Graco PGM Instructions - Parts Manual

Page 1
Instructions - Parts
PGM
Precision Gear Metering
For metering and dispensing ambient or high-temperature, high-viscosity single-component materials. For professional use only.
2500 psi (17.2 MPa, 172 bar) Maximum Working Outlet Pressure 1500 psi (10.3 MPa, 103 bar) Maximum Working Inlet Pressure See Technical Specifications on page 102 for temperature ranges
3A5185B
EN
See page 4 for model information.
Important Safety Instructions
Read all warnings and instructions in this manual. Save these instructions.
Page 2
Contents
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bulk Melt (Therm-O-Flow 20 + Therm-O-Flow 200)
and Ambient Hoses . . . . . . . . . . . . . . . . . . . 4
Remote Dispense Valves . . . . . . . . . . . . . . . . . . 5
Fixed Dispense Valves . . . . . . . . . . . . . . . . . . . . 5
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
System Configurations . . . . . . . . . . . . . . . . . . . . 8
Component Identification . . . . . . . . . . . . . . . . . 10
System Overview . . . . . . . . . . . . . . . . . . . . . . . 11
Typical Applications . . . . . . . . . . . . . . . . . . . . . 11
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Before Installation . . . . . . . . . . . . . . . . . . . . . . . 12
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Install Control Center . . . . . . . . . . . . . . . . . . . . 13
Install Gear Meter Assembly . . . . . . . . . . . . . . . 14
Install Cable Assemblies . . . . . . . . . . . . . . . . . . 17
System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Configure Control Settings . . . . . . . . . . . . . . . . 19
Configure Mode Settings . . . . . . . . . . . . . . . . . 19
Configure Delay Settings . . . . . . . . . . . . . . . . . 20
Adjust Pressure Sensors . . . . . . . . . . . . . . . . . 20
Configure Errors . . . . . . . . . . . . . . . . . . . . . . . . 21
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Load Material . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Maintenance Mode Operation . . . . . . . . . . . . . . 23
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dispense from Maintenance Screen . . . . . . . . . 25
Automation Control (Normal) Operation . . . . . . 25
Typical Automation Cycle . . . . . . . . . . . . . . . . . 25
Pressure Relief Procedure . . . . . . . . . . . . . . . . . . 26
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Dispense Valves . . . . . . . . . . . . . . . . . . . . . . . . 30
Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
View Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Diagnose Errors . . . . . . . . . . . . . . . . . . . . . . . . 31
Clear Errors and Reset Control Unit . . . . . . . . . 31
Error Codes and Troubleshooting . . . . . . . . . . . 32
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Maintenance Schedule . . . . . . . . . . . . . . . . . . . 34
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Gear Meter Assembly . . . . . . . . . . . . . . . . . . . . 35
PGM-6 Pump Repair . . . . . . . . . . . . . . . . . . . . . 40
PGM-20 Pump Repair . . . . . . . . . . . . . . . . . . . . 44
Gear Pump Maintenance Guide . . . . . . . . . . . . 47
Installing new heater units and RTD sensors . . 48
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
PGM-20 Mounting Frame . . . . . . . . . . . . . . . . . 49
PGM-20 Lower Assembly Block . . . . . . . . . . . . 50
PGM-20 Pump Heat Kit . . . . . . . . . . . . . . . . . . . 51
PGM Drive - 20 cc Pump . . . . . . . . . . . . . . . . . . 52
EnDure Dispense Valve Fix Mounted . . . . . . . . 53
Gear Meter Assembly Panel . . . . . . . . . . . . . . . 54
PGM Back Panel . . . . . . . . . . . . . . . . . . . . . . . . 56
Remote Mount Amplifiers . . . . . . . . . . . . . . . . . 57
PGM Remote Dispense Valve . . . . . . . . . . . . . . 58
PGM Ambient Transducer . . . . . . . . . . . . . . . . . 59
PGM-6 Mounting Frame . . . . . . . . . . . . . . . . . . 60
PGM-6 Drive Kit . . . . . . . . . . . . . . . . . . . . . . . . . 61
PGM-6 Lower Assembly Block . . . . . . . . . . . . . 62
PGM-6 Pump Heat Kit . . . . . . . . . . . . . . . . . . . . 63
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Accessory Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Automation Interface Cable Assembly . . . . . . . 74
Dynamic Regulators (98****) . . . . . . . . . . . . . . . 75
EnDure Valve Nozzles . . . . . . . . . . . . . . . . . . . . 81
Heater Nests . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Appendix A - User Interface Display . . . . . . . . . . 82
Screen Navigation Diagram . . . . . . . . . . . . . . . . 82
Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Calibrate Screen . . . . . . . . . . . . . . . . . . . . . . . . 84
Home Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Maintenance Screen . . . . . . . . . . . . . . . . . . . . . 86
Robot I/O Screen . . . . . . . . . . . . . . . . . . . . . . . . 87
Setup #1 Screen . . . . . . . . . . . . . . . . . . . . . . . . 88
Setup #2 Screen . . . . . . . . . . . . . . . . . . . . . . . . 89
Setup #3 Screen . . . . . . . . . . . . . . . . . . . . . . . . 90
Setup #4 Screen . . . . . . . . . . . . . . . . . . . . . . . . 91
Setup #5 Screen . . . . . . . . . . . . . . . . . . . . . . . . 92
Setup #6 Screen . . . . . . . . . . . . . . . . . . . . . . . . 93
Supply Pump Screen . . . . . . . . . . . . . . . . . . . . . 94
Pressure Trend Screen . . . . . . . . . . . . . . . . . . . 95
Torque Trend Screen . . . . . . . . . . . . . . . . . . . . 96
Alarm Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
2 3A5185B
Page 3
Appendix B - I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Using the PGM I/O . . . . . . . . . . . . . . . . . . . . . . 98
Appendix C - Theory of Operation . . . . . . . . . . . 101
Theory of Operation . . . . . . . . . . . . . . . . . . . . 101
Technical Specifications . . . . . . . . . . . . . . . . . . . 102
Graco Standard Warranty . . . . . . . . . . . . . . . . . . 104
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . 104
Related Manuals
Part Description
309376
310538
334130 Therm-O-Flow 200 (P/N UH****)
311208 Therm-O-Flow 200 (P/N 98****)
313296 Warm Melt Supply Systems
309213 Therm-O-Flow Accessory Heat Zone
EnDure Instructions-Parts List
Therm-O-Flow Valves Instructions-Parts List
Instructions-Parts
Instructions
Instructions-Parts
Controls Instructions-Parts List
®
Automatic Dispense Valves
®
Automatic Dispense
313526 Ambient Supply Systems Operation
3A5185B 3
Page 4

Models

Models
NOTE: This manual covers a series change to the PGM system. For systems built prior to 2016, refer to manual
3A0260.
Check the identification (ID) plate for the 6-digit part number of the fluid metering system. Use the following matrix to define the construction of the system, based on the six digits. For example, Part PG0111 represents a PGM fluid metering system (PG), with a 6cc system (0), unheated (1), with controls/3m (1), and an EnDure snuff-back (1).
NOTE: To order replacement parts, see Parts section in this manual. The digits in the matrix do not corre­spond to the Ref. Nos. in the Parts drawings and lists.
PG 0
First and
Second Digits
Third Digit
Size
1
Fourth Digit
Heat
1
Fifth Digit
Controls *
2
Sixth Digit
Valve
Description Description Description Description
PG
(Precision
Gear Meter)
0 2 20cc 2 Heated 1 Controls / 3m 6 Remote mount
6cc 1 Unheated 0 No controls 1 EnDure
snuff-back
2 Controls / 6m 3 Controls / 9m 4 Controls / 15m
* PGM Control Center does not include heat controls. Heat loads are configured to be controlled by Therm-O-Flow
Controllers.
Bulk Melt (Therm-O-Flow 20 + Therm-O-Flow 200) and Ambient Hoses
Hose Diameter
- 8
3/4 in. - 16 JIC
6 ft None 19M404
10 ft 19M402
15 ft Non None None None 109165/
Hose Length
PGM Inlet (-16 SAE)
PGM Outlet (3/4 in. npt)
Valve Inlet 124287 C20768 107052 124288 158256 † 190451 †
17J652
None None 124238
124286 C20595 15M863 107127 124290 † 124289 †
- 10
7/8 in. - 14 JIC
17J654
19M405
17J655
- 12
1-1/16 in. - 12
JIC
None 19M416
19M412
17J662
Fittings
124235 (90°)
1-5/16 in. - 12 JIC
- 16
17J666
19M417
17J667
124239
124243 †
124236 (90°)
Non-Heated Hoses
3/8 in. 1/2 in.
109163 626720
None 215441
685602*
None None
(1/2 in. x 5 ft)
511381*
* Indicates PTFE hose, all others Buna-N.
Indicates swivel. Therm-O-Flow part number 98xxxx models.
4 3A5185B
Page 5
Models

Remote Dispense Valves

Part Description
243694 Heated Dispense Valve
244951 EnDure Valve, Heated,
1/2 in. npt male outlet
244909 EnDure Valve, Heated

Fixed Dispense Valves

Part Description
244907 EnDure Valve snuff-back

Accessories

Part Description
24D824 Automation I/O Cable
24E654 Ribbon Nozzle Kit, 10 x 1.5 mm
24E655 Bead Nozzle Kit, 3 mm dia.
25A055 Dynamic Air Regulator for
Therm-O-Flow (P/N UH****)
24E575 Dynamic Air Regulator for
Therm-O-Flow (P/N 98****)
24E607 Gear Pump Seals, 6 cc
24E619 Gear Pump Seals, 20 cc
24E677 O-ring Kit, 6 cc
24E626 O-ring Kit, 20 cc
24E678 Heated Nest, Pilot
24E679 Heated Nest, Ribbon or Bead
16E242 Nozzle Heater Insert
16E256 Ported Nozzle Heater Insert
Part Description
124267 Seal Housing, 6 cc
24E826 Gear Shaft Repair Kit, 6 cc
24E827 Seal Shaft Repair Kit, 6 cc
124266 Pump Seal Housing, 20 cc
24E824 Gear Shaft Repair Kit, 20 cc
24E825 Seal Shaft Repair Kit, 20 cc
124235 Elbow Fitting, 90 degree, 3/4 in.
tube x 16 SAE
124236 Elbow Fitting, 90 degree, 1 in. tube
x 16 SAE
124237 Elbow Fitting, 90 degree, 16 SAE x
20 JIC
124238 Adapter Fitting, 3/4 in. Tube x
16 SAE
124239 Adapter Fitting, 1 in. Tube x
16 SAE
124240 Adapter Fitting, 1-1/4 in. Tube x
16 SAE
124241 Adapter Fitting, 16 SAE x
1in.NPTF
124242 Swivel, 16 SAE x 1 in. NPTF
124243 Swivel, 16 SAE x 1 in. tube
124244 Swivel, 1/2 NPTM x 10 JIC
124245 Swivel, 1/2 NPTM x 1/2 NPTF
124286 Adapter Fitting, 3/4 NPTM x 8 JICM
124287 Adapter Fitting, 1/2 NPTM x 8 JICM
124288 Adapter Fitting, 1/2 NPTM x 16
JICM
124289 Swivel Fitting, 3/4 NPTM x 1/2 NPS
124290 Swivel Fitting, 3/4 NPTM x 3/8 NPS
3A5185B 5
Page 6

Warnings

WARNING
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When these symbols appear in the body of this manual or on warning labels, refer back to these Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before disconnecting any cables and before servicing or installing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regu­lations.
SKIN INJECTION HAZARD
High-pressure fluid from dispensing device, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical
treatment.
Engage trigger lock when not dispensing.
Do not point dispensing device at anyone or at any part of the body.
Do not put your hand over the fluid outlet.
Do not stop or deflect leaks with your hand, body, glove, or rag.
Follow the Pressure Relief Procedure when you stop dispensing and before cleaning, checking, or servicing equipment.
Tighten all fluid connections before operating the equipment.
Check hoses and couplings daily. Replace worn or damaged parts immediately.
BURN HAZARD
Equipment surfaces and fluid that is heated can become very hot during operation. To avoid severe burns:
Do not touch hot fluid or equipment.
6 3A5185B
Page 7
Warnings
WARNING
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. Paint or solvent flowing through the equipment can cause static sparking. To help prevent fire and explosion:
Use equipment only in well-ventilated area.
Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop cloths (potential static sparking).
Ground all equipment in the work area. See Grounding instructions.
Never spray or flush solvent at high pressure.
Keep work area free of debris, including solvent, rags and gasoline.
Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes are present.
Use only grounded hoses.
Hold gun firmly to side of grounded pail when triggering into pail. Do not use pail liners unless they are anti-static or conductive.
Stop operation immediately if static sparking occurs or you feel a shock. Do not use equipment until you identify and correct the problem.
Keep a working fire extinguisher in the work area.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maximum working pressure or temperature rating of the lowest rated system com­ponent. See Technical Specifications in all equipment manuals.
Use fluids and solvents that are compatible with equipment wetted parts. See Technical Specifications in all equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information about your material, request Safety Data Sheets (SDSs) from distributor or retailer.
Do not leave the work area while equipment is energized or under pressure.
Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufac­turer’s replacement parts only.
Do not alter or modify equipment. Alterations or modifications may void agency approvals and create safety hazards.
Make sure all equipment is rated and approved for the environment in which you are using it.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed.
Read Safety Data Sheets (SDSs) to know the specific hazards of the fluids you are using.
Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. Protective equipment includes but is not limited to:
Protective eyewear, and hearing protection.
Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer.
3A5185B 7
Page 8

Overview

AD
AC
AH
AB*
AF*
AA*
AE
AK
AM
AG
Air Supply Drop Site
AN
Power
AL
AJ
AH
AH
AO
AO
Overview

System Configurations

Typical Heated System Installation
F
IG. 1: Typical Heated System Installation
Key:
AA *Control Center (User Interface) AB *Gear Meter Assembly AC Applicator/Dispense Valve† AD Automation Robot AE Automation Interface Cable † AF *Gear Meter Cables
AG Heated Fluid Supply System AH Fluid Supply Hose AJ Heat Control AK Automation Controller AL Air Filter Assembly AM Remote Dispense Hose † AN Heated Manifold AO Dynamic Regulator †
*Included † Accessory
8 3A5185B
Page 9
Typical Ambient System Installation
G
D
C*
F*
A*
E
H
J
Air Supply Drop Site
K
Power
B*
Overview
F
IG. 2: Typical Ambient System Installation
Key:
A *Control Center (User Interface) B *Gear Meter Assembly C *Applicator/Dispense Valve D Automation Robot E Automation Interface Cable†
F *Gear Meter Cables G Fluid Supply System H Fluid Supply Hose J Automation Controller K Air Filter Assembly
* Included † Accessory
3A5185B 9
Page 10
Overview
Key:
1 Gear Meter 2 System Controls Box 3 User-Interface Touch Display 4 External Control Interface
Connections 5 Power Input 6 Main Power Switch
7 Emergency Stop 8 Pump Fault Indicator Light 9 Control Power On/Off buttons 10 Pump Ready Light 11 Manual Purge Button 12 Dispense Valve
1
2
3
4
5
12
6
7
8
9
10
11

Component Identification

FIG. 3
10 3A5185B
Page 11
Overview

System Overview

F
IG. 4: Control Center Dimensions
The PGM system provides positive displacement meter­ing for precision bead control. The control accepts auto­mation signals to provide accurate and consistent output flow. The gear meter can achieve high flow rates with high viscosity materials.
Control Power On/Off

Typical Applications

Solar Panel
Perimeter Seal
Desiccant
Edge Seal
Automotive Manufacturing
Window and Door General Assembly
Control Power is the power for the signals to the gear meter which control gear meter rotation. When Control Power is off, the gear meter cannot rotate.
Pump Ready Light
The Pump Ready light displays when the pump is ready for Automatic Mode dispensing. When Manual mode is enabled, this light will not turn on.
Pump Fault Light
The Pump Fault light is illuminated whenever a pump fault is active.
Manual Purge Button
The Manual Purge button initiates a shot.
3A5185B 11
Page 12

Installation

Installation

Before Installation

Have all system and component documentation
available during installation.
See component manuals for specific data on compo­nent requirements. Data presented here applies to the PGM assemblies only.
Be sure all accessories are adequately sized and pressure-rated to meet system requirements.
Use the PGM control center only with the PGM metering assembly.

Overview

The basic steps to install a PGM system are shown below. See the separate component manuals for detailed information on supply systems and dispense
valves.
NOTICE
To avoid damaging the PGM system, use at least two people to lift, move, or disconnect the system. The system is too heavy for one person to lift or move.
Installation Steps
1. Mount control center.
2. Connect and ground control center.
3. Mount gear meter assembly.
4. Ground gear meter assembly.
5. Check ground continuity.
6. Connect fluid line between gear meter and dispense valve. For remote mount dispense valves, con­nect fluid supply line and air supply to gear meter.
7. Plumb filter assembly near air drop site that will be used for gear meter assembly.
8. Connect other fluid and air lines to additional system components as instructed in their manuals.
9. Install cable assemblies.
12 3A5185B
Page 13
Installation
A
B
C
D

Install Control Center

Mount
Ensure the following criteria are met before mounting the PGM control center:
Select a location for the control center that allows adequate space for installation, service, and use of the equipment.
For best viewing, the user interface should be 60-64 in. (152-163 cm) from the floor.
Ensure there is sufficient clearance around the con­trol unit to run cables to other components.
Ensure there is easy access to an appropriate elec­trical power source. The National Electric Code requires 3 ft. (0.91 m) of open space in front of the control center.
Ensure there is easy access to the power switch.
Secure the control center with appropriate size bolts through the 0.50 in. (13 mm) diameter holes. See the mounting dimensions in the following table and F
Control Center Assembly Measurement
A B
C
D
24.0 in. (610 mm)
22.5 in. (572 mm)
30.0 in. (762 mm)
28.5 in. (724 mm)
IG. 5.
Ensure the mounting surface can support the weight of the control center and the cables attached to it.
F
IG. 5: Control Center Dimensions
3A5185B 13
Page 14
Installation
L2
L1
Ground
Electrical Connections
Follow these precautions when grounding, connect­ing cables, connecting to a power source or making other electrical connections.
To reduce the risk of fire, explosion, or electric shock:
The control center must be electrically connected to a true earth ground; the ground in the electrical system may not be sufficient.
A qualified electrician must complete all ground­ing and wiring connections.
For wiring, refer to F
Refer to your local code for the requirements for a “true earth ground” in your area.
If power and grounding connections are not done prop­erly, the equipment will be damaged and the warranty voided.
IG. 6.
NOTICE

Install Gear Meter Assembly

To install the PGM metering assembly:
Mount the gear meter assembly.
Ground gear meter assembly.
Connect the gear meter assembly to the control cen-
ter.
Connect fluid lines and cables.
Mount
Before Mounting Assembly
See component manuals for specific information on
component requirements. Information presented here pertains to the PGM gear meter assembly only.
Have all system and subassembly documentation available during installation.
Be sure all accessories are adequately sized and pressure-rated to meet the system's requirements.
Use only the Graco PGM gear meter assembly with the Graco PGM control center.
Mount Assembly
F
IG. 6: 240 Vac Wiring
1. Select a location for the gear meter assembly. Keep
the following in mind:
Allow sufficient space for installing the equip­ment.
Make sure all fluid lines, cables and hoses eas­ily reach the components to which they will be connected.
Make sure the gear meter assembly allows the automation unit to move freely along all axis.
Make sure the gear meter assembly provides easy access for servicing its components.
14 3A5185B
Page 15
2. Mount and secure the gear meter assembly to the
C
B
6 cc Pump
20 cc Pump
A
A
D
C
B
0.238 in. (6.0 mm) diameter
0.238 in. (6.0 mm) diameter
automation unit (or other mounting surface) with mounting plate. The mounting plate is tapped with M10 x 1.5 bolts. Maximum bolt length through plate is 0.75 in. (19 mm). See the mounting dimensions in Table 4 and F
IG. 7.
Table 4: Gear Meter Assembly Measurement
6 cc Pump 20 cc Pump
Installation
A
B
C
D
2.00 in. (50.8 mm) 3.00 in. (76.2 mm)
5.00 in. (127 mm) 3.875 in. (98.43 mm)
2.375 in. (60.33 mm) 2.313 in. (58.75 mm)
NA 1.063 in. (27.00 mm)
F
IG. 7: Gear Meter Assembly Dimensions
3A5185B 15
Page 16
Installation
Grounding
The equipment must be grounded to reduce the risk of static sparking and electric shock. Electric or static sparking can cause fumes to ignite or explode. Improper grounding can cause electric shock. Grounding provides an escape wire for the electric current.
NOTICE
If power and grounding connections are not done prop­erly, the equipment will be damaged and the warranty voided.
Gear Meter
Ground the gear meter assembly as instructed here and in the individual component manuals. Make sure the gear meter assembly and its components are installed correctly to ensure proper grounding.
For a remote mount dispense valve, connect a fluid line between the gear meter outlet and the dis­pense valve. Shorter fluid lines (hoses) will provide better fluid system response.
See page 4 for list of inlet fittings.
FIG. 8: Inlet Fitting
Air and Fluid Hoses
For static dissipation, use only electrically conductive hoses or ground the applicator / dispense valves.
Dispense Valve
Follow the grounding instructions in the dispense valve manual.
Connect Fluid and Air Lines
NOTICE
Route all fluid and air lines carefully. Avoid pinching and premature wear due to excessive flexing or rub­bing. Hose life is directly related to how well they are supported.
Follow the instructions in your separate component manuals to connect air and fluid lines. The following are only general guidelines.
The PGM gear meter assembly should be installed on the automation unit or in another appropriate place, as close as practical to the dispense valve.
Air must be clean and dry, between 60-100 psi (0.41-0.68 MPa, 4.14-6.89 bar). Flush air line before plumbing in air filter assembly (234967). Plumb in air filter assembly near air drop site (upstream of PGM). Adding an air regulator to this line will provide more consistent dispense valve response times.
Connect a 1/4 in. OD air supply line to the inlet port on the PGM air supply inlet.
NOTE: To maximize system performance keep the dispense hose length as short as the application will allow.
16 3A5185B
Page 17
Install Cable Assemblies
NOTE: Models with 15 meter cables include a remote junction box to be mounted in the field.
Installation
1. Connect servo motor power and feedback cables.
2. Connect pressure transducer cable.
3. Connect dispense valve solenoid cable.
4. Connect heat cables, if equipped, to Therm-O-Flow controller.
F
IG. 9: Cable Installation Diagram
3A5185B 17
Page 18

System Setup

System Setup
Configure Control Settings (page 19)
Configure Mode Settings (page 19)
Configure Delay Settings (page 20)
Adjust Pressure Sensors (page 20)
Configure Errors (page 21)
End System Setup
System Setup

Overview

The PGM system compensates for temperature, flow, or pressure fluctuations. However, if there is a hardware change on the supply system or the dispense material is changed, the PGM system must be setup again.
After material is loaded into the supply system, set up the PGM system using the Setup screens. F shows the major system setup steps. The following sub­sections provide instructions to complete each setup step. Once these steps are complete the module is ready for operation.
NOTE: See Appendix A - User Interface Display on page 82 for detailed operating instructions for each user interface screen.
IG. 10
F
IG. 10
18 3A5185B
Page 19
System Setup

Configure Control Settings

Set the controls for the dispense source, how dispense commands are sent, and auto mode settings.
1. From the Home screen, select the Setup icon
.
NOTE: The Setup screens are password protected. Enter password “PGM17 screens.
”to access the following

Configure Mode Settings

Set the dispense mode (bead or shot). The bead scale and pre-charge are also adjustable from the Mode Set­tings screen.
NOTE: See Appendix A - User Interface Display on page 82 for a description of each feature.
1. With the system in setup mode,
igate to the Mode Settings screen.
press
to nav-
F
IG. 11
2. Select Display or Remote from the Command Value Source Options.
3. If Command Value Source is set to Remote, enter the Remote Max Flow (cc/min) for the 10 VDC command source.
4. Select Enable or Disable for Run Mode Bead Adjust Options. Default is Disable.
5. Select Display or Remote for Job End Mode Options.
6. If Job End Mode is set to Display, press Job End Delay Display field and enter desired delay time in seconds.
FIG. 12
2. Select Bead or Shot for the Dispense Mode.
3. If Command Value Source is set to Display, enter the flow rate in cc/min in the Fixed Command Flow Rate. See Configure Control Settings for instruc­tions to set the Command Value Source value.
4. If Shot Time is displayed, enter the Shot Time in Seconds.
NOTE: Shot Time is only displayed if Dispense Mode is set to Shot.
3A5185B 19
Page 20
System Setup

Configure Delay Settings

Set on and off delays (in milliseconds) for the dispense valve.
1. With the system in setup mode,
igate to the Delay Settings screen.
F
IG. 13
press
to nav-

Adjust Pressure Sensors

Set pressure offsets and pressure limits.
1. With the system in setup mode,
igate to the Pressure Sensor screen.
FIG. 14
press
to nav-
2. Press the On Delay field and enter a desired delay value in milliseconds. Default is zero milliseconds.
3. Press the Off Delay field and enter e desired value in milliseconds. Default is zero milliseconds.
2. Set the desired offset for the inlet and outlet pres­sures. Remove all pressure on the sensors, and then adjust the offset so the measured value reads 0.
NOTE: Offsets are set at the factory.
3. Set the desired minimum and maximum pressure limits for the inlet and outlet.
NOTE: These values may need changed after the system has gone through the Startup procedure.
20 3A5185B
Page 21

Configure Errors

Set the error type (error or deviation) that will be issued if the pressure or drive torque goes outside the set high and/or low limits. See Appendix A - User Interface Display on page 82 for information on the purpose of each error type.
NOTE: When an alarm is set to Error the machine will be disabled when the alarm occurs.
System Setup
1. With the system in setup mode,
igate to the Errors screen.
F
IG. 15
2. Select Enable or Disable for the Error Reset.
3. Select Error or Deviation for the Inlet Pressure.
4. Select Error or Deviation for the Outlet Pressure.
press
to nav-
5. Select Error or Deviation for the Drive Torque.
3A5185B 21
Page 22

Operation

Operation

Startup

Initial Startup
1. Ensure the PGM control enclosure and all of the proper connections to and from the control enclo­sure have been made. Ensure fittings are tight.
2. Read and understand the Operation and User Interface sections of this manual along with the related manuals.
3. Continue startup with Step 2 in Standard Startup.
Standard Startup
1. Carefully inspect the entire system for signs of leak­age or wear. Replace or repair any worn or leaking components before operating the system.
2. Press the Stop button on the control enclosure.
3. Turn on air and electrical power to the system.
4. Turn on the main power to supply power to the PGM.

Load Material

Before using the system, material must be loaded into the supply system.
1. If this is a new installation, follow the Initial Startup procedure. Otherwise, follow the Standard Startup procedure.
2. Turn on the fluid supply pressure to the fluid inlet block for the PGM.
3. Place the dispense valve over a waste container.
4. Navigate to the Maintenance screen. See Screen
Navigation Diagram on page 82 in the Appendix A - User Interface Display section.
5. Select Manual Control Mode .
6. Enter the minimum flow rate to prime the system. See the following table.
Pump Size
cc / revolution
612
20 40
Min Flow Rate
cc / minute
5. Check Interface Signals: If this is a new installa­tion, power on each system input and verify that each input is being received. See Appendix B - I/O on page 98.
6. For heated systems, open the dispense valve over a waste container while the system is heating up. This will prevent a pressure build-up caused by fluids or gases expanding from the heat.
7. Turn on the material supply system.
22 3A5185B
7. Press and hold the manual start button .
Dispense fluid until clean, air-free fluid flows from the dispense valve.
NOTE: The manual purge button on the user-inter­face panel can be used to prime the system.
8. If desired, press to navigate to the Home
screen.
Page 23
Operation

Maintenance Mode Operation

Operating from maintenance mode enables the pump to
begin dispensing when the user presses .
Dispense parameters and duration depend on the selected control.
Verify System Operation
Use maintenance mode to manually check the operation of the PGM system components before switching over to automation control (normal operation).
NOTE: Perform any of the following procedures while in maintenance mode.
Set Inlet Pressure
The inlet pressure reading should be in the range of 300 psi (2.1 MPa, 21 bar) to 1500 psi (10.3 MPa, 103 bar). The recommended inlet pressure should be 500 psi (3.4 MPa, 34 bar) lower than the outlet pres­sure.
Dispense Weight Verification
1. From maintenance screen, select Shot mode.
2. Enter a 10 second shot time.
3. Enter the desired flow rate.
4. Record a minimum of 5 shot weights.
5. If shot weights are inconsistent check feed pressure or reduce flow rate and repeat shot test.
NOTE: Regular weight checks are recommended to ensure system is performing properly.
Follow steps in the supply system manual to set the inlet pressure.
NOTICE
Excessive inlet pressure will cause accelerated wear on the gear meter seals and the pump feed system.
Feed System Pressure Drop
During material flow, the PGM inlet pressure decreases. The amount the pressure decreases is the amount of pressure lost between the feed pump and the PGM inlet.
With high viscosity fluids, long line lengths, or small diameter line sizes this pressure decrease can be thou­sands of psi (hundreds of bar). This means that the static pump pressure is set much higher than the PGM needs at its inlet. To prevent excessive static pressure at the inlet of the PGM, a dynamic regulator is recom­mended on air motor supply air. During dispense the normal pump regulator is active. During a stalled condi­tion the dynamic regulator is active.
3A5185B 23
Page 24
Operation

Calibration

1. Perform Startup procedure, page 22. Verify all sys­tem components are at desired pressures and tem­peratures. Adjust as desired.
2. Navigate to the Calibrate screen. See Screen Navi-
gation Diagram on page 82 in the Appendix A ­User Interface Display section.
NOTE: PGM systems are calibrated at the factory. Per-
form calibration after pump maintenance or during trou­bleshooting (see page 29 for troubleshooting matrix).
3. Press the Enable Calibration button .
4. Weigh one disposable container and tare the scale.
5. Place container below dispense tip.
15. Enter the volume into the High Speed Calibration
Actual Volume input box .
16. Press the Done button .
17. If desired, press to navigate to the Main
screen.
6. Press the Start Low Speed Calibration
button .
7. Weigh the container.
8. Divide the weight of the dispensed material by the specific gravity to determine the volume.
9. Enter the volume into the Low Speed Calibration
Actual Volume input box .
10. Weigh a second disposable container and tare the scale.
11. Place container below dispense nozzle.
12. Press the Start High Speed Calibration
button .
13. Weigh the container.
14. Divide the weight of the dispensed material by the specific gravity to determine the volume.
24 3A5185B
Page 25
Operation

Dispense from Maintenance Screen

1. Navigate to the Maintenance screen. See Screen Navigation Diagram on page 82 in the Appendix A - User Interface Display section.
2. Select Manual Control Mode .
3. Select Bead or Shot from the Manual Mode Option.
Manually Dispense Fluid
1. Press and verify the dispense valve
opens.
2. Continue to press as long as needed to
load or dispense material. Release to stop dispens­ing.

Automation Control (Normal) Operation

During automation control (normal operation) the PGM automatically dispenses when it receives a command from the automation unit.
NOTE: See Appendix B - I/O on page 98.
To enter Auto mode, select Auto (A) Control
Mode .

Typical Automation Cycle

In order for the system to run it must be in Auto mode. Before a cycle begins the robot outputs should have the following values:
Job Complete: 0
Dispense Trigger: 0
A typical cycle consists of the following dispensing sequence.
3. If desired, press to navigate to the Home
screen.
1. The robot checks that Dispenser Ready signal is set to On (High). If On, a cycle can begin.
2. If command source is set to Remote, robot sends 0-10 VDC Flow Rate signal.
NOTE: See Setup Screen 1 information in the Appendix A - User Interface Display section begin­ning on page 82.
3. Robot turns on dispense trigger.
4. PGM turns on In Cycle.
5. Robot removes dispense trigger.
6. If Job Complete is set to Remote, robot turns on Job Complete.
7. Robot removes Job Complete before starting the next cycle.
NOTE: In the event of a deviation alarm, the Dis­pense Ready signal will remain on along with the alarm signal. In the event of an error alarm, the Dis­pense Ready signal will turn off and the alarm signal will remain on.
3A5185B 25
Page 26

Pressure Relief Procedure

Pressure Relief Procedure
Follow the Pressure Relief Procedure whenever you see this symbol.
This equipment stays pressurized until pressure is manually relieved. To help prevent serious injury from pressurized fluid, such as skin injection, follow the Pressure Relief Procedure when you stop dispens­ing and before cleaning, checking, or servicing the equipment.
1. Shut off the fluid supply to the PGM inlet block.
2. If equipped, place a waste container beneath the fluid drain valve under the filter.
3. Place a waste container beneath the dispense valve.
4. Slowly open the drain valve at each fluid filter to relieve fluid pressure. Close valve when pressure gauge reads zero.
5. Navigate to the Maintenance screen. See Screen
Navigation Diagram on page 82 in the Appendix A - User Interface Display section.
6. Perform the following steps to perform a low flow dispense:
a. From the Mode drop-down menu, select Bead
mode.
b. Enter the minimum flow rate for your system.
For example, 12 cc/min or 40 cc/min depending on the size of the gear meter.
c. Press or the Purge button on the
control enclosure to begin the low flow dis­pense.
d. Continue to dispense until the inlet pressure on
the PGM is near zero.
e. Visually locate the plug installed at the back of
the inlet block.
f. Place a container under the plug and slowly
remove the plug to relieve remaining inlet pres­sure.
7. In maintenance mode, select Open Dispense Valve
Control mode , which opens
the dispense valve. Press the manual dispense but-
ton until fluid flow stops.
26 3A5185B
Page 27
Pressure Relief Procedure
Dispense Valve Air Solenoid
8. If the dispense device cannot be actuated from the control center, refer to F
IG. 16 and perform the fol-
lowing steps to open the dispense valve and relieve fluid pressure:
a. Manually actuate the plunger on the solenoid,
that opens the dispense valve to relieve fluid pressure. Refer to F
IG. 16.
b. Continue actuating the plunger until all pressure
is purged from the system between the needle and dispense valve before proceeding to the next step.
9. If you suspect that a valve, hose, or dispense nozzle is clogged or that pressure has not been fully relieved:
a. Very slowly remove the dispense tip, clean the
orifice, and continue relieving pressure as described in steps 6-8.
b. If this does not remove the obstruction, very
slowly loosen the hose end coupling to relieve pressure gradually, then loosen the coupling completely. Clear the valves or hose. Do not pressurize the system until the blockage is cleared.
10. Shut off power and air to the fluid supply system.
FIG. 16: Dispense Valve Air Solenoid
3A5185B 27
Page 28

Shutdown

Shutdown
1. Press the Stop button. See FIG. 17.
2. Shut off the material supply to the gear meter/meter.
3. Shut off heat to PGM. See related manuals section for Therm-O-Flow manual and Accessory Heat Con­trol.
4. For heated systems, open the dispense valve over a waste container while the system is cooling down. This will prevent a pressure build-up caused by flu­ids or gases expanding from the heat.
5. Shut off power and air to the fluid supply system.
6. Turn off the main power supply.
FIG. 17: Stop Button
28 3A5185B
Page 29

Troubleshooting

Troubleshooting
NOTE: Check all possible solutions in the chart below before you disassemble the system.
Refer to Supply Systems manual for additional trouble­shooting; refer to Related Manuals on page 3. Also refer to Error Codes and Troubleshooting, page 32.
PGM Fluid Assembly
Problem Cause Solution
No Inlet Pressure No air pressure on supply system Verify supply system pressure
Leak in supply system Check supply lines and connections
False signal being sent to control Check inlet pressure sensor output;
verify that it corresponds to zero pressure; replace sensor and/or amplifier
Leak at PGM drive shaft Replace drive shaft seals
No Outlet Pressure Dispense motor not rotating Refer to Error code section of the
manual; Cycle power and perform startup
Dispense Off delay set too long Verify Dispense valve delays in
setup screens
Dispense valve solenoid stuck open
False signal being sent to control Check outlet pressure sensor out-
High Outlet Pressure Blocked dispense tip Replace dispense tip
Flow rate too high for application decrease flow rate
Dispense valve On delay set too long
Dispense valve solenoid stuck closed
3A5185B 29
Verify function of dispense valve
put; verify that it corresponds to zero pressure; replace sensor and/or amplifier
Verify Dispense valve delays in setup screens
Verify function of dispense valve
Page 30
Troubleshooting
Dispense pattern too light Supply pressure too low Verify inlet pressure needed for flow
rate
Flow rate too high for application Perform dispense weight verifica-
tion, see Calibration procedure on page 24; Lower flow rate and repeat
Measured flow does not match command
Supply pressure too low Verify inlet pressure needed for flow
rate
Flow rate too high for application Perform dispense weight verifica-
tion, see Calibration procedure on page 24; Lower flow rate and repeat
Gear meter is not calibrated Perform calibration; Perform weight
verification, see Calibration proce­dure on page 24
Gear meter is worn or damaged Perform weight verification, see Cal-
ibration procedure on page 24; if weights are not repeatable repair or replace gear meter

Dispense Valves

Problem Cause Solution
Valve not opening Air not getting to open port Verify air pressure solenoid
No Dispense Trigger signal from automation unit
Valve not shutting off Air not getting to close port (except
AutoPlus valve)
Dispense Trigger signal from auto­mation unit is on
Sluggish open/close Air pressure low Verify air pressure is above 60 psi
Needle/seat worn Rebuild valve; replace needle/seat
Pressurized material past the valve shut-off is escaping
Material leaks from back of valve Shaft seal is worn Rebuild valve; replace seals
Air leaks from dispense valve Loose air connections Check air connections; tighten if
Worn piston o-ring Rebuild valve; replace piston o-ring
Check input from automation unit
Verify air pressure to solenoid
Verify solenoid operation
Verify air line routing and connec­tions
Check input from automation unit
(0.4 MPa, 4 bar)
Reduce running pressure
Reduce nozzle length
Increase nozzle orifice size
necessary
30 3A5185B
Page 31

Errors

Access the Alarm View screen
Errors

View Errors

Errors can be viewed from the Home screen or from the Alarm View screen.
There are three levels of errors: alarms, deviations, and advisories. Alarms are critical and require immediate correction; therefore the system automatically shuts down. Deviations are important and require attention but not immediately. Advisories are not critical but still require attention.
NOTE:
Errors set the dispenser ready signal LOW.

Clear Errors and Reset Control Unit

From the Alarm View screen, perform the following steps to clear an error before restarting the control unit:
1. Press Acknowledge All List
2. Press Clear All Alarms
NOTE: Acknowledging alarms does not clear them.
NOTE: See the Configure Errors section on page 21.
Advisories and deviations do not set the dispenser
ready signal LOW.

Diagnose Errors

See Error Codes and Troubleshooting for valid error codes, possible causes, and solutions.
3A5185B 31
Page 32
Errors
Error Codes and Troubleshooting
Error No.
1 Control Power Off Control power has
2 Inlet Pressure Devia-
3 Inlet High Pressure
4 Inlet Low Pressure
5 Outlet Pressure Devi-
Error Name Error Description
PGM Control Errors
been removed
Inlet material pres-
tion
Error
Error
ation
sure outside limits
Inlet material pres­sure above max limit
Inlet material pres­sure below min limit
Outlet material pres­sure outside limits
Error Type
Advisory Stop button or
Deviation Feed pressure set
Alarm Feed pressure too
Alarm Feed pressure too
Deviation Back pressure is
Cause Solution
E-stop
too high or too low. Limits are not set correctly
high. Limits are not set correctly.
low. Limits are not set correctly.
too high or too low. Limits are not set correctly.
Press Control Power button
Verify pressure limits in Setup Screen 5. Verify supply pres­sures during dis­pense.
Verify pressure limits in Setup Screen 5. Verify supply pres­sures during dis­pense.
Verify pressure limits in Setup Screen 5. Verify supply pres­sures during dis­pense.
Verify pressure limits in Setup Screen 5. Verify outlet pres­sures during dis­pense.
6 Outlet High Pressure
Error
7 Outlet Low Pressure
Error
8 Inlet Max Pressure
Fault - Relieve Pres­sure and Cycle Power
Outlet material pres­sure above max limit
Outlet material pres­sure below min limit
Inlet material pres­sure exceeds max rated pressure
Alarm Back pressure is
too high. Limits are not set cor­rectly.
Alarm Outlet pressure
too low. Limits are not set correctly.
Alarm Feed system pres-
sure is set too high. Pressure sensor damaged.
Verify pressure limits in Setup Screen 5. Verify outlet pres­sures during dis­pense.
Verify pressure limits in Setup Screen 5. Verify outlet pres­sures during dis­pense.
Perform pressure relief procedure. Change inlet supply pressure. Cycle power; Verify Pres­sure sensor is work­ing properly.
32 3A5185B
Page 33
Errors
Error No.
9 Outlet Max Pressure
10 Drive Torque Devia-
Error Name Error Description
Outlet material pres­Fault - Relieve Pres­sure and Cycle Power
sure exceeds max
rated pressure
Motor exceeds con­tion
tinuous rated torque
11 Drive Torque Error Motor exceeds con-
tinuous rated torque
12 Drive Peak Torque
Error - Drive disabled,
Motor exceeds peek
torque rating Cycle Power
Error Type
Cause Solution
Alarm Dispense valve
not opening. Flow rate too high. Material not at temperature.
Deviation Flow rate too high.
Dispense Valve not opening. Material not at temperature.
Alarm Flow rate too high.
Dispense Valve not opening. Material not at temperature.
Alarm Flow rate too high.
Dispense Valve not opening. Material not at temperature.
Perform pressure relief procedure; Cycle Power; Verify Dispense valve func­tion; Perform weight check verification; Reduce flow rate.
Lower flow rate; reduce outlet pres­sure drop; Verify material temperature.
Lower flow rate; reduce outlet pres­sure drop; Verify material temperature.
Cycle Power Lower flow rate; reduce out­let pressure drop; Verify material tem­perature.
13 Pre-Charge Timeout Pre-Charge Pressure
was not reached
after dispense
14 High Pressure Inter-
lock OFF
15 Dispense Valve Open
(Auto Default)
16 Calibration is enabled
complete calibration
Pressure limit is
bypassed
Dispense valve is
open
Calibration mode
enabled procedure
17 Drive Fault, Cycle
Power
18 Calibration out of
range
Motor drive is dis-
abled
Calibration values
are out of range or
flow rate is too low
for current K factor
Advisory Pre-Charge value
not set correctly.
Advisory Pressure sensors
are disabled.
Advisory Dispense valve
open button has been selected.
Advisory Calibration
enabled selected from the calibrate screen.
Alarm Various condi-
tions.
Advisory Improper calibra-
tion, flow rate too low, or pump wear.
Set Pre-Charge to zero. Monitor outlet pressure; Adjust Pre-Charge pressure.
Contact Graco cus­tomer service.
From the Mainte­nance screen select Dispense valve Auto.
Complete calibration procedure.
Cycle Power verify motor torque during dispense.
Perform calibration procedure.
3A5185B 33
Page 34

Maintenance

Maintenance
Prior to performing any maintenance procedures, follow the Pressure Relief Procedure on page 26.
Maintenance Schedule
The following tables list the recommended maintenance procedures and frequencies to operate the equipment safely. The maintenance is divided between mechanical and electrical tasks. Maintenance must be performed by trained personnel per this schedule to assure safety and reliability of the equipment.
Mechanical
Operator Maintenance Person
Task Daily Weekly Monthly
Inspect system for leaks Depressurize fluid, after opera-
tion Remove heat from system,
after operation
Inspect filter (234967) bowls and drain
Check hoses for wear Check/tighten fluid connections Check/tighten air connections
Lubricate dispense valves*
Replace gear meter seals
Rebuild dispense valve*
Replace air filter
Replace Solenoid
Replace gear meter drive shaft
Replace gear head
* Check component manual for more detailed maintenance information.
3-6
months
or
125,000
cycles
18-24
months
or
500,000
cycles
36-48
months
or
1,000,000
cycles
As
Required
Electrical
Task Weekly
Check cables for wear
Verify cable connections
Verify operation of “System Stop” button
* Check Component Manual for more detailed maintenance information.
34 3A5185B
Page 35

Repair

Repair
NOTE: Refer to Parts section beginning on page 49 for part reference number identification.

Gear Meter Assembly

This section describes how to remove and replace com­ponents on the gear meter assembly.
Prepare Gear Meter Assembly for Repair
Replace Servo Motor or Gear Head
Replacing either the Servo Motor or Gear Head requires the following procedure.
Remove Servo Motor and Gearhead
1. Prepare Gear Meter Assembly for Repair, page 35.
2. Remove support gussets (9, 1106).
3. Remove bolts (1, 1103) connecting top mounting plate (8, 1105) to vertical mounting plate (10, 1107).
4. Remove servo motor, gear head, and top plate. Coupling (303, 1203) will separate.
5. Remove coupling half.
6. Remove 4 screws (3, 1110) that mount to plate to gear head.
7. Remove gear head coupling covers (302a, 1202a).
8. Loosen gearhead coupling on gearhead shaft.
FIG. 18
1. Perform Pressure Relief Procedure, page 26.
2. Disconnect main power at the control box.
3. If present, remove power from the heat control.
4. Remove servo power cable and servo feed back cable. See gear meter assembly parts; see Parts section starting on page 49.
5. Remove heat cables.
6. Remove pressure transducer cables and dispense valve cable.
7. Remove supply air pressure from solenoid.
8. Remove front guard.
9. Remove material hoses if necessary.
9. Remove 4 bolts connecting servo motor to gear­head.
10. Remove servo motor from gear head.
3A5185B 35
Page 36
Repair
SEE DETAIL
A
DETAIL
A
SCALE
3/2
Install Servo Motor or Gearhead
1. Remove key from motor shaft.
NOTICE
Use caution when handling servo motor to prevent damage. Do not use tools that could cause damage.
2. Slide the gear head. bushing into the drive coupling and align slots in drive coupling and bushing. See
IG. 19.
F
FIG. 19
3. Rotate the drive coupling to align clamping bolts with access holes.
4. Place motor on work surface with motor shaft facing
NOTE: Orient servo motor so that the motor connec­tions do not interfere with material inlet hose.
9. Install gussets with shoulder bolts (5, 1104).
straight up then mount the gear head. Mounting the gear head in any other orientation will usually lead to misalignment and excessive noise.
Remove Coupling
1. Prepare Gear Meter Assembly for Repair,
5. Pre-torque drive coupling to 0.4 N•m (4 in-lb).
6. Bolt gear head to the motor with fasteners provided.
7. Final toque drive coupling to 8.5 N•m (76 in-lb) in three steps increasing torque each time.
8. Do not tighten coupling to gear head output shaft
page 35.
2. Remove support gussets (9, 1106).
3. Remove bolts (1, 1103) connecting top mounting plate (8, 1105) to vertical mounting plate (10, 1107).
4. Remove servo motor, gear head, and top plate.
until drive assembly is mounted in frame.
36 3A5185B
Page 37
Repair
Gap
5. Loosen clamping bolts on each side of coupling and remove coupling.
NOTE: Pump shaft key may fall out during coupling removal. Secure pump shaft key until coupling is replaced.
Install Coupling
5. Separate coupling until proper gap is created. F
21. See the following table.
Pump Size
cc / revolution Gap (mm)
618
20 20
FIG. 21
IG.
FIG. 20
1. Slide coupling onto gear head output shaft. Tighten coupling bolt just enough to hold it’s position.
2. Align pump shaft key and slide coupling onto pump shaft. Tighten coupling bolt just enough to hold it’s position.
3. Attach servo motor, gear head, and top plate to pump assembly. See F
IG. 20.
4. Slide drive coupling so it is evenly spaced between pump and gearhead. Both sides of coupling should slide easily on each shaft. If coupling does not slide freely, loosen pump bolts (103, 1303) and align pump until coupling moves freely. Tighten pump to pump block to 430-480 in-lb (48.58-54.23 N•m).
6. Tighten coupling bolts to the following torques:
Pump Size
cc / revolution
Torque,
in-lb (N•m)
6 132 (15)
20 309 (35)
7. Install gussets with shoulder bolts (5, 1104).
3A5185B 37
Page 38
Repair
Dispense Valve Air Solenoid
Remove Dispense Valve
1. Prepare Gear Meter Assembly for Repair, page 35.
2. Manually actuate solenoid to ensure pressure has been removed.
4. Connect air lines.
5. Apply air to the solenoid.
6. Manually shuttle solenoid, see F pense valve is open when solenoid is depressed.
IG. 22. Verify dis-
Replace Solenoid
1. Prepare Gear Meter Assembly for Repair, page 35.
2. Disconnect solenoid cable. Remove mating screws (405) from gusset.
3. Remove the dispense valve solenoid (410) and replace it with a new solenoid.
4. Reconnect solenoid cable.
Gear Meter O-Ring Replacement
Refer to Parts section starting on page 49 for o-ring kits.
1. Prepare Gear Meter Assembly for Repair, page 35.
FIG. 22: Dispense Valve Air Solenoid
3. Verify air supply is off.
4. Remove air lines from dispense valve.
5. Remove four dispense valve mounting bolts and remove dispense valve.
NOTE: For remote mount dispense valves, remove supply hose at inlet block of dispense valve.
6. Refer to dispense valve manual for complete dis­pense valve repair instructions; refer to Related
Manuals on page 3.
Install Dispense Valve
1. For direct mounted dispense valves, replace o-ring (409) if necessary.
2. Align dispense valve with mounting pins on front block.
2. Remove pump block shoulder bolts (4, 1102). See F
IG. 23.
NOTICE
Pump section should be fully supported to prevent damage being dropped. It is recommended that the gear meter assembly be located on a work bench for service.
3. Install four mounting bolts (408) torque to 50-60 in-lb (5.6-6.7 N•m).
38 3A5185B
Page 39
Repair
4, 1102
*107, 1306
105,
1305*
102, 1302
104, 1304
* Provided in o-ring kit 24E626.
103,
1303
106, 1304
109, 1308
412
407
108, 1309
3. Remove drive assembly. See FIG. 23.
12. Replace pump block o-rings (106, 104; 1304). See F
IG. 24.
FIG. 23
4. Perform Remove Dispense Valve procedure.
5. Loosen 4 bolts (407) and remove front block (412).
6. Loosen 4 bolts and remove inlet block (110, 1302).
7. Loosen pump bolts (3, 1303) and remove pump (108, 1309).
8. Replace front block o-ring (105, 1305).
9. Install front block (412) onto pump block (109,
1308).
10. Replace inlet block o-ring (107, 1306).
11. Install inlet block (102, 1302) onto pump block.
FIG. 24
13. Place pump (109, 1308) onto pump block. Install bolts (103, 1303) and tighten to 430 in-lb (48.58 N•m).
14. Locate drive assembly on top of pump assembly.
15. Tighten pump block mounting shoulder bolts to frame (4, 1102).
16. Replace all electrical connections and fluid connec­tions before applying fluid pressure and power.
3A5185B 39
Page 40
1614
1611
1612†
1611
1612†
1613
1601
1602
1607
1608
1615
1605
1609
1604
1606
1603
1610
† Parts included in kit 24E607.
Parts included in kit 24E827.
Parts included in kit 24E826.
(P/N: 125657)
(P/N: 125656)
Repair

PGM-6 Pump Repair

FIG. 25: PGM-6
40 3A5185B
Page 41
Repair
PGM-6 Pump Disassembly
1. Prepare Gear Meter Assembly for Repair, page 35.
2. Refer to Gear Pump Maintenance Guide on page 47 for special notes regarding gear pump repair.
3. Remove four pump block shoulder bolts (1102).
NOTICE
Pump section should be fully supported to prevent damage being dropped. It is recommended that the gear meter assembly be located on a work bench for service.
4. Remove drive assembly. See F
NOTICE
IG. 23.
NOTE: Notches on the pump plates can be used to separate the plates.
9. To remove the drive shaft (1605) from the bottom plate (1603) press the shaft and gear from the bot­tom pump plate towards the coupling end.
10. To remove the drive gear (1607) from the drive shaft (1605), support the drive gear at the lower end to allow the shaft to be pressed through the gear from the top or coupling end. Make sure to leave clear­ance for the drive key.
11. The stud (1606) for the driven gear (1608) is press fit into the back plate (1603) and need not be
removed if not worn.
NOTICE
The PGM pump design relies on a lap fit between components for performance and sealing. Be careful not to drop the gears (1607, 1608) or damage the mating surfaces of the pump plates (1601, 1603) and gear case (1602). To prevent damage, do not use pli­ers or screwdrivers to remove the gears.
Thicker materials may require heating prior to disas­sembly. Do not expose the pump to thermal shock. Raise temperature at a maximum rate of 180°F (100°C) per hour. Do not exceed 400°F (204°C). Exceeding this temperature could promote leakage in the pump. Gradually cool the pump to room tempera­ture.
5. Remove seal retainer fasteners (1614) and seal retainers (1611).
6. Remove pump dowel pins (1610) using an arbor press.
NOTICE
Do not use a hammer to remove dowel pins as this will damage the pump.
7. Remove the pump plate screws (1613).
8. Separate the pump front plate (1601), gear case (1602) and back plate (1603).
12. Clean all components thoroughly before reassem­bly. The use of an ultrasonic cleaner is recom­mended.
3A5185B 41
Page 42
Repair
1515,
1614
1512,
1611
*1513,
1612
Pump Body
PGM-6 Pump Assembly
NOTICE
Do not hammer or force components together or dam­age may occur. Parts will drop into place if properly cleaned and aligned. Use of a compatible oil is recom­mended during assembly.
1. Place the back plate (1603) on a table inside facing up.
2. Place the driven gear (1608) on its stud (1606).
3. Place gear case (1602) onto back plate (1603). Check orientation of dowel pin holes to assure they align with the ones in the back plate.
4. Slide drive gear (1607) onto drive shaft (1605). Ver­ify shaft key (1609) is installed properly.
5. Install drive gear (1607) and drive shaft (1605) into back plate (1603).
6. Position top plate (1601) over drive shaft (1605) and place onto gear case (1602).
12. Install new seals (1612). See F
FIG. 26: Seal Locations
IG. 26 and FIG. 27.
7. Rotate the gears several times to ensure free rota­tion.
8. Insert the dowel pins (1610) and rotate the gears several times to ensure free rotation.
NOTE: Dowel pins are not a press fit and may be installed using a plastic hammer if necessary.
9. Install pump plate screws (1613) and tighten to 85-105 in-lb (9.6-11.8 N•m).
10. Rotate the gears several times to ensure free rota­tion.
11. Apply a heat resistant, non-evaporating lubricant to the seal area of the drive shaft (1605).
FIG. 27: Seal Orientation
13. Install seal retainers (1611) and seal retainer screws (1614). Tighten screws to 85-105 in-lb (9.6-11.8 N•m).
14. Align pump shaft key and slide coupling onto pump shaft. Tighten coupling bolt just enough to hold it’s position.
15. Attach servo motor, gear head, and top plate to pump assembly. See F
IG. 20.
16. Separate coupling until proper gap is created. See F
IG. 21.
17. Tighten pump block mounting shoulder bolts to frame (1102).
18. Replace all electrical connections and fluid connec­tions before applying fluid pressure and power.
42 3A5185B
Page 43
Repair
3A5185B 43
Page 44
Repair
1515
1512
1513
1512
1513
1511
1510
1504
1508
1516
1514
1509
1501
1502
1506
1503
1507
1505
† Parts included in kit 24E619.
Parts included in kit 24E825.
Parts included in kit 24E824.
(P/N: 125655)
(P/N: 125654)

PGM-20 Pump Repair

FIG. 28: PGM-20
44 3A5185B
Page 45
Repair
PGM-20 Pump Disassembly
1. Prepare Gear Meter Assembly for Repair, page 35.
2. Refer to Gear Pump Maintenance Guide on page 47 for special notes regarding gear pump repair.
3. Remove six pump block shoulder bolts (4).
NOTICE
Pump section should be fully supported to prevent damage being dropped. It is recommended that the gear meter assembly be located on a work bench for service.
4. Remove drive assembly. See F
NOTICE
IG. 23.
be needed. These will provide clearance for the drive shaft key (1508) and the top plate (1501).
10. Support pump top plate (1501) and press drive shaft (1504) through drive gear (1506). Stop when there is enough clearance between the drive gear (1506) and top plate (1501) to insert one spacer. Be sure to allow clearance for drive key (1508).
11. Continue pressing the drive shaft (1504) and insert­ing spacers until the shaft is free from the drive gear (1506).
12. The stud (1505) for the driven gear (1507) is press fit into the back plate (1503) and need not be
removed if not worn.
NOTICE
The PGM pump design relies on a lap fit between components for performance and sealing. Be careful not to drop the gears (1607, 1608) or damage the mating surfaces of the pump plates (1601, 1603) and gear case (1602). To prevent damage, do not use pli­ers or screwdrivers to remove the gears.
Thicker materials may require heating prior to disas­sembly. Do not expose the pump to thermal shock. Raise temperature at a maximum rate of 180°F (100°C) per hour. Do not exceed 400°F (204°C). Exceeding this temperature could promote leakage in the pump. Gradually cool the pump to room tempera­ture.
5. Remove seal retainer fasteners (1515) seal retain­ers (1512), spacers (1510) and (1511).
6. Remove pump dowels (1509) using an arbor press.
NOTICE
Do not use a hammer to remove dowel pins as this will damage the pump.
7. Remove the pump plate screws (1514).
8. Separate the pump front plate (1501), gear case (1502) and back plate (1503).
NOTE: Notches on the pump plates can be used to separate the plates.
13. Clean all components thoroughly before reassem­bly. The use of an ultrasonic cleaner is recom­mended.
9. To remove drive shaft (1504) from the drive gear (1506) several flat spacers 1/8 in. (3 mm) thick will
3A5185B 45
Page 46
Repair
PGM-20 Pump Assembly
NOTICE
Do not hammer or force components together, or damage may occur. Parts will drop into place if prop­erly cleaned and aligned. Use of a compatible oil is recommended during assembly.
1. Place back plate (1503) on a table inside face up.
2. Install the driven gear (1507) on stud (1505).
3. Place gear case (1502) onto back plate (1503). Check orientation of dowel pin holes to assure they align with the ones in the back plate.
4. Place the top plate (1501) on its edge on a table. Pass the drive shaft (1504) through the top plate from the seal side so that the boss on the shaft rests on the top plate.
5. Rotate the drive shaft (1504) to position the drive key slot at the top. Insert the drive key (1508) and driven gear (1506).
14. Align pump shaft key and slide coupling onto pump shaft. Tighten coupling bolt just enough to hold it’s position.
15. Attach servo motor, gear head, and top plate to pump assembly. See F
IG. 20.
16. Separate coupling until proper gap is created. See F
IG. 21.
17. Tighten pump block mounting shoulder bolts to frame (4).
18. Replace all electrical connections and fluid connec­tions before applying fluid pressure and power.
6. Grasp the top plate (1501), drive shaft (1504) and driven gear (1506) to prevent them from separating and carefully lower them into position onto the gear case (1502).
7. Rotate the gears several times to ensure free rota­tion.
8. Insert the dowel pins (1509) and check again for free rotation.
NOTE: Dowel pins are not a press fit and may be installed using a plastic hammer if necessary.
9. Install pump plate screws (1514) and tighten to 85-105 in-lb (9.6-11.8 N•m).
10. Rotate the gears several times to ensure free rota­tion.
11. Apply a heat resistant, non-evaporating lubricant to the seal area of the drive shaft (1504).
12. Install new seals (1513). See F
IG. 26 and FIG. 27.
13. Install spacers (1510, 1511), seal retainers, (1512) and seal retainer screws (1515). Tighten screws to 85-105 in-lb (9.6-11.8 N•m).
46 3A5185B
Page 47

Gear Pump Maintenance Guide

Review these guidelines prior to performing any mainte­nance on the pumps.
Do not run pump dry.
Do not pull from a vacuum or negative suction head.
Do not flush with water or other non-lubricating fluid.
Do not pump corrosives, abrasives and/or fluids car­rying particles that may harm the pump.
Do not heat or cool pump faster than 180°F (100°C) per hour.
Do not drop disassembled parts on a hard surfaces and do not let parts knock together.
Never strike the pump parts with an iron hammer. The parts are designed to drop in place if properly aligned. Use arbor press to insert or remove press fit components.
Repair
Do not use pliers to lift the gears.
Never use a screwdriver to pry the gears upward.
Apply clean oil or compatible fluid during assembly.
3A5185B 47
Page 48
Repair

Installing new heater units and RTD sensors

1.Prepare Gear Meter Assembly for Repair, page 35.
2. Disconnect the power cables from the heaters.
3. Remove two M3 screws to remove the kit from the inlet block.
6. Remove the heaters and sensor from the block.
NOTICE
The heaters may be difficult to remove and removal depends on the system type. To ensure proper heat transfer and to avoid premature heater failure,
System with through hole:
Press out the heater element using an 0.125” (3 mm) diameter pin.
System without through hole:
Drill out the heater element using a 5mm (0.203 in.) drill bit. Do not increase the hole diameter.
7. Clean any residue from both heater and sensor ports.
8. Installation is the reverse of removal.
4. Remove two M6 screws to remove the kit from the pump block.
5. Remove the two M8 heater nuts and M6 sensor nut.
48 3A5185B
Page 49

Parts

12
11
10
9
3
8
1
4
2
5
ti21285a
PGM-20 Mounting Frame
Parts
Ref Part Description Qty
1 124164 SCREW, shcs, M6-1.0 x 25 4 2 124165 SCREW, bhcs, M5-0.6 x 10 4 3 124166 SCREW, bhcs, M6-1.0 x 10 4 4 124167 SCREW, shoulder, 10x30, M8-1.25 6 5 124168 SCREW, shoulder, 8 x 6, M6-1.0 8 8 16D840 PLATE, mounting 1 9 16D841 GUSSET 2 10 16D842 PLATE 1 11 16D843 INSULATOR 1 12 16V444 GUARD, drive 1
3A5185B 49
Page 50
Parts
103
108
104
101
101
102
105
109
106
107
110
PGM-20 Lower Assembly Block
Ref Part Description Qty
101 101970 PLUG, pipe, headless 2 102 124173 SCREW, M6-1.0 x 90 4 103 124174 SCREW, M10-1.5 x 75 6 104† O-RING 1 105† PACKING, o-ring 1 106† PACKING, o-ring 1 107† PACKING, o-ring 1 108* 16D827 METER, gear, precision, 20cc/rev 1 109 16D915 BLOCK, pump, mounting 1 110 16D916 BLOCK, inlet, PGM 1
† Part included in o-ring kit 24E626.
* For part breakdown and repair kits, refer to PGM-20
Pump Repair, page 44.
50 3A5185B
Page 51
PGM-20 Pump Heat Kit
203
201
202
1
3
204
1
1
Ground location.
3
206
206
205
Parts
Ref Part Description Qty
201 117764 SENSOR, pressure 2 202 24E412 KIT, heat, pump, PGM-20 1 203 24E413 KIT, heat, PGM, inlet 1 204125363 LABEL, heat/burn, warning 2 205 16D923 INSULATOR 1 206 124175 SCREW 3
Replacement Danger and Warning labels, tags, and
cards are available at no cost.
3A5185B 51
Page 52
Parts
301
302
303
302a
PGM Drive - 20 cc Pump
Ref Part Description Qty
301 16D947 MOTOR, PGM drive, servo, 4
frame
302 16D946 GEAR REDUCER, PGM drive,
50:1, 80mm frame
302a COVER 1
303 16D945 COUPLING, PGM drive, 18x20mm,
w/key
1
1
1
52 3A5185B
Page 53
EnDure Dispense Valve Fix Mounted
410
403
405
412
404
409
411
402
406
401
408
406
407
Parts
Ref Part Description Qty
401 597151 FITTING, elbow, 1/4 tube x 1/8 NPT, male 1 402 117820 SCREW, cap, socket head, M3 2 403 124200 SCREW, socket head cap screw, M6-1.0 x 30,
stainless steel
404 124201 SCREW, socket head cap screw, M5-0.8 x 60,
stainless steel 405 116768 PACKING, o-ring 1 406 124403 FITTING, adapter, 1/8 NPTM x 03 JICM, mild steel 4 407 124405 SWIVEL, elbow, 90 deg, 03 JICF x 03 JICM, mild
408 198446 VALVE, dispense, closer 1 409 244907 VALVE, EnDure 1 410 16D943 BLOCK, mounting 1 411 16E899 HOSE, assembly, stainless steel braid, 3/16 x 12 2 412 C32089 RETAINER, seat 1
steel
4
4
2
3A5185B 53
Page 54
Parts
652
624
609
626, 612
618
622, 625
601
614
614
614
616
616
617
615
615
614
617
611, 612, 613
606
608
607
604
605
610
651
603
620
619
602
Gear Meter Assembly Panel
54 3A5185B
Page 55
Parts
Part
Ref
601
---
Description Qty
ENCLOSURE, control, gear meter
1
painted 602 25C836 MODULE, HMI, PGM 1 603 121148 HANDLE, disconnect, electric 1 604 81/2060-
BUTTON, dual, grn/red, w/pl-wht 1
P/11
605 81/2065-
BUTTON, operator, pl, red 1
R/11
606 81/2065-
BUTTON, operator, pl, green 1
G/11
607
---
LABEL, legend, panel, PGM 1
608 16D363 BUTTON, operator, pb, flush, black 1 609
---
610
---
611 81/1060-
14/25
FITTING, bulkhead, gland, 9wire 1
GRIP, cord, .35-.63, 3/4 1
CONNECTOR, sq, 14pw/key, 7a,
panel m
1
612 96/0360/99FASTENER, shc, 4-40x0.25, ms, e 12
613
---
COVER, dust, amp17 conn w/chain1
614 81/2070/11LATCH, operator 4
Part
Ref
615 81/2080-
Description Qty
CONTACT, block, no 2
1/11
616 81/2072-
LIGHT, led, white, 24vdc, latch 3
2/11
617 81/2081-
CONTACT, block, nc 2
1/11
619 81/2060-
BUTTON, mush, maint, twist, red 1
E/11
620 81/2060-
LABEL, legend, e-stop, 60mm 1
EL/11
622 126987 CABLE, communication 1 62484/0130-
LABEL, prot earth(grnd).375x.375 1
23/11
625
---
626 81/1060-
4/25
STRAP, wrap, spiral, 1/2'', nylon 4
CONNECTOR, sq, 4p w/key, 7a, panel m
2
651196548 LABEL, caution 1 65215M511 LABEL, warning,
1
english/spanish/french
Replacement Danger and Warning labels, tags, and
cards are available at no cost.
Cables
Description 3 Meter 6 Meter 9 Meter 15 Meter
Servo Power Cable 17R673 17R674 17R675 17R676
Feedback Cable 17R677 17R678 17R679 17R680
Dispense Valve 24E571 24E572 24E573 24U020
3A5185B 55
Page 56
Parts
718, 720
718, 720
718, 720
716
701
704
729
728
719, 721
710, 725
727
726, 728
717
714
722*
746 713
711
705
708
709
717
706
707
731
702, 707
712
715
PGM Back Panel
Ref Part Description Qty
701
---
702 123361 SWITCH, disconnect, 32a 1 703 124228 EXTENSION, disconnect,
704 117666 TERMINAL, ground 1 705 U70077 TERMINAL, lug, ground, bus type 1 706 123298 CIRCUIT, breaker, 2p, 20a, ul489 1 707 123296 CIRCUIT, breaker, 2p, 1a, ul489 1 708 123359 RELAY, contactor, 30a, 3p, 24vdc co1
709 130185 FILTER 1 710 121808 POWER SUPPLY, 24vdc, 4.0a,
PANEL, back, for30x24 encl, conduit
230-350mm
100w
1
1
1
Ref Part Description Qty
711 123718 FILTER, emi, 6a, spade con 1 712 25C833 MODULE, plc, 14di/10do, 24dc 1 713 129709 MODULE, analog in 1 714 U70899 MODULE, ana-out 1 715 25C834 DRIVE, indexer (PGM-06 only) 1
716
717
718
719
720
721
25C835 DRIVE, indexer (PGM-20 only) 1
---
---
---
---
---
---
STRIP, terminal, PGM, control 1
RAIL, din 1
WIREWAY, panduit, 1.5""x3.0""x6' 6
WIREWAY, panduit, 1"x3"x6' 6
COVER, panduit, 1.5""x6' 6
WIREWAY, cover, panduit, 1"x6' 6
56 3A5185B
Page 57
Parts
8.77 in.
(222.76 mm)
Ø .31 in.
(7.87 mm)
4.0 in.
(101.6 mm)
Ref Part Description Qty
722 129710 AMPLIFIER, signal conditioner,
PGM (3, 6, or 9 m cables) 725 120997 CABLE, turck, rs 4t-4 1 727
---
CLAMP, wire, harness, 1/4,
galvaniz
2
1
Remote Mount Amplifiers
Only for control centers with 15 m cables.
Ref Part Description Qty
72884/0130-
23/11
72984/0130-
26/11
746 --- MODULE, varistor 1
Replacement Danger and Warning labels, tags, and
cards are available at no cost.
LABEL, prot earth (grnd).375x.375 1
LABEL, pe 1
3A5185B 57
Page 58
Parts
809
807
808
805
804
PGM Remote Dispense Valve
Ref Part Description Qty
804 FITTING 1 805 117820 SCREW, cap, socket head, M3 2 807 124200 SCREW, shsc, M6-1.0 x 30, stain-
808 198446 VALVE, dispense, closer 1 809 16E055 BLOCK, outlet, PGM, 3/4 NPTF,
less steel
stainless steel
4
1
58 3A5185B
Page 59
PGM Ambient Transducer
901901901
20 cc Pump 6 cc Pump
901
Parts
Ref Part Description Qty
901 124517 SENSOR, pressure 2
NOTE: Ambient sensors are used on models PGx1xx (unheated). See technical page for ambient operating temperature range.
3A5185B 59
Page 60
Parts
1107
1103
1105
1106
1104
1102
1108
1109
1101
1101
PGM-6 Mounting Frame
Ref Part Description Qty
1101 124165 SCREW, bhcs, M5-0.8 x 10, stain-
less steel
1102 124167 SCREW, shoulder, 10 x 30,
M8-1.25, stainless steel
1103 124313 SCREW, shcs, M6-1 x 16 mm,
stainless steel
1104 124314 SCREW, shoulder, 6 x 8, M5 - 0.8,
carbon steel 1105 16E327 PLATE, mounting, drive, PGM-6 1 1106 16E328 GUSSET, drive, PGM-6 2 1107 16E329 PLATE, mounting, pump, PGM-6 1 1108 16E330 INSULATOR, pump, PGM-6 1 1109 16E331 GUARD, drive, PGM-6 1
7
4
3
8
60 3A5185B
Page 61
PGM-6 Drive Kit
1203a
1203b
1203
1202
1201
1202a
Parts
Ref Part Description Qty
1201 16E367 COUPLING, PGM drive, 12 mm x
14 mm, with key
1202 16E368 GEAR REDUCER, PGM drive,
50:1, 60 mm frame 1202a COVER 1 1203 16E369 MOTOR, PGM drive, frame 1 1203a SCREW 4 1203b WASHER 4
1
1
3A5185B 61
Page 62
Parts
1303
1309
1304
1308
1302
1307
1310
1305
1306
1301
PGM-6 Lower Assembly Block
Ref Part Description Qty
1301 101970 PLUG, pipe, headless 2 1302 124173 SCREW, shcs, M6-1.0 x 90, stain-
less steel
1303 124174 SCREW, shcs, M10- 1.5 x 75,
stainless steel 1304† --- PACKING, o-ring 2 1305† --- O-RING 1 1306† --- PACKING, o-ring 1 1307 16D916 BLOCK, inlet, PGM 1 1308 16E340 BLOCK, pump mounting, PGM-6 1 1309* 24E832 METER, gear, precision, 6cc/rev 1 1310 16K738 WASHER, split, lock, M10, sst 4
† Parts are available in o-ring kit 24E677.
* For part breakdown and repair kits, refer to PGM-6
Pump Repair, page 40.
62 3A5185B
4
4
Page 63
PGM-6 Pump Heat Kit
1
3
1401
1405
1402
Ground location.
3
1406
1403
1
1404
Parts
Ref Part Description Qty
1401 117764 SENSOR, pressure 2 1402 24E732 KIT, heat, pump, PGM-6 1 1403 24E413 KIT, heat, PGM, inlet 1 1404125363 LABEL, heat, warning 2 1405 16E366 INSULATOR 1 1406 124166 SCREW 2
Replacement Danger and Warning labels, tags, and
3A5185B 63
cards are available at no cost.
Page 64

Schematics

CUSTOMER MUST SUPPLY BRANCH CIRCUIT PROTECTION
50-60HZ
1PH/
230V/
DISC-1
L21L2
L11L1
GND
1L1
CB5
1L1
1L21L2
1L1
CB1A
1L1
1L21L2
20A
5A
110
111
100
101
GND
FIL-1
LOAD
LINE
102
103
GND
FIL-2
LOAD
LINE
112
113
X3
AC
POWER
GND
-RB
-DC
+RB
L1
L2
L3
PE
PS-1
N
24V DC
L
FG
V-
V+
130
125
104
105
HARNESS
10 AWG
10 AWG
12 AWG
16 AWG
DC COM
2
PG-PS1
3
PG-PS1
HARNESS 120997
1
PG-PS1
12 AWG
CABLE FROM PS-1
P
N
P
N
P
N
P
N
17S930
104
105
HARNESS 17S895
DVS-1
DVS-2
14 AWG
14 AWG
105
104
140
149
147
145
142
110
138
136
134
132
130
128
126
124
122
120
118
114
116
112
108
106
104
102
100
141
148
144
146
143
111
139
137
135
133
131
129
127
125
123
121
119
115
117
113
109
107
105
103
101
CRM
12
CRM
34
4
3
2
1
7
6
5
BRN
BLU
WHT
BLU
BRN
Schematics
FIG. 29: Schematics, Page 1 of 10
64 3A5185B
Page 65
Schematics
CRM
A1 A2
5
9
3
8
7
4
1
6
2
0X
I
PB-1
125
CONTROL POWER
140
CONTROL_PWR
ON
PL-3
130
0
PB-1A
XO
24
VDC
REMOTE STOP
125
125
130
130
130
141
142
143
143
DC COM
PB-2
XO
E-STOP
HMI1
PE
+
_
RS232 PORT
125
130
CAB-1
126987
PLC1
FG
+24 COM
RS232
PORT
125
130
USB PORTPROGRAMMING
ETHERNET PORT
190
199
197
195
192
160
188
186
184
182
180
178
176
174
172
170
168
164
166
162
158
156
154
152
150
191
198
194
196
193
161
189
187
185
183
181
179
177
175
173
171
169
165
167
163
159
157
155
153
151
W
125 130
125 130
CRM
56
FIG. 30: Schematics, Page 2 of 10
3A5185B 65
Page 66
Schematics
0X
PB-3
MANL-PURGE
24
VDC
130
CONTROL POWER
1
2
5
125
DC COM
PG-IO
PG-IO
PG-IO
125
320
14
PG-IO
310
ONBOARD DIGITAL
INPUTS
I-04
I-05
I-06
I-07
COM
0
PLC-1
AUTOMATION START
AUTOMATION JOB COMPLETE
MANUAL START
X8
125
DRIVE-1 FAULT
24VDC+
12524VDC+
DRIVE-1 RUN
CONNECTOR
SPARE
I-00
I-01
I-02
I-03
SPARE HARNESS 17R672
DRIVE-1 I/O
X7
CONNECTOR
HARNESS
17R671
DRIVE-1 I/O
125 130
XXX XXX
240
249
247
245
242
210
238
236
234
232
230
228
226
224
222
220
218
214
216
212
208
206
204
202
200
241
248
244
246
243
211
239
237
235
233
231
229
227
225
223
221
219
215
217
213
209
207
205
203
201
125
125
1
2
5
6
ORG
ORG
ORG
310
212
210
208
206
204
202
200
FIG. 31: Schematics, Page 3 of 10
66 3A5185B
Page 67
Schematics
24
VDC
130
DC
COM
DRIVE-1
I-08
COM
01
ONBOARD DIGITAL
INPUTS
PLC-1
HARNESS 17R671
X7
12524VDC+
CONNECTOR
DRIVE-1 I/O
DIGITAL-OUT1
I-09
I-10
I-11
I-12
I-13
RESERVED
SPARE
SPARE
SPARE
SPARE
125 130
125 130
258
265
263
260
256
254
252
250
259
266
262
264
261
257
255
253
251
267 268
279
298
296
294
292
290
287
283
285
281
277
275
273
271
269
280
299
297
295
293
291
289
284
286
282
278
276
274
272
270
288
125
7
8
214
.
.
.
.
.
FIG. 32: Schematics, Page 4 of 10
3A5185B 67
Page 68
Schematics
125
24VDC
130
130
DC
COM
R
FAULT
PL-2
DISPENSE VALVE
OPEN
130
SOL-DV
+
1
RED
-
2
WHT
BLK
DC
ONBOARD DIGITAL
OUTPUTS
+24
+
CM0
+
CM1
DC
-24
O
00
O
01
-
CM0
0
02
PLC-1
125
130
125
310
GEARMETER FAULT
GEARMETER FAULT
IN CYCLE
GEARMETER
11
12
6
130
24VDC COMMON
PG-IO
PG-IO
PG-IO
0
03
0
04
249
508
READY TO DISPENSE
GEARMETER
10
PG-IO
G
READY
PL-1
130
125 130
125 130
310
319
317
315
312
308
306
304
302
300
311
318
314
316
313
309
307
305
303
301
329
336
334
331
326
324
322
320
330
337
333
335
332
328
325
323
321
327
348
346
344
342
340
338
349
347
345
343
341
339
CRM
13 14
306
308
300
304
302
302
FIG. 33: Schematics, Page 5 of 10
68 3A5185B
Page 69
Schematics
RESERVED
24VDC
DC
COM
X8
CONNECTOR
130
312
DC COM
HARNESS
17R672
DRIVE-1 I/O
DRIVE-1 ENABLE
PRIMARY A DYNAMIC REGULATOR
130
130
SOL-B
BLK
+
1
RED
-
2
WHT
PG-B
2
PG-B
1
3
TANDEM B
130
SOL-A
BLK
+
1
RED
-
2
WHT
PG-A
2
PG-A
1
3
130
DYNAMIC REGULATOR
0
05
0
06
0
07
0
08
ONBOARD DIGITAL
OUTPUTS
PLC-1
0
09
-
CM1
X7
CONNECTOR
130
314
DC COM
HARNESS
17R671
DRIVE-1 I/O
DRIVE-1 DIGITAL-IN3
130
125 130
125 130
378
387
385
383
380
376
374
372
370
368
366
364
362
360
358
356
352
354
350
379
386
382
384
381
377
375
373
371
369
367
365
363
361
359
357
353
355
351
391
398
396
393
389
392
399
395
397
394
390
388
130
4
3
4
1
318
314
316
312
320
130
FIG. 34: Schematics, Page 6 of 10
3A5185B 69
Page 70
Schematics
+EXCITATION
-EXCITATION
-SIGNAL
+SIGNAL
POWER TRANSDUCER
WHITE
GREEN
BLACK
RED
WHITE
RED
BLACK
. . . . . .
. . . . . .
-SHUNT
+SUPPLY
-SUPPLY
+OUTPUT
-OUTPUT
+SHUNT
+EXCITATION
-EXCITATION
.
POWER TRANSDUCER
BLACK
RED
WHITE
RED
BLACK
RES A
RES B
. . . . . .
-SHUNT
+SUPPLY
-SUPPLY
+OUTPUT
-OUTPUT
+SHUNT
. . . . . .
.
RES A
RES B
A B C D E F
-SIGNAL
+SIGNAL
WHITE
GREEN
A B C D E F
400
130
24VDC
COM
DC
INLET PRESURE TRANSDUCER
402
130
24VDC
OUTLET PRESURE TRANSDUCER
404
7
130
8
0-10 VDC ANALOG FLOW COMMAND
ANALOG COM
FROM AUTOMATION
PG-IO
PG-IO
X8
CONNECTOR
408
HARNESS
17R672
DRIVE-1 I/O
ANALOG-OUT +
PLC ANALOG IN MODULE
DRIVE-1
A GND
DRIVE-1
24VDC
130
406
404
402
405
403
400 401
442
449
447
444
411
440
438
436
434
432
430
428
426
424
422
419
415
417
413
409
407
443
446
448
445
412
441
439
437
435
433
431
429
427
425
423
421
416
418
414
410
408
420
125 130
125
125 130
125
7
8
ORG
ORG
COM
VI-0
CI-2
COM
COM
VI-1
VI-3
CI-1
CI-3
COM
VI-2
CI-0
B3 B4 B6B1 B2 B5
A1 A2 A3 A4 A5 A6
INLET AMP
OUTLET AMP
FIG. 35: Schematics, Page 7 of 10
70 3A5185B
Page 71
Schematics
24VDC
COM
DC
HARNESS
17R672
DRIVE-1 I/O
ANALOG OUT
0-10 VDC COMMANDED
FLOW TO DRIVE
PLC ANALOG OUT MODULE #1
412
410
DRIVE-1
ANALOG-IN COM
ANALOG-IN +
X8
CONNECTOR
410
412
RESERVED
451
450
461
468
466
463
458
456
454
452
462
469
465
467
464
460
457
455
453
459
474
471
470
473
472
475
486
498
496
494
490
492
488
484
482
480
478
476
487
499
497
495
491
493
489
485
483
481
479
477
125 130
125 130
10
9
B1
VO-0
COM
CO-0
COM
VO-1
COM
CO-1
COM
B2 B3 B4
A1 A2 A3 A4
FIG. 36: Schematics, Page 8 of 10
3A5185B 71
Page 72
Schematics
6
POWER CABLE
FEEDBACK CABLE
MOTOR
X10
X2
X3
X7
223
HARNESS 17R671
X8
215
HARNESS 17R672
DRIVE
I/0
DRIVE
I/0
DRIVE
PWR
259
355 440
X1
24VDC
PWR
320
HARNESS 17S161
130
125
24VSTO
-24V
+24V
310
130
125
X7 PIN DESCRIPTION
1 DC COM
2 IN 7 3 IN 4 4 IN 3 5 OUT 2­6 OUT 2+ 7 OUT 1­8 OUT 1+ 9 IN 2
10 IN 1
X8 PIN DESCRIPTION 1FAULT 2FAULT 3 DC COM 4 ENABLE 5 IN 6 6 IN 5 7 A GND 8 ANALOG OUT + 9 ANALOG IN ­10 ANALOG IN +
365 458
110
HARNESS 17S930
516
525
523
521
518
514
512
510
508
506
504
502
500
517
524
520
522
519
515
513
511
509
507
505
503
501
534
541
539
536
532
530
528
526
535
542
538
540
537
533
531
529
527
543 544
549
547
545
548
546
DRIVE-1
FIG. 37: Schematics, Page 9 of 10
72 3A5185B
Page 73
Schematics
TO GROUND
DIST. BAR #1
STAR WASHER
GROUND LUG
INCOMING GROUND PROTECTIVE EARTH
SUBPLATE
PE GROUND STUD GRN/YEL
DRIVE-1 PE
DRIVE-1 X3-1
PLACE NEAR GROUND DIST BAR
GROUNDING NOTES:
1. GROUND ALL DISTRIBUTION BARS.
2. GROUND ALL DOORS.
3. DO NOT JUMPER GROUND WIRES.
PE
PLACE NEAR GROUND LUG
FIL-2
FIL-1
585
595
593
591
587
555
583
581
579
577
575
573
571
569
567
565
563
559
561
557
553
551
586
594
589
592
588
556
584
582
580
578
576
574
572
570
568
566
564
560
562
558
554
552
550
598
596
599
597
590
GROUND DIST. BAR
FIGURE 2
NTS
FIGURE 1
NTS
FIG. 38: Schematics, Page 10 of 10
3A5185B 73
Page 74

Accessory Parts

Accessory Parts
Automation Interface Cable Assembly
The cable length of automation interface cable assembly 24D824 is 40 ft (12.2 m). This figure shows the cable and identifies the cable interface signals. See Appendix B - I/O on page 98 for wiring details. See Appendix C - Theory
of Operation on page 101.
Pin # Wire # Color Description
1 208 Black Dispense Start 2 210 Red Job Complete 3 SPARE White N/C 4 SPARE White/Black N/C 5 125 Orange 24 VDC from PGM 6 130 Blue 24 VDC common 7 404 Red/Black Analog flow command 8 130 Green Analog common
9 SPARE Green/Black N/C 10 302 Blue/Black Dispenser ready 11 300 Red/White Fault present 12 304 Orange/Black In cycle 13 SPARE Green/White N/C 14 310 Blue/White 24 VDC thru E-stop
74 3A5185B
Page 75
Dynamic Regulators (98****)
1011
1004
1008
1006
1010
1013
1001
1005
1004
1004
1014
1016
1003
1002
1012
1007
1009
1018
1017
1021
1020
1019
NOTE: This kit is intended for Therm-O-Flow units built prior to 2016, which includes part numbers that start with 98xxxx. See Accessories on page 5 for the latest version of the Therm-O-Flow which includes part number UHxxxx.
Kit 24E575
Accessory Parts
Ref Part Description Qty
1001 112699 TUBE, 1/4 OD 2 1002 C20466 FITTING, nipple, hex 1 1003 112307 FITTING, elbow, street 1 1004 100139 PLUG, pipe 2 1005 112781 FITTING, elbow, swivel 1 1006 054776 TUBE, nylon, round, 5/16 in/ 8 mm 2 1007 110321 BRACKET, mounting 1 1008 297612 SCREW, cap, button head 2 1009 110318 REGULATOR, air, 1/4 in. npt 1 1010 110319 GAUGE, pressure, air, 1/8 npt 1 1011 115948 FITTING, elbow, 1/4 nptM, 5/16T OD 1 1012 107110 NUT, lock 2 1013 121022 FITTING, elbow, male, 1/4 npt 1 1014 198171 FITTING, elbow 1 1015 198446 VALVE, dispense, closer 1 1016 24E574 CABLE, feed regulator, PGM, 9 meter 1 1017 080226 VALVE, quick exhaust, 3/4 in. nptf 1 1018 C20461 FITTING, nipple, reducing, hex 1 1019 125466 FITTING, swivel, elbow, 1/2 nptf 1 1020 100896 FITTING, bushing, pipe 1 1021 111530 MUFFLER 1
3A5185B 75
Page 76
Accessory Parts
Dynamic Regulator Setup and Installation (P/N 98****) 24E575
1. Remove air pressure from Therm-O-Flow supply system. See Pressure Relief Procedure in manual
311208.
2. Install dynamic regulator kit. See F page 77.
3. Apply air to the Therm-O-Flow supply. Check for air leaks.
4. Set the secondary regulator for a low operating pressure, for example 20-25 psi.
5. Adjust the panel mount Therm-O-Flow regulator to zero psi.
6. Connect the dynamic regulator cable from the Therm-O-Flow to the PGM control box.
7. Navigate to the Supply Pump screen. See Appen- dix A - User Interface Display starting on page 82 for Supply Pump screen information.
8. Select ON mode for the Primary or Tandem Pump drop-down menu.
9. Set the appropriate press for the panel mount regu­lator on the Therm-O-Flow. For example, 30-40 psi.
10. Select AUTO mode for the Primary or Tandem Pump drop-down menu.
IG. 39 on
11. Verify operation of the new regulator and adjust pressure as needed to achieve a maximum static pressure of 1500 psi (103 bar) when the system is not dispensing.
76 3A5185B
Page 77
Dynamic Regulator Installation 24E575
Detail A
3
1
6
2
4
11/16 in.
7/32 in.
5
diameter
7
8
Remove plug and attach supplied tubing to regulator inlet.
Holes required for mounting. See detail A.
5/32 in. tubing removed from Therm-O-Flow regulator to be attached here.
Regulator pilot port will have an existing 5/32 in. air line. This air line and its fitting are to be removed from the regulator and replaced with the fitting supplied with dynamic regulator.
The existing pilot tube will be connected to the 5/32 fitting on the diverting valve supplied with 24E575.
To Therm-O-Flow regulator pilot port.
Regulator inlet.
Thread existing air line with 1/2 in. npt coupling to 90° swivel fitting.
Attach to PGM control panel.
1234567
8
5/16 in.
Accessory Parts
F
IG. 39
The dynamic regulator kit is used to control the static pressure of a Therm-O-Flow (98****). The PGM has a maximum inlet pressure of 1500 psi. During dispense the dynamic regulator kit will activate the normal regula­tor located on the front panel of the Therm-O-Flow. When the system is idle the secondary regulator will control static pressure.
3A5185B 77
Page 78
Accessory Parts
1001
1002
1003
1004
1005
1006
1018
1007
1016
1017
1009
1012
1014
1014
1015
1003
1013
1012
1011
1010
1009
1018
1008
NOTE: This kit is for the current series of Therm-O-Flow which contains part number UHxxxx.
Kit 25A055
Dynamic Regulators (UH****)
Ref Part Description Qty
1001 158491 FITTING, nipple 1 1002 120435 REGULATOR, remote piloted 1 1003 121022 FITTING, elbow, male, 1/4 npt 2 1004 C20461 FITTING, nipple, reducing, hex 1 1005 080226 VALVE, quick exhaust, 3/4” nptf 1 1006 111530 MUFFLER 1 1007 121282 FITTING, swivel, straight, 1/2 fx3/4 m 1 1008 24E574 CABLE, feed regulator, pgm, 9 mtr 1 1009 112781 ELBOW, swivel, 90 deg 2 1010 112307 FITTING, street elbow 1 1011 C20466 FITTING, nipple, hex 1 1012 100139 PLUG, pipe 2 1013 110318 REGULATOR, air, 1/4” npt 1 1014 123257 FITTING, nipple, hex, 1/4 npt, brs 2 1015 113264 CROSS, pipe 1 1016 110319 GUAGE, press, air, 1/8” npt 1 1017 198446 VALVE, dispense, closer 1 1018 054130 TUBE, plyeth .250 od 3
78 3A5185B
Page 79
Dynamic Regulator Setup and Installation (P/N UH****) 25A055
1. Remove air pressure from Therm-O-Flow supply system. See Pressure Relief Procedure in manual
334130.
Accessory Parts
2. Install dynamic regulator kit. See F page 80.
3. Apply air to the Therm-O-Flow supply. Check for air leaks.
4. Set the secondary regulator for a low operating pressure, for example 20-25 psi.
5. Adjust the air motor regulator at the top of the air tree to zero psi.
6. Connect the dynamic regulator cable from the Therm-O-Flow to the PGM control box.
7. Navigate to the Supply Pump screen. See Appen- dix A - User Interface Display starting on page 82 for Supply Pump screen information.
8. Select ON mode for the Primary or Tandem Pump drop-down menu.
9. Set the appropriate pressure for the air motor regu­lator at the top of the air tree on the Therm-O-Flow. For example, 30-40 psi.
IG. 40 on
10. Select AUTO mode for the Primary or Tandem Pump drop-down menu.
11. Verify operation of the new regulator and adjust pressure as needed to achieve a maximum static pressure of 1500 psi (103 bar) when the system is not dispensing.
3A5185B 79
Page 80
Accessory Parts
5
7
1
4
3
6
2
Disconnect red airline from air tree.
Remove pressure relief safety valve from air tree.
Screw in the cross with adjustable air pressure regulator into the pressure relief safety valve hole.
Attach the dynamic regulator assembly to the hose connection on the air tree.
Attach the red air hose to the dynamic regulator assembly.
Attach the pressure relief safety valve to open port on the cross fitting.
Attach to PGM control panel.
12345
6
7
Dynamic Regulator Installation
F
IG. 40
The dynamic regulator kit is used to control the static pressure of a Therm-O-Flow (UH****). The PGM has a maximum inlet pressure of 1500 psi. During dispense the dynamic regulator kit will activate the normal regula­tor located on the front panel of the Therm-O-Flow. When the system is idle, the secondary regulator will control static pressure.
80 3A5185B
Page 81
EnDure Valve Nozzles Heater Nests
Accessory Parts
Part Description
24E654 10 x 1.5 mm Ribbon Nozzle 24E655 1/8 in. Bead Nozzle
Part Description
24E678 Heater Nest with Blank Insert 24E679 Heater Nest with Ported Insert
3A5185B 81
Page 82

Appendix A - User Interface Display

Screen #1
Current Setup
Screen
Screen #2
Screen #3
Screen #4
Screen #5
Main
START MACHINE
Maintenance
Home
Calibrate
Robot I/O
Setup Screens Flow
Supply Pump
Setup Screens
Alarm Screen
Screen #6
Appendix A - User Interface Display
Screen Navigation Diagram
82 3A5185B
Page 83
Appendix A - User Interface Display
Key:
A Navigate to the Home screen B Navigate to the Calibrate screen
A
B

Main Screen

Press the appropriate button to navigate to either the Home or Calibration screen. To access the Calibration screen, select the login button and enter user “setup
.
and passwordPGM17”.
3A5185B 83
Page 84
Appendix A - User Interface Display
Key:
C Enable Calibration button (Begin
Calibration) D Done button (Finish Calibration)\ E Calibration Shot Time Input Box F Calibration K Factor (Automatically
Calculated) G Start Low Speed Calibration button
H Low Speed Calibration Shot Volume Input
Box J Start High Speed Calibration button K High Speed Calibration Shot Volume Input
Box L Navigate to Main Screen M Pump RPM during low speed calibration N Pump RPM during high speed calibration
K
F
E
L
J
G
H
C
D
N
M
Calibrate Screen
NOTE: See Calibration procedure on page 24.
84 3A5185B
Page 85
Home Screen
Key:
O Enable Manual mode P Enable Automatic mode R Increase Bead Scale S Decrease Bead Scale T Current Bead Scale setting U Navigate to Maintenance Screen
V Navigate to Robot I/O Screen W Navigate to Setup Screens X Navigate to Main Screen Y Navigate to Alarm Screen Z Navigate to Supply Pump Screen AA Navigate to Trend Screen
R
T
S
Y
U
X
W
AA
V
Z
O
P
Appendix A - User Interface Display
Manual Mode
In Manual Mode, the machine only accepts signals from the User Interface touch screen and the physical buttons on the machine. All signals from an External Control Interface to initiate a shot will be ignored.
Automatic Mode
In Automatic Mode, the machine only accepts initiate shot signals from an external machine. All signals to initi­ate a shot using the User Interface touch screen or the physical buttons on the machine will be ignored.
The primary purpose of the bead scale is to be able to quickly adjust volume dispensed to be able to find that actual desired volume. Once the correct volume is found, the flow rate should be adjusted accordingly.
Screens Navigation
Access to the Setup screens requires the setup pass­word.
Flow Rate Display
The Home screen will display the commanded Flow Rate from 1 of 3 sources:
Bead Scale
The bead scale function adjusts the quantity dispensed by the scale percent value shown. For example, if the system is setup to dispense 100 cc/min and the bead scale setting is 110 then the machine will dispense 100 cc/min x 110% scale =110 cc/min.
3A5185B 85
1 - Maintenance Flow Rate (see Maintenance Screen on page 86)
2 - Auto Mode Display Flow (see Setup #2 Screen on page 89)
3 - Remote 0-10 VDC Command Flow (see Appen- dix B - I/O on page 98)
Page 86
Appendix A - User Interface Display
Key:
AB Enable Automatic Dispense Valve
Control
AC Open the Dispense Valve, Disable
Automatic Dispense Valve Control
AD Enable Bead Manual Mode
AE Enable Shot Manual Mode AF Dispense Duration Input Box AG Flow Rate Input Box AH Manual Start Dispense
A
AC
AB
AG
AD
AF
AH
Q
AE
P
Maintenance Screen
Dispense Valve Control
Dispense Duration: This is the amount of time the
machine will dispense at the given flow rate. This value
When Automatic Dispense Valve Control is enabled, the
is only used in Shot Mode.
dispense valve will open and close as needed to dis­pense material.
Flow Rate: This is the rate at which the machine will dispense for the given dispense duration.
When Open the Dispense Valve is selected, the dis­pense valve will open and remain open until Automatic Dispense Valve Control is enabled.
Manual Start Dispense
After adjusting the settings, the user can press the Man-
Dispense Settings
Dispense Mode: Options include Bead and Shot.
In Bead mode, dispensing begins when the initiate shot button is pressed and dispensing ends when the initiate shot button is released.
ual Start Dispense button (AH) to dispense material using the current settings.
NOTE: This button performs the same function as the manual purge button located on the control panel.
In Shot mode, dispensing begins when the initiate shot button is pressed and released. Dispensing ends when the Dispense Duration (AF) elapses.
86 3A5185B
Page 87
Robot I/O Screen
A
Appendix A - User Interface Display
Overview
This screen is for settings related to an external machine setup to control the dispense operation of this system. See Appendix B - I/O on page 98 for more information.
Robot Outputs
These are signals sent by the external machine when the related action should occur. The Job Complete sig­nal is sent to stop the In Cycle signal. The Dispense Trigger is sent to begin dispensing. The Command Volt­age is a display of the voltage of the command cable and is for troubleshooting only. See Appendix B - I/O on page 98 for more information.
Robot Inputs
These are signals sent to the external machine to notify it of system conditions. The Dispense Ready signal tells the external machine that the system is ready to dis­pense and a dispense can be initiated. The No Alarm signal tells the machine that there are currently no active alarms. The In Cycle signal tells the external machine that the system is currently busy so dispensing cannot be initiated.
NOTE: Dispense Ready remains on while in Auto Mode. If a deviation alarm occurs the Dispense Ready and Alarm signal will remain ON. If an error alarm occurs the Dispense Ready will be removed.
3A5185B 87
Page 88
Appendix A - User Interface Display
A
Setup #1 Screen
#1 to #6 Buttons
Press to navigate to the Setup Screen with that number. For example, press #3 to navigate to Setup Screen #3.
Command Value Source
Command Values can be controlled by the user-inter­face touch screen or by an external machine connected to the system via the External Control Interface.
Run Mode Bead Adjust
When this option is enabled the Bead Scale function appears on the Home Screen. See the Home Screen on page 85 for more information.
Job End Mode
The In Cycle signal can be dropped when the dispense trigger is removed when Display is selected.
If Remote is selected the Job Complete signal is required to remove the In Cycle signal.
Job End Delay (sec)
When Job End mode is set to Display the In Cycle signal is removed after the time in this field.
88 3A5185B
Page 89
Setup #2 Screen
A
Appendix A - User Interface Display
Overview
The Dispense Mode, Flow Rate, and Dispense Duration settings apply to Automatic Control Mode
only. Values changed on this
screen independent of changes made on the Mainte­nance screen.
The Bead Scale value is a duplicate to the Bead Scale setting on the Home Screen, which can be enabled or disabled from the Setup #1 screen. See Setup #1
Screen on page 88 for more information.
Fixed Command cc/min
Flow rate can be entered here. This field is only used when command value source is set to Display on Setup Screen 1. See Setup #1 Screen on page 88 for more information.
Pre-Charge
This is the pressure between the meter and the dis­pense valve when the dispense valve is closed. If the pre-charge setting is non-zero then, immediately after dispensing, the gear meter will continue to rotate after the dispense valve closes until the pre-charge pressure value is achieved. The maximum Pre-Charge value is
2500 psi (17.2 MPa, 172 bar).
Larger values for the On Delay setting lead to larger pressures in the system. If a value too large is input, the machine could over-pressurize leading to rup­tured components and serious injury.
#1 to #6 Buttons
Press to navigate to the Setup Screen with that number. For example, press #3 to navigate to Setup Screen #3.
3A5185B 89
Page 90
Appendix A - User Interface Display
A
Setup #3 Screen
#1 to #6 Buttons
Press to navigate to the Setup Screen with that number. For example, press #3 to navigate to Setup Screen #3.
Delay Settings
Larger values for the On Delay setting lead to larger pressures in the system. If a value too large is input, the machine could over-pressurize leading to rup­tured components and serious injury.
The Delay Settings affect the timing of the Dispense Valve opening and closing when a shot is initiated.
The On Delay is the amount of time, in milliseconds, between a shot being initiated and the dispense valve opening. If the On Delay is set to 100 the machine will wait 100 milliseconds after a shot is initiated before opening the dispense valve. This will lead to a pressure build up between the meter and dispense valve until the dispense valve opens.
The Off Delay is the amount of time, in milliseconds, between a shot completing and the dispense valve clos­ing. If the Off Delay is set to 100 the machine will wait 100 milliseconds after a shot is complete before closing the dispense valve.
Drive Information
Motor Torque
Display motor torque during dispense. If motor torque climbs above continuous torque an alarm is issued. See
Errors on page 31.
Cont. Torque
Continuous torque rating of the motor.
NOTE: The motor torque display is a good way to deter­mine the maximum flow rate with a given viscosity.
90 3A5185B
Page 91
Setup #4 Screen
A
Appendix A - User Interface Display
#1 to #6 Buttons
Press to navigate to the Setup Screen with that number. For example, press #3 to navigate to Setup Screen #3.
Pump Settings
Snuff Back: This enables the gear meter to rotate in
reverse, immediately following dispensing, to pull mate­rial back from the dispense valve to minimize or elimi­nate material drooling. The Snuff Back Time and Snuff Back Pump RPM are the settings used when Snuff Back is enabled. These settings should be adjusted to work best for your material.
NOTE: Not recommended for very viscous materials.
Pump Hour Totalizer: This field will record the total dis-
pense time on the machine in hours. This field is non-resettable.
Pump Hour Meter: This field displays total dispense time in hours. This field is resettable.
3A5185B 91
Page 92
Appendix A - User Interface Display
A
Setup #5 Screen
Overview
This screen controls settings for the pressure sensors. These values are used for triggering errors.
#1 to #6 Buttons
Press to navigate to the Setup Screen with that number. For example, press #3 to navigate to Setup Screen #3.
Inlet, Outlet Offset
The inlet, outlet offset values are used to tune the pres­sure transducer. If the pressure transducers do not reg­ister zero pressure when there is no material in the system, enter a value to shift the pressure value to zero. For example, if 15 psi is shown, enter -15 psi to shift the value to 0.
Min/Max Inlet/Outlet Limits
These limit values are used to set the acceptable range of values for dispensing. If values are outside of this range during dispensing the machine will issue an alarm. See Errors on page 31.
PSI, BAR
Set the unit of measure for pressure system-wide.
92 3A5185B
Page 93
Setup #6 Screen
A
Appendix A - User Interface Display
Fault Settings
Error Reset: If set to Disable, errors cannot be reset. If
set to Enable, errors can be reset.
Inlet/Outlet Pressure, Drive Torque: If set to Error, an error will be generated when the out-of-limit condition occurs. The machine will be disabled until the error is reset. If set to deviation, an error will be generated when the out-of-limit condition occurs. The machine will not be disabled until the error is reset.
If set to Deviation, an error will be generated when the out-of-limit condition occurs. The machine will not be disabled. See Errors on page 31.
3A5185B 93
Page 94
Appendix A - User Interface Display
A
Supply Pump Screen
NOTE: This screen is used to control the optional dynamic regulator kit for a Therm-O-Flow. See Accessory Parts section on page 74 for additional information on the dynamic regulator kit option.
Supply Pumps (Dynamic Analog Regulator)
Primary Supply Pump Mode
Auto Mode: During normal operation this mode will activate the dynamic regulator solenoid when the dispense valve solenoid is activated.
On Mode: This will activate the dynamic regulator solenoid.
Off Mode: The dynamic regulator option is dis­abled.
Secondary Supply Pump Mode
Same control features as primary pump.
94 3A5185B
Page 95
Pressure Trend Screen
Key:
AI Navigate to the Torque Trend
screen.
A
AI
Appendix A - User Interface Display
Overview
The Pressure Trend screen allows the user to view both inlet and outlet pressures in real time. The pressures displayed on this screen are the same values shown on the Home and Maintenance screens.
3A5185B 95
Page 96
Appendix A - User Interface Display
Key:
AJ Navigate to the Pressure Trend
screen.
A
AJ
Torque Trend Screen
Overview
The Torque Trend screen allows the user to view the pump torque and motor torque in real time.
Pump Torque
The Pump Torque shows the effective torque on the pump during operation.
Motor Torque
The Motor Torque shows the torque on the motor during operation and is measured in in/lbs.
96 3A5185B
Page 97
Appendix A - User Interface Display
A
Alarm Screen
Refer to Error Codes and Troubleshooting on page 32 for information on possible errors.
Acknowledge All List
When pressed, the Acknowledge All List button acknowledges all errors listed on the Alarm Screen and adds to the screen the time when the errors were acknowledged. This button must be pressed prior to pressing the Clear All Alarms button.
NOTE: Acknowledging alarms does not clear them.
Clear All Alarms
When pressed, the Clear All Alarms button will remove all errors listed on the Alarm Screen. Before pressing the Clear All Alarms button, all alarms must be acknowl­edged.
NOTE: The Clear All Alarms button can only be pressed if Error Reset is Enabled (see Configure Errors on page 21).
3A5185B 97
Page 98

Appendix B - I/O

Automation PGM Control
Input Circuit
24VDC
Relay Contact
Input
Pin 1 or 2
5
Appendix B - I/O

Using the PGM I/O

The gear meter uses several I/O signals to communicate with plant automation controllers. There are two digital inputs, three digital outputs, and one analog input. All of these signals are routed to the I/O connector on the top of the controller.
Other pins on the I/O connector include 24 VDC power, 24 VDC common, analog common, and a signal which is 24 VDC power only when the controller E-Stop switch is latched in. None of the signals are isolated; all are referenced to the ground plane of the control box. The following paragraphs describe typical connection methods for the auto­mation controller signals.
Digital Inputs
The two digital inputs are Dispense Start and Job Com­plete. These inputs require a 24 VDC current sourcing output from the automation controller. See F
IG. 41.
If the automation controller uses relay contacts to acti­vate I/O signals, the 24 VDC available at the gear meter I/O connector (pin 5) should be used to drive the inputs. If the automation controller uses high-side switching of 24 VDC, the automation outputs can be directly con­nected to the inputs as long as the 24 VDC common (pin 6) of the gear meter is able to be connected to the automation controller common. If the automation con­troller outputs are low-side switching (open collector) or a voltage other than 24 VDC, relays must be used as shown in F
IG. 41.
FIG. 41
98 3A5185B
Page 99
Digital Outputs
AutomationPGM Control
Output Circuit
Load (750 mA max)
Pins 10, 11, 12
DC Common
6
The three digital outputs are Dispenser Ready, Fault Present and In Cycle. These outputs perform high-side switching of 24 VDC and require a 24 VDC current sink­ing input at the automation controller. See F automation controller uses 24 VDC relay coils to receive I/O signals, the signals should be connected as shown in F
IG. 42.
If the automation controller inputs are current sourcing or use a voltage other than 24 VDC, relays with 24 VDC coils must be used as shown in F
IG. 42.
IG. 42. If the
Appendix B - I/O
IG. 42
F
3A5185B 99
Page 100
Appendix B - I/O
+24 VDC
E-Stop Switch
Pin 14
Analog Inputs
The PGM receives a flow rate analog command from the automation. The 0 to 10 VDC analog input is refer­enced to analog common on the control. See F The reference for the automation controller analog out­put must be connected to the PGM analog reference (pin 8) for this signal to function properly.
AutomationPGM Control
0 to 10 VDC
Pin 7
Pin 8
Analog Input
F
IG. 43
_
+
-
IG. 43.
Voltage
Relays
If the use of relays is required to condition the digital I/O signals, these are some examples of part numbers that could be used.
For 24 VDC Coils:
Relay: Phoenix Contact Part Number: 2966171
For 120 VAC Coils:
Relay: Phoenix Contact Part Number: 2966197
24 VDC From E-Stop
The PGM provides a signal that can be used by the automation controller to monitor the emergency stop switch position of the PGM controller. See F
F
IG. 44
IG. 44.
100 3A5185B
Loading...