The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The
exclamation point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific
risks. When these symbols appear in the body of this manual or on warning labels, refer back to these
Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout
the body of this manual where applicable.
WARNING
FIRE AND EX
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. Paint or
solvent flowing through the system can cause static sparking. To help prevent fire or explosion:
• Electrostatic equipment must be used only by trained, qualified personnel who understand
the requirements of this manual.
• Ground all equipment, personnel, object being sprayed, and conductive objects in or close to
the spray location. Resistance must not exceed 1 megohm. See Grounding instructions.
•Donotuse
• Always use the required arc detection settings and maintain a safe distance of at least 6
inches (152 mm) between the applicator and the workpiece.
• Stop operation immediately if static sparking or repeated arc detection errors occur. Do not
use equipment until you identify and correct the problem.
•Checka
• Use and clean equipment only in a well ventilated location.
• Always turn off and discharge the electrostatics when flushing, cleaning or servicing
equipment.
• Elimin
c drop cloths (potential static arc).
plasti
• Do not plug or unplug power cords or turn lights on or off when flammable fumes are present.
• Keep the spray area clean at all times. Use non-sparking tools to clean residue from the
booth and hangers.
• Keep a
• Interlock the gun air and fluid supply to prevent operation unless ventilation air flow is above
the minimum required value.
• Interlock the Electrostatic Controller and fluid supply with the booth ventilation system to
disable operation if the air flow falls below minimum values. Follow your local codes.
PLOSION HAZARD
pail liners unless they are conductive and grounded.
pplicator resistance and electrical grounding daily.
ate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and
working fire extinguisher in the work location.
CTRIC SHOCK HAZARD
ELE
s equipment must be grounded. Improper grounding, setup, or usage of the system can
Thi
se electric shock.
cau
• Turn off and disconnect power at main switch before disconnecting any cables and before
servicing or installing equipment.
nect only to grounded power source.
•Con
• All electrical wiring must be done by a qualified electrician and comply with all local codes
and regulations.
3A3954B3
Warnings
WARNING
EQUIPMENT MISUSE HAZARD
Misuse can ca
• Do not operate the unit when fatigued or under the influence of drugs or alcohol.
• Do not exceed
system compo
• Use fluids and solvents that are compatible with equipment wetted parts. See Technical
Specifications in all equipment manuals. Read fluid and solvent manufacturer’s warnings.
For complete information about your material, request the Safety Data Sheet (SDS) from
distributor or retailer.
• Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
• Check equi
manufactu
• Do not alter or modify equipment. Alterations or modifications may void agency approvals
and create safety hazards.
• Make sure all equipment is rated and approved for the environment in which youareusingit.
• Use equip
• Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
• Do not kink or over bend hoses or use hoses to pull equipment.
• Keep chil
• Comply with all applicable safety regulations.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work location to help prevent serious
injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective
equipment includes but is not limited to:
• Protective eyewear, and hearing protection.
• Respirators, protective clothing, and gloves as recommended by the fluid and solvent
manufacturer.
use death or serious injury.
the maximum working pressure or temperature rating of the lowest rated
nent. See Technical Specifications in all equipment manuals.
pment daily. Repair or replace worn or damaged parts immediately with genuine
rer’s replacement parts only.
ment only for its intended purpose. Call your distributor for information.
dren and animals away from work location.
4
3A3954B
ProBell System I
nformation
ProBell Syste
Information
The ProBell Ai
the ProBell R
Air Controll
paint, dump,
electronica
air pressur
all air in th
used to set t
This manual
Controller
troublesh
Rotary App
all system
connect th
system gro
The applic
informat
(3A3955)
the Air Co
r Controller is an optional component in
otary Applicator system. The Electronic
er sends air activation signals for the
and solvent (cup wash) valves. It also
lly controls the inner and outer shaping
es. The Manual Air Controller controls
e system. Manual air regulators are
he turbine and shaping air pressures.
covers information specific to the Air
s. It includes information on installation,
ooting, repair, and parts. See the ProBell
licator manual (334452 or 334626) for
information, including how to install and
e whole system, required interlocks,
unding, and required electrical tests.
ator manual also contains all operation
ion. See the System Logic Controller Manual
for details on how to set up parameters for
ntroller.
m
3A3954B5
Figure 1 ProBell Electronic Air Controller, shown on
Cart (sold separately)
System Connections and Features
System Connec
Air LinePort Label
B(BearingAi
BK (Braking Air)
BR (Bearing Air Return)
DT (Dump V
PT (Paint Valve Trigger)
SI (Shaping Air Inner)
r)
alve Trigger)
tions and Features
Speed Controller
Connections
**
**
Electronic
Air Controller
Connections
Manual Air
Controller
Connections
SO (Sha
ST (Solvent Trigger)
TA (Turbine Air)
Aux
flex
*In
spe
ping Air Outer)
**
iliary Triggers (for system
ibility)
systems with a speed controller, bearing air, bearing air return, and turbine air must be used from the
ed controller, not the manual air controller.
1, 2, 3,
63A3954B
Component Ident
ification
Component Ide
Electronic Ai
r Controller
ntification
Ref.Compo
A
BTerm
CSolenoid Valves — send air activation
D
E
Contr
of al
conn
signals for paint, dump, and solvent valves;
auxiliary signals available for system
flexibility
Air Manifold — directs incoming air to the
controller components
In
of
nent
ol Module — manages the operation
l air controller components
inal Blocks —provide electrical wire
ections
ner Shaping Air Solenoid Valve — shuts
f the flow of the inner shaping air
3A3954B
Ref.Compo
F
G
HVolt
J
Outer
off t
Volt
volt
volt
Optocoupler — isolated input to trigger
paint valve from PLC
nent
Shaping Air Solenoid Valve — shuts
he flow of the outer shaping air
age to Pressure Regulator — converts
age to pressure for the inner shaping air
age to Pressure Regulator — converts
age to pressure for the outer shaping air
7
Component Ident
ification
Manual Air Con
troller
Ref.Component
A
BTerminal Blocks —provide electrical wire
CSole
J
K
L
M
Control Module — manages the operation
of all air controller components
connections
noid Valves — send air activation
als for paint, dump, and solvent valves;
sign
liary signals available for system
auxi
bility
flexi
Pressure Switch — verifies that the bearing
air is at least 70 psi.
High-Flow Remote — piloted regulator for
turbine air
gh-Flow Remote — piloted regulator for
Hi
ner shaping air
in
High-Flow Remote — piloted regulator for
outer shaping air
Ref.Component
N
P
RTurb
SOuter Shaping Air Gauge
T
U
VAir
W
Outer Shaping Air Regulator — air pressure
signal to regulator M
Shaping Air Regulator — air pressure
Inner
l to regulator L
signa
ine Air Regulator — air pressure signal
gulator K
to re
Inner Shaping Air Gauge
Turbine Air Gauge
Filter — supplementary coalescing
filter, protects the bearing from any
air
ticles that get through the main air
par
ering system.
filt
Optocoupler — isolated input to trigger
paint valve from PLC
83A3954B
Installation
Mount the Controller
To reduce the risk of fire or explosion, do not install
equipment approved only for a non-hazardous
location in a hazardous location.
NOTE: Install the air controller in a non-hazardous
location only.
The air controller can be mounted on the control box
stand or wall mounted. The box comes with four
mounting brackets installed in a vertical orientation.
Remove and turn the brackets if a horizontal
orientation works better for your installation.
Installation
Wall Mounting
The pre-installed mounting brackets can be used to
mount the controller on any flat wall. Mount the Air
Controller in the non-hazardous area, as close to
the applicator as possible to minimize pressure loss
in the air lines.
1. Determine the mounting location. Ensure that
the wall is strong enough to support the weight
of the mounting bracket and the controller. See
Technical Specifications, page 41.
2. See the Dimensions or use the box as a template
to mark the mounting hole locations.
3. Drill holes and use four screws to attach the
controller to the wall.
Electron
ic Air Controller
3A3954B9
Installation
Manual Air Controller
Cart Mounting
For some ordering options, the air controller will be
mounted on the cart at the factory. If the cart was
ordered separately, follow these steps:
1. Remo
ve the 4 mounting brackets. Turn them so
are oriented horizontally. Reattach them to
they
ir controller box.
the a
2. Use four screws (provided with cart) to mount
the air controller box on the cart in the location
showninFigure1.
103A3954B
Installation
Ground the Con
The equipment must be grounded to reduce the
risk of static sparking and electric shock. Electric
or static sparking can cause fumes to ignite or
explode. Improper grounding can cause electric
shock. Grounding provides an escape wire for the
electric current.
For full system grounding instructions and
requirements, see your ProBell Rotary Applicator
manual (334452 or 334626). Use the ground wire
and clamp provided to ground the Air Controller to a
true earth ground.
troller
Figure 3 Manual Air Controller Grounding Location
Figure 2 Electronic Air Controller Grounding Location
3A3954B
11
Controller Connections
Controller Co
nnections
Overview
Air control in your ProBell system will use one of the
following common setups:
• All air control is provided by the Graco Manual Air
Controller.
• Air controls are split between the Graco Electronic
Air Controller and the Graco Speed Controller. Be
sure your system includes a power supply (sold
separately) to be mounted on either controller.
Manual Air Controller
• Your system uses some combination of Graco
controllers and your existing devices. Air
control will then require a combination of the
connections shown in the figures and use of
the Auxiliary Triggers. Be sure your system
includes a power supply (sold separately). See
ProBell System Information, page 5 for all system
connection information.
Electronic Air Control
2
1
3A3954B
Table 1 Key for Cable Connections, Electrical or Manual Air Controller
Controller Connections
Ref.
Port LabelLabel
Description
Color
A
AUX-APorts 1–3Black
AUX-EBlack
BRed
BRRed
CAN
Black
DTWhite
Mounting Holes for Power Supply
Auxiliary Ai
r Ports — Use 4 mm (5/32 in) tubing.
Auxiliary port for optional optocoupler wiring.
Bearing Air
— Use 8 mm (5/16 in) OD tube
Bearing Air Return – Use 4 mm (5/32 in) tubing.
Graco CAN/Power (24VDC)
Dump Val
ve Trigger – Use 4 mm (5/32 in) tubing.
MABlackMain Air Port — 1/2 in. npt
PT
GreenPaint V
alve Trigger – Use 4 mm (5/32 in) tubing.
SIGrayShaping Air Inner — Use 8 mm (5/16 in.) tubing.
SO
ST
Blue
Black
TABrow
Shaping Air Outer — Use 8 mm (5/16 in.) tubing.
ent Trigger (Cup Wash) – Use 4 mm (5/32 in) tubing.
Solv
n
Turbine Air — Use 8 mm (5/16 in.) tubing with 1 mm (0.04 in) wall to
minimize pressure drop.
3A3954B13
Controller Connections
Connect Air Li
Graco Air Controllers are labeled with the same
reference letters as the applicator, for easier
matching.
nes
NOTICE
Use filtered air to prevent contamination of the
paint finish and to prevent damage to the air
bearing. Air that is not adequately filtered can clog
bearing air passages and cause bearing failure.
The ProBell Rotary Applicator Manual contains
detailed filtering specifications.
NOTE: For the turbine air (TA), bearing air (B),
shaping air inner (SI) and shaping air outer (SO)
lines, use 8 mm (5/16 in) OD tube with 1 mm (0.04
in) wall. For the bearing air return (BR) and the three
triggers (DT, PT, and ST), use 4 mm (5/32 in) tube.
NOTICE
Take great care to connect the air lines to the
correct ports. Incorrect air line connections will
damage the applicator.
1. Connect all nine required air lines to the
applicator first. See your applicator manual for
instructions.
2. Air Activation Signal Lines (DT, PT, ST): Connect
the lines that provide air activation signals for the
dumpvalve(DT),thepaintvalve(PT)andthe
solvent valve (ST).
3. Shaping Air Lines (SI, SO): Connect the lines
that provide the shaping air inner (SI) and the
shaping air outer (SO).
4. Turbine Air (TA), Bearing Air (B), and Bearing Air
Return (BR):
Connect Commu
The air controllers (Manual or Electronic)
communicate to the rest of the system over Graco
CAN cables. Each component and the power supply
must be on the Graco CAN network. The best
connection pattern depends on whether the Air
Controller is electronic or manual.
1. Connect a Gra
Controller
(DD).
2. If the power
Controller
on the spli
Controlle
terminati
If not, the
3. Manual Air
a. Connect a Graco CAN cable from the power
b. Connect a Graco CAN cable from the
(CC) to the System Logic Controller
, install the termination resistor (201)
tter inside the box. NOTE: If the Air
r was purchased as part of a system, the
on resistor will be installed at the factory.
resistor comes with the power supply.
Controller:
supply (AA) to the right (inside) port on the
Air Controller (BB).
other port on the Air Controller (BB) to the
Electrostatic Controller (CC).
nication Cables
co CAN cable from Electrostatic
supply is attached to the Air
• Electronic Air Controller: Connect these air line
to the Graco speed controller (if present) or to
another air control device in your system.
• Manual Air Controller: Connect these air lines
to the ports with the matching labels.
5. Connect the main air supply line into the main air
fitting (MA, Ref. 7) on the side of the box.
E: Once the air is applied, it will flow freely
NOT
Port B. The controller has no option to turn
out
is air off. (Manual Controller only)
th
4
1
4. Elec
tronic Air Controller (with Speed Controller):
a. Connect a Graco CAN cable from the power
supply (AA) to the lower/rear port on the
Speed Controller (EE)
b. Connect a Graco CAN cable from the Speed
Controller (EE) to the Air Controller (BB).
c. Connect a Graco CAN cable from the Air
Controller (BB) to the Electrostatic Controller
(CC).
3A3954B
One Gun Wiring
Two Gun Wiring
Controller Connections
Other configurations (not shown) are possible. Follow these rules when building the CAN network.
• Connect controllers in series.
• A termination resistor must be installed on the
power supply port.
3A3954B15
• Remove any other termination resistors from the
system.
• Set IDs on all boxes.
Controller Connections
Connect Power
One power supply is required in the Graco CAN
network, typically mounted on the bottom of the
Speed Controller, or the Manual Air Controller.
1. Connect a pow
connector. A
America is pr
Technical Sp
supply is so
but include
2. Connect the
See Technic
informati
er cord to the power supply
cord suitable for use in North
ovided with the power supply. See
ecifications, page 41. The power
ld separately from the air controllers,
d in system purchases.
other end of the cord to AC power.
al Specifications, page 41,formore
on.
3. Replace the plug.
4. Restart the system by removing and reapplying
power.
Wiring the Pai
The Paint Trigger Input provides a means to signal
the System Logic Controller to activate the paint
trigger solenoid. This normally open (maintained)
contact provides a signal to the system to indicate
whether or not to trigger spray device or spray device
is triggered (Input Only). If the input is OPEN the
system deactivates paint trigger solenoid. The input
must be maintained CLOSED to activate paint trigger
solenoid.
NOTE: The P
enabled on
to ’Local’
and the spr
network c
Logic Con
The Paint Trigger Input uses an optocoupler to
protect the Graco ProBell air control box from outside
voltages.
the System Logic Controller. If it is set
or ‘Network’, the discrete input is ignored
ay device trigger signal is handled via the
ommunications, or manually. (see System
troller manual 3A3955).
nt Trigger Input
aint Trigger discrete input must be
Set Air Control Identity
The air controller comes preset from the factory to
control one applicator. In two-applicator systems, the
identity of the control module must be set in order to
communicate with the system properly.
1. Remove plug (24) to access control module
rotary switch by pushing from the inside of the
box with a screwdriver.
2. Using a screwdriver, set the control module
rotary switch to “1” for the air controller that
controls the second applicator.
• Optocoupler ports 13+ and 14 are wired to the
control module.
• Optocoupler ports A1+ and A2- are wired to the
external device or PLC.
Apply t
Only on
the two
he 24 VDC signal to A1+ and GND to A2–.
e A2– port needs to be connected to GND, as
ports labeled A2– are connected internally.
tion
A1+ (relative to A2–)
DC
24 V
Less than 13.5 VDC
Func
Paint Trigger Active
Paint Trigger
Inactive
163A3954B
Controller Connections
Wiring the Opt
The Optional Interlock Input provides a means
to signal the System Logic Controller to stop the
ProBell system. This normally open contact turns
the applicator off when activated. If the ProBell air
controller reads the input as CLOSED it interrupts
system operation and puts the gun into Gun Off
mode. If the input is read as OPEN, the system
operates normally.
The optiona
pre-instal
separately
Interlock I
For each ProBell Air Controller, the Interlock Input is
on different terminal blocks. Remove the wires in the
existing terminal blocks and install in the Optocoupler
ports as shown below.
Optocoupler
Port 14
Optocou
Port 13
l interlock optocoupler does not come
led and must be purchased and installed
. Install kit 24Z226 to use the Optional
nput.
pler
+
ional Interlock Input
Terminal Block
Manual Air
Controller
98
109
Electronic Air
Controller
The Optional Interlock Input uses an optocoupler to
protect the Graco ProBell air control box from outside
voltages.
• Optocoupler p
control modul
• Optocoupler p
external dev
Apply the 24 VDC signal to A1+ and GND to A2–.
Only one A2– port needs to be connected to GND, as
the two ports labeled A2– are connected internally.
A1+ (relative to A2–)
24 VDC
Less than 13.5 VDC
orts 13+ and 14 are wired to the
e.
orts A1+ and A2- are wired to the
ice or PLC.
Function
Interloc
k Activated
(system s
Interlock Inactive
(system run)
top)
NOTICE
To prevent damage to equipment, do not use these
terminal blocks without an optocoupler present.
3A3954B
17
Troubleshooting
Troubleshooting
Table 2 Contro
Module Status LED Signal
Green on
YellowInternal communication is in progress.
Red solid
Red flashing fastThe system is uploading software.
Red flashing slow
Table3Co
Code
CAP1
or
CAP2
CA00
l Module LED Diagnostics
mmunication Errors
Event
Type
Alarm
Alarm
NameDescrip
Communication
Error Air
Control
Communication Error Logic
Controller
Diagnosis
The system is powered up.
Hardware fa
Token erro
tion
The System Logic
Controller has lost
communication
with the air
controller.
System Logic
Controller
communication
has been lost.
ilure
r
Solution
• Verify Graco CAN connection on bottom of the Air
Controller.
• Check status LEDs on the control module.
• Cycle power.
Verify Graco CAN connection on the System Logic
Controller
Solution
———
———
Replace the module.
———
Remove the
upload th
again.
token and
e software token
CDP1
or
CDD
AlarmDuplicate
2
Air Controller
ystem Logic
The S
roller sees
Cont
or more air
two
trollers set to
con
same gun.
the
•Thea
•Adj
ir controller has the same CAN ID as another
le.
modu
ust the selector switch on the Control Module. See
Air Control Identity, page 16 for instructions.
Set
183A3954B
Table 4 Electronic Shaping Air Errors
Troubleshooting
Code
P111 or
P112
P121 or
P122
P211 or
P212
P221 or
P222
P311 or
P312
P321 or
P322
P411 o
P412
Event
NameDescription
Type
AlarmPressure Low,
Air 1 (Inner)
AlarmPressure Low,
Air 2 (Outer)
Deviation
Deviation
Deviation
Pressure Low,
Air 1 (Inner)
Pressure
Air 2 (Out
Pressure
High, Air 1
(Inner)
Deviation
Pressure
High, Air 2
(Outer)
r
AlarmPress
High,
r)
(Inne
ure
Air 1
Low,
er)
Actual air pre
is lower than t
limit for long
alarm time (a
ssure 1
he alarm
er than the
s set on Gun
Screen 2).
Actual air pressure 2
is lower than the alarm
limit for longer than the
alarm time (as set on Gun
Screen 2).
Actual air pressure 1 is
lower than the deviation
limit for longer than the
deviation time (as set on
Gun Screen 2).
Actual ai
lower tha
limit for
deviatio
Gun Scree
r pressure 2 is
n the deviation
longer than the
ntime(asseton
n2).
Actual air pressure 1 is
higher than the deviation
limit for longer than the
deviation time (as set on
Gun Screen 2).
Actual air pressure 2 is
higher than the deviation
limit for longer that the
deviation time (as set on
Gun Screen 2).
l air pressure 1 is
Actua
r than the alarm
highe
for longer than the
limit
time (as set on Gun
alarm
en 2).
Scre
Solution
Verify shaping air 1 (inner) hose is not
cut or split.
Verify shaping air 2 (outer) hose is not
cut or split.
Verify sha
cut or spli
ping air 1 (inner) hose is not
t.
Verify shaping air 2 (outer) hose is not
cut or split.
• Calibrate the voltage to pressure
regulator. See the System Logic
Controller manual.
• Verify air tubing is connected properly.
• Verify cable connection between
voltage to pressure (V2P) regulator
and connector 6 on the control
module. Retry calibration.
• Replace the V2P regulator.
P421 or
P422
AlarmPressure
High, Air 2
(Outer)
P511 or
P512
P521 or
P522
Alarm
Alarm
ibration
Cal
or, Inner
Err
aping Air
Sh
Calibration
Error, Outer
Shaping Air
3A3954B19
Actual air pressure 2 is
higher than the alarm
limit for longer than the
alarm time (as set on Gun
Screen 2).
returned value of
The
inner shaping air
the
libration is out of range.
ca
The returned value of
the outer shaping air
calibration is out of range.
• Relieve inlet air pressure. Retry
calibration. See System Logic
Controller manual.
• Verify cable connection between
voltage to pressure (V2P) regulator
and connector 6 on the control
module. Retry calibration.
• Replace cable 17K902.
• Replace volltage to pressure regulator
Troubleshooting
Code
Event
Type
P611 or
Alarm
P612
P6Y1 or
Alarm
P6Y2
Table 5 Solenoid Errors
Code
Event
NameDescriptionRemedy
Type
WJ31
or
Alarm
Paint Solenoid
Removed
WJ32
WJ41
or
WJ42
WJ51
or
WJ52
AlarmDump
Solenoid
Removed
Alarm
Cup Wash
Solenoid
Removed
NameDescription
Sensor
Disconnected,
Inner Shaping
The returned value of the
pressure sensor for inner
shaping air is zero
Air
Sensor
Disconnected,
Outer Shaping
The returned value of the
pressure sensor for outer
shaping air is zero.
Air.
System does not detect the
Paint Trigger solenoid.
System does not detect the
Dump Trigger solenoid.
System does not detect the
CupWashsolenoid.
Solution
• Replace cable 17K902.
• Replace volltage to pressure regulator
Electronic: Verify wiring on terminals 1
and 3. Manual: Verify wiring on terminals
1 and 2.
Electronic: Verify wiring on terminals 4
and 5. Manual: Verify wiring on terminals
5 and 6.
Electronic: Verify wiring on terminals 6
and 7. Manual: Verify wiring on terminals
7 and 8.
WJ61
or
WJ62
WJ71
or
WJ72
WJ81
or
WJ82
WJ91
or
WJ92
WJA1
or
WJa2
WJB1
or
WJB2
Alarm
Inner Shaping
Air Solenoid
Removed
Alarm
Outer Shaping
Air Solenoid
Removed
AlarmTurbine Air
Solenoid
Removed
AlarmAuxiliary 1
Solenoid
Removed
AlarmAuxiliary 2
Solenoid
Removed
AlarmAuxiliary 3
Solenoid
Removed
System does not detect
the Shaping Air 1 (inner)
solenoid.
System does not detect
the Shaping Air 2 (outer)
solenoid.
System does not detect
the Turbine Air solenoid,
Manual Air Controller.
System does not detect the
Auxiliary 1 solenoid.
System does not detect the
Auxiliary 2 solenoid.
System does not detect the
Auxiliary 3 solenoid.
Table 6 Bearing Air Pressure Errors (Manual Air Controller Only)
Code
Event
NameDescription
Type
Electronic: Verify wiring on terminals
13 and 14. Manual: Verify wiring on
terminals 17 and 18.
Electronic: Verify wiring on terminals
20 and 21. Manual: Verify wiring on
terminals 20 and 21.
Manual: Verify wiring on terminals 3 and
4 in the Manual Air Controller.
Electronic: Verify wiring on terminals
27and 28. Manual: Verify wiring on
terminals 23 and 24.
Electronic: Verify wiring on terminals
29 and 30. Manual: Verify wiring on
terminals 25 and 26.
Electronic: Verify wiring on terminals
31 and 32. Manual: Verify wiring on
terminals 27 and 28.
Solution
P9P1
or
Alarm
Air Control
Pressure Low
P9P2
203A3954B
Air Controller no longer
detects bearing air.
(Manual air controller
only.)
Verify that inlet air pressure and flow are
sufficient.
Table 7 Maintenance Advisories
Troubleshooting
Code
Event
NameDescriptionRemedy
Type
MD11AdvisoryMaintenance V
alve
Paint Gun 1
MD12AdvisoryMaintenance Valve
Paint Gun 2
MD21AdvisoryMaintenance Valve
Dump Gun 1
MD22AdvisoryMaintenanc
eValve
Dump Gun 2
MD31AdvisoryMaintenance Valve
CupWashGun1
MD32AdvisoryMaintenance Valve
CupWashGun2
MD41AdvisoryMainten
Air 1 Gun
ance Valve
1
MD42AdvisoryMaintenance Valve
Air 1 Gun 2
MD51AdvisoryMaintenance Valve
Air 2 Gun 1
MD52Advis
ory
enance Valve
Maint
Gun 2
Air 2
Gun1paintvalveisduefor
maintenance.
Gun 2 paint va
maintenance
lve is due for
.
Gun 1 dump valve is due
for maintenance.
Gun 2 dump valve is due
for maintenance.
Gun 1 cup w
due for ma
ash valve is
intenance.
Gun1cupwashvalveis
due for maintenance.
Gun1Air1valveisduefor
maintenance.
Gun2Ai
mainte
r 1 valve is due for
nance.
Gun1Air2valveisduefor
maintenance.
Gun2Air2valveisduefor
maintenance.
•Perfo
• Clear
rm required maintenance
advisory and clear
e count on corresponding
valv
tanance Screen
Main
MD61AdvisoryMaintenance Valve
Auxiliary 1 Gun 1
MD62AdvisoryMaintenance Valve
Auxiliary 1 Gun 2
MD
71
Ad
visory
intenance Valve
Ma
xiliary 2 Gun 1
Au
MD72AdvisoryMaintenance Valve
Auxiliary 2 Gun 2
MD81AdvisoryMaintenance Valve
Auxiliary 3 Gun 1
MD82AdvisoryMaintenance Valve
Auxiliary 3 Gun 2
MD91AdvisoryMaintenance Valve
Turbine Gun 1
MD92AdvisoryMaintenance Valve
Turbine Gun 2
MMUXAdvisory
Maintenance USB
Logs Full
Gun 1
due
Auxiliary 1 valve is
for maintenance.
Gun 2 Auxiliary 1 valve is
due for maintenance.
Gun 1 Auxiliary 2 valve is
due for maintenance.
un 2 Auxiliary 2 valve is
G
ue for maintenance.
d
Gun 1 Auxiliary 3 valve is
due for maintenance.
Gun 2 Auxiliary 3 valve is
due for maintenance.
Gun 1 Turbine valve is due
for maintenance
Gun 2 Turbine valve is due
for maintenance
USB maintenance logs are
full.
• UseaUSBdrivetosave
maintenance logs
3A3954B
21
Repair
Repair
Electrical Schematics
AUX 2 SOLENOID
AUX 1 SOLENOID
#1
#2
COM
+24VDC
+24VDC
COM
AUX 3 SOLENOID
#3
COM
+24VDC
-UNUSED
22
BLOCKS
TERMINAL
CAN 1
123451234
1 2
-UNUSED
2 BROWN
3 GREEN
4 YELLOW
5 GRAY
6 PINK
7 BLUE
-UNUSED
8 RED
232425262728293031
1 WHITE
5
CAN 2
5
BROWN 1
1
2345678
BLOCKS
TERMINAL
1
BLUE 3
WHITE 2
BLACK 4
1
GRAY 5
UNUSED
UNUSED
1
234
234
5
6
MODULE
CONTROL
BROWN 1
13+
14
9
OPTOCOUPLER
A1+
A2-
A2-
5
7
2
BLUE 3
WHITE 2
BLACK 4
1011121314151617181920
3
BLUE 3
GRAY 5
DRAIN 2
BLACK 4
BROWN 1
UNUSED-
DRAIN 2
BROWN 1
UNUSED-
4
BLUE 3
BLACK 4
21
1
Figure 4 Manual Air Controller
2
2
234
CABLE
BULKHEAD "A"
5
1
SPLITTER
234
CABLE
5
CABLE
BULKHEAD "B"
+24VDC
COM
#6
PAINT TRIGGER SOLENOID
+24VDC
COM
#7
TURBINE AIR SOLENOID
+24VDC
COM
#5
DUMP VALVE SOLENOID
+24VDC
COM
#4
SOLVENT VALVE SOLENOID
COM
COM
ACTIVE LOW INPUT
ACTIVE HIGH INPUT
INTERLOCK IN
TRIGGER IN
A
A
BLACK
RED
WHITE
NC
NO
COM
PRESSURE SWITCH
17M109
COM
+24VDC
#8
INNER AIR (1) SOLENOID
COM
+24VDC
#9
OUTER AIR (2) SOLENOID
3A3954B
AUX 1 SOLENOID
#1
COM
+24VDC
-UNUSED
26
2728293031323334353637
BLOCKS
TERMINAL
1 WHITE
2 BROWN
3 GREEN
AUX 3 SOLENOID
AUX 2 SOLENOID
#2
#3
COM
COM
+24VDC
+24VDC
-UNUSED
4 YELLOW
5 GRAY
6 PINK
7 BLUE
8 RED
5
-UNUSED -UNUSED
-UNUSED
1 BROWN
2 WHITE
3 BLUE
-UNUSED
38
1
234
4 BLACK
5 DRAIN
6
MODULE
CONTROL
Repair
UNUSED
5
7
Figure 5 Electronic Air Controller
CAN 1
234
1
1
234
5
5
CABLE
BULKHEAD
1
1
CONNECTOR
234
SPLITTER
1 2
234
CAN 2
5
5
BLOCKS
TERMINAL
1
BLUE 3
WHITE 2
BROWN 1
1
23456
UNUSED-
+24VDC
COM
#6
PAINT TRIGGER SOLENOID
GRAY 5
BLACK 4
+24VDC
COM
#5
DUMP VALVE SOLENOID
7
+24VDC
COM
#4
SOLVENT VALVE SOLENOID
3
GRAY 5
DRAIN 2
BROWN 1
101112131415161718192021222324
UNUSED-
UNUSED-
+24VDC
COM
1 BROWN
#8
INNER AIR (1) SOLENOID
WHITE 2
BROWN 1
13+
14
8
OPTOCOUPLER
A1+
A2-
A2-
COM
ACTIVE HIGH INPUT
TRIGGER IN
2
BLUE 3
BLACK 4
9
BLUE 3
BLACK 4
2 WHITE
3 BLUE
4 BLACK
5 GREY
V/P TRANSDUCER
SHAPING AIR 1
DRAIN 2
BROWN 1
-UNUSED
4
BLUE 3
BLACK 4
+24VDC
COM
1 BROWN
2 WHITE
#9
V/P TRANSDUCER
OUTER AIR (2) SOLENOID
3 BLUE
4 BLACK
SHAPING AIR 2
-UNUSED
25
5 GREY
3A3954B23
Repair
Prepare for Se
• To avoid electric shock, remove power from the
system before servicing.
• All electrical wiring must be done by a qualified
electrician and comply with all local codes and
regulations.
• Do not substitute or modify system components.
•ReadWarnings, page 3 .
rvice
NOTICE
To avoid equipment damage, the bearing air must
be on while the turbine is spinning and must not be
turned off until the cup comes to a complete stop.
1. Verify that the cup is not rotating.
2. Close the air shutoff valve on the air controller
air supply line.
3. Unplug the power supply.
Replace the Co
Follow these instructions to replace the control
module (Refs. 2 and 6). Order Kit 25C423, which
includes the module and the necessary software
token.
1. Follow direc
2. Label each ca
connection
the base mod
3. Remove the m
4. Loosen the f
module (6)
5. Remove fas
base (2).
6. Install th
and 4).
7. Install t
fastener
8. Reinstal
9. Refer to
you did n
cover. R
table fo
10. Load the
module
.
e new base (2). Tighten fasteners (3
he new control module (6). Tighten the
s (6a).
l the module door (5).
the labels to reconnect each cable. If
ot use labels, remove the wire duct
efer to the schematic and the following
r connection information.
correct software onto the control
, using the token.
ntrol Module
tions at Prepare for Service, page 24.
ble with the number of the
port. Disconnect all cables from both
ule (2) and the cube module (6).
odule door (5).
asteners (6a) and remove the control
teners (3 and 4), then remove the
NOTICE
The mo
insta
Contr
softw
dule will not work if the software is not
lled. See directions in the System Logic
oller manual (3A3955) for loading the
are.
4
2
3A3954B
Table 8 Replace Control Module, Electronic Air Controller
Repair
Table 9 Replace Control Module, Manual Air Controller
3A3954B25
Repair
Front Side
Table 10 Electronic Air Controller
Module
Purpose
System Connection
Connection
1
Paint Trigger Solenoid
Dump Trigger Solenoid
Solvent Trigger Solenoid
2Trigger In
3
Shaping Air Inner Solenoid and V2P
Terminal Blocks 1 and 3
Terminal Blocks 4 and 5
Terminal Blocks 6 and 7
Optocoupler
Terminal Blocks 12–17
Regulator
4
Shaping Air Outer Solenoid and V2P
Terminal Blocks 19–24
Regulator
5
Auxiliary Solenoids
Terminal Blocks 27–32, 35
6V2P Regulator Pressure FeedbackNone
7
Unused
Back Side
Table 11 Manual Air Controller
Module
Purpose
Connection
1
Turbine Air Solenoid
Paint Trigger Solenoid
Dump Trigger Solenoid
Solvent Trigger Solenoid
2
Trigger In
Pressure Switch
3
4
5
Shaping Air Inner Solenoid
Shaping Air Outer Solenoid
Auxiliary Solenoids
6Unused
7
263A3954B
System Connection
Terminal Blocks 1 and 2
Terminal Blocks 3 and 4
Terminal Blocks 5 and 6
Terminal Blocks 7 and 8
Optocoupler
Terminal Blocks 11–13
Terminal Blocks 15–17
Terminal Blocks 19–21
Terminal Blocks 23–27, 28, and 31
Unused
Repair
Replace a Trig
1. Follow directions at Prepare for Service, page 24.
2. Disconnect the electrical wires. See table.
Table 12 Wire Connections, Solenoids 4–7
Solenoid
4 — Solvent
5 — Dump4 and 55 and 6
6 — Paint1 and 31 and 2
7 — TurbineN/A3 and 4
ger or Auxiliary Solenoid Valve
Terminal Blocks
Electronic
Controls
6 and 77 and 8
Manual
Controls
3. Remove the solenoid (34).
4. Install a new solenoid (34). Connect the line
power and the COM wire to the two terminal
blocks listed. It doesn’t matter which wire goes to
which terminal. See table.
5. Test the new solenoid using maintenance
screens on the System Logic Controller. See
manual 3A3955, System Logic Controller, for
more information.
ctronic Air Controller
Ele
3A3954B
ual Air Controller
Man
27
Repair
Replace the Vo
NOTE: This part is not used on Manual Air
Controllers.
Follow these d
pressure reg
1. Follow directions at Prepare for Service, page 24.
2. Remove the turbine air solenoid. See Replace a
Trigger or Auxiliary Solenoid Valve, page 27.
3. Disconnect the cable (44) and tube (50).
4. Remove screws (35) to remove the regulator
assembly, including the bracket (40).
5. Remove screws (40a) to disconnect the regulator
from the bracket.
6. Remove the elbows (10, 12),the muffler (61) and
the reducer bushing (69).
7. Apply thread sealant to the threads on the elbows
(10, 12) and the reducer bushing (69). Tighten
them into the new regulator (41), along with the
muffler (61).
irections to replace the voltage to
ulator (41).
ltage to Pressure (V2P) Regulator
8. Use screws (40a) to attach the new regulator
(41) to the bracket.
11. Reinstall the turbine air solenoid. See Replace
a Trigger or Auxiliary Solenoid Valve, page 27.
Also see the calibration procedure on the System
Logic Controller manual, 3A3955, in Inital
Setup/Calibration Screen
NOTE: For better accuracy, perform a “zero clear”
as detailed in the instruction manual that is included
with the V2P regulator. The unit should be powered
on with no air applied.
.
283A3954B
Repair
Replace A Shap
NOTE: This part is not used on Manual Air
Controllers.
Follow these d
shaping air (
(SO) solenoi
1. Follow directions at Prepare for Service, page 24.
2. Disconnect air tubing (49).
3. Disconnect the electrical wires. See table.
Table 13 Wi
Solenoid
Inner Shap
Outer Shaping Air
4. Loosen the swivel on fitting (58). Remove the
solenoid assembly.
irections to replace either the inner
SI) solenoid (57) or the outer shaping air
d(57).
re Connections, Solenoids 8 and 9
ing Air
ing Air Solenoid Valve
Terminal B
13 and 14
20 and 21
lock
5. Remove fittings (58, 59) and muffler (61) from
the solenoid (57).
6. Apply thread sealant to the threads on the fittings
(58, 59). Tighten them into the new solenoid,
along with the muffler (61).
7. Install the solenoid assembly and tighten the
swivel on fitting (58).
8. Reconnect the wires. Connect the line power
and the COM wire to the two terminal blocks
listed. It doesn’t matter which wire goes to which
terminal. See the table.
9. Reconnect air tubing (49).
10. Test new solenoid using maintenance screens on
the system logic controller. See manual 3A3955,
System Logic Controller, for more information.
3A3954B29
Repair
Replace the Pr
NOTE: This part is not used on Electronic Air
Controllers.
Follow these d
(101, Kit 26A
1. Follow directions at Prepare for Service, page 24.
2. Disconnect the air tubing (26).
3. Disconnect the wires (110) from the pressure
switch (101).
4. Remove two screws (96), then remove the
pressure switch assembly.
5. Use screws (96) to attach the pressure switch
assembly to the box.
6. Reconnect the wires (110).
7. Reconnect the air tubing (26).
292).
Pressure Switch Wire
essure Switch
irections to replace the pressure switch
Terminal Block
COM
NO
NC
11
12
13
Replace a Pres
NOTE: This part is not used on Electronic Air
Controllers.
Follow these d
(104)
1. Follow directions at Prepare for Service, page 24.
2. Remove the air tubing (26).
3. Loosen the swivel on elbow (107).
4. Remove the nuts (104a and 40b) the bracket
(104c) and the pressure gauge (104).
5. Install a new pressure gauge (104). Slide the
bracket (104c) onto the gauge and secure with
nuts (104a and 104b).
6. Tighten the swivel on the elbow (107).
7. Reconnect the air tubing (26).
irectionstoreplaceapressuregauge
sure Gauge
303A3954B
Repair
Replace A Pressure Regulator
NOTE: This par
Controllers.
Follow these directions to replace a pressure
regulator (106).
1. Follow directions at Prepare for Service, page 24.
2. Remove the air tubing (26).
3. Loosen the regulator nut (105) on the front of
the box.
4. Remove the regulator assembly.
5. Remove the elbows (33, 99, and 107), pipe plug
(39), and the connector (108).
6. Apply thread sealant to the threads on the elbows
(33, 99, and 107) and the connector (108).
Tighten them into the new regulator (106). Install
thepipeplug(39).
7. Install the new regulator assembly and tighten
the regulator nut (105).
8. Reconnect the air tubing (26).
t is not used on Electronic Air
Replace the Bearing Air Filter
NOTE: This par
Controllers.
Follow these directions to replace the bearing air
filter (79).
1. Follow directions at Prepare for Service, page 24.
2. Pull fitting (109) off of tee (103).
3. Leave tee and fitting (80) together and pull the
assembly off of the filter (79).
4. Remove the filter (79) from fitting (81).
Note the flow
flow should g
bulkhead o
5. Install th
6. Reattach t
tee (103).
7. Reconnec
t is not used on Electronic Air
direction arrow on the filter. The
o from the air manifold block to the
n the enclosure.
enewfilter(79)onfitting(81).
he push-to-connect fitting (80) and the
t fitting (109).
3A3954B31
Parts
Parts
Electronic Air Controller (Model 24Z222)
323A3954B
Electronic Air Controller (Model 24Z222)
Parts
3A3954B33
Parts
PartDescription
Ref
———
1
2289697
———
3
ENCLOSURE
MODULE, base
SCREW, machine, pan
head,6–32x11/2in.
———
4
SCREW, machi
head, 6–32 x 0
5
277674
6289696
7
158491NIPPLE, 1/2–14 npt1
———
8
9514930
DOOR, cube
MODULE, cube
MANIFOLD, air speed
SCREW, cap, socket head,
ne, pan
.75 in.
#10–32 x 2.5 in.
1016F151
ELBOW, swivel, 3/8 T x 3/8
npt
11100721
12110249
PLUG, pipe
ELBOW, 90 degree, 1/4–18
npt
———
13
14
C06061
UNION,
bulkhe
MUFFLER, sintered, 1/8
5/16 Tube,
ad
dia
16121818
———
17
18112446
2024Z246
21120
22120
23
24
25
2659
28
29
3011
1
3
491
490
———
———
———
8095
———
———
0874
12144
1
UNION
RAIL, mounting1
BLOC
BLOC
opto
BLOCK, terminal
COVER, end
PLUG, button, 1 5/16 in.
PLUG, 1 in., round, plastic
CABLE, M12—5P
TUBE, 5/32 OD20 ft.
CABLE, M8–4P, 0.3 m
CABLE, M12–8P, 0.5 m
WASHER, flat
SCREW, machine, pan
, 5/32 Tube
K, clamp end
K, terminal,
coupler
head, #8–32 x 0.25 in.
3224T563
33114151
MANIFOLD, solenoid
ELBOW, male, swivel, 5/32
T x 1/8 nptf
3416P316VALVE, solenoid6
35103833
SCREW, machine, cross
recessed, pan head,
#10–32 x 0.375 in.
36108982
———
37
CONNECTOR, tube
DUCT, wire
Qty
1
1
1
4
1
1
1
2
5
1
2
2
1
6
2
1
38
1
1
2
1
2
1
6
6
1
6
12
1
1
PartDescription
Ref
———
38
39100139
4017D921
41
17G386 REGULATOR,
COVER, wire duct
PLUG, pipe
BRACKET, regulator
electro/pneumatic, 3/8
npt
———
43
———
44
———
45
49054776
50054134
———
51
CABLE, M12–5P, 0.5 m
CABLE, M12–5P, 1.0 m
CABLE, M12–5P, 0.3 m
TUBE, 5/16 OD2 ft.
TUBE, 3/8 OD4 ft.
MARKER, terminal block,
1–10
———
52
MARKER, terminal block,
11–20
53
———
MARKER, t
erminal block,
21–30
———
54
MARKER, terminal block,
31–40
56111987
57
116463VALVE, solenoid, 3–way2
58156823
59115948
———
60
CONNECT
UNION,
ELBOW,
BRACKE
enclos
OR, strain relief
swivel
1/4 npt x 5/16T
T, mounting,
ure
61112173MUFFLER4
———
62
O-RING, 13mm, light blue,
included with Ref. 63
6324T56
5
PLUG, manifold, includes
o-ring (ref. 62)
———
66
67101390
68100272
69
C19
———
70
74151395
75
103181
76100518
7
7
116343
WIRE, ground1
HER, lock
WAS
HER, lock, #6
WAS
675
HING, reducer
BUS
LABEL, port locations1
SHER, flat
WA
SHER, lock, ext.
WA
REW, machine, pan
SC
ad, #6–32 x 0.375 in.
he
SCREW, ground
78172953LABEL, grounding location 1
84▲ 17K394LABEL, warning1
8517E418
Replacement Danger and Warning labels, tags,
▲
CABLE, splitter
and cards are available at no cost.
Qty
1
5
2
2
1
2
2
2
2
2
2
1
2
2
1
3
3
2
1
2
4
4
4
1
1
343A3954B
Parts
Manual Air Con
troller (Model 24Z221)
3A3954B35
Parts
Manual Air Controller (Model 24Z221)
363A3954B
Parts
PartDescription
Ref
———
1
2289697
———
3
ENCLOSURE
MODULE, base
SCREW, machine, pan
head, 6–32 x 1 1/2 in.
———
4
SCREW, machi
head, 6–32 x 0
5
277674
6289696
7
159239NIPPLE, pipe, 3/8–18 npt
DOOR, cube
MODULE, cube
x1/2–14npt
14
C06061
MUFFLER, sintered, 1/8
dia
16121818
———
17
18112446
2024Z226
21120491
22120490
———
23
———
24
———
25
2659809
———
28
———
29
3011087
3111214
UNION, 5/
RAIL, mounting1
BLOCK, cl
BLOCK, te
optocoup
BLOCK, terminal
COVER, end
PLUG, button, 1 5/16
PLUG, 1 in., round, plastic
CABLE, M12—5P
5
TUBE, 5/32 OD28 ft.
CABLE, M8–4P, 0.3 m
CABLE, M12–8P, 0.5 m
4
WASHER, flat
4
SCREW, machine, pan
32 T
ler
head, #8–32 x 0.25 in.
3224T563
33114151
3416P
3510
316
3833
FOLD, solenoid
MANI
OW, male, swivel, 5/32
ELB
/8 nptf
Tx1
VE, solenoid
VAL
SCREW, machine, cross
recessed, pan head,
#10–32 x 0.375 in.
36108982
——
—
37
———
38
39100139
———
45
50054134
———
51
ONNECTOR, 3/8 Tube,
C
0degree,
9
DUCT, wire
COVER, wire duct
PLUG, pipe
CABLE, M12–5P
TUBE, 3/8 OD1.5 ft.
MARKER, terminal block,
1–10
———
52
MARKER, terminal block,
11–20
———
53
MARKER, terminal block,
21–30
ne, pan
.75 in.
amp end
rminal,
Qty
1
1
1
4
1
1
3
1
7
2
1
31
1
1
2
2
2
1
6
6
1
12
9
4
1
1
1
5
2
2
2
2
PartDescription
Ref
54
———
MARKER, termin
al block,
31–40
56111987
———
60
CONNECTOR, strain relief
BRACKET, mounting,
enclosure
———
66
67101390
68100272
———
70
74151395
75
103181
76100518
WIRE, ground1
WASHER, lock
WASHER, lock, #6
LABEL, port
locations
WASHER, flat
WASHER, lock, ext.
SCREW, machine, pan
head, #6–32 x 0.375 in.
77
116343
SCREW, gro
und
78172953LABEL, grounding location 1
7917M754 FILTER, coalescing,
miniature
8017A244
FITTING, push to connect,
1/2 to 1/4 reducing
81128798
83154636
FITTING
1/4 Tub
WASHER, flat
, push to connect,
ex3/8npt(m)
84▲ 17K394LABEL, warning1
8517E418
92512905
93111411
———
94
95120435
96100
CABLE, splitter
FITTING, brass
CONNECTOR, 1/2T
TEE, 1/2–14 npt x 1/2 TOD3
LATOR, remote
REGU
ted
pilo
171
SCREW, pan head,#4–40
x0.5in.
———
98
9911
———
00
1
4469
NNECTOR, push-in,
CO
16 T, 3/8 nptf
5/
ELBOW, swivel, 1/4 nptf
CONNECTOR, male,
10–32UNFx5/32T
10126A292
SWITCH, pressure, 70 psi,
includes screws (Ref. 96)
and connector (Ref. 100)
———
102
CONNECTOR, spade
103513226TEE, 1/2 in.1
104P00569
GAUGE, pressure, air
105115244NUT, regulator3
106110318
REGULATOR, air, 1/4 in.
npt
10715T498
ELBOW, 90 degree,
swivel, 5/32T x 1/8 npt
10815D916
CONNECTOR, 5/32 to 1/4
npt
Qty
2
1
1
2
1
1
4
4
4
1
1
1
1
4
1
1
1
3
2
4
6
1
1
3
3
3
3
3
3A3954B37
Parts
PartDescription
Ref
———
109
111061513
Qty
FITTING, straight, 1/2 x
1
3/8 Tube
TUBE, 1/2 OD2 ft.
▲
Replacement Danger and Warning labels, tags,
and cards are available at no cost.
383A3954B
Kits and Accessories
Power Supply Kit 24Z224
Kits and Accessories
Ref.
74100518
75
76141395
201120999
200
———
PartDescription
WASHER, flat
103181
———
245202
WASHER, lock
SCREW, machine, pan head, #6–32 x 0.375 in.
RESISTOR, termination
POWER SUPPLY
CORDSET, USA, 10 ft. (3 m) 13A, 120V; not shown
3A3954B39
Qty.
4
4
4
1
1
1
Kits and Accessories
System Logic C
PartDescription
———
17M465
MODULE, System Logic
Controller
TOKEN, software upgrade
ontroller Kit 24Z223
Graco CAN Cables
PartLength
130193
121001
121002
121003
0.5 m (1.6 ft.)
1 m (3.3 ft.)
1.5 m (4.9 ft.)
3 m (9.8 ft.)
Communication Gateway Kits
PartDescrip
CGMDN0
CGMEP0
DeviceNet
EhterNe
tion
tIP
Qty.
1
1
ProBell Gatew
ay Installation Kit
24Z574
PartDescription
———
130193
121901
———
100272
———
———
TOKEN, progr
CABLE, CAN, 0
SUPPRESSOR
SCREW, mach
1–1/2
WASHER, lock, #6
SCREW, #6–32 x 0.75 in.
GROMMET, bulkhead, cable
entry
amming
.5 m
ine, 6–32 x
Optocoupler Kit 24Z246
PartDescript
———
Block, t
ion
erminal, optocoupler
ProBell Token Programming Kit
17M465
Qty
1
1
2
1
1
4
1
Qty
1
24W462
CGMPN0PROFINET
Modbus
TCP
Syste
m Logic Controller Screen
Protector 15V511
403A3954B
Technical Speci
fications
Technical Spe
cifications
ProBell Air Controller
US
Maximum air working pressure100 psi0.69 MPa, 7.0 bar
Turbine spe
operating
Bearing air, minimum required70 psi0.5 MPa, 5.0 bar
Air Connec
Maximum Operating Voltage24 VDC, 2.5A
Operating Temperature Range32° to 122° F0° to 50° C
Power co
External Power Requirements for
part 24Z224
Storage Temperature Range–22° to 140° F–30° to 60° C
Weight47.5 lb.21.5 kg.
ed, maximum
tion
nnection for part 24Z224
60,000 rpm
1/2” npt
Straigh
t IEC 320–C13 male connector and a North American
NEMA 5–1
100–240 VAC, 50/60 Hz, 2A maximum draw, 15 amp
5P ISP male plug are provided.
circuit breaker recommended
Metric
3A3954B
41
Graco Standard Warranty
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its
name to be free from defects in material and workmanship on the date of sale to the original purchaser for
use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a
period of twelve months from the date of sale, repair or replace any part of the equipment determined
by Graco to be defective. This warranty applies only when the equipment is installed, operated and
maintained in accordance with Graco’s written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction,
damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper
maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall
Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment
with structures, accessories, equipment or materials not supplied by Graco, or the improper design,
manufacture, installation, operation or maintenance of structures, accessories, equipment or materials
not supplied by Graco.
This warranty is conditioned upon
authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco
will repair or replace free of charge any defective parts. The equipment will be returned to the original
purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material
or workmanship, repairs will be
parts, labor, and transportat
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY
OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above.
The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages
for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall
be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH
ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY
GRACO. These items sold, but not manufactured by Graco (such as electric motors
are subject to the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable
assistance in making any claim for breach of these warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from
Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other
goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or
otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents,
notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or
indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du
présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés,
donnés ou intentés, à la suite de ou en rapport, directement ou indirectement, avec les procédures
concernées.
the prepaid return of the equipment claimed to be defective to an
made at a reasonable charge, which charges may include the costs of
ion.
, switches, hose, etc.),
Graco Information
For the latest information about Graco products, visit www.graco.com. For patent information, see
www.graco.com/patents.
To place an order, contact your Graco Distributor or call to identify the nearest distributor.
Phone: 612-623-6921 or Toll Free: 1-800-328-0211 Fax: 612-378-3505
All written and visual data contained in this document reflects the latest product information available at the time of publication.
Graco reserves the right to make changes at any time without notice.
Original Instructions. This manual contains English, MM 3A3657
International Offices: Belgium, China, Japan, Korea
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS, MN 55440-1441 • USA
Copyright 2016, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco Headquarters: Minneapolis
www.graco.com
Revision B, June 2017
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.