The following kit includes the Communications Gateway
Module (CGM) parts and software that are required for
Therm-O-Flow 20 or Therm-O-Flow 200 machines using
a CGM. This kit enables the Therm-O-Flow machines to
connect to a fieldbus device.
Part No.Description
25C994Thermo-O-Flow CGM Installation Kit
Kit 25C994 is used with the following CGM models,
each of which includes all of the remaining parts necessary to install the CGM. See Communications Gateway Module Instructions - Parts, manual 312864, for repair
The Communications Gateway Module (CGM) provides
a control link between the Therm-O-Flow (TOF) system
and a selected fieldbus. The control link provides the
means for remote monitoring and control by external
automation systems.
The data available to the fieldbus from the CGM
depends on the amount of channels installed on the
Therm-O-Flow system. A data map is available on a
token provided in this kit.
See Available Internal Data on page 9 for a list of internal data from the Therm-O-Flow system that can be
viewed or modified by the fieldbus device.
312864Communications Gateway Module
Instructions - Parts
334130Therm-O-Flow 200 Instructions - Parts
334129Therm-O-Flow 20 Instructions - Parts
406987GCA CAN Cables, Reference
23A5186B
NOTE: The following system network configuration files
are available at www.graco.com.
•EDS file: DeviceNet or Ethernet/IP fieldbus networks
Page 3
Installation
Recommended
Location for
Mounting Holes
3.25 in.
(82.6 mm)
2.75 in.
(69.9 mm)
#10-32 UNF
(M5 x 0.8)
CAN Cable Connectors
D
A
C
B
Installation
NOTE: Turn off the main power switch on the
Therm-O-Flow before starting. See the Therm-O-Flow
manuals referenced in Related Manuals on page 2 for
information about turning off the power.
To install the CGM, you will need to drill mounting holes
on the Therm-O-Flow below the electrical control panel
in a location where the CAN cables can be connected to
the CGM. See Figure 1 for the recommended location.
Mounting the CGM
1. Drill the mounting holes.
2. Remove the access cover from the CGM (D).
Loosen the two screws (C) and remove the CGM
(A) from the base (B).
FIG. 1: Mounting Location
The center of the CGM should be 4 inches from the bottom of the electrical control panel and 8 inches from
each side. Refer to the following mounting dimensions
when drilling the holes for the CGM.
NOTE: Mount the CGM with the CAN cable connectors
on the left side to make it easier to connect the cables.
FIG. 2: Removing the CGM Access Cover
3. With the CAN connectors on the left side, mount the
base (B) in the mounting holes using the four
screws supplied in this kit. See Parts on page 12.
4. Mount the CGM (A) on the base (B) with the two
screws (C) that were removed in step 2.
5. Reattach the access cover (D).
Connecting the CAN Cables
1. Disconnect the ADM’s CAN cable from the ADM
and from the splitter on the back of the
Therm-O-Flow’s electrical control panel.
2. Connect one end of the 1.5 m (4.9 ft) CAN cable
included in this kit to the ADM. Run the cable down
and through the opening underneath the electrical
control box as shown in Figure 3.
3A5186B3
Page 4
Installation
CAN Cable from ADM
CAN Cable
from Splitter
Opening Leading to CGM
CAN Connector 1
CAN Connector 2
Fieldbus Connection
3. Connect the CAN cable that you removed from the
ADM to the available splitter connection on the back
of the electrical control panel. Run that cable
through the same opening as the other CAN cable.
FIG. 3: CAN Cable Connection
4. Connect the two cables to the CGM connectors.
Either cable can be connected to either connector.
7. Connect the Ethernet, DeviceNet, or PROFIBUS
cable to the CGM as applicable. Connect the other
end of the cable to the fieldbus device.
FIG. 5: Connecting the Fieldbus
8. Perform the Install or Update Data Map procedure
in Communications Gateway Module Instructions - Parts, manual 312864.
9. See the Available Internal Data on page 9 for
details on the fieldbus pinout setup.
10. Perform Setup on page 5 to configure the fieldbus.
FIG. 4: CGM Connectors
5. Attach the two ferrite suppressors included in the kit
to the ends of the two cables closest to the CGM.
6. Use the adhesive cable tie included in the kit to
attach the CAN cables to the back of the control
box.
43A5186B
Page 5
Setup
Setup
NOTICE
To prevent damage to soft key buttons on the ADM, do
not press the buttons with sharp objects such as pens,
plastic cards, or fingernails.
Gateway Screens
Use the Gateway screens on the ADM to configure the
fieldbus. These screens are shown only if a CGM is correctly installed in your system. See Installation on page
3.
1. With the system on and enabled, press on the
ADM to access the Setup screens.
2. Use the ADM’s arrow keys to navigate to the main
Gateway screen.
EtherNet/IP Fieldbus Screens
Screen 2
Use the down arrow key on the ADM to navigate to
screen 2. This screen displays the hardware revision,
system serial number, and data map identification information.
DeviceNet Fieldbus Screen
NOTE: These screens are shown only if you have an
EtherNet/IP fieldbus CGM installed.
Screen 1
Press the key to access this screen. Use the arrow
keys to navigate to each field and the keypad to set the
IP address, DHCP settings, subnet mask, gateway, and
DNS information.
NOTE: This screen is shown only if you have a DeviceNet fieldbus CGM installed.
Press the key to access this screen. You can set
the device address and baud rate. You can also view
the hardware revision, system serial number, and data
map identification information.
3A5186B5
Page 6
Setup
PROFIBUS Fieldbus Screen
NOTE: These screens are shown only if you have a
PROFIBUS fieldbus CGM installed.
Screen 1
Press the key to access this screen. Use the arrow
keys to navigate to each field and the keypad to set the
device address, install date, location tag, function tag,
and description.
PROFINET Fieldbus Screens
NOTE: These screens are shown only if you have a
PROFINET fieldbus CGM installed.
Screen 1
Press the key to access this screen. Use the arrow
keys to navigate to each field and the keypad to set the
IP address, DHCP settings, subnet mask, gateway, and
DNS information.
Screen 2
Use the down arrow key on the ADM to navigate to
screen 2. This screen displays the hardware revision,
system serial number, and data map identification information.
Screen 2
Use the down arrow key on the ADM to navigate to
screen 2. Press the key to access this screen. You
can set the station name, install date, location tag, function tag, and description.
63A5186B
Page 7
Screen 3
Use the down arrow key on the ADM to navigate to
screen 3. This screen displays the hardware revision,
system serial number, and data map identification information.
Setup
3A5186B7
Page 8
Maintenance
Maintenance
Software Update Procedure
When software is updated on the ADM, the software is
then automatically updated on the CGM and all other
connected Graco Control Architecture components.
1. At the ADM, turn the power switch to Off.
2. Remove the ADM from the bracket.
3. Use a hex key to remove the token access panel.
6. The Graco Splash screen is displayed until communication with other modules is established.
7. Wait for the update to complete. An approximate
time to completion displays below the progress bar.
8. When the update is completed successfully, press
the key.
FIG. 6: Token Location
4. Insert and press the software upgrade token firmly
into the slot.
5. Turn the power switch to On.
NOTICE
A status is shown while software is updating to indicate progress. To prevent corrupting the software
load, do not remove the token until the status screen
disappears.
9. Remove the token and replace the token access
panel.
NOTE: The software version history for each system
can be viewed in the technical support section at
www.graco.com.
83A5186B
Page 9
Available Internal Data
Available Internal Data
See Appendix A - I/O Signal Descriptions on page 13 for additional details regarding each input/output. Unless
stated otherwise:
•Values are subject to the same maximum and minimum restrictions of the ADM.
•Some of the temperature data may have slight rounding errors compared to temperatures displayed on the ADM.
•On some controlling devices, the byte order may need to be reversed (byte order within instance, least significant
-> most significant.
Automation Inputs (Signals from the Therm-O-Flow to the PLC)
Instance
Number
10 -1Pump Actual Temperature, Primary°C/°F
22 - 3Platen Actual Temperature, Primary°C/°F
34 - 5Zone #1 Actual Temperature, Primary°C/°F
46 - 7Zone #2 Actual Temperature, Primary°C/°F
58 - 9Zone #3 Actual Temperature, Primary°C/°F
610 - 11Zone #4 Actual Temperature, Primary°C/°F
712 - 13Zone #5 Actual Temperature, Primary°C/°F
814 - 15Zone #6 Actual Temperature, Primary°C/°F
916 - 17Zone #7 Actual Temperature, Primary°C/°F
1018 - 19Zone #8 Actual Temperature, Primary°C/°F
1120 - 21Zone #9 Actual Temperature, Primary°C/°F
1222 - 23Zone #10 Actual Temperature, Primary°C/°F
1324 - 25Zone #11 Actual Temperature, Primary°C/°F
1426 - 27Zone #12 Actual Temperature, Primary°C/°F
1528 - 29 Pump Setpoint Temperature Indication, Primary/Secondary°C/°F
1630 - 31Platen Setpoint Temperature Indication, Primary/Secondary°C/°F
1732 - 33Zone #1 Setpoint Temperature Indication, Primary/Secondary°C/°F
1834 - 35Zone #2 Setpoint Temperature Indication, Primary/Secondary°C/°F
1936 - 37Zone #3 Setpoint Temperature Indication, Primary/Secondary°C/°F
2038 - 39Zone #4 Setpoint Temperature Indication, Primary/Secondary°C/°F
2140 - 41Zone #5 Setpoint Temperature Indication, Primary/Secondary°C/°F
2242 - 43Zone #6 Setpoint Temperature Indication, Primary/Secondary°C/°F
2344 - 45Zone #7 Setpoint Temperature Indication, Primary/Secondary°C/°F
2446 - 47Zone #8 Setpoint Temperature Indication, Primary/Secondary°C/°F
2548 - 49Zone #9 Setpoint Temperature Indication, Primary/Secondary°C/°F
2650 - 51Zone #10 Setpoint Temperature Indication, Primary/Secondary°C/°F
2752 - 53Zone #11 Setpoint Temperature Indication, Primary/Secondary°C/°F
2854 - 55Zone #12 Setpoint Temperature Indication, Primary/Secondary°C/°F
2956 - 57Pump, Platen, Zones 1 – 3 States, Primary
3058 - 59Zones 4 – 8 States, Primary
3160 - 61Zones 9 – 12 States, Primary
32*62 - 63Pump Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
33*64 - 65Platen Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
34*66 - 67Zone #1 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
35*68 - 69Zone #2 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
36*70 - 71Zone #3 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
37*72 - 73Zone #4 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
Input Byte
Index(es)
DescriptionUnits
3A5186B9
Page 10
Available Internal Data
Instance
Number
Input Byte
Index(es)
DescriptionUnits
38*74 - 75Zone #5 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
39*76 - 77Zone #6 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
40*78 - 79Zone #7 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
41*80 - 81Zone #8 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
42*82 - 83Zone #9 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
43*84 - 85Zone #10 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
44*86 - 87Zone #11 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
45*88 - 89Zone #12 Setback Setpoint Temperature Indication, Primary/Secondary°C/°F
46**90 - 91Pump Actual Temperature, Secondary °C/°F
47**92 - 93Platen Actual Temperature, Secondary°C/°F
48**94 - 95Zone #1 Actual Temperature, Secondary°C/°F
49**96 - 97Zone #2 Actual Temperature, Secondary°C/°F
50**98 - 99Zone #3 Actual Temperature, Secondary°C/°F
51**100 - 101Zone #4 Actual Temperature, Secondary°C/°F
52**102 - 103Zone #5 Actual Temperature, Secondary°C/°F
53**104 - 105Zone #6 Actual Temperature, Secondary°C/°F
54**106 - 107Zone #7 Actual Temperature, Secondary°C/°F
55**108 - 109Zone #8 Actual Temperature, Secondary°C/°F
56**110 - 111Zone #9 Actual Temperature, Secondary°C/°F
57**112 - 113Zone #10 Actual Temperature, Secondary°C/°F
58**114 - 115Zone #11 Actual Temperature, Secondary°C/°F
59**116 - 117Zone #12 Actual Temperature, Secondary°C/°F
60**118 - 119Pump, Platen, Zones 1 – 3 States, Secondary
61**120 - 121Zones 4 – 8 States, Secondary
62**122 - 123Zones 9 – 12 States, Secondary
63**124 - 127Error / Event Code(s) Present†
64**128 - 131Error / Event Code(s) Needing Acknowledged†
65**132 - 133Status Word 1 Indication Bits
66**134 - 135Status Word 2 Indication Bits
67**136 - 137Data Exchange Interface Pointer Last Serviced
68**138 - 141Data Exchange Interface Input Value
69**142System Mode/State, Primary‡
70**143System Mode/State, Secondary‡
*Data instances (setback mode setpoint temperatures) are NOT provided for the PROFIBUS and PROFINET versions of the map since the
field protocols do not support that large of a map size. For PROFIBUS or PROFINET, you should use the data exchange interface to obtain
setback setpoint information.
** For the PROFIBUS or PROFINET versions of the map, 14 should be subtracted from the instance number and 28 should be subtracted for the
input byte count so that the PROFIBUS and PROFINET versions have 56 input instances containing 116 input bytes total.
Zone states are packed in groups of three bits, where each zone state equates to the following. Each zone is packed from bit 0, bit 3, bit 6, bit
9, and bit 12 corresponding to the order presented in the description. 000 - zone is not installed, 001 - zone is off, 010 - zone is in warm up
state, 011 - zone is in heat soak state, 100 - zone at temperature, 101 - zone in setback mode.
Temperature units match units of the ADM. Values are in tenths of a degree (for example, a value of 4005 corresponds to 400.5 °F). Setpoint
temperatures are either for the primary or secondary unit, depending on the system selected by the PLC in the System Control Word.
† See Appendix C - Error/Event Tables on page 22.
See the Status Indication Bit Tables on page 13.
See Appendix B - Data Exchange Interface on page 17.
NOTE: The CGM is not included in the kit. See Models on page 2 for available CGM modules.
123A5186B
Page 13
Appendix A - I/O Signal Descriptions
Appendix A - I/O Signal Descriptions
This section provides details about the CGM automation input and output signals.
Heat Zone States
The signal is 0 on power up. The following values of this signal correspond to the various heat zone states. Each
zone is bit packed into 3 bits for each zone designation in input instances 29-31 and 60-62 of the map.
NumberBinary #Heat Zone State
0000Zone Not Installed
1001OFF
2010Warm Up
3011Heat Soak State
4100At Temperature
5101Setback Mode
Status Indication Bit Tables
The following tables reflect bit-packed data, which corresponds to the status words located at input instances 65 and
66.
Status Word 1 Indication Bits
Bit
Number
00x00010000 0000 0000 0001System is ON
10x00020000 0000 0000 0010Active System is Secondary (B) System
20x00040000 0000 0000 0100Heat is Turned ON for Primary (A) System
30x00080000 0000 0000 1000Heat is Turned ON for Secondary (B) System
40x00100000 0000 0001 0000Setpoint Indications are for Secondary (B) System
50x00200000 0000 0010 0000Setback Setpoint Indications are for Secondary (B) System
60x00400000 0000 0100 0000Material Tracking is ON or Active
70x00800000 0000 1000 0000Pump Priming is Active for Primary (A) System
80x01000000 0001 0000 0000Pump Priming is Active for Secondary (B) System
90x02000000 0010 0000 0000Pump is ON for Primary (A) System
100x04000000 0100 0000 0000Pump is ON for Secondary (B) System
110x08000000 1000 0000 0000Setback Mode is Active for Primary (A) System
120x10000001 0000 0000 0000Setback Mode is Active for Secondary (B) System
130x20000010 0000 0000 0000Data Exchange Interface is Active or in Transition
14-15------------Reserved for Future Use
Hex
Equivalent
Binary NumberDescription
3A5186B13
Page 14
Appendix A - I/O Signal Descriptions
Status Word 2 Indication Bits
Bit
Number
Hex
Equivalent
Binary NumberDescription
00x00010000 0000 0000 0001Heat Soak Timer Active for Primary (A) System
10x00020000 0000 0000 0010Heat Soak Timer Active for Secondary (B) System
20x00040000 0000 0000 0100Turn ON Primary System (A), Heat Command Active
30x00080000 0000 0000 1000Turn ON Secondary System (B), Heat Command Active
40x00100000 0000 0001 0000Prime/Pump on A Command Active
50x00200000 0000 0010 0000Prime/Pump on B Command Active
60x00400000 0000 0100 0000Setback A Command Active
70x00800000 0000 1000 0000Setback B Command Active
80x01000000 0001 0000 0000Cross Over Command Active
90x02000000 0010 0000 0000PLC Control Active Indication
100x04000000 0100 0000 0000
Heart Beat Indication for PLC from TOF (
Control Bits
)
See Note 7 in System
110x08000000 1000 0000 0000Error/Event Reported is an Alarm
12-15------------Reserved for Future Use
System Control Bits
The following table reflects the bit variables in output instance 4, which can be set or cleared to control the following
conditions.
Bit
Number
Hex
Equivalent
Binary NumberDescriptionNotes
00x00010000 0000 0000 0001 Turn ON Heat Command for System A Command1
10x00020000 0000 0000 0010 Turn ON Head Command for System B Command1
20x00040000 0000 0000 0100 Turn ON/Prime Pumps for System A Command2
30x00080000 0000 0000 1000 Turn ON/Prime Pumps for System B Command2
40x00100000 0000 0001 0000 Setback Command System A3
50x00200000 0000 0010 0000 Setback Command System B3
60x00400000 0000 0100 0000 Cross Over Command4
70x00800000 0000 1000 0000 Pause Material Tracking/Counters Command5
80x01000000 0001 0000 0000 Continue Material Tracking Command5
90x02000000 0010 0000 0000 Command Setpoint Indications on Map for System B6
100x04000000 0100 0000 0000 Command Setback Setpoint Indications for System B6
110x08000000 1000 0000 0000 Heart Beat Output to TOF7
120x10000001 0000 0000 0000 PLC Control Command8
13-15------------Reserved for Future Use
1 Same as pressing on the main Run screen.
2 Same as pressing on the main Run screen.
3 Same as pressing on the main Run screen.
4 Same as pressing on the main Run screen.
5 Same as pressing or on the main Run screen.
143A5186B
Page 15
Appendix A - I/O Signal Descriptions
6 After changing the state of the command XX setpoint indications on the map for the Secondary B system bit, the controlling PLC logic should
monitor the corresponding status indication bit and verify it corresponds to the command bit before monitoring the corresponding setpoint indication from the Therm-O-Flow.
7 The PLC or controlling logic needs to generate a dynamic signal at approximately a 0.333 Hz (1.5 seconds high, 1.5 seconds low) oscillation
rate. The signal is present to enable detection of a communication failure between the Therm-O-Flow system and the controlling logic. The
TOF system also generates the same rate dynamic signal indication (heart beat indication for PLC from TOF) signal for controlling logic to the
monitor.
8 The PLC Control Command bit needs to be set, and the controlling logic needs to generate a valid heart beat output (described in note 7) to
the Therm-O-Flo system before the TOF will grant the PLC requests or commands. If the heart beat output to TOF becomes a static signal
(always low or high) after an extended period of time while the TOF is in PLC control, the TOF reverts to a safe state, and generates a corre-
sponding alarm. This situation would be similar to an operator pressing the key
3A5186B15
Page 16
Appendix A - I/O Signal Descriptions
Temperature Setpoint Zone Designation Table
The following table shows the setpoint designations in
output instance 2 used to command the Therm-O-Flow
temperature zones to the corresponding setpoint. Prior
to writing to instance 2, the PLC needs to write the
desired temperature setpoint (in tenths of a degree for
the selected temperature unit of measure) to output
instance 3 for the selected zone. After the zone designation has been written, the PLC can monitor the setpoint change by monitoring the correct setpoint
The Data Exchange Interface is a bi-directional interface
that enables both transmitting and receiving data
between the Therm-O-Flow system and the controlling
logic (PLC). The interface allows a large amount of data
to exchange between the systems while only occupying
a very small data map to support the exchange. The
interface also allows for future expansion of data without
changing the map structure.
To get or receive data from the supply system, the controlling PLC needs to:
1. Write to the Data Exchange Interface Pointer Output
Designation location on the map (output instance 6)
a value corresponding to the data the PLC wants to
receive.
2. Wait for the Therm-O-Flow to provide the same
Pointer Designation number written in the previous
step at input instance 67 (Data Exchange Interface
Pointer Last Serviced).
3. Read the requested data at input instance 68, Data
Exchange Interface Input Value.
After valid data is present at the input instances, the
Therm-O-Flow system clears the bit. While the bit is set,
the controlling PLC should ignore the interface inputs
until the bit is cleared. After the Therm-O-Flow system
services the request, the designation pointer input
matches the designation pointer output. If the scan rate
of the controlling PLC or control logic is slow enough,
monitoring of the status bit may not be necessary.
NOTE: When changes are made over the Data
Exchange Interface, the Therm-O-Flow system display
screen may not update immediately. It may be necessary to navigate away from the screen, then back to it.
To write or transmit data to the supply system, the controlling PLC needs to:
1. Write the data for the Therm-O-Flow system to the
Data Exchange Interface Output Value location, output instance 7.
2. Write to the Data Exchange Interface Pointer Output
Designation location on the map (output instance 6)
a value corresponding to the data the PLC is going
to transmit to the supply system.
3. The Therm-O-Flow system echoes back to the PLC
the Pointer Designation and the Data Interface
Value after the Therm-O-Flow system processes
the data transmit request to input instances 67 and
68 respectively.
When the controlling logic is exchanging data over this
interface, the Therm-O-Flow system sets the Data
Exchange Interface Active or in Transition status bit
while it processes the request and writes to the Data
Exchange Interface input locations (input instances 67
and 68).
3A5186B17
Page 18
Appendix B - Data Exchange Interface
Data Exchange Interface Pointer Designation Tabl
DescriptionComments
Pointer
Designation
0Interface Not Active
1Set Temperature Units
2Read Temperature UnitsWrite
3Set Mass Units
4Read Mass UnitsRead
5Set Specific Gravity
6Read Specific GravityRead
7Set High Temp. Alarm Offset
8Get High Temp. Alarm OffsetRead
9Set High Temp. Deviation OffsetWrite
10Get High Temp. Deviation OffsetRead
11Set Low Temp. Alarm OffsetWrite
Value - Setting
0 - °F
1 - °C
Value - Setting (0 - g, 1 - kg, 2 - lb)
Specific gravity in thousandths (for instance a SG setting of
1.055 = 1055).
In whole selected C or F units of measure.
Read/
Write
Read
Write
Write
Write
12Get Low Temp. Alarm OffsetRead
13Set Low Temp. Deviation OffsetWrite
14Get Low Temp. Deviation OffsetRead
15Set Prime Pump Duration
16Get Prime Pump DurationRead
17Read System Version
18Read System Date
19Read System Time
20Read ADM Version
21 - 90 Reserved for Future Use
Prime pump duration setting in second increments
A 32-bit string in the format of 0xXXCCBBAA.
0xCC…Build Version
0xBB…Minor Version
0xAA…Major Version
A 32-bit string in the format of 0xXXDDCCBB.
0xDD…Year (0x0D corresponds to 2013)
0xCC…Month (0x0A corresponds to October)
0xBB…Day
A 32-bit string in the format of 0xDDHHMMSS.
0xHH…Hours
0xMM…Minutes
0xSS…Seconds
0xDD...Day of week (0x01 corresponds to Monday)
A 32-bit string in the format of 0xXXMMNNBB
0xMM...Major #
0xNN...Minor #
0xBB...Build #
Write
Read
Read
Read
183A5186B
Page 19
Appendix B - Data Exchange Interface
DescriptionComments
Read/
Write
Pointer
Designation
Read Pump A Resettable Mate-
91
rial counter
Read Pump B Resettable Mate-
92
rial counter
Reset Pump A Resettable mate-
93
rial counter
Reset Pump B Resettable mate-
94
rial counter
Read Pump A Resettable Cycle
95
counter
Read Pump B Resettable Cycle
96
counter
Reset Pump A Resettable Cycle
97
counter
Reset Pump B Resettable Cycle
98
counter
99-100
Reserved for Future Use
101Get Heat Soak Timer A
102
Get Heat Soak Timer BRead
103 -
Reserved for Future Use
110
In selected mass units, times 10. So, for instance, if in Kg mode,
101 = 10.1 Kg.
No Data required for Data Exchange Interface Output Value
location (Same as pressing on the corresponding setup or
run screen).
In whole pump cycle units of measure.
No Data required for Data Exchange Interface Output Value
location (Same as pressing on the corresponding setup or
run screen).
Get Primary or Secondary Heat Soak timer Remaining Count in
Seconds (= 0 if not active)
Write
Write
Write
Write
Read
111Get CV Percent (5051 = 50.51%) Get Control Variable for Pump, Primary Heat ZoneRead
112
Get CV Percent (5051 = 50.51%) Get Control Variable for Platen, Primary Heat ZoneRead
113
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 1, PrimaryRead
114
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 2, PrimaryRead
115
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 3, PrimaryRead
116
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 4, PrimaryRead
117
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 5, PrimaryRead
118
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 6, PrimaryRead
119
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 7, PrimaryRead
120
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 8, PrimaryRead
121
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 9, PrimaryRead
122
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 10, PrimaryRead
123
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 11, PrimaryRead
124
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 12, PrimaryRead
read
read
read
read
3A5186B19
Page 20
Appendix B - Data Exchange Interface
Pointer
Designation
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139 -
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
DescriptionComments
Read/
Write
Get CV Percent (5051 = 50.51%) Get Control Variable for Pump, Secondary Heat ZoneRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Platen, Secondary Heat ZoneRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 1, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 2, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 3, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 4, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 5, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 6, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 7, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 8, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 9, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 10, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 11, SecondaryRead
Get CV Percent (5051 = 50.51%) Get Control Variable for Heat Zone 12, SecondaryRead
Reserved for Future Use
Get Pump A Setback Setpoint
Temperature
Get Platen A Setback Setpoint
Temperature
Get Zone 1, A Setback Setpoint
Temperature
Get Zone 2, A Setback Setpoint
Temperature
Get Zone 3, A Setback Setpoint
Temperature
Get Zone 4, A Setback Setpoint
Temperature
Get Zone 5, A Setback Setpoint
Temperature
Get Zone 6, A Setback Setpoint
Temperature
Get Zone 7, A Setback Setpoint
Temperature
Get Zone 8, A Setback Setpoint
Temperature
Get Zone 9, A Setback Setpoint
Temperature
Get Zone 10, A Setback Setpoint
Temperature
Get Zone 11, A Setback Setpoint
Temperature
Get Zone 12, A Setback Setpoint
Temperature
Provides the selected Primary System Zone Setback Mode setpoint temperature setting to the interface. Temperature Units
match units of the ADM. Values are in tenths of a degree (for
example, a value of 2505 corresponds to 250.5°F). These
pointer designations are typically used for PROFIBUS and
PROFINET applications.
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
203A5186B
Page 21
Appendix B - Data Exchange Interface
Pointer
Designation
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179 ~65k
DescriptionComments
Get Pump B Setback Setpoint
Temperature
Get Platen B Setback Setpoint
Temperature
Get Zone 1, B Sec. Setback Setpoint Temperature
Get Zone 2, B Setback Setpoint
Temperature
Get Zone 3, B Setback Setpoint
Temperature
Get Zone 4, B Setback Setpoint
Temperature
Get Zone 5, B Setback Setpoint
Temperature
Get Zone 6, B Setback Setpoint
Temperature
Get Zone 7, B Setback Setpoint
Temperature
Get Zone 8, B Setback Setpoint
Temperature
Get Zone 9, B Setback Setpoint
Temperature
Get Zone 10, B Setback Setpoint Temperature
Get Zone 11, B Setback Setpoint Temperature
Get Zone 12, B Setback Setpoint Temperature
Reserved for Future Use
Provides the selected Secondary System Zone Setback Mode
setpoint temperature setting to the interface. Temperature Units
match units of the ADM. Values are in tenths of a degree (for
example, a value of 2505 corresponds to 250.5°F). These
pointer designations are typically used for PROFIBUS and
PROFINET applications.
Read/
Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
3A5186B21
Page 22
Appendix C - Error/Event Tables
Appendix C - Error/Event Tables
The following table reflects codes provided in input
instances 63 and 64 and output instance 5. To acknowledge an error, when the PLC notices a non-zero error
code in instance 64, the PLC logic needs to write the
same code to output instance 5 to remove the error
message pop-up window from the ADM display. After
the event or error is acknowledged by the PLC, the
pop-up window disappears and the error code is cleared
from instance 64. If the condition is no longer present,
the error code is removed from instance 63. If multiple
conditions exist, the process may need to be repeated
for each condition.
The error codes described and presented on input 63
and 64 are the four digit codes presented below in
ASCCI format packed into a 32-bit double word. Each
character of the code occupies a byte within the 32-bit
double word, read right to left.
Error/Event
Code
0
A1A1
A1A2
A1A3
A1A4
A1A5
A1A6
A1A7
A1A8
A1A9
A1AA
A1AB
A1AC
A1AD
A1AE
A1B1
A1B2
A1B3
A1B4
A1B5
A1B6
A1B7
A1B8
A1B9
No Active Error
Low Current Unit A Zone 1
Low Current Unit A Zone 2
Low Current Unit A Zone 3
Low Current Unit A Zone 4
Low Current Unit A Zone 5
Low Current Unit A Zone 6
Low Current Unit A Zone 7
Low Current Unit A Zone 8
Low Current Unit A Zone 9
Low Current Unit A Zone 10
Low Current Unit A Zone 11
Low Current Unit A Zone 12
Low Current Unit A Pump
Low Current Unit A Platen
Low Current Unit B Zone 1
Low Current Unit B Zone 2
Low Current Unit B Zone 3
Low Current Unit B Zone 4
Low Current Unit B Zone 5
Low Current Unit B Zone 6
Low Current Unit B Zone 7
Low Current Unit B Zone 8
Low Current Unit B Zone 9
Description
A1BA
A1BB
A1BC
A1BD
A1BE
A1C1
A1C2
A1C3
A1C4
A1C5
A1C6
A1C7
A1CG
A1CV
A1CW
A1CX
A1CY
A2A1
A2A2
A2A3
A2A4
A2A5
A2A6
A2A7
A2A8
A2A9
A2AA
A2AB
A2AC
A2AD
A2AE
A2B1
A2B2
A2B3
A2B4
A2B5
A2B6
A2B7
A2B8
A2B9
A2BA
Low Current Unit B Zone 10
Low Current Unit B Zone 11
Low Current Unit B Zone 12
Low Current Unit B Pump
Low Current Unit B Platen
Low Current Fan MZLP 1
Low Current Fan MZLP 2
Low Current Fan MZLP 3
Low Current Fan MZLP 4
Low Current Fan MZLP 5
Low Current Fan MZLP 6
Low Current Fan MZLP 7
Low Current Fan Gateway
Low Current Fan AWB, Unit A
Low Current Fan AWB, Unit B
Low Current Fan System I/O, Unit A
Low Current Fan System I/O, Unit B
Low Current Unit A Zone 1
Low Current Unit A Zone 2
Low Current Unit A Zone 3
Low Current Unit A Zone 4
Low Current Unit A Zone 5
Low Current Unit A Zone 6
Low Current Unit A Zone 7
Low Current Unit A Zone 8
Low Current Unit A Zone 9
Low Current Unit A Zone 10
Low Current Unit A Zone 11
Low Current Unit A Zone 12
Low Current Unit A Pump
Low Current Unit A Platen
Low Current Unit B Zone 1
Low Current Unit B Zone 2
Low Current Unit B Zone 3
Low Current Unit B Zone 4
Low Current Unit B Zone 5
Low Current Unit B Zone 6
Low Current Unit B Zone 7
Low Current Unit B Zone 8
Low Current Unit B Zone 9
Low Current Unit B Zone 10
223A5186B
Page 23
Appendix C - Error/Event Tables
Error/Event
Code
A2BB
A2BC
A2BD
A2BE
Low Current Unit B Zone 11
Low Current Unit B Zone 12
Low Current Unit B Pump
Low Current Unit B Platen
Description
A2C1Low Current Fan MZLP 1
A2C2Low Current Fan MZLP 2
A2C3Low Current Fan MZLP 3
A2C4Low Current Fan MZLP 4
A2C5Low Current Fan MZLP 5
A2C6Low Current Fan MZLP 6
A2C7Low Current Fan MZLP 7
A2CGLow Current Fan Gateway
A2CVLow Current Fan AWB, Unit A
A2CWLow Current Fan AWB, Unit B
A2CXLow Current Fan System I/O, Unit A
A2CYLow Current Fan System I/O, Unit B
A3A1High Current Unit A Zone 1
A3A2High Current Unit A Zone 2
A3A3High Current Unit A Zone 3
A3A4High Current Unit A Zone 4
A3A5High Current Unit A Zone 5
A3A6High Current Unit A Zone 6
A3A7High Current Unit A Zone 7
A3A8High Current Unit A Zone 8
A3A9High Current Unit A Zone 9
A3AAHigh Current Unit A Zone 10
A3ABHigh Current Unit A Zone 11
A3ACHigh Current Unit A Zone 12
A3ADHigh Current Unit A Pump
A3AEHigh Current Unit A Platen
A3B1High Current Unit B Zone 1
A3B2High Current Unit B Zone 2
A3B3High Current Unit B Zone 3
A3B4High Current Unit B Zone 4
A3B5High Current Unit B Zone 5
A3B6High Current Unit B Zone 6
A3B7High Current Unit B Zone 7
A3B8High Current Unit B Zone 8
A3B9High Current Unit B Zone 9
A3BAHigh Current Unit B Zone 10
A3BBHigh Current Unit B Zone 11
A3BCHigh Current Unit B Zone 12
A3BDHigh Current Unit B Pump
A3BEHigh Current Unit B Platen
A3C1High Current Fan MZLP 1
A3C2High Current Fan MZLP 2
A3C3High Current Fan MZLP 3
A3C4High Current Fan MZLP 4
A3C5High Current Fan MZLP 5
A3C6High Current Fan MZLP 6
A3C7High Current Fan MZLP 7
A3CGHigh Current Fan Gateway
A3CVHigh Current Fan AWB, Unit A
A3CWHigh Current Fan AWB, Unit B
A3CXHigh Current Fan System I/O, Unit A
A3CYHigh Current Fan System I/O, Unit B
A4A1High Current Unit A Zone 1
A4A2High Current Unit A Zone 2
A4A3High Current Unit A Zone 3
A4A4High Current Unit A Zone 4
A4A5High Current Unit A Zone 5
A4A6High Current Unit A Zone 6
A4A7High Current Unit A Zone 7
A4A8High Current Unit A Zone 8
A4A9High Current Unit A Zone 9
A4AAHigh Current Unit A Zone 10
A4ABHigh Current Unit A Zone 11
A4ACHigh Current Unit A Zone 12
A4ADHigh Current Unit A Pump
A4AEHigh Current Unit A Platen
A4B1High Current Unit B Zone 1
A4B2High Current Unit B Zone 2
A4B3High Current Unit B Zone 3
A4B4High Current Unit B Zone 4
A4B5High Current Unit B Zone 5
A4B6High Current Unit B Zone 6
A4B7High Current Unit B Zone 7
A4B8High Current Unit B Zone 8
A4B9High Current Unit B Zone 9
A4BAHigh Current Unit B Zone 10
A4BBHigh Current Unit B Zone 11
A4BCHigh Current Unit B Zone 12
A4BDHigh Current Unit B Pump
A4BEHigh Current Unit B Platen
3A5186B23
Page 24
Appendix C - Error/Event Tables
Error/Event
Code
Description
A4C1High Current Fan MZLP 1
A4C2High Current Fan MZLP 2
A4C3High Current Fan MZLP 3
A4C4High Current Fan MZLP 4
A4C5
A4C6
High Current Fan MZLP 5
High Current Fan MZLP 6
A4C7High Current Fan MZLP 7
A4CGHigh Current Fan Gateway
A4CVHigh Current Fan AWB, Unit A
A4CWHigh Current Fan AWB, Unit B
A4CXHigh Current Fan System I/O, Unit A
A4CYHigh Current Fan System I/O, Unit B
A7A1Unexp. Curr. Unit A Zone 1
A7A2Unexp. Curr. Unit A Zone 2
A7A3Unexp. Curr. Unit A Zone 3
A7A4Unexp. Curr. Unit A Zone 4
A7A5Unexp. Curr. Unit A Zone 5
A7A6Unexp. Curr. Unit A Zone 6
A7A7Unexp. Curr. Unit A Zone 7
A7A8Unexp. Curr. Unit A Zone 8
A7A9Unexp. Curr. Unit A Zone 9
A7AAUnexp. Curr. Unit A Zone 10
A7ABUnexp. Curr. Unit A Zone 11
A7ACUnexp. Curr. Unit A Zone 12
A7ADUnexp. Curr. Unit A Pump
A7AEUnexp. Curr. Unit A Platen
A7B1Unexp. Curr. Unit B Zone 1
A7B2Unexp. Curr. Unit B Zone 2
A7B3Unexp. Curr. Unit B Zone 3
A7B4Unexp. Curr. Unit B Zone 4
A7B5Unexp. Curr. Unit B Zone 5
A7B6Unexp. Curr. Unit B Zone 6
A7B7Unexp. Curr. Unit B Zone 7
A7B8Unexp. Curr. Unit B Zone 8
A7B9Unexp. Curr. Unit B Zone 9
A7BAUnexp. Curr. Unit B Zone 10
A7BBUnexp. Curr. Unit B Zone 11
A7BCUnexp. Curr. Unit B Zone 12
A7BDUnexp. Curr. Unit B Pump
A7BEUnexp. Curr. Unit B Platen
A7C1Unexp. Curr. Fan MZLP 1
A7C2Unexp. Curr. Fan MZLP 2
A7C3Unexp. Curr. Fan MZLP 3
A7C4Unexp. Curr. Fan MZLP 4
A7C5Unexp. Curr. Fan MZLP 5
A7C6Unexp. Curr. Fan MZLP 6
A7C7Unexp. Curr. Fan MZLP 7
A7CGUnexp. Curr. Fan Gateway
A7CVUnexp. Curr. Fan AWB, Unit A
A7CWUnexp. Curr. Fan AWB, Unit B
A7CXUnexp. Curr. Fan System I/O, Unit A
A7CYUnexp. Curr. Fan System I/O, Unit B
A8A1No Current Unit A Zone 1
A8A2No Current Unit A Zone 2
A8A3No Current Unit A Zone 3
A8A4No Current Unit A Zone 4
A8A5No Current Unit A Zone 5
A8A6No Current Unit A Zone 6
A8A7No Current Unit A Zone 7
A8A8No Current Unit A Zone 8
A8A9No Current Unit A Zone 9
A8AANo Current Unit A Zone 10
A8ABNo Current Unit A Zone 11
A8ACNo Current Unit A Zone 12
A8ADNo Current Unit A Pump
A8AENo Current Unit A Platen
A8B1No Current Unit B Zone 1
A8B2No Current Unit B Zone 2
A8B3No Current Unit B Zone 3
A8B4No Current Unit B Zone 4
A8B5No Current Unit B Zone 5
A8B6No Current Unit B Zone 6
A8B7No Current Unit B Zone 7
A8B8No Current Unit B Zone 8
A8B9No Current Unit B Zone 9
A8BANo Current Unit B Zone 10
A8BBNo Current Unit B Zone 11
A8BCNo Current Unit B Zone 12
A8BDNo Current Unit B Pump
A8BENo Current Unit B Platen
A8C1No Current Fan MZLP 1
A8C2No Current Fan MZLP 2
A8C3No Current Fan MZLP 3
A8C4No Current Fan MZLP 4
243A5186B
Page 25
Appendix C - Error/Event Tables
Error/Event
Code
Description
A8C5No Current Fan MZLP 5
A8C6No Current Fan MZLP 6
A8C7No Current Fan MZLP 7
A8CGNo Current Fan Gateway
A8CVNo Current Fan AWB, Unit A
A8CWNo Current Fan AWB, Unit B
A8CXNo Current Fan System I/O, Unit A
A8CYNo Current Fan System I/O, Unit B
AAMANo Current Fan Unit A
AAMBNo Current Fan Unit B
AM31High Current SSR MZLP 1
AM32High Current SSR MZLP 2
AM33High Current SSR MZLP 3
AM34High Current SSR MZLP 4
AM35High Current SSR MZLP 5
AM36High Current SSR MZLP 6
AM37High Current SSR MZLP 7
AM3GHigh Current SSR Gateway
AM3VHigh Current SSR AWB, Unit A
AM3WHigh Current SSR AWB, Unit B
AM3XHigh Current SSR System I/O, Unit A
AM3YHigh Current SSR System I/O, Unit B
AM41High Current Contactor MZLP 1
AM42High Current Contactor MZLP 2
AM43High Current Contactor MZLP 3
AM44High Current Contactor MZLP 4
AM45High Current Contactor MZLP 5
AM46High Current Contactor MZLP 6
AM47High Current Contactor MZLP 7
AM4GHigh Current Contactor Gateway
AM4VHigh Current Contactor AWB, Unit A
AM4WHigh Current Contactor AWB, Unit B
AM4X
AM4Y
High Current Contactor System I/O, Unit
A
High Current Contactor System I/O, Unit
B
AM71Unexp. Curr. Contactor MZLP 1
AM72Unexp. Curr. Contactor MZLP 2
AM73Unexp. Curr. Contactor MZLP 3
AM74Unexp. Curr. Contactor MZLP 4
AM75Unexp. Curr. Contactor MZLP 5
AM76Unexp. Curr. Contactor MZLP 6
AM77Unexp. Curr. Contactor MZLP 7
AM7GUnexp. Curr. Contactor Gateway
AM7VUnexp. Curr. Contactor AWB, Unit A
AM7WUnexp. Curr. Contactor AWB, Unit B
AM7X
AM7Y
Unexp. Curr. Contactor System I/O, Unit
A
Unexp. Curr. Contactor System I/O, Unit
B
AM81No Current Contactor MZLP 1
AM82No Current Contactor MZLP 2
AM83No Current Contactor MZLP 3
AM84No Current Contactor MZLP 4
AM85No Current Contactor MZLP 5
AM86No Current Contactor MZLP 6
AM87No Current Contactor MZLP 7
AM8GNo Current Contactor Gateway
AM8VNo Current Contactor AWB, Unit A
AM8WNo Current Contactor AWB, Unit B
AM8XNo Current Contactor System I/O, Unit A
AM8YNo Current Contactor System I/O, Unit B
CAC1Comm. Error MZLP 1
CAC2Comm. Error MZLP 2
CAC3Comm. Error MZLP 3
CAC4Comm. Error MZLP 4
CAC5Comm. Error MZLP 5
CAC6Comm. Error MZLP 6
CAC7Comm. Error MZLP 7
CACGComm. Error Gateway
CACHGateway Heart Beat Lost
CACVComm. Error AWB, Unit A
CACWComm. Error AWB, Unit B
CACXComm. Error System I/O, Unit A
CACYComm. Error System I/O, Unit B
DAAXPump Runaway Unit A
DABXPump Runaway Unit B
DCAXPump Diving Unit A
DCBXPump Diving Unit B
DEAXCycle Switch Err. Unit A
DEBXCycle Switch Err. Unit B
EAAAHeat On Unit A
EAABHeat On Unit B
EACAMat. Counter Paused Unit A
EACBMat. Counter Paused Unit B
EAPAPump On Unit A
3A5186B25
Page 26
Appendix C - Error/Event Tables
Error/Event
Code
Description
EAPBPump On Unit B
EAUXUSB Activity In Process
EB0XStop Button Pressed
EBAAHeat Off Unit A
EBABHeat Off Unit B
EBCAMat. Counter Unpaused Unit A
EBCBMat. Counter Unpaused Unit B
EBPAPump Off Unit A
EBPBPump Off Unit B
EBUXUSB Drive Removed
EBRXRed Key locked out PLC
EC0XSetup Value(s) Changed
ECA1Unit A Zone 1
ECA2Unit A Zone 2
ECA3Unit A Zone 3
ECA4Unit A Zone 4
ECA5Unit A Zone 5
ECA6Unit A Zone 6
ECA7Unit A Zone 7
ECA8Unit A Zone 8
ECA9Unit A Zone 9
ECAAUnit A Zone 10
ECABUnit A Zone 11
ECACUnit A Zone 12
ECADUnit A Pump
ECAEUnit A Platen
ECB1Unit B Zone 1
ECB2Unit B Zone 2
ECB3Unit B Zone 3
ECB4Unit B Zone 4
ECB5Unit B Zone 5
ECB6Unit B Zone 6
ECB7Unit B Zone 7
ECB8Unit B Zone 8
ECB9Unit B Zone 9
ECBAUnit B Zone 10
ECBBUnit B Zone 11
ECBCUnit B Zone 12
ECBDUnit B Pump
ECBEUnit B Platen
ECMAMaintenance Counter Changed Unit A
ECMBMaintenance Counter Changed Unit B
EHCAHeat Soak Complete Unit A
EHCBHeat Soak Complete Unit B
EHHAHeat Soak Started Unit A
EHHBHeat Soak Started Unit B
EHPAPump Inactive Timeout Unit A
EHPBPump Inactive Timeout Unit B
EHSASetback Unit A
EHSBSetback Unit B
EHTAAt Temp Unit A
EHTBAt Temp Unit B
EHWAWarmup Unit A
EHWBWarmup Unit B
EKAAAuto-Crossover To A
EKABAuto-Crossover To B
EKMAManual-Crossover To A
EKMBManual-Crossover To B
EL0XSystem Power On
EM0XSystem Power Off
EP0XBlue Token Detected
EQU1Sys. Settings Downloaded
EQU2Sys. Settings Uploaded
EQU3Custom Lang. Downloaded
EQU4Custom Lang. Uploaded
EQU5Logs Downloaded
ERCAPump Cycles Tot. Reset Unit A
ERCBPump Cycles Tot. Reset Unit B
ERMAUser Maint. Count Reset Unit A
ERMBUser Maint. Count Reset Unit B
ERWAPump Weight Tot. Reset Unit A
ERWBPump Weight Tot. Reset Unit B
ETAATimer Event On Unit A
ETABTimer Event On Unit B
ETBATimer Event Off Unit A
ETBBTimer Event Off Unit B
ETSATimer Event Setback Unit A
ETSBTimer Event Setback Unit B
EVUXUSB Disabled
L1AXLevel Sensor Error Unit A
L1BXLevel Sensor Error Unit B
L2AXDrum Empty Unit A
L2BXDrum Empty Unit B
L3AXDrum Low Unit A
263A5186B
Page 27
Appendix C - Error/Event Tables
Error/Event
Code
Description
L3BXDrum Low Unit B
M8MAClean/Check Fan Unit A
M8MBClean/Check Fan Unit B
MMUXUSB Logs Full
MNAXMaintenance Due - User Unit A
MNBXMaintenance Due - User Unit B
T1A1Low Temp. Unit A Zone 1
T1A2Low Temp. Unit A Zone 2
T1A3Low Temp. Unit A Zone 3
T1A4Low Temp. Unit A Zone 4
T1A5Low Temp. Unit A Zone 5
T1A6Low Temp. Unit A Zone 6
T1A7Low Temp. Unit A Zone 7
T1A8Low Temp. Unit A Zone 8
T1A9Low Temp. Unit A Zone 9
T1AALow Temp. Unit A Zone 10
T1ABLow Temp. Unit A Zone 11
T1ACLow Temp. Unit A Zone 12
T1ADLow Temp. Unit A Pump
T1AELow Temp. Unit A Platen
T1B1Low Temp. Unit B Zone 1
T1B2Low Temp. Unit B Zone 2
T1B3Low Temp. Unit B Zone 3
T1B4Low Temp. Unit B Zone 4
T1B5Low Temp. Unit B Zone 5
T1B6Low Temp. Unit B Zone 6
T1B7Low Temp. Unit B Zone 7
T1B8Low Temp. Unit B Zone 8
T1B9Low Temp. Unit B Zone 9
T1BALow Temp. Unit B Zone 10
T1BBLow Temp. Unit B Zone 11
T1BCLow Temp. Unit B Zone 12
T1BDLow Temp. Unit B Pump
T1BELow Temp. Unit B Platen
T1C1Low Temp. MZLP 1
T1C2Low Temp. MZLP 2
T1C3Low Temp. MZLP 3
T1C4Low Temp. MZLP 4
T1C5Low Temp. MZLP 5
T1C6Low Temp. MZLP 6
T1C7Low Temp. MZLP 7
T1CGLow Temp. Gateway
T1CVLow Temp. AWB, Unit A
T1CWLow Temp. AWB, Unit B
T1CXLow Temp. System I/O, Unit A
T1CYLow Temp. System I/O, Unit B
T2A1Low Temp. Unit A Zone 1
T2A2Low Temp. Unit A Zone 2
T2A3Low Temp. Unit A Zone 3
T2A4Low Temp. Unit A Zone 4
T2A5Low Temp. Unit A Zone 5
T2A6Low Temp. Unit A Zone 6
T2A7Low Temp. Unit A Zone 7
T2A8Low Temp. Unit A Zone 8
T2A9Low Temp. Unit A Zone 9
T2AALow Temp. Unit A Zone 10
T2ABLow Temp. Unit A Zone 11
T2ACLow Temp. Unit A Zone 12
T2ADLow Temp. Unit A Pump
T2AELow Temp. Unit A Platen
T2B1Low Temp. Unit B Zone 1
T2B2Low Temp. Unit B Zone 2
T2B3Low Temp. Unit B Zone 3
T2B4Low Temp. Unit B Zone 4
T2B5Low Temp. Unit B Zone 5
T2B6Low Temp. Unit B Zone 6
T2B7Low Temp. Unit B Zone 7
T2B8Low Temp. Unit B Zone 8
T2B9Low Temp. Unit B Zone 9
T2BALow Temp. Unit B Zone 10
T2BBLow Temp. Unit B Zone 11
T2BCLow Temp. Unit B Zone 12
T2BDLow Temp. Unit B Pump
T2BELow Temp. Unit B Platen
T2C1Low Temp. MZLP 1
T2C2Low Temp. MZLP 2
T2C3Low Temp. MZLP 3
T2C4Low Temp. MZLP 4
T2C5Low Temp. MZLP 5
T2C6Low Temp. MZLP 6
T2C7Low Temp. MZLP 7
T2CGLow Temp. Gateway
T2CVLow Temp. AWB, Unit A
T2CWLow Temp. AWB, Unit B
3A5186B27
Page 28
Appendix C - Error/Event Tables
Error/Event
Code
Description
T2CXLow Temp. System I/O, Unit A
T2CYLow Temp. System I/O, Unit B
T3A1High Temp. Unit A Zone 1
T3A2High Temp. Unit A Zone 2
T3A3High Temp. Unit A Zone 3
T3A4High Temp. Unit A Zone 4
T3A5High Temp. Unit A Zone 5
T3A6High Temp. Unit A Zone 6
T3A7High Temp. Unit A Zone 7
T3A8High Temp. Unit A Zone 8
T3A9High Temp. Unit A Zone 9
T3AAHigh Temp. Unit A Zone 10
T3ABHigh Temp. Unit A Zone 11
T3ACHigh Temp. Unit A Zone 12
T3ADHigh Temp. Unit A Pump
T3AEHigh Temp. Unit A Platen
T3B1High Temp. Unit B Zone 1
T3B2High Temp. Unit B Zone 2
T3B3High Temp. Unit B Zone 3
T3B4High Temp. Unit B Zone 4
T3B5High Temp. Unit B Zone 5
T3B6High Temp. Unit B Zone 6
T3B7High Temp. Unit B Zone 7
T3B8High Temp. Unit B Zone 8
T3B9High Temp. Unit B Zone 9
T3BAHigh Temp. Unit B Zone 10
T3BBHigh Temp. Unit B Zone 11
T3BCHigh Temp. Unit B Zone 12
T3BDHigh Temp. Unit B Pump
T3BEHigh Temp. Unit B Platen
T3C1High Temp. MZLP 1
T3C2High Temp. MZLP 2
T3C3High Temp. MZLP 3
T3C4High Temp. MZLP 4
T3C5High Temp. MZLP 5
T3C6High Temp. MZLP 6
T3C7High Temp. MZLP 7
T3CGHigh Temp. Gateway
T3CVHigh Temp. AWB, Unit A
T3CWHigh Temp. AWB, Unit B
T3CXHigh Temp. System I/O, Unit A
T3CYHigh Temp. System I/O, Unit B
T4C1High Temp. MZLP 1
T4C2High Temp. MZLP 2
T4C3High Temp. MZLP 3
T4C4High Temp. MZLP 4
T4C5High Temp. MZLP 5
T4C6High Temp. MZLP 6
T4C7High Temp. MZLP 7
T4CGHigh Temp. Gateway
T4CVHigh Temp. AWB, Unit A
T4CWHigh Temp. AWB, Unit B
T4CXHigh Temp. System I/O, Unit A
T4CYHigh Temp. System I/O, Unit B
T4A1High Temp. Unit A Zone 1
T4A2High Temp. Unit A Zone 2
T4A3High Temp. Unit A Zone 3
T4A4High Temp. Unit A Zone 4
T4A5High Temp. Unit A Zone 5
T4A6High Temp. Unit A Zone 6
T4A7High Temp. Unit A Zone 7
T4A8High Temp. Unit A Zone 8
T4A9High Temp. Unit A Zone 9
T4AAHigh Temp. Unit A Zone 10
T4ABHigh Temp. Unit A Zone 11
T4ACHigh Temp. Unit A Zone 12
T4ADHigh Temp. Unit A Pump
T4AEHigh Temp. Unit A Platen
T4B1High Temp. Unit B Zone 1
T4B2High Temp. Unit B Zone 2
T4B3High Temp. Unit B Zone 3
T4B4High Temp. Unit B Zone 4
T4B5High Temp. Unit B Zone 5
T4B6High Temp. Unit B Zone 6
T4B7High Temp. Unit B Zone 7
T4B8High Temp. Unit B Zone 8
T4B9High Temp. Unit B Zone 9
T4BAHigh Temp. Unit B Zone 10
T4BBHigh Temp. Unit B Zone 11
T4BCHigh Temp. Unit B Zone 12
T4BDHigh Temp. Unit B Pump
T4BEHigh Temp. Unit B Platen
T4MAHigh Temp. Transformer Unit A
T4MBHigh Temp. Transformer Unit B
283A5186B
Page 29
Appendix C - Error/Event Tables
Error/Event
Code
Description
T6A1Sensor Err. Unit A Zone 1
T6A2Sensor Err. Unit A Zone 2
T6A3Sensor Err. Unit A Zone 3
T6A4Sensor Err. Unit A Zone 4
T6A5Sensor Err. Unit A Zone 5
T6A6Sensor Err. Unit A Zone 6
T6A7Sensor Err. Unit A Zone 7
T6A8Sensor Err. Unit A Zone 8
T6A9Sensor Err. Unit A Zone 9
T6AASensor Err. Unit A Zone 10
T6ABSensor Err. Unit A Zone 11
T6ACSensor Err. Unit A Zone 12
T6ADSensor Err. Unit A Pump
T6AESensor Err. Unit A Platen
T6B1Sensor Err. Unit B Zone 1
T6B2Sensor Err. Unit B Zone 2
T6B3Sensor Err. Unit B Zone 3
T6B4Sensor Err. Unit B Zone 4
T6B5Sensor Err. Unit B Zone 5
T6B6Sensor Err. Unit B Zone 6
T6B7Sensor Err. Unit B Zone 7
T6B8Sensor Err. Unit B Zone 8
T6B9Sensor Err. Unit B Zone 9
T6BASensor Err. Unit B Zone 10
T6BBSensor Err. Unit B Zone 11
T6BCSensor Err. Unit B Zone 12
T6BDSensor Err. Unit B Pump
T6BESensor Err. Unit B Platen
T6C1Sensor Err. MZLP 1
T6C2Sensor Err. MZLP 2
T6C3Sensor Err. MZLP 3
T6C4Sensor Err. MZLP 4
T6C5Sensor Err. MZLP 5
T6C6Sensor Err. MZLP 6
T6C7Sensor Err. MZLP 7
T6CGSensor Err. Gateway
T6CVSensor Err. AWB, Unit A
T6CWSensor Err. AWB, Unit B
T6CXSensor Err. System I/O, Unit A
T6CYSensor Err. System I/O, Unit B
T8A1No Temp. Rise Unit A Zone 1
T8A2No Temp. Rise Unit A Zone 2
T8A3No Temp. Rise Unit A Zone 3
T8A4No Temp. Rise Unit A Zone 4
T8A5No Temp. Rise Unit A Zone 5
T8A6No Temp. Rise Unit A Zone 6
T8A7No Temp. Rise Unit A Zone 7
T8A8No Temp. Rise Unit A Zone 8
T8A9No Temp. Rise Unit A Zone 9
T8AANo Temp. Rise Unit A Zone 10
T8ABNo Temp. Rise Unit A Zone 11
T8ACNo Temp. Rise Unit A Zone 12
T8ADNo Temp. Rise Unit A Pump
T8AENo Temp. Rise Unit A Platen
T8B1No Temp. Rise Unit B Zone 1
T8B2No Temp. Rise Unit B Zone 2
T8B3No Temp. Rise Unit B Zone 3
T8B4No Temp. Rise Unit B Zone 4
T8B5No Temp. Rise Unit B Zone 5
T8B6No Temp. Rise Unit B Zone 6
T8B7No Temp. Rise Unit B Zone 7
T8B8No Temp. Rise Unit B Zone 8
T8B9No Temp. Rise Unit B Zone 9
T8BANo Temp. Rise Unit B Zone 10
T8BBNo Temp. Rise Unit B Zone 11
T8BCNo Temp. Rise Unit B Zone 12
T8BDNo Temp. Rise Unit B Pump
T8BENo Temp. Rise Unit B Platen
T8C1No Temp. Rise MZLP 1
T8C2No Temp. Rise MZLP 2
T8C3No Temp. Rise MZLP 3
T8C4No Temp. Rise MZLP 4
T8C5No Temp. Rise MZLP 5
T8C6No Temp. Rise MZLP 6
T8C7No Temp. Rise MZLP 7
T8CGNo Temp. Rise Gateway
T8CVNo Temp. Rise AWB, Unit A
T8CWNo Temp. Rise AWB, Unit B
T8CXNo Temp. Rise System I/O, Unit A
T8CYNo Temp. Rise System I/O, Unit B
TAAXOver Temp Switch Unit A
TABXOver Temp Switch Unit B
V1I1Low Voltage 24VDC MZLP 1
V1I2Low Voltage 24VDC MZLP 2
3A5186B29
Page 30
Appendix C - Error/Event Tables
Error/Event
Code
Description
V1I3Low Voltage 24VDC MZLP 3
V1I4Low Voltage 24VDC MZLP 4
V1I5Low Voltage 24VDC MZLP 5
V1I6Low Voltage 24VDC MZLP 6
V1I7Low Voltage 24VDC MZLP 7
V1IGLow Voltage 24VDC Gateway
V1IVLow Voltage 24VDC AWB, Unit A
V1IWLow Voltage 24VDC AWB, Unit B
V1IXLow Voltage 24VDC System I/O, Unit A
V1IYLow Voltage 24VDC System I/O, Unit B
V1M1Low Voltage Line MZLP 1
V1M2Low Voltage Line MZLP 2
V1M3Low Voltage Line MZLP 3
V1M4Low Voltage Line MZLP 4
V1M5Low Voltage Line MZLP 5
V1M6Low Voltage Line MZLP 6
V1M7Low Voltage Line MZLP 7
V1MGLow Voltage Line Gateway
V1MVLow Voltage Line AWB, Unit A
V1MWLow Voltage Line AWB, Unit B
V1MXLow Voltage Line System I/O, Unit A
V1MYLow Voltage Line System I/O, Unit B
V4I1High Voltage 24VDC MZLP 1
V4I2High Voltage 24VDC MZLP 2
V4I3High Voltage 24VDC MZLP 3
V4I4High Voltage 24VDC MZLP 4
V4I5High Voltage 24VDC MZLP 5
V4I6High Voltage 24VDC MZLP 6
V4I7High Voltage 24VDC MZLP 7
V4IGHigh Voltage 24VDC Gateway
V4IVHigh Voltage 24VDC AWB, Unit A
V4IWHigh Voltage 24VDC AWB, Unit B
V4IXHigh Voltage 24VDC System I/O, Unit A
V4IYHigh Voltage 24VDC System I/O, Unit B
V4M1High Voltage Line MZLP 1
V4M2High Voltage Line MZLP 2
V4M3High Voltage Line MZLP 3
V4M4High Voltage Line MZLP 4
V4M5High Voltage Line MZLP 5
V4M6High Voltage Line MZLP 6
V4M7High Voltage Line MZLP 7
V4MGHigh Voltage Line Gateway
V4MVHigh Voltage Line AWB, Unit A
V4MWHigh Voltage Line AWB, Unit B
V4MXHigh Voltage Line System I/O, Unit A
V4MYHigh Voltage Line System I/O, Unit B
V6I1Wiring Error 24VDC MZLP 1
V6I2Wiring Error 24VDC MZLP 2
V6I3Wiring Error 24VDC MZLP 3
V6I4Wiring Error 24VDC MZLP 4
V6I5Wiring Error 24VDC MZLP 5
V6I6Wiring Error 24VDC MZLP 6
V6I7Wiring Error 24VDC MZLP 7
V6IGWiring Error 24VDC Gateway
V6IVWiring Error 24VDC AWB, Unit A
V6IWWiring Error 24VDC AWB, Unit B
V6IXWiring Error 24VDC System I/O, Unit A
V6IYWiring Error 24VDC System I/O, Unit B
V6M1Wiring Error Line MZLP 1
V6M2Wiring Error Line MZLP 2
V6M3Wiring Error Line MZLP 3
V6M4Wiring Error Line MZLP 4
V6M5Wiring Error Line MZLP 5
V6M6Wiring Error Line MZLP 6
V6M7Wiring Error Line MZLP 7
V6MGWiring Error Line Gateway
V6MVWiring Error Line AWB, Unit A
V6MWWiring Error Line AWB, Unit B
V6MXWiring Error Line System I/O, Unit A
V6MYWiring Error Line System I/O, Unit B
V8I1No Voltage 24VDC MZLP 1
V8I2No Voltage 24VDC MZLP 2
V8I3No Voltage 24VDC MZLP 3
V8I4No Voltage 24VDC MZLP 4
V8I5No Voltage 24VDC MZLP 5
V8I6No Voltage 24VDC MZLP 6
V8I7No Voltage 24VDC MZLP 7
V8IGNo Voltage 24VDC Gateway
V8IVNo Voltage 24VDC AWB, Unit A
V8IWNo Voltage 24VDC AWB, Unit B
V8IXNo Voltage 24VDC System I/O, Unit A
V8IYNo Voltage 24VDC System I/O, Unit B
V8M1No Voltage Line MZLP 1
V8M2No Voltage Line MZLP 2
303A5186B
Page 31
Appendix C - Error/Event Tables
Error/Event
Code
Description
V8M3No Voltage Line MZLP 3
V8M4No Voltage Line MZLP 4
V8M5No Voltage Line MZLP 5
V8M6No Voltage Line MZLP 6
V8M7No Voltage Line MZLP 7
V8MGNo Voltage Line Gateway
V8MVNo Voltage Line AWB, Unit A
V8MWNo Voltage Line AWB, Unit B
V8MXNo Voltage Line System I/O, Unit A
V8MYNo Voltage Line System I/O, Unit B
WJ1ASolenoid Error No Current Unit A
WJ1BSolenoid Error No Current Unit B
WJ2ASolenoid Error High Current Unit A
WJ2BSolenoid Error High Current Unit B
WSUXConfig. Error USB
3A5186B31
Page 32
Graco Information
Sealant and Adhesive Dispensing Equipment
For the latest information about Graco products, visit www.graco.com.
For patent information, see www.graco.com/patents.
TO PLACE AN ORDER, contact your Graco distributor, go to www.graco.com and select
“Where to Buy” in the top blue bar, or call to find the nearest distributor.
If calling from the US: 800-746-1334
If calling from outside the US: 0-1-330-966-3000
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2016, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco reserves the right to make changes at any time without notice.
Original instructions. This manual contains English. MM 3A5186
International Offices: Belgium, China, Japan, Korea
Graco Headquarters: Minneapolis
www.graco.com
Revision
B, December 2017
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.