GRACO Therm-O-Flow 200 Instruction manual

Page 1
Instructions-Parts
®
Therm-O-Flow
For applying hot melt sealant and adhesive materials from 200 Liter (55 Gallon) drums. For professional use only.
Important Safety Instructions
Read all warnings and instructions in this manual and in related manuals. Save these instructions.
Maximum Operating Temperature 400°F (204°C) See page 7 for model information.
See Technical Specifications, page 113, for maximum working pressures.
200
334130T
EN
3143485
Page 2
Contents
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Component Identification . . . . . . . . . . . . . . . . . . . . . . . . . 8
Integrated Air Controls . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Control Enclosure . . . . . . . . . . . . . . . . . . . . 10
Advanced Display Module (ADM) . . . . . . . . . . . . . . . . 11
Screen Components . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Air and Fluid Hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Heat Control Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Unpack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . 15
Install System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Install Hydraulic Power Supply . . . . . . . . . . . . . . . . . . 15
Mechanical Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Install Heated Hose . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connect Multiple Devices . . . . . . . . . . . . . . . . . . . . . . 18
Connect Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Connect Secondary System . . . . . . . . . . . . . . . . . . . . 20
Check Sensor Resistance . . . . . . . . . . . . . . . . . . . . . . 21
Check Heater Resistance . . . . . . . . . . . . . . . . . . . . . . 22
Select ADM Settings . . . . . . . . . . . . . . . . . . . . . . . . . .23
Connect PLC (Hard Wired Interface Version) . . . . . . . 25
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Purge System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Load Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Heat Up System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Prime Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Prime System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Setback Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Pressure Relief Procedure . . . . . . . . . . . . . . . . . . . . . 35
Stop Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Change Drums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Light Tower (Optional) . . . . . . . . . . . . . . . . . . . . . . . . 40
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Ram Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 47
Heated Pump Troubleshooting . . . . . . . . . . . . . . . . . . 48
Air Motor Troubleshooting . . . . . . . . . . . . . . . . . . . . . . 48
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Replace Wipers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Replace Platen RTD . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Separate the Air Motor and Pump . . . . . . . . . . . . . . . 50
Remove Platen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Replace Heater Band and Pump RTD . . . . . . . . . . . . 53
Replace MZLP Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Replace MZLP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Replace MZLP Daughter Card . . . . . . . . . . . . . . . . . . 56
Replace AWB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Replace Power Supply . . . . . . . . . . . . . . . . . . . . . . . . 57
Replace Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Replace Transformer . . . . . . . . . . . . . . . . . . . . . . . . . 59
Update Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Electrical Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
230V, 3 Phase/60Hz . . . . . . . . . . . . . . . . . . . . . . . . . . 62
400V, 3 Phase/50Hz . . . . . . . . . . . . . . . . . . . . . . . . . . 63
400-600VV, 3 Phase/60Hz . . . . . . . . . . . . . . . . . . . . . 64
AWB and MZLP#1 . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
MZLP#2, MZLP#3, Overtemp, and Pump Heaters . . . 66
MZLP Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Therm-O-Flow 200 Supply Unit . . . . . . . . . . . . . . . . . 68
Therm-O-Flow 200 Supply Unit . . . . . . . . . . . . . . . . . 69
Air Control Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 70
Electrical Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Electrical Control Module Parts . . . . . . . . . . . . . . . . . 73
Electrical Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
230V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
400V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Electrical Panel Parts . . . . . . . . . . . . . . . . . . . . . . . . . 77
Merkur 2200, 23:1 Pump Modules . . . . . . . . . . . . . . . 78
Merkur 2200, 23:1 Pump Modules . . . . . . . . . . . . . . . 79
Merkur 3400, 36:1 Pump Modules . . . . . . . . . . . . . . . 80
Merkur 3400, 36:1 Pump Modules . . . . . . . . . . . . . . . 81
NXT 6500, 70:1 Pump Modules . . . . . . . . . . . . . . . . . 82
NXT 6500, 70:1 Pump Modules . . . . . . . . . . . . . . . . . 83
24V619, Pump Shield . . . . . . . . . . . . . . . . . . . . . . . . . 84
Heated Platens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
24V633, Heated Drum Platen, Mega-Flo
(Code E-option M) . . . . . . . . . . . . . . . . . . . . . . . . 85
24V634, Heated Drum Platen, Standard Grid
(Code E-option F) . . . . . . . . . . . . . . . . . . . . . . . . 85
24V635, Heated Drum Platen, Smooth Bottom (no fin)
(Code E- option S) . . . . . . . . . . . . . . . . . . . . . . . . 85
Heated Platens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
24V633, Heated Drum Platen, Mega-Flo
(Code E-option M) . . . . . . . . . . . . . . . . . . . . . . . . 86
24V634, Heated Drum Platen, Standard Grid
(Code E-option F) . . . . . . . . . . . . . . . . . . . . . . . . 86
2 334130T
Page 3
24V635, Heated Drum Platen, Smooth Bottom (no fin)
(Code E- option S) . . . . . . . . . . . . . . . . . . . . . . . 86
Drum Ram Post Saddle Clamp . . . . . . . . . . . . . . . . . 88
C32463 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Option H-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Drum Ram Post Saddle Clamp . . . . . . . . . . . . . . . . . 89
918395 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Option H-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Fiber Drum Reinforcement Shell Clamp . . . . . . . . . . 90
918397 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Option H-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Vent Hood Kit, 233559 . . . . . . . . . . . . . . . . . . . . . . . . 91
Accessories and Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Wiper Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Applicators and Dispense Valves . . . . . . . . . . . . . . . . 92
CGM Installation Kit, 25C994 . . . . . . . . . . . . . . . . . . . 92
Flow Control and Manifolds . . . . . . . . . . . . . . . . . . . . 92
Accessory Extension Cables . . . . . . . . . . . . . . . . . . . 93
Light Tower Kit, 24W589 . . . . . . . . . . . . . . . . . . . . . . 93
Heated Hoses and Fittings . . . . . . . . . . . . . . . . . . . . . 94
8 Channel Upgrade Kit, 24V755 . . . . . . . . . . . . . . . . 96
8 Zone Upgrade Kit Installation . . . . . . . . . . . . . . . . . 97
12 Channel Upgrade Kit, 24V756 . . . . . . . . . . . . . . . 98
12 Zone Upgrade Kit Installation . . . . . . . . . . . . . . . . 99
Appendix A - ADM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
General Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 100
ADM Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Screen Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Enable, Disable Heating System . . . . . . . . . . . . . . . 100
Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Operation Screens . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Setup Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Appendix B - USB Data . . . . . . . . . . . . . . . . . . . . . . . . . 109
Download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Access Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Upload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
USB Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
System Settings File . . . . . . . . . . . . . . . . . . . . . . . . 110
System Language File . . . . . . . . . . . . . . . . . . . . . . . 111
Create Custom Language Strings . . . . . . . . . . . . . . 111
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Ram Mounting and Clearance . . . . . . . . . . . . . . . . . 112
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . 113
California Proposition 65 . . . . . . . . . . . . . . . . . . . . . . . 113
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . . . . . 114
334130T 3
Page 4

Warnings

WARNING
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama-
tion point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When these symbols appear in the body of this manual or on warning labels, refer back to these Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.
BURN HAZARD
Equipment surfaces and fluid that is heated can become very hot during operation. To avoid burns:
Do not touch hot fluid or equipment.
SPLATTER HAZARD
severe
Hot or toxic fluid can cause serious injury if splashed in the eyes or on skin. During blow off of platen, splatter may occur.
Use minimum air pressure when removing platen from drum.
MOVING PARTS HAZARD
Moving parts can pinch, cut or amputate fingers and other body parts.
Keep clear of moving parts.
Do not operate equipment with protective guards or covers removed.
Pressurized equipment can start without warning. Before checking, moving, or servicing equipment, follow the Pressure Relief Procedure and disconnect all power sources.
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before disconnecting any cables and before servicing or installing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regu-
lations.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed.
Read MSDSs to know the specific hazards of the fluids you are using.
Store hazardous fluid in approved containers, and dispose of it according to applicable
4 334130T
guidelines.
Page 5
THERMAL EXPANSION HAZARD
WARNING
Fluids subjected to heat in confined spaces, including hoses, can create a rapid rise in pressure the thermal expansion. Over- pres su riz ation can resu lt in equi pm ent ru pture and se rious
Open a valve to relieve the fluid expansion during heating.
Replace hoses proactively at regular intervals based on your operating conditions.
SKIN INJECTION HAZARD
High-pressure fluid from dispensing device, hose leaks, or ruptured components will pierce may look like just a cut, but it is a serious injury that can result in amputation. Get
treatment.
injury.
skin. This
immediate surgical
Warnings
due to
Engage trigger lock when not dispensing.
Do not point dispensing device at anyone or at any part of the body.
Do not put your hand over the fluid outlet.
Do not stop or deflect leaks with your hand, body, glove, or rag.
Follow the Pressure Relief Procedure when you stop dispensing and before cleaning, checking, or servicing equipment.
Tighten all fluid connections before operating the equipment.
Check hoses and couplings daily. Replace worn or damaged parts immediately.
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help fire and explosion:
Use equipment only in well ventilated area.
Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and cloths (potential static arc).
Keep work area free of debris, including solvent, rags and gasoline.
Do not plug or unplug power cords, or turn power or light switches on or off when flammable present.
Ground all equipment in the work area. See Grounding instructions.
Use only grounded hoses.
Hold gun firmly to side of grounded pail when triggering into pail. Do not use pail liners unless antistatic or conductive.
Stop operation immediately if static sparking occurs or you feel a shock. Do not use you identify and correct the problem.
Keep a working fire extinguisher in the work area.
equipment until
prevent
plastic drop
fumes are
they are
334130T 5
Page 6
Warnings
WARNING
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maximum working pressure or temperature rating of the lowest rated ponent. See Technical Data in all equipment manuals.
Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete your material, request MSDS from distributor or retailer.
Do not leave the work area while equipment is energized or under pressure.
Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine turer’s replacement parts only.
Do not alter or modify equipment. Alterations or modifications may void agency approvals safety hazards.
Make sure all equipment is rated and approved for the environment in which you are using it.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
system com-
information about
manufac-
and create
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective not limited to:
Protective eyewear, and hearing protection.
Respirators, protective clothing, and gloves as recommended by the fluid and solvent
equipment includes but is
including
manufacturer.
6 334130T
Page 7

Models

The model number stamped on your systems defines the equipment in the following categories.
See Technical Specifications, page 113, for maximum working pressure.
SER A B C D E F G H
Series Frame Size Air
Air/Electric
Zone
Config
Pump
Ratio
Platen
Style
Platen
Seal
Ram Drum
Models
Clamp
Code A Frame Size
200 55 Gallon (200 Liter)
Code B Air/Electric
A Air control only E Air and Electric
Code C Zones, Volts, Type
11P 4 Zones, 230 V, Primary 11S 4 Zones, 230 V, Secondary 12P 4 Zones, 400 V/N, Primary 12S 4 Zones, 400 V/N, Secondary 13P 4 Zones, 400 V, Primary 13S 4 Zones, 400 V, Secondary 14P 4 Zones, 480 V, Primary 14S 4 Zones, 480 V, Secondary 15P 4 Zones, 600 V, Primary 15S 4 Zones, 600 V, Secondary 21P 8 Zones, 230 V, Primary 21S 8 Zones, 230 V, Secondary 22P 8 Zones, 400 V/N, Primary 22S 8 Zones, 400 V/N, Secondary 23P 8 Zones, 400 V, Primary 23S 8 Zones, 400 V, Secondary 24P 8 Zones, 480 V, Primary 24S 8 Zones, 480 V, Secondary 25P 8 Zones, 600 V, Primary 25S 8 Zones, 600 V, Secondary 31P 12 Zones, 230 V, Primary 31S 12 Zones, 230 V, Secondary 32P 12 Zones, 400 V/N, Primary 32S 12 Zones, 400 V/N, Secondary 33P 12 Zones, 400 V, Primary 33S 12 Zones, 400 V, Secondary 34P 12 Zones, 480 V, Primary 34S 12 Zones, 480 V, Secondary 35P 12 Zones, 600 V, Primary 35S 12 Zones, 600 V, Secondary
NNN None
Code D Pump Ratio
1 23:1 CF (carbon filled PTFE) 236:1 370:1 4 23:1 (glass filled PTFE) 536:1 670:1
Code E Platen Style
S Smooth Bottom (No Fin) F Standard Finned Bottom
M Mega-Flo
Code F Platen Seal
1 2 Black EPDM/EPDM, SS wire braid 400°F
(204°C) hose wipers with spring retention
2 1 lower black EPDM/Chlorobutyl, SS wire
braid 400°F (204°C) hose wiper and 1 upper Green Silicone, fiberglass braid
400°F (204°C), hose wiper 3 2 White Silicone 250°F (121°C) T-Wipers 4 1 lower black EPDM/Chlorobutyl, SS wire
braid 375°F (190°C) hose wiper and 1
upper White Silicone 375°F (190°C),
T-wiper 5 2 Orange silicone o-ring 400°F (204°C)
Code G Ram
P Pneumatic
H Hydraulic
Code H Drum Clamps
NNone
1 Saddle Clamp 2 Fiber Clam Shell 3 Heavy Drum Band
334130T 7
Page 8

Related Manuals

Related Manuals
Manual Description
334129 Therm-O-Flow 20, Instructions-Parts 3A5186 Communications Gateway Module
Therm-O-FLow Air Motor Manuals 311238
3A1211
Displacement Pump Manual 334127
334128
Ram Manual 334198 Therm-O-Flow 200 Pneumatic and
Accessory and Kit Manuals 3A4241 Heated Hose, Instructions-Parts 309160 Heated Hose, Instructions-Parts 309196 Wiper Kits, Repair-Parts 310538 Air-Operated Dispense Valves,
311209 Top Feed and Bottom Feed Hot Melt
334201 Air Controls, Repair Kit
®
Air Motor, Instructions-Parts
NXT
®
Saniforce
Check-Mate
Check-Mate
Air Motor, Instructions-Parts
®
800 Pump, Repair-Parts
®
800 Throat Seal Repair Kit,
Repair-Parts
Hydraulic Ram, Instructions-Parts
tions-Parts
pense Guns, Instructions-Parts
Instruc-
Dis-
8 334130T
Page 9

Component Identification

C
M
D
A
P
B
T
J
N
L
K
H
R, S
G
E
ti24544a
F
Component Identification
FIG. 1: TOF 200 Pneumatic
Key:
A Lift Strap Positions B Multi-Zone Low Power Temperature Control Module
(MZLP) C Light Tower D Cable Track ERam F Heated Pump G Heated Platen H Integrated Air Controls (3/4 in npt inlet) J Electrical Control Panel K Main Power Switch (can be locked in the open position) LADM M Air Motor Solenoid
N Electrical Power Input P Air Motor R Ram Plate Bleed Stick S Drum Blow Off Valve (behind ram plate bleed stick) T Drum Low and Empty Sensors
334130T 9
Page 10
Component Identification
CN
CM
CK
CJ
CH
CD
CC
CB
CA
CE
CG
CF
CL

Integrated Air Controls

FIG. 2: Integrated Air Controls
Key:
CA
Main Air Slider Valve
Turns air on and off to the entire system. When closed,
the valve relieves pressure downstream. Can be locked in
the closed position.
Ram Down Air Regulator
CB
Controls the ram down pressure.
Ram Director Valve
CC
Controls the ram direction.
Ram Up Air Regulator
CD
Controls the ram up pressure. CE
Ram Down Air Gauge
Displays the ram down pressure.
Ram Up Air Gauge
CF
Displays the ram up pressure.
Blowoff Button
CG
Turns air on and off to push the platen out of an empty
drum.
CH
Blowoff Pressure Gauge
Displays the blowoff pressure.
Blowoff Air Regulator
CJ
Controls platen blowoff pressure.
Air Motor Air Regulator
CK
Controls the air pressure to the motor.
Air Motor Pressure Gauge
CL
Displays the air pressure to the motor.
Air Motor Slider Valve
CM
Turns air on and off to the air motor. When closed, the valve relieves air trapped between it and the motor. Push the valve in to shut off air. Can be locked in the closed position.
Air Motor Solenoid Valve
CN
Turns air on and off to the air motor when system stopped on the ADM. When closed, the valve relieves air trapped between it and the motor.
10 334130T
Page 11

Electrical Control Enclosure

Back Panel With Transformer
DL
DJ
DH
DG
DF
DN
DE
DM
DC
DD
DB
DA
DK
Component Identification
FIG. 3: Electrical Enclosure
Key:
DA Multi-Zone Low Power Temperature Control Module
(MZLP) DB Ventilation Grill DC Electrical Control Panel DD Automatic Wiring Board (AWB) DE Power Supply (24V) DF Residual Current Device (GFI), 63A
334130T 11
DG Platen SSR (65A) DH Platen Contractor DJ Platen Fuse DK Transformer Circuit Breaker DL Transformer Fuse DM Transformer DN System Contactor
Page 12
Component Identification
BB
BC
BD
BE
BF
BA
BH
BG
System Shutdown
Enable/Disable

Advanced Display Module (ADM)

The ADM display shows graphical and text information related to setup and spray operations. For detail on the display and individual screens, see Appendix A - ADM, page 100.
Use the USB port on the ADM to download or upload ta. For more information about the USB data, see
pendix B - USB Data, page 109.
Ap-
da-
NOTICE
To prevent damage to the softkey buttons, do not press buttons with sharp objects such as pens, plastic cards, or fingernails.
FIG. 4: Front View
Key Function
BA Heating system and Pump Enable/Disable BB System status indicator (LED) BC Stop all system processes BD Defined by icon next to softkey BE Abort current operation BF Accept change, acknowledge error, select
item, toggle selected item
BG Toggle between Operation and Setup
screens
BH Navigate within a screen or to a new screen
12 334130T
Page 13
FIG. 5: Back View
BK
BL
BM
BN
BP
BR
BK Part Number and Identification Label BL USB Interface BM CAN Cable Connection (Power Supply and
Communication) BN Module Status LEDs BP Light Tower (Optional) BR Software Token Access Panel
Component Identification
Table 1 ADM LED Status Descriptions
LED Conditions Description System Status Green Solid Run Mode, System On
Green Flashing Setup Mode, System On Yellow Solid Run Mode, System Off
USB Status (BL) Green Flashing Data recording in progress
Yellow Solid Downloading information to USB Green and Yellow Flashing ADM is busy, USB cannot transfer
information when in this mode
ADM Status (BN) Green Solid Power applied to module
Yellow Solid Active Communication
Red Steady Flashing Software upload from token in prog-
ress
Red Random Flashing or Solid Module error exists
334130T 13
Page 14
Component Identification

Screen Components

1. Screen Order
2. Current date and time
3. Operating Mode
4. Faults, Status
5. MZLP Plug Identifier
6. Zone Setpoint Temperature
7. Zone Actual Temperature
Operating Mode Description Component Status
System Off The system does not have power. No system status indicator LED on the
ADM
No heat
Pump is off
Inactive The heating system and pumps are dis-
abled.
Warm Up The system is heating the material to the
setpoint temperature.
Heat Soak Heat zones are all at temperature. Material
is soaking for a user specified amount of time.
Ready All enabled zones are at setpoint tempera-
ture. The Air Motor does not have power.
Active The system is ready to dispense. Solid green system status indicator LED
Yellow system indicator LED on the ADM
No heat
Pump is off
Flashing green system status indicator LED on the ADM
Heat is increasing to setpoint temperature
Pump is off
Flashing green system status indicator LED on the ADM
Heat is at setpoint
Material is absorbing more heat
Pump is off
Heat soak counter counts down on the Home screen.
Flashing green system status indicator LED on the ADM
Heat is at setpoint
Pump is off
on the ADM
Heat is at setpoint temperature
Pump is on
14 334130T
Page 15

Overview

Overview
A Heated Platen melts the sealant or adhesive and rects the molten material to the Pump inlet. The then travels through a Heated Pump and moves to the application tool.
heated fluid
material
di-

Air and Fluid Hoses

The Therm-O-Flow requires Graco single-circuit rial hoses rated at a maximum of 1250 watts. all air and fluid hoses are properly sized
for the system.
mate-
Make sure

Heat Control Zone

The Therm-O-Flow has 4, 8, or 12 heat zones. Zones for the Heated Drum Platen and the Heated Pump are not included in the zone count. Zones 1 and 2, 5 and 6, 7 and 8, 9 and 10, and 11 and available through 12-pin connectors. The heated hoses have a 16-pin connector at the nector at the outlet. All heated heaters are equipped with an
inlet, and an 8-pin con-
valves, manifolds, and
8-pin mating connector.
12 are each
3 and 4,
FIG. 6: Heat Control Zone Selection
334130T 15
Page 16

Setup

Setup
1. Unpack the Ram
2. Locate and Install the Ram
3. Mechanical Setup
4. Connect hoses to Electrical Control Panel
5. Connect Electrical Control Panel to power source
6. Ground system
7. Select ADM settings

Unpack

1. Inspect the shipping box carefully for damage. Con-
tact the carrier promptly if there is damage.
2. Open the box and inspect the contents carefully. There should not be any loose or damaged parts in the box.
3. Compare the packing slip against all items in the
box. Repost any shortages or other inspection prob-
lems immediately.
4. Remove the unit from the skid and place it in the desired location. See Location Requirements.
5. Make sure there is easy access to an appropriate electrical power source. The National Electrical Code requires 3 ft (0.9 m) of open space in front of the electrical panel. Comply with all local codes and regulations.
6. For hydraulic rams, locate the hydraulic power sup-
ply in an area that has:
easy access for servicing and adjusting the
hydraulic pressure on the supply unit
sufficient clearance for the hydraulic lines that
attach to the Pump
easy access to read the hydraulic fluid level
gauge

Install System

Refer to Dimensions, page 112 for mounting and ance dimensions.
Follow all Location Requirements, page 16, when selecting a location for the Ram.
1. Apply 50 psi download pressure to Ram.
2. Wrap the bar with the lifting sling.
clear-

Location Requirements

1. Make sure there is sufficient overhead clearance for the Heated Pump and Ram when the Ram is in the fully raised position (approximately 110 in. (280 cm)).
2. If you are installing a vent hood, make sure there is sufficient horizontal clearance for it. Locate the Ram near a connection to the factory ventilation system.
3. Make sure the air regulators for the Heated Pump and Ram are fully accessible, with room to stand directly in front of the Pneumatic Control Panel and the Electrical Control Panel.
4. When locating the system, do not install closer than 36 in. (914 mm) to vertical surfaces.
3. Lift the system off the pallet using a crane or a lift and place in desired location.
4. Level the base of the Ram, using metal shims.
5. Bolt the Ram to the floor, using anchors that are long enough to prevent the unit from tipping.
fork-

Install Hydraulic Power Supply

See the Ram manual for installation and dimensions.
16 334130T
Page 17
Setup
H
B
A
C1
C2

Mechanical Setup

1. Fill displacement Pump wet cup 2/3 full with Graco
Throat Seal Liquid (TSL™) for Butyl and PSA mate-
rials.
NOTE: Use IsoGuard Select for PUR or reactive Polyurethane material. IGS is designed to dissolve and suspend the Polyurethane materials. IGS will solidify after a period of time and should be replaced once the solidified lube does not
return to liquid form after heating.
®
(IGS) (part no. 24F516)
4. Ensure Drum Low and Empty Sensors (C) are mounted as shown.
NOTE: The Drum Low and Empty Sensors are indicate that a drum is empty. mounting and a cable for connecting the panel Enclosure.
bracket (A), activator (B), sensors (C1, C2),
The kit contains a sensor
inside the Electrical
used to
FIG. 7: Wetcup
2. Turn all air regulators to their full counterclockwise position. See Integrated Air Controls, page 10.
3. Connect a 1/2 in. (13 mm) air line from an air source to the system air inlet (H), capable of delivering a minimum of 25-50 cfm at 100 psi (0.7 MPa, 7.0 bar).
Do not use quick disconnects.
5. Increase the distance between the low (C1) and empty (C2) sensors to increase the heat up time for the tandem secondary system. Lower the drum empty sensor (C2) to force the Heated Platen lower into the drum. If empty sensor is set too low, the Pump could cavitate and cause an alarm.
FIG. 8: Air Connection
334130T 17
Page 18
Setup

Install Heated Hose

To connect a hose to a fluid control device or heated manifold.
1. Install fitting and heated hose onto Pump outlet with
the large electrical connector side toward the sys-
tem. Use 2 wrenches to tighten hose. Torque to 45 ft-lbs (61 N•m).
NOTE: See Accessories and Kits, page 92, for avail-
able fittings and heated hoses.
5. For proper operation, cables must be plugged into zones 1–2 and 3–4 at all times.
6. Install cap on any unused MZLP electrical connec-
tors.
7.
Connect the small 8 pin connector from the heated hose to the fluid control device or heated manifold.
FIG. 9
2. Wrap exposed fittings on the Pump outlet with
Nomex insulation and secure insulation using fiber-
glass tape.
3. Connect large heated hose connector to MZLP.
4. Repeat for any remaining channels.
FIG. 10: Heated Manifold 243697
NOTE: The heated manifold (part no. 243697) shown.
See Accessories and Kits, page 92, for available man-
ifolds and fluid control devices.
8. Use 2 wrenches to tighten hose. Torque to 45 ft-lbs (61 N•m).
9. To connect multiple devices, see Connect Multiple Devices, page 19.
18 334130T
Page 19
Setup

Connect Multiple Devices

If your application requires multiple fluid control devices:
Connect heated hose electrical connections to the Electrical Enclosure. Remove from shipping box to connect heated hoses to the Electrical Enclosure. For additional cables, heated hose, and fluid control devices, see Accessories and Kits, page 92.
Connect fluid control devices to a heated hose or
the Electrical Enclosure. Use accessories if neces-
sary.
Setup all heat zones on Heat-A and Heat-B screens.
Example: Heated zones used to connect a primary and secondary system to a manifold and two guns. A-# zones are on the Heat-A screen and B-# zones are on
the Heat-B screen.
FIG. 11
334130T 19
Page 20
Setup

Connect Power

The Electrical Control Panel comes already attached and wired to the Ram, however before the supply unit becomes functional you must connect the Electrical
Control Panel to a power source.
All electrical wiring must be done by a qualified elec­trician and comply with all local codes and regula-
tions.
NOTE: Required voltage and amperage is noted on the control panel label. Before running power to the unit, make sure the plant electrical service meets the
machine’s electrical requirements. Branch circuit protec-
tion shall be provided by the end user.
Use copper conductors rated 600 volts minimum and 167°F (75°C) minimum only. Torque to 55 in-lb (6.2 N•m).
Table 2 Electrical Requirements
Electrical
Panel
Voltage Hz Phase Platen
230 V 50/60 3 EF, ES 90 3 AWG
EM 100 3 AWG
400 V/N 50/60 3 EF, ES 45 8 AWG
EM 50 8 AWG
400 V 50/60 3 EF, ES 45 8 AWG
EM 50 8 AWG
480 V 50/60 3 EF, ES 45 8 AWG
EM 50 8 AWG
600 V 50/60 3 EF, ES 50 8 AWG
3EM508 AWG
Full
Load
Amps AWG
FIG. 12
To reduce the risk of fire, explosion, or electric shock, the resistance between the supply unit components and true earth ground must be less than 0.25 ohms.
3. Connect the ground wire to the ground lug. Have a qualified electrician check the resistance between each Therm-O-Flow system ground and the true earth ground. The resistance must be less than 0.1 ohms. If the resistance is greater than 0.1 ohms, a
different ground site may be required. Do not oper-
ate the system until the problem is corrected.
NOTE: Use a meter that is capable of measuring resis-
tance at this level.
EF Standard Finned Bottom EM Mega-Flo ES Smooth Bottom
1. Locate the opening in the control panel’s top hous-
ing for the conduit that will enclose the wire from the facility’s power source. The hole will accept a cord diameter range of 0.7–1.2 in (17–30 mm).
2. Thread the wire from the power source into the con-
trol panel housing, and then connect the power source wires to the appropriate terminals on the DISCONNECT switch.
20 334130T
Page 21
Setup
AC
SC
SS

Grounding

Ground the unit as instructed here and in the compo-
nent manuals.
The equipment must be grounded to reduce the risk of static sparking and electric shock. Electric or static sparking can cause fumes to ignite or explode. Improper grounding can cause electric shock. Grounding provides and escape path for the electric current.
System: ground through ground lug in Electrical Enclo-
sure. See Connect Power, page 20.
Air and Fluid Hoses: use only electrically conductive hoses.
Air compressor: follow manufacturer’s recommenda-
tions.
Spray gun / Dispense valve: ground through connec-
tion to a properly grounded fluid hose and Pump.
Material drums: follow local code. Use only metal drums placed on a grounded surface. Do not place the drum on a nonconductive surface, such as paper or cardboard, which interrupts the grounding continuity
To maintain grounding continuity when flushing or relieving pressure: follow instructions in your separate
gun manual for instructions on how to safely ground your gun while flushing.

Connect Secondary System

A secondary system is a Therm-O-Flow supply system that connects to the primary Therm-O-Flow system, with the ADM. See Models, page 7 for secondary system model numbers.
1. Connect adapter cable (AC) and communication cable (SC) to the secondary Electrical Enclosure
and rout to splitter (SS) installed on the primary sys-
tem.
2. To enable a secondary system, select “Enable Tan-
dem System” on the System 1 screen. See Select
ADM Settings, page 24.
FIG. 13
334130T 21
Page 22
Setup

Check Sensor Resistance

To reduce risk of injury or damage to equipment, con-
duct these electrical checks with the Main Power Switch OFF.
The package includes up to twelve heat sensors and
controllers for each of the heated zones. To check sen-
sor resistance:
1. Turn Main Power Switch OFF.
2. Wait for components to cool down to ambient room temperature 63°-77°F (17°-25°C). Check electrical resistance for the components.
MZLP Pins TOF Hose
First Heat Zone A, J Second Heat Zone C, D First RTD G, K Second RTD M, K Earth Ground B
Table 3 RTD Sensors
MZLP MZLP Plug Component
Ram Plate 100 +/- 2 Fluid Pump 100 +/- 2 Heated
1, 2
1
3, 4
5, 6
2
7, 8
9, 10
3
11, 12
Accessory 1 Heated Accessory 2 Heated Accessory 3 Heated Accessory 4 Heated Accessory 5 Heated Accessory 6 Heated Accessory 7 Heated Accessory 8 Heated Accessory 9 Heated Accessory 10100 +/- 2
Heated Accessory 11100 +/- 2
Heated Accessory 12100 +/- 2
RTD Range
(Ohms)
100 +/- 2
100 +/- 2
100 +/- 2
100 +/- 2
100 +/- 2
100 +/- 2
100 +/- 2
100 +/- 2
100 +/- 2
3. Replace any parts whose resistance readings do
not comply with the ranges listed in the RTD Sen-
sors chart below.
22 334130T
Page 23
Setup

Check Heater Resistance

To reduce risk of injury or damage to equipment, con-
duct these electrical checks with the Main Power Switch OFF.
1. Turn Main Power Switch OFF. 2. Make electrical resistance checks for the compo-
nents.
3. Replace any parts whose resistance readings do not comply with the ranges listed in tables.
NOTE: Check resistance at ambient room temperature 63°-77°F (17°-25°C).
Table 4 Heaters
Component
Platen
Pump
Resistance Across Terminals
AD to BE, BE to CF, CF to AD
A to B, B to C, C to D, D to E, E to F and F to A380 - 600V
Any terminal to Ground
2610 to 2620 T1/B1 to T3/B3
Unit Input Voltage
220 - 240V
All voltage ver-
sions
All voltage ver-
sions
Platen or Pump Module Resistance Values
24V633 5.25 to 4.35 Ohms
24V634 & 24V635 6.36 to 4.8 Ohms
24V633 12.0 to 14.5 Ohms
24V634 & 24V635 13.5 to 18 Ohms
All Greater than 100,000 Ohms
All 43.2 to 53 Ohms
334130T 23
Page 24
Setup

Select ADM Settings

NOTE: See Appendix A - ADM, page 100 for detailed
ADM information, including general operation.
1. Turn Main Power Switch ON.
2. When the ADM is finished starting up, press to switch from the Operation screens to the Setup screens. Use the arrows to navigate between screens.
3. Check system settings on the System 1 screen.
5. Set primary system setpoint and setback tempera-
tures for the Pump, Platen, and heat zones on the Heat-A-screens.
NOTE: Setback temperatures must be at least 20°F (10°C) lower than the setpoint temperatures.
NOTE: To ensure accurate hose temperatures, be sure all heated hoses have their “zone type” set to “Hose.” Hoses are only present on odd zone numbers: 1, 3, 5, 7, 9, or 11.
4. Set alarm levels on the System 2 screen.
a. Select the appropriate “Zone Type” for all
installed zones.
b. Check the “A” and “B” boxes according to which
systems needs to use the heated accessory.
6. If a secondary system is used, set temperatures on the Heat-B-screens.
7. Set the system date and time on the Advanced 1 screen.
24 334130T
Page 25
Setup
8. Set the temperature and mass units on the Advanced 2 screen. Set the specific gravity of the material for Material Tracking functionality.
NOTE: If the Specific Gravity is set to zero, the Home screen will display a cycle counter instead of grams or pounds.
9. To setup the optional Schedule function, see Schedule, page 37. The schedule function allows the system to automatically enable and disable heating and setback at specified times.
10. Optional: Set any remaining settings in the Setup screens before using the system. These are not required for system operation, but include useful functions. See Appendix A - ADM, page 100 for detailed information about each setup item.
334130T 25
Page 26
Setup

Connect PLC (Hard Wired Interface Version)

A PLC can control and monitor all items shown in the
Customer Digital Inputs and Outputs shown on the Diag-
nostics screen. See Appendix A - ADM, page 100.
When the PLC has control of the system:
Functionality is restricted from the ADM
Automatic crossover is disabled. Rely on the PLC and machine state indicators to know when to cross over using the I/O.
Table 5 Customer Input
Signal No. Unit A Description
1 Heat On Request Turn on the Heat
2 Setback Request Put the Unit in Set-
back 3 Pump On Request Turn on the Pump 4PLC Control
Request (input applies to primary unit A only)
Table 6 Customer Output
Control the primary
and secondary TOF
systems from the
PLC instead of the
ADM
Table 7 Output Error States
Error State
Bit High Error State Bit Low
0 0 Machine is good, no
errors are present
0 1 Active Unit Drum
Low
1 0 Active Unit Drum
Empty
1 1 Alarm Present in
System
Table 8 Output Run States
Run State
Bit High Run State Bit Low
0 0 Pump Off/ Heat Off 0 1 Pump Off/ Heat On 1 0 Pump Off/ Heat At
Temp
1 1 Pump On/ Heat At
Temp
NOTE: All outputs are normally open when power is off. For error (alarm) output, the contacts close when an alarm occurs. For all others, contacts close.
NOTE: The TOF system ships with two screw terminal connectors that plug into MZLP connectors H1 and H2. Connectors are located in a bag on the inside of the Electrical Enclosure. To replace the connectors, order kit 24P176.
Signal No. Unit A or B Description
1 Run State Bit Low See Run State
Chart 2 Run State Bit High See Run State
Chart 3 Error State Bit Low See Error State
Chart 4 Error State Bit High See Error State
Chart
26 334130T
1. Turn Main Power Switch OFF.
2. Open the Electrical Enclosure door.
3. Route I/O cables through strain relief.
4. Remove power from the PLC.
5. Connect the PLC to connectors H1 and H2.
Page 27
NOTE: Each connector has four signals. The MZLP board specifies the input range for each signal. See the
following table for pin assignments.
FIG. 14
Setup
H1 Customer Input
Signal Pin
11,2 23,4 35,6 47,8
H2 Customer Output
Signal Pin
11,2 23,4 35,6 47,8
Inputs: High: 10–30 VDC, Low: 0–5 VDC. Inputs func-
tion without concern for polarity. Applying “high” voltage will turn the heaters on and enable setback. Removing voltage will turn the heaters off and disable setback.
Outputs: 0–250 VAC, 0–30 VDC, 2A Maximum.
334130T 27
Page 28
Setup
PLC Connections Block Diagrams
The following block diagrams show how to connect customer inputs and outputs to the MZLP. For convenience, each system ships with connector kit 24P176. If a connector is lost or damaged, order kit 24P176 for replacements.
FIG. 15: Customer Input
FIG. 16: Customer Output
28 334130T
Page 29

Operation

1. Turn the Main Power Switch ON. The Graco logo will display until communication and initialization is complete.
Operation
NOTICE
Use fluids that are chemically compatible with the
equipment wetted parts. See Technical Specifica-
tions in all of the equipment manuals.
1. Select the material for the initial material load.
2. Verify whether the factory-test oil and the initial material load are compatible:
a. If the two substances are compatible omit the
remaining steps in this procedure and refer to Load Material, page 30.
b. If the two substances are incompatible perform
the remaining steps in this procedure to flush the system.
2. Press the button. Verify the machine is in “Warm Up” state, and that the temperatures are increasing. Allow the system to reach the “Ready” state before pumping. The Pump will automatically turn on, if autostart is enabled in setup screens,
when all the heat zones reach their setpoint tem-
perature.

Purge System

NOTICE
Purge the system before initial use and when chemi-
cals are changed to prevent material contamination, which may cause the material to fail or perform poorly. The system was factory- tested using a light soluble oil, a soybean oil, or some other oil as tagged. Flush the system to avoid contaminating the material that has been designated for initial material loading.
3. Select a drum of material that can eliminate the fac-
tory-test oil from the system. If necessary, check
with Graco or the material supplier for a recom-
mended solvent.
4. Before purging be sure the entire system and waste drum are properly grounded. See Grounding, page
21.
5. Turn all heat zones’ setpoint temperature to the material manufacturer’s recommended dispense
temperature, or a minimum of 100°F (37°C) mini-
mum.
NOTE: Remove any dispense valve orifices before purging. Reinstall after purging has been completed.
6. Purge the material through the system for approxi-
mately 1 to 2 minutes.
7. Remove the drum if purge material was used. See Change Drums, page 38.
334130T 29
Page 30
Operation
CA
CD
CC

Load Material

NOTICE
To prevent damage to Platen wipers, do not use a drum of material that has been dented or damaged. An empty drum clamp can interfere with up and down operation of the Ram. When raising the Ram, make sure the drum clamp stays clear of the Platen.
NOTE: Before loading material, make sure there is a minimum overhead clearance of 110 in. (280 cm) and all
air regulators are backed off to their full counterclock-
wise position.
1. Open the Main Air Slider Valve (CA).
4. Fill displacement pump wet cup 2/3 full with Graco
Throat Seal Liquid (TSL™) for Butyl and PSA mate-
rials.
NOTE: Use IsoGuard Select for PUR or reactive Polyurethane material. IGS is designed to dissolve and suspend the Polyurethane materials. IGS will solidify after a period of time and should be replaced once the solidified lube does not
return to liquid form after heating.
FIG. 18: Wetcup
®
(IGS) (part no. 24F516)
2. Set Ram Director Valve (CC) to UP and slowly turn the Ram Up Regulator (CD) clockwise until the
Platen (G) begins to rise.
5. Open drum, remove any packing material, and inspect material for any contamination.
6. Slide the drum between the drum centering guides
and against the stops at the back of the Ram base-
plate.
FIG. 17: Raise the Platen
3. Apply a thin coating of high temperature grease lubricant (part no. 115982) to the Platen drum seals.
30 334130T
FIG. 19: Drum Placement
Page 31
Operation
R
CC
CB
7. Remove the Ram Plate Bleed Stick (R).
FIG. 20: Platen Bleed Handle
8. Set Ram Director Valve (CC) to down.

Heat Up System

To reduce the risk of bursting a hose, never pressur-
ize a hot melt system before turning on the heat. The
air will be locked from the Air Motor until all tempera­ture zones are within a preset window of the tempera-
ture setpoints.
Keep the dispense valve open over a waste container while the system is heating up and also when cooling down. This will prevent a pressure build-up caused by fluids or gases expanding from the heat.
NOTE: Operate at the lowest temperature and pressure necessary for your application.
1. Turn the Main Power Switch on the Electrical Con-
trol Panel door to the ON position.
2. Press the button. The zones begin to heat
(provided they are enabled). Press if the zones do not begin to heat. Display status bar reads Warm Up. When temperature reaches setpoint, the display status bar reads Heat Soak. When heat is on, the status will display in the status bar. See Advanced Display Module (ADM), page 12, for operation mode descriptions.
NOTE: The air will be locked from the Air Motor until all
FIG. 21: Lower the Platen
9. Slowly turn the Ram Down Air Regulator (CB) clock-
wise to approximately 5–10 psi (34–69 kpa, 0.3–0.7 bar). The Platen will begin to lower into the drum.
10. After the Platen seals enter the material drum, adjust the Ram Down Air Regulator (CB) to 30–50 psi (207–345 kPa, 2.1–3.4 bar).
11. When the Ram stops, reinsert the Ram Plate Bleed Stick (R) and hand tighten.
temperature zones are within a preset window of the temperature setpoints, allowing the system to heat fully and complete the material heat soak period.
334130T 31
Page 32
Operation
CK
CN
CM
CK
Z

Prime Pump

1. Ensure that the system has completed the heat soak cycle. The display status bar should read Active.
2. Adjust the Air Motor Air Regulator (CK) to 0 psi.
3. Adjust the Air Motor Slider Valve (CM) to the open position.
4. Adjust the Air Motor Air Regulator (CK) to approxi-
mately 20 psi (138 kPa, 1.38 bar).
5. Place a waste container under the bleed stem (Z). Using an adjustable wrench, open the bleed stem counterclockwise 1/3 -1/2 turn.
32 334130T
Page 33
Operation
CA
6. If a new drum was installed and the unit is equipped
with proximity sensors, press the Pump Ready but-
ton . Press the pause button on material tracking.
7. Adjust the Air Motor Air Regulator (CK) up by 5 psi (34 kPa, 0.3 bar). Never adjust the regulator by more than 5 psi (34 kPa, 0.3 bar) increments. Make sure the Pump begins to cycle and heated material flows from the bleed stem (Z) after several cycles of the Pump.
8. Prime the Pump until it moves smoothly in both directions with no air popping or erratic movement and close the bleed stem (Z).
For Tandem Operation
Complete steps 1-5 on page 32 for the inactive unit. Note that the heat will remain on for the inactive unit until the system is turned off.
6. If a new drum has been installed in the inactive unit,
press the Pump Ready button on the inactive unit. The light on the solenoid of the inactive unit should be on (CN).
7. Adjust the Air Motor Air Regulator (CK) up by 5 psi (34 kPa, 0.3 bar). Never adjust the regulator by more than 5 psi (34 kPa, 0.3 bar) increments. Make sure the Pump begins to cycle and heated material flows from the bleed stem (Z) after several cycles of the Pump.
8. Prime the Pump until it moves smoothly in both directions with no air popping or erratic movement and close the bleed stem (Z).
9. Press the Pump Ready button for the inactive unit.
9. Press the Play button on the home screen to enable material tracking and press the Pump Ready button.
334130T 33
Page 34
Operation
CA
Z

Prime System

1. Close the Main Air Slider Valve (CA).
2. If using a manual gun, lock the dispense valve trig-
ger open by pulling and securing the trigger using the trigger retainer (Z).
7. Close the Main Air Slider Valve (CA) and release the trigger lock.
8. Engage the trigger lock.
FIG. 22: Trigger Lock Engaged
9. Press to engage material tracking.
10. Turn the Air Motor regulator to operating pressure.
3. Place the dispense valve over a waste container.
4. Press the pause material tracking button on home screen.
5. Slowly open the Main Air Slider Valve (CA).
6. Prime the system until a smooth flow of material dis-
penses from each dispense valve.
NOTE: On initial system startup, the Pump will cycle until the hoses are filled. If a new drum was placed on the frame, the Pump will cycle until all air has been removed.
NOTE: The amount of time before the Pump is automat­ically placed in setback is determined by the Pump Inac-
tivity Timeout, located on System Setup Screen 1. See
Setup Screens, page 104.

Setback Mode

Set the ADM to setback mode if the system will only be inactive for a few hours. This will reduce the time the system needs to return to setpoint temperatures.
1. Press to enter Setback Mode.
NOTE: The amount of time before the Pump is automat­ically placed in setback is determined by the Pump Inac-
tivity Timeout, located on System Setup Screen 1. See Setup Screens, page 104.
34 334130T
Page 35
Operation
CA
CC

Pressure Relief Procedure

Follow the Pressure Relief Procedure When-
ever you see this symbol.
This equipment stays pressurized until pressure is manually relieved. To help prevent serious injury from pressurized fluid, such as skin injection, splashing fluid and moving parts, follow the Pressure Relief
Procedure when you stop spraying and before clean-
ing, checking, or servicing equipment.
NOTE: If using a different dispense applicator, see the applicator manual for pressure relief instructions.
1. Engage the trigger lock.
3. Set the Ram Director Valve (CC) to the neutral posi-
tion.
4. Disengage the trigger lock.
FIG. 24: Disengaged
FIG. 23: Engaged
2. Close the system Main Air Slider Valve (CA).
334130T 35
5. Hold a metal part of the gun firmly to a grounded metal pail. Trigger the gun to relieve pressure.
6. Engage the trigger lock.
7. Open all fluid drain valves in the system, having a waste container ready to catch drainage. Leave drain valve(s) open until you are ready to dispense again.
8. If you suspect the tip or hose is clogged or that pres-
sure has not been fully relieved after following the
steps above, VERY SLOWLY loosen hose end cou­pling to relieve pressure gradually, then loosen com-
pletely. Clear hose or tip obstruction.
Page 36
Operation
System Shutdown
NOTE: If work needs to be performed on the Ram por-
tion, perform the following additional steps to relieve any trapped air in the inactive portion of the Ram.
9. Validate that the Heated Pump is fully supported and is resting on the bottom plate.

Stop Controls

Normal Stop Control
To stop all electrical and most pneumatic processes,
press the System Shutdown button located on the ADM.
10. Toggle the Ram Director Valve up and down to relieve any trapped air.
All electrical operations will be shut down and the air pressure to the Air Motor will be immediately relieved, which will stop the movement of the Heated Pump.
Electrical components located in the main control box will remain energized, but all operations will stop until
the system Enable/Disable button has been pressed.
The Ram Director Valve will remain operable.
Air Motor and Heated Pump Stop
To stop only the Air Motor and Heated Pump, close the Air Motor Slider Valve (CM). This is the preferred method while changing drums.
36 334130T
Page 37
Operation
CM

Shutdown

1. Press to disable the heaters and Pump. The screen will say “Inactive”. If using the Schedule function, the heaters and Pump will be disabled
automatically at the set time. Only press to disable the heating system before the set time. If the
heaters were manually disabled, the Schedule func-
tion will automatically enable them at the next set time.
Air pressure to the Air Motor will be immediately relieved, which will stop movement of the Heated Pump but allow the heater to remain operable.
The Ram Director Valve will also remain operable.
The Air Motor Slider Valve can be locked in the closed position.
Total System Shutdown
To stop all electrical and most pneumatic processes, turn the Main Power Switch OFF.
This will remove all electrical power to the system past the Main Power Switch.
Air pressure to the Air Motor will be relieved, which will stop movement of the Heated Pump.
NOTE: Do not perform step 2 if using the Schedule function. Leave the power on.
2. Turn the Main Power Switch OFF.

Schedule

The Schedule function allows the user to specify times when the system will automatically turn on and off the heaters and Pump.
The Ram Director Valve will remain operable.
The Main Power Switch can be locked in the open posi-
tion.
334130T 37
Page 38
Operation
Table 9 Schedule Screen Color Identification
Color Description
Green System on Yellow Setback Red System off Gray Disabled
Set Schedule Times
Times are set using a 24-hour clock. Several on and off times can be set each day.
Use the Schedule Function
At the end of the work day leave the Main Power Switch ON. The Schedule function will automatically enable and disable the heaters and Pump at the specified times.

Change Drums

To prevent serious burns from dripping material, never reach under the Heated Platen after the Platen is out of the drum.
Moving parts can pinch or amputate fingers, or can
crush feet. When the Pump is running, and when rais-
ing or lowering the Ram, keep fingers and hands away from the Pump intake, Platen, and lip of the drum. When lowering the Platen to the baseplate, keep feet away from the Platen.
1. On the Schedule screen (in the Setup screens), set the ON times for each day of the week
2. Set the off times for each day of the week.
3. Set the setback times for each day of the week.
Enable Schedule Function
The Schedule function is automatically enabled when values are entered in the Schedule screen. To disable a
scheduled event, navigate to the event and press .
The event will appear gray on the screen when it is dis-
abled. To re-enable an event, navigate to the event and
press .
The event will appear red (system off), yellow (system setback), or green (system on). If no events are needed, turn the Main Power Switch OFF to prevent system from automatically enabling and disabling the heaters.
Perform the following procedure to change the drum on a fully heated system.
NOTICE
Be sure to reload the empty supply unit with a full drum of material immediately. Do not raise the Ram
and remove the Platen from the empty drum until you are ready to immediately install a new drum.
Do not raise the Ram and remove the Platen from the empty drum unless the supply unit is at full operating temperature. Drum changes can only be
performed when the system is heated.
An empty drum clamp can interfere with the up and down operation of the Ram. When raising or lowering
the Ram, make sure the drum clamp stays clear of the Platen assembly.
Do not use a drum of material that has been dented or otherwise damaged; damage to the Platen wipers
can result.
38 334130T
Page 39
All systems include Low/Empty Sensors:
CM
CC
CG
The air will shut off to prevent the Pump from cavita-
tion. If the Light Tower kit is installed, a solid red light indicates that the pail is empty and ready to change.
In a tandem system, a flashing red light means that
both drums are empty and the system has shut-
down.
Operation
Excessive air pressure in the material drum could cause the drum to rupture, causing serious injury. The Platen must be free to move out of the drum. Never use drum blowoff air with a damaged drum.
4. Release the blowoff air button and allow the Ram to rise to its full height.
1. Press to stop material tracking.
2. Push in the Air Motor Slider Valve (CM) to stop the Pump.
3. Set Ram Director Valve (CC) to UP and raise the Platen (G) and immediately press and hold the Blowoff Buttons (CG) until the Platen is completely
out of the drum. Use minimum amount of air pres-
sure necessary to push the Platen out of the drum.
5. Remove the empty drum.
6. Inspect Platen and if necessary, remove any remaining material or material build-up.
7. Follow steps in Load Material, page 30, and Prime Pump, page 32.
334130T 39
Page 40

Troubleshooting

Troubleshooting

Light Tower (Optional)

Signal Description
Red Light Off If green light is also off, system power may be off or system operating mode is Inactive. If
green is on or flashing, there are no active errors Red Light On User interaction required — alarm, system is shut down Red Light Flashing User interaction required — advisory, deviation, or system is in a state that could prohibit
dispensing Green Light Off System is inactive Green Light On System is ready to dispense. The heat and Pump are on. Green Light Flashing System will be ready to dispense in time without user interaction (heat on, Pump off, and
temperature control zones have not reached set point)
40 334130T
Page 41
Troubleshooting

Error Codes

There are three types of errors that can occur. Errors are indicated on the display as well as by the optional Light Tower.
Alarms are indicated by . This condition indicates a parameter critical to the process has reached a level requiring the system to stop. The alarm needs to be addressed immediately.
Deviations are indicated by . This condition indicates a parameter critical to the process has reached a level requiring attention, but not sufficient enough to stop the system at this time.
Advisories are indicated by . This condition indicates
a parameter that is not immediately critical to the pro­cess. The advisory needs attention to prevent more seri-
ous issues in the future.
To acknowledge the error, press .
The last digit of the error code indicates which system component the error applies. The “#” (pound) character
indicates the code applies to multiple system compo-
nents.
Code Relates To System
Last Digit “#”
1MZLP 1 2MZLP 2 3MZLP 3 5MZLP 5 6MZLP 6 7MZLP 7 G Gateway (CGM) H Gateway Heartbeat Loss VAWB Unit A WAWB Unit B X Daughter Board Unit A Y Daughter Board Unit B
The last digit of the error code indicates which heat zone
the error applies. The “_” (underscore) character indi-
cates the code applies to multiple system components.
Component:
The third digit, or sometimes the last digit of the error
code, indicates which unit the error is active on. The “★”
(star) character indicates the code applies to multiple system components.
Third or Last Digit “★” Code Relates To:
AUnit A BUnit B
Code Relates To Heat
Last Digit “_”
1 Zone 1 2 Zone 2 3 Zone 3 4 Zone 4 5 Zone 5 6 Zone 6 7 Zone 7 8 Zone 8 9 Zone 9 A Zone 10 B Zone 11 C Zone 12 DPump EPlaten
Zone:
334130T 41
Page 42
Troubleshooting
Code Description Type Cause Solution
A3MF
AWB Clean Fan Filter
Alarm
Cooling inlet
Clean inlet screen.
screen is dirty
A4 _
High Current Unit _ Zone _
Alarm
Defective or shorted to ground on
Verify accessory is rated for 240 VAC.
Verify heater resistance and check for shorts to ground. Replace as necessary.
zone
A4C#
High Current Fan AWB, Unit _
Deviation Fan is drawing
too much cur-
rent
Verify there is not an air obstruction at the inlet/outlet of enclosure. Verify nothing is preventing fan rotation. Replace fan if necessary.
A7 _
A8 _
Unexp. Curr. Unit _ Zone _
No Current Unit _ Zone _
Alarm
Unexpected current flow to zone
Alarm No Current
Flow to the Zone
Replace MZLP.
Faulty accessory heater. Measure resistance to ground between heater leads.
Check for loose or disconnected wires or plugs.
Check for blown fuses on MZLP.
Check heater resistance for open circuit.
Check for shorts between heater and ground.
Verify cable is plugged into zones 3-4. Replace heater if necessary.
A8C
AWB No Fan Current
Alarm Cooling Fan
Verify fan is plugged in. Replace if necessary.
not Working
AM3#
High Current SSR MZLP _
Alarm
Excessive current flow in
Check for shorts in harness to SSR. Check polarity of wiring to SSR. Replace if necessary.
the SSR
AM4#
High Current Contactor MZLP _
Alarm
Defective or shorted to ground on
Check for shorts in the harness to contactor. Check the polarity to contactor. Replace contactor if necessary.
MZLP
AM8#
CAC#
No Current Contactor MZLP _
Comm Error MZLP _
Alarm
Alarm
No Current Flow to the Contactor
System not responding to ADM.
Ensure harness to MZLP is connected. Ensure wiring to contactor is secure. Replace contactor if necessary.
System is not properly loaded with correct Soft-
ware.
Dial not set correct on MZLP. Duplicate MZLP dial positions (i.e. 1 to 1, 2 to 2, ect).
Check all CAN connections between the ADM and missing MZLP.
Check if hardware exists on the network.
Replace MZLP if necessary.
CACX
DB Not Present Unit A
Alarm
Daughter Board not responding
Dial not set correct on MZLP 5. Set to 5 on board with daughter board.
Ensure connections between the ADM and hardware are secure.
Replace Daughter Board.
42 334130T
Page 43
Code Description Type Cause Solution
CCAG
Comm. Error, Gateway
Alarm
CGM Module is no longer responding
Power removed from Gateway. Restore power. Rotary switch on Gateway changed to positions
between 2 and 8 (must be in 0, 1, or >8 positions).
CACH
Gateway Heartbeat Loss
Alarm
Heartbeat signal was removed while PLC was
PLC went off line. Field Bus connection to CGM was broken.
Restore connection between Field Bus and CGM.
controlling the TOF via the CGM
CACY
DB Not Present Unit B
Alarm
Daughter Board not responding
Dial not set correct on MZLP. Set to 4 on board with daughter board.
Ensure connections between the ADM and hardware are secure.
Replace Daughter Board.
CACV
AWB not present Unit A
Alarm
AWB not responding
Ensure connections between the ADM and hardware are secure.
If a tandem system, ensure AWB 2 jumper is installed at startup.
Replace AWB.
CACW
AWB not present Unit
B
Alarm
AWB not responding
AWB 2 jumper was not in place at start up
Ensure connections between the ADM and hardware are secure.
Replace AWB.
DA X
Pump Runaway Detected
Alarm
Pump is trying to feed adhesive, no adhesive to feed.
Adjust the drum empty level sensor to detect an empty state.
Ensure the Ram Director Valve is in the down position and sufficient air is forcing the Ram down.
Melter at incorrect temperature, too low. Check setpoint and set to manufactures recommendation.
Worn or
Inspect Pump seals and replace if necessary damaged Pump seals
DE X
Reed Switch Failure Detected
Alarm Reed switch
failed
Check that sensor cable is plugged into the daughter board at J16.
Check for loose connection at reed switch. Ensure reed switch is securely attached to the Air Motor. Replace if necessary.
Troubleshooting
334130T 43
Page 44
Troubleshooting
Code Description Type Cause Solution
DC X Pump Diving Alarm
Pump is trying to feed adhesive, no adhesive to feed.
Adjust the drum empty level sensor to detect an empty state.
Ensure the Ram Director Valve is in the down position and sufficient air is forcing the Ram down.
Melter at incorrect temperature, too low. Check setpoint and set to manufactures recommendation.
Worn or
Inspect Pump seals and replace if necessary damaged Pump seals
L1 X Material Level Sen-
sor Error
Alarm
Machine is detecting an empty state without a low state
Make sure the empty level sensor is not covered in material
Verify the low level sensor is plugged into J15 of the daughter board. Verify the low level sensor is close enough to the metal bar; adjust if necessary.
Replace sensors.
L2 X Material Level Empty Alarm Material drum
is empty
L3 X Material Level Low Deviation Material level
Replace material container. If more material is leftover, lower the empty level sensor.
Replace at appropriate time.
is low
MMUX USB Log Full Advisory
USB logs fulls. Data loss will
Download USB data or disable the USB log
errors on the Advanced screen 3. occur if not downloaded.
MN X Pump _ Requires
Maintenance
Advisory
User defined Pump
Perform Pump maintenance, then reset the
counter on the maintenance setup screen. maintenance counter has run out
Ta
Over Temperature Switch
Alarm
An over temperature switch has opened.
Check Heat Rate Option on Advanced Screen 2 to make sure it is set to Normal or Slow. If set to Fast, the switch will open on the pump or platen.
If “_” is 9, A, B, or C, make sure jumper 16W035 is installed in J5 on MZLP 5 and MZLP 7 (for tandem units).
T1 _
Low Temp. Unit _ Zone _
Alarm
Zone temperature too low
Reduce flow rate.
Increase temperature of accessory upstream.
Faulty accessory heater measure resistance
between heater leads.
Change Low Temp Alarm Offset.
Replace accessory.
T2 _
Low Temp. Unit _ Zone _
Deviation Zone tem-
perature too low
Reduce flow rate.
Change Low Temp Deviation Offset.
Add zone (temperature) upstream.
44 334130T
Page 45
Code Description Type Cause Solution
Troubleshooting
T3 _
T4C#
T4M#
T4 _
T6 _
T6C#
T8V_
V1|#
V1M#
V4|#
V6M#
High Temp. Unit _ Zone _
AWB Temperature Runaway Transformer
AWB High Transformer Temp
High Temp. Unit _ Zone _
Sensor Err. Unit _ Zone _
AWB Invalid Thermistor Reading
No Temp. Rise Unit _ Zone _
Low CAN Voltage, MZLP _
Low Voltage Line AWB, Unit _
High CAN Voltage, MZLP _
Wiring Error Line MZLP _
Deviation
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Deviation
Alarm
Alarm
Temperature reading has risen too high
Cooling fan not working or inlet is blocked/dirty
Transformer Temperature is too High
Temperature reading has risen too high
Bad RTD Reading
Transformer thermistor temperature is incorrect
Temperature reading does not change.
Bad or overloaded power supply
The voltage to the AWB is below threshold
Bad or overloaded power supply
Incoming power is wired incorrectly
Change High Temp Deviation Offset.
Verify setpoint upstream is not hotter than this zone’s setpoint.
Ensure inlet and outlets are not obstructed.
Verify fan is plugged in.
Ensure inlet and outlets are not obstructed.
Verify fan is plugged in.
Change High Temp Alarm Offset.
Verify setpoint upstream is not hotter than this zone’s setpoint.
Check RTD wiring and harness/connector integrity.
Replace RTD.
Verify thermister is securely connected to J7 of the AWB. Replace transformer if necessary.
Check fuses on MZLP connected to that Zone.
Check wiring to device.
Check heater resistance on device.
Verify power supply voltage is 24 VDC. If voltage is low, disconnect the power lines and re-check voltage reading. If voltage is still low, replace power supply. If voltage is correct after disconnecting the power lines. Connect items one at a time until the voltage drops to isolate the bad module.
Verify transformer voltage top matches incoming voltage. Verify incoming voltage is correct.
Verify power supply voltage is 24 VDC. If voltage is high, replace power supply unit.
Correct the Wiring.
334130T 45
Page 46
Troubleshooting
Code Description Type Cause Solution
V8M#
V4M#
WJ1
WJ2
WSUX
No Line Voltage MZLP _
AWB High Line Voltage
Pump _ Solenoid is disconnected
Pump _ Solenoid High Current
Configuration Error USB
Alarm
Alarm
Alarm
Alarm
Advisory
Incoming line voltage is less than 100 VAC.
Incoming voltage is too high
Pump is not turning on when it should
Solenoid is drawing too much current
USB configuration is not loaded
Verify transformer has the correct tap selected.
Verify CB-1 or FU-4, FU-5, and FU-6 are not tripped/blown.
Verify RCD-1 is not tripped.
Measure incoming power with system unplugged. If line voltage is less than 100 VAC, contact qualified electrician to correct the low voltage.
Verify the MZLP is plugged in at J2 and the AWB is plugged in at J5 or J6.
Check incoming voltage is correct for configu-
ration.
Verify the transformer has the correct tap (400, 480, 600) selected.
Verify harness is plugged into J13 of the daughter board. Verify it is secured to the solenoid.
Replace Solenoid.
Inspect for short in harness. Inspect for a shorted solenoid cable/short to the ground. Replace solenoid.
Install software.
46 334130T
Page 47

Ram Troubleshooting

Problem Cause Solution
Ram will not raise or lower.
Ram raises or lowers too fast.
Air leaks around cylinder rod.
Fluid squeezes past Platen wipers.
Pump will not prime properly, or pumps air.
Air pressure will not push Platen out of drum.
Troubleshooting
Closed main air valve or clogged air line, Not enough Ram air pressure. Increase Ram air pressure.
Worn or damaged Ram piston. Replace piston. See instruction man-
Platen not fully up to temperature. Wait for full temperature. Ram air pressure too high. Decrease Ram air pressure. Dented drum has stopped Platen. Fix or replace drum. Ram "up / down" air pressure too high. Worn rod seal. Replace o-rings in guide sleeve. See
Ram air pressure too high. Decrease Ram air pressure. Worn or damaged wipers. Replace wipers. Closed main air valve or clogged air
line. Not enough air pressure. Increase air pressure.
Worn or damaged Ram piston. Replace piston. See instruction man-
Ram directional valve closed or clogged. Ram directional valve dirty, worn, or damaged.
Directional valve not in the down position. Dented drum has stopped Platen. Fix or replace drum. Closed main air valve or clogged air line.
Platen not fully up to temperature. Wait for full temperature. Not enough blow-off air pressure. Increase blow-off air pressure. Blow-off valve passage clogged. Clean valve passage. Dented drum has stopped Platen. Fix or replace drum.
Wipers bonded to drum or drum liner. Lubricate wipers with high tempera-
Open air valve; clear air line.
ual 310523.
Decrease Ram air pressure.
instruction manual 310523.
Open air valve; clear air line.
ual 310523. Open valve; clear valve or exhaust.
Clean; repair valve.
Position handle in the down position.
Open air valve; clear air line.
ture grease at every drum change.
334130T 47
Page 48
Troubleshooting

Heated Pump Troubleshooting

See Pump manual for additional Pump troubleshooting information.
Problem Cause Solution
Rapid downstroke or upstroke (Pump cavitation).
Material leaks around Pump outlet.
Material leaks around bleed port.
Pump will not move up and down.
Leak around Pump wet-cup.
Material not heated to proper temperature.
Air is trapped in Pump.
Downstroke: Dirty or worn Pump intake valve.
Upstroke: Dirty or worn Pump piston valve.
Machine is out of material Adjust empty level sensor. Loose outlet fitting. Tighten outlet fitting.
Loose bleed port fitting. Tighten bleed port fitting.
Problem with Air Motor. See Air Motor Manual. Foreign object lodged in Pump. Relieve pressure. See Pump Manual. Platen not fully up to temperature. Wait for full temperature. Valve to Air Motor is off.
Worn throat seals.
Check and adjust temperature to proper setpoint. Wait for Pump/Platen to heat up.
Bleed air from Pump. See Prime Pump, page 32.
Clean or repair. See Pump Manual.
Clean or repair.
Check gauges and valves to the air motor.
Replace throat seals. See Servicing the Throat packings in manual 334127 or 334128.

Air Motor Troubleshooting

See Air Motor manual for additional Air Motor troubleshooting information. See Related Manuals, page 8.
Problem Cause Solution
Air motor will not run.
Air motor stalled.
Air continuously exhausting around Air Motor shaft.
Air continuously exhausting around air valve/slide valve.
Air continuously exhausting from muffler when motor is idle.
Icing on muffler.
Air motor solenoid is off. Wait for heat zones in use to reach
temperature setpoint values. Damaged main air valve spool or poppets.
Damaged Air Motor shaft seal. Replace Air Motor shaft seal. See Air
Air valve/slide valve gasket is dam-
aged.
Internal seal damage. Rebuild Air Motor. See Air Motor
Air motor operating at high pressure or high cycle rate.
Inspect and clean poppets. See Air
Motor Manual.
Rebuild main air valve. See Air Motor
Manual.
Motor Manual.
Replace the valve gasket. See Air
Motor Manual.
Manual.
Reduce pressure, cycle rate, or duty
cycle of motor.
48 334130T
Page 49

Repair

V
CC
CB
Repair

Replace Wipers

1. To replace a worn or damaged wiper (V) raise the Ram Plate up out of the drum. Perform steps 1 through 7 of Change Drums, page 38. See wiper kit
manual for instructions about replacing the wipers.
FIG. 25: Replace Wiper
2. Make sure the Ram Plate is down and the Ram Director Valve is in the OFF position.
To reduce the risk of injury or damage to equipment,
make sure the Main Power Switch is OFF before con-
tinuing with this procedure.

Replace Platen RTD

Reference Electrical Schematics, page 62, for wiring connections.
1. If the material drum has already been removed from the supply unit, go to step 2. If you need to remove the material drum, see Change Drums, page 38.
3. Turn the Main Power Switch OFF.
4. Remove the Pump cover.
FIG. 26: Pump Covers and Platen RTD
334130T 49
Page 50
Repair
CC
ti24671a
5. Remove the Platen RTD (605) from the Platen.
6. Disconnect the Platen RTD wires from pin 3 and pin 6 from the J5 connector on MZLP MZTCM-1 or
MZTCM-5.
FIG. 27: RTD Wire Connections
2760 Red
2770 White
2790 White

Separate the Air Motor and Pump

This procedure must be done with the unit still warm. The material and equipment will be hot!
1. If the material drum has already been removed from the supply unit, go to step 2. If you need to remove the material drum, perform steps 1 through 6 of the Change Drums section, page 38. Pump must be in the full down position (Air Motor shaft fully extended).
2. Make sure the Ram Plate is down and the Ram Director Valve (CC) is in the neutral position.
7. Attach the leads from the new sensor to the leads of the old sensor and pull the new sensor leads through the cable pump shield, Cable Track, and into the Electrical Enclosure.
8. Install the new sensor (605) into the follower/tire
plate after coating with non-silicone heat sink com-
pound. Tighten compression nut. Ensure RTD is fully inserted.
9. Connect the red and white wires from the new sen-
sor to the J5 connector on MZLP MZTCM-1 or MZTCM-5.
10. Replace the Pump covers.
3. Follow Pressure Relief Procedure on page 35.
4. Bleed off excess material and pressure in the sys-
tem by opening the dispense gun and catching the material in a waste container.
5. On the ADM, turn off the system heat (D).
6. Turn the Main Power Switch OFF.
7. Disconnect all material hoses.
50 334130T
Page 51
Repair
8. Remove the Pump sheet metal enclosure.
a. Remove the cover screws.
b. Remove the heater bands and disconnect the
ground wire.
9. If vent hood is installed, remove it.
22. Reverse this procedure to reinstall the new or rebuilt Air Motor.
10. Remove the Air Motor top cover.
11. Disconnect the electrical cable from the Air Motor.
12. Remove air line from Air Motor and air lines to the follower blow-off valve.
13. Tightly strap the Air Motor to the tie bar with a cable through the Air Motor lift ring and around the tie bar. See F
IG
. 29, page 53.
14. Loosen u-bolts (X) from Platen lift rods.
15. Remove nuts (F) from Heated Pump/Air Motor stand-off rods at the Pump end.
16. Remove nuts (Z) and bolts holding cable tract to Air Motor support plate.
17. Slide end of Cable Track outboard of the mounting plate.
18. Remove nuts (N) from follower lift rods.
19. Fully loosen Pump rod coupler to the Air Motor rod (G).
20. Slowly raise elevator to achieve enough separation of the Pump (Air Motor) tie rods to remove the Pump.
21. Remove the Pump.
334130T 51
Page 52
Repair
Z
N
X
G
F
FIG. 28
52 334130T
Page 53
Repair
309a
309b
320
321
ti25222a

Remove Platen

1. Turn the Main Power Switch OFF.
2. Disconnect the Platen power wires and the ground wire from within the main control panel and pull out of conduit.
3. Remove the Platen assembly from the Ram.
4. Reverse this procedure to reinstall the new or rebuilt Platen assembly.

Replace Heater Band and Pump RTD

8. Remove the screws and covers.
9. Remove white ceramic caps and disconnect the electrical wires from the heater band (309).
10. Remove the screw that holds the heater band in place.
11. Remove the heater band (309a, 309b) from the Pump.
Replace Heater Band
1. If the material drum has already been removed from the supply unit, go to step 2. If you need to remove the material drum, perform steps 1 through 6 of the Change Drums, page 38. Pump must be in the full down position (Air Motor shaft fully extended).
2. Make sure the Ram Plate is down and the Ram Director Valve is in the neutral position.
3. Follow the Pressure Relief Procedure, page 35.
4. Bleed off excess material and pressure in the sys-
tem by opening the applicator and catching the material in a waste container.
5. On ADM, turn off the system heat (D).
6. Turn the Main Power Switch OFF.
7.
12. Coat the inside of the heater with non silicone heat
sink compound before mounting. Maximum thick-
ness is 0.005 in. Coat only to within 3/4 in. of vertical ends.
13. Install a new heater band (309a, 309b) in the same location as the old heater band:
a. Locate heater terminals so they line up with the
back of the Pump.
b. Tighten the heater band.
c. Re-connect the heater wires and re-attach the
ceramic caps that insulate the terminal.
334130T 53
FIG. 29
Page 54
Repair
Replace Pump RTD
1. Turn the Main Power Switch OFF.
Fuse Kit Fuse Part
F1, F2 250VAC, 25A, long, white
24V289
F3-F10 250VAC, 8A, fast acting, clear
Spare fuse kit included with system.
ceramic
glass
2. Remove the screws that hold the front shroud in place and remove the front shroud.
3. If the sensor wire is connected to the Electrical Enclosure, disconnect it.
4. Loosen the clamp (321) holding the sensor on the Pump.
5. Tie the leads of the new sensor (320) to the old sen-
sor and remove the old sensor. The leads of the new sensor will be easily drawn through the conduit for reconnecting.
6. Replace the sensor (320) in the clamp (321):
a. Place the sensor approximately 30° counter
clock-wise from the Pump outlet.
b. Tighten the clamp (321).
7. Re-connect the sensor wire to the Electrical Enclo-
sure.
NOTICE
To prevent system damage, always use fast acting
fuses. Fast acting fuses are required for short-cir-
cuit protection.
1. Turn the Main Power Switch OFF.
2. Open Electrical Enclosure door.
3. Use a proper non-conductive fuse puller tool to remove the blown fuse.
NOTICE
Using an improper tool, such as screw drivers or pliers, may break the glass on the fuse.
NOTE: F1 and F2 are white ceramic and indicate 25A on the barrel.

Replace MZLP Fuse

Each MZLP module comes with the following fuses:
FIG. 30: Fuse Locations
54 334130T
NOTE: F3-F10 are clear glass and indicate 8A on the barrel.
4. Use a proper non-conductive fuse puller tool to install the new fuse.
NOTICE
Using an improper tool, such as screw drivers or pliers, may break the glass on the fuse.
5. Close the Electrical Enclosure.
Page 55
Repair
112
112
J5
ti25223a
115
111

Replace MZLP

1. Turn the Main Power Switch OFF.
2. Disconnect the heated hose electrical connectors from the MZLP (111 or 112).
3. Note the location of each cable, then unplug all cables from the MZLP (111 or 112) that will be replaced.
4. Remove the four screws (115) securing the MZLP
(111 or 112) to the Electrical Enclosure, then care­fully remove the MZLP from the Electrical Enclo-
sure.
6. To reassemble the MZLP, set the MZLP rotary switch based on location. See MZLP Rotary Switch Table.
7. Use the four screws (115) to install MZLP (111 or
112) to Electrical Enclosure.
8. Reconnect the cables to the MZLP.
NOTE: Do not force the electrical connection. Minimal force is required to seat the connector. If resistance is felt, stop and verify the connector orientation.
NOTE: If unable to determine the connector location, see Electrical Schematics, page 62.
9. Connect the heated hose electrical connectors to the new MZLP.
NOTE: The MZLP may need updated software. See Update Software, page 61.
Table 10 MZLP Rotary Switch
MZLP System Rotary Switch
#1 with Daughter Card
#2 Primary 2
#3 Primary 3
Primary 1 Secondary 5
Secondary 6
Secondary 7
FIG. 31: MZLP Identification
5. Replace MZLP.
a. To replace MZLP #1, remove the daughter card
and standoffs, and re-install them on the new MZLP #1.
b. To replace MZLP #2 of #3, remove the jumper
(162) from MZLP #2 or #3 J5 connector and reinstall it on the new MZLP J5 connector.
334130T 55
Page 56
Repair
112b
112a
112
Rotary Switch

Replace MZLP Daughter Card

1. Turn the Main Power Switch OFF.
2. Note the location of each cable, then unplug all cables from the MZLP daughter card on MZLP #1 (112).
3. Remove the four mounting screws (112b) from the daughter card (112a) and set aside.
4. Unplug the daughter card (112a) from MZLP #1 (112).
5. Plug the new daughter card (112a) into the MZLP (112).
6. Use the screws (112b) to secure the daughter card to the MZLP (112).
7. Connect the cables to the new daughter card (112a).
NOTE: Do not force the electrical connection. Minimal force is required to seat the connector. If resistance is felt, stop and verify the connector orientation.
NOTE: If unable to determine the connector location, see Electrical Schematics, page 62.
FIG. 32: MZLP Daughter Card
56 334130T
Page 57
Repair
182
205
223
ti25224a
206
208

Replace AWB

1. Turn the Main Power Switch OFF.
2. Note the location of each cable, then unplug all cables from the AWB (205).
NOTE: For an AWB on a secondary system, remove the connector (182) and connect to the new AWB.

Replace Power Supply

FIG. 33: AWB Connections
3. Remove the two screws (223) securing the AWB (205) to the electrical panel, then carefully remove the AWB.
4. Install the new AWB (205) and reconnect the cables.
NOTE: Do not force the electrical connection. Minimal force is required to set the connector. If resistance is felt, stop and verify the connector orientation.
NOTE: See Electrical Schematics, page 62, if unable to determine the connector location.
1. Turn the Main Power Switch OFF.
2. Open the Electrical Enclosure.
3. Remove the power supply (208) from the din rail (206). Disconnect the screw terminal connections between the power supply and the power supply
harness.
Power Supply
Connection Harness Label
V+ V+
V- V-
GND GND
LL
NN
4. Connect the power supply harness to the new power supply.
5. Reattach the power supply to the din rail (206).
6. Torque terminals to 4.53-6.2 in-lbs (0.5-0.7 N•m).
334130T 57
7. Close the Electrical Enclosure door.
Page 58
Repair
ti25226a
J7
137
136138
139
141
ti25227a

Replace Fan

1. Turn the Main Power Switch OFF.
2. Disconnect the plug from the power outlet or turn off the circuit breaker for incoming power.
3. Open the Electrical Enclosure door.
4. Remove the connector from the J7 connector on the AWB board. Remove the red (+) and black (-) fan wires from the connector.
6. Remove the screws (141), grill (137), four nuts (139), rear fan grill (138), and fan (136).
7. Mount the new fan (136), rear fan grill (138), and nuts (139) on the grill (137) with the arrow pointing toward the grill (137).
5. Cut any cable ties between the end of the fan wires to the fan (136).
8. Tie down the fan wires onto the tie down locations on the grill (137) using cable zip ties.
9. Route the fan wires into the Electrical Enclosure.
Connect the red and black fan wires to the J7 con-
nector. Reconnect the J7 connector to the AWB. Use cable ties to secure the fan wires to other cables in the electrical enclosure.
NOTE: To prevent fan errors on the ADM, remove the excess slack and ensure that the cabling and zip ties do not contact the fan blades.
10. Reinstall the fan grill (137) and close the Electrical Enclosure.
58 334130T
Page 59
Repair
480VAC
600VAC
400VAC
ti25228a

Replace Transformer

See FIG. 34, page 60.
1. Turn the Main Power Switch OFF.
2. Open the Electrical Enclosure door.
3. Disconnect the incoming power harness (234) from the top of the transformer (235).
4. Disconnect the transformer (235) output power har-
ness wires (CR2-W1, -W2, -W3, -W4) from CR2.
13. Connect transformer output power harness (234) to power terminal connections. Torque to 25–27 in-lbs (2.8–3.1 N•m).
Table 11 Transformer Output Power Harness Connections
Power Harness Wires CR-2 Connections
CR2-W1 Terminal 1 CR2-W2 Terminal 3 CR2-W3 Terminal 5 CR2-W4 Terminal 13
14. Install the incoming power harness (234) to the top of the transformer in the voltage port specified on the machine serial number label.
5. Disconnect the transformer (235) ground wire from the back panel ground lug.
6. Disconnect the red (+) and black (-) wire of the fan from pins 4 and 3 of the J7 connector on the AWB (205). Disconnect the J7 connector from the AWB.
7. Cut the wire zip ties securing the fan wires.
8. Remove the flanged nuts (N) and transformer (235) from the back panel (201).
9. Install the transformer (235) onto mounting studs on the back panel (201) and secure with flanged nuts (N).
10. Insert the thermal sensor connector from the trans-
former (235) onto the J7 connector on the AWB (205).
11. Reconnect the red (+) wire from the fan into pin 4 and the black (-) wire into pin 3 of the J7 connector.
12. Install the transformer (235) ground wire onto the ground lug of the back panel (201).
15. Verify all electrical connections, including earth grounds, are complete and tight. All connections and plugs must be connected prior to applying power.
16. Close the Electrical Control Panel door.
17. Apply power to the machine. Turn on the Main Power Switch.
18. Restart the system.
334130T 59
Page 60
Repair
201
N
235
234
G
Z
J7
205
CR-2
FIG. 34: Inside of Electrical Control Enclosure
60 334130T
Page 61
Repair
T

Update Software

When software is updated on the ADM, the software is
then automatically updated on all connected GCA com-
ponents. A status screen is shown while software is updating to indicate progress.
1. Turn the system Main Power Switch OFF.
2. Remove the ADM from the bracket.
3. Remove the token access panel.
NOTE: When the Screen turns on, you will see the fol-
lowing screens:
First:
Software is checking which GCA modules will take the available updates.
Second:
Status of the update with approximate time until completion.
Third:
Updates are complete.
Icon indicates update suc­cess/failure. See the fol-
lowing Icon table.
4. Insert and press the software upgrade token (T) firmly into the slot.
NOTE: There is no preferred orientation of the token.
5. Install the ADM into the bracket.
6. Turn the system Main Power Switch ON.
NOTICE
A status is shown while software is updating to indi-
cate progress. To prevent corrupting the software load, do not remove the token until the status screen disappears.
Icon Description
Update successful.
Update unsuccessful.
Update complete, no changes necessary.
Update was successful/complete, but one or more HCA modules did not have a CAN boot-loader, so software was not updated on that module.
7. Remove the token (T).
8. Replace the token access panel.
9. Press to continue to the operation screens.
334130T 61
Page 62

Electrical Schematics

Electrical Schematics

230V, 3 Phase/60Hz

62 334130T
Page 63

400V, 3 Phase/50Hz

Electrical Schematics
334130T 63
Page 64
Electrical Schematics

400-600VV, 3 Phase/60Hz

64 334130T
Page 65
A RELEASED A257M
Z090146
06/24/14
B SEE ECO
Z090616
07/23/14
C SEE ECO
Z091443
08/26/14
D SEE SHEETS 1,2,3
Z092531
10/17/14
E SEE SHEETS 1 AND 2.
Z093615
12/04/14
F SEE SHEET 1
Z095498
23MAR15
G SEE SHEET 1
Z097266
02JUN15
H REVISED SHEET3
Z098180
30JUN15
J SEE SHEET 1
Z104520
17MAR16
K REVISED SHEETS 2,3, & 4
Z106725
06/16/16
J5
J6
J7
J8
J9
J4
J3
J2
CAN
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
J1
AWB-1
24+
GND
N
L
EGND
-
N
L
+
PS-1
129
130
131
265
266
267
268
332
330
329
122
125
ENCLOSURE FAN
(FAN-2)
127421
110
109
115
114
372
374
220
221
222
223
315
313
312
238
237
236
235
234
300
301
302
303
304
281
282
283
284
285
MOTOR-UP
MOTOR-DN
SOL-1
PX-LOW
PX-EMPTY
PUMP-RTD
PLATEN-RTD
54 32 1
G32
1
G32
1
1290
1300
1310
1220
1250
2610
2620
J16 J14J15
J7
J6
J5
J1
J2
MZTCM-1
J13 J12
L1
L3
G
L3L2L1
543214321
4
3
2
1
5 4 3 2 1
5 4 3 2 1
65432
1
4
3
2
1
432
1
4 3
2 1
1140
1150
1090
1100
W1W2W3W4G
2270
2320
2790
RED
2770
2720
2710
2700
2670
2680
2650
2640
2560
2570
-
N
L
+
+V
-V
N
L
GND
132
1320
HARNESS 17A559
AWB-1-J8 TO MZTCM-1-J6
BLACK
YELLOW
YELLOW
RED
-
+
HARNESS 17A543
AWB-1-J6 TO MZTCM-1-J2
HARNESS 17A544 OR 17A545
AWB-1-J5 TO MZTCM-2-J2
AWB-1-J5 TO MZTCM-3-J2
HARNESS 17A543
MZTCM-1-J2 TO AWB-1-J6
HARNESS 17A551
MZTCM-1-J1 TO TERM BLOCKS
HARNESS 17A557
MZTCM-1-J12 TO SOL-1
HARNESS 127511
MZTCM-1-J3 TO MZTCM-2-J6
J3
HARNESS 24V745
HARNESS 17A559
MZTCM-1-J6 TO AWB-1-J8
HARNESS 17A553
MZTCM-1-J7 TO SSR-1 AND CR-1
BLUE
RED
RED
BLUE
HARNESS 17A555
2730
2740
RED
BLUE
RED
WHITE
WHITE
2760
355
358
RED
RED
HARNESS 17B768
HARNESS 17A552
18 AWG
10 AWG
10 AWG
10 AWG
18 AWG
12 AWG
10 AWG
22 AWG
22 AWG
22 AWG

AWB and MZLP#1

Electrical Schematics
334130T 65
Page 66
Electrical Schematics
A RELEASED A257M
Z090146
06/24/14
B SEE ECO
Z090616
07/23/14
C SEE ECO
Z091443
08/26/14
D SEE SHEETS 1,2,3
Z092531
10/17/14
E SEE SHEETS 1 AND 2.
Z093615
12/04/14
F SEE SHEET 1
Z095498
23MAR15
G REVISED PUMP WIRING
Z097266
02JUN15
H REVISED SHEET 3
Z098180
30JUN15
J SEE SHEET 1
Z104520
17MAR16
K REVISED SHEETS 2,3, & 4
Z106725
06/16/16
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
B3
T3
262
261
2
240V/1200W TOTAL
2610
2620
215
217
218
254
253
252
251
250
215
217
218
MZTCM-3
MZTCM-2
J7
43
21
J7
J6
J5
J1
J2
L3
L1
G
L3L2L1
54321
54321
65432
1
43
21
J3
HARNESS 127511
MZTCM-2-J3 TO MZTCM-3-J6
J6
J5
54321
65432
1
J1
J2
L3
L1
G
L3L2L1
54321
J3
HARNESS 127511
MZTCM-2-J6 TO MZTCM-1J3
HARNESS 17A544 OR 17A545
MZTCM-2-J2 TO AWB-1-J5
HARNESS 17A545
MZTCM-3-J2 TO AWB-1-J5
B1
T1
321
2740
275
274
2730
2740
2731
2730
2730
2731
2732
2740
2731
2732
2732
PLATEN
PUMP
PUMP
TYPICALL ALL TOF200 AND TOFP20's
OVERTEMPS
ALL VOLTAGES
2740
275
274
2730
2740
2730
2730
2731
2732
2740
PLATEN
TYPICALL OF TOFP20's WITH CODE D
OVERTEMP
AT SELECTION 7. ALL VOLTAGES
10 AWG
10 AWG
16 AWG

MZLP#2, MZLP#3, Overtemp, and Pump Heaters

66 334130T
Page 67

MZLP Zones

A RELEASED A257M
Z090146
06/24/14
B SEE ECO
Z090616
07/23/14
C SEE ECO
Z091443
08/26/14
D SEE SHEETS 1,2,3
Z092531
10/17/14
E SEE SHEETS 1 AND 2.
Z093615 12/04/14
F SEE SHEET 1
Z095498
23MAR15
G SEE SHEET 1
Z097266
02JUN15
H REVISED SHEET 3
Z098180
30JUN15
J SEE SHEET 1
Z104520
17MAR16
K REVISED SHEETS 2,3, & 4
Z106725
06/16/16
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
MZTCM-1
J8
J9
C
D
E
F
G
H
J
M
L
K
A
B
TYPICAL ZONE PIN OUT
CONNECTOR PIN # FUNCTION
MZTCM-1
MZTCM-1 J9
A ZONE 1,L2
B SHIELD
C ZONE 2,L1
D ZONE 2,L2
E JUMPER
F ZONE 1,START
G ZONE 1,RTD
H JUMPER
J ZONE 1,L1
K RTD EXCITE
L ZONE 2,START
M ZONE 2,RTD
MZTCM-1 J8
A ZONE 3,L2
B SHIELD
C ZONE 4,L1
D ZONE 4,L2
E JUMPER
F ZONE 3,START
G ZONE 3,RTD
H JUMPER
J ZONE 3,L1
K RTD EXCITE
L ZONE 4,START
M ZONE 4,RTD
MZTCM-2
MZTCM-2 J9
A ZONE 5,L2
B SHIELD
C ZONE 6,L1
D ZONE 6,L2
E JUMPER
F ZONE 5, START
G ZONE 5,RTD
H JUMPER
J ZONE 5,L1
K RTD EXCITE
L ZONE 6,START
M ZONE 6,RTD
MZTCM-2 J8
A ZONE 7,L2
B SHIELD
C ZONE 8,L1
D ZONE 8,L2
E JUMPER
F ZONE 7,START
G ZONE 7,RTD
H JUMPER
J ZONE 7,L1
K RTD EXCITE
L ZONE 8,START
M ZONE 8,RTD
MZTCM-3
MZTCM-3 J9
A ZONE 9,L2
B SHIELD
C ZONE 10,L1
D ZONE 10,L2
E JUMPER
F ZONE 9,START
G ZONE 9,RTD
H JUMPER
J ZONE 9,L1
K RTD EXCITE
L ZONE 10,START
M ZONE 10,RTD
MZTCM-3 J8
A ZONE 11,L2
B SHIELD
C ZONE 12,L1
D ZONE 12,L2
E JUMPER
F ZONE 11,START
G ZONE 11,RTD
H JUMPER
J ZONE 11,L1
K RTD EXCITE
L ZONE 12,START
M ZONE 12,RTD
ZONE-1-RTD
ZONE-2-RTD
ZONE-1-START
ZONE-2-START
ZONE-2-HEAT
ZONE-1-HEAT
A
J
C
D
G
F
K
L
M
E
H
B
TYPICAL ZONE PIN OUT
MZTCM-2
MZTCM-3
J8
J9
J8
J9
21
65
109
43
87
1211
Electrical Schematics
334130T 67
Page 68

Parts

6
12
3
28
7
8
5
10
9
24
11
16
21
22
23
20
19
18
16
11
15
14
17
1
4
29
2
25
26
27
13
ti25003a
Parts

Therm-O-Flow 200 Supply Unit

68 334130T
Page 69

Therm-O-Flow 200 Supply Unit

Parts
Ref Part Description Qty
1--- Frame 1 2 24W870 KIT, air controls; see Air Control
Assembly, page 70
3 --- CONTROL, electrical 1
4 --- MODULE, pump; see Pump Mod-
ules, page 78
5 --- PLATEN; see Heated Platens,
page 85 6 --- RAM; see ram manual 1 7 --- CLAMP, drum; see Drum Ram
Post Saddle Clamp, page 88 8 --- SEALS, see manual 309196 1 9 24W812 ADM 1 10 24W589 KIT, light tower (optional); see
Accessories and Kits, page 92 11 253288 CABLE, track, IGUS 1 12 234966 KIT, hose hanger 1 13 24V745 SENSOR, level, low/empty 1 14 15H543 BRACKET, mounting 1
Replacement Warning Labels, signs, tabs, and cards
are available at no cost.
1
1
1
1
1
Ref Part Description Qty
15 120186 BOLT, mounting, u-bolt 2 16 101864 SCREW, cap, sch 8 17 111303 NUT, hex 4 18 100575 SCREW, cap, hex hd 4 19 100023 WASHER, flat 4 20 --- BRACKET, mounting, enclosure 1 21 100643 SCREW, cap, sch 4 22 100016 WASHER, lock 4 23 110755 WASHER, plain 4 24 233559 KIT, vent hood (optional); see
Accessories and Kits, page 92.
2515J076 LABEL, warning, instructions 2 2615J074 LABEL, warning; moving objects,
pinch
2715H668 LABEL, warning; hot surface,
splatter
2815J075 LABEL, warning; hot surface,
shock
29184090 LABEL, warning 1
1
4
2
2
334130T 69
Page 70
Parts
Integrated Control For
TOF With Electrical Enclosure
24X026, Integrated Control For
Hydraulic TOF With Electrical
Enclosure
Integrated Control For
TOF Without Electrical Enclosure
52
53
54
55
66
51
62
61
66
57
60
59
58
51
66
56

Air Control Assembly

Ref Part Description Qty
51
52 53 54 55 56
57 --- FITTING, adapter, 1/8 x 1/8 NPT(f) 1 58 --- BLOCK, adapter, regulator 2
70 334130T
24W870
121235 17A557 113445 121282 120375
KIT, CONTROL, air, 3 regulator;
see manual 334201
SOLENOID, air motor, ram 1
HARNESS, solenoid, MZLP 1
FITTING, elbow, street 1
FITTING, swivel, straight 1
ADAPTER, elbow, 3/4-14 nptf x
1/2-14 npsm
Ref Part Description Qty
59 --- O-RING 4
1
60 --- SCREW, cap, socket hd; 1.5 in,
#8-32
61 --- CONTROL, air, 3 regulator,
62 --- LABEL, valve, shutoff, air control 1 66 255651 KIT, reg, air motor, ram 1
1
Parts only used with 24X026 on TOF 200 Hydraulic Sys-
tems.
hydraulic
8
1
Page 71

Electrical Module

184
143
144
148 150 152 153
142
106
152
153
105
145
147
149
120
174
222
141
137
136
138
139
140
141
222
160
159
157
158 101
104
103
172
170153146 151
177, 119
222
118
111
116
115
114
113
183
161
131
112
112
116
115
Parts
334130T 71
Page 72
Parts
110
165
167
169
125
126
181
222
128
127 122
168
125
131
165
111
129
130
156
162
124
123
108
109
135
133
132
134
72 334130T
Page 73

Electrical Control Module Parts

Parts
Ref Part Description Qty
101 --- ENCLOSURE, electrical 1 103 --- BUSHING, strain relief, m40
thread 104 --- NUT, strain relief, m40 thread 1 105 125946 PLUG, hole, 1/2 in 2 106 123967 KNOB, operator disconnect 1 107 --- PANEL, elec, transformer
(transformer assemblies only)
--- PANEL, elec, 400v/n (400V modules only)
--- PANEL, elec, 230v/n (230V modules only)
108 100133 WASHER, lock, 3/8 4 109 100307 NUT, hex 8 110 123396 NUT, flange, serrated, 3/8-16 4 111 --- MODULE, gca, mzlp w/ daughter
board
112 24V510 MODULE, gca, mzlp
(8 zone assemblies only; Qty 1) (12 zone assemblies only; Qty 2)
112a 24R042 KIT, daughter, board 1 113 --- GASKET, foam
(8 zone assemblies only; Qty 1) (12 zone assemblies only; Qty 2)
114 24P175 PLATE, blank
(4 zone assemblies only; Qty 2) (8 zone assemblies only; Qty 1)
115 125856 SCREW, 8-32, serrated flange 12 116 16T440 CAP, souriau, uts 14
(4 zone assemblies only; Qty 2) (8 zone assemblies only; Qty 4) (12 zone assemblies only; Qty 6)
118 --- WIRE, grounding, door 1 119 100166 NUT, full hex 2 120 --- GASKET, hphm 1 122 17A543 HARNESS, power, mzlp1, awb 1 123 17A544 HARNESS, power, mzlp2, awb
(8 zone assemblies only)
17A545 HARNESS, power, mzlp2/3, awb
(12 zone assemblies only)
1
1
1
1
1
1
1
Ref Part Description Qty
125 --- HARNESS, pump, mzlp1, tb, tof 1 126 --- HARNESS, output, mzlp1, ssr,
contact 127 17A555 HARNESS, pump, reed switch, tof 1 128 17A559 HARNESS, board, mxm, comm 1 129 127511 CABLE, board, samtec
(8 zone assemblies only; Qty 1)
(12 zone assemblies only; Qty 2) 130 121226 CABLE, can, male / female, 0.4m 1 131 121612 CONNECTOR, thru, m12, mxf 1 132 123969 SWITCH, disconnect, 100a 1
123968 SWITCH, disconnect, ph exp 100
A (400V only) 134 --- HARNESS, disc, fuse, 230-600v 1
17A547 HARNESS, disc, cb, 400v/n, tof 1
136 24V911 FAN, 24v dc, 120m x 120m
(400V only) 137 16X884 GRILL, fan (400V only) 1 138 115836 GUARD, finger (400V only) 1 139 127278 NUT, keps, hex (400V only) 4 140 24V746 GRILL, vent
(230V and 400V assemblies only;
Qty 2) (Transformer assemblies
only; Qty1) 141 119865 SCREW, mach, hex serrated 4
142 --- CONTROL, air, assy; with sole-
noid 143 24W812 ADM (Primary assemblies only) 1 144 15V551 SHIELD, membrane, ADM
(Primary assemblies only) 145 121001 CABLE, can, female / female 1.0m
(Primary assemblies only) 146 --- BRACKET, mounting, assembly
(Primary assemblies only)
147 121250 SCREW, shcs, 1/4uncx4.25 (Pri-
mary assemblies only) 148 102040
149 110755 WASHER, plain (Primary assem-
150 121253
151 ---
152 101550
NUT, lock, hex
(Primary assemblies only)
blies only)
KNOB, display adj., ram pkgs
(Primary assemblies only)
BRACKET, pendant pivot,
(Primary assemblies only)
SCREW, cap, sch
(Primary assemblies only)
1
1
1
1
0.1
1
1
1
1
1
1
1
4
334130T 73
Page 74
Parts
Ref Part Description Qty
153 100016
WASHER, lock (Primary assemblies only)
156 24V745 SENSOR, level, low/empty 1 157 --- BUSHING, strain relief 1 158 --- NUT, bushing 1 159 --- GROMMET, wire 1 160 124654
CONNECTOR, splitter, 12(m) x m12(f)
(Secondary modules only)
161 121228
CABLE, can, female/female,
15.0 m (Secondary modules only)
162 16W035
CONNECTOR, jumper (8 zone assemblies only; Qty 1) (12 zone assemblies only; Qty 2)
163 ---
CONTACT, socket, 20-24 awg, crimp, tin
164 --- TUBE, 1/16 shrink tube 0.13 165 ---
166 127771
HARNESS, input, mzlp1, RTD BRIDGE, plug-in, 2pos, ut16 (400V and Transformer modules only)
167 ---
FERRULE, wire, 10awg (230V modules only; Qty 2) (400V and transformer modules only; Qty
8)
168 --- FERRULE, wire, 16awg 6 169 ---
FERRULE, wire, 18 awg, long
170196548 LABEL, warning, shock 1
172 --­181 ---
ARTWORK, instructions, wiring, ul FERRULE, wire, 10awg, twin (Secondary assemblies only)
182 17C669
CONNECTOR, jumper, male (Secondary assemblies only)
183 123856
HARNESS, CAN, cable (Secondary assemblies only)
184 17C712
TOKEN (Secondary assemblies only)
5
1
1
3
1 1
6
1 3
1
1
1
Replacement Warning labels, signs, tags, and cards
are available at no cost.
74 334130T
Page 75

Electrical Panel

Torque terminals to 25-27 in-lbs (2.8-3.1 N•m).
Torque terminals to 13.3-16 in-lbs (1.5-1.8 N•m)
Torque terminals to 4.53-6.2 in-lbs (0.5-0.7 N•m)
123
Transformer Panel Shown
4
239
240
235
211
205
223
228
226
201
223, 224
225
214
1
227
215
1
216, 229
1
230, 231
1
213
208
210
1
212
206
202, 203, 204, 236
7
234
6
241
242
230V 400V Transformer
Parts
334130T 75
Page 76
Parts
Torque terminals to 25-27 in-lbs (2.8-3.1 N•m).
Torque terminals to 13.3-16 in-lbs (1.5-1.8 N•m)
Torque terminals to 4.53-6.2 in-lbs (0.5-0.7 N•m)
123
230V Panel
400V Panel
230
232
230
233
211
219
243
220
221
207
218
217
1
2
2
3
76 334130T
Page 77

Electrical Panel Parts

Parts
Ref Part Description Qty
201 --­202 117666 TERMINAL, ground 1
203 113783 SCREW, machine, pn hd 1 204 100985 WASHER, lock ext 1 205 24V816 MODULE, gca, awb 1 206 --- RAIL, din, 6.5in 1 207 123363
208 126453 POWER SUPPLY, 24v 1 209 ---
210 128097 211 --- HARNESS, rcd, awb 1
212 126811 BLOCK, clamp end 2 213 --- RAIL, din, 19in 1 214 120399
215 123359
216 6690-24
-165 217 128314 BLOCK, terminal 3-wire 8 218 128321 COVER, end 2 219 126819
220 127717 221 127718 COVER, end, ut16 1
22217C137 LABEL, multi safety 1
223 103833 SCREW, mach, crbh 33 224 123452
225 --­226 --- HARNESS, fuse, contactor 1
227 --- HARNESS, contactor, ssr 1
PANEL, elec, tof, 11ga, zinc
BLOCK, terminal, ground, 10mm
HARNESS, power supply, awb CIRCUIT, breaker, 63a, 4p, rcd
CONTROL, 65 amp, 120-600v RELAY, contactor, 30a, 3p, 24vdc co FUSE, fuse block buss jt60060
BRIDGE, plug-in, 2-position BLOCK, terminal, 2pos, ut16
HOLDER, anchor, wire tie, nylon HARNESS, wire, ground, 8awg
1
3
1 1
1 1
3
1 3
12
1
Ref Part Description Qty
228 --- HARNESS, rcd, ssr fan 1 229 --- See Code C Table 3 230 6690-24
-164 127744
127745
231 --- See Code C Table 3 232 17L788
233 17L789
234 17A541
235 24V718
237 128014
238 112380 SCREW, mach, pn hd 2 239 81/0163
-B/11
240 81/0164
-B/11 241 17L790 HARNESS 1 242 129120 CONTACTOR 240V 1 243 17L787 HARNESS 1
Replacement Warning labels, signs, tags, and cards
are available at no cost.
FUSE, fuse block buss jt60030
CIRCUIT, breaker, 3p, 32a, ul489; 230V Panel only CIRCUIT, breaker, 20a,
4p, ul489; 400V Panel only
HARNESS, cb, rcd, 230-400V; 230V and 400V Panel only HARNESS, cb, rcd, 400v/n; 400V Panel only HARNESS, fuses, transformer; Transformer panel only
TRANSFORMER, multi-tap/230v, 6kva; Transformer panel only FILTER, voltage, transient, 600V, 3P
WIREWAY, panduit 4
COVER, panduit 4
3
1
1
1
1
1
1
If Code A is 200 and Code E is M and Code C is If Code A is 200 and Code E is F/S and Code C is
Code C (229) (231) Code C (229) (231)
X1X 24X885 NA X1X 24X885 NA X2X 24X881 NA X2X 24X880 NA X3X 24X881 24X878 X3X 24X880 24X878 X4X 24X882 24X877 X4X 24X881 24X877 X5X 24X884 24X874 X5X 24X883 24X874
334130T 77
Page 78
Parts
Torque to 50-60 ft-lbs (68-81 N•m).
Torque to 145-155 ft-lbs (196-210 N•m).
Coat mounting surface of sensor mounting block (322) with non-silicone heat sink compound. Do not coat sensor.
Prior to tightening band clamp (321), RTD sensor (320) must be fully contained within the sensor mount (322).
After fastening band clamp (321), secure excess with fiberglass tape.
12345
Coat inside of heater (309a, 309b) only to within 0.75 in. (19 mm) of vertical ends with non-silicone heat sink compound before mounting.
Cap screws (311) must be loose while tie rods (307) are being torqued.
Torque to 150 ft-lb (203 N•m).
Install swivel fitting (302) prior to screw (303) and reed switch assembly (304).
Apply anaerobic sealant to threads.
678
9
10
ti25145a
333
326
309b
321
322
325
324
323
309a
310
308
329
315
338
301
327
337
302
304
312
318
311
317
316
307
306
318
305
335b
336
335a
334
320
9
8
1
7
10
4
2
6
5
3
6
1

Merkur 2200, 23:1 Pump Modules

78 334130T
Page 79

Merkur 2200, 23:1 Pump Modules

Parts
Ref Part Description Qty
301 24W754 302 155470 304 24R885 SWITCH, reed assy 1
305 --- BRACKET, motor mount 1 306 15H397 ADAPTER, rod, pump 1 307 16A223
308 106166 NUT, mach ,hex 3 309 128322
310 24W150
24W151
311 109211 SCREW, cap, sch 3 312 17A637 BLOCK, standoff, mounting 3 315 102656
316 186925 317 184129 318 120186 BOLT, mounting, u-bolt 2
320 24Z093 SENSOR, RTD 1
MOTOR, air, 6 in, 4.75 stroke, blue FITTING, swivel, union, 90°
ROD, tie, vert driver
HEATER, pump, 600 watt PUMP, long shaft, cf; 24V003 only PUMP, long shaft, gf; 24V006 only
MUFFLER NUT, coupling COLLAR, coupling
1 1
3
2 1
1 1 2
Ref Part Description Qty
321 C31012 322 C03507 323 C38162 SCREW, machine 1
324 C38163 WASHER, lock, ext. tooth 1 325 --- CONDUCTOR, ground 1 326 ---
329 103347 330 C33049 TAPE, adhesive, fiberglass 1.5
331 --­333 206994 FLUID, tsl 8 oz bottle 1
334 17B715 335 127671
336 122338 337 214656 HOSE, coupled, 10 ft (3 m) 1
338 16C009 HOOK 1
CLAMP SUPPORT, sensor
SHIELD, pump, tof200; see 24V619, Pump Shield, page 84 VALVE, safety, 100 psi
LUBRICANT, high temp, thermal
SUPPORT, block, overtemp SWITCH, over temp, fixed, 450°F (232°C) SCREW, cap, socket bh
1 1
1
1
1
1 2
4
334130T 79
Page 80
Parts
Torque to 50-60 ft-lbs (68-81 N•m).
Torque to 145-155 ft-lbs (196-210 N•m).
Coat mounting surface of sensor mounting block (322) with non-silicone heat sink compound. Do not coat sensor.
Prior to tightening band clamp (321), RTD sensor (320) must be fully contained within the sensor mount (322).
After fastening band clamp (321), secure excess with fiberglass tape.
12345
Coat inside of heater (309) only to within 0.75 in. (19 mm) of vertical ends with non-silicone heat sink compound before mounting.
Cap screws (311) must be loose while tie rods (307) are being torqued.
Torque to 150 ft-lbs (203 N•m).
Install swivel fitting (302) prior to screw (303) and reed switch assembly (304).
Apply anaerobic sealant to threads.
6
789
10
338
301
337
327
304
305
318
306
307
316
317
311
318
312
315
326
333
336
335b
335a
336
320
308
310
329
323
324
325
309a
322
321
334
309b
302
8
7
1
2
9
10
1
6
3
5
6
4

Merkur 3400, 36:1 Pump Modules

80 334130T
Page 81

Merkur 3400, 36:1 Pump Modules

Ref Part Description Qty
301 24R015 302 155470 304 24R885 SWITCH, reed assy 1
305 15H173 306 15H397 ADAPTER, rod, pump 1
307 16A223 308 106166 NUT, mach, hex 3
309 128322 310 24W150
24W151
311 109211 SCREW, cap, sch 3 312 17A637 BLOCK, standoff, mounting 3 315 102656
316 186925 317 184129 318 120186 BOLT, mounting, u-bolt 2
320 24Z093 SENSOR, RTD 1 321 C31012
322 C03507 323 C38162 SCREW, machine 1
324 C38163 WASHER, lock, ext. tooth 1 325 --- CONDUCTOR, ground 1 326 ---
329 103347 330 C33049 TAPE, adhesive, fiberglass 1.5
331 --­333 206994 FLUID, tsl 8 oz bottle 1
334 17B715 335 127671
336 122338 337 214656 HOSE, coupled, 10 ft (3 m) 1
338 16C009 HOOK 1
MOTOR, assy, air, 7.5 in, blue FITTING, swivel, union, 90°
BRACKET, motor mount, tof 200
ROD, tie, vert driver
HEATER, pump, 600 watt PUMP, long shaft, cf; 24V004 only PUMP, long shaft, gf; 24V007 only
MUFFLER NUT, coupling COLLAR, coupling
CLAMP SUPPORT, sensor
SHIELD, pump, tof200; see 24V619, Pump Shield, page 84 VALVE, safety, 100 psi
LUBRICANT, high temp, thermal
SUPPORT, block, overtemp SWITCH, over temp, fixed, 450°F (232°C) SCREW, cap, socket bh
1 1
1
3
2 1 1
1 1 2
1 1
1
1
1
1 2
4
Parts
334130T 81
Page 82
Parts
Torque to 50-60 ft-lbs (68-81 N•m).
Torque to 145-155 ft-lbs (196-210 N•m).
Coat mounting surface of sensor mounting block (411) with non-silicone heat sink compound. Do not coat sensor.
Prior to tightening band clamp (412), RTD sensor (410) must be fully contained within the sensor mount (411).
123
4
After fastening band clamp (412), secure excess with fiberglass tape.
Coat inside of heater (407) only to within 0.75 in. (19 mm) of vertical ends with non-silicone heat sink compound before mounting.
Torque to 150 ft-lb (203 N•m).
Apply anaerobic sealant to threads.
568
10
401
402
418
423
409
404
414
413
405
422
433
403
418
406
424
408
417
415
416
407a
411
412
429
407b
410
431
430a
430b
431
428
ti25160a
1
2
8
10
4
6
5
3
6
1

NXT 6500, 70:1 Pump Modules

82 334130T
Page 83

NXT 6500, 70:1 Pump Modules

Ref Part Description Qty
401 N65LR0 402 120375
403 15H542
404 17A406 ADAPTER, rod, pump, tof 1 405 16A223
406 106166 NUT, mach, hex 3 407 128322
408 24W150
24W151 409 C19837 410 24Z093 411 C03507 SUPPORT, sensor 1
412 C31012 CLAMP 1 413 186925
414 184129 415 C38163 416 --- CONDUCTOR, ground 1
417 C38162 SCREW, machine 1 418 120186
419 100307 422 ---
423 120588 PLUG, pipe, round 1 424 120012 VALVE, safety, 50 psi 1 425 ---
426 C33049 428 206994 FLUID, tsl 8 oz bottle 1
429 17B715 430 127671
431 122338 432 17C255 433 ---
MOTOR, 6500, low-noise, remote ADAPTER, elbow, 3/4 npti x 1/2 npte BRACKET, mounting, motor, tof200
ROD, tie, vert driver
HEATER, pump, 600 watt PUMP, long shaft, cf; 24V005 only PUMP, long shaft, gf; 24V008 only SCREW, cap, socket hd SENSOR, RTD
NUT, coupling COLLAR, coupling WASHER, lock, ext. tooth
BOLT, mounting, u-bolt NUT, hex SHIELD, pump, tof200; see 24V619, Pump Shield, page 84
LUBRICANT, high temp, thermal TAPE, adhesive, fiberglass
SUPPORT, block, overtemp SWITCH, over temp, fixed, 450°F
(232°C) SCREW, cap, socket bh CABLE, M12, 8p, 5p, m, 0.2 m HOSE, coupled, 13.5 ft (4 m)
1.5
Parts
1 1
2
3
2 1 1 4 1
1 2 1
2 4 1
1
1 2
4 1 1
334130T 83
Page 84
Parts
506
510 505
509
506
504
506
502
501
508
507
503
506
509
507
508
511
ti25162a

24V619, Pump Shield

Ref Part Description Qty
500 24V619PKG 501* --­502* --­503* --­504* --- COVER, pump, top, front 1
505* --­506* ---
84 334130T
SHIELD, pump, TOF200 COVER, pump, bottom COVER, pump, right COVER, pump, left
COVER, pump, top, back FASTENER, thread-cutting screw
1 1 1 1
12
Ref Part Description Qty
507*17J504
508* 104088
509*15J075
510 --­511 C20731
Replacement Warning labels, signs, tags, and cards
are available at no cost.
* Parts included in Kit 24V619PKG.
LABEL, warning RIVET, blind LABEL, safety, hot surface and shock BUSHING, conduit, 1 in FITTING, conduit, connector, 1 in.
2 4 2
1 1
Page 85

Heated Platens

601
605
601
609
608
607
615
614
603
627
624
623
606
601
622
604
619
602
612
613
605
609
625
628
610
626
629
630
611, 629

24V633, Heated Drum Platen, Mega-Flo (Code E-option M) 24V634, Heated Drum Platen, Standard Grid (Code E-option F) 24V635, Heated Drum Platen, Smooth Bottom (no fin) (Code E­option S)

Parts
334130T 85
Page 86
Parts

Heated Platens

24V633, Heated Drum Platen, Mega-Flo (Code E-option M) 24V634, Heated Drum Platen, Standard Grid (Code E-option F) 24V635, Heated Drum Platen, Smooth Bottom (no fin) (Code E­option S)

Ref Part Description Qty
601 --­602 C32204 PACKING, o-ring 1
603 15G967 PLATE, tire 1 604 C19049
605 24Z095 SENSOR, temperature 1 606 C32201 GASKET, follower 1 607 158491
608 158581 COUPLING, hex 1 609 617227
610 246501 611 100361 PLUG, pipe 4
612 100133 WASHER, lock 6 613 C19846 SCREW, cap socket, HD 6 614 150707
--­615 100508 616 --­617 ---
PLATEN — see table below
SCREW, mach, slotted, RND HD
FITTING, nipple
HANDLE, follower, bleed VALVE, blow off
PLATE, designation PLATE, designation; 24V633 only SCREW, drive CONDUCTOR, 14.2 ft (4.3 m) CONDUCTOR, 1.7 ft (0.5 m)
1
1
1
1 1
1 1 2 6 2
Ref Part Description Qty
618 --­619 --­620 112901 NUT, hex 12
621 111640 WASHER, lock, internal 12 622 --- PLUG, follower, plate 1 623 127671
624 122338 625 --- TUBE, ptfe, 1/4 X 5/16 3
626 --- TUBE, ptfe, 3/32 X 5/32 3 627 ---
628 127690
629 127689
630 ---
CONDUCTOR, 0.3 ft (0.09 m) CONDUCTOR, ground
SWITCH, over temp, fixed, 450°F (232°C) SCREW, cap, socket bh
SLEEVE, fiberglass, hi-temp FITTING, adapter, 5/16 in. tube x
1/4 in tube FITTING, adapter, 1/4 in tube x
5/32 in tube TUBE, polyeth, 1/4 OD; 26 ft (7.9 m)
4 1
1
2
3 1
1
1
Platen Model Description Ref. No. 601 Qty. Element Resistance
24V633 Mega-Flo 194254 1 16.5 ohms +1/-2 24V634 Standard Grid 617225 1 19.2 ohms +2/-3 24V635 Smooth Bottom C57358 1 19.2 ohms +2/-3
86 334130T
Page 87
Parts
334130T 87
Page 88
Parts
703
706
701
707
705
704
701
707
705
704708
706
702
1
1
ti25188a
Torque to 50 in-lbs.
1

Drum Ram Post Saddle Clamp

C32463 Option H-1
Ref Part Description Qty
701 C32424 702 160111 703 100103 704 100307 NUT, hex 4
705 100133 706 C38182 707 C32461 708 166265
88 334130T
BOLT, U, 7 in. (177.8 mm) CLAMP, barrel PIN, cotter
WASHER, lock WASHER, plain CLAMP, saddle PIN, pivot
2 1 2
4 2 2 1
Page 89

Drum Ram Post Saddle Clamp

751
759
708
707
706
702
704
710
756
761
703
705
ti25189a
Torque to 50 in-lbs.
1
1
918395 Option H-3
Parts
Ref Part Description Qty
702 100101 703 918421 704 918423 705 617395 PIN, quick release 2
756 100133 707 C19200 708 617433 759 617395 710 100131 761 C32424
334130T 89
SCREW, cap, hex hd CLAMP, back half assembly KIT, repair
WASHER, lock WASHER, plain SPACER, drum clamp CLAMP, saddle NUT, full hex BOLT, U 7 in. (177.8 mm)
8 1 1
8 8 8 4 8 4
Page 90
Parts
ti25190a
801
804
803
805
6
807
803
802
1
Torque to 50 in-lbs.
1

Fiber Drum Reinforcement Shell Clamp

918397 Option H-2
Ref Part Description Qty
6 C32424 801 C32271 802 C19126 803 100133 WASHER, lock 12
804 100307 805 617340 807 617341
BOLT, U, 7 in. (177.8 mm) CLAMSHELL SCREW, cap, hex hd
NUT, hex CLAMP, saddle MOUNT, clam shell
4 1 8
8 4 2
90 334130T
Page 91

Vent Hood Kit, 233559

855
852
853
851
Parts
Ref Part Description Qty
851 --­852 112166 853 100016
855C14038 LABEL, warning 1
VENT hood SCREW, cap, sch WASHER, lock
1 4 4
Replacement Warning labels, signs, tags, and cards
are available at no cost.
334130T 91
Page 92

Accessories and Kits

Accessories and Kits

Wiper Kits

See manual 309196 for installation and repair instruc-
tions.
Part No. Description
253291 Hose/Spring Wiper Kit 253290 Hose and T-Wiper Kit 253289 Twin Hose Wiper Kit 253292 T-Wiper Kit

Applicators and Dispense Valves

Part No. Description
249515 Manual Gun, Top Feed, 240V 249514 Manual Gun, Bottom Feed, 240V 249513
249512
Manual Gun, Top Feed, Electric Switch, 240V Manual Gun, Bottom Feed, Electric Switch, 240V
Air-Operated Heated Dispense Valves
Part No. Description
243694
244951
244909
243701
Automatic Dispense Valve, 240V, Air-Operated Heated Dispense Valve Automatic Endure Dispense Valve, 240V, Air-Operated High Flow Heated Dispense Valve Automatic Endure Dispense Valve, 240V, Air-Operated Snuff-Back Heated Dispense Valve 45 in (114 cm) Distribution Header With Valve, 240V

CGM Installation Kit, 25C994

This kit enables controlling logic, such as a robot con-
troller or PLC continuously monitoring data from the Therm-O-Flow system, as well as optionally controlling the system accordingly. Refer to manual 3A5186 for details on the interface. When ordering this kit, select and order the correct communication gateway module
(CGM) that matches the field bus being used. The fol-
lowing CGM modules are available for the Therm-O-Flow system.
Part No. Description
CGMEP0 EitherNet/IP CGMDN0 DeviceNet CGMPB0 ProfiBus CGMPN0 ProfiNet

Flow Control and Manifolds

Part No. Description
243700
243656
243657
243697
289208 Compact Heated Regulator
Heated Air Operated Mastic Pressure Regulator, 240V 23:1 Heated Pressure Compensator Valve, 240V 51:1 Heated Pressure Compensator Valve, 240V Heated Distribution Manifold, 240V
Includes (2) 3/4 npt(f) inlet check valves, (1) npt 4–ported manifold, (2) 1 in npt(f) outlet gate valves, mounting bracket, 400w 230 VAC heaters, RTD sensor, and 8 pin connector box.
92 334130T
Page 93
Accessories and Kits

Accessory Extension Cables

Use to connect fluid control devices and heated hoses to the electrical control enclosure.
Part No. Description
Connect between controller and heated hose 129300 15 ft, 12 pin to 12 pin 129301 25 ft, 12 pin to 12 pin Connect between controller and heated accessory 129302 15 ft, 12 pin to 8 pin 129303 25 ft, 12 pin to 8 pin Connect between controller and heated devices 129703 25 ft, 12 pin to (2) 8 pin 129304 50 ft, 12 pin to (2) 8 pin Connect between two heated devices 15C294 30 ft, 8 pin to 8 pin

Light Tower Kit, 24W589

Tie Rod Kits
Use to retrofit Check-Mate 800 Displacement Pump to an existing Therm-O-Flow system.
Part No. Description
24V750
24V754 NXT® Tie Rod Kit; see manual 334132
Bulldog® and Senator® Tie Rod Kit; see manual 334131
334130T 93
Page 94
Accessories and Kits

Heated Hoses and Fittings

NOTE: Refer to Heated Hose, Instructions-Parts man-
ual 3A4241 for additional information about heated hoses. See Related Manuals on page 8.
-6 (9/16 in -18
Hose Diameter
Hose Length 3 ft (1 m) None None None 19M410 None None 4 ft (1.2 m) None 19M400 None None None None 6 ft (1.8 m) None 19M401 19M404 19M411 19M416 None 10 ft (3 m) 19M423 19M402 19M405 19M412 19M417 19M421 15 ft (4.6 m) None 19M403 19M406 19M413 19M418 19M422 20 ft (6 m) None None 19M407 19M414 19M419 None 25 ft (7.6 m) None None 19M408 19M415 19M420 None 30 ft (9 m) None None 19M409 None None None Pump Fittings
TOF 20/200 PUMP 1-11 1/2 DUAL OUTLET ADD 120263 TOF MINI 5 PUMP 1/2 NPT DUAL OUTLET ADD 120241
Hose to Hose Fittings
-6 Hose (.308 ID) 125779 123684 123683
-8 Hose (.401 ID) 123684 120241 120242 120244
-10 Hose (.495 ID) 123683 120242 120243 120246
-12 Hose (.617 ID)
-16 Hose (.687 ID)
-20 Hose (1.125 ID) None
Fittings Compensator 51:1, 243657 Compensator 23:1, 243656 Inlet & Outlet: 1-11 1/2 in NPTF
JIC)
16V432 100380
16V432 C20678 C20679 C38006 158586
123683 120265 123683 120265 120267
16V432 100380
-8 (3/4 in -16 JIC)
253267 253268 120260 120261 120262
120244 120246 120247 120248
120244 120267
6308-82
126521
6308-82
-10 (7/8 in -14 JIC)
120246 120267
120246 120267 120268
123135 120266
-12 (1-1/16 in -12 JIC)
123683 120265
120248 120249
123135 126521
123135 123854
-16 (1-5/16 in -12 JIC)
-20 (1-5/8 in -12 JIC)
123683 120265 120267 120244 120267 120246 120267
120249 120268
120804 120268
None
6308-82
126521
6308-82
126521 123135 126521
120249 120268
120250
15D936
94 334130T
Page 95
Accessories and Kits
Hose Diameter
Distribution manifold, 243697 Inlet: 3/4 in NPTF Distribution manifold, 243697 Outlet: 1-11 1/2 in NPTF Compact Heated Regulator, 289208 Inlet & Outlet: 3/8 in NPTF Mastic Regulator, 243700 Inlet & Outlet: 3/4 in NPTF Top and bottom feed guns with and without switch, 249512, 249513, 249514, 249515 Inlet: 7/8-14 (JIC
-10) male Standard, High Flow & Snuff-back Dispense valves, 243694, 244951, 244909 Inlet: 1/2 NPTF Distribution header, 243701 Inlet: 1/2 NPTF Precision Gear Meter PGM Inlet: 1-5/16-12 o-ring face seal Precision Gear Meter PGM Outlet: 3/4 NPTF PCF Metering System Inlet & Outlet: 3/4 NTPF
-6 (9/16 in -18 JIC)
16V432
100896
16V432
100380
16V432
100896
16V432
100896
117677
16V432
16V432
None
16V432
100896
16V432
100896
-8 (3/4 in -16 JIC)
-10 (7/8 in -14 JIC)
-12 (1-1/16 in -12 JIC)
-16 (1-5/16 in -12 JIC)
124286 15Y934 C20708 125661
6308-82
123135 120266
123135 123854
121311 116765 116766
124286 15Y934 C20708 125661
120264 None 120265 None
124287 C20768 94/1027/99 125662
124287 C20768 94/1027/99 125662
None None 124238 124239
124286 15Y934 C20708 125661
124286 15Y934 C20708 125661
116766 120267
-20 (1-5/8 in -12 JIC)
125661 120268
15D936
116766 120267 120268
125661 120268
None
125662 120268
125662 120268
124240
125661 120268
125661 120268
334130T 95
Page 96
Accessories and Kits
ti25236b
7
C
A
B
4
2
3
B
5
6
8
4
J3
J6
J2
5
6J5

8 Channel Upgrade Kit, 24V755

Use this kit to upgrade a 4 Channel system to an 8 channel system.
Ref Part Description Qty
1 --- MODULE, GCA, MZLP 1 2 125856 SCREW, 8–32, serrated flange 4 3 16T440 CAP, souriau, UTS14 2 4 127511 CABLE, board, samtec 1
Ref Part Description Qty
5 16W035 CONNECTOR, jumper 1 6 17A544 HARNESS, power, MZLP2, AWB 1 7 112190 STRAP, wrist, grounding 1 8 17C712 TOKEN, software upgrade 1
96 334130T
Page 97

8 Zone Upgrade Kit Installation

1. Disconnect the plug from the power outlet or turn off the circuit breaker for incoming power.
2. Place the grounding wrist strap (7) over your wrist and secure the other end to a grounded surface.
3. Set the kit’s MZLP (1) rotary switch to “2” on a pri-
mary system or “6” on a secondary system.
4. Remove the screws (B), the plate (A), and the gas-
ket (C) from the system. Use the screws (2) to install the MZLP (1) onto the system as shown.
NOTE: The new MZLP (1) will be refereed to as MZLP2, and the original MZLP that came with the system will be referred to as MZLP 1.
Accessories and Kits
5. Open the Electrical Enclosure door.
NOTE: Do not force the electrical connection. Minimal force is required to seat the connector. If resistance is felt, stop, and verify the connector orientation.
6. Connect the cable (4) to the J3 connector on MZLP 1 and the J6 connector on MZLP 2.
7. Connect the power harness (6) to the MZLP 2 J2 connector and the J5 connector on the AWB. Install the jumper (5) on the MZLP 2 J5 connector.
8. Use fittings and hoses that meet your hose routing needs. See Accessories and Kits, page 92.
9. To ensure your system has the latest software,
insert the token (8) into the ADM. See Update Soft-
ware, page 61.
334130T 97
Page 98
Accessories and Kits
ti25237b
B
A
C
2
1
5
4
J3
4
J6
J2
8
6
J5
5
J2
7
6
3

12 Channel Upgrade Kit, 24V756

Use this kit to upgrade an 8 channel system to a 12 channel system.
Ref Part Description Qty
1 --- MODULE, GCA, MZLP 1 2 125856 SCREW, 8–32, serrated flange 4 3 16T440 CAP, souriau, UTS14 2 4 127511 CABLE, board, samtec 1 5 16W035 CONNECTOR, jumper 1
Ref Part Description Qty
6 17A545 HARNESS, power, MZLP2/3,
AWB 7 112190 STRAP, wrist, grounding 1 8 17C712 TOKEN, software upgrade 1
1
98 334130T
Page 99

12 Zone Upgrade Kit Installation

1. Disconnect the plug from the power outlet or turn off the circuit breaker for incoming power.
2. Place the grounding wrist strap (7) over your wrist and secure the other end to a grounded surface.
3. Set the kit’s MZLP (1) rotary switch to “3” on a pri-
mary system or “7” on a secondary system.
4. Remove the screws (B), plate (A), and the gasket (C) from the system. Use the screws (2) to install the MZLP (1) on to the system as shown.
NOTE: The new MZLP (1) will be referred to as MZLP 3, and the other two that came with the system will be referred to as MZLP 1 and MZLP 2.
Accessories and Kits
5. Open the Electrical Enclosure door.
NOTE: Do not force the electrical connection. Minimal force is required to seat the connector. If resistance is felt, stop, and verify the connector orientation.
6. Connect the cable (4) to the J3 connector on MZLP 2 and the J6 connector on MZLP (1). Remove the existing power cable from MZLP 2 J2 and AWB J5 connector.
7. Connect the power harness (6) to MZLP 2 and the MZLP 3 J2 connector and the J5 connector on the AWB.
8. See Install Heated Hose, page 18, to connect a heated hose or fluid control device.
9. To ensure your system has the latest software,
insert the token (8) into the ADM. See Update Soft-
ware, page 61.
334130T 99
Page 100

Appendix A - ADM

Appendix A - ADM

General Operation

ADM Power

The ADM automatically turns on when the Main Power Switch is turned on.

Screen Navigation

To switch between the Setup and Operation screens,
press . Use the keypad to navigate between screens.

Enable, Disable Heating System

To enable or disable the entire heating system, press
. To set which channels are active when the heat-
ing system is enabled, use the Heat-A and Heat-B Setup screens.
100 334130T
Loading...