Graco Therm-O-Flow 25C994 Instructions Manual

Instructions - Parts
Communications Gateway Module
3A5186B
Therm-O-Flow® Installation Kit
Kit No. 25C994
Important Safety Instructions
Read all warnings and instructions in this manual and in all related manuals. Save all instructions.
EN
Related Manuals
Contents
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Mounting the CGM . . . . . . . . . . . . . . . . . . . . . . . 3
Connecting the CAN Cables . . . . . . . . . . . . . . . . 3
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Gateway Screens . . . . . . . . . . . . . . . . . . . . . . . . 5
EtherNet/IP Fieldbus Screens . . . . . . . . . . . . . . . 5
DeviceNet Fieldbus Screen . . . . . . . . . . . . . . . . 5
PROFIBUS Fieldbus Screen . . . . . . . . . . . . . . . . 6
PROFINET Fieldbus Screens . . . . . . . . . . . . . . . 6
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Software Update Procedure . . . . . . . . . . . . . . . . 8
Available Internal Data . . . . . . . . . . . . . . . . . . . . . . 9
Automation Inputs (Signals from the Therm-O-Flow
to the PLC) . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Automation Outputs (Signals from the PLC to the
Therm-O-Flow) . . . . . . . . . . . . . . . . . . . . . . 11
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Kit No. 25C994 . . . . . . . . . . . . . . . . . . . . . . . . . 12
Appendix A - I/O Signal Descriptions . . . . . . . . . 13
Heat Zone States . . . . . . . . . . . . . . . . . . . . . . . 13
Status Indication Bit Tables . . . . . . . . . . . . . . . 13
System Control Bits . . . . . . . . . . . . . . . . . . . . . 14
Temperature Setpoint Zone Designation Table 16
Appendix B - Data Exchange Interface . . . . . . . . 17
Data Exchange Interface Pointer Designation Tabl
18
Appendix C - Error/Event Tables . . . . . . . . . . . . . 22
Related Manuals
Manual Description
Models
The following kit includes the Communications Gateway Module (CGM) parts and software that are required for Therm-O-Flow 20 or Therm-O-Flow 200 machines using a CGM. This kit enables the Therm-O-Flow machines to
connect to a fieldbus device.
Part No. Description
25C994 Thermo-O-Flow CGM Installation Kit
Kit 25C994 is used with the following CGM models, each of which includes all of the remaining parts neces­sary to install the CGM. See Communications Gateway Module Instructions - Parts, manual 312864, for repair
parts for these assemblies.
Part No. Fieldbus
CGMEP0 EtherNet/IP CGMDN0 DeviceNet CGMPB0 PROFIBUS CGMPN0 PROFINET
Overview
The Communications Gateway Module (CGM) provides a control link between the Therm-O-Flow (TOF) system and a selected fieldbus. The control link provides the means for remote monitoring and control by external automation systems.
The data available to the fieldbus from the CGM depends on the amount of channels installed on the Therm-O-Flow system. A data map is available on a token provided in this kit.
See Available Internal Data on page 9 for a list of inter­nal data from the Therm-O-Flow system that can be viewed or modified by the fieldbus device.
312864 Communications Gateway Module
Instructions - Parts
334130 Therm-O-Flow 200 Instructions - Parts
334129 Therm-O-Flow 20 Instructions - Parts
406987 GCA CAN Cables, Reference
2 3A5186B
NOTE: The following system network configuration files are available at www.graco.com.
EDS file: DeviceNet or Ethernet/IP fieldbus net­works
Installation
Recommended Location for Mounting Holes
3.25 in.
(82.6 mm)
2.75 in.
(69.9 mm)
#10-32 UNF
(M5 x 0.8)
CAN Cable Connectors
D
A
C
B
Installation
NOTE: Turn off the main power switch on the Therm-O-Flow before starting. See the Therm-O-Flow manuals referenced in Related Manuals on page 2 for information about turning off the power.
To install the CGM, you will need to drill mounting holes on the Therm-O-Flow below the electrical control panel in a location where the CAN cables can be connected to the CGM. See Figure 1 for the recommended location.
Mounting the CGM
1. Drill the mounting holes.
2. Remove the access cover from the CGM (D). Loosen the two screws (C) and remove the CGM (A) from the base (B).
FIG. 1: Mounting Location
The center of the CGM should be 4 inches from the bot­tom of the electrical control panel and 8 inches from each side. Refer to the following mounting dimensions when drilling the holes for the CGM.
NOTE: Mount the CGM with the CAN cable connectors on the left side to make it easier to connect the cables.
FIG. 2: Removing the CGM Access Cover
3. With the CAN connectors on the left side, mount the base (B) in the mounting holes using the four screws supplied in this kit. See Parts on page 12.
4. Mount the CGM (A) on the base (B) with the two screws (C) that were removed in step 2.
5. Reattach the access cover (D).
Connecting the CAN Cables
1. Disconnect the ADM’s CAN cable from the ADM and from the splitter on the back of the Therm-O-Flow’s electrical control panel.
2. Connect one end of the 1.5 m (4.9 ft) CAN cable included in this kit to the ADM. Run the cable down and through the opening underneath the electrical control box as shown in Figure 3.
3A5186B 3
Installation
CAN Cable from ADM
CAN Cable from Splitter
Opening Leading to CGM
CAN Connector 1
CAN Connector 2
Fieldbus Connection
3. Connect the CAN cable that you removed from the ADM to the available splitter connection on the back of the electrical control panel. Run that cable through the same opening as the other CAN cable.
FIG. 3: CAN Cable Connection
4. Connect the two cables to the CGM connectors. Either cable can be connected to either connector.
7. Connect the Ethernet, DeviceNet, or PROFIBUS cable to the CGM as applicable. Connect the other end of the cable to the fieldbus device.
FIG. 5: Connecting the Fieldbus
8. Perform the Install or Update Data Map procedure in Communications Gateway Module Instructions - Parts, manual 312864.
9. See the Available Internal Data on page 9 for details on the fieldbus pinout setup.
10. Perform Setup on page 5 to configure the fieldbus.
FIG. 4: CGM Connectors
5. Attach the two ferrite suppressors included in the kit to the ends of the two cables closest to the CGM.
6. Use the adhesive cable tie included in the kit to attach the CAN cables to the back of the control
box.
4 3A5186B
Setup
Setup
NOTICE
To prevent damage to soft key buttons on the ADM, do not press the buttons with sharp objects such as pens, plastic cards, or fingernails.
Gateway Screens
Use the Gateway screens on the ADM to configure the fieldbus. These screens are shown only if a CGM is cor­rectly installed in your system. See Installation on page
3.
1. With the system on and enabled, press on the
ADM to access the Setup screens.
2. Use the ADM’s arrow keys to navigate to the main Gateway screen.
EtherNet/IP Fieldbus Screens
Screen 2
Use the down arrow key on the ADM to navigate to screen 2. This screen displays the hardware revision, system serial number, and data map identification infor­mation.
DeviceNet Fieldbus Screen
NOTE: These screens are shown only if you have an
EtherNet/IP fieldbus CGM installed.
Screen 1
Press the key to access this screen. Use the arrow
keys to navigate to each field and the keypad to set the IP address, DHCP settings, subnet mask, gateway, and DNS information.
NOTE: This screen is shown only if you have a Devi­ceNet fieldbus CGM installed.
Press the key to access this screen. You can set
the device address and baud rate. You can also view the hardware revision, system serial number, and data map identification information.
3A5186B 5
Setup
PROFIBUS Fieldbus Screen
NOTE: These screens are shown only if you have a
PROFIBUS fieldbus CGM installed.
Screen 1
Press the key to access this screen. Use the arrow
keys to navigate to each field and the keypad to set the device address, install date, location tag, function tag, and description.
PROFINET Fieldbus Screens
NOTE: These screens are shown only if you have a
PROFINET fieldbus CGM installed.
Screen 1
Press the key to access this screen. Use the arrow
keys to navigate to each field and the keypad to set the IP address, DHCP settings, subnet mask, gateway, and DNS information.
Screen 2
Use the down arrow key on the ADM to navigate to screen 2. This screen displays the hardware revision, system serial number, and data map identification infor­mation.
Screen 2
Use the down arrow key on the ADM to navigate to
screen 2. Press the key to access this screen. You
can set the station name, install date, location tag, func­tion tag, and description.
6 3A5186B
Screen 3
Use the down arrow key on the ADM to navigate to screen 3. This screen displays the hardware revision, system serial number, and data map identification infor­mation.
Setup
3A5186B 7
Maintenance
Maintenance
Software Update Procedure
When software is updated on the ADM, the software is then automatically updated on the CGM and all other connected Graco Control Architecture components.
1. At the ADM, turn the power switch to Off.
2. Remove the ADM from the bracket.
3. Use a hex key to remove the token access panel.
6. The Graco Splash screen is displayed until commu­nication with other modules is established.
7. Wait for the update to complete. An approximate time to completion displays below the progress bar.
8. When the update is completed successfully, press
the key.
FIG. 6: Token Location
4. Insert and press the software upgrade token firmly into the slot.
5. Turn the power switch to On.
NOTICE
A status is shown while software is updating to indi­cate progress. To prevent corrupting the software load, do not remove the token until the status screen disappears.
9. Remove the token and replace the token access panel.
NOTE: The software version history for each system can be viewed in the technical support section at www.graco.com.
8 3A5186B
Available Internal Data
Available Internal Data
See Appendix A - I/O Signal Descriptions on page 13 for additional details regarding each input/output. Unless stated otherwise:
Values are subject to the same maximum and minimum restrictions of the ADM.
Some of the temperature data may have slight rounding errors compared to temperatures displayed on the ADM.
On some controlling devices, the byte order may need to be reversed (byte order within instance, least significant
-> most significant.
Automation Inputs (Signals from the Therm-O-Flow to the PLC)
Instance Number
1 0 -1 Pump Actual Temperature, Primary °C/°F 2 2 - 3 Platen Actual Temperature, Primary °C/°F 3 4 - 5 Zone #1 Actual Temperature, Primary °C/°F 4 6 - 7 Zone #2 Actual Temperature, Primary °C/°F 5 8 - 9 Zone #3 Actual Temperature, Primary °C/°F 6 10 - 11 Zone #4 Actual Temperature, Primary °C/°F 7 12 - 13 Zone #5 Actual Temperature, Primary °C/°F 8 14 - 15 Zone #6 Actual Temperature, Primary °C/°F
9 16 - 17 Zone #7 Actual Temperature, Primary °C/°F 10 18 - 19 Zone #8 Actual Temperature, Primary °C/°F 11 20 - 21 Zone #9 Actual Temperature, Primary °C/°F 12 22 - 23 Zone #10 Actual Temperature, Primary °C/°F 13 24 - 25 Zone #11 Actual Temperature, Primary °C/°F 14 26 - 27 Zone #12 Actual Temperature, Primary °C/°F 15 28 - 29 Pump Setpoint Temperature Indication, Primary/Secondary °C/°F 16 30 - 31 Platen Setpoint Temperature Indication, Primary/Secondary °C/°F 17 32 - 33 Zone #1 Setpoint Temperature Indication, Primary/Secondary °C/°F 18 34 - 35 Zone #2 Setpoint Temperature Indication, Primary/Secondary °C/°F 19 36 - 37 Zone #3 Setpoint Temperature Indication, Primary/Secondary °C/°F 20 38 - 39 Zone #4 Setpoint Temperature Indication, Primary/Secondary °C/°F 21 40 - 41 Zone #5 Setpoint Temperature Indication, Primary/Secondary °C/°F 22 42 - 43 Zone #6 Setpoint Temperature Indication, Primary/Secondary °C/°F 23 44 - 45 Zone #7 Setpoint Temperature Indication, Primary/Secondary °C/°F 24 46 - 47 Zone #8 Setpoint Temperature Indication, Primary/Secondary °C/°F 25 48 - 49 Zone #9 Setpoint Temperature Indication, Primary/Secondary °C/°F 26 50 - 51 Zone #10 Setpoint Temperature Indication, Primary/Secondary °C/°F 27 52 - 53 Zone #11 Setpoint Temperature Indication, Primary/Secondary °C/°F 28 54 - 55 Zone #12 Setpoint Temperature Indication, Primary/Secondary °C/°F 29 56 - 57 Pump, Platen, Zones 1 – 3 States, Primary 30 58 - 59 Zones 4 – 8 States, Primary 31 60 - 61 Zones 9 – 12 States, Primary
32* 62 - 63 Pump Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 33* 64 - 65 Platen Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 34* 66 - 67 Zone #1 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 35* 68 - 69 Zone #2 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 36* 70 - 71 Zone #3 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 37* 72 - 73 Zone #4 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F
Input Byte
Index(es)
Description Units
3A5186B 9
Available Internal Data
Instance
Number
Input Byte
Index(es)
Description Units
38* 74 - 75 Zone #5 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 39* 76 - 77 Zone #6 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 40* 78 - 79 Zone #7 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 41* 80 - 81 Zone #8 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 42* 82 - 83 Zone #9 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 43* 84 - 85 Zone #10 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 44* 86 - 87 Zone #11 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F
45* 88 - 89 Zone #12 Setback Setpoint Temperature Indication, Primary/Secondary °C/°F 46** 90 - 91 Pump Actual Temperature, Secondary °C/°F 47** 92 - 93 Platen Actual Temperature, Secondary °C/°F 48** 94 - 95 Zone #1 Actual Temperature, Secondary °C/°F 49** 96 - 97 Zone #2 Actual Temperature, Secondary °C/°F 50** 98 - 99 Zone #3 Actual Temperature, Secondary °C/°F 51** 100 - 101 Zone #4 Actual Temperature, Secondary °C/°F 52** 102 - 103 Zone #5 Actual Temperature, Secondary °C/°F 53** 104 - 105 Zone #6 Actual Temperature, Secondary °C/°F 54** 106 - 107 Zone #7 Actual Temperature, Secondary °C/°F 55** 108 - 109 Zone #8 Actual Temperature, Secondary °C/°F 56** 110 - 111 Zone #9 Actual Temperature, Secondary °C/°F 57** 112 - 113 Zone #10 Actual Temperature, Secondary °C/°F 58** 114 - 115 Zone #11 Actual Temperature, Secondary °C/°F 59** 116 - 117 Zone #12 Actual Temperature, Secondary °C/°F 60** 118 - 119 Pump, Platen, Zones 1 – 3 States, Secondary 61** 120 - 121 Zones 4 – 8 States, Secondary 62** 122 - 123 Zones 9 – 12 States, Secondary 63** 124 - 127 Error / Event Code(s) Present 64** 128 - 131 Error / Event Code(s) Needing Acknowledged 65** 132 - 133 Status Word 1 Indication Bits 66** 134 - 135 Status Word 2 Indication Bits 67** 136 - 137 Data Exchange Interface Pointer Last Serviced 68** 138 - 141 Data Exchange Interface Input Value 69** 142 System Mode/State, Primary 70** 143 System Mode/State, Secondary
* Data instances (setback mode setpoint temperatures) are NOT provided for the PROFIBUS and PROFINET versions of the map since the
field protocols do not support that large of a map size. For PROFIBUS or PROFINET, you should use the data exchange interface to obtain setback setpoint information.
** For the PROFIBUS or PROFINET versions of the map, 14 should be subtracted from the instance number and 28 should be subtracted for the
input byte count so that the PROFIBUS and PROFINET versions have 56 input instances containing 116 input bytes total.
Zone states are packed in groups of three bits, where each zone state equates to the following. Each zone is packed from bit 0, bit 3, bit 6, bit
9, and bit 12 corresponding to the order presented in the description. 000 - zone is not installed, 001 - zone is off, 010 - zone is in warm up state, 011 - zone is in heat soak state, 100 - zone at temperature, 101 - zone in setback mode.
Temperature units match units of the ADM. Values are in tenths of a degree (for example, a value of 4005 corresponds to 400.5 °F). Setpoint
temperatures are either for the primary or secondary unit, depending on the system selected by the PLC in the System Control Word.
† See Appendix C - Error/Event Tables on page 22.
See the Status Indication Bit Tables on page 13.
See Appendix B - Data Exchange Interface on page 17.
‡ System Mode/State: 0 = System Off, 1 = Inactive, 2 = Warm Up, 3 = Heat Soak, 4 = Ready (at temperature, heat soak done, pump off), 5 =
Active (at ready and pump ON), 6 = Setback Mode.
10 3A5186B
Loading...
+ 22 hidden pages