OPERATION: Initiate lubricant flow from the lube pump serving the
divider valve or pump to point system (until flow has been established,
the electric or pneumatic circuit to the Lube Sentry must be bypassed).
Lubricant passing through the hydraulic section of the valve (See Figure
1 or 2) from port (1) to port (2) moves to piston (3) in the direction of the
arrow. The actuator rod (4) is attached to piston (3) and simultaneously
moves in the same direction allowing the directional spool (5) in the air
valve of the Pneumatic Lube Sentry (See Figure 1) to permit air to flow
between port “A” and port “C” or tripping the microswitch(es). (See Figure
2 Note 2 on the Electric Lube Sentry.) The Lube Sentry is now in a flow
position.
When lubricant flow stops, spring (6) returns piston (3) in the opposite
direction, closing the porting to the lube outlet (7). The lubricant ahead
of piston (3) is forced back through the adjustable needle valve (8) at a
controlled rate. As piston (3) returns to the right, the attached actuator rod
(4) moves the Pneumatic Lube Sentry directional spool (5) permitting air
to now flow between port “A” and port “B” (See Figure 1), or changing the
position of the microswitch(es) (See Figure 2 Note 2) on the Electric Lube
Sentry. The Lube Sentry is now in a no-flow condition. Figure 1 shows a
typical no-flow position.
Adjusting needle valve (8) clockwise increases shutdown time. A
counterclockwise adjustment decreases the shutdown time.
For Closed Contact: Use Red and Blue Wires (Red Common)
For Open Contact: Use Red and White Wires (Red Common)
NO-FLOW CONDITION:
For Open Contact: Use Red and Blue Wires (Red Common)
For Closed Contact: Use Red and White Wires (Red Common)
CAUTION: If only two of the three wires are used, tape un-used wire.
Page 2
Manzel® Pneumatic/Electric Lube Sentry Valve
INSTALLATION
General Lube Line Connection
The Lube Sentry Valve should be located in the lube line 1.
downstream of pump, filters, and controls, but ahead of the
master divider valve. (A high-pressure line filter placed after
the pump is insurance against system plugging due to oil-born
dirt.)
A pressure rupture assembly (Disk Relief Type) must be located 2.
in the main lube line between the pump and the line filter.
Always install Lube Sentry with “LUBE OUT” port up, to permit 3.
natural air purging of the device.
General Shutdown Reaction Adjustment
See graphs for minimum flow rates, with various viscosity oils, 1.
and shutdown time recommendations.
Start with the adjustment screw (Figures 1 & 2, Item 8) 2.
flush with end of housing. Turn on lube system with pump
discharging oil at normal flow rate and pressure.
45425
NOTE: Do not use below minimum recommended
flow rates or inconsistent shutdown times occur.
Graph 1. Minimum Flow Rate
Slowly rotate adjustment screw clockwise until the electric 3.
switch/air valve changes mode (flow condition).
Stop oil flow and note time for electric switch air valve to 4.
change mode (no-flow condition).
Start normal flow of oil and note that the electric switch/air 5.
valve changes mode (flow condition) within two minutes and
remains in this mode as long as normal oil flow continues.
For positive shutdown indication on the Electric Lube Sentry, 6.
an ohmmeter or continuity meter should be connected to
wiring as follows: No flow condition – continuity between red
and white wires. Flow condition – continuity between red and
blue wires. Caution – In an explosive atmosphere, use only
approved device for checking continuity
This is the minimum shutdown time attainable for the 7.
application. The shutdown time can be increased by continuing
to turn the adjustment screw clockwise. Caution – Do not
adjust shutdown time greater than shown on graphs or
inconsistent shutdown time will result.
Pneumatic Lube Sentry Valve Installation
Pneumatic Connections
Series Type (in-line) Safety Control Pneumatic CircuitsA. (See
Figure 3)
Trace pneumatic safety circuits from the source of its take-off 1.
air supply through the various safety devices used on the
engine and compressor to the entrance of the pilot air port
(bonnet port) on the safety control valve or gas shut-off valve.
Select the most convenient location to break into the air circuit, 2.
either between two other safety devices or between the last
safety device and the bonnet port of the safety control valve.
NOTE: At minimum flow rate, the shutdown time is not
adjustable. Times indicated are approximate results when
the attached procedure is followed. Attempting to increase
the shutdown time will result in inconsistent shutdown time.
Graph 2. Minimum Shutdown Time
Break the air circuit at the selected point and tube the Lube 3.
Sentry Valve into the circuit with air flow entering port “A” and
leaving port “C” (See Figure 1). If gas is used as the control
medium rather than air, tube the exhaust port “B” into a
suitable vent line.
CAUTION – Never plug port in series type shutdown circuits.
To test device for operation, start engine to initiate flow in the 4.
divider valve system. Operation of the air valve within the Lube
Sentry will be observed as the tripping out of the reset latch
(manual override) lever on the safety control valve (see Figure
3), and the continued operation of the engine.
After a short interval of running during which the engine and
compressor receive sufficient lubrication and all other safety
devices move to the RUN position, dump the output of the
pumps serving the divider valve systems by removing the
pump blowout disc or a pipe plug from the pump manifold
assembly. When the flow to the distribution system stops,
the Lube Sentry should operate to dump the pressure in the
pneumatic safety circuit, dropping out the safety control valve
to stop the engine. (If shutdown action is sluggish, reduce the
setting of the adjustable orifice through which air for the safety
circuit passes.
Page 2
Page 3
Manzel
®
Pneumatic/Electric Lube Sentry Valve
45425
The Lube Sentry is provided with a 1/8” air valve. If the control orifice for
the safety system is too large, air will be supplied to the Lube Sentry too
quickly to permit it to dump properly.)
A pneumatic relay may be operated by the Lube Sentry (see Figure 4).
Parallel Type Safety Control Pneumatic CircuitsB. (See Figure 5)
Parallel type safety circuits rely on their devices to dump the 1.
pilot control pressure on the safety control valve in case of
trouble. This control pressure is supplied to the pilot (bonnet)
port of the safety shutdown valve through an adjustable orifice
which permits enough air to enter the circuit to maintain
pressure on the port. When any safety device operates, the
pilot pressure is dumped, with the control orifice preventing
sufficient air to enter the system to maintain pressure.
The Lube Sentry should be teed in to the line serving the pilot 2.
port of the safety shutdown valve.
Connect port “B” into the safety circuit.3.
Plug port “C”.4.
Port “A” (exhaust) may be connected to a vent line if necessary.5.
To test device for operation see item 4 under Series Type.6.
Electric Lube Sentry Valve Installation
Electric Switch Adjustment and Replacement
The electrical end of the Lube Sentry has been adjusted correctly at the
factory. If the electric switch assembly is replaced, repairs required or
adjustment necessary, proceed as follows:
housing, consisting of conduit elbow and cap, nipple, and
adaptor by loosening and removing the adaptor, (Figure 7, Item
31) from the switch housing.
Loosen setscrew (Item 26) located on bottom of switch body.3.
Actuating piston must be completely extended (Item 15).4.
Rotate switch enclosure screw (Item 23) clockwise until switch 5.
just actuates. (Continuity is obtained between red and white
wires.) Rotate additonal 1/4 turn after switch actuates.
Tighten setscrew (Item 26) to lock nylon ball (Item 25) against 6.
switch enclosure screw.
If microswitch is defective, replace.7.
Re-adjust switch. 8.
Figure 3. Typical Series Installation of
Pneumatic Engine Shutdown Circuit
Warning: Never remove the Lube Sentry Electric Switch Assembly from
the Actuator Assembly or make any adjustments to the Electric Switch
without first being sure there is NO Electricity Present at the Lube
Sentry.
To Replace Electric Switch Assembly
After determining there is no electricity to the Lube Sentry, 1.
remove the switch assembly from the actuator assembly
by removing the four-socket head screws holding the two
assemblies together, being careful not to scratch the mating
surfaces.
Be sure no corrosion or dirt is present. In a no-flow condition, 2.
the actuator rod should extend approx. 5/32 inches beyond the
actuator rod housing.
Replace electric switch assembly. 3. Caution: Do not reassemble
if scratches, dirt, or corrosion are present on mating surfaces
of switch and actuator assembly.
To Adjust Electric Switch Assembly
With no lubricant flowing, Lube Sentry should be in shutdown 1.
or warning position (switch actuated). You should show
continuity between red and white wires, if not, the microswitch
is misadjusted or broken.
If adjustment is required, remove the electrical connection 2.
Figure 4. Typical Installation with
Pneumatic Indicating Relay
NOTE: Installation of the Pneumatic Lube Sentry as shown on
the drawing provides automatic signalling of cylinder lubrication
trouble. No flow caused by pump failure, broken line or low
oil supply will cause the Lube Sentry to operate, removing air
pressure from the fuel valve and stopping the engine.
Figure 5. Typical Parallel Gas Engine Installation of Lubriquip
Pneumatic Lube Sentry with Fulton-Sylphon No. 530
Pneumatic Pilot Valve
Page 3
Page 4
Ordering Information
DescriptionPart No.Old Part No.
Pneumatic Lube Sentry, Complete563506527-100-190
Pneumatic Valve563503527-100-150
Actuator563502527-100-130
Electric Lube Sentry, Complete563505527-100-180
Switch Assembly563504527-100-170
For more information on the Pneumatic or Electric Lube Sentry Valve consult Literature L15831
Figure 6. Actuator Assembly
Item DescriptionPart No.Old Part No.Qty.
1Lube Sentry Actuator Assembly563502527-100-1301
2Body (Matched Fit)•560999527-100-0001
3Piston (Matiched Fit)•561000527-100-0101
4*Valve - Adjustment•561005527-100-0621
5*Housing Adjustment Screw•561004527-100-0521
6*O-Ring, Viton, 70 Duro•556560422-041-1402
7*O-Ring, Viton, 70 Duro•556551422-040-0601
8*Back-Up Ring•557719527-000-7602
9*O-Ring•556554422-040-1101
10*Setscrew, 1/4-20 x 1/4 Hex•555531417-060-0201
11*Ball, 3/16, Steel•556328401-030-0301
12*Spring-Piston Return•557753527-100-1101
13*O-Ring•556557422-040-1401
14*Spacer, O-Ring Retaining•561009527-100-1001
15*Piston-Switch Actuating•561002527-100-0301
16*Locking Screw, 3/8-24 x 3/16•556470416-700-7801
All written and visual data contained in this document are based on the latest product information available at the time of publication. Graco reserves the right to make changes at any time without notice.
Operating Temperature-20ºF to 180ºF (-29ºC to 82ºC)
Max Air Pressure (Pneu.)125 psi (8 bar)
Elecrical Rating1) 5 amps @ 125/250 VAC
(1) Ref to Graph 1
2) A, B or C @ 28 VDC
(A) Inductive - 3 amp
(B) Resistive - 5 amp
(C) Max Inrush - 15 amp
Contact us today!
To receive product information or talk with a Graco representative,
call 800-533-9655 or visit us online at www.graco.com.