Grass Valley Trinix User Manual

Trinix
DIGITAL VIDEO ROUTER

Planning and Installation Manual

SOFTWARE VERSION 2.4.1
071827607 August 4, 2007
Affiliate with the N.V. KEMA in The Netherlands
A
Certificate Number: 510040.001
The Quality System of:
Grass Valley, Inc.
400 Providence Mine Road Nevada City, CA 95945 United States
15655 SW Greystone Ct. Beaverton, OR 97006 United States
10 Presidential Way
rd
Floor, Suite 300
3 Woburn, MA 01801 United States
Nederland B.V. 4800 RP BREDA The Netherlands
Technopole Brest Iroise CS 73808 29238 Brest Cedex 3 France
7140 Baymeadows Way Suite 101 Jacksonville, FL 32256 United States
Weiterstadt, Germany Brunnenweg 9 D-64331 Weiterstadt Germany
17 rue du Petit Albi-BP 8244 95801 Cergy Pontoise Cergy, France
Rennes, France Rue du Clos Courtel Cesson-Sevigne, Cedex France
2300 South Decker Lake Blvd. Salt Lake City, UT 84119 United States
Including its implementation, meets the requirements of the standard:
ISO 9001:2000
Scope: The design, manufacture and support of video hardware and software products and related systems.
This Certificate is valid until: June 14, 2009 This Certificate is valid as of: August 30, 2006 Certified for the first time: June 14, 2000
H. Pierre Sallé President KEMA-Registered Quality
The method of operation for quality certification is defined in the KEMA General Terms And Conditions For Quality And Environmental Management Systems Certifications. Integral publication of this certificate is allowed.
KEMA-Registered Quality, Inc.
4377 County Line Road Chalfont, PA 18914 Ph: (215)997-4519 Fax: (215)997-3809
CRT 001 073004
ccredited By:
ANAB
Trinix
DIGITAL VIDEO ROUTER
Planning and Installation Manual
SOFTWARE VERSION 2.4.1
071827607 August 4, 2007
Contacting Grass Valley
International
Support Centers
Local Support
Centers
(available
during normal
business hours)
France
24 x 7
Australia and New Zealand: +61 1300 721 495 Central/South America: +55 11 5509 3443
Middle East: +971 4 299 64 40 Near East and Africa: +800 8080 2020 or +33 1 48 25 20 20
Europe
+800 8080 2020 or +33 1 48 25 20 20 +800 8080 2020 or +33 1 48 25 20 20
Hong Kong, Taiwan, Korea, Macau: +852 2531 3058 Indian Subcontinent: +91 22 24933476
Asia
Southeast Asia/Malaysia: +603 7805 3884 Southeast Asia/Singapore: +65 6379 1313 China: +861 0660 159 450 Japan: +81 3 5484 6868
Belarus, Russia, Tadzikistan, Ukraine, Uzbekistan: +7 095 2580924 225 Switzerland: +41 1 487 80 02 S. Europe/Italy-Roma: +39 06 87 20 35 28 -Milan: +390248414658 S. Europe/Spain: +34 91 512 03 50 Benelux/Belgium: +32 (0) 2 334 90 30 Benelux/Netherlands: +31 (0) 35 62 38 42 1 N. Europe: +4545968870 Germany, Austria, Eastern Europe: +49 6150 104 444 UK, Ireland, Israel: +44 118 923 0499
Copyright © Grass Valley, Inc. All rights reserved. All specifications subject to change without notice. This product may be covered by one or more U.S. and foreign patents.
United States/Canada
24 x 7
+1 800 547 8949 or +1 530 478 4148
Grass Valley Web Site
The www.thomsongrassvalley.com web site offers the following:
Online User Documentation — Current versions of product catalogs, brochures,
data sheets, ordering guides, planning guides, manuals, and release notes in .pdf format can be downloaded.
FAQ Database — Solutions to problems and troubleshooting efforts can be
found by searching our Frequently Asked Questions (FAQ) database.
4 Trinix Planning and Installation Manual

Contents

Preface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Safety Summary
Regulatory Notices
About This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Safety Terms and Symbols. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terms in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Terms on the Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Symbols on the Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Certifications and Compliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
FCC Emission Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Canadian EMC Notice of Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
EN 55103 Class A Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Canadian Certified Power Cords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Canadian Certified AC Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Laser Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Laser Safety Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Laser Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
FCC Emission Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Section 1 — Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SD and HD in the Same Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Easy to Create Very Large Routers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Control Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
The Trinix Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Trinix Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Serviceability and Reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Broadlinx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Broadlinx Web Page Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
SNMP/NetCentral Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Section 2 — Planning Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Trinix Frame. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Power Supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Cooling System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Sync Reference Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Output Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Signal Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Analog Processing Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Pre-wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Trinix Planning and Installation Manual 5
Contents
Connector Numbering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Alarm System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Duplication and Expansion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Output Duplication - Dual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Output Duplication - Quad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Expanded Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Termination for Pre-wired Expansion Frames . . . . . . . . . . . . . . . . . . . . . . . . . 56
Monitoring with Expanded Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Protected Paths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Worksheet for Protected Path Implementation . . . . . . . . . . . . . . . . . . . . . . . . 69
Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Jupiter Facility Control System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
SMS 7000 / Encore Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
LAN and Com Bus Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Com Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
System Monitoring Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Physical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Quick Look . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Chassis, Board, Weight and Power Summary for Select Matrix Sizes . . . . . 81
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Frames . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Input, Output, and Matrix Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Additional video signal cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Power Supplies and Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
NIC/Sync/OPM Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Port Expanders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
SNMP/NetCentral Software Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Miscellaneous. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Section 3 — Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Summary of Installation Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Rear Panel Dip Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Miscellaneous rear panel connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Power Supply Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
DV-33128 and DV-33256 Chassis Installations . . . . . . . . . . . . . . . . . . . . . . . . 104
DV-33512 Chassis Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Sync Reference Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
NR/SR-33000 / SR-33500 V-Phasing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Output Board Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Duplication and Expansion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Output Duplication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Input Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Output Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Output Reclocker Bypass Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Sync Selection Switch S5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Input Equalization Settings (DV-33512 Models Only) . . . . . . . . . . . . . . . . . . . . . 136
6 Trinix Planning and Installation Manual
Output Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Setting the Output Monitor Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Output Monitor Reclock / Force Bypass Settings. . . . . . . . . . . . . . . . . . . . . . 142
Monitoring with Expanded Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Frame Number Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Setting the Chassis for Input/output Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Jupiter Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
SMS 7000 / Encore Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
LAN and Com Bus Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Com Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
NR-33000 (Broadlinx) Board Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Section 4 — Broadlinx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Network Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Simple Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Complex Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Software Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
SNMP/NetCentral Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Broadlinx / Internet Explorer Monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Firmware Update. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
On-line Help. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Contents
Section 5 — Protected Path Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
System Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Encore Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Jupiter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Operation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Section 6 — Analog Input Processing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
TRX-VI-33100 Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Analog Processing Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Customizing Analog Video Processing Settings. . . . . . . . . . . . . . . . . . . . . . . . . 194
Terminal Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Main Menu Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Section 7 — Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Signal flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Section A — SNMP Managers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Adding SNMP Managers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Deleting SNMP Managers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Trinix Planning and Installation Manual 7
Contents
8 Trinix Planning and Installation Manual

Preface

About This Manual

This manual provides system planning, installation and troubleshooting information specific to the Trinix Digital Video Router.
The Trinix Digital Video Router can be controlled by the Grass Valley Jupiter or Encore Control System. Configuration information for the control system itself is contained in the control system’s documentation set:
Jupiter Control System Release Notes series, 0718275xx. Jupiter VM-3000 Installation and Operating Manual, 0718305xx. Jupiter CM-4000 Installation and Operating Manual, 0718261xx. Jupiter Getting Started Guide, 04-045707-003.
Encore Control System Release Notes series, 0718153xx. Encore Installation and Service Manual, 0718103xx. Encore Control System User Manual, 0718104xx. Encore Control Panels Manual, 0718053xx
An electronic copy of the documentation set is normally provided with the system on CD-ROM 0718130xx. The CD Includes SMS7000 Series Control System, Acappella, Concerto, Encore, Jupiter, JEP 100, Prelude, and Trinix documentation.
Individual printed manuals may be ordered by contacting Technical Sup­port. They are also available on our web site. See page 4.

Additional Documentation

NetCentral IV TV Facility Monitoring System User Guide, 0718338xx.
CD-ROM 071827407 includes legacy Jupiter, Saturn, Triton, and Venus manuals.
.
Planning and Installation Manual 9
Preface
10 Planning and Installation Manual
Safety Summary
Read and follow the important safety information below, noting especially those instructions related to risk of fire, electric shock or injury to persons. Additional specific warnings not listed here may be found throughout the manual.
WARNING Any instructions in this manual that require opening the equipment cover
or enclosure are for use by qualified service personnel only. To reduce the risk of electric shock, do not perform any servicing other than that con­tained in the operating instructions unless you are qualified to do so.

Safety Terms and Symbols

Terms in This Manual

Safety-related statements may appear in this manual in the following form:
WARNING Warning statements identify conditions or practices that may result in per-
sonal injury or loss of life.
CAUTION Caution statements identify conditions or practices that may result in damage
to equipment or other property, or which may cause equipment crucial to your business environment to become temporarily non-operational.

Terms on the Product

The following terms may appear on the product:
DANGER — A personal injury hazard is immediately accessible as you read
the marking.
WARNING — A personal injury hazard exists but is not immediately acces-
sible as you read the marking.
CAUTION — A hazard to property, product, and other equipment is present.
Planning and Installation Manual 11
Safety Summary

Symbols on the Product

The following symbols may appear on the product:
Indicates that dangerous high voltage is present within the equipment enclosure that may be of sufficient magnitude to constitute a risk of electric shock.
Indicates that user, operator or service technician should refer to product manual(s) for important operating, maintenance, or service instructions.
This is a prompt to note fuse rating when replacing fuse(s). The fuse referenced in the text must be replaced with one having the ratings indicated.
Identifies a protective grounding terminal which must be con­nected to earth ground prior to making any other equipment connections.

Warnings

Identifies an external protective grounding terminal which may be connected to earth ground as a supplement to an internal grounding terminal.
Indicates that static sensitive components are present which may be damaged by electrostatic discharge. Use anti-static procedures, equipment and surfaces during servicing.
The following warning statements identify conditions or practices that can
result in personal injury or loss of life.
Dangerous voltage or current may be present — Disconnect power and remove
battery (if applicable) before removing protective panels, soldering, or
replacing components.
Do not service alone — Do not internally service this product unless another
person capable of rendering first aid and resuscitation is present.
Remove jewelry — Prior to servicing, remove jewelry such as rings, watches,
and other metallic objects.
Avoid exposed circuitry — Do not touch exposed connections, components or
circuitry when power is present.
12 Planning and Installation Manual
Safety Summary
Use proper power cord — Use only the power cord supplied or specified for
this product.
Ground product — Connect the grounding conductor of the power cord to
earth ground.
Operate only with covers and enclosure panels in place — Do not operate this
product when covers or enclosure panels are removed.
Use correct fuse — Use only the fuse type and rating specified for this
product.
Use only in dry environment — Do not operate in wet or damp conditions.
Use only in non-explosive environment — Do not operate this product in an
explosive atmosphere.
High leakage current may be present — Earth connection of product is essential
before connecting power.
Dual power supplies may be present — Be certain to plug each power supply
cord into a separate branch circuit employing a separate service ground. Disconnect both power supply cords prior to servicing.

Cautions

Double pole neutral fusing — Disconnect mains power prior to servicing.
Use proper lift points — Do not use door latches to lift or move equipment.
Avoid mechanical hazards — Allow all rotating devices to come to a stop before
servicing.
The following caution statements identify conditions or practices that can result in damage to equipment or other property
Use correct power source — Do not operate this product from a power source
that applies more than the voltage specified for the product.
Use correct voltage setting — If this product lacks auto-ranging power sup-
plies, before applying power ensure that the each power supply is set to match the power source.
Provide proper ventilation — To prevent product overheating, provide equip-
ment ventilation in accordance with installation instructions.
Use anti-static procedures — Static sensitive components are present which
may be damaged by electrostatic discharge. Use anti-static procedures, equipment and surfaces during servicing.
Planning and Installation Manual 13
Safety Summary
Do not operate with suspected equipment failure — If you suspect product
damage or equipment failure, have the equipment inspected by qualified
service personnel.
Ensure mains disconnect — If mains switch is not provided, the power cord(s)
of this equipment provide the means of disconnection. The socket outlet
must be installed near the equipment and must be easily accessible. Verify
that all mains power is disconnected before installing or removing power
supplies and/or options.
Route cable properly — Route power cords and other cables so that they ar not
likely to be damaged. Properly support heavy cable bundles to avoid con-
nector damage.
Use correct power supply cords — Power cords for this equipment, if provided,
meet all North American electrical codes. Operation of this equipment at
voltages exceeding 130 VAC requires power supply cords which comply
with NEMA configurations. International power cords, if provided, have
the approval of the country of use.
Use correct replacement battery — This product may contain batteries. To
reduce the risk of explosion, check polarity and replace only with the same
or equivalent type recommended by manufacturer. Dispose of used bat-
teries according to the manufacturer’s instructions.
Troubleshoot only to board level — Circuit boards in this product are densely
populated with surface mount technology (SMT) components and applica-
tion specific integrated circuits (ASICS). As a result, circuit board repair at
the component level is very difficult in the field, if not impossible. For war-
ranty compliance, do not troubleshoot systems beyond the board level.
14 Planning and Installation Manual

Regulatory Notices

Certifications and Compliances

FCC Emission Control

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equip­ment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equip­ment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Changes or modifications not expressly approved by Grass Valley Group can affect emission compliance and could void the user’s authority to operate this equipment.

Canadian EMC Notice of Compliance

This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regula­tions of the Canadian Department of Communications.
Le présent appareil numérique n’emet pas de bruits radioélectriques dépassant les limites applicables aux appareils numeriques de la classe A préscrites dans le Règlement sur le brouillage radioélectrique édicte par le ministère des Communications du Canada.

EN 55103 Class A Warning

For products that comply with Class A. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Planning and Installation Manual 15
Regulatory Notices

Canadian Certified Power Cords

Canadian Certified AC Adapter

Laser Compliance

Laser Safety Requirements
Canadian approval includes the products and power cords appropriate for
use in the North America power network. All other power cords supplied
are approved for the country of use.
Canadian approval includes the AC adapters appropriate for use in the
North America power network. All other AC adapters supplied are
approved for the country of use.
The device used in this product is a Class 1 certified laser product. Oper-
ating this product outside specifications or altering from its original design
may result in hazardous radiation exposure, and may be considered an act
of modifying or new manufacturing of a laser product under U.S. regula-
tions contained in 21CFR Chapter1, subchapter J or CENELEC regulations
in HD 482 S1. People performing such an act are required by law to recertify
and reidentify this product in accordance with provisions of 21CFR sub-
chapter J for distribution within the U.S.A., and in accordance with
CENELEC HD 482 S1 for distribution within countries using the IEC 825
standard.
Laser Safety
Laser safety in the United States is regulated by the Center for Devices and
Radiological Health (CDRH). The laser safety regulations are published in
the “Laser Product Performance Standard,” Code of Federal Regulation
(CFR), Title 21, Subchapter J.
The international Electrotechnical Commission (IEC) Standard 825, “Radi-
ation of Laser Products, Equipment Classification, Requirements and
User’s Guide,” governs laser products outside the United States. Europe
and member nations of the European Free trade Association fall under the
jurisdiction of the Comite European de Normalization Electrotechnique
(CENELEC).
For the CDRH: The radiant power is detected trough a 7 mm aperture at a
distance of 200 mm from the source focused through a lens with a focal
length of 100 mm.
For IEC compliance: The radiant power is detected trough a 7 mm aperture
at a distance of 100 mm from the source focused through a lens with a focal
length of 100 mm.
16 Planning and Installation Manual
FCC Emission Limits

Certification

Regulatory Notices
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may no cause harmful inter­ference, and (2) this device must accept any interference received, including interference that may cause undesirable operation. This device has been tested and found to comply with FCC Part 15 Class B limits for a digital device when tested with a representative laser-based fiber optical system that complies with ANSI X3T11 Fiber Channel Standard.
Category Standard Designed/tested for compliance with:
Safety ANSI/UL 1950-1997 3rd Ed.
CAN/CSA-C22.2 No. 950-95 EN 60950
Professional Video and Audio Equipment
Planning and Installation Manual 17
Regulatory Notices
18 Planning and Installation Manual

Introduction

General

Section 1
The Trinix family of routing switchers represents a revolutionary new approach to digital Venus—the best selling routing switcher ever. Trinix is a high-quality and fully featured digital video routing switcher offering a large number of crosspoints in one of the smallest physical frames available. Four fixed frame sizes are available: a 128 x 128 router in eight rack units, a 128 x 256 router in 12 RUs, a 256 x 256 router in 15 RUs, and a 512 x 512 router in 32 RUs. Fixed frame designs offer optimal solutions for customers who have minimum space requirements yet still need a large number of crosspoints. Features of the Trinix routing switcher architecture include:
Fourth generation based on Venus
Standard Definition (SD) and High Definition (HD) in the same frame
Easy to upgrade
High density in minimal space
Each I/O card supports 32 signals
Same “crosspoint bus” control as Venus, providing easy integration with Jupiter Facility Control Systems.
1
signal distribution that builds on the success of
Mission critical components are front loading and hot swappable
Extensive alarm notification/status
Load sharing power supplies
Redundant fans
Protected path operation
Broadlinx option combines network interface, sync input, and output monitor circuitry; allows LAN-based control by Encore/ SMS and system monitoring via Microsoft Internet Explorer. SNMP/NetCentral system monitoring also available
Passive expanders for input/output expansion, dual/quad outputs
Chassis design maximizes air flow
1.
The new VI-33100 module provides analog as well as digital inputs.
Planning and Installation Manual 19
Introduction

SD and HD in the Same Frame

Easy to Create Very Large Routers

Trinix supports both SD and HD video in all configurations. The matrix cards and high-speed backplane are designed for both SD and HD sig­nals. The only difference between SD and HD implementations is the I/ O cards. This makes upgrading easy on both budgets and implementa­tion, thus solving the problem of deciding when to prepare for HD in a facility.
Creating very large routers in the Trinix design is accomplished by using special circuitry for simple and cost effective expansion. Using passive port expansion modules, a 1024 x 1024 router can be built in four equipment racks using four 512 x 512 frames coupled together with expanders. These expanders can also be used to provide dual or quad non-inverting outputs.

Control Systems

The Jupiter Facility Control System can be used to control the Trinix router using a crosspoint bus connection (see Glossary) to a VM-3000 System Controller or CM-4000 System Controller. The VM/CM can receive switching commands from a variety of serial sources, including Jupiter control panels or an automation computer.
The Trinix can also be controlled using direct Ethernet (“CPL”) integra­tion with a Grass Valley Encore or SMS 7000 control system.

The Trinix Frame

High-density crosspoints in compact frames
Fixed matrix sizes can be combined to form larger routers
Modular design allows for both HD and SD within the same frame
Trinix is optimized for crosspoint density, with reliability and service­ability in mind. Each frame has redundant power supplies, redundant fans, and a physical topology designed to maximize cooling. Mission critical modules are front loading and hot swappable.
All Trinix frames accommodate two load-sharing power supplies and have two AC inputs. This allows for full redundant operations. They are front loading and hot swappable and each power supply has its own fan for cooling. The 128 x 128 frame runs on a 600 W power supply, the 256 x 256 frame runs on a 1250 W power supply, and the 512 x 512 runs on two 1250 W power supplies—all with plenty of power to spare.
20 Planning and Installation Manual
The 128 x 128 chassis includes two fan modules; the 256 x 256 chassis includes three, and the 512 x 512 includes six. Both power supplies and fan modules are front loading and hot swappable.

Trinix Architecture

The architecture of the Trinix signal flow is organized into three cards: input card, matrix card, and output card. These are connected to a passive backplane circuit card. Each input and output card accommo­dates 32 signals, which allows the routers to be built in increments of 32 as well a mixed population of SD and HD cards in increments of 32.
On switchers with HO-33110 HD and HO-33120 SD/HD output cards, signal reclocking can be set to “Auto On/Off” or “Off” for each of the 32 outputs. In “Auto On/Off” mode, properly-formed standard data rate signals will be reclocked but other signals will be bypassed (not reclocked). “Standard” data rates are listed on page 79.
The new VI-33100 “universal” input board auto-senses and accepts 16 composite analog SD, digital SD, or digital HD signals in any combina­tion and passes them in digital SD or digital HD form (as appropriate) to the Trinix matrix board. When analog signals are received, an exten­sive set of gain, phase, filtering, and other adjustments are available for each signal. For a list of these adjustments, see page 40.
The BL-33000 Broadlinx option combines network interface, sync input, and output monitor circuitry. Each card has two sync inputs and two monitor outputs. Two cards can be installed for a total of four ports for each. The sync reference supports generation of Vertical Interval Switch Timing strobe from standard NTSC or PAL Black Burst or HDTV Tri­level sync defined in the SMPTE 274M-1998 standard (see Glossary). Sync reference granularity is 32 outputs. An internal DIP switch is used to select one of the available references for the respective 32-output blocks. Trinix can also operate without a sync reference.
The Trinix fixed-frame routers all come standard as pre-wired single­output units. The dual output option is implemented by adding phys­ical expanders in increments of 16 up to 256. Both outputs are non­inverting and fully meet DVB-ASI (see Glossary) specifications.

Serviceability and Reliability

Trinix routing switchers are engineered by the same team that devel­oped the Venus and Venus2001 family of routing switchers and use many of the same proven circuit designs that made the Venus line the best selling routers in the world. In addition, Trinix employs cutting­edge technology to reduce the number of components, increase the reli-
Planning and Installation Manual 21
Introduction
ability of individual parts, enhance air movement throughout the chassis, and identify potential system problems in time to take preven­tive measures.
Trinix also offers Broadlinx technology, which aids serviceability by providing status displays and monitoring functions through a network connection.
All circuit boards contain some common circuitry for hot swapping, cir­cuitry for DC to DC conversion, and a micro-controller as part of the Broadlinx technology.
Hot swap circuitry is used to simplify field servicing and upgrades.
The DC to DC conversion is necessary because the chassis design dis­tributes one voltage, 48 volts, to all cards leaving the responsibility to each card to convert down to the needed voltage level.
Each board has a micro-controller that is part of an overall communica­tions bus which is part of the hardware for the Broadlinx technology. This hardware is what gathers all of the particular board information (voltages, signal presence, reclocking settings, etc.) as well as enables the firmware updates via network connection.

Broadlinx

For “protected path” operation, the Broadlinx software can be config­ured to monitor router outputs that are feeding critical downstream equipment (such as a transmitter). If the “primary” output signal is interrupted, the system will automatically select the “secondary” output that is carrying the same signal and trigger a system alarm. Pro­tected path operation is available for single-chassis (non-expanded) systems only, with the exception of multi-chassis DV-33512 routers with expanded inputs. Protected path operation also requires HO­33120 HD/SD Output Boards in the paths to be protected. For more information, see page 60.
The Broadlinx option, which consists of Broadlinx software running on the NR-33000 Sync/NIC/OPM board, allows SMS 7000 or Encore control using Grass Valley CPL (Control Point Language) through an Ethernet connection.
Broadlinx also provides web pages for the following operations:
Network configuration of the NR-33000 board(s)
Downloading of software upgrades to the various boards in the system
System monitoring using Internet Explorer
22 Planning and Installation Manual
When licensed to do so, Broadlinx will also support SNMP/NetCentral monitoring.
The monitoring network consists of a Windows PC, network interface connection (NIC) circuitry on the NR-33000 board, and microproces­sors on each circuit board in the system. All of the processors are inter­connected via a communications bus (Com Bus).

Broadlinx Web Page Monitoring

Broadlinx uses HTTP (Hypertext Transfer Protocol) web pages to deliver detailed system information through the network to a PC with Microsoft Internet Explorer 5.0 or newer (Internet Explorer 6 or newer is recommended for best performance).
Typical aspects that can be monitored as “warnings” or alarms are all the voltages on each circuit board, input signal presence, and output reclocking status. Also, information on the current version of firmware that is being used is available.
For more information, see Broadlinx / Internet Explorer Monitoring on
page 166.

SNMP/NetCentral Monitoring

When enabled, the Trinix SNMP (Simple Network Management Pro­tocol) Agent allows the Grass Valley NetCentral application to monitor the following:
Ta b l e 1.
Item Description
System Broadlinx board IP Address and frame
type.
Fans Fan names and status
Board Master Status of input, output, and cros-
spoint boards
Signal Master Status of input and output signals
present on frame
Reference Status of reference signal(s) presented to
the Broadlinx board
Power AC and DC status of each power supply
Thermal Master Frame temperature status
Planning and Installation Manual 23
Introduction
The Trinix SNMP agent is supplied with Broadlinx 2.2 and later soft­ware. By default, the agent is disabled; a hardware address (MAC) based license key must be obtained for it to become active. This license can be purchased as part of the original system or later by contacting Grass Valley Technical Support. The MAC address is shown in the “SNMP” section of the “Configuration” Broadlinx web access display; an “Enter License Key” button allows entry of the Grass Valley-sup­plied key. For an illustration, see page 164.
Because the license is stored in the NR-33000 board flash memory, a new key will have to be obtained if the board is ever replaced. However, in the case of redundant NR-33000 installations, if the secondary board (i.e., the board not having the licensed MAC address) is replaced the existing license will automatically be copied to the new board when installed.
NetCentral
NetCentral is a suite of software modules residing on one or more com­puters. These modules work together to monitor and report the opera­tional status of SNMP-enabled devices such as Trinix, Encore, 7500NB/ WB frames, Concerto Fast Controllers, etc.
When the Trinix SNMP Agent is activated, it automatically sends mes­sages to the NetCentral Monitoring Station, reporting the device status. (Up to five Monitoring Stations are supported.) Messages are given a Status Level ranging from “Informational” to “Critical.” The NetCen­tral Monitoring Station can be configured to listen to and, depending on Status Level, respond to these messages in a variety of ways, including:
Sound computer “beep”
•Play sound file
Send E-mail message to one or more addresses
Send E-mail message to pager or cell phone
•Run program
Open web browser and go to specified URL
For example, when a Critical message is received, NetCentral can be configured to open an Internet Explorer window and go to the Home Page for the Broadlinx web pages described under Broadlinx / Internet
Explorer Monitoring on page 166.
The Trinix SNMP Agent provides support for NetCentral, but does not include the actual NetCentral product, which is available separately. Once the Trinix SNMP Agent is installed and configured, it can be mon­itored by NetCentral, or by any other SNMP management application.
For more information, please refer to the NetCentral User Guide, part no. 071 8338 xx.
24 Planning and Installation Manual
Non-NetCentral Managers
For information concerning registration of Monitoring Stations (SNMP Managers) for use with non-NetCentral SMNP management applica­tions, please refer to Appendix A-SNMP Managers.
Planning and Installation Manual 25
Introduction
26 Planning and Installation Manual

Planning Guide

Introduction

The following discussion is intended to provide both an overview and an in-depth understanding of the configuration possibilities of the Trinix Digital Video Routing Switcher.
Included in this document are the details necessary for the planning and designing of your facility with the Trinix router in mind.
The beginning of this section includes conceptual descriptions and drawings for those who need a basic understanding of the product and the configuration options. Later subsections provide additional detail such as connection diagrams and ordering information.
Section 2

Trinix Frame

Note If you are actually installing the router at this time, please refer to
Section 3-Installation on page 91.
Trinix routers are available in four fixed frame sizes:
DV-33128: 128 x 128 in 8 rack units (RU). See Figure 1 and
Figure 2.
DV-33256: 256 x 256 in 15 RUs. See page 30 and page 31.
DV-33512: 512 x 512 in 32 RUs. See page 32 and page 33.
Planning and Installation Manual 27
Planning Guide
SR-33000 Sync Reference / NR-33000 Broadlinx Board slots
Fan modules
FAN ALARM
FAN ALARM
Power supplies
Matrix board
Input/output boards (configuration varies)
Figure 1. DV-33128 front view (door removed).
28 Planning and Installation Manual
INPUT EXPAND OUTPUT EXPAND SYNC REDUNDANT INT XPT CNTL 60Hz ENABLE A B C
Figure 2. DV-33128 rear panel.
MONITOR
512
DV-33512 DV-33128
GPIO/TC
1024
1536
2048
96 80
64
48 32
MONITOR
112
16
128
0
16
48 80
112
0
256
MONITOR
DV-33256 128 x 256
8
LEVEL SUPER
32
64
12
96
384 512
12
14
10
FRAME
14
10
0
15
1
13 11
79
8
0
15
1
13 11
9
7
8
256
768
512
1024
2
3
4 5 6
2 3
4 5
6
OUTPUT MONITOR
SECONDARY
96
80
64
48
32
ULTRA
MONITOR
Trinix Frame
LEVEL
SUPER
0
32
112
16
48
64
80
16
112
96
0
128
384
256
512
REF IN
434
12
FRAME
12
0
2
14
15
1
13
3
4
5
11
79
10
6
8
0
2
14
15
1
13
3
4
5
11
7
9
10
6
3
OUTPUT MONITOR
PRIMARY
12
REF IN
12
IP EXPAND OP EXPAND VIT REDUNDANT INT XPT 60Hz ENABLE A B C
ALARM
WARNING: FOR CONTINUED PROTECTION
AGAINST RISK OF FIRE, REPLACE ONLY WITH SAME TYPE AND RATING OF FUSE
115: 6.0A 250V SLOW BLOW
230: T2.5A 240V
AUTO SELECT 100-130V/200-240V
6.0A/2.5A 47-63HZ
DC IN + DC IN -
PS B PS A
L
E
N
N
E
L
97-128
OUTPUTS
65-9633-64
OUTPUTS
1-32
OUTPUTS OUTPUTS
97-128
INPUTS
65-96
INPUTS
33-64
INPUTS
1-32
INPUTS
LAN BCOM BUS
CONSOLE B
17
17
17
17
17
17
17
17
19
18
1
2
19
18
1
2
19
18
1
2
19
18
1
2
19
18
1
2
19
18
1
2
19
18
1
2
19
18
1
2
21
20
3
4
21
20
3
4
21
20
3
4
21
20
3
4
21
20
3
4
21
20
3
4
21
20
3
4
21
20
3
4
CROSSPOINT BUS CONTROL
23
22
6
5
23
22
6
5
23
22
6
5
23
22
6
5
23
22
6
5
23
22
6
5
23
22
6
5
23
22
6
5
CONSOLE A
28
27
26
25
24
7
8
9
10
26
25
24
7
8
9
10
26
25
24
7
8
9
10
26
25
24
7
8
9
10
26
25
24
7
8
9
10
26
25
24
7
8
9
10
26
25
24
7
8
9
10
26
25
24
7
8
9
10
12
11
28
27
12
11
28
27
12
11
28
27
12
11
28
27
12
11
28
27
12
11
28
27
12
11
28
27
12
11
COM BUS
29
13
29
13
29
13
29
13
29
13
29
13
29
13
29
13
LAN A
CROSSPOINT BUS
31
30
30
30
30
30
30
30
30
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
Planning and Installation Manual 29
Planning Guide
OK
DC
VADJ
OK
AC DCOKAC
OK
VADJ
FAN ALARM
FAN ALARM
FAN ALARM
SR-33000 Sync Reference / NR-33000 Broadlinx Board slots
Fan modules Power supplies
Matrix boards
Input/output boards (configuration varies)
Figure 3. DV-33256 front view (door removed).
30 Planning and Installation Manual
Figure 4. DV-33256 rear panel
See page 29 for detail
Trinix Frame
SECONDARY
NIC B
31
OP MON
42
COM BUS
PRIMARY
NIC A
OP MON
COM BUS
PS B
PS B
L
E
N
INPUTS INPUTS
17
1
1
18
2
2
19
3
3
20
4
4
21
5
5
22
6
6
23
7
7
24
8
8
25
9
9
26
10
10
27
11
11
28
12
12
29
13
13
30
14
14
31
15
15
32
16
16
DC INPUT 42 - 54 VDC 30-24 AMPS
INPUTS
33-641-32
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
PS A
IN EXPAND OP EXPAND VIT REDUNDANT INT XPT CNTL 60Hz ENABLE A B C
96
80
64
48 32 ULTRA
MONITOR
3
CONSOLE
REF
IN
4
LEVEL
0
SUPER
0
14
2
32
15
112
16
1
13
48
3
12
64
4
11
5
80
79
112
16
6
10
96
8
0
FRAME
128
0
14
384
2
256
15
1
13
512
3
12
4
5
11
79
6
10
8
CONTROL
GPIO/TC
B
1
CONSOLE
REF
IN
2
CROSSPOINT BUS
A
DC IN -DC IN +
WARNING: FOR CONTINUED PROTECTION
PS A
N
E
L
INPUTSINPUTS
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
AGAINST RISK OF FIRE, REPLACE ONLY WITH SAME TYPE AND RATING OF FUSE 115: 12.5A 250V SLOW BLOW 230: T6.3A 240V
AUTO SELECT 100-130V/200-240V
10.0A/5.0A 47-63HZ
OUTPUTS OUTPUTS
OUTPUTS
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
OUTPUTS
OUTPUTS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
OUTPUTS OUTPUTSOUTPUTS
17
1
18
2
19
3
20
4
21
5
22
6
23
7
24
8
25
9
26
10
27
11
28
12
29
13
30
14
31
15
32
16
17
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
OUTPUTS
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
INPUTS 129-160
225-256193-224129-160 161-19265-9633-64 97-1281-3297-12865-96
17
1
1
18
2
2
19
3
3
20
4
4
21
5
5
22
6
6
23
7
7
24
8
8
25
9
9
26
10
10
27
11
11
28
12
12
29
13
13
30
14
14
31
15
15
32
16
16
INPUTS INPUTS
17
1
18
2
19
3
20
4
21
5
22
6
23
7
24
8
25
9
26
10
27
11
28
12
29
13
30
14
31
15
32
16
INPUTS
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
ALARM
INPUTS
193-224161-192 225-256
17
1
1
18
2
2
19
3
3
20
4
4
21
5
5
22
6
6
23
7
7
24
8
8
25
9
9
26
10
10
27
11
11
28
12
12
29
13
13
30
14
14
31
15
15
32
16
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Planning and Installation Manual 31
Planning Guide
Rear view. See page 29 and page 33 for detail
Figure 5. DV-33512 main chassis and associated power supply unit.
SR-33000 Sync Reference / NR-33000 Broadlinx Board slots
Fan modules
Input/output boards (configuration varies)
INPUTS 481 - 512
PRIMARY
SECONDARY
FAN ALARM
FAN A
INPUTS 449 - 480
INPUTS
FAN ALARM
FAN B
417 - 448
385 - 416 225 - 256 193 - 224 161 - 192
VADJ
OK OK
65 - 96 33 - 6497 - 128
INPUTS
DCAC
Power supply unit may be
VADJ
OK
AC
OK
DC
FAN ALARM
FAN F
POWER ALARM IFC
INPUTSINPUTSINPUTS 1 - 32
mounted above or below main chassis
A
1
B
A
2
B
OP MON
A
3
B
A
4
B
1
2
REF IN
3
4
ACDC
OKOK
VADJ
PS CPS A
DCAC
OKOK
VADJ
PS DPS B
FAN ALARM
FAN ALARM
FAN C
OUTPUTS
OUTPUTSOUTPUTSINPUTSINPUTS
OUTPUTSOUTPUTS 97 - 128
129 - 160
OUTPUTS
INPUTS 257 - 512 / OUTPUTS 1 - 256
OUTPUTS 65 - 96
OUTPUTS 33 - 64
OUTPUTS
FAN ALARM
FAN EFAN D
INPUTS
1 - 32
Matrix boards
Input/output boards (configuration varies)
INPUTS 353 - 384
INPUTS
INPUTS 1 - 256 / OUTPUTS 1 - 256
INPUTS 257 - 512 / OUTPUTS 257 - 512
INPUTS 1 - 256 / OUTPUTS 257 - 512
OUTPUTSINPUTS
INPUTSINPUTS
257 - 288289 - 320321 - 352
353 - 384
321 - 352
289 - 320
OUTPUTS 257 - 288
OUTPUTS 481 -512
OUTPUTS OUTPUTS
417 - 448449 - 480
OUTPUTS
OUTPUTS
OUTPUTS
OUTPUTS
385 - 416
INPUTS
INPUTSINPUTS
INPUTS
INPUTS
129 - 160
161 - 192
193 - 224225 - 256
32 Planning and Installation Manual
Figure 6. DV-33512 main chassis and power supply chassis.
RP-33500 board. See
page 29 for
detail
Trinix Frame
DC INPUT 2 NOT FUSED
42 - 54 VDC 30 - 24 AMPS
DC IN +
DC IN -
DC INPUT 1 NOT FUSED
42 - 54 VDC 30 - 24 AMPS
DC IN + DC IN -
A
B
A
B
OP MON
A
B
A
B
REF
IN
1
2
3
4
1
2
3
4
ULTRA
MONITOR
XPT BUS
LEVEL
SUPER
0
32
96
112
16
80
48
64
64
80
48
112
16
96
32
0
FRAME
1024
512
1536 2048
PS IFC FAN IFC
COM BUSCOM BUS
0
14
15
1
13
3
12
5
11
79
8
0
14
15
1
13
3
12
5
11
9
7
10
ALARM
2
4
610
2
4
6
8
INPUT EXPAND OUTPUT EXPAND SYNC REDUNDANT INT XPT CNTL 60Hz ENABLE A B C
INPUTS
129 - 160
AC INPUT: 100-240 V ~, 10.0-5.0A, 50-60Hz
100-120V: 12.5A, 250V, SLO BLO
200-240V: T6.3A, 250V
PS D
L
E
N
161 - 192
DC OUTPUT 2
42 - 54 VDC
30 - 24 AMPS
DC INPUT 2 42 - 54 VDC
30 - 24 AMPS
193 - 224
DC OUT -DC OUT +
DC IN -DC IN +
PS C PS A
N
L
INPUTS
INPUTS
INPUTS
OUTPUTS
225 - 256
385 - 416
E
WARNING: FOR CONTINUED PROTECTION AGAINST RISK OF FIRE, REPLACE ONLY WITH SAME TYPE AND RATING OF FUSE
OUTPUTS
417 - 448
OUTPUTSINPUTS
OUTPUTS
OUTPUTS
449 - 480
AC INPUT: 100-240 V ~, 10.0-5.0A, 50-60Hz
PS B
E
OUTPUTS
481 - 512
257 - 288
DC OUTPUT 1
42 - 54 VDC
30 - 24 AMPS
DC OUT + DC OUT -
DC INPUT 1 42 - 54 VDC
30 - 24 AMPS
100-120V: 12.5A, 250V, SLO BLO
200-240V: T6.3A, 250V
L
N
INPUTS
OUTPUTS 289 - 320
OUTPUTS
321 - 352
OUTPUTS
353 - 384
INPUTS 257 - 288
INPUTS
289 - 320
INPUTS
321- 352
INPUTS
353 - 384
PRIMARY
REF IN
1
COM BUS
NIC A
2
CONSOLE A
SECONDARY
REF IN
3
GPIO/TC
COM BUS
XPT BUS
NIC B
FRAME IFC
4
DC IN -DC IN +
CONSOLE B
CONTROL
N
E
L
Planning and Installation Manual 33
Planning Guide
Figure 7. Signal flow and power supply system for DV-33512 router.
Powered by
PS C and PS D
Inputs
385-512
Powered by
PS A and PS B
Outputs
129-256
1-128
Outputs
1-128
Inputs
Input/Output
boards
DM-33501/2
Matrix boards
Input/Output
Inputs
257-384
Outputs
257-384
Outputs
385-512
Inputs
129-256
boards
Primary Supplies
PS A
PS B
PS C
PS D
34 Planning and Installation Manual

Power Supplies

Two power supply types are used in the Trinix routing family, one type for the 128 chassis and another for the 256 and 512 chassis. Both types, which share the same feature set, are OEM products. The power sup­plies differ primarily in power delivered, size, and weight.
The 128 and 256 chassis are designed for two power supplies. The optional (and recommended) second supply provides redundancy and increased reliability due to “load sharing” - both supplies work less, creating less strain and decreasing the likelihood of failure of either unit.
In AC power applications, the 512 chassis is equipped with two power supplies mounted in a separate chassis. For redundancy, space is pro­vided for two additional supplies (recommended). The 512 power supply chassis may be mounted above or below the main chassis, depending on video cable routing requirements (or weight distribution requirements).
All power supplies are front loading and hot swappable and each has its own fan for cooling. Automatic line sensing technology is used to adapt the supply to all major power standards throughout the world. The back panel of the chassis provides a separate AC connector for each supply and a third connection for a 48 VDC input.
Trinix Frame
The power supplies each deliver 48 volts to all components and the individual components convert down the voltages for their particular need.
For additional redundancy, it is possible to operate the router with a combination of internal power supplies and a external DC power source.
Planning and Installation Manual 35
Planning Guide
Right side Rear Left side
IN
IN
IN
OUT OUT

Cooling System

The Trinix uses fan modules (FM-33000) for cooling the main chamber of the chassis. A fan module consists of two blower-type fans that are housed in a mechanical assembly. The 128 x 128 chassis uses two mod­ules, the 256 x 256 chassis uses three, and the 512 uses six. The fan modules are front-loading and hot-swappable.
Airflow openings for the 128 chassis are shown in Figure 8. Air is taken in from the sides of the chassis (primarily the left side), where the air is drawn across the I/O cards, past the matrix card, and up to the top rear of the chassis where it is expelled. A small amount of air is drawn from the right side of the chassis as well to help cool the matrix board.
Figure 8. Airflow openings for DV-33128 chassis.
36 Planning and Installation Manual
Trinix Frame
Right side
Rear
Left side
IN
IN
IN
OUT
ININ
IN
Right side Rear Left side
OUT
IN
IN
IN IN
IN IN
IN
IN
OUT
Airflow openings for the 256 and 512 chassis are shown in Figure 9 and
Figure 10. Air is taken in from the bottom of the chassis (cut-outs are
located on the very bottom of the sides), and from the central area of the left and right sides. This air is then drawn up through all of the I/O cards as well as the matrix boards to the top rear of the chassis and expelled out the back.
Figure 9. Airflow openings for DV-33256 chassis.
Figure 10. Airflow openings for DV-33512 power supply and main chassis.
Planning and Installation Manual 37
Planning Guide
Using a central set of fan modules to cool the main chamber eliminates the possibility of cooling loss in one area due to failure of a single fan. If a fan does fail, the system will continue to operate, providing a safe interval during which the failed fan can be replaced and the system returned to normal redundant operation.

Sync Reference Options

For synchronous vertical interval switching the same sync reference signal must be sent to the control system (e.g., Jupiter CM-4000) and to the Trinix. (The Trinix will operate without a sync connection but switching will be non-synchronous.) Each sync input uses looping 75 ohm BNC connectors.
The sync signal can be NTSC or PAL black burst, or tri-level (HD) sync, and up to four sync signals can be mixed within the same chassis on an output-board basis. For example, NTSC sync could be used for one set of 32 outputs and HD sync for another set of 32 outputs.
In DV-33128 and DV-33256 units, one or two independent sync signals can be connected to a NR-33000 Broadlinx board and either of these can then be selected for use on each output board. Adding a second Broad­linx board provides a total of four independent sync sources.
In DV-33512 units, which are normally supplied with an SR-33500 Sync/OPM board, up to four independent sync sources can be con­nected and any of the four can be selected for each output board. If desired, an NR-33000 board can be installed in the associated power supply chassis to provide Broadlinx capability. It is also possible to divide the sync sources between the SR-33500 and the Broadlinx board but the maximum number of sync sources is always four.
Sync Redundant mode
For all systems, two Broadlinx boards can be operated in Sync Redun­dant mode where the sync signal(s) are looped through each board; if the primary Broadlinx board fails the system will switch automatically to the secondary board. However, for redundant operation the number of sync signals is limited to two.
For sync reference details, see page 107.

Output Monitoring

With the DV-33128 and DV-33256 chassis, two pairs of output monitor ports are provided by the NR-33000 board (one side of each pair is inverted). Two additional dual ports are optionally available when a second NR-33000 is added; this would provide a total of four monitor ports.
38 Planning and Installation Manual
With the DV-33512 chassis, the SR-33500 Sync/OPM board provides
32 Output
Card
Matrix Card
(128 x 128)
32 Output
Card
32 Output
Card
32 Output
Card
32 Input
Card
32 Input
Card
32 Input
Card
32 Input
Card
four monitoring ports.
For configurations that require multiple chassis, the monitor signals are brought through a PE-33016 Port Expander used as a combiner (see
page 59).

Signal Flow

Trinix is a “three-board” routing system, where the input board, output board, and matrix board are the basic modules.
Shown below is the signal flow through a 128 x 128 routing system. Inputs are received and outputs are delivered to the rear of the chassis directly with a connection to the rear panels (no cabling).
Figure 11. Input and output routing through matrix board for 128 x 128 switcher.
Trinix Frame
For a description of the various input, output, and matrix cards avail­able for Trinix, see page 83.
Planning and Installation Manual 39
Planning Guide
Save/recall settings
Mono mode
•Setup on/off
•Chroma kill
•Comb/trap filter
•AGC on/off
Manual gain control
ACC on/off
•Manual chroma control
Blank video (per VBI line)
Add setup (per VBI line)
Reserve VBI line for data
Horizontal timing
Detail enhancement
Display channel status
Insert Error Detec­tion and Handling (EDH) data
Contrast / Y gain
Saturation / chroma gain
Brightness / Y offset
•Hue / chroma phase
Notch decode on/ off (VBI)
Chroma kill (VBI)

Analog Processing Control

The VI-33100 “universal” input module accepts analog as well as digital signals. Adjustments for analog signals include the following:.
For more information about the VI-33100 module, please refer to
Section 6-Analog Input Processing.

Pre-wiring

All Trinix switchers are pre-wired to the size of the chassis. That is, a 128-chassis is essentially pre-wired to 128 x 128 with all rear panels and BNCs in place. The 256-chassis is pre-wired to 256 x 256. By convention, switcher sizes are shown as:
M x N (P x Q)
This indicates that the functional router size is M x N and is pre-wired to (P x Q). For Trinix pre-wiring is only possible in multiples of 128 x 128, as that is the smallest chassis size increment.

Connector Numbering

Late-model Trinix routers have video input/output connectors that begin with “1” instead of “0.” An adhesive overlay set, which indicates connector groups using a 0-based numbering scheme (e.g., “Inputs 0­31,” “Inputs 32-63,” etc.) is provided for customers who are using a 0­based control system such as Jupiter.
40 Planning and Installation Manual

Alarm System

There are two Trinix alarm classes: primary and secondary. A sec­ondary alarm is asserted when a single fan has failed or when the sec­ondary NR/SR Broadlinx board has taken control of the system. All other alarms (multiple fan failure, power supply failure, etc.) are con­sidered primary alarms.
All major components include a local alarm LED. NR/SR-33000 boards have separate LEDs for primary and secondary alarms.
The master alarm indicator is a tri-color LED on the front panel (“Power/Alarm”) where green indicates normal operation, red indi­cates a primary alarm, and amber indicates a secondary alarm.
The rear panel “Alarm” BNC can be configured to report primary alarms only or both primary and secondary alarms. The factory default configuration is to report both. (DV-33128 and DV-33256 configuration is via a jumper on the NR/SR-33000 board, as shown on page 119 and
page 120. DV-33512 configuration is via a jumper on the RP-33500 512
x 512 Rear Panel board as shown on page 122.)
Trinix Frame
Electrically, the Alarm BNC operates according to SMPTE standard 269M-1999. When an alarm is asserted, the circuit associated with the Alarm connector will present a low impedance to an external current source circuit provided by the customer. See Figure 12.
Planning and Installation Manual 41
Planning Guide
EXTERNAL CIRCUIT
(EXAMPLE)
NOT TO EXCEED 24 VDC @ 20 mA
REAR PANEL BNC
Figure 12. Rear panel master alarm circuit (left) and example of customer-supplied indicator circuit (right)
.
All of the alarm and status information is also gathered by the Broad­linx technology to make it available to the user via web pages. For more information, see page 22.
42 Planning and Installation Manual

Duplication and Expansion

Trinix routers are designed to duplicate/expand inputs and outputs using passive splitter/combiner expansion panels.
Note For Jupiter-controlled (0-based) systems, the input/output numbers in
Note Frame numbers are determined by the input/output blocks served by the
Note Unused connectors should be terminated for optimum performance.

Output Duplication - Dual

The PE-33016 Port Expander is a passive, transformer-based module that can be used to provide two copies of the same signal. Functionality is bi-directional and depends on connections only; no configuration is needed. Figure 13 and Figure 14 show a splitting application. Note that the unused connectors should be terminated for optimum perfor­mance.
Duplication and Expansion
the following discussion should be decreased by one (1). For example, block 1-256 should be understood as block 0-255, etc.
particular frame. E.g., for a DV-33256 router, inputs 1-256 and outputs 1-256 must be connected to frame zero. For more information about frame numbering, see page 146.
Figure 13.
1 - 256
Frame 0
Trinix
256 x 256
1 - 256
16
PE 33016
used as splitters
1 - 256
Dual outputs
Planning and Installation Manual 43
Planning Guide
1B
1A
1B
1A
Exterior sideInterior side
(Terminated)
Figure 14. PE-33016 used to provide 16 dual outputs.
In the splitting application, the PE-33016 Port Expander can be used to provide dual outputs in groups of 16 outputs. All outputs are non­inverting. For example, a 256 x 256 router could be arranged as follows:
256 inputs x 240 single outputs and 16 dual outputs - uses 1 PE-33016 or 256 inputs x 224 single outputs and 32 dual outputs - uses 2 PE-33016s or 256 inputs x 208 single outputs and 48 dual outputs - uses 3 PE-33016s... etc.
Figure 15 shows a router with 240 single outputs and 16 dual outputs.
44 Planning and Installation Manual
Figure 15.
Duplication and Expansion
1 - 16
Frame 0
1 - 256
Trinix
256 x 256
1
PE 33016
used as
splitter
1 - 16
Dual outputs
17 - 256
Single outputs
In this application, 16 of the PE-33016 rear BNCs can be used for inputs (outputs from the router) and all 32 of the front BNCs can be used for
1
outputs.
Up to 16 PE-33016 modules can be mounted in the MK-33000 Mounting Kit, which is eight rack units high and approximately four inches deep.
Figure 16 shows a 128 input router with a single PE-33016 mounted in
an MK-33000; this provides 112 single outputs and 16 dual outputs.
Figure 17 shows a 256 input router with 256 dual outputs; this arrange-
ment requires 16 PE-33016 Port Expanders.
1.
All unused connectors must be terminated. 16 terminators are supplied with each PE-33016. See page 87.
Planning and Installation Manual 45
Planning Guide
Dual outputs
123 16
1A
These 16 cables connect to rear of PE
1B
2A
2B 3A
3B
16A
16B
Terminate
Unused BNCs
PE-33016-1
Exterior
390-1796-00
PE-33016-1
Interior
390-1797-00
Figure 16. Use of single PE-33016 to provide dual outputs for 16 switcher outputs
46 Planning and Installation Manual
Duplication and Expansion
A
B
C
16 PE-30016 Expander Modules in MK-33000 Mounting Kit
EXTERIOR
INTERIOR
3.25 in.
(82 mm)
Figure 17. PE-33016 Port Expanders used to provide 256 dual outputs for 256 input switcher.
Planning and Installation Manual 47
Planning Guide

Output Duplication - Quad

The PE-33008 Port Expander can be used to provide quad outputs in groups of 16 outputs. All outputs are non-inverting. A 128 x 128 switcher could be arranged as follows:
128 inputs x 112 single outputs and 16 quad outputs - uses 2 PE-33008s or 128 inputs x 96 single outputs and 32 quad outputs - uses 4 PE-33008s or 128 inputs x 80 single outputs and 48 dual outputs - uses 6 PE-33008s... etc.
In this application, the eight PE-33008 rear BNCs are used for inputs (outputs from the router) and all 32 of the front BNCs are used for out-
1
Up to 16 PE-33008 modules can be mounted in an MK-33000
puts. Mounting Kit, which is 8 RU high and approximately 4 inches (100 mm) deep.
1.
All unused connectors must be terminated with 75 ohm terminators; for PE-33008 applications terminators must be sup-
plied by end-user.
48 Planning and Installation Manual
Figure 18. Use of 2 PE 33008s to provide quad outputs for 16 switcher outputs
3A 3B
3C
3D
Quad outputs
2A 2B
2C
2D
Duplication and Expansion
Figure 18 shows a 128 input router with two PE-33008s mounted in an
MK-33000; this provides 112 single outputs and 16 quad outputs. A 256 input router with 128 single outputs and 128 quad outputs would appear similar to the system shown in Figure 17; this arrangement requires 16 PE-33008 Port Expanders.
Connections to 2nd PE-33008 are similar
123 8
1A
1B
1C 1D
These cables connect to rear of PE
8A 8B
8C
8D
Terminate
Unused BNCs
Terminate
Unused BNCs
PE-33008-1
Exterior
390-1795-00
PE-33008-1
Interior
390-1794-00
Planning and Installation Manual 49
Planning Guide
1A
1B
Exterior sideInterior side
1A
1B

Expanded Systems

The PE-33016 and PE-33008 Port Expanders can be used to “combine” outputs for an input expansion application. In Figure 19 and Figure 20, a PE-33016 is downstream of the router. The router will present only one of the two possible signals to each combiner, which will produce two copies of that signal. Note that any unused connectors should be terminated for optimum performance. The port expanders are mounted in an MK-33000 Mounting Kit as described previously (page 46).
Figure 19. PE-33016 used as a combiner. Only one of the input signals will be present at a time, and this signal is duplicated.
Expanded configurations include:
1024 inputs x 512 dual outputs 1024 inputs x 1024 dual outputs 512 inputs x 1024 outputs 2048 inputs x 2048 outputs 1024 inputs x 1024 outputs
Some of these configurations are shown on the following pages. Notice that the same port expander type is used for both downstream com­bining (for input expansion) and upstream splitting (for output expan­sion). All outputs are non-inverting.
50 Planning and Installation Manual
Figure 20. Examples of input and output expansion.
1 - 512
Inputs expanded to 1024
513 - 1024
Frame 0
Trinix
512 x 512
Frame 1
Trinix
512 x 512
1 - 512
32
PE 33016
used as
combiners
512 - 1024
1 - 512
Inputs expanded to 1024 (restricted)
1 - 512
Dual outputs
Frame 0
Trinix
512 x 512
Duplication and Expansion
1 - 16
17 - 512
32
PE 33016
used as
combiners
17 - 512
Dual outputs
1 - 512
32
PE 33016
used as splitters
1 - 512
1 - 512
Frame 0
Trinix
512 x 512
Frame 2
Trinix
512 x 512
1 - 512
Outputs expanded to 1024
513 - 1024
17 - 512
513 - 1024
32
PE 33016
used as splitters
Frame 1
Trinix
512 x 512
1 - 16
1 - 512
17 - 512
17 - 512
Frame 0
1 - 512
Trinix
512 x 512
Outputs expanded to 1024 (restricted)
Frame 2
513 - 1024
Trinix
512 x 512
The term “restricted” refers to a wiring scheme where some signal paths are not available. For example, the second system shown in
Figure 20 will not allow outputs 1-16 to receive inputs 513-1024.
Planning and Installation Manual 51
Planning Guide
1 - 512 Dual outputs
Figure 21. 1024 x 1024 system.
1 - 512
32
PE-33016
used as
splitters
1 - 512
Frame 0
Trinix
512 x 512
Frame 2
Trinix
512 x 512
1 - 512
513 - 1024
32
PE-33016
used as
combiners
1 - 512
Inputs and outputs expanded to 1024
513 - 1024
32
PE-33016
used as splitters
513 - 1024
513 - 1024
Frame 1
Trinix
512 x 512
Frame 3
Trinix
512 x 512
1 - 512
513 - 1024
32
PE-33016
used as
combiners
513 - 1024
Dual outputs
52 Planning and Installation Manual
Figure 22. 1024 x 2048 system.
Frame 0
Duplication and Expansion
Inputs
1 - 512
64
PE-33008
used as
1 x 4
splitters
Inputs expanded to 1024
1 - 512
1 - 512
1 - 512
1 - 512
Trinix
512 x 512
Frame 2
Trinix
512 x 512
Frame 8
Trinix
512 x 512
Frame 10
Trinix
512 x 512
Frame 1
32
1 - 512
PE-33016
used as
Dual outputs
combiners
Outputs expanded to 2048
32
513 - 1024
PE-33016
used as
Dual outputs
combiners
Inputs
513 - 1024
64
PE-33008
used as
1 x 4
splitters
513 - 1024
513 - 1024
513 - 1024
513 - 1024
Trinix
512 x 512
Frame 3
Trinix
512 x 512
Frame 9
Trinix
512 x 512
Frame 11
Trinix
512 x 512
32
PE-33016
used as
combiners
32
PE-33016
used as
combiners
1025 - 1536
Dual outputs
1537 - 2048
Dual outputs
Planning and Installation Manual 53
Planning Guide
Inputs
1 - 512
Inputs expanded to 2048
Inputs
513 - 1024
Figure 23. 2048 x 1024 system.
1 - 512
32
PE-33016
used as splitters
1 - 512
513 - 1024
32
PE-33016
used as splitters
513 - 1024
Frame 0
Trinix
512 x 512
Frame 2
Trinix
512 x 512
Frame 1
Trinix
512 x 512
Frame 3
Outputs expanded to 1024
64
PE-33008
1 - 512
used as
Dual outputs
4 x 1
combiners
Inputs
1025 - 1536
Inputs
1537 - 2048
32
PE-33016
used as splitters
32
PE-33016
used as splitters
1025 - 1536
1025 - 1536
1537 - 2048
1537 - 2048
Trinix
512 x 512
Frame 4
Trinix
512 x 512
Frame 6
Trinix
512 x 512
Frame 5
Trinix
512 x 512
Frame 7
64
PE-33008
used as
4 x 1
combiners
513 - 1024
Dual outputs
Trinix
512 x 512
54 Planning and Installation Manual
Figure 24. 2048 x 2048 system.
Duplication and Expansion
Inputs and outputs expanded to 2048
Inputs
513 - 1024
Inputs
1 - 512
PE-33008
used as
splitters
1 x 4
64
PE-33008
used as
1 x 4
splitters
513 - 1024
513 - 1024
64
513 - 1024
513 - 1024
Frame 1
Trinix
512 x 512
Frame 3
Trinix
512 x 512
Frame 9
Trinix
512 x 512
Frame 11
Trinix
512 x 512
1 - 512
1 - 512
1 - 512
1 - 512
1025 - 1536
Frame 0
Trinix
512 x 512
Frame 2
Trinix
512 x 512
Frame 8
Trinix
512 x 512
Frame 10
Trinix
512 x 512
Frame 4
Trinix
512 x 512
64
PE-33008
used as
4 x 1
combiners
64
PE-33008
used as
4 x 1
combiners
1 - 512
Dual outputs
513 - 1024
Dual outputs
Inputs
1025 - 1536
Inputs
1537 - 2048
64
PE-33008
used as
1 x 4
splitters
PE-33008
used as
1 x 4
splitters
1025 - 1536
1025 - 1536
1537 - 2048
1537 - 2048
64
1537 - 2048
1537 - 2048
Frame 5
Trinix
512 x 512
Frame 7
Trinix
512 x 512
Frame 13
Trinix
512 x 512
Frame 15
Trinix
512 x 512
1025 - 1536
Frame 6
Trinix
512 x 512
Frame 12
Trinix
512 x 512
Frame 14
Trinix
512 x 512
64
PE-33008
used as
4 x 1
combiners
64
PE-33008
1025 - 1536
used as
Dual outputs
4 x 1
combiners
1537 - 2048
Dual outputs
Planning and Installation Manual 55
Planning Guide
Termination for Pre-wired Expansion Frames
Figure 25. LD-33100 Loader board
As described above, unused BNC connectors on port expanders should be terminated for best performance. However, it may be desirable to install an empty or partially stuffed frame and associated cabling to simplify future expansion, and when such cabling connects to a port expander that is carrying active signals, special termination hardware is required. Since the presence of pre-wired cabling will not permit standard BNC terminators to be installed on the expander, an LD-33100 Loader board is installed in the associated frame in place of an input or output board to provide correct termination.
Input Expansion
For example, Figure 26 shows a 512 x 512 system expandable to 1024 x 512:
Figure 26.
Frame 0
1 - 512
1 - 512
32
PE 33016
used as
combiners
Installed pre-wiring
Output slots should be terminated using LD-33100 Loader boards
outputs
1 - 512
Future input wiring
Trinix
512 x 512
Frame 1
(unused)
Trinix
512 x 512
Frame 1 contains no input or output boards, but wiring has already been installed between Frame 1 and the PE-331016 Port Expanders.
56 Planning and Installation Manual
Duplication and Expansion
Input 1B - from Frame 1 Output 1.
Input 1A - from Frame 0 Output 1
Output 1A - to downstream equipment
Output 1B - not used. Termination provided by
Termination provided by LD-33000
75 ohm BNC terminator
in upstream Trinix frame.
Now consider Output 1 of Frame 0. This sign al is conn ected to Input 1A of the first PE-33016 Port Expander. See Figure 27.
Figure 27. Detail of one PE-33016 shown in Figure 26.
In this example:
Only Input 1A and Output 1A are presently functional.
Following the rule that unused connectors should be terminated, Output 1B is fitted with a 75 ohm BNC terminator.
Input 1B is pre-wired to Frame 1, so there is no place for a termi­nator. In this case, termination will be provided by an LD-33100 Loader board installed in output board slot “1-32” of Frame 0. Fur­thermore, in this example all 16 output slots of Frame 0 should have an LD-33000 installed.
When the system is upgraded to 1024 x 512, the LD-33000 boards will be removed and replaced by output boards. Cabling to the port expanders is already in place.
The concepts in this example apply equally to systems with PE-33008 Port Expanders. For example, they would apply to a 1024 x 1024 system that is pre-wired for expansion to 2048 x 1024 (similar to the system shown on page 54, where LD-33100 Loader boards would be installed in place of output boards in Frames 4 through 7).
Planning and Installation Manual 57
Planning Guide
Input 1A - from upstream equipment
Output 1A - to Frame 0 Input 1
Input 1B - not used. Termination
provided by 75 ohm BNC terminator
Output 1B - to Frame 1 Input 1. Termination provided by LD-33100 in Frame 1.
Output Expansion
Similarly, LD-33100 Loader boards may also be used for output­expandable systems. For example, Figure 28 shows a 512 x 512 system expandable to 512 x 1024:
Figure 28.
Frame 0
1 - 512
Future output wiring
1 - 512
32
PE 33016
used as splitters
Installed pre-wiring
Input slots should be terminated using LD-33100 Loader boards
1 - 512
Trinix
512 x 512
Frame 1
(unused)
Trinix
512 x 512
Again, considering one signal path (Figure 29), pre-wired cable connec­tions do not allow for installation of individual terminators. Instead, LD-33100 Loader boards are installed in the unused frame, but in this case they are installed in the input slots.
Figure 29. Detail of one PE-33016 shown in Figure 28.
Input and Output Expansion
The rules just described for use of LD-33100 Loader boards will also apply to systems designed for expansion of both inputs and outputs. An example would be a 512 x 512 pre-wired for expansion to 1024 x 1024 (similar to the system shown on page 52). Only chassis 0 would be active in the 512 x 512 router, so only the port expanders connected to Frame 0 would be in use. Frame 1’s inputs are connected to the top left PE; while Frame 2’s outputs are connected to the top right PE. Therefore Frame 1’s input slots would require LD-33100s and Frame 2’s output slots would require LD-33100s. No LDs would be needed for Frame 3.
58 Planning and Installation Manual
Monitoring with Expanded Systems
In expanded systems, output monitor signals must be brought through a combiner. An example of an output-expanded system in shown in
Figure 30; an input-expanded system is shown in Figure 31.
Note Output monitoring is not available for input-expanded systems con-
trolled by an SR-33000 Sync/OPM board.
Figure 30. Monitoring with output-expanded system.
1 - 256
Duplication and Expansion
Frame 0
1 - 256
Trinix
256 x 256
1 - 256
1 - 256
Frame 0
Trinix
256 x 256
PE-33016s
used as splitters
1 - 256
1 - 256
PE-33016s
combiners
32
used as
Frame 2
Trinix
256 x 256
Output monitor video
Dual outputs
Output monitor video
257 - 512
PE-33016
used as
combiner
1 - 256
QC station
Frame 1
257-512
Trinix
256 x 256
257 - 512
Output monitor video
PE-33016
used as
combiner
QC station
Figure 31. Monitoring with input-expanded system.
Planning and Installation Manual 59
Planning Guide

Protected Paths

Overview

The protected path function is designed to monitor router outputs that are feeding critical downstream equipment and, in the event of signal loss, automatically select the output that i s carrying the same signal and trigger the system alarm.
This function assumes the following:
HO-33120 HD/SD Output Board(s) are providing the output signal(s) to be monitored. These boards allow individual outputs to be enabled or disabled using software controls.
Protection is provided for paths, i.e., input/output pairs. The installer must identify critical outputs and an associated critical input for each. For redundancy, two paths must be defined: a “pri­mary” path and a failover “secondary” path.
Protected pairs should be hard wired to back-panel connectors that will provide the most independent possible paths through the router. For example, the two paths should use different input boards and different output boards. Depending on router size, the two paths may also be able to use different matrix boards and dif­ferent power sources.
For full redundancy, two copies of each protected input must be wired to the router. For example, the master control switcher output could be sent through a passive splitter upstream of the router. One copy is used for the primary path, and the other for the secondary path. If an upstream splitter is used, steps must be taken to boost the gain for the appropriate block of inputs (as described in the Trinix manual).
The primary output and the secondary output must be wired to a passive combiner, the output of which is connected to the down­stream equipment. The protected path software will automatically boost individual outputs as needed for proper gain level through the splitter. Outputs not configured for protected path operation should be set for gain levels as described in the manual. (The pro­tected path software will override the manual settings as needed.)
The control system (e.g. Encore or Jupiter) must be operated so that the secondary path is always ready to provide a copy of the pro­tected signal. For example, the operator would switch the Master Control output to the transmitter on the primary path; the control system would then switch the secondary path automatically. For more information, see Encore Configuration on page 184 or Jupiter
Configuration on page 189.
60 Planning and Installation Manual
Splitter
Combiner
Primary path
Output Status
Signal OK, driver ON
Output assigned to protected path, driver OFF
Protected Paths
Figure 32 shows an example of a DV-33512 router with a pair of pro-
tected paths.(Depending on system requirements, the upstream splitter may or may not be needed.) The signal detector monitors the primary path and if necessary will disable the primary path output driver and enable the secondary path output driver. Notice that the two paths use independent sets of hardware.
Figure 32. Example of protected paths for DV-33512 router
Output Status
Signal OK, driver ON
Output assigned to protected path, driver OFF
Splitter
Powered by
PS C and PS D
Inputs
Inputs
385-512
257-384
Powered by
PS A and PS B
Outputs
129-256
Outputs
257-384
1-128
Outputs
Outputs
385-512
Input 1Output 1
1-128
Inputs
Inputs
129-256
Input/Output
boards
DM-33501/2
Matrix boards
Input/Output
boards
Combiner
Output 257Input 257
Secondary path
The following discussion describes the protected path planning pro­cess.
Planning and Installation Manual 61
Planning Guide

Planning

Note The following discussion is based on a “1-based” numbering scheme. If
you are using a “zero-based” numbering system, subtract “1” from all instances of input/output numbers.
DV-33512
The recommended protected path ranges for DV-33512 routers are as follows:
Ta b l e 2.
Primary path Secondary path
Output Input Output Input
1-128 1-128 257-384 257-384
For example, to protect an output in the range 1-128, choose a corre­sponding input in the range 1-128; this will be the primary path. For the secondary (failover) path, choose an output in the range 257-384 and a corresponding input in the range 257-384.
Alternatively, the high-range of connectors can be used for the primary path and the low range for the secondary path, as shown in Tab le 3 :
Ta b l e 3.
Primary path Secondary path
Output Input Output Input
257-384 257-384 1-128 1-128
Using either of these schemes will provide the most independent pos­sible paths through a DV-33512, i.e., the primary path will use one set of input, matrix, and output boards connected to one power source while the secondary path will use a different set of boards connected to a different power source.
Note that for a DV-33512 router the maximum number of protected paths is 256.
62 Planning and Installation Manual
Protected Paths
A more detailed example is shown in Tab le 4 . This table shows a sequential wiring scheme for a system yet to be installed or a system where cables will be re-arranged in a symmetrical pattern in order to simplify protected path configuration.
Table 4. DV-33512 protected paths (example of sequential numbering)
Primary path Secondary path
Out In Out In
Name No. Name No. Name No. Name No.
AirPP 1 MCPP 1 AirSP 257 MCSP 257
Sat1PP 2 StuAPP 2 Sat1SP 258 StuASP 258
Sat2PP 3 StuBPP 3 Sat2SP 259 StuBSP 259
.. ..
.. ..
.. ..
NetPP 256 MainPP 256 NetSP 512 MainSP 512
The numbers shown here correspond to the connector numbers used during router configuration (but not, in most cases, to the actual silk screen number on the rear panel itself since the silk screen numbers only run from “1” to “32.”)
In Jupiter-controlled systems, the “Name” in these tables corresponds to the “logical input/output name” and the entries in the number column correspond to the “physical” input/output number.
The next example applies to existing systems where re-arrangement of cables in a sequential pattern is not practical or desirable:
Table 5. DV-33512 protected paths (example of non-sequential numbering)
Primary path Secondary path
Out In Out In
Name No. Name No. Name No. Name No.
AirPP 21 MCPP 12 AirSP 390 MCSP 265
Sat1PP 253 StuAPP 254 Sat1SP 413 StuASP 348
Sat2PP 109 StuBPP 98 Sat2SP 289 StuBSP 409
.. ..
.. ..
.. ..
NetPP 4 MainPP 256 NetSP 440 MainSP 454
Notice that in all cases the primary path I/O numbers are always in the 1-256 range while the secondary path I/O numbers are always in the 257-512 range.
Planning and Installation Manual 63
Planning Guide
DV-33256
Recommended protected path ranges for DV-33256 routers are as fol­lows:
Ta b l e 6.
Primary path Secondary path
Out In Out In
1-128 1-128 129-256 129-256
For example, to protect an output in the range 1-128, choose a corre­sponding input in the range 1-128; this will be the primary path. For the secondary (failover) path, choose an output in the range 129-256 and a corresponding input in the range 129-256.
This will provide the most independent possible paths through a DV­33256, i.e., the primary path will use one set of input, matrix, and output boards while the secondary path will use a different set of boards.
CAUTION With a DV-33256, it isn’t possible to arrange completely independent
paths, i.e., paths that use different power supplies. Protected path con­figuration for DV-33256 routers provides redundancy for matrix boards and input and output boards only.
Note that for a DV-33256 router the maximum number of protected paths is 128.
A more detailed example is shown in Tab le 7 . This table shows a sequential wiring scheme for a system yet to be installed or a system where cables will be re-arranged in a symmetrical pattern in order to simplify protected path operation.
Table 7. DV-33256 protected paths (example of sequential numbering)
Primary path Secondary path
Out In Out In
Name No. Name No. Name No. Name No.
AirPP 1 MCPP 1 AirSP 129 MCSP 129
Sat1PP 2 StuAPP 2 Sat1SP 130 StuASP 130
Sat2PP 3 StuBPP 3 Sat2SP 131 StuBSP 131
.. ..
.. ..
.. ..
NetPP 128 MainPP 128 NetSP 256 MainSP 256
64 Planning and Installation Manual
Protected Paths
Splitter
Combiner
Output Status
Signal OK, driver ON
Output assigned to protected path, driver OFF
The numbers shown here correspond to the connector numbers used during router configuration (but not, in most cases, to the actual silk screen number on the rear panel itself since the silk screen numbers only run from “1” to “32.”)
In Jupiter-controlled systems, the “Name” corresponds to the “logical input/output name” and the number corresponds to the “physical” input/output number.
Figure 33. Example of protected paths for DV-33256 router
DM-33100
Matrix boards
Primary path
Splitter
Secondary path
Inputs
129-256
1-128
Outputs
129-256
Output 128Input 128
Outputs
1-128
Inputs
Input 1Output 1
Input/Output
boards
Output Status
Signal OK, driver ON
Output assigned to protected path, driver OFF
Combiner
Planning and Installation Manual 65
Planning Guide
The next example applies to existing systems where re-arrangement of cables in a sequential pattern is not practical or desirable:
Table 8. DV-33256 protected paths (example of non-sequential numbering)
Primary path Secondary path
Out In Out In
Name No. Name No. Name No. Name No.
AirPP 21 MCPP 12 AirSP 190 MCSP 165
Sat1PP 53 StuAPP 54 Sat1SP 133 StuASP 248
Sat2PP 109 StuBPP 98 Sat2SP 189 StuBSP 129
.. ..
.. ..
.. ..
NetPP 4 MainPP 56 NetSP 144 MainSP 145
Notice that in all cases the primary path I/O numbers are always in the 1-128 range while the secondary path I/O numbers are always in the 129-256 range.
66 Planning and Installation Manual
Protected Paths
DV-33128
Recommended protected path ranges for DV-33128 routers are as fol­lows:
Ta b l e 9.
Primary path Secondary path
Out In Out In
1-32 1-32 33-128 33-128
33-64 33-64
65-96 65-96
97-128 97-128 1-96 1-96
1-32,
65-128
1-64,
97-128
For example, to protect an output in the range 1-32, choose a corre­sponding input in the range 1-32; this will be the primary path. For the secondary (failover) path, choose an output in the range 33-128 and a corresponding input in the range 33-128.
1-32,
65-128
1-64,
97-128
This will provide the most independent possible paths through a DV­33128, i.e., the primary path will use one pair of input and output boards while the secondary path will use a different pair of boards.
CAUTION With a DV-33128, it isn’t possible to arrange completely independent
paths, i.e., paths that use different matrix boards and power supplies. Protected path configuration for DV-33128 routers provides redundancy for input and output boards only.
Note that for a DV-33128 router the maximum number of protected paths is 64.
A more detailed example is shown in Tab le 1 0. This table shows a sequential wiring scheme for a system yet to be installed or a system where cables will be re-arranged in a symmetrical pattern in order to simplify protected path operation.
Table 10. DV-33128 protected paths (example of sequential numbering)
Primary path Secondary path
Out In Out In
Name No. Name No. Name No. Name No.
AirPP 1 MCPP 1 AirSP 33 MCSP 33
Sat1PP 2 StuAPP 2 Sat1SP 34 StuASP 34
Sat2PP 3 StuBPP 3 Sat2SP 35 StuBSP 35
.. ..
.. ..
.. ..
NetPP 64 MainPP 64 NetSP 128 MainSP 128
Planning and Installation Manual 67
Planning Guide
The numbers shown here correspond to the connector numbers used during router configuration (but not, in most cases, to the actual silk screen number on the rear panel itself since the silk screen numbers only run from “1” to “32.”)
In Jupiter-controlled systems, the “Name” corresponds to the “logical input/output name” and the number corresponds to the “physical” input/output number.
The next example applies to existing systems where re-arrangement of cables in a sequential pattern is not practical or desirable:
Table 11. DV-33128 protected paths (example of non-sequential numbering)
Primary path Secondary path
Out In Out In
Name No. Name No. Name No. Name No.
AirPP 21 MCPP 12 AirSP 33 MCSP 33
Sat1PP 53 StuAPP 54 Sat1SP 1 StuASP 1
Sat2PP 109 StuBPP 95 Sat2SP 96 StuBSP 64
Notice that I/O numbers conform to the ranges shown in Tab le 9.
68 Planning and Installation Manual
Worksheet for Protected Path Implementation
Based on the preceding examples, specific primary and secondary paths should be identified and noted. The following worksheet is pro­vided for this purpose.
Table 12. Protected paths worksheet
Primary path Secondary path
Output Input Output Input
Name No. Name No. Name No. Name No.
Protected Paths
Planning and Installation Manual 69
Planning Guide

Control Systems

Jupiter Facility Control System

The Jupiter control system can be used to operate the Trinix router using a VM-3000 or CM-4000 System Controller (Figure 34). The VM/ CM can receive switching commands from a variety of serial sources, including Jupiter control panels or an automation computer.
Figure 34. Control connections to Jupiter Facility Control System (example).
Trinix routing
switcher(s)
10Base2 LAN
VM-3000 System Controller
T
T
10/100BaseT LAN
Media converter or hub
Ungrounded
=
T
50-ohm terminator
Jupiter file server
Crosspoint bus
Crosspoint bus terminator
MPK bus
T
Jupiter control panels
In this application, the Trinix is operated in the “external crossspoint bus control” mode, during which the Broadlinx board releases control of the crosspoint bus. Switch commands arriving at the crosspoint bus connector on the rear of the chassis will be executed.
70 Planning and Installation Manual
Control Systems
CC-2010 Matrix (Crosspoint Bus) Cable
Connection from a Jupiter VM-3000 or CM-4000 System Controller is via a crosspoint bus cable, which can be supplied in 3, 10, 25, or 50 foot lengths. The crosspoint bus connector is looped out in order to connect the bus to the next item under crosspoint control.
Depending on the size of the switcher this bus may require interme­diate buffering through a CB-3000 Control Buffer. A CB 3000 is required in the following cases:
DV-33128 - eight or more chassis DV-33256 - four or more chassis DV-33512 - two or more chassis
The CB-3000 is described in detail in the Jupiter Installation and Oper­ating manual.
In Trinix applications, the crosspoint bus must be terminated at the point farthest from the control processor using a Crosspoint Bus Termi­nator, part number 01-053050-001.
The CC-2010 is a 10-conductor (plus ground) cable. Ready-made cables, with installed 15-pin D male connectors, are available from Grass Valley; see page 88.
All rear-panel crosspoint bus connectors are 15-pin D, female.
For those who wish to prepare their own cables, pin-outs are shown on
page 150. The cable itself should be Belden 9505 or equivalent. User-
supplied matrix cables for VDE installations require a ferrite core over each end of the cable, adjacent to the connector. Details concerning ferrite cores are given on page 150.
Jupiter Control System Installation
Refer to the Jupiter VM-3000 System Controller Installation and Oper­ation Manual, part no. 071 8305 xx or the Jupiter CM-4000 System Con­troller Installation and Operation Manual, part no. 071 8261 xx for control system installation details.
Planning and Installation Manual 71
Planning Guide

SMS 7000 / Encore Control

These control systems use an Ethernet connection to the Broadlinx application, which runs on the NR-33000 Sync/NIC/OPM board.
The system is operated in the “internal crosspoint bus control” mode, during which the Broadlinx board sends commands to the crosspoint bus.
LAN components are described below.
Refer to the SMS 7000 or Encore documentation for control system planning information.
72 Planning and Installation Manual

LAN and Com Bus Connections

The LAN (NIC) connections use a standard 10/100BaseT twisted pair cable with RJ-45 connectors (Cat 5E Enhanced is recommended). Shielded cable is also recommended, maximum length 60 meters. Maximum length for unshielded cable is 100 meters.
LAN Monitoring Only (Jupiter Control)
In this arrangement the router is under Jupiter control and the only purpose of the connection is LAN monitoring using Broadlinx web pages or SNMP. See Figure 35.
Figure 35. LAN connections for LAN monitoring only (Jupiter Control)
LAN and Com Bus Connections
1
NIC B connector
Trinix
Ethernet switch
Monitoring PC
NIC A connector
If you plan on using a secondary Broadlinx board another Ethernet cable must be connected from the “NIC B” jack to the network switch.
If the Trinix LAN is connected to the Internet the connection should be made through a firewall.
1.
Compliance with EEC, EMC, EN series, UL- 1950, and CSA C22.2 No. 950-M89 standards requires use of a shielded cable.
Planning and Installation Manual 73
Planning Guide
SMS Control
In this arrangement the router is under SMS control via a LAN connec­tion. The PC is used to configure the SMS and is also available for Broadlinx or SNMP monitoring. See Figure 36.
Figure 36. SMS connections to Trinix.
NIC B connector
Trinix
Ethernet switch
7000 SMS
MCPU frame
Ethernet connector
PC
NIC A connector
If you plan on using a secondary NR-33000 board another Ethernet cable must be connected from the “NIC B” jack to the network switch.
If the Trinix LAN is connected to the Internet the connection should be made through a firewall.
74 Planning and Installation Manual
LAN and Com Bus Connections
Encore Control
In this arrangement the router is under Encore control via a LAN con­nection. The PC is used to configure the Encore and is also available for Broadlinx or SNMP monitoring. Figure 37 shows the recommended connections when the system is equipped with redundant NR-33000 boards and redundant Encore controllers.
Figure 37. Encore connections to Trinix
PC
Ethernet switch
Ethernet switch
Primary Encore controller
NIC A connector
EN1
EN2
Trinix
Encore control panels
EN1
Secondary Encore controller
EN2
NIC B connector
Ethernet switch
Planning and Installation Manual 75
Planning Guide

Com Bus

Trinix frame with NR-33000 Sync/NIC/ OPM board (Broadlinx board)
In multi-frame systems, a “Com Bus” is used to loop through each frame, up to a maximum of four. The Com Bus is intended to provide switcher monitoring of multiple frames using Broadlinx web pages or SNMP. The Com Bus uses a 10/100BaseT (Cat 5 twisted pair) cable with RJ-45 connectors. Shielded cable is recommended, maximum length 60
1
meters.
Figure 38.
Maximum length for unshielded cable is 100 meters.
Trinix frames with SR-33000 Sync/OPM or SR-33500 Sync/OPM boards
Com Bus cable (see discussion for specifications)
In DV-33512 systems, if the power supply chassis is equipped with an NR-33000 Broadlinx board, a Cat 5 twisted pair cable must be installed between the power supply chassis Com Bus connector associated with the NR board and one of the main chassis Com Bus connectors.
If there are additional DV-33512 main frames in the system, and they do not have Broadlinx boards, then the Com Bus should be daisy-chained to those frames also.
For an illustration, see page 102.
1.
Compliance with EEC, EMC, EN series, UL- 1950, and CSA C22.2 No. 950-M89 standards requires use of a shielded cable.
76 Planning and Installation Manual

System Monitoring Applications

For a detailed description of Broadlinx web page monitoring using Internet Explorer, see Broadlinx / Internet Explorer Monitoring on
page 166.
For a brief description of system monitoring using SNMP/NetCentral, see SNMP/NetCentral Monitoring on page 23.
System Monitoring Applications
Planning and Installation Manual 77
Planning Guide

Specifications

Electrical

Connectors: 75 ohm BNC
Input cards: 32 inputs each.
Output cards: 32 outputs each.
Matrix cards: DM-33100: 128 inputs x 128 outputs.
Level: 800 mV p-p (+/-10%) 75 ohm terminating
Return loss: HD: >/=15 dB from 5 MHz to 1.5 GHz
General
DM-33512: 256 inputs x 256 outputs. For additional information about the various input, output, and matrix cards available for Trinix, see page 83.
Video Inputs
SD: >/=15 dB from 5 MHz to 540 MHz
Sync Inputs
Level: Nominal 1 Vp-p (+/-6 dB) video or black burst.
Tri-level sync also accepted
Video standard: NTSC/PAL/HDTV, auto-detected
Return loss: >/=40 dB from 100 kHz to 20 MHz
>/=30 dB from 20 MHz to 30 MHz
Video Outputs
Level: 800 mV p-p +/-10% 75 ohm
Return loss: >/=15 dB from 5 MHz to 1.5 GHz (except Monitor outputs)
Performance Characteristics
Maximum data rate: 1.5 Gbps
Minimum data rate: 3.072 Mbps
Signal standards: SMPTE 292M-1998,
fall times correspond to SMPTE 292M)
Equalization: SI-33110 Input Card (SD): automatic up to 300 meters of
Belden 1694A, 250 meters of Belden 8281 or equivalent coax cable for SD equalizer at 270 Mbps. Reducing to 150 meters at 540 Mbps.
1
SMPTE 259M-19971 (Output rise and
1.
See Glossary
78 Planning and Installation Manual
HI-33110 Input Card (SD/HD): automatic up to 100 meters of Belden 1694A or equivalent coax cable.
VI-33100 Input Card (SD/HD): For digital SD operation, automatic up to 300 meters of Belden 1694A or equivalent coax cable. For HD operation, automatic up to 100 meters of Belden 1694A or equivalent coax cable.
HI-33200 Input Card (SD/HD): For SD operation, auto­matic up to 300 meters of Belden 1694A or equivalent coax cable. For HD operation, automatic up to 100 meters of Belden 1694A or equivalent coax cable.
Data reclocking: Switch selectable on an output-by-output basis.
The HO-33110 Output Board provides individual selection of reclocking for 1.485 Gbps or non-reclocking for all data rates. The HO-33120 Output Board provides individual selection of reclocking On or Off for the supported data rates. The data rate for reclocking is automatically selected by the cir­cuitry on the board for 1.485 Gbps, 540 Mbps, 360 Mbps, 270 Mbps, 177 Mbps, and 143 Mbps. Other data rates will not be reclocked. The SO-33110 Output Board is non-reclocking.
Specifications
Output jitter: </= 0.2 unit interval
AC Power Input
Mains connection: IEC Connector, separate mains input for each power sup-
ply module
Voltage range: 100-240 VAC 50-60 Hz, universal, auto-ranging (fuses must
be selected and installed as appropriate for mains voltage)
Operating current 128 x 128 frame: approx. 5.36 A @ 100 VAC, approx. 2.23 A
@ 240 VAC. 256 x 256 frame: approx. 9.36 A @ 100 VAC, approx. 3.90 A @ 240 VAC 512 x 512 frame: approx. 19.08 A @ 100 VAC; approx. 7.63 A @ 240 VAC
Inrush current 128 x 128 frame: 49.05 A
256 x 256 frame: 55.0 A 512 x 512 frame: 45 A
Hold-up time: Minimum 20 msec at full load
Conducted emissions: per FCC Class B, EN55022 Class B
Power Supply DC Output
Voltage: +48 (+/-0.5) VDC
Current: 128 x 128 frame: 12.5 A/supply (full redundancy).
Planning and Installation Manual 79
Planning Guide
256 x 256 frame: 26 A/supply (full redundancy). 512 x 512 frame: approx. 26 A/supply (full redundancy).
Current sharing: Yes, maximum 20% differential unbalance
Ripple/noise: <200 mVp-p
DC Power Input
Input voltage range 42-54 VDC
Operating current 128 x 128 frame: approx. 9.5 A @ 48 VDC.
256 x 256 frame: approx. 16 A @ 48 VDC. 512 x 512 frame: approx. 34 A @ 48 VDC.
Inrush current 128 x 128 frame: 15 A.
256 x 256 frame: 21 A. 512 x 512 frame: approx. 25 A.
Alarm
The relay connector is a BNC type and meets SMPTE 269M-1999 (see Glossary).

Environmental

0 to +35 degrees C (+32 to +95 F)

Physical

14 inches (8 RU) high x 19 in. wide x 17.50 in. deep (356 x 483 x 445 mm)
26.25 inches (15 RU) high x 19 in. wide x 17.5 in. deep (667 x 483 x 445 mm)
Main chassis: 49 inches (28 RU) high x 19 in. wide x 17.5 in. deep (1245 x 483 x 445 mm)Power supply chassis: 7 inches (4 RU) high x 19 in. wide x 21 in. deep (178 x 483 x 533 mm)
14 inches (8 RU) high x 19 in. wide x approximately 4 in. deep (356 x 483 x 100 mm)
128 x 128 frame
256 x 256 frame
512 x 512 frame
MK-33000 Mounting Kit (for port expansion)
80 Planning and Installation Manual

Configuration

Quick Look

Building block size: 32 Inputs or 32 Outputs
Options: SD or HD rate I/O modules
Standards supported: SMPTE 259M-1997, SMPTE 292M-1998
Standard connectors: 75-Ohm BNC
Output monitor: Yes, 2 standard
Sync reference input:Yes, 2. Granularity: per 32 outputs
Control options: Jupiter, SMS 7000, Encore
Configuration
Dual outputs, quad outputs
Additional monitor outputs (2)
Redundant sync inputs (2)
Redundant monitor/status/control
Redundant power supplies

Chassis, Board, Weight and Power Summary for Select Matrix Sizes

Ta b l e 13 .
Matrix Size
# of Chassis 1111111 1
# Input Boards 1234567 8
# Output Boards 1234567 8
# of Matrix Boards 1111444 4
Weight in pounds (kilograms)
Power Consumption* (W) ~350 ~400 ~440 ~480 ~850 ~900 ~950 ~1000
32
x
32
75
(34)
*Approximate
64
x
64
128 Chassis 256 Chassis
81
(37)
96
x
96
88
(40)
128
x
128
94
(43)
160
x
160
163
(74)
192
x
192
169
(77)
224
x
224
176 (80)
256
x
256
182 (83)
Planning and Installation Manual 81
Planning Guide
Ta b l e 14 .
Matrix Size
# of Chassis 1 1 1 1 2 2
# Input Boards 8 8 16 16 32 32
# Output Boards 8 16 8 16 24 32
# of Matrix Boards 1 2 2 4 6 8
Weight* in pounds (kilograms)
# of RUs 32 32 32 32 64 64
Power Consumption* (W) ~1000 ~1400 ~1600 ~2000 ~3500 ~4000
Ta b l e 15 .
Matrix Size
768
x
512
256
x
256
~300
(~140)
768
x
768
256
x
512
~350
(~160)
1024
x
512
512
x
256
512 Chassis
~350
(~160)
1024
x
1024
512
x
512
~400
(~180)
512
768
~750
(~340)
x
512
x
1024
~800
(~360)
2048
x
2048
512 Chassis
# of Chassis 2 4 2 4 16
# Input Boards 24 48 32 64 256
# Output Boards 32 48 32 64 256
# of Matrix Boards 6 9 8 16 64
Weight* in pounds (kilograms)
# of RUs 64 192 64 192 512
Power Consumption* (W) ~4000 ~6000 ~4000 ~8000 ~32000
~750
(~340)
~1400 (~640)
~800
(~360)
~1600
(~730)
~6400
(~2900)
*Approximate
82 Planning and Installation Manual

Ordering Information

Trinix routing systems are ordered as a base frame; a set of input, output, and matrix boards; and options.

Frames

TRX-DV-33128
128 x 277P MAESTRO.xls128 Frame with 1 PS, 1 Broadlinx, 2 Fan Mod­ules. 8 RU
TRX-DV-33256
256 x 256 Frame with 1 PS, 1 Broadlinx, 3 Fan Modules. 15 RU
TRX-DV-33512
512 x 512 Frame with 2 PS, 1 Broadlinx, 6 Fan Modules. 32 RU
Ordering Information

Input, Output, and Matrix Boards

Input and output boards each have 32 inputs or outputs and can be grouped into SD and HD blocks within a frame. The matrix board is available in two sizes.
TRX-SI-33110
SD Input Module - consists of a 16-input base board (SI-33110) and a 16­input mezzanine board (SI-33011), providing 32 inputs. Supports data rates of 3 to 540 Mbps. A “gain cell” is included on this board to be used in conjunction with the port expanders in order to create multi-chassis routers.
TRX-HI-33200
SD/HD Input Module - consists of a 16-input base board (HI-33200) and a 16-input mezzanine board (HI-33201), providing 32 inputs. The module supports data rates of 3 Mbps to 1.485 Gbps. A “gain cell” is included on this board to be used in conjunction with the port expanders in order to create multi-chassis routers.
TRX-VI-33100
Video Input Module - consists of a 16-input “universal” base board (VI-
33100) and a 16-input digital-only mezzanine board (HI-33201), pro-
viding 32 inputs.
The VI-33100 Universal base board auto-senses and accepts 16 com­posite analog SD, digital SD, or digital HD signals in any combina­tion and passes them in digital SD or digital HD form (as appropriate) to the Trinix matrix board. When analog signals are
Planning and Installation Manual 83
Planning Guide
received, an extensive set of gain, phase, filtering, and other adjust­ments are available for each signal. For a list of these adjustments, see page 40.
The HI-33201 SD/HD Digital Input mezzanine board auto-senses and accepts a second set of 16 digital SD or digital HD signals in any combination and passes them in digital SD or digital HD form (as appropriate) to the Trinix matrix board.
TRX-HI-33200
SD/HD Digital Input Module - consists of a 16 input base board (HI-
33200) and a 16 input mezzanine board (HI-33201), providing a total of
32 inputs. Each board auto-senses and accepts 16 digital SD or digital HD signals in any combination and passes them in digital SD or digital HD form (as appropriate) to the Trinix matrix board. The TRX-HI-33200 is similar to the TRX-VI-33100 but is not fully stuffed.
TRX-SO-33110
SD Output Module, non-reclocked - consists of a 16 output base board (SO-33110) and a 16 output mezzanine board (SO-33011), providing a total of 32 outputs.
A “gain cell” is included on this board to be used in conjunction with the port expanders in order to create multi-chassis routers as well as dual or quad outputs. A switch is included to select one of four syn­chronizing inputs.
TRX-HO-33110
HD Output Board, 1.5 G reclocked - consists of a 16 output base board (HO-33110) and a 16 output mezzanine board (HO-33011), providing a total of 32 outputs.
Each output can be set for Auto Detect “ON” or “OFF.” When Auto Detect is ON the signal will be checked to see if it is a valid HD signal running at 1.485 Gbps; if so, the signal will be reclocked; if not, it will be bypassed. When Auto Detect is OFF the output signal is never reclocked. A “gain cell” is included on this board to be used in conjunc­tion with the port expanders in order to create multi-chassis routers as well as dual or quad outputs. A switch is included to select one of four synchronizing inputs.
TRX-HO-33120
Universal Output Module, multi-rate reclocker - consists of a 16-output base board (HO-33120) and a 16-output mezzanine board (HO-33121).
Each output can be set for Auto Detect “ON” or “OFF.” When Auto Detect is ON the signal will be checked to see if it is a valid HD or SD signal running at a supported data rate; if so, the signal will be reclocked; if not, it will be bypassed. When Auto Detect is OFF the output signal is never reclocked. A “gain cell” is included on this board to be used in conjunction with the port expanders in order to create
84 Planning and Installation Manual
Ordering Information
multi-chassis routers as well as dual or quad outputs. A switch is included to select one of four synchronizing inputs. A list of data rates supported by the HO-33120 Output Board is shown on page 79.
Protected path operation requires HO-33120 Output Modules in the paths to be protected.
TRX-DM-33100
Digital Matrix Board - 128 x 128 for use with 128 and 256 frame
Contains 32 instantiations of a 32 x 16 crosspoint IC. It handles both SD and HD data rates and is used in both the 128 and 256 chassis. It has a memory refresh circuit which is used to keep the configuration of the crosspoints in the event of some power interruption to the controlling element. One card is needed for all configurations in the 128 chassis and 1, 2, or 4 are needed for the 256 chassis depending on the needed matrix size.
TRX-DM-33512
Digital Matrix Board - 256 x 256 for use with 512 frame
This module consists of two circuit boards interconnected, each with a 256 x 128 matrix function. The matrix board uses redundant power-con­ditioning circuitry and 144 x 144 crosspoint ICs (used as 128 x 128) each with its own control circuit. A 512-chassis, fully stuffed to 512 x 512 inputs and outputs, requires four of these modules.

Options

Additional video signal cards
Additional input, output, and matrix cards can be selected for spares or an additional level of signal routing.
Power Supplies and Fans
A redundant power supply and spare can be added if desired.
TRX-PS-33100
Power Supply - 128 frame
TRX-PS-33200
Power Supply - 256 and 512 frame
TRX-FM-33000
Fan Module
Planning and Installation Manual 85
Planning Guide
NIC/Sync/OPM Boards
TRX-BL-33000
Broadlinx board- consists of one NR-33000 NIC/Sync/OPM board and associated software; combines synchronization, network interface, and output monitoring functions.
Requires TRX-CTRL-CPL for SMS 7000 / Encore control or TRX-CTRL­XPT for Jupiter control.
Sync Functions: The BL-33000 includes two sync-reference inputs, which can be NTSC, PAL or Tri-level inputs.
NIC Functions: The NIC (Network Interface Controller) functions include the network connection as well as a computing element that is the heart of the Broadlinx hardware. This controller communicates with the internal micro-controllers within the Trinix chassis as well as with the outside world via the network connection. The NIC is a 10/100 connection that will communicate via HTTP and (optionally) SNMP protocols.
Output Monitor: The BL-33000 provides output monitoring for DV­33128 and DV-33256 systems. Two output monitor ports are included, each with an inverted and non-inverted output. (These output monitor ports are not available when the NR-33000 is installed in a DV-33512 chassis. DV-33512 monitoring is provided by the SR-33500 board, described below.)
1
Adding a second BL-33000 provides two extra sync inputs,
two extra
output monitor ports, and redundant Broadlinx functionality.
TRX-CTRL-CPL
Trinix Info Command: CPL Control
TRX-CTRL-XPT
Trinix Info Command: XPTControl
NR-33000
See BL-33000 Broadlinx option.
TRX-SR-33500
Sync Reference / Output Monitor (OPM) Board. This board is used in DV-33512 units only.
Sync functions: The SR-33500 includes four looping sync-reference 75 ohm BNC inputs which can be NTSC, PAL or Tri-level inputs.
1.
Although a DV-33512 chassis may include SR-33000 and NR-33000 boards (each with two sync inputs), and an SR-33500
board (with four sync inputs), the maximum number of usable sync inputs for any Trinix chassis remains four.
86 Planning and Installation Manual
Ordering Information
Output monitor: Four output monitor ports are included, each with an inverted and non-inverted output.
Broadlinx capability can be added by installing an BL-33000 Broadlinx option in the associated power supply chassis.
Port Expanders
As described above (page 43), these passive, bi-directional modules provide dual and quad outputs as needed for signal duplication and system expansion.
TRX-PE- 33016
The PE-33016 Port Expander has 32 connectors on one side and 32 on the other. Sometimes referred to a “2 x 2 module,” the PE-33016 can be used as a 2 to 1 combiner (with dual outputs) or a 1 to 2 splitter. One or many of these can be installed as the need requires. Using this as a splitter provides dual outputs (non-inverting) for 16 outputs at a time. Installs in MK-33000 Mounting Kit. Since no application uses more than 48 connectors, each PE-33016 is supplied with 16 BNC 75 ohm termina­tors. Additional connectors, if needed, must be provided by the end­user.
TRX-PE-33008
The PE-33008 is a 4 x 1 expander module that has eight BNC connectors on one side and 32 on the other. This unit can be used as a 4 to 1 com­biner or a 1 to 4 splitter. One or many of these can be installed as the need requires. Using this as an output splitter makes quad outputs for eight outputs at a time. Installs in MK-3000 Mounting Kit. All unused connectors must be terminated with 75 ohm BNC terminators (not sup­plied by Grass Valley).
1
TRX-MK-33000
The MK-33000 Mounting Kit, which accommodates up to 16 port expander modules, is eight rack units high and approximately 4 inches deep.
TRX-LD-33100
Loader module. These boards are available for use in systems that have been pre-wired for later expansion. They provide correct termination for installed but unused cables that connect to an “active” Port Expander module. For more information, see page 56.
SNMP/NetCentral Software Options
Order one license key per frame being monitored via SNMP/NetCen­tral. Note: For an overview of NetCentral and associated applications, see page 22.
Planning and Installation Manual 87
Planning Guide
TRX-NETCEN-128
NetCentral SNMP Agent License Key for Trinix 128 x 128 frame
TRX-NETCEN-256
NetCentral SNMP Agent License Key for Trinix 256 x 256 frame
TRX-NETCEN-512
NetCentral SNMP Agent License Key for Trinix 512 x 512 frame
Miscellaneous
MNC-XPT-CBL-3
Crosspoint Bus Cable, 3 ft. (0.91 m)
MNC-XPT-CBL-10
Crosspoint Bus Cable, 10 ft. (3 m)
MNC-XPT-CBL-25
Crosspoint Bus Cable, 25 ft. (7.6 m)
MNC-XPT-CBL-50
Crosspoint Bus Cable, 50 ft. (15.2 m)
Crosspoint Bus Terminator
Included with all systems. Part number: 01-053050-001.
CB-3000B
Crosspoint Bus Buffer. Provides eight additional crosspoint bus outputs. 1 RU. 110/220 VAC.
DV-33128 systems with eight or more chassis
DV-33256 systems with four or more chassis
DV-33512 systems with two or more chassis
MNC-CBLBNC-02
BNC to BNC Cable, 2 meters
TRX-HD128-KIT
Trinix 128HD Spares Kit. Includes 1 ea. BL-33000, DM-33100, FM-33000, HI-33200, HO-33120, and PS-33100
TRX-HD256-KIT
A CB-3000 is required in the following cases:
Trinix 256HD Spares Kit. Includes 1 ea. BL-33000, DM-33100, FM-33000, HI-33200, HO-33120, and PS-33200
88 Planning and Installation Manual
Ordering Information
TRX-HD512-KIT
Trinix 512HD Spares Kit. Includes 1 ea. BL-33000, DM-33512, FM-33000, HI-33200, HO-33120, and PS-33200
TRX-MAN
Trinix Planning and Installation Manual
Planning and Installation Manual 89
Planning Guide
90 Planning and Installation Manual

Installation

Summary of Installation Procedure

The following is a summary of the steps needed for installation of the Trinix Routing Switcher System. Additional details may be found else­where in this manual as indicated.
1. Before unpacking the equipment, inspect the shipping carton for
evidence of freight damage. After unpacking carefully inspect all equipment for freight damage.
If the contents have been damaged, notify the carrier and Grass Valley (see page 4 for contact information). Retain all shipping cartons and padding material for inspection by the carrier.
Section 3
Do not return damaged merchandise to Grass Valley until an appro­priate claim has been filed with the carrier and a material return authorization number has been received from Grass Valley.
2. If the switcher is received without a rack, it should be mounted in a
19-inch wide frame or other suitable enclosure that provides power and cooling facilities for the equipment.
a. It may be necessary to install special rack spacers so that the
router's access door can be opened far enough to permit removal of components on the right side of the chassis (such as power supply modules). The spacers, which are available on request, should only be installed when the rack's mounting holes are recessed more than 0.6 inch (15.2 mm) from the front surface of the rack. For more information, see page 96.
b. Some switchers are supplied with PE-33016 Port Expanders,
which depending on the configuration can be used to provide dual outputs, quad outputs, input expansion, output expansion, and multi-chassis output monitoring. For illustrations of port expander applications, see page 43.
c. Power requirements are shown on page 79.
d. Environmental limits are shown on page 80.
Planning and Installation Manual 91
Installation
3. Power supplies are factory-installed and auto-sensing. No field
adjustment should be necessary.
Power supplies for 512 x 512 (DV-33512) switchers are mounted in a separate chassis and require cabling (supplied) from the “DC Output” connector of the power supply chassis to the “DC Input” connector of the switcher chassis. The 512 power supply chassis may be mounted above or below the main chassis, depending on video cable routing requirements (or weight distribution require­ments).
For additional power supply information, see page 104.
4. For 512 x 512 (DV-33512) switchers:
CAUTION In order to avoid damaging the switcher, power must be Off before
installing the “IFC” cables as described in the following step.
a. Install the “IFC” cables (supplied) between (1) the power
supply chassis and main chassis, and (2) between the main chassis center section and the fan module section.
For an illustration, see page 102.
5. If the system is supplied with PE-33016 Port Expanders, check the
input/output expansion DIP switches and jumpers for correct position.
These switches and jumpers are normally set at the factory based on the configuration shown in the sales order. For more information, see page 124.
6. On High Definition switchers:
a. Signal reclocking mode can be set for each output on an output
board. The factory default setting is “Auto,” meaning that properly-formed, standard data rate signals will be reclocked but other signals will be bypassed (not reclocked). See page 134 for details.
SD switchers do not include reclocking.
7. Make sure all cards are all seated in their backplane sockets.
This should not normally be an issue since the boards are held in place with locking extractors.
92 Planning and Installation Manual
8. Connect the desired input and output video cables.
To permit proper vertical interval switching, the inputs must be aligned within plus/minus 1/4 line with respect to the reference signal.
The use of 75 ohm BNC connectors (rather than 50 ohm) is recom­mended for HDTV applications.
If the system includes port expanders, all unused BNC connectors must be terminated with 75 ohm terminators.
On DV-33512 units, the output connectors are not arranged in a left­to-right sequence. The rear-panel labels are correct.
Note Labels for “0-based” numbering schemes are available. See page 40.
9. For “protected path” operation, the Broadlinx software can be
configured to monitor router outputs that are feeding critical downstream equipment (such as a transmitter). If the “primary” output signal is interrupted, the system will automatically select the “secondary” output that is carrying the same signal and trigger a system alarm. For wiring information, see page 60. For configuration instructions, see Section 5-Protected Path Configuration.
10. If the router is equipped with VI-33100 “universal” input boards,
and analog signals are received, an extensive set of gain, phase, filtering, and other adjustments are available for each signal. For more information about the VI-33100 module, please refer to
Section 6-Analog Input Processing.
11. Connect the appropriate house reference signal(s).
Depending on the system, up to four independent sync references can be used. For system diagrams, see page 107.
12. Re-configure the switch point if desired.
The switch point is factory-set to the recommended video line for the standard that is detected. A V-phasing feature, available with the NR-33000, SR-33000 with Rev B FPGA Software Update, and SR-33500 allows the user to adjust the switch point from -1 line to +2.5 lines if necessary. For more information, see page 117.
Note If you make adjustments on the SR-33500 as part of this step, you may
want to wait until all remaining steps in this list have been followed and any additional adjustments made before reinstalling the board.
13. Select the desired sync line on each Output board.
This applies to systems with more that one sync reference. Each output board provides a block of 32 outputs and by factory default each block is assigned to sync line 1, which corresponds to the “Pri-
Planning and Installation Manual 93
Installation
mary Ref IN 1” connector on the rear panel. If additional references are used, DIP switches are set to assign each board to one of four possible sync lines. See page 123.
14. If output monitoring is required, refer to the installation
instructions starting on page 137.
15. On multi-chassis systems, the Frame number switches should be
checked. See page 146.
16. Connect the switcher to the control system:
— For Jupiter control system connections and settings, see
page 148.
— For SMS 7000 or Encore control system connections and
settings, see page 153.
17. LAN and Com Bus connections and configuration of the Broadlinx
board (NR-33000 NIC/Sync/OPM board) are covered in the above discussions about control systems.
The Broadlinx board is equipped with a plug-in, rechargeable lithium-ion battery used to back up switcher status for Encore-con­trolled systems. The battery is rated for approximately 500 power cycles. If there is a power failure, and the battery fails to provide power, the Broadlinx board will need to obtain router status from the Encore System Control Module (data will be sent automati­cally). For the location of this battery, see page 119.
18. (Optional) Connect the rear panel ALARM BNC to the facility
alarm system. The alarm port operates according to SMPTE standard 269M-1999.
For an overview of the alarm system, see page 42.
The rear panel Alarm BNC can be configured to report primary alarms only or both primary and secondary alarms. The factory default setting is to report both. DV-33128/33256 configuration is via a jumper on the NR/SR-33000 board, as shown on page 119 and
page 120. DV-33512 configuration is via a jumper on the RP-33500
512 x 512 Rear Panel board as shown on page 122.
19. Power up the system by connecting the AC power cords. If the LED
on the front panel turns to green after the first few seconds of operation, the system is operating properly. If the LED continues to glow red, remove power and diagnose the problem before powering up the system again. For an explanation of LED alarm lights, see page 211.
CAUTION For DV-33512 switchers: In order to avoid damage, power must be Off
before removing/installing the “IFC” cables.
94 Planning and Installation Manual
Summary of Installation Procedure
20. Keep the front door closed as much as possible when the system is
running.
Note The front door should be closed during normal operation. Although the
Trinix switcher will function properly with the door open, leaving the chassis open on a consistent basis will result in shortened product life.
Planning and Installation Manual 95
Installation
INSTALL RACK SPACERS ONLY WHEN MOUNTING HOLES ARE RECESSED MORE THAN 0.6 INCH (15.2 MM) FROM FRONT SURFACE OF RACK (DIMENSION ). SPACERS WILL POSITION SWITCHER CHASSIS SO THAT ACCESS DOOR CAN BE OPENED FAR ENOUGH TO PERMIT REMOVAL OF RIGHT-HAND COMPONENTS. EACH SPACER IS SECURED WITH 2 RACK SCREWS (SUPPLIED).
DV-33256 CHASSIS
RACK SPACERS FOR
(KIT NO. 44-052990-001)
RACK SPACERS FOR DV-33128 CHASSIS (KIT NO. 44-052989-001)
DV-33512 CHASSIS/
RACK SPACERS FOR
POWER SUPPLY NOT SHOWN. (KIT NO. 650-4352-00)
Figure 39. Installation of rack spacers (when needed).
96 Planning and Installation Manual
Figure 40. DV-33128 front view (door removed).
SR-33000 Sync Reference / NR-33000 Broadlinx Board slots
Fan modules
FAN ALARM
FAN ALARM
Power supplies
Matrix board
Input/output boards (configuration varies)
Summary of Installation Procedure
Planning and Installation Manual 97
Installation
INPUT EXPAND OUTPUT EXPAND SYNC REDUNDANT INT XPT CNTL 60Hz ENABLE A B C
Figure 41. DV-33128 rear panel
MONITOR
1024
512
DV-33512 DV-33128
GPIO/TC
1536
2048
96
80
64
48
32
MONITOR
112
16
0
16
48 80
112
0
128
256
MONITOR
DV-33256 128 x 256
8
LEVEL
SUPER
32
64
12
96
384 512
12
14
10
FRAME
14
10
256
768
512
1024
0
2
15
1
13
3
4
5
11
79
6
8
0
2
15
1
13
3
4
5
11
9
7
6
8
96
80
64
48
32 ULTRA
MONITOR
LEVEL
SUPER
0
32
112
16
48
64
80
16
112
96
0
128
384
256
512
12
FRAME
12
0
2
14
15
1
13
3
4
5
11
79
10
6
8
0
2
14
15
1
13
3
4
5
11
7
9
10
6
IP EXPAND OP EXPAND VIT REDUNDANT INT XPT 60Hz ENABLE A B C
ALARM
WARNING: FOR CONTINUED PROTECTION
AGAINST RISK OF FIRE, REPLACE ONLY WITH SAME TYPE AND RATING OF FUSE
115: 6.0A 250V SLOW BLOW
230: T2.5A 240V
AUTO SELECT 100-130V/200-240V
6.0A/2.5A 47-63HZ
DC IN + DC IN -
PS B PS A
L
E
N
N
E
L
97-128
OUTPUTS
65-9633-64
OUTPUTS
1-32
OUTPUTS OUTPUTS
97-128
INPUTS
65-96
INPUTS
33-64
INPUTS
1-32
INPUTS
OUTPUT MONITOR
CONSOLE B
17
17
17
17
17
17
17
17
19
18
1
2
3
19
18
1
2
3
19
18
1
2
3
19
18
1
2
3
19
18
1
2
3
19
18
1
2
3
19
18
1
2
3
19
18
1
2
3
SECONDARY
LAN BCOM BUS
21
20
4
5
21
20
4
5
21
20
4
5
21
20
4
5
21
20
4
5
21
20
4
5
21
20
4
5
21
20
4
5
REF IN
434
CROSSPOINT BUS CONTROL
23
22
22
22
22
22
22
22
22
24
6
7
23
24
6
7
23
24
6
7
23
24
6
7
23
24
6
7
23
24
6
7
23
24
6
7
23
24
6
7
3
25
8
25
8
25
8
25
8
25
8
25
8
25
8
25
8
OUTPUT MONITOR
CONSOLE A
27
26
9
10
11
27
26
9
10
11
27
26
9
10
11
27
26
9
10
11
27
26
9
10
11
27
26
9
10
11
27
26
9
10
11
27
26
9
10
11
PRIMARY
12
COM BUS
28
29
12
13
28
29
12
13
28
29
12
13
28
29
12
13
28
29
12
13
28
29
12
13
28
29
12
13
28
29
12
13
REF IN
12
LAN A
CROSSPOINT BUS
31
30
30
30
30
30
30
30
30
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
31
32
14
15
16
Figure 42.
98 Planning and Installation Manual
OK
DC
VADJ
OK
AC DCOKAC
OK
VADJ
FAN ALARM
FAN ALARM
FAN ALARM
SR-33000 Sync Reference / NR-33000 Broadlinx Board slots
Fan modules Power supplies
Matrix boards
Input/output boards (configuration varies)
Figure 43. DV-33256 front view (door removed).
Summary of Installation Procedure
Planning and Installation Manual 99
Installation
See page 98 for detail
Figure 44. DV-33256 rear panel
PS B
PS B
L
E
N
INPUTS INPUTS
17
1
1
18
2
2
19
3
3
20
4
4
21
5
5
22
6
6
23
7
7
24
8
8
25
9
9
26
10
10
27
11
11
28
12
12
29
13
13
30
14
14
31
15
15
32
16
16
DC INPUT 42 - 54 VDC 30-24 AMPS
INPUTS
33-641-32
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
SECONDARY
NIC B
PRIMARY
NIC A
31
PS A
IN EXPAND OP EXPAND VIT REDUNDANT INT XPT CNTL 60Hz ENABLE A B C
96
64
32 ULTRA
MONITOR
OP MON
42
COM BUS
3
CONSOLE
B
REF
IN
4
LEVEL
0
SUPER
0
14
2
32
15
112
16
1
13
48
3
80
12
64
4
11
48
5
80
79
112
16
6
10
96
8
0
FRAME
128
0
14
384
2
256
15
1
13
512
3
12
4
5
11
79
6
10
8
CONTROL
GPIO/TC
OP MON
COM BUS
1
CONSOLE
REF
IN
2
CROSSPOINT BUS
A
DC IN -DC IN +
WARNING: FOR CONTINUED PROTECTION
PS A
N
E
L
INPUTSINPUTS
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
AGAINST RISK OF FIRE, REPLACE ONLY WITH SAME TYPE AND RATING OF FUSE 115: 12.5A 250V SLOW BLOW 230: T6.3A 240V
AUTO SELECT 100-130V/200-240V
10.0A/5.0A 47-63HZ
OUTPUTS OUTPUTS
OUTPUTS
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
OUTPUTS
OUTPUTS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
OUTPUTS OUTPUTSOUTPUTS
17
1
18
2
19
3
20
4
21
5
22
6
23
7
24
8
25
9
26
10
27
11
28
12
29
13
30
14
31
15
32
16
17
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
OUTPUTS
17
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
1
18
18
2
19
19
3
20
20
4
21
21
5
22
22
6
23
23
7
24
24
8
25
25
9
26
26
10
27
27
11
28
28
12
29
29
13
30
30
14
31
31
15
32
32
16
INPUTS 129-160
225-256193-224129-160 161-19265-9633-64 97-1281-3297-12865-96
17
1
1
18
2
2
19
3
3
20
4
4
21
5
5
22
6
6
23
7
7
24
8
8
25
9
9
26
10
10
27
11
11
28
12
12
29
13
13
30
14
14
31
15
15
32
16
16
INPUTS INPUTS
17
1
18
2
19
3
20
4
21
5
22
6
23
7
24
8
25
9
26
10
27
11
28
12
29
13
30
14
31
15
32
16
INPUTS
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
ALARM
INPUTS
193-224161-192 225-256
17
1
1
18
2
2
19
3
3
20
4
4
21
5
5
22
6
6
23
7
7
24
8
8
25
9
9
26
10
10
27
11
11
28
12
12
29
13
13
30
14
14
31
15
15
32
16
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
100 Planning and Installation Manual
Loading...