Electronically-controlled fluid metering system that provides precise continuous flow of
up to four single-component sealants and adhesives through closed-loop technology.
Not for use in explosive atmospheres or hazardous locations.
For professional use only.
Important Safety Instructions
Read all warnings and instructions in this
manual. Save these instructions.
EN
See page 4 for model information. See page 5 for
maximum working pressure and approvals.
IMPORTANT:
This manual does not apply to some PCF systems. See note on page 3 to verify this is the
correct manual for your PCF system.
The following is a list of component manuals written in
English. These manuals and any available translations
can be found at www.graco.com.
ManualDescription
313377
309403PrecisionSwirl Orbital Dispenser
307517
308647
309834
3A4649Integrated PCF Instructions
3A5295Coriolis Flow Meter Instructions - Parts
NOTE: In the Advanced screens on your system, if the
Advanced Display software part number shown is
16F528 or 15V769 then this manual does not apply to
your system; refer to manual 313377 for your system.
Otherwise, the part number shown should be 16K405
and you should use this manual.
Original PCF Instructions - Parts
(see the note below)
Check the identification (ID) plate for the 6-digit part number of the fluid metering system. Use the following matrix to
define the construction of the system, based on the six digits. For example, Part PF1110 represents a PCF fluid
metering system (PF), a two style system (1), a fluid plate with a cartridge regulator and no meter (1), a DeviceNet
user interface (1) with a 100-240 Vac power supply (0).
NOTE: To order replacement parts, see Parts section in this manual. The digits in the matrix do not correspond to the
Ref. Nos. in the Parts drawings and lists.
™
PF1
First and
Second Digits
PF
(Precision
Continuous
Flow)
1
Third Digit
Style/Size
DescriptionRegulatorMeterDescriptionDescription
12 Styles1Cartridge None0Discrete0100 - 240 Vac
16 Styles2MasticNone 1
2
3256 Styles3CartridgeHigh
4MasticHigh
5Heated
6 Heated Mas-
7CartridgeUltra High
8CartridgeHigh
9MasticHigh
CCartridgeCoriolis
Fourth Digit
Fluid Plate
Mastic
tic
2
Resolution
3
Resolution
Heated
Standard Res-
olution
None5Not Used.
Resolution
Resolution /GB
Resolution /GB
4
6DeviceNet
7EtherNet I/P
1
Fifth Digit
User Interface
DeviceNet
EtherNet/IP
PROFIBUS
PROFINET
No ADM
No ADM
™
124 Vdc
™
2 100 - 240 Vac with
™
324 Vdc with
™
0
Sixth Digit
Voltage
Integrated Swirl
Integrated Swirl
Discrete Gateway systems do not include automation interface cables. The following Graco accessories are avail-
able for wiring to the automation system. Installers should follow Appendix B - Discrete Gateway Module (DGM) Connection Details, page 121, for custom wiring.
For single fluid plate systems only: 50 ft (15 m) cable with flying leads (123793)
All systems: Breakout board (123783) and 50 ft (15 m) cable (123792)
NOTE: 256 styles option is not available with Discrete Gateway systems.
These fluid metering systems have ETL certification.
NOTE: Fluid metering systems with heated mastic regulators are not ETL certified.
1
This product has been tested to the requirements of CAN/CSA-C22.2 No. 61010-1, second edition, including
C
Amendment 1, or a later version of the same standard incorporating the same level of testing requirements.
43A2098S
Models
Fluid Plate Kits
NOTE: The fluid plate kit numbers listed below include a CAN splitter. The fluid plate assembly included in each
PFxxxx assembly does not include a CAN splitter.
Includes:
Fluid
Plate Kit
24B958PF13xx
24B959PF11xx
24B960PF14xx
24B961PF12xx
24B962PF15xx
24C901PF16xx
24J873PF17xx
24K801PF23xx
24K802PF21xx
24K803PF24xx
24K804PF22xx
24K805PF25xx
24K806PF26xx
24K807PF27xx
24K808PF33xx
24K809PF31xx
24K810PF34xx
24K811PF32xx
24K812PF35xx
24K813PF36xx
24K814PF37xx
24V592PF18xx
Used by
Model
Maximum Working
Pressure
6000 psi
(41 MPa, 414 bar)
6000 psi
(41 MPa, 414 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
6000 psi
(41 MPa, 414 bar)
6000 psi
(41 MPa, 414 bar)
6000 psi
(41 MPa, 414 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
6000 psi
(41.4 MPa, 414 bar)
6000 psi
(41 MPa, 414 bar)
6000 psi
(41 MPa, 414 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
6000 psi
(41 MPa, 414 bar)
6000 psi
(41 MPa, 414 bar)
Regula-
Description
Cartridge Regulator, High Resolution Flow
Meter, 2 styles
Cartridge Regulator, No Flow Meter,
2styles
Mastic Regulator, High Resolution Flow
Meter, 2 styles
Mastic Regulator, No Flow Meter, 2 styles246642---16M101
Heated Mastic Regulator, Standard Resolu-
tion Heated Flow Meter, 2 styles
Heated Mastic Regulator, No Flow Meter,
2styles
Cartridge Regulator, Ultra High Resolution
Flow Meter, 2 styles
Cartridge Regulator, High Resolution Flow
Meter, 16 styles
Cartridge Regulator, No Flow Meter,
16 styles
Mastic Regulator, High Resolution Flow
Meter, 16 styles
Mastic Regulator, No Flow Meter, 16 styles246642---16M103
Heated Mastic Regulator, Standard Resolu-
tion Heated Flow Meter, 16 styles
Heated Mastic Regulator, No Flow Meter,
16 styles
Cartridge Regulator, Ultra High Resolution
Flow Meter, 16 styles
Cartridge Regulator, High Resolution Flow
Meter, 256 styles
Cartridge Regulator, No Flow Meter,
256 styles
Mastic Regulator, High Resolution Flow
Meter, 256 styles
Mastic Regulator, No Flow Meter,
256 styles
Heated Mastic Regulator, Standard
Resolution Heated Flow Meter, 256 styles
Heated Mastic Regulator, No Flow Meter,
256 styles
Cartridge Regulator, Ultra High Resolution
Flow Meter, 256 styles
Cartridge Regulator, Glass Bead High
Resolution Flow Meter, 2 styles
tor
24473424665216M100
244734---16M101
24664224665216M100
24664324634016M100
246643---16M101
24473416E99316M100
24473424665216M102
244734---16M103
24664224665216M102
24664324634016M102
246643---16M103
24473416E99316M102
24473424665216M104
244734---16M105
24664224665216M104
246642---16M105
24664324634016M104
246643---16M105
24473416E99316M104
24473424P68816M100
Flow
Meter
FCM Key
Token
3A2098S5
Models
Fluid
Plate Kit
24V593PF28xx
24V594PF38xx
24V595PF19xx
24V596PF29xx
24V597PF39xx
24W201PF15xx
24W202PF25xx
24W203PF35xx
25C783PF1Cxx
25C784PF2Cxx
25C785PF3Cxx
Used by
Model
Maximum Working
Pressure
6000 psi
(41 MPa, 414 bar)
6000 psi
(41 MPa, 414 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
5000 psi
(35 MPa, 345 bar)
Description
Cartridge Regulator, Glass Bead High
Resolution Flow Meter, 16 styles
Cartridge Regulator, Glass Bead High
Resolution Flow Meter, 256 styles
Mastic Regulator, Glass Bead High
Resolution Flow Meter, 2 styles
Mastic Regulator, Glass Bead High
Resolution Flow Meter, 16 styles
Mastic Regulator, Glass Bead High
Resolution Flow Meter, 256 styles
Heated Mastic Regulator, Standard
Resolution Heated Flow Meter, 2 styles
Heated Mastic Regulator, Standard
Resolution Heated Flow Meter, 16 styles
Heated Mastic Regulator, Standard
Resolution Heated Flow Meter, 256 styles
Cartridge Regulator, Coriolis Flow Meter, 2
styles
Cartridge Regulator, Coriolis Flow Meter,
16 styles
Cartridge Regulator, Coriolis Flow Meter,
256 styles
Includes:
Regula-
tor
24473424P68816M102
24473424P68816M104
24664224P68816M100
24664224P68816M102
24664224P68816M104
24664324634016M100
24664324634016M102
24664324634016M104
24473425D02616M100
24473425D02616M102
24473425D02616M104
Flow
Meter
FCM Key
Token
63A2098S
Models
Control Panel Kits
NOTE: The control kit numbers listed below are replacement control enclosures with their voltage and automation
interface listed.
Automation
Part No.
16K601ACCESSORY SWIRLVAC
16K602ACCESSORY SWIRLVAC
16K603ACCESSORY SWIRLVAC
16K604ACCESSORY SWIRLVAC
16K605ACCESSORY SWIRLVACIO
16K606ACCESSORY SWIRLVDC
16K607ACCESSORY SWIRLVDC
16K608ACCESSORY SWIRLVDC
16K609ACCESSORY SWIRLVDC
16K610ACCESSORY SWIRLVDCIO
16M350SWIRL EXPANSIONVACN/A
16M351SWIRL EXPANSIONVDCN/A
24S023STANDARDVAC
25C590STANDARDVAC
25C591STANDARDVAC
25C592STANDARDVAC
25C593STANDARDVACIO
24S024STANDARDVDC
25C594STANDARDVDC
25C595STANDARDVDC
25C596STANDARDVDC
25C597STANDARDVDCIO
25C582INTEGRATED (No ADM)VAC
25C583INTEGRATED (No ADM)VAC
25C584INTEGRATED (No ADM)VAC
25C585INTEGRATED (No ADM)VAC
25C586INTEGRATED (No ADM)VDC
25C587INTEGRATED (No ADM)VDC
25C588INTEGRATED (No ADM)VDC
25C589INTEGRATED (No ADM)VDC
System Type
Voltage
Interface
DeviceNet
EtherNet/IP
PROFIBUS
PROFINET
DeviceNet
EtherNet/IP
PROFIBUS
PROFINET
DeviceNet
EtherNet/IP
PROFIBUS
PROFINET
DeviceNet
EtherNet/IP
PROFIBUS
PROFINET
DeviceNet
EtherNet/IP
DeviceNet
EtherNet/IP
DeviceNet
EtherNet/IP
DeviceNet
EtherNet/IP
3A2098S7
Models
Expansion Swirl Enclosure Assemblies
The following enclosures are ETL approved. Assemblies PFxxx2, and PFxxx3 are setup for one PrecisionSwirl Orbital
Dispenser. If you wish to have additional swirl dispensers, order one expansion PrecisionSwirl assembly below for each.
Systems with a DGM as the automation gateway can have up to two swirl dispensers total. Systems with a CGM as the
automation gateway can have up to four swirl dispensers total.
2331256 ft (1.8 m) motor extension cable assembly
2331249 ft (2.7 m) motor extension cable assembly
23312315 ft (4.6 m) motor extension cable assembly
61787055 ft (16.8 m) motor extension cable assembly
83A2098S
Automation Gateway Assemblies
Automation Gateway
(DGM or CGM)
Swirl Control DGM
Each control center comes with one automation gateway assembly. The automation gateway module is either a Discrete Gateway Module (DGM) or one of the Communications Gateway
Modules (CGM).To order a replacement, see the following table.
You will also need to order software upgrade token (16K743).
NOTE: Base and cable are not included.
Gateway
Compatible
with
Advanced
CGM Map
PCF
Model
User
Interface
Description
Part
Number
To
Order
Rotary
Switch
Position
Models
PFxx0xDiscrete
(DGM)
PFxx1x
+
PFxx6x
PFxx2x
+
PFxx7x
PFxx3x
PFxx4x
DeviceNet
(CGM)
EtherNet/IP
(CGM)
PROFIBUS
(CGM)
PROFINET
(CGM)
24B6810No
™
15V759AnyYes
™
15V760AnyYes
™
15V761AnyNo
™
15V762AnyNo
Swirl Control DGM
The assemblies below each contain one swirl control DGM used
to control one Swirl Dispenser. To order a replacement, see the
following table. You will also need to order software upgrade
token (16K743).
Assembly
Part Number
To Order
Rotary Switch
Position
PFxxx2,
PFxxx3,
16M350,
16M351
3A2098S9
24B681
see Swirl Control
DGM on page 22
1, 2, 3, or 4;
Models
Integration Upgrade with
Advanced Map
NOTE: See manual 3A4649 for more information.
Graco provides an upgraded software solution for PCF
systems that came with automation communication
gateway modules (CGM). The table below shows which
systems have the ability to upgrade their system with
the update kit (25C527). This kit includes new CGM
software, as well as a larger data map.
Benefits of Upgrading:
1. Direct access to important information such as flowrates and pressures of the system (all four fluid
plates).
2. Allows for a complete integration of a Graco PCF
system, meaning an ADM is no longer necessary.
3. Much easier set up and integrate.
4. Much more supporting documentation to identify
what is important.
NOTE: Only systems with Ethernet I/P and Device Net
are capable of upgrading to use the Advanced Map.
Table 1: Software Upgrade Tokens
PartDescriptionContents
16K743
* 16N601 PCF Gateway map token: Installs
16T061PCF Gateway map token: Installs
16K742Historical PCF Gateway map
25C527Advanced integration software kit.
Includes PCF software for the
ADM, FCM, CGM, and DGM
the CGM map starting on
page 128.
the CGM map starting on page
128.
token: Only for users that used the
original PCF with a Gateway, have
purchased a new PCF, and do not
wish to change their Gateway
setup from the old Gateway map
to the new Gateway map.
Includes the latest PCF software
for the ADM, FCM, CGM, and
DGM (16K743). It also includes
the larger Map (17P799). Both of
these must be installed for the
CGM to run, and have advanced
integration features.
System
Software
Standard
Gateway
Map
Basic
Gateway
Map (2
fluid plate),
No Swirl
Historical
Map
System
Software
and
Advanced
Map
Table 2: Fieldbus Setup Options
PCF
Model
User Interface
Description
Able to
Upgrade
Upgrade
Kit
PFxx0xDiscrete (DGM)NoN/A
PFxx1xDevice Net
Yes25C527
(CGM)
PFxx2xEthernet I/P
Yes25C527
(CGM)
PFxx3xProfiBus (CGM)NoN/A
PFxx4xProfiNet (CGM)NoN/A
PFxx6xDevice Net
(CGM)
PFxx7xEthernet I/P
(CGM)
Already
has
upgrade
installed
Already
has
upgrade
installed
Already
has
upgrade
installed
Already
has
upgrade
installed
Basic Gateway Map: 16T061
System Software: 16K743
Comm. Format:Data - SINT
Input Assembly Instance:100
Input Instance Size:10
Output Assembly Instance:150
Output Instance Size:6
Standard Gateway Map: 16N601
System Software: 16K743
Comm. Format:Data - SINT
Input Assembly Instance:100
Input Instance Size:26
Output Assembly Instance:150
Output Instance Size:42
Advanced Gateway Map: 17P799
System Software: 16K743 (newest version)
Comm. FormatData - SINT
Input Assembly Instance:100
Input Instance Size126
Output Assembly Instance:150
Output Instance Size:44
103A2098S
Warnings
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When
these symbols appear in the body of this manual, refer back to these Warnings. Product-specific hazard symbols and
warnings not covered in this section may appear throughout the body of this manual where applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause
electric shock.
•Turn off and disconnect power at main switch before disconnecting any cables and before servicing
or installing equipment.
•Connect only to grounded power source.
•All electrical wiring must be done by a qualified electrician and comply with all local codes and
regulations.
SKIN INJECTION HAZARD
High-pressure fluid from dispensing device, hose leaks, or ruptured components will pierce skin. This
may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical
treatment.
•Do not point dispensing device at anyone or at any part of the body.
•Do not put your hand over the fluid outlet.
•Do not stop or deflect leaks with your hand, body, glove, or rag.
•Follow the Pressure Relief Procedure when you stop dispensing and before cleaning, checking, or
servicing equipment.
•Tighten all fluid connections before operating the equipment.
•Check hoses and couplings daily. Replace worn or damaged parts immediately.
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help prevent
fire and explosion:
•Use equipment only in well ventilated area.
•Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop
cloths (potential static arc).
•Keep work area free of debris, including solvent, rags and gasoline.
•Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes
are present.
•Ground all equipment in the work area. See Grounding instructions.
•Use only grounded hoses.
•Hold gun firmly to side of grounded pail when triggering into pail.
•If there is static sparking or you feel a shock, stop operation immediately. Do not use equipment
until you identify and correct the problem.
•Keep a working fire extinguisher in the work area.
3A2098S11
Warnings
WARNING
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
•Do not operate the unit when fatigued or under the influence of drugs or alcohol.
•Do not exceed the maximum working pressure or temperature rating of the lowest rated system
component. See Technical Data in all equipment manuals.
•Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all
equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information
about your material, request MSDS forms from distributor or retailer.
•Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
•Do not alter or modify equipment.
•Use equipment only for its intended purpose. Call your distributor for information.
•Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
•Do not kink or over bend hoses or use hoses to pull equipment.
•Keep children and animals away from work area.
•Comply with all applicable safety regulations.
BURN HAZARD
Equipment surfaces and fluid that’s heated can become very hot during operation. To avoid severe
burns:
• Do not touch hot fluid or equipment.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or
swallowed.
•Read MSDS’s to know the specific hazards of the fluids you are using.
•Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
PERSONAL PROTECTIVE EQUIPMENT
You must wear appropriate protective equipment when operating, servicing, or when in the operating
area of the equipment to help protect you from serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. This equipment includes but is not limited to:
•Protective eyewear, and hearing protection.
•Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer
123A2098S
System Configurations
G
D
C
B*
F*
A*
E
H
J
K*
Power In
Air Supply
Drop Site
L
M
NOTE: Shown with one fluid plate and one swirl dispenser.
F*
N
Typical Installation - Single Swirl, Single Fluid Plate
System Configurations
F
IG. 1: Typical Ambient System Installation
Key:
A*Control Center (User Interface)
B*Fluid Plate Assembly
CApplicator/Dispense Valve
DSealer Automation
EAutomation Interface Cable
F*CAN Cable
G Fluid Supply System
HFluid Supply Hose
JAutomation Controller
3A2098S13
K*Air Filter Assembly
LPrecisionSwirl Orbital Dispenser (Swirl Dispenser)
M PrecisionSwirl Cable
NSealer Automation Control Cable
* Included
Optional
System Configurations
J
Air Supply
Drop Site
K*
H
Power In
A
E
F*
F*
F*
F*
B*
B*
B*
B*
D
C
D
C
D
C
D
C
H
H
H
G
G
G
G
F*
L
L
L
Typical Installation - Multiple Fluid Plates, No Swirl Dispensers
F
IG. 2: Typical Multiple Fluid Plate System Installation
IG. 3: Typical Multiple Fluid Plate System Installation
Key:
A*Control Center (User Interface)
B*Fluid Plate Assembly
CApplicator/Dispense Valve
DSealer Automation
EAutomation Interface Cable
F*CAN Cable
G Fluid Supply System
HFluid Supply Hose
JAutomation Controller
K*Air Filter Assembly
LPrecisionSwirl Orbital Dispenser (Swirl Dispenser)
M PrecisionSwirl Cable
NExpansion Swirl Enclosure
O Sealer Automation Control Cable
* Included
Optional
3A2098S15
Overview
System shown with one fluid plate and one swirl dispenser
Control Center
(User Interface)
Fluid Plate Assembly
Overview
System Overview
The PCF fluid metering system combines closed-loop
pressure control with the ability to change bead profiles
quickly. When used with an optional flow meter, the
system automatically adjusts for fluctuations in the
operating environment, such as material viscosity,
temperature and tip wear, in order to maintain the
desired dispense rate. The module responds to
automation signals to provide an accurate and
consistent output flow based on a comparison of actual
to desired flow rates.
Typical Applications
•Bead dispensing
•Gasketing
•Seam sealing
•Hem flange
•Sound deadening
•Anti-flutter
•Body panel reinforcement
•Profile wrapping
•Cable filling
Control Center (User Interface)
NOTE: The control center is available with or without an
ADM, depending on the model you are using. See
Models on page 4.
The control center communicates with the PCF fluid
plate assembly to control fluid pressure and dispense
valve operation.
The control center receives input from the automation
controller, and uses these inputs to determine
communication to the fluid plate assembly.
Fluid Plate Assembly
The fluid plate assembly contains components that
control and monitor fluid dispensing. A PCF fluid
metering system can have up to four fluid plates. Each
fluid plate can control up to four dispense valves. The
system supports up to 16 dispense valves and can
simultaneously dispense from up to 10 dispense valves.
PrecisionSwirl Orbital Dispenser
(Swirl Dispenser), Sold Separately
System Components
The diagram in FIG. 4 shows an example of the PCF
module and cables.
F
IG. 4: PCF System Components
The swirl dispenser dispenses material in a circular pattern at speeds from 6600 to 24000 rpm. A PCF fluid
metering system can have up to four swirl dispensers.
See manual 309403 for detailed information.
163A2098S
Overview
U
R
P
T
S
Fluid Plate Assembly Overview
Fluid Plate Components
The fluid plate assembly in FIG. 5 can be attached to an
automation arm or mounted on a pedestal. The main
components of the fluid plate assembly include:
•Fluid regulator (cartridge, ambient mastic, or heated
mastic) (P).
•Flow meter (R) (optional) precisely measures the
flow rate of fluid dispensed.
•Solenoid air valve (S) controls the dispense valve.
•Voltage to Pressure Transducer (T), abbreviated V/P
transducer, adjusts the air pressure to the fluid regulator (P).
•Fluid Control Module (FCM) (U) receives pulse readings from the flow meter (R) and pressure readings
from the regulator. It also controls the fluid regulator
(P) and solenoid air valve (S).
The PCF fluid regulator is electrically controlled by the
PCF fluid control module. Consistent material flow is
assured by a closed-loop pressure or closed-loop flow
control design. The module responds to automation-supplied signals to provide an accurate and consistent output flow based on a comparison of actual to
desired flow rates. The fluid regulator uses air pressure
to control fluid pressure and to provide fast response to
electronic commands and ensure a precisely controlled,
continuous flow of material.
The fluid plate assembly is available in two versions:
ambient and heated.
Ambient Fluid Plate Assembly
There are five ambient versions available:
•cartridge regulator without a flow meter
•ambient mastic regulator without a flow meter
•cartridge regulator with a high resolution meter
•ambient mastic regulator with a high resolution
meter
•cartridge regulator with an ultra high resolution
flow meter
•cartridge regulator with Coriolis flow meter
Heated Fluid Plate Assembly
There are two heated versions available:
•heated mastic fluid regulator with a heated flow
meter
•heated mastic fluid regulator without a flow
meter
F
IG. 5: Fluid Plate Components
3A2098S17
Overview
3
4
5
CAN
Connectors
6
7
Status
LEDs
1
2
Key
token
Rotary
Switch
Fluid Regulator
There are three fluid regulator options:
•cartridge
•ambient mastic
•heated mastic
All of the fluid regulator options use air pressure to control fluid pressure, provide fast response to electronic
commands, and ensure a precisely controlled, continuous flow of material.
Cartridge
The cartridge regulator (244734) is ideal for low to
medium viscosity sealants and adhesives.
Ambient Mastic
The ambient mastic regulator (246642) is ideal for
medium to high viscosity sealants and adhesives.
Heated Mastic
The heated mastic regulator (246643) is ideal for low to
high viscosity warm-melt and hot-melt sealants or adhesives.
Fluid Control Module (FCM)
F
IG. 6: FCM Sensor Connections
Connection Sensor Description
1Dispense solenoid
2Flow meter
3Outlet pressure sensor (heated systems only)
4Voltage to Pressure (V/P) Transducer
5Command cable (optional accessory kit)
6Inlet pressure sensor (non-heated systems
7Outlet pressure sensor (non-heated systems
CAN
Connectors
Table 3: FCM Sensor Connections
only)
only)
---
Rotary Switch on FCM
The rotary switch on the FCM, see F
IG. 6, must be set to
a valid position and each FCM must have a unique
rotary switch position. The FCM rotary switch position
determines which number to assign to that fluid plate.
The settings, including defined styles, for each fluid
plate are stored in each FCM so changing the rotary
switch position causes the settings to be shown under
the new number on the ADM.
Rotary Switch
Item
Fluid Plate 10 or 1
Fluid Plate 22
Fluid Plate 33
Fluid Plate 44
Position
NOTE: See LED Diagnostic Information, page 69, for
signal definitions.
183A2098S
Control Center Assembly Overview
Front ViewSide View
ADM
Gateway
Module
Front View
Swirl Board
Swirl Control
DGM
100-240 Vac Assembly
CAN Splitter
- To Fluid Plate
- To ADM
Overview
F
IG. 7: Control Center Components
The control center includes the following components:
•Advanced Display Module (ADM) with USB; see
page 20 for details.
•USB enables users to download job, event, and
data logs; save and restore system settings; and
customize the language. See USB Data on
page 63.
•24 Vdc and 100-240 Vac customer-wired options
available.
•If system has a swirl dispenser: Swirl Control DGM
(the module on the left) and Swirl Board.
•Automation Gateway Module (the module on the
right), which can be one of the following five types:
•Discrete (supports up to 2 Fluid Plates)
•DeviceNet (supports up to 4 Fluid Plates)
•EtherNet/IP (supports up to 4 Fluid Plates)
•PROFIBUS (supports up to 4 Fluid Plates)
•PROFINET (supports up to 4 Fluid Plates)
Expansion Swirl Enclosure
If more than one swirl dispenser is installed, the system will have one Expansion Swirl Enclosure for each additional
swirl dispenser. The Expansion Swirl Enclosure is similar to the primary control center, but it does not include the
ADM or the Automation Gateway module.
Displays system status. Green LED indicates the
system is active. Orange LED indicates the system is off. Solid LEDs (green or orange) indicate
the system is in Run mode. Flashing LEDs (green
or orange) indicate the system is in Setup mode.
BCStop Button
Stops all system processes. However, it is not a
safety or emergency stop.
BDSoft Keys
Functions vary depending on the screen.
BECancel Button
Clears system errors and cancels a selection or
number entry while in the process of entering a
number or making a selection.
BFEnter Button
Acknowledge changing a value or making a
selection.
BGLock/Setup
Toggle between run and setup screens. If setup
screens are password protected, button toggles
between run and password entry screens.
Callout Function
BHNavigation Buttons
Navigate within a screen or to a new screen.
BJFlat Panel Mount
Mounts to control center bracket (optional).
BKModel Number Tag
Model number.
BLUSB Module Interface
USB port and USB indicator LEDs.
BMCAN Connector
Power connection.
BNModule Status LEDs
BPBattery Cover
BRToken Access Cover
BSDigital I/O Port for Light Tower
See LED Diagnostic Information, page 69, for
signal definitions.
NOTICE
To prevent damage to the soft key buttons, do not
press the buttons with sharp objects such as pens,
plastic cards, or fingernails.
203A2098S
Automation Gateway Module
TI11816A
PROFIBUS
Discrete
CG
CC
TI11814A
TI11815A
CA
CD
Gateway Module Connectors
CB
PROFINET or EtherNet/IP
DeviceNet
CE
CF
CH
FrontBack
CC
CC
Rotary
Switch
Software
Token Slot
Front
(Access Cover Removed)
See the following table for the appropriate rotary switch position for your automation gateway module.
Overview
PCF
ModelUser Interface Description
Gateway Part Number
To Order
Rotary Switch
Position
Max Number of
Fluid Plates
PFxx0xDiscrete (DGM)24B68102
PFxx1x
PFxx2x
PFxx3x
PFxx4x
DeviceNet
EtherNet/IP
PROFIBUS
PROFINET
™
(CGM)
™
(CGM)
™
(CGM)
™
(CGM)
15V759Any4
15V760Any4
15V761Any4
15V762Any4
NOTE: See Control Center Assembly Overview on page 19 for automation and swirl control DGM identification.
IG. 9: Automation Gateway Module Components
F
Key:
CA Gateway Module
CB Base
CC Fieldbus Connector (see Appendix C - Communi-
cations Gateway Module (CGM) Connection
Details, page 128, for more information)
CD Module Connection Screws
CE Access Cover
CF Module Status LEDs (see LED Diagnostic Infor-
mation, page 69)
3A2098S21
CG D-Subminiature (D-Sub) Connector (see Appendix
CH CAN Connectors
B - Discrete Gateway Module (DGM) Connection
Details, page 121, for pinout details)
Overview
CA
CD
CB
CE
CF
CH
Front
Back
Rotary
Switch
Software
Token Slot
Front
(Access Cover Removed)
Swirl Control DGM
One swirl control DGM is included in the integrated Swirl
control center, and in each expansion swirl enclosure.
Each Swirl control DGM controls one swirl orbiter.
Each swirl control DGM must have a unique rotary
switch position. The rotary switch position determines
the number assigned to the swirl dispenser attached to
that DGM. If the rotary switch position must be changed,
do so with the power off.
Each integrated swirl control center and swirl enclosure
comes with a pre-installed cable between the swirl control DGM and the swirl board. The customer does not
need to make any external connections with the swirl
control DGM.
DGM Function
Swirl Control 11
Swirl Control 22
Swirl Control 33
Swirl Control 44
Rotary Switch
Position
FIG. 10: Swirl Control DGM
223A2098S
Overview
FCMADM
Key Tokens
The ADM and FCM must each have a key token
installed in order to operate. If the incorrect key token is
installed, the module will not operate. The DGM does
not require a key token.
F
IG. 11
NOTE: There is one FCM located on each fluid plate.
If a new ADM or FCM is installed, follow the instructions
on page 81 to upgrade the software in the new module
and to install the key token from the old module in the
new module.
The following is a list of key token part numbers. If you
lose your key token be sure to order the correct item to
ensure proper system operation.
NOTE: The key tokens for the ADM and FCM look alike
but only work in one module or the other. If the key
tokens for the ADM and FCM become mixed, locate the
part number on each token then refer to the following
table to determine which module each token applies to.
PartDescription
16M100FCM Key Token, 2 styles, Flow Meter,
ADM required
16M101FCM Key Token, 2 styles, No Flow Meter,
ADM required
16M102FCM Key Token, 16 styles, Flow Meter,
Integrator Mode Enabled, ADM not
required
16M103FCM Key Token, 16 styles, No Flow
Meter, Integrator Mode Enabled, ADM not
required
16M104FCM Key Token, 256 styles, Flow Meter,
Integrator Mode Enabled, ADM not
required
16M105FCM Key Token, 256 styles, No Flow
Meter, Integrator Mode Enabled, ADM not
required
16M217ADM Key Token, Standard PCF
3A2098S23
Installation
Installation
Before Installation
•Have all system and component documentation
available during installation.
•See component manuals for specific data on component requirements. Data presented here applies to
the PCF assemblies only.
•Be sure all accessories are adequately sized and
pressure-rated to meet system requirements.
•Use the PCF control center only with the PCF fluid
plate assembly.
Overview
The basic steps to install a PCF system are shown
below. See the separate component manuals for
detailed information.
To avoid injury and damage to equipment, use at
least two people to lift, move, or disconnect the system. The system is too heavy for one person to lift or
move.
10. For systems with swirl dispensers, install each swirl
dispenser onto outlet of a dispense valve.
11. Connect other fluid and air lines to additional system
components as instructed in their manuals.
2. For systems with multiple swirl dispensers, mount
expansion Swirl enclosures, page 25.
3. Connect and ground control center and expansion
Swirl enclosures, page 26.
4. Mount each fluid plate assembly, page 27.
5. If using a Coriolis flow meter system, mount the flow
meter, page 149.
6. Ground each fluid plate assembly, page 31.
7. Check ground continuity.
8. Connect fluid lines between each fluid plate and
applicator. Connect fluid supply line and air supply
to module. See page 31.
9. Plumb air filter assembly near air supply drop site
that will be used for fluid plate assembly.
243A2098S
Installation
A
B
C
D
Install Control Center
NOTE: This section applies to both the primary control
center and the expansion Swirl enclosures.
Mount
Ensure the following criteria are met before mounting
the PCF control center:
•Select a location for the control center that allows
adequate space for installation, service, and use of
the equipment.
•For best viewing, the ADM should be 60-64 in.
(152-163 cm) from the floor.
•Ensure there is sufficient clearance around the control unit to run cables to other components.
•Ensure there is safe and easy access to an appropriate electrical power source. The National Electric
Code requires 3 ft (0.91 m) of open space in front of
the control center.
Secure the control center with appropriate size bolts
through the 0.27 in. (7 mm) diameter holes in the mounting tabs. See the following mounting dimensions.
Table 4: Control Center Assembly Measurement
A
B
C
D
10.50 in. (267 mm)
5.75 in. (146 mm)
22.00 in. (559 mm)
21.25 in. (540 mm)
•Ensure there is easy access to the power switch.
•Ensure the mounting surface can support the weight
of the control center and the cables attached to it.
F
IG. 12: Control Center Dimensions
3A2098S25
Installation
+
-
Ground
Ground
N
L
Electrical Connections
This product must be grounded. In the event of an
electrical short circuit, grounding reduces the risk of
electric shock by providing an escape wire for the
electric current.
•The control center must be electrically connected
to a true earth ground; the ground in the electrical
system may not be sufficient. Refer to your local
code for the requirements for a “true earth ground”
in your area.
•All wires used for grounding must be 18 AWG
minimum.
•All electrical wiring must be done by a qualified
electrician and comply with all local codes and
regulations.
FIG. 14: 100-240 Vac Wiring
•For 24 Vdc wiring refer to F
•For 100-240 Vac wiring refer to F
•Incoming power wiring must be guarded from the
enclosure. Use a protective grommet where the
power wiring enters the enclosure to prevent
wear.
NOTICE
If power and grounding connections are not done
properly, the equipment will be damaged and the
warranty voided.
IG. 13.
IG. 14.
Connect Light Tower Accessory
NOTE: A light tower is not included on models that do
not have an ADM. See Models on page 4.
1. Order the 255468 Light Tower Accessory as a
diagnostic indicator for the PCF system.
2. Connect the cable from the light tower to the digital
I/O port (BS) on the ADM.
See Table 3 for a description of light tower signals.
Table 5: Light Tower Signals
SignalDescription
GreenNo errors.
Yellow An advisory exists.
Yellow flashingA deviation exists.
Red solidAn alarm exists. One or more fluid
plates may be shutdown.
NOTE: See Errors, page 70, for error definitions.
F
IG. 13: 24 Vdc Wiring
263A2098S
Installation
D
A
B
C
Inlet
Outlet
CAN
Connector
Dispense
Valve to
Gun Open
Dispense
Valve to
Gun Close
Install Fluid Plate Assemblies
To install the PCF fluid plate assemblies:
•Mount the fluid plate assemblies, page 27
•Ground fluid plate assemblies, page 31
•Connect one fluid plate assembly to the control center. See Install Cable Assemblies on page 32.
•If multiple fluid plates, connect the fluid plates
together. See Install Cable Assemblies on
page 32.
•Connect fluid lines, air lines, and cables; page 31
Mount
Before Mounting Assembly
•See component manuals for specific information on
component requirements. Information presented
here pertains to the PCF fluid plate assembly only.
2. Mount and secure the fluid plate assembly to the
automation unit (or other mounting surface) with
appropriate size bolts through the 0.397 in. (10 mm)
diameter holes in the base plate. See the mounting
dimensions in Table 4 and F
IG. 15.
Table 4: Fluid Plate Assembly Measurement
A
B
C
D
16.5 in. (419 mm)
14.0 in. (356 mm)
14.4 in. (366 mm)
13.4 in. (340 mm)
•Have all system and subassembly documentation
available during installation.
•Be sure all accessories are adequately sized and
pressure-rated to meet the system's requirements.
•Use only the Graco PCF fluid plate assembly with
IG. 15: Fluid Plate Assembly Dimensions
F
the Graco PCF control center.
Mount Assembly
1. Select a location for the fluid plate assembly. Keep
the following in mind:
•Allow sufficient space for installing the equipment.
•Make sure all fluid lines, cables and hoses easily reach the components to which they will be
connected.
•Make sure the fluid plate assembly allows the
automation unit to move freely along all axis.
•Make sure the fluid plate assembly provides
easy access for servicing its components.
3A2098S27
Installation
check valve
Mount Coriolis Flow Meter
NOTE: A Coriolis flow meter only comes with PFxCxx
assemblies.
NOTICE
See Fluid Plate Assembly Technical Data on page
149 for the weight of your meter. The meter is heavy
and must be properly supported to avoid stress on the
fluid connections.
Fluid Flow Upward
Mounting so fluid flow is upward through the meter is
preferred as this allows solids to settle out and air to rise
away from metering tube. See F
IG. 16.
Horizontal Installation
The horizontal installation is the recommended installation.
If the medium might contain solid particles, mount the
meter as shown in position A, in all other cases as
shown in position B.
F
IG. 16. Fluid Flow Upward
FIG. 17.
283A2098S
Installation
GCA Cable
Splitter Assembly
Hole for bulkhead fitting
Connection 1
J1J3
J2J4
Critical Installations
The meters must be mounted at the highest point of the
tubing (A), if gas bubbles are to be expected, or at the
lowest point (B), if solid particles are to be expected, as
in both cases also the right orientation might not help.
F
IG. 18.
Mount Four-Valve Breakout Kit 24B693
PCF is capable of controlling up to four separate
dispense valves from port 1 on the FCM. A four-valve
breakout kit (24B693) is available to split the dispense
solenoid connector (port 1 on the FCM) into four
separate dispense solenoid connectors. For each
additional dispense valve, order one dispense valve
solenoid (258334) and one solenoid cable (121806).
2. Install bulkhead fitting (included in the kit) into the
empty hole on the fluid plate.
FIG. 19: Mount Breakout Kit
Follow this procedure if using the four-valve breakout
kit.
1. Remove the existing dispense solenoid and cable
from the fluid plate.
3. Connect one end of the extension cables (included
in the kit) to connection 1 on the FCM and the other
end of the cable to the bulkhead fitting.
4. Connect the splitter assembly to the bulkhead fitting.
5. Connect the dispense valve cable(s) to the
connections on the splitter assembly.
Connects to Splitter
Cable for:
Dispense Valve 1J1
Dispense Valve 2J2
Dispense Valve 3J3
Dispense Valve 4J4
Connection Labeled:
6. Mount splitter assembly and dispense valves, and
connect air lines as necessary for application.
3A2098S29
Installation
Custom Breakout Cable
If desired, the following connector pinout information
may be used to build a custom breakout cable:
Pinout of FCM Port 1
Pin 1: Dispense Solenoid 4
Pin 2: Dispense Solenoid 2
Pin 3: Voltage - (common for all solenoids)
Pin 4: Dispense Solenoid 1
Pin 5: Dispense Solenoid 3
Dispense solenoid outputs are 24 Vdc. Dispense
solenoid outputs are capable of sourcing up to 0.5A
each (maximum 12W coil).
Install Command Cable Kit 24B694
Follow this procedure if using the command cable kit.
1. Install bulkhead fitting (included in the kit) into the
empty hole on the fluid plate. See F
IG. 19 on
page 29.
2. Connect one end of the extension cable (included in
the kit) to connection 5 on the FCM and the other
end of the cable to the bulkhead fitting.
3. Connect command cable to bulkhead fitting and
wire to automation controller per the following pinout
table.
Function
FCM
Port
Pin #
Command
Cable Wire
Color
1WhiteCommand voltage (0-10 Vdc)Command voltage (0-10 Vdc)