolant used in your machine tool or machining center.
• Ensure that all fittings and connections are properly tightened.
• Be sure that there are no bends or kinks in the fluid return hose back to the tank. A blockage in the fluid return line will cause the coalescing chamber to over­flow.
Never work with equipment you feel may be unsafe. Contact your Supervisor immediately.
INTRODUCTION
Upon receipt of the OSEP-2 immediately inspect the fil­tration system for any damage that may have occurred during shipping. The OSEP-2 is shipped completely assembled and will only require minor adjustments and
connections to be completed for operation. The unit is designed to continuously remove tramp oil and suspend­ed solids.
SITE REQUIREMENTS
• The OSEP-2 requires a level area within ten feet of the tank or sump it is servicing.
• The unit requires a space of approximately two feet (2') by three feet (3'). This will allow access to the equip­ment for service and inspection.
• Plant air with a maximum of 50 psi is also required to operate unit. Position unit within reach of plant air.
• This equipment requires an air connection (maximum pressure 50 psi) but does not require an independent electrical power source.
• The system weighs approximately 170 pounds dry. Once it is charged with aqueous coolant, it will weigh approximately 300 pounds.
SET-UP AND INSTALLATION
• Remove OSEP-2 from skid by removing two of the front wooden hold-downs.
For stationary installation, place next to machine tool
sump/tank and adjust threaded levelers accordingly.
795-90654
GM 04-01
For portable installation, remove threaded levelers and
replace with heavy-duty dual wheel swivel casters (provided).
• Connect the 3/8" clear suction skimmer hose to the inlet strainer basket and clamp.
• Connect 1" oil discharge hose to clean coolant outlet on side of OSEP-2 tank. Hoses have been provided in 10 foot lengths. Do not exceed 10 feet. However, if all your sumps can be serviced with shorter suction and discharge hoses, cut hoses as short as possible for opti­mum performance.
• Close all system drain valves.
• Make sure clear inlet strainer gasket is in place and bowl is secure.
• Open fluid conditioning filter vessel. Make sure filter cartridge is securely in place.
• Lift the oil intake nozzle (orange and blue) straight up even with top.
• Fill the coalescing chamber and fluid conditioning filter vessel (approximately 17 US gallons) with fresh charge of coolant used for normal machining operation.
• Close fluid conditioning filter vessel and tighten wing nuts.
• Open black cap on auto air bleeder on fluid condition­ing filter vessel lid.
• Be sure that machine tool sump/tank is full (especially on low profile coolant tanks).
• Locate floating skimmer in coolant sump/tank as close to machine tool discharge as possible. Use the handy hose spring clamp to stabilize and/or secure the floating skimmer in place. Be sure the skimmer is floating with the proper side up and is level to assure optimum flow through the OSEP-2 system.
• Clamp the return hose to the sump/tank, as far away from the skimmer as possible. Be sure to leave an air gap for positive flow and to provide the best possible circulation and accelerate turnover.
• Place an oil recovery pail, supplied by customer, under oil outlet (1/2" hose).
• Close 1/4" ball valve on air regulator.
• Install 1/4" male air fitting on 1/4" ball valve and con­nect air line. (Air fitting is supplied by customer.)
START UP
• Open 1/4" ball valve on air regulator.
• Be sure regulator is set at 50 psi. Higher or lower pres-
sure will adversely effect system performance. Do not
use an air lubricator.
• Check system for leaks.
• Once system has run for approximately 10 minutes, adjust oil intake nozzle in coolant sump/tank to approx­imately 3/16" above coolant level.
BE PATIENT! The OSEP-2 may take several hours or even days to begin discharging tramp oil. This is due to the fact that the system must reach its saturation point based on the amount of tramp oil in each machine.
OPERATION & MAINTENANCE
Turn unit off prior to servicing.
The OSEP-2 is designed to run continuously and unat­tended. A periodic check of the oil recovery pail is need­ed to prevent an overflow situation. Use proper judge­ment when leaving the unit unattended for long periods. Be sure to follow all federal and local EPA requirements when disposing of waste oil.
Cycle Times
Cycle times will vary due to tramp oil levels in coolant tank. Run OSEP-2 until sump is noticeably free of float­ing tramp oil.
Servicing inlet strainer basket
Periodically remove clear canister on front of unit and check stainless mesh screen. Wash out and replace, return to normal operation.
Servicing fluid conditioning filter
Periodically monitor the pressure gauge on the inlet of the fluid conditioning filter. When the gauge reads 15 psi change the filter cartridge.
Service instructions:
• Close 1/4" ball valve on air supply.
• Remove wing nuts on the vessel. Remove lid.
• Lift out cartridge and replace.
• Inspect and clean vessel rim gasket.
• Return system to normal operation.
Diaphragm Pump
Refer to manual 795-08691 enclosed with this unit for pump operation/maintenance. For replacement pump
use DPHG-50 Diaphragm Pump 1/2", 1/1 Hytrel.
Loading...
+ 2 hidden pages