See Product Configurator on page 5 for detailed product configuration information.
System
Full Load
Peak
Amps Per
Phase*
Voltage
(phase)Power DescriptionSystem Watts †
Maximum
Fluid Working
Pressure ‡
psi (MPa, bar)
200-240VAC, 1 phase, 50/60Hz,
55 A230V (1)
12, 650
2 wire and PE
HFR,
Non-Heated
29 A230V (3)
200-240VAC, 3 phase
wire and PE
Δ, 50/60Hz, 3
11,340
3000
(20.7, 207)
380-415VAC, 3 phase Y, 50/60Hz,
55 A 400V (3)
12,650
2 wire and PE
116 A230V (1)
200-240VAC, 3 phase
Δ, 50/60Hz, 3
26,680
wire and PE
HFR,
Heated
73 A230V (3)
200-240VAC, 3 phase
wire and PE
Δ, 50/60Hz, 3
28,600
3000
(20.7, 207)
380-415VAC, 3 phase Y, 50/60Hz,
63 A 400V (3)
28,600
2 wire and PE
*Full load amps with all devices operating at maximum ca pabilities. Fuse requirements at various flow rates and
mix chamber sizes may be less.
† 210 ft (64 m) maximum heated hose length, including whip hose.
approved.
‡ The maximum fluid working pressure for the base machine without hoses is 3000 psi (20.7 MPa, 207 bar). If
hoses rated at less than 3000 psi are installed, the system maximum fluid working pressure becomes the rating of
the hoses. If 2000 psi hoses were purchased an d insta lled by Gr aco , th e wor kin g pr es su re for th e ma ch in e is
already setup for the lower 2000 psi (13.8 MPa, 138 bar) working pressure by Graco. If the machine was pur
chased without hoses and aftermarket hoses rated at or above 3000 psi are to be installed, see instruction man
ual 313998 for the procedure to setup the machine for higher rated hoses. The change in working pressure is
made by changing a rotary switch setting in the Motor Cont rol Module. The minimum pressure rating for hoses is
2000 psi. Do not install hoses with a pressure rating lower than 2000 psi.
See 400 V Power Requirements.
400 V Power Requirements
•400 V systems are intended for International voltage
requirements. Not for voltage requirements in North
America.
•If a 400 volt configuration is operated in North Amer
ica, a special transformer rated for 400 V (“Y” con
figuration (4 wire)) may be required.
•North America mostly employs a 3 wire or Delta
configuration. The two configurations are not inter
changeable.
4313997ZAA
Page 5
Product Configurator
HFR-A------
Product Configurator
Ref.:12345 6
Configurator Revision
Base
Voltage
B (Blue) Pump
A (Red) Pump
Primary/Hose Heat
Hose Bundle Assembly
An example of the product configurator would be the following configurator code.
HFR- A - 1 - 6 - AM - AM - D - AG
Ref.:123456
Configurator Revision
Base
Voltage
B (Blue) Pump
A (Red) Pump
Primary/Hose Heat
High Volume/Low Volume
High Volume/Low Volume
The following part number fields apply for the HFR part numbering configurator fields.
Ref. 1Part Base Unit
1HFR Base Unit, Carbon Steel
2HFR Base Unit, Stainless Steel
Ref. 2Part Voltage
1230V, 1 phase;
No Heat
2230V, 1 phase;
Maximum of Two 6 kW Primary Heater and One
Zone of Hose Heat
3230V, 3 phase;
No Heat
4230V, 3 phase;
Maximum of Two 6 kW Primary Heaters and Two
Zones of Hose Heat
5400V, 3 phase;
No heat
6400V, 3 phase;
Maximum of Two 6 kW Primary Heaters and Two
Zones of Hose Heat
Ref. 3Part B (Blue) Pump †
AAL010S1 10 cc Stainless Steel
ABL015S1 15 cc Stainless Steel
ACL020S1 20 cc Stainless Steel
ADL025S1 25 cc Stainless Steel
AEL030S1 30 cc Stainless Steel
AFL040S1 40 cc Stainless Steel
AGL050S1 50 cc Stainless Steel
AHL060S1 60 cc Stainless Steel
AJL080S1 80 cc Stainless Steel
AKL100S1 100 cc Stainless Steel
ALL120S1 120 cc Stainless Steel
AML160S1 160 cc Stainless Steel
AQL005S1 5 cc Stainless Steel
ASL086S1 86 cc Stainless Steel
ARL065S1 65 cc Stainless Steel
AT
L035S1 35 cc Stainless Steel
AU
L045S1 45 cc Stainless Steel
AV
L105S1 105 cc Stainless Steel
Ref. 4Part A (Red) Pump †
Code, Part, and Description for Ref. 4 are the same as Ref. 3
313997ZAA5
Page 6
Product Configurator
Ref. 5Part Primary/Hose Heat
ANo Heat
BA (Red) and B (Blue) Primary Heaters
CA (Red) and B (Blue) Primary Heaters, One Zone
of Hose Heat
DA (Red) and B (Blue) Primary Heaters, A (Red)
EA (Red) and B (Blue) Hose Heat, Carbon Steel
FA (Red) and B (Blue) Hose Heat, Stainless Steel
GB (Blue) Primary Heaters, B (Blue) Hose Heat
24E953 Air Hose, 5 ft
15B280 Air Hose, 10 ft
15C624 Air Hose, 25 ft
15B295 Air Hose, 50 ft
313997ZAA9
Page 10
Product Configurator
24E900 Signal Cable, 5 pin, Male/Female, 2.0 meter
24E899 Signal Cable, 5 pin, Male/Female, 4.0 meter
24E898 Signal Cable, 5 pin, Male/Female, 8.5 meter
24E897 Signal Cable, 5 pin, Male/Female, 16.0 meter
24E896 Fluid Temperature Sensor Cable, 4 pin,
Male/Female, 2.0 meter
24E895 Fluid Temperature Sensor Cable, 4 pin,
Male/Female, 3.0 meter
24E894 Fluid Temperature Sensor Cable, 4 pin,
Male/Female, 8.0 meter
24E893 Fluid Temperature Sensor Cable, 4 pin,
Male/Female, 15.7 meter
24E954 Scuff Guard, 1.75 in. (44 mm), 200 ft (61 m) Roll
24E961 Scuff Guard, 1.75 in. (44 mm), 200 ft (61 m) Roll
261821 Wire Connector, 6AWG (4.11 mm)
24E955 Hose Lacing, 1500 ft (457.2 m) Roll
15B679 Hose Safety Label
Applicator
NOTE: When selecting an applicator, if an applicator is
chosen which does not have a signal communicating to
the HFR, then the sizes of the A and B pumps added
together must be greater or equal to 120 cc. For exam
ple: A (red) pump size = 20 cc, B (blue) pump size =
100 cc, 20 cc + 100 cc = 120 cc. Since the pump sizes
combined = 120 cc, an applicator may be selected
which does not have a signal communicating to the
HFR.
Part Description
24A084L-Head 6/10 With Calibration Orifice
24A085L-Head 10/14 With Calibration Orifice
24A086L-Head 13/20 With Calibration Orifice
24A090S-Head 6-625 With Calibration Orifice
24A092S-Head 6-500 L/S With Calibration Orifice
24A093S-Head 6-625 L/S With Calibration Orifice
24J187GX-16, 24:1, Straight, Machine Mount
24K233GX-16, 24:1, Left, Machine Mount
24K234GX-16, No Orifice, Left, Machine Mount
24E876GX-16, No Orifice, Straight, Machine Mount
24E877GX-16, 24:1, Right, Machine Mount
Electric
24D536Applicator, MD2, 10:1, Hard, Stainless Steel,
Lever
24D537Applicator, MD2, 10:1, Hard, Stainless Steel,
Pneumatic
24E505MD2 Orifice Adapter Kit
257999EP Pour Gun, Pistol Grip, 1/4 in. Purge Rod
24C932EP Pour Gun, Machine mount, 1/4 in. Purge Rod
24C933EP Pour Gun, Pistol Grip, 3/8 in. Purge Rod
24C934EP Pour Gun, Machine Mount, 3/8 in. Purge Rod
LC0058Mixer Kit, (10) 3/8 in. x 24 Element with Shroud
LC0059Mixer Kit, (10) 3/8 in. x 36 Element with Shroud
LC0060Mixer Kit, (10) 3/8 in. Combo with Shroud
LC0295Mixer Kit, (10) 1/2 in. x 24 Element with Shroud
LC0296Mixer Kit, (10) 1/2 in. x 36 Element with Shroud
LC0079Mixer Pack, (50) 3/8 in. x 24 Element
LC0080Mixer Pack, (50) 3/8 in. x 24 Element
LC0081Mixer Pack, (50) 3/8 in. Combo Element
LC0086Mixer Pack, (250) 3/8 in. x 24 Element
LC0087Mixer Pack, (250) 3/8 in. x 36 Element
LC0088Mixer Pack, (250) 3/8 in. Combo Element
B (Blue) Applicator Orifice
S-Head and L-Head
Description Part For Use With Applicator:
Calibrate24A036S-Head Only
0.2524A037S-Head Only
0.3524A038S-Head Only
0.5024A039S-Head Only
0.6024A040S-Head Only
0.7024A041S-Head Only
0.8024A042S-Head Only
0.9024A043S-Head Only
1.0024A044S-Head Only
1.1024A045S-Head Only
1.2024A046S-Head Only
1.3024A047S-Head Only
1.4024A050S-Head Only
1.5024A051S-Head Only
1.6024A052S-Head Only
1.7024A053S-Head Only
1.8024A054S-Head Only
1.9024A055S-Head Only
2.0024A056S-Head Only
2.5024A057S-Head Only
3.0024A058S-Head Only
3.5024A059S-Head Only
4.0024A060S-Head Only
4.2024A061S-Head Only
4.5024A062S-Head Only
5.0024A063S-Head Only
5.5024A064S-Head Only
6.0024A065S-Head Only
6.5024A066S-Head Only
7.0024A067S-Head Only
CalibrateM0934A-4L-Head Only
0.25247761L-Head Only
0.45247762L-Head Only
0.5247763L-Head Only
0.75247764L-Head Only
0.8247765L-Head Only
0.85247766L-Head Only
1247767L-Head Only
1.1247811L-Head Only
1.2247848L-Head Only
1.25248858L-Head Only
1.3247859L-Head Only
1.4247860L-Head Only
1.5247861L-Head Only
1.6247862L-Head Only
1.65247863L-Head Only
1.7247864L-Head Only
1.75247865L-Head Only
1.8247866L-Head Only
1.9247867L-Head Only
313997ZAA11
Page 12
Product Configurator
2247868L-Head Only
2.4247869L-Head Only
3.2247870L-Head Only
3.6247871L-Head Only
4.2247872L-Head Only
5247873L-Head Only
5.6247874L-Head Only
GX-16
DescriptionPart
2577010.011 in. Orifice
2577020.013 in. Orifice
2577030.016 in. Orifice
2577040.018 in. Orifice
2577050.020 in. Orifice
2577060.022 in. Orifice
2577070.023 in. Orifice
2577080.024 in. Orifice
2577090.025 in. Orifice
2577100.026 in. Orifice
2577110.028 in. Orifice
2577120.029 in. Orifice
2577130.032 in. Orifice
2577140.035 in. Orifice
2577150.036 in. Orifice
2577160.038 in. Orifice
2577170.039 in. Orifice
2577180.040 in. Orifice
2577190.042 in. Orifice
2577200.043 in. Orifice
2577210.044 in. Orifice
2577220.049 in. Orifice
2577230.052 in. Orifice
2577240.061 in. Orifice
24K6820.085 in. Orifice
™
Gun
EP
DescriptionPart For Use With Applicator:
Orifice Kit24E250EP 250, 6 Blue, 6 Red
0.51 mm Poly
Orifice
0.79 mm Poly
Orifice
1.19 mm Poly
Orifice
1.52 mm Poly
Orifice
1.70mm Poly
Orifice
2.18 mm Poly
Orifice
0.41 mm Poly
Orifice
0.61 mm Poly
Orifice
24C751EP 250 Poly Side Orifice, Std
24C752EP 250 Poly Side Orifice, Std
24C753EP 250 Poly Side Orifice, Std
24C754EP 250 Poly Side Orifice, Std
24C755EP 250 Poly Side Orifice, Std
24C756EP 250 Poly Side Orifice, Std
24C805EP 250 Poly Side Orifice
24C806EP 250 Poly Side Orifice
0.71 mm Poly
Orifice
0.89 mm Poly
Orifice
0.99 mm Poly
Orifice
1.07 mm Poly
Orifice
1.32 mm Poly
Orifice
1.40 mm Poly
Orifice
1.60 mm Poly
Orifice
1.85 mm Poly
Orifice
Orifice Kit24E251EP 375, 6 Blue, 6 Red
0.51 mm Poly
Orifice
0.79 mm Poly
Orifice
1.19 mm Poly
Orifice
1.52 mm Poly
Orifice
1.70 mm Poly
Orifice
2.18 mm Poly
Orifice
0.41 mm Poly
Orifice
0.61 mm Poly
Orifice
0.71 mm Poly
Orifice
0.89 mm Poly
Orifice
0.99 mm Poly
Orifice
1.07 mm Poly
Orifice
1.32 mm Poly
Orifice
1.40 mm Poly
Orifice
1.60 mm Poly
Orifice
1.85 mm Poly
Orifice
24C807EP 250 Poly Side Orifice
24C808EP 250 Poly Side Orifice
24C809EP 250 Poly Side Orifice
24C810EP 250 Poly Side Orifice
24C811EP 250 Poly Side Orifice
24C812EP 250 Poly Side Orifice
24C813EP 250 Poly Side Orifice
24C815EP 250 Poly Side Orifice
24C761EP 375 Poly Side Orifice, Std
24C762EP 375 Poly Side Orifice, Std
24C763EP 375 Poly Side Orifice, Std
24C764EP 375 Poly Side Orifice, Std
24C765EP 375 Poly Side Orifice, Std
24C766EP 375 Poly Side Orifice, Std
24C794EP 375 Poly Side Orifice
24C795EP 375 Poly Side Orifice
24C796EP 375 Poly Side Orifice
24C797EP 375 Poly Side Orifice
24C798EP 375 Poly Side Orifice
24C799EP 375 Poly Side Orifice
24C800EP 375 Poly Side Orifice
24C801EP 375 Poly Side Orifice
24C802EP 375 Poly Side Orifice
24C804EP 375 Poly Side Orifice
12313997ZAA
Page 13
Product Configurator
Iso A (Red) Applicator Orifice
S-Head and L-Head
The A (Red) applicator orifices for the S-Head and
L-Head are the same as the B (Blue) applicator orifices.
See page 11.
GX-16
DescriptionPart
2577010.011 in. Orifice
2577020.013 in. Orifice
2577030.016 in. Orifice
2577040.018 in. Orifice
2577050.020 in. Orifice
2577060.022 in. Orifice
2577070.023 in. Orifice
2577080.024 in. Orifice
2577090.025 in. Orifice
2577100.026 in. Orifice
2577110.028 in. Orifice
2577120.029 in. Orifice
2577130.032 in. Orifice
2577140.035 in. Orifice
2577150.036 in. Orifice
2577160.038 in. Orifice
2577170.039 in. Orifice
2577180.040 in. Orifice
2577190.042 in. Orifice
2577200.043 in. Orifice
2577210.044 in. Orifice
2577220.049 in. Orifice
2577230.052 in. Orifice
2577240.061 in. Orifice
24K6820.085 in. Orifice
EP Gun
DescriptionPart For Use With Applicator:
0.51 mm Iso
Orifice
0.79 mm Iso
Orifice
1.19 mm Iso
Orifice
1.52 mm Iso
Orifice
1.70mm Iso
Orifice
2.18 mm Iso
Orifice
0.41 mm Iso
Orifice
0.61 mm Iso
Orifice
24D223EP 250 Iso Side Orifice, Std
24D224EP 250 Iso Side Orifice, Std
24D225EP 250 Iso Side Orifice, Std
24D226EP 250 Iso Side Orifice, Std
24D227EP 250 Iso Side Orifice, Std
24D228EP 250 Iso Side Orifice, Std
24D229EP 250 Iso Side Orifice
24D230EP 250 Iso Side Orifice
0.71 mm Iso
Orifice
0.89 mm Iso
Orifice
0.99 mm Iso
Orifice
1.07 mm Iso
Orifice
1.32 mm Iso
Orifice
1.40 mm Iso
Orifice
1.60 mm Iso
Orifice
1.85 mm Iso
Orifice
0.51 mm Iso
Orifice
0.79 mm Iso
Orifice
1.19 mm Iso
Orifice
1.52 mm Iso
Orifice
1.70 mm Iso
Orifice
2.18 mm Iso
Orifice
0.41 mm Iso
Orifice
0.61 mm Iso
Orifice
0.71 mm Iso
Orifice
0.89 mm Iso
Orifice
0.99 mm Iso
Orifice
1.07 mm Iso
Orifice
1.32 mm Iso
Orifice
1.40 mm Iso
Orifice
1.60 mm Iso
Orifice
1.85 mm Iso
Orifice
24D231EP 250 Iso Side Orifice
24D232EP 250 Iso Side Orifice
24D233EP 250 Iso Side Orifice
24D234EP 250 Iso Side Orifice
24D235EP 250 Iso Side Orifice
24D236EP 250 Iso Side Orifice
24D237EP 250 Iso Side Orifice
24D238EP 250 Iso Side Orifice
24D239EP 375 Iso Side Orifice, Std
24D240EP 375 Iso Side Orifice, Std
24D241EP 375 Iso Side Orifice, Std
24D242EP 375 Iso Side Orifice, Std
24D243EP 375 Iso Side Orifice, Std
24D244EP 375 Iso Side Orifice, Std
24D245EP 375 Iso Side Orifice
24D246EP 375 Iso Side Orifice
24D247EP 375 Iso Side Orifice
24D248EP 375 Iso Side Orifice
24D249EP 375 Iso Side Orifice
24D250EP 375 Iso Side Orifice
24D251EP 375 Iso Side Orifice
24D252EP 375 Iso Side Orifice
24D253EP 375 Iso Side Orifice
24D254EP 375 Iso Side Orifice
313997ZAA13
Page 14
Product Configurator
AC Power Pack with
S-Head/L-Head Hoses, Optional
Boom
Part Description
24D829 230V, Boom, L-Head Hoses
24D830 230V, Boom, S-Head Hoses
24D834 400V, Boom, L-Head Hoses
24D835 400V, Boom, S-Head Hoses
24D831 230V, L-Head Hoses, No Boom
24D832 230V, S-Head Hoses, No Boom
24D836 400V, L-Head Hoses, No Boom
24D837 400V, S-Head Hoses, No Boom
24F297 230V, L-Head Application, No Boom, No Hoses
24J912 230V, S-Head Application, No Boom, No Hoses
24F298 400V, L-Head Application, No Boom, No Hoses
24J913 230V, S-Head Application, No Boom, No Hoses
257798 Power Pack GX-16 Connection Kit
24E347 Hydraulic Power Pack Level Sensor Kit
24C872 Hydraulic Power Pack Pressure Gauge Kit
24E348 Hydraulic Power Pack Temperature Sensor
124217 Power Pack Accumulator Charging kit
Flow Meters
Flow Meter Electronics (Necessary)
Part Description
24J318 Flow Meter Electronics Kit
“A” and “B” Side Flow Meter (One for each side)
Part Description
24J319 S3000 Flow Meter Kit
(0.01 to 0.53 gpm, 50 to 2000 cc per min)
(1 to 1000 cps)
24J320 G3000 Flow Meter Kit
(0.02 to 1.0 gpm, 75 to 3800 cc per min)
(20 to 3000 cps)
24J321 G3000HR Flow Meter Kit
(0.01 to 0.5 gpm, 38 to 1900 cc per min)
(20 to 3000 cps)
24J322 HG6000 Flow Meter Kit
(0.013 to 6.0 gpm, 50 to 22,700 cc per min)
(30 to 1,000,000 cps)
24J323 HG6000HR Flow Meter Kit
(0.007 to 2.0 gpm, 25 to 7571 cc per min)
(30 to 1,000,000,cps)
Dispense Valve Interface Kit
Part Description
24C757 MD2 Valve Solenoid, Machine Mount
24D160 MD2 Valve Solenoid, Remote Mount
24D161 Auto-Fusion Solenoid for Fusion Dispense Valve
24C067 Fusion Gun Pressure Adjust Kit
Flow Meter Calibration Kit (per applicator)
Part Description
24J324 L-Head Flow Meter Calibration Kit
24J325 S-Head Flow Meter Calibration Kit
24J326 P2 Flow Meter Calibration Kit
24J357 GX-16 Flow Meter Calibration Kit
24F227 EP/Fusion Flow Meter Calibration Kit
255247 MD2 1:1 Flow Meter Calibration Kit
255245 MD2 10:1 Flow Meter Calibration Kit
257757 Insulator Blanket for 38L Tank
257758 Insulator Blanket for 75L Tank
257770 Refill Kit For Customer Supplied Feed System
257778 Nitrogen Kit For 1 Tank
257779 Nitrogen Kit For 2 Tanks
257916 Vacuum Pump Kit, 6.9 cfm, 1st, 230V, 1 phase
24D271 3rd Level Sensor Prox Switch Option
LC0097 Desiccant Dryer, 3/8 in. Npt With Adapter And
24C871 Hydraulic Power Pack Hydraulic Tank Fluid Level
Sensor
24C873 Hydraulic Power Pack Manifold Oil Temperature
Sensor
24P090 Mobile Pallet Base with Casters
24F516 IsoGuard Select fluid, 6 quarts
121728 Extension Cable for Advanced Display Module,
4meter,
255244 Foot Switch with Guard and 4 meter Cable
24F227 EP and Fusion Gun Ratio Check
24F235 25 ft hose extensions for L-Head applicator;
material, hydraulic, and signal cables
24F236 50 ft hose extensions for L-Head applicator;
material, hydraulic, and signal cables
24F237 25 ft hose extensions for S-Head applicator;
material, hydraulic, and signal cable
24F238 50 ft hose extensions for S-Head applicator;
material, hydraulic, and signal cable
24K206 Nip Sensor Kit
24H019 Air Inlet Filter for Hydraulic Power Pack
255468 Light Tower Kit
Discrete Gateway Module (DGM)
The HFR Discrete Gateway Module allows the user to
control an HFR through multiple external control devices
such as contact blocks or relays. The DGM operates in
conjunction with the existing Advanced Display Module
(ADM) such that both devices can be used to control the
machine. See HFR Communication Gateway Module
manual for more information
Part Description
24F843 Single DGM Cube with Board
24F844 Two DGM Cubes with Board
24G830 Single DGM Cube
Communications Gateway Module (CGM)
The HFR Communication Gateway Module allows the
user to control an HFR through an external control
device such as a PLC. The CGM operates in conjunc
tion with the existing Advanced Display Module (ADM)
such that both devices can be used to control the
machine. See HFR Communication Gateway Module
manual for more information
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama
tion point symbol alerts you to a general warning and the ha zard symbol refe rs to procedure-sp ecific risk. Refer back
to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where
applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause elec
tric shock.
•Turn off and disconnect power at main switch before disconnecting any cables and before servicing
equipment.
•Connect only to grounded power source.
•All electrical wiring must be done by a qualified electrician and comply with all local codes and reg
ulations.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or
swallowed.
•Read MSDSs to know the specific hazards of the fluids you are using.
•Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
•Always wear chemically impermeable gloves when spraying, dispensing, or cleaning equipment.
PERSONAL PROTECTIVE EQUIPMENT
You must wear appropriate protective equipment when operating, servicing, or when in the operating
area of the equipment to help protect you from serious injury, including eye injury, hearing loss, inhala
tion of toxic fumes, and burns. This equipment includes but is not limited to:
•Protective eyewear, and hearing protection.
•Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufac
turer.
SKIN INJECTION HAZARD
High-pressure fluid from dispensing device, hose leaks, or ruptured components will pierce skin. This
may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical
treatment.
•Do not point dispensing device at anyone or at any part of the body.
+
•Do not put your hand over the fluid outlet.
•Do not stop or deflect leaks with your hand, body, glove, or rag.
•Follow the Pressure Relief Procedure when you stop dispensing and before cleaning, checking,
or servicing equipment.
•Tighten all fluid connections before operating the equipment.
•Check hoses and couplings daily. Replace worn or damaged parts immediately.
18313997ZAA
Page 19
Warnings
WARNING
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To he lp pre
vent fire and explosion:
•Use equipment only in well ventilated area.
•Eliminate all ignition sources; such as pilot ligh ts, cigaret te s , po rt ab le ele ct ric lam p s, and pla s tic
drop cloths (potential static arc).
•Keep work area free of debris, including solvent, rags and gasoline.
•Do not plug or unplug power cords, or turn power or light switches on or off when fla mmable fu mes
are present.
•Ground all equipment in the work area. See Grounding instructions.
•Use only ground ed ho se s.
•Hold gun firmly to side of grounded pail when triggering into pail.
•If there is static sparking or you feel a shock, stop operation immediately. Do not use equipment
until you identify and correct the problem.
•Keep a working fire extinguisher in the work area.
PRESSURIZED EQUIPMENT HAZARD
Fluid from the gun/dispense valve, leaks, or ruptured comp onents can splash in the eyes or on skin and
cause serious injury.
•Follow the Pressure Relief Procedure when you stop spraying and before cleaning, checking, or
servicing equipment.
•Tighten all fluid connections before operating the equipment.
•Check hoses, tubes, and couplings daily. Replace worn or damaged parts immediately.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
•Do not operate the unit when fatigued or under the influence of drugs or alcohol.
•Do not exceed the maximum working pressure or temperature rating of the lowest rated system
component. See Technical Data in all equipment manuals.
•Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all
equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information
about your material, request MSDS from distributor or retailer.
•Do not leave the work area while equipment is energized or under pressu re . Turn off all e qui pme nt
and follow the Pressure Relief Procedure when equipment is not in use.
•Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manu
facturer’s replacement parts only.
•Do not alter or modify equipment.
•Use equipment only for its intended purpose. Call your distributor for information.
•Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
•Do not kink or over bend hoses or use hoses to pull equipment.
•Keep children and animals away from work area.
•Comply with all applicable safety regulations.
313997ZAA19
Page 20
Important Two-Component Material Information
WARNING
MOVING PARTS HAZARD
Moving parts can pinch, cut or amputate fingers and other body parts.
•Keep clear of moving parts.
•Do not operate equipment with protective guards or covers removed.
•Pressurized equipment can start without warning. Before checking, moving, or servicing equip
ment, follow the Pressure Relief Procedure and disconnect all power sources.
BURN HAZARD
Equipment surfaces and fluid that’s heated can become very hot during ope ration. To avoid severe
burns:
•Do not touch hot fluid or equipment.
Important Two-Component Material Information
Isocyanate Conditions
Spraying or dispensing materials containing isocya
nates creates potentially harmful mists, vapors, and
atomized particulates.
Read material manufacturer’s warnings and m ate r ial
MSDS to know specific hazards and precautions
related to isocyanates.
Prevent inhalation of isocyanate mists, vapors, and
atomized particulates by providing sufficient ventila
tion in the work area. If sufficient ventilation is not
available, a supplied-air respirator is required for
everyone in the work area.
To prevent contact with isocyanates, appropriate per
sonal protective equipment, including chemically
impermeable gloves, boots, aprons, and goggles, is
also required for everyone in the work area.
Material Self-ignition
Keep Components A (Red) and
B(Blue) Separate
Cross-contamination can result in cured material in
fluid lines which could cause serious injury or dam
age equipment. To prevent cross-contamination of
the equipment’s wetted parts, never interchange
component A (Red) and component B (Blue) parts.
Some materials may become self-igniting if applied
too thickly. Read material manufacturer’s warnings
and material MSDS.
20313997ZAA
Page 21
A (Red) and B (Blue) Components
Moisture Sensitivity of
Isocyanates
Isocyanates (ISO) are catalysts used in two component
foam and polyurea coatings. ISO will react with moisture
(such as humidity) to form small, hard, abrasive crystals,
which become suspended in the fluid. Eventually a film
will form on the surface and the ISO will begin to gel,
increasing in viscosity. If used, this partially cured ISO
will reduce performance and the life of all wetted parts.
NOTE: The amount of film formation and rate of crystal
lization varies depending on the blend of ISO, the
humidity, and the temperature.
To prevent exposing ISO to moisture:
•Always use a sealed container with a desiccant
dryer in the vent, or a nitrogen atmosphere. Never
store ISO in an open container.
•Keep the ISO lube pump reservoir (if installed) filled
with IsoGuard Select, part 24F516. The lubricant
creates a barrier between the ISO and the atmo
sphere.
•Use moisture-proof hoses specifically designed for
ISO, such as those supplied with your system.
•Never use reclaimed solvents, which may contain
moisture. Always keep solvent containers closed
when not in use.
•Never use solvent on one side if it has been con
taminated from the other side.
•Always lubricate threaded parts with ISO pump oil
or grease when reassembling.
Foam Resins with 245 fa
Blowing Agents
Some foam blowing agents will froth at temperatures
above 90°F (33°C) when not under pressure, especially
if agitated. To reduce frothing, minimize preheating in a
circulation system.
Changing Materials
•When changing materials, flush the equipment mul
tiple times to ensure it is thoroughly clean.
•Always clean the fluid inlet strainers after flushing.
•Check with your material manufacturer for chemical
compatibility.
•Most materials use ISO on the A (Red) side, but
some use ISO on the B (Blue) side. See the follow
ing section.
A (Red) and B (Blue) Components
IMPORTANT!
Material suppliers can vary in how they refer to plural
component materials.
Be aware that when standing in front of the manifold on
proportioner:
•Component A (Red) is on the left side.
•Component B (Blue) is on the right side.
For all machines:
•The A (Red) side is intended for ISO, hardeners,
and catalysts.
•If one of the materials being used is moisture-sensi
tive, that material should always be in the A (Red)
side.
•The B (Blue) side is intended for polyols, resins, and
bases.
NOTE: For machines with material volume ratios other
than 1:1, the higher volume side is typically the B (Blue)
side.
313997ZAA21
Page 22
A (Red) and B (Blue) Components
22313997ZAA
Page 23
Typical Installation
B
C*
D
E
F
K
J
ti7821a3
* Shown exposed for clarity.
Wrap with tape during operation.
J
A
K
P
N
H
L
G
K
B (Blue) Side Supply Detail
G
K
M
A (Red) Side Supply Detail
ti7821a2
ti14720a
P
H
Typical Installation
FIG. 1
Key:
AHFR Unit (see FIG. 2, page 25)
BHose
CFluid Temperature Sensor (FTS); 2x, 1 for each hose
DWhip Hose
EDispense Gun
FGun Air Supply Hose
GFeed Pump Air Supply Lines
HWaste Container
JFluid Supply Lines
AA Advanced Display Module (see page 30)
BA Component A (Red) Pressure Relief Outlet
BB Component B (Blue) Pressure Relief Outlet
CO Base and Casters (Optional)
FA Component A (Red) Fluid Manifold Inlet (on left side of
manifold block)
FB Component B (Blue) Fluid Manifold Inlet
FM HFR Fluid Manifold
FP Feed In let Pressure Gauge
FS Feed Inlet Strai ner (standard filter size is 20 mesh)
FT Feed Inlet Temperature Gauge (heated models only)
FV Feed Inlet Valve (A (Red) side shown)
GA Component A (Red) Outlet Pressure Gauge
GB Component B (Blue) Outlet Pressure Gauge
HA Component A (Red) Hose Connection (from feed to gun
or mix head)
HB Component B (Blue) Hose Connection (from feed to gun
or mix head)
HP Hydraulic Power Pack Assembly
HT Hydraulic Tank
LR IsoGuard Se lect Fluid Reservoir
LS Pumpline Linear Sensor
MA Motor Control Module, see page 28
MP Main Power Switch
PA Component A (Red) Pump
PB Component B (Blue) Pump
PD Power Distribution Box
PH Primary Heater
PI Primary Heater Fluid Inlet
PO Primary Heater Fluid Outlet
PR Primary Heater RTD
PS Primary Heater Overtemperature Switch
SA Component A (Red) PRESSURE RELIEF/DISPENSE
Valve
SB Component B (Blue) PRESSURE RELIEF/DISPENSE
Valve
TA Component A (Red) Pressure Transducer
TB Component B (Blue) Pressure Transducer
TC High Power Temperature Control Module (not shown, see
page 34)
24313997ZAA
Page 25
Component Identification
ti9880a1
GA
GB
SB
FB
BB
HB
HA
BA
FA
SA
Fluid Manifold (FM) Detail
LR
PA
PB
FV
FT
FP
FS
AA
HP
FM
PD
HT
MA
FS
FP
FT
MP
PH
TA
TB
LS
PI
PO
PR
PS
Rear View
Primary Heater (PH) Detail,
B (Blue) side shown
24C352_313998_3g
24C327_313998_1e
24C352_313998_4e
CO
FIG. 2: Component Identification, Heated Model shown with shrouds removed
313997ZAA25
Page 26
Component Identification
CB1
CB5
CB4
CB2CB3
CB9
CB7
CB6
CB8
24C681_313998_1e
CB579
CB718
B (Blue)
Left Side from Rear View
A (Red)
Right Side from Rear View
24C332_313998_3f
24C332_313998_6f
Main Power Switch
Located on top of the power distribution box, see
25. The main power switch turns power
page
ON and OFF. The main power switch
does not turn pumps or heat zones on.
Circuit Breakers
Most circuit breakers are located inside the power distri
bution box. The main block of circuit breakers in the
power distribution box is shown below, with detailed
information in the following table. For more information
about items in the power distribution box, see power d is
tribution box manual for more information.
Additional circuit breakers for protection of the second
ary side of the heated hose transformer are loc ate d
inside the frame. See the parts list for the installed pri
mary/hose heat option. See Ref. 5 of the product config
urator code for your machine to determine which
primary/hose heat option is installed. See Product Con
figurator on page 5.
Size
230V/
1 phase,
Ref.
400V/
3 phase
230V/
3 phase
Component
CB163A30AMotor Control Module
CB240A40APrimary Heater A
CB315A15ATank Heat A
CB440A40AHose Heat A
CB55A5AMiscellaneous
CB65A5AMiscellaneous
CB740A40AHose Heat B
CB815A15ATank Heat B
CB940A40APrimary Heater B
26313997ZAA
Page 27
Hydraulic Power Pack
DA
DG
DE
DD
DH
DB
DF
24C352_313998_2g
DK
Component Identification
FIG. 3
Key:
DA 8 Gallon Hydraulic Oil Reservoir (see Tech nical Data on
page 108 for specifications)
DB Electric Motor
DC Dipstick (not shown, located at rear left of hydraulic tank)
DD Hydraulic Housing
DE Directional Valve
DF Motor Control Module (see page 28)
DG Fan
DH Oil Filter
DJ Shroud (not shown, removed for clarity)
DK Air Inlet Filter
313997ZAA27
Page 28
Component Identification
A
r_257396_3b9905_01b
r_257396_3b9905_03b
C
12
B
13
1A
11
1B
5
7
6
8
9
10
2
3
Motor Control Module (MCM)
NOTICE
If the Motor Control Module is replaced, the selec
tor switch must be set prior to initial startup of the
Motor Control Module or damage may occur. See
HFR Repair manual for details, see Related Manuals on page 3.
For MCM location, see reference MA in FIG. 2 on
page 25. When installed, the end of the MCM with the
power input connection (12) faces down and the end
with the access cover (A) faces up.
The Motor Control Module uses an 8-position selector
switch to set the system maximum workin g pre ssu re .
FIG. 4: MCM Component Identification
28313997ZAA
Page 29
RefDescription
AAccess Cover
BLEDs
CWarning Label
1A, 1BCAN Connections
2Three-way Splitter to: Oil Low Level
Sensor, Dispense Valve Solenoid, and
Footswitch
3Oil Temperature Sensor
5Electric Motor Temperature Sensor
6LVDT
7Three-way Splitter to:
Hydraulic Directional Valve,
Oil Overtemperature Switch
8Pressure Transducer B (Blue) side
9Pressure Transducer A (Red) side
10Not used
11Motor Position Sensor
12MCM Power Input Connection
13Motor Power Connection
Component Identification
313997ZAA29
Page 30
Component Identification
TI12362a1
CA
CB
CC
CE
CH
CG
CF
CD
Advanced Display Module (ADM)
User Interface
FIG. 5: ADM Component Identification - Front
Buttons
Ref. ButtonFunction
CASystem
enable/
disable
CBSystem
Status
Indicator
Light
CCStopStops all system processes.
Enables/disables system. When sys
tem is disabled, temperature control
and dispense operation are disabled.
Displays system status. See System Status Indicator (CB) Conditions on
page 31 for details.
Ref. ButtonFunction
CDSoft
Defined by application using ADM.
Keys
CECancelCancel a selection or number entry
while in the process of entering a
number or making a selection.
CFEnterAcknowledge changing a value or
making a selection.
CGLock/SetupToggle between run and setup
screens. If setup screens are pass
word protected, button toggles
between run and password entry
screen.
CHNaviga
tion
Navigate within a screen or to a new
screen.
30313997ZAA
Page 31
Component Identification
CR
CK
CJ
CL
CP
CN
CM
CS
r_24E451_3B9900_1a
IG. 6: ADM Component Identification - Rear
F
Key:
CJ Flat Panel Mount
CK Model Number
CL USB Module Interface
CM CAN Cable Connections
System Status Indicator (CB) Conditions
Green Solid - Run Mode, System On
Green Flashing - Setup Mode, System On
Yellow Solid - Run Mode, System Off
Yellow Flashing - Setup Mode, System Off
The following figure calls out the navigational, status, and general infor mational components of each screen. For
details regarding the user interface display see Advanced Display Module (ADM) Operation, page 46.
F
IG. 7: Main Display Components
32313997ZAA
Page 33
Fluid Control Module (FCM)
ti12337a1
ti12336a1
A
E
B
C
D
F
Component Identification
FIG. 8:
Key:
AFluid Control Module
BBase
CModule Connection Screws
DAccess Cover
EModule Status LEDs
FCAN Connectors
313997ZAA33
Page 34
Component Identification
1
2
3
5
4
6
LED
Signals
7
ti12352a1
ti12353a1
1
2
3
4
5
6
7
ti12356a1
ti12357a1
Temperature Control Module (Heated HFR Only)
FIG. 9: High Power Temperature Control Module Sensor Connections
4DC Output Connection
5Input Power Connection
6CAN Connections
7Base
34313997ZAA
Page 35
Heat Control Zone Selection
Hose Heater B (Blue)Primary Heater B (Blue)
Hose Heater A (Red)
Primary Heater A (Red)
Right Side from
Rear View
Left Side from
Rear View
24C332_313998_3f
24C332_313998_6f
(Heated models only)
The HFR unit supports 4 independent temperature con
trol zones. The high power temperature control modules
are located inside the frame below the hydraulic power
pack.
Component Identification
313997ZAA35
Page 36
Component Identification
High Power Module Rotary Switch Location
Low Power Module Rotary Switch Location
S
S
ti12360a
ti12361a
Adjust Rotary Switch
The rotary switch setting indicates which zone the tem
perature control module will control in the system. The
high power module uses an 8-position rotary switch.
The low power module uses a16-position rotary switch.
Set the rotary switch (S) to the specific selection accord
ing to the settings listed in the following tables.
High Power Module Rotary Switch Settings
SettingZone
0Not Used
1B (Blue) Primary Heat
2B (Blue) Hose Heat
3A (Red) Primary Heat
4A (Red) Hose Heat
5Not Used
6Not Used
7Not Used
Low Power Module Rotary Switch Settings
SettingZone
0Not Used
1Not Used
2Not Used
3Not Used
4Not Used
5B (Blue) Tank Heater
6A (Red) Tank Heater
7B (Blue) Chiller
8A (Red) Chiller
9Not Used
ANot Used
BNot Used
CNot Used
DNot Used
ENot Used
FNot Used
IG. 11
F
36313997ZAA
Page 37
Dispense Valves Overview
Three types of dispense valves can be used with the
HFR system:
•Stall-at-pressure
•Solenoid controlled
•Hydraulically actuated and recirculating
The P2 Gun and Fusion Gun are examples of
stall-at-pressure dispense valves. When not dispensing,
the fluid in the chemical lines are fully pressurized.
When using a stall-to-pressure dispense valve, a
footswitch cannot be used. Any signals sent from a
footswitch will be ignored.
The EP Gun and MD2 Valve are examples of solenoid
controlled dispense valves. When the trigger is pulled
the signal requests the dispense to start. When the
machine sees the signal, fluid rises to dispensing pres
sure and the valve is opened to begin dispensing. When
the trigger is released, the solenoid signals that the dis
pense is finished.
Dispense Valves Overview
The L-Head, S-Head, and GX-16 are examples of
hydraulically actuated, recirculating dispense valves.
When not dispensing, material is recirculated to main
tain temperature and pressure. Opening and closing the
valve is controlled hydraulically which leads to faster
actuation and more accurate dispenses.
313997ZAA37
Page 38
Setup
Setup
Perform this setup procedure to secure all necessary
machine connections for machine operation.
1. Locate HFR.
a. Locate HFR on a level surface. See Dimen
sions on page 110 for space requirements.
b. Anchor the HFR to the floor (suggested
anchors: McMaster Carr anchor, 92403A400).
See Dimensions, page 110, for bolt locations.
If machine mobility is required, purchase Mobile
Pallet Base with Casters Kit, 24P090.
NOTICE
To avoid tipping the machine and personal injury, do
not attach wheels directly to the standard HFR
mounting brackets.
c.Do not expose HFR to rain.
NOTICE
Bolt HFR to original shipping pallet before lifting.
2. Electrical requirements. See Models on page 4
for detailed electrical requirements information.
3. Connect electrical cord.
NOTE: See Power Line Voltage Surges informati on on
page 39.
NOTE: Power cord is not supplied. See the following
table.
Table 1: Power Cord Requirements
Cord Requirements
2
Model
Non-Heated HFR,
230V, 1 phase
Non-Heated HFR,
230V, 3 phase
Non-Heated HFR,
400V, 3 phase
Heated HFR,
230V, 1 phase
Heated HFR,
230V, 3 phase
Heated HFR,
400V, 3 phase
AWG (mm
6 (13.3), 2 wire + ground
8 (8.4), 3 wire + ground
6 (13.3), 4 wire + ground †
1 (42.4), 2 wire + ground
4 (21.2), 3 wire + ground
4 (21.2), 4 wire + ground †
)
† Residual Current Device (RCD) must be rated at
300 mA if installed.
Installing this equipment requires access to parts
which may cause electric shock or other serious injury
if work is not performed properly. Have a qualified
electrician connect power and ground to main power
switch terminals, see step 3 in this setup procedure.
All electrical wiring must be done by a qualified electri
cian and comply with all local codes and regulations.
NOTICE
Never connect to 480V, 3 phase power. Severe
equipment damage will occur.
38313997ZAA
Electrical Cord Wires by Model
230V, 1 phase: L1, L2, GND
230V, 3 phase: L1, L2, L3, GND
400V, 3 phase: L1, L2, L3, N, GND
* Constructed from ITIC 1996 curve, referenced by IEC 61000-2-4
1200Vac, 1697Vdc
264Vac, 373Vdc
336Vac, 475Vdc
288Vac, 407Vdc
480Vac, 679Vdc
<--1 MW Max Surge Power
<--150 KW Max Surge Power
<--50 KW Max Surge Power
<--No Power Limit
0
200
400
600
800
1000
1200
1400
Time (seconds)
Voltage (Volts RMS)
0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10
Use 5/32 or 4 mm hex allen wrench to connect the two
or three power leads to L1, L2, and L3, as applicable.
Connect green to ground (GND).
IG. 12: 400V, 3 phase shown
F
Power Line Voltage Surges
Power conversion equipment can be sensitive to voltage
fluctuations on incoming power. The Motor Control Mod
ule falls under the category of power conversion equip
ment because energy is stored on a capacitive bus and
then modulated to control a brushless motor. Engi
neered design takes this into account and withstands a
wide range of conditions, but it is possible for supplied
power to occasionally fall outside the tolerable range in
industrial plants with high-amperage reactive pulsed
loads such as welding equipment. If the tolerable range
is exceeded, an overvoltage condition is flagged and the
system will shut down in an alarm state to protect itself
and alert the user of unstable power. Excessive or
repeated overvoltage may permanently damage hard
ware.
c.Press “Min Max” successively to show the peak
positive and negative DC voltages.
d. Confirm readings do not exceed 400VDC
(Motor Control Module alarm issued at
420VDC).
The chart below shows the permissible magnitude and
duration of temporary over-voltage events:
The MAX-HOLD feature on a multimeter can be used to
determine peak DC voltage on the line. DC is the proper
setting, as opposed to AC, because peak voltage is the
critical parameter that affects the DC voltage level
stored on the capacitive bus in power conversion equip
ment. Reading should not regularly exceed approxi
mately 400VDC to avoid tripping the 420VDC alarm
level in the Motor Control Module. If power quality is
suspect, power conditioning or isolation of the device(s)
causing poor power quality is recommended. Consult a
qualified electrician if there are any concerns about the
available power supply.
Power Line Test Steps with Multimeter
a. Set multimeter to “DC voltage”.
b. Connect multimeter probes to supplied power
line.
313997ZAA39
Page 40
Setup
FP
ti10006a1
ti9883a1
FV
ti9880a1
BA
BB
R
R
SB
SA
4. Connect feed lines
a. Install feed pumps (K) in component A (Red)
and B (Blue) supply drums. See F
2, pages 23 and 25.
NOTE: A minimum feed pressure of 50 psi (0.35 MPa,
3.5 bar) is required at both feed inlet pressure gauges
(FP). Maximum feed pressure is 250 psi (1.75 MPa,
17.5 bar). Maintain A (Red) and B (Blue) feed pressures
within 10% of each other.
b. Seal component A (Red) drum and use desic
cant dryer (M) in vent.
c.Install agitator (L) in component B (Blue) drum,
if necessary.
IG. 1 and FIG.
5. Connect pressure relief lines
Do not install shutoffs downstream of the PRESSURE
RELIEF/DISPENSE valve outlets (BA, BB). The
valves function as overpressure relief valves when set
to DISPENSE . Lines must be open so valves
can automatically relieve pressure when machine is
operating.
If circulating fluid back to the supply drums, use high
pressure hose rated to withstand the maximum work
ing pressure of this equipment.
a. Recommended: Connect high pressure hose
(R) to relief fittings (BA, BB) of both PRES
SURE RELIEF/DISPENSE valves. Route hose
back to component A (Red) and B (Blue) drums.
IG. 1, page 23.
See F
d. Ensure A (Red) and B (Blue) inlet valves (FV)
are closed.
NOTE:
Supply hoses from feed pumps should be 3/4 in.
(19 mm) ID minimum.
e. Connect and tighten component B (Blue) supply
hose to the 3/4 npt(f) swivel on the component
B (Blue) inlet valve.
f.Connect and tighten component A (Red) supply
hose to the 1/2 npt(f) swivel on the component
A (Red) inlet valve.
b. Alternately: Secure supplied bleed tubes (N) in
grounded, sealed waste containers (H). See
IG. 1, page 23.
F
6. For Heated HFR models only, install Fluid Tem
perature Sensor (FTS)
a. Install FTS between main hose and whip hose.
See Heated Hose manual for instructions.
40313997ZAA
Page 41
Setup
ti9881a1
V
Y
ti2411a1
7. Connect heated hose monitor zones
NOTE: For Heated HFR models only, see Heated Hose
manual for detailed instructions on connecting heated
hoses.
NOTICE
For Heated HFR models only, the FTS (C) and
whip hose (D) must be used with heated hose. See
step 6 on page 40 for FTS installation. Hose length,
including whip hose, must be 10 ft (3 m) minimum.
a. Turn main power OFF .
b. For Heated HFR Models only, assemble
heated hose sections, FTS, and whip ho se. See
Heated Hose manual 3A0237 for heated hose
connection details and illustrations for the vari
ous types of heated hoses.
For Non-Heated HFR Models only, assemble
fluid supply hose sections and whip hose.
d. For Heated HFR Models only, connect
cables (Y). Connect electrical connectors (V).
Be sure cables have slack when hose bends.
Wrap cable and electrical connections with
electrical tape. See Heated Hose manual for
heated hose connection details and illustrations
for the various types of heated hoses.
8. For systems with a gun fluid manifold, close gun
fluid manifold valves A (Red) and B (blue).
c.Connect A (Red) and B (Blue) hoses to A (Red)
and B (Blue) outlets on HFR fluid manifold (FM).
Hoses are color coded: red for component A,
blue for component B. Fittings are sized to pre
vent connection errors.
NOTE: Gun fluid manifold hose adapters allow use of
1/4 in. and 3/8 in. ID fluid hoses. To use 1/2 in. (13 mm)
ID fluid hoses, remove adapters from gun fluid manifold
and install as needed to connect hose.
313997ZAA41
Page 42
Setup
ti2417a1
LR
RB
24C352_312998_8g
9. For models with an MD2 valve, connect whip
hose to MD2 valve component A (Red) and com
ponent B (Blue) fluid inlets.
For models with a dispense gun, connect whip
hose to gun fluid manifold. Do not connect man
ifold to gun. See F
IG. 13
F
IG. 13.
10.Pressure check hose
See hose manual. Pressure check for leaks. If no leaks,
wrap hose and electrical connections to protect from
damage.
11.Ground system
pense gun firmly to the side of a grounded metal
pail, then trigger gun.
12.Check hydraulic fluid level
Hydraulic reservoir is filled at the factory. Check fluid
level before operating the first time, and weekly thereaf
ter. See Technical Data on page 108 for specifications.
13.IsoGuard Select Fluid system setup
Component A (Red) Pump: Fill IsoGuard Select reser
voir (LR) with IsoGuard Select fluid (24F516).
a. Lift the reservoir (LR) out of the bracket (RB)
and remove the container from the cap.
This equipment must be grounded.
a. HFR: grounded through power cord. See step 3
on page 38.
b. EP Gun or Dispense Valve: If supplied, connect
whip hose ground wire to FTS, see step 6 on
page 40. Do not disconnect wire or dispense
without whip hose.
c.Fluid supply containers: follow your local code.
d. Object being dispensed: follow your local code.
e. Solvent pails used when flushing: follow your
local code. Use only metal pails, which are con
ductive, placed on a grounded surface. Do not
place pail on a nonconductive surface, such as
paper or cardboard, which interrupts grounding
continuity.
f.To maintain grounding continuity when flushing
or relieving pressure, hold a metal part of dis
b. Fill with fresh fluid. Thread the reservoir onto
the cap assembly and place it in the
bracket (RB).
c.Push the supply tube approximately 1/3 of the
way into the reservoir. The supply tube is the
tube with the check valve with an arrow pointing
in the direction of flow towards the IsoGuard
Select fluid cylinder.
d. Push the return tube into the reservoir until it
reaches the bottom. The return tube is the tube
with the check valve with an arrow pointing in
the direction of flow away from the IsoGuard
Select fluid cylinder.
NOTE: The return tube must reach the bottom of the
reservoir to ensure that isocyanate crystals will settle to
the bottom and not be siphoned into the supply tube and
returned to the pump.
42313997ZAA
Page 43
Setup
ti10442a1
LOCKED
ti9877a1
SA
SB
In this example, B (Blue)
side pressure is higher,
so use the B (Blue) side
valve to balance pres
sures.
ti9877a1
GA
GB
ti10441a1
UNLOCKED
14. Prime IsoGuard Select fluid cylinder
The IsoGuard Select fluid cylinder must be primed when
replacing IsoGuard Select fluid. See IsoGuard Select
®
System on page 57 for instructions.
15. Install dispense valve
a. Navigate to System Screen 2 and select the
appropriate dispense valve from the “Dispense
Valve” dropdown menu. See System Screen 2
on page 73.
b. Set pressure relief valves (SA, SB) to RELIEF.
c.If dispense valve has a trigger safety lock,
engage the trigger safety lock.
g. Press to enable system. LED should be
solid green.
h. Check that heat zones are on and temperatures
are on target, see Status Screen on page 85.
i.Check fluid pressure display and adjust as nec
essary.
j.For MD2 and Auto-Fusion dispense valves, per
form Connect Solenoid Kit procedure. See
Heated Hoses and Applicator Kits manual for
procedure.
k.Check fluid pressure gauges (GA, GB) to
ensure proper pressure balance. If im balanced ,
reduce pressure of higher component by
slightly turning PRESSURE RELIEF/DIS
PENSE valve for that component toward PRES
SURE RELIEF/CIRCULATION , until
gauges show balanced pressures.
d. Connect gun to machine. Verify gun is ready for
operation. See appropriate gun manual listed in
Related Manuals on page 3 for detailed
instructions.
e. If gun has pneumatics, verify air line is con
nected then open bleed-type master air line
valve.
f.Set PRESSURE RELIEF/DISPENSE valves
(SA, SB) to DISPENSE .
313997ZAA43
l.For MD2 and Auto-Fusion dispense valves, per
form Connect Solenoid Kit procedure. See
Heated Hoses and Applicator Kits manual for
procedure.
m. If dispense valve has a trigger safety lock, dis
engage the trigger safety lock.
Page 44
Setup
n. For EP Gun and GX-16, perform a test pour into
a waste container. Adjust pressure and tem
perature to get desired results. Equipment is
ready to dispense.
o. For all dispense valves other than the EP Gun,
perform mix ratio test using two tared cups.
Weigh the cups and divide the weights to verify
the mix ratio by weight. See Ratio Checking
section in the dispense valve manual for more
information.
p. For Fusion dispense valves, perform DC Power
Pack Hydraulic Pressure Setup. See HFR
Repair manual for procedure.
q. Equipment is ready to dispense.
Vacuum De-gas
NOTE: This procedure is for assemblies with vacuum
tree manifold and no agitator or auto-refill.
1. Disable machine movement by pressing the
Machine Disable Mode key ().
2. Close the shut-off ball valves at the base of the
tanks.
3. If the tank lid has a fill port, turn off any systems that
might refill the tank during the vacuum de-gas pro
cedure.
4. Close the fill port ball valve.
5. If the tank lid requires a desic can t dr ye r or nitroge n
pump installed, install one into the top ball valve of
the vacuum tree manifold.
6. Close the top ball valve of the vacuum tree mani
fold.
7. Attach vacuum pump to the bottom ball valve of the
vacuum tree manifold then open the ball valve.
8. Turn on the vacuum pump.
9. Continue to de-gas for sufficient time to de-gas the
material.
10. Close bottom ball valve of the vacuum tree mani
fold.
11. Turn off the vacuum pump.
12. Open the top ball valve of the vacuum tree manifold.
NOTICE
Operating the tank after the vacuum de-gas proce
dure without the top ball valve open will result in
pump cavitation, off-ratio conditions, and possible
collapse of the tank.
13. Open the shutoff valves at the base of the tanks.
44313997ZAA
Page 45
Setup
Vacuum De-gas and Vacuum
Manual Refill
NOTE: This procedure is for assemblies with a vacuum
tree manifold, agitator, and auto-refill.
1. Press the Select Operatin g M od e butt on ()
repeatedly to select Shot, Sequence, or Operator
(Manual) mode.
2. Close the shut-off ball valves at th e ba se of the
tanks.
3. If the tank lid requires a desicc an t dr ye r or nit ro gen
pump installed, install one into the top ball valve of
the vacuum tree manifold).
4. Close the top ball valve of the vacuum tree mani
fold.
5. Attach vacuum pump to the bottom ball valve of the
vacuum tree manifold then open the ball valve.
6. Turn on the vacuum pump.
12. Close bottom ball valve of the vacuum tree mani
fold).
13. Turn off the vacuum pump.
14. Open the top ball valve of the vacuum tree manifold.
NOTICE
Operating the tank after the vacuum de-gas proce
dure without the top ball valve open will result in
pump cavitation, off-ratio conditions, and possible
collapse of the tank.
15. Open the shutoff valves at the base of the tanks.
7. Turn on agitator.
8. Select Manual Refill mode. See operation manual
referenced at the beginning of this manual for more
information.
9. Press the appropriate Auto-Refill Tank Select button
or buttons ( and/or ) to select the tanks to
refill.
10. If necessary, press the Abort/Cancel button ()
to cancel auto-refill.
If an auto-refill is aborted or times out, the software
will not initiate a new auto-refill until a manually initi
ated auto-refill has completed. To complete a man
ually initiated auto-refill after an aborted or timed
out auto-refill, restart at step 2.
NOTICE
If an auto-refill is stopped and not restarted as
described in the previous note, the pumps may be
run dry and chemical crossover at the valve may
occur.
11. Continue to de-gas for sufficient time to de-gas the
material.
313997ZAA45
Page 46
Advanced Display Module (ADM) Operation
Advanced Display Module (ADM) Operation
When main power is turned on by turning the main
power switch (MP) to the ON position, the splash screen
will be displayed until communication and initialization is
complete.
To begin using the ADM, the machine must be on and
enabled. To verify the machine is enabled, verify the
System Status Indicator Light (CB) is illuminated green,
IG. 5 on page 30. If the System Status Indicator
see F
Light is not green, press the ADM Power On/Off (CA)
button. The System Status Indicator Light will illu
minate yellow if the machine is disabled.
7. If L-Head is installed, define L-Head contr ol
details. See Mix Head Operating Details Screen,
page 74.
8. Define level sensors and refill settings. See Supply Screen, page 76.
9. Enable/disable temperature conditioning compo
nents. See Conditioning Screen 1, page 77.
10. Define temperature conditioning setpoints. See
Conditioning Screen 2, page 78.
11. If Night mode will be used, define Night mode set
tings. See Conditioning Screen 3, page 79.
12. Calibrate machine. See Calibration Screen, Main,
page 72.
13. Define shots. See Shots Screen, page 69.
14. Define sequences. See Sequences Screen,
page 71.
15. If desired, view/reset counters. See Maintenance Screen, page 76.
If the machine is in the Disabled mode screen press
repeatedly to select a different operating mode.
Perform the following tasks to fully setup your system.
1. Set general system settings. See Advanced Screen 1, page 80.
2. Set units of measure. See Advanced Screen 2,
page 80.
3. Enable/disable syste m fe atu r es. See Advanced Screen 3, page 81.
4. Define control mode, dispense mode, and pump
information. See System Screen 1, page 73.
5. Define dispense valve an d ot he r sys te m se ttin gs .
See System Screen 2, page 73.
6. Define labels and other system settings. See System Screen 3, page 75.
46313997ZAA
Page 47
Startup
ti9877a1
SA
SB
FV
ti10002a1
ti2484a1
Do not operate HFR without all covers and shrouds in
place.
1. Use feed pumps to load fluid
NOTE:
The HFR is tested with oil at the factory. Flush out the oil
with a compatible solvent before dispensing. See Flushing on page 52.
a. Check that all machine connections are setup.
See Setup procedure, page 38.
b. Check that inlet screens are clean before daily
startup, see page 56.
Startup
g. Open fluid inlet valves (FV). Check for leaks.
Keep Components A (Red) and B (Blue) Separate
Cross-contamination can result in cured material in
fluid lines which could cause serious injury or damage
equipment. To prevent cross-contamination of the
equipment’s wetted parts, never interchange compo
nent A (Red) and component B (Blue) parts.
c.Check level and condition of ISO lube daily, see
®
IsoGuard Select
System on page 57.
d. Turn on component B (Blue) and component A
(Red) agitators, if used.
e. Turn both PRESSURE RELIEF/DISPENSE
valves (SA, SB) to DISPENSE .
f.Start feed pumps.
h. Use feed pumps to load system.
i.For models with an EP, Fusion, or P2 gun
only, hold gun fluid manifold over two gr ounded
waste containers. Open gun fluid valves A
(Red) and B (Blue) until clean, air-free fluid
comes from valves. Close valves.
j.For models with an MD2 Valve only, hold
MD2 valve nose piece, without a mixer installed,
over two grounded waste containers. Leave
mixer off and trigger gun until both fluids flow
freely from the nose piece without any air.
k.To prime the pump, cycle the pump a few times
or until air-free fluid dispenses.
313997ZAA47
Page 48
Startup
2. Calibrate HFR
The HFR calibration procedure is a two step process.
The first step, Learn Mode, must be performed when
ever the pump line is rebuilt or if any other maintenance
is performed that may affect the mechanical tolerances
in the pump line. If the machine does not appear to be
utilizing the full extent of the pump stroke, or if the
machine appears to be contacting the end of the
hydraulic cylinder, follow the Learn Mode procedure.
The Learn Mode procedure will teach the system the
mechanical limits of travel.
Learn Mode Procedure:
a. Navigate to the Calibration screen.
b. Press the Learn Mode Calibration button
and set the mode to run as the dispense appli
cator that is installed on the system.
NOTE: During this process, the system learned the
mechanical limits of travel. If the pump did not reach
both the left and right extreme limits for any reason,
repeat the procedure.
NOTE: For circulation systems, set the mode as either
EP or MD2 valves. These settings will not dispense
material.
c.Place a waste container below the dispense
valve. The next steps will cause the machine to
dispense material for all other settings.
d. Press the go right button and then the dis
pense button. The pump will travel to the
right most extreme position.
e. After the pump stops moving, press the go left
button and then press the dispense
button. The pump will travel to the left most
extreme position.
f.After the pump stops moving, press the con
tinue button to go on to the next step in the
calibration process or the page back button
to return to the main Calibration screen.
48313997ZAA
Page 49
Startup
3. Set temperatures (Heated models only)
This equipment is used with heated fluid, which can
cause equipment surfaces to become very hot. To
avoid severe burns:
•Do not touch hot fluid or equipment.
•Allow equipment to cool completely before touch
ing it.
•Wear gloves if fluid temperature exceeds 110°F
(43°C).
For detailed temperature adjustments, including alarm
levels, or upon initial machine configuration, see Conditioning Screen 2 on page 78 for details. For minor
adjustments to the temperature setpoint once the
machine has been initially configured, see the Status
Screen on page 85.
4. Set system control and dispense modes: See
System Screen 1 on page 73.
7. Change pressure imbalance setting (optional)
The pressure imbalance function detects conditions that
can cause off-ratio dispense, such as loss of feed pres
sure/supply, pump seal failure, clogged fluid inlet filter,
or a fluid leak.
The pressure imbalance default is factory-set at 500 psi
(3.5 MPa, 35 bar). For tighter ratio error detection, select
a lower value. For looser detection or to avoid nuisance
alarms, input a higher value.
a. Navigate to System Screen 3.
b. Press to enter the screen.
c.Navigate to the pressure imbalance field.
d. Type the desired pressure imbalance setting
then press Enter.
5. Set pump sizes: See System Screen 1 on
page 73.
6. Define Shot Recipes
a. Navigate to the Shots screen.
b. Press to enter the screen.
c.Use the directional keypad to navigate to the
shot detail column for the desired shot number.
d. Type the desired setting for that item then
press.
e. Repeat the previous two steps for all desired
shot numbers.
313997ZAA49
Page 50
Shutdown
ti9883a1
FV
Shutdown
1. Park pumps.
a. From the Home screen, press and select
Standby mode.
b. Press . Material will dispense for non cir
culation systems. Pump will park automatically.
Once pump is parked, pump will stop moving.
If a dispense gun with a trigger is installed,
pulling the trigger will begin a park operation.
Material will dispense for non circulation sys
tems.
c.For models with an EP, Fusion, or P2 gun
only, turn diversion valves to tank then press
Park . Pressure must be below 400 psi
(2.8 MPa, 28 bar).
2. Press the enable/disable key on the ADM to
disable the ADM.
3. Turn main power switch (MP) to OFF position.
4. Close A (Red) and B (Blue) fluid supply valves (FV).
5. Perform Pressure Relief Procedure on page 51.
6. Shut down feed pumps as required. See feed pump
manual.
50313997ZAA
Page 51
Pressure Relief Procedure
ti9879a1
SA
SB
1. Shut off feed pumps and agitator, if used.
2. Turn PRESSURE RELIEF/DISPENSE valves (SA,
SB) to PRESSURE RELIEF/CIRCULATION .
Route fluid to waste containers or supply tanks.
Ensure gauges drop to 0.
Pressure Relief Procedure
3. For models with an dispense valve with a safety
lock, engage gun safety lock.
4. Relieve pressure in dispense valve. See dispense
valve manual.
313997ZAA51
Page 52
Flushing
SA
SB
ti9880a1
N
N
Flushing
Flush equipment only in a well-ventilated area. Do not
dispense flammable fluids. Do not turn on heaters
while flushing with flammable solvents.
•Flush out old fluid with new fluid, or flush out old
fluid with a compatible solvent before introducing
new fluid.
•Use the lowest possible pressure when flushing.
•All fluid components are compatible with common
solvents. Use only moisture-free solvents. See
Technical Data on page 108 for list of wetted com
ponents to verify compatibility of solvent with wetted
materials. See solvent manufacturers information
for material compatibility.
•To maintain grounding continuity when flushi ng or relieving pressure, hold a metal part of dispense
gun firmly to the side of a grounded metal pail, then
trigger gun.
•To flush feed hoses, pumps, and heaters separately
from heated hoses, set PRESSURE RELIEF/DIS
PENSE valves (SA, SB) to PRESSURE
RELIEF/CIRCULATION . Flush through bleed
lines (N).
•To flush entire system, circulate through gun fluid
manifold (with manifold removed from gun).
•To prevent moisture from reacting with isocyanate,
always leave the system dry or filled with a mois
ture-free plasticizer or oil. Do not use water. See
Important Two-Component Material Information
on page 20.
•Solvent pails used when flushing: follow your local
code. Use only metal pails, which are conductive,
placed on a grounded surface. Do not place pail on
a nonconductive surface, such as paper or card
board, which interrupts grounding continuity.
52313997ZAA
Page 53
Maintenance
ti9879a1
S
DS
ti7861a1
IM
24C352_313998_1
Maintenance
Change Break-in Oil
After initial break-in, see Table 5 for recommended fre
quency of oil changes.
TaskSchedule
Change break-in oil in a new unitAfter first 250
hours of opera
tion or within 3
months, which
ever comes first
Inspect hydraulic and fluid lines
for leaks
Inspect fluid inlet strainer
screens, page 56
Inspect IsoGuard Select fluid
level and condition, refill or
replace as needed, page 57
Check hydraulic fluid levelWeekly
Grease circulation valves with
Fusion grease (117773)
Verify operation of air drying sys
tem to prevent isocyanate crystal
lization
Verify vent holes on bottom of
electrical cabinet are clear and
unobstructed
Inspect air filter (part 24H018),
clean or replace as necessary,
Daily
Daily
Daily
Weekly
Weekly
Weekly
Daily
Table 2: Frequency of Oil Changes
Ambient
Temperature
0 to 90°F
(-17 to 32°C)
90°F and above
(32°C and above)
Recommended
Frequency
1000 hours or 12 months,
whichever comes first
500 hours or 6 months,
whichever comes first
Grease Circulation Valves With Fusion
Grease (117773)
Check Hydraulic Fluid Level
Check hydraulic fluid level on dipstick (DS). Fluid level
must be between indent marks (IM) on dipstick. Refill as
required with approved hydraulic fluid; see Technical Data on page 108. If fluid is dark in color, change fluid
and filter.
Use compressed air to remove
dust buildup on control boards,
fan, motor (under shield), and
hydraulic oil coolers
Clean up all hydraulic leaks; iden
tify and repair cause of leak
Clean dispense valve mix cham
ber ports regularly, see dispense
valve manual
Clean dispense valve check
valve screens, see dispense
valve manual
313997ZAA53
Monthly
As needed
See dispense
valve manual
See dispense
valve manual
Page 54
Maintenance
ti12364a1
r_257396_3b9905_02b
Heat
Sink Fins
ti12353a1
ti12357a1
Heat Sink Fins
ADM - Battery Replacement and
Screen Cleaning
Battery Replacement
A lithium battery maintains the ADM clock when power
is not connected.
To replace the battery:
1. Disconnect power to the ADM.
NOTE: This can be done by removing the CAN cable
from the bottom of the ADM.
2. Remove rear access panel.
MCM and TCM - Clean Heat Sink
Fins
Keep heat sink fins clean at all times. Clean them using
compressed air.
NOTE: Do not use conductive cleaning solvents on the
module.
3. Remove the old battery and replace with a new
CR2032 battery.
4. Properly dispose the old lithium battery according to
local codes.
5. Replace rear access panel.
6. Connect the power to the ADM and reset the clock
through Advanced Screen 1. Refer to Appendix B
- ADM Setup Screens Overview for more detail.
Cleaning
Use any alcohol-based household cleaner, such as
glass cleaner, to clean the ADM. Spray on the rag then
wipe ADM. Do not directly spray the ADM.
FIG. 14: Clean Heat Sink Fins
54313997ZAA
Page 55
Install Upgrade Tokens
r_257396_3b9905_04b
ti12334a1
ti12358a1
ti12354a1
NOTE: The Motor Control Module, Fluid Control Mod
ule, and Temperature Control Module connection to the
system is temporarily disabled during the installation of
upgrade tokens.
To install software upgrades:
1. Use correct software token stated in the table. See
™
Graco Control Architecture
manual for instructions.
NOTE: Upgrade all modules in the system to the
software version on the token, even if you are
replacing only one or two modules. Different soft
ware versions may not be compatible.
All data in the module (System Settings, USB Logs,
Recipes, Maintenance Counters) may be reset to
factory default settings. Download all settings and
user preferences to a USB before the upgrade, for
ease of restoring them following the upgrade.
Module Programming
Maintenance
See manuals for locations of specific GCA compo
nents.
The software version history for each system can be
viewed in the technical support section at
www.graco.com.
FIG. 15: Remove Access Cover
Token Application
16H821 HFR:
- Advanced Display Module
- Motor Control Module
- High Power Temperature Control Module
- Fluid Control Module (AC Power Pack)
- Discrete Gateway Module
- Communication Gateway Module
16G584 Tank Stand:
- Fluid Control Module
- Low Power Temperature Control Module
16G407 Ratio Monitoring (Flow Meters):
- Fluid Control Module
313997ZAA55
Page 56
Maintenance
59g*
59h
59j
59k
ti9886a1
59d
Fluid Inlet Strainer Screen
The inlet strainers filter out particles that can plug the
pump inlet check valves. Inspect the screens daily as
part of the startup routine, and clean as required. The
standard strainer is 20 mesh.
Use clean chemicals and follow proper storage , transfer,
and operating procedures, to minimize contamination of
the A-side screen.
NOTE:
Clean the A-side screen only during daily startup. This
minimizes moisture contamination by immediately flush
ing out any isocyanate residue at the start of dispensing
operations.
1. Perform Pressure Relief Procedure on page 51.
2. Close the fluid inlet valve at the pump inlet and shut
off the appropriate feed pump. This prevents mate
rial from being pumped while cleaning the screen.
6. Open the fluid inlet valve, ensure that there are no
leaks, and wipe the equipment clean. Proceed with
operation.
FIG. 16. Fluid Inlet Strainer
3. Place a container under the strainer manifold (59d)
to catch fluid. Remove the strainer plug (59j).
4. Remove the screen (59g) from the strainer mani
fold. Thoroughly flush the screen with compatible
solvent and shake it dry. Inspect the screen. If more
than 25% of the mesh is blocked, replace the
screen. Inspect the gasket (59h) and replace as
required.
5. Ensure the pipe plug (59k) is screwed into the
strainer plug (59j). Install the strainer plug with the
screen (59g) and gasket (59h) in place and tighten.
Do not overtighten. Let the gasket make the seal.
56313997ZAA
Page 57
Maintenance
24C352_313998_8e
IsoGuard Select® System
Check the condition of the A (Red) pump IsoGuard
Select fluid daily. Change the fluid if it becomes a gel, its
color darkens, or it becomes diluted with isocyanate.
Gel formation is due to moisture absorption by the pump
IsoGuard Select fluid (24F516). The interval between
changes depends on the environment in which the
equipment is operating. The pump lubrication system
minimizes exposure to moisture, but some contamina
tion is still possible.
Fluid discoloration is due to continual seepage of small
amounts of isocyanate past the pump packings during
operation. If the packings are operating properly,
IsoGuard Select fluid (24F516) replacement due to dis
coloration should not be necessary more often than
every 3 or 4 weeks.
9. Push the return tube (RT) into the reservoir until it
reaches the bottom.
NOTE:
The return tube must reach the bottom of the reservoir,
to ensure that isocyanate crystals will settle to the bot
tom and not be siphoned into the supply tube and
returned to the pump.
To change pump IsoGuard Select fluid (24F516):
1. Perform Pressure Relief Procedure on page 51.
2. Remove fittings from IsoGuard Select fluid cylinder
inlet and outlet ports. Keep supply tube (ST), return
tube (RT), and leak management tube (LT) con
nected to the fittings.
3. Carefully place ends of tubes with fittings still con
nected into an empty pail to drain IsoGuard Select
fluid.
4. Lift the IsoGuard Select fluid reservoir (LR) out of
the bracket (RB) and remove the container from the
cap. Holding the cap over a suitable container,
remove the inlet check valve and allow the IsoGuard
Select fluid to drain. Reattach the check valve to the
inlet hose. See F
IG. 17.
5. Drain the reservoir and flush it with clean IsoGuard
Select fluid (24F516).
6. When the reservoir is flushed clean, fill with fresh
IsoGuard Select fluid (24F516).
FIG. 17: IsoGuard Select Fluid System
Prime IsoGuard Select Fluid Cylinder
Ensure that the IsoGuard Select fluid cylinder outle t
faces upward for air to exhaust.
1. Install IsoGuard Select fluid cylinder inlet fitting and
inlet tube into bottom of cylinder. The inlet tube is
the tube with a check valve installed in it which
points in the direction of flow towards the IsoGuard
Select fluid cylinder.
2. Install IsoGuard Select fluid cylinder outlet fitting
and outlet tube into top of cylinder. The outlet tube is
the tube with a check valve installed in it which
points in the direction of flow away from the
IsoGuard Select fluid cylinder.
3. Remove check valve from end of outlet tube.
4. Use funnel to pour IsoGuard Select fluid (24F516)
into tube to fill cylinder.
7. Thread the reservoir onto the cap assembly and
place it in the bracket (RB).
8. Push the supply tube (ST) approximately 1/3 of the
way into the reservoir.
313997ZAA57
5. With check valve arrow pointing away from the
IsoGuard Select fluid cylinder, install check valve in
end of outlet tube.
6. Install tubes into reservoir and install reservoir into
holder.
Page 58
Troubleshooting
Troubleshooting
Before performing any troubleshooting procedure:
1. Perform Pressure Relief Procedure on page 51.
2. Turn main power OFF.
3. Allow equipment to cool.
Try the recommended solutions in the order given for
each problem, to avoid unnecessary repairs. Also,
determine that all circuit breakers, switches, and con
trols are properly set and wiring is correct before assum
ing there is a problem.
Light Tower (Optional)
SignalDescription
Green on onlySystem is powered up and there are
no error conditions present
Yellow onAn advisory exists
Red flashingA deviation exists
Red onThe system is shut down due to an
alarm occurring.
Errors include advisories, deviation s, or alar m s, so
green will only be on when none of these occur. A yel
low light can be on at the same time as red (flashing or
solid on) when an advisory exists at the same time as a
deviation or alarm.
Common Problems
ProblemCauseSolution
General
Display Module completely
dark
No or incorrect amount of
material dispensed from
either side
Significant material leaking
from pump seal
Material dispensed not cor
rect weight
A (Red) and B (Blue) Primary Heaters
Control of primary heat is
abnormal; high temperature
overshoots
No PowerVerify AC Power switch is ON
Thrown BreakerCheck Machines Breakers and Reset
Loose ConnectionTighten 5-pin cable on Advanced Display Module
Bad Display ModuleReplace Advanced Display Module
Ball Valve closed (if Installed)Open tank ball valve.
Tank EmptyAdd fluid
Tank CloggedClean tank
Air In MaterialPrime the machine
Pump shaft worn and/or shaft seal
worn
Specific gravity of one or more of the
two materials has changed since cali
bration
Check valve malfunctionRemove check valve; clean or replace as necessary
Piston worn or brokenReplace Piston
Dirty RTD connectionUnplug and re-plug RTD wires.
RTD not contacting heater elementLoosen ferrule nut, push in RTD so tip contact heater
Failed heater elementReplace
Signal failure from RTDCheck connections
RTD wired incorrectlyCheck connections. Power up zones one at a time
Remove pump shaft assembly and reinstall read
pump rebuild kit
Run calibration
element. Holding RTD tip against heater element,
tighten ferrule nut 1/4 turn past tight.
and verify that temperature for each zone rises.
58313997ZAA
Page 59
Troubleshooting
ProblemCauseSolution
Hose Heat System
Hose heats but heats slower
than usual or it does not
reach temperature
Ambient temperature is too coldUse auxiliary hose system.
FTS failed or not installed correctlyCheck FTS
Low supply voltageVerify line voltage. Low line voltage significantly
reduces power available to hose heat system, affect
ing longer hose lengths.
Hose does not maintain tem
perature while spraying
A and B setpoints too lowIncrease A (Red) and B (Blue) setpoints. Hose is
designed to maintain temperature, not to increase it.
Ambient temperature is too coldIncrease A (Red) and B (Blue) setpoints to increase
fluid temperature and keep it steady
Flow too highUse smaller mix chamber. Decrease pressure.
Hose was not fully preheatedWait for hose to heat to correct temperature before
spraying
Low supply voltageVerify line voltage. Low line voltage significantly
reduces power available to hose heat system, affect
ing longer hose lengths.
Hose temperature exceeds
setpoint
A (Red) and/or B (Blue) primary heat
ers are overheating material
Check primary heaters for either an RTD problem or a
failed element attached to thermocouple
Faulty RTD connectionsVerify that all FTS connections are snug and that pins
of connectors are snug and that pins of connects are
clean. Examine connection of thermocouples to long
green plug on heater control board. Unplug and
re-plug RTD wires, cleaning off any debris. Unplug
and re-plug long green connector on heater control
board.
Erratic hose temperatureFaulty RTD connectionVerify that all FTS connections are snug and that pins
of connectors are clean. Examine connection of RTD
to long green plug on heater control board. Unplug
and re-plug RTD wires, cleaning off any debris.
Unplug and re-plug long green connector.
FTS not installed correctlyFTS should be installed close to end of hose in same
environment as gun. Verify FTS installation.
Hose does not heatFTS failed or is not contacting cor
Check FTS
rectly
FTS not installed correctlyFTS should be installed close to end of hose in same
environment as gun. Verify FTS installation.
Temperature control alarmSee Appendix D - ADM Error Codes on page 88
Hoses near system are
warm, but hoses downstream
are cold
Shorted connection or failed hose
heating element
With hose heat on and temperature setpoint above
displayed hose zone temperature, verify voltage
between connectors at each section of hose.
Proportioning System
Proportioning pump does not
Pump piston or intake valve leaking1.Observe gauges to determine which pump is los
hold pressure when stalled
313997ZAA59
Voltage should drop incrementally for each section of
hose further from the system. Use safety precautions
when hose heat is turned on.
ing pressure.
2.Determine in which direction the pump has
stalled by observing which directional valve indi
cator light is on.
3.Repair the valve.
Page 60
Troubleshooting
ProblemCauseSolution
Material imbalance.Inadequate flow from pump; cavitation Increase fluid supply to proportioning pump:
•Use 2:1 supply pump
•Use minimum 3/4 in. (19 mm) ID supply hose, as
short as practical
Fluid is too thick. Consult your material supplier for
the recommended fluid temperature to maintain a vis
cosity of 250 to 1500 centipoise.
Pressure relief/circulation valve leak
ing back to supply
Erratic pump movementPump cavitationFeed pump pressure is too low. Adjust pressure to
Pump output lowObstructed fluid hose or gun; fluid
hose ID too small
Worn piston valve or intake valve in
displacement pump
Inadequate feed pump pressureCheck feed pump pressure and adjust to 100 psi (0.7
Remove return line and determine if flow is present
while in SPRAY mode
maintain 100 psi (0.7 MPa, 7 bar) minimum.
Open, clear; use hose with larger ID
See pump manual
MPa, 7 bar) minimum.
60313997ZAA
Page 61
ADM Troubleshooting
CR
CK
CJ
CL
CP
CN
CM
CS
r_24E451_3B9900_1a
Troubleshooting
FIG. 18: ADM Component Identification - Rear
ADM Module Status LEDs (CN) Conditions
Module Status LED SignalDescription
Green onSystem is powered up.
Yellow onCommunication in progress.
Red solidADM hardware failure.
Red flashingUploading software.
USB Module Status LEDs (CL) Conditions
Module Status LED SignalDescription
Green flashingSystem is powered up.
Yellow onDownloading information to USB
Green/Yellow FlashingADM is busy, USB cannot transfer
information when in this mode
313997ZAA61
Page 62
Troubleshooting
LED
Signals
r_257396_3b9905_07b
Motor Control Module
For MCM location, see reference MA in FIG. 2 on
page 25.
Diagnostic Information
7
Module Status LED SignalDescription
Green onSystem is powered up.
Yellow onInternal communication in progress.
Red solidMCM hardware failure. Replace MCM.
Red flashing fastUploading software.
Red flashing slowToken error. Remove token and upload
Table 3: LED Status Signal
software token again.
FIG. 19: LED Signals
62313997ZAA
Page 63
Acceptable Size and Duration of Power Line Voltage Fluctuations
Maximum Permissible Transient Voltage Surges
* Constructed from ITIC 1996 curve, referenced by IEC 61000-2-4
1200Vac, 1697Vdc
264Vac, 373Vdc
336Vac, 475Vdc
288Vac, 407Vdc
480Vac, 679Vdc
<--1 MW Max Surge Power
<--150 KW Max Surge Power
<--50 KW Max Surge Power
<--No Power Limit
0
200
400
600
800
1000
1200
1400
Time (seconds)
Voltage (Volts RMS)
The Motor Control Module is designed to withstand volt
age fluctuations from the incoming power supply. If the
incoming power supply goes outside of the tolerable
range, an over-voltage condition is flagged and the sys
tem shuts down in an alarm state. Excessive or
repeated over-voltage may permanently damage hard
ware. The chart below shows the permissible mag nitude
and duration of temporary over-voltage events. Consult
a qualified electrician if there are any concerns about
the available power supply.
Troubleshooting
313997ZAA63
0.000001 0.00001 0.0001 0.001 0.01 0.1 1 10
Page 64
Troubleshooting
ti12337a1
Module Status LEDs
Fluid Control Module
Diagnostic Information
Module Status LED SignalDiagnosis
Green onSystem is powered up
YellowInternal communication in progress
Red solidFCM hardware failure. Replace FCM.
Red flashing fastUploading software
Red flashing slowToken error. Remove token and
upload software token again.
FIG. 20:
64313997ZAA
Page 65
Temperature Control Module
LED
Signals
ti12353a1
ti12357a1
LED
Signals
Diagnostic Information
Module Status LEDs
SignalDescription
Green onTemperature control module is
powered up.
Yellow onInternal communication in prog
ress.
Red solidTemperature control module fail
ure. See Troubleshooting table.
Red flashingSoftware is updating.
Blue light off
(High Power
Module only)
Blue flashing
(High Power
Module only)
Temperature control module is off.
See Troubleshooting table.
Length of flashes indicates amount
of power running through tempera
ture control module.
Troubleshooting
F
IG. 21: LED Signals
313997ZAA65
Page 66
Appendix A - ADM Icons Overview
Appendix A - ADM Icons Overview
Setup Screen Icons
IconDescription
Enter Screen
Exit Screen
On Learn Mode Calibration screen:
Move pump
All other screens:
Begin Dispense
Stop Dispense
Abort Changing the Label
Select left direction
Select right direction
Backspace
IconDescription
Erase All Counters on Page
Access Flowmeter Calibration
Valve Details
Selects all shots to be changed to the
same user specific value
Pressure
Shot Number
Sequence Position
Flow
Time (Duration)
Tank Blanket Heater
Back to main calibration screen from
learn mode calibration screen
or
Back to system screen 2 from mix
head operating details screen
Access Learn Mode Calibration
screen
Run MCM Learn Mode
Proceed to next step in calibration
procedure
On Main Calibration screen:
Calibrate Weight Dispense or Enter
Specific Gravity Information
On Flow Meter Calibration screen:
Use Dispensed Material Weight to
Calibrate Flow Meters. If pressed,
icon will change and units are
changed to volume units.
Erase Selected Item or Control Data
Primary Heater
Heated Hose
Chiller
Move Cursor to the Left
Move Cursor to the Right
Upper/Lower Case Letters
Positive / Negative
66313997ZAA
Page 67
Run Screen Icons
Appendix A - ADM Icons Overview
IconDescription
Select mode.
Set system in park (icon will be
selected when system is parked)
Open, Close Valve
A (Red) and B (Blue) refill button
(Press to start/abort refill)
With a mix head installed: Turns on
the mix head hydraulics and puts the
machine in low pressure circulation.
Press a second time to turn off insti
gated system action.
If Green:
Allowed to Dispense
If Red:
Not Allowed to Dispense
Stop Dispense
OR
Jump in and use the key pad to select
a shot number.
Skip the next shot in selected
sequence. Only available when the
system is not dispensing.
Abort sequence and reset to first valid
position
Edit Operator Dispense Setting
Press to enter the Conditioning Con
trol screen
IconDescription
Sets machine to low pressure
Sets machine to high pressure
Current and setpoint temperature for
primary heater. Not displayed if heat
zone is not enabled.
Current and setpoint temperatures for
heated hose. Not displayed if heat
zone is not enabled.
Current temperatures for heated hose
monitor. Not displayed if heat zone is
not enabled.
Current and setpoint temperatures for
tank blanket. Not displayed if heat
zone is not enabled.
Current temperatures for tank blanket
monitor. Not displayed if heat zone is
not enabled.
Current and setpoint temperatures for
chiller. Not displayed if heat zone is
not enabled.
Current temperatures for chiller moni
tor. Not displayed if heat zone is not
enabled.
Amount of material moved through
pump (volume tracking)
Cycles
Turn on or off the highlighted zone.
Turn on or off all zones.
Erase a single batch
Erase all batch data points
313997ZAA67
Page 68
Appendix B - ADM Setup Screens Overview
Calibration
Maintenance
Shot #1
Shot #2
Shot #...
Sequences #1
Sequences #2
Sequences #...
Advanced #1
Advanced #2
Advanced #...
System #1
System #2
System #3
Supply
Conditioning #1
Conditioning #2
Conditioning #3
Appendix B - ADM Setup Screens Overview
The ADM will start in the Run screens at the “Home”
screen. From the Run screens, press to access
the Setup screens. If the Setup screens password is
turned on, use the ADM keypad to enter the password
then press.
From the Setup screens, press to access the Run
screens. For Run screens information, see Appendix C
- ADM Run Screens Overview on page 82. F
IG. 22
shows the flow of the Setup screens.
FIG. 22: Setup Screens Navigation Diagram
68313997ZAA
Page 69
Appendix B - ADM Setup Screens Overview
Shots Screen
This screen allows the user to edit shot definitions. The
contents of this screen change based on the Dispense
and Control Mode selections. Shots may be defined by
pressure or flow rate depending upon the Control Mode
selection and by time (duration), volume, or weight
depending upon the Dispense Mode selection. See Sys
tem Screen #1 for Control and Dispense Mode options.
See Home Screen, Shot Mode on page 83 for informa
tion on how to use predefined shots.
NOTE: 100 shot definition are available across ten
pages.
To edit a shot definition:
1. Press then use the arrow keys to navigate to the
desired value.
Due to variation in material properties, the
∆ column
gives the ability to adjust the shot time/volume/weight
for each defined shot.
NOTE: If the
∆ column is used, it is recommended that
a minimum of 5 shots are dispensed, measured and
averaged for each dispense before entering a value for
∆ column.
the
Time Based Example:
A 75 cc/s shot is defined to dispense for 2 seconds.
2. Type the new value then press to accept the
new value.
3. If desired, press to quickly enter the same value
for the rate and time/volume/weight.
4. Repeat step 2 as required.
1. Dispense 5 shots into 5 sepa ra te con ta ine rs.
2. Measure the dispensed amount and record the
data.
Shot
Example 1
Dispensed Volume
(cc)
Example 2
Dispensed Volume
(cc)
1146.2156.2
2
146.4156.4
3145.6155.6
4
145.8155.8
5146.0156.0
3. Calculate the averag e of the 5 sh ot s.
Example 1 = 146cc
Example 2 = 156cc
313997ZAA69
Page 70
Appendix B - ADM Setup Screens Overview
((Flow Rate x Time) - Average Volume)
Flow Rate
Example 1:
= 0.053 sec
Example 2:
((75cc/sec x 2sec) - 146cc)
75 cc/sec
= -0.08 sec
((75cc/sec x 2sec) - 156cc)
75 cc/sec
Example 1:
Example 2:
(Requested Amount - Actual Amount)
Example 3:
(75cc - 72.5cc = 2.5cc)
4. Use the following formula to calculate the ∆ column
value.
5. Enter the calculated value in the
∆ column.
Volume/Weight Based Example:
A 75 cc/s shot is defined to dispense for 75 cc.
1. Dispense 5 shots into 5 sepa ra te con ta ine rs.
2. Measure the dispensed amount and record the
data.
Example 3
Dispensed Volume
Shot
(cc)
NOTE: Depending on the dispensed volume average,
∆ column may be either a positive or negative
the
value.
172.2
2
372.6
4
572.5
3. Calculate the averag e of the 5 sh ots .
Example 3 = 72.5cc
4. Use the following formula to calculate the
value.
72.4
72.8
∆ column
70313997ZAA
Page 71
Appendix B - ADM Setup Screens Overview
Example 3:
5. Enter the calculated value in the ∆ column.
Sequences Screen
This screen allows the user to edit sequence informa
tion. The contents of this screen change based on the
Dispense and Control Mode selections.
Dispense detail is shown as volume, time, or weight
depending on which Dispense Mode is selected. See
System Screen 1 on page 73 for Dispense Mode
options. See Home Screen, Sequence Mode on
page 84 for information on how to use predefined
sequences.
NOTE: Five sequences with 20 positions each ar e avail
able across 10 pages.
To edit a sequence:
1. Press the Enter screen button then use the
arrow keys to navigate to the desired value.
2. Type the new value then press the Enter button
to accept the new value.
313997ZAA71
Page 72
Appendix B - ADM Setup Screens Overview
Previously saved left
position
Previously saved right
position
Current position
Calibration Screen, Main
This screen shows calibration information for the system
and provides access to other calibration screens. See
Calibrate HFR on page 48 for how to use the calibration
screens to calibrate the machine.
The date next to each key represents the last time that
calibration was performed.
The “Cal. Min” and “Cal. Max” values are the system
recognized extreme ends of piston travel. See Calibra
tion Screen, Learn Mode.
Calibration Screen, Learn Mode
This screen allows the user to calibrate piston position.
The piston can be moved to the left and right to obtain
the full range of motion. See Calibrate HFR on page 48
for how to use this screen to calibrate the machine.
Press to go to the Calibration Screen, Learn Mode screen.
Press to erase the motor control database in the
motor control module.
Press and then to move the pump all the way
to the left.
Press and then to move the pump all the way
to the right.
Press to return to the Calibration Screen, Main.
This saves the new left and right numbers.
72313997ZAA
Page 73
Appendix B - ADM Setup Screens Overview
System Screen 1
NOTE: Not all of the following modes may be available
depending on the dispense valve selected.
This screen allows the user to set important system set
tings specific to what dispense applicator has been
selected. Control Mode can be set to Pressure or Flow.
With Control Mode set to Pressure, the machine will
adjust dispense flow rate in order to maintain the
requested pressure. With Control Mode set to Flow, the
machine will dispense at a continuous flow rate regard
less of pressure fluctuations unless pressure alarm con
ditions occur.
Dispense Mode can be set to Time, Volume, or Weight.
Dispense Mode controls how displayed amounts are
measured. If Dispense Mode is set to Weight, then the
machine dispenses until the desired weight of material
is dispensed. See Calibrate HFR on page 48 for more
information.
Pump sizes and inlet pressures must be entered on this
screen.
If pump sizes and inlet pressures are not entered prop
erly, system performance will be affected. The inlet
pressure must be set to the maximum feed pressure
that will be seen by that side of the machine.
The maximum working pressure for the machine is dis
played on this screen. The maximum working pressure
is dependent on the installed hoses and dispense valve.
The maximum working pressure is set to the lowest
rated system component. If 2000 psi hoses are installed
and the maximum working pressure displayed is not
2000 psi, see HFR repair/parts manual for instructions
to set the maximum working pressure for hoses. If the
installed dispense valve rating is below the maximum
working pressure shown here, verify the correct dis
pense valve is selected on System Screen 2.
System Screen 2
This screen allows the user to set the Gel Timer proper
ties and set which items are installed on the machine.
When enabling the Gel Timer, the user must select one
of the 100 available shot definitions to use as the Gel
Shot. This shot will be dispensed when the Idle Period
expires. The Idle Period will begin after a dispense is
completed. Any dispense operation in the middle of the
timer countdown will reset the Idle Period counter. The
system will generate an audible alarm based upon the
user Alarm setting. The alarm will sound the
user-entered number of seconds before the Idle Period
expires.
The hydraulic level sensor and hydraulic RTD for both
the pump line and mix head must be marked as enabled
when installed in the system. If the sensors are not
marked as enabled, they will be ignored by the machine
controls.
Select the dispense valve installed in the system. This
selection is critical to ensure proper operation of the
machine. When a mix head is selected, button will
become active when the is pressed. When active,
pressing this button will open a screen used to define
the mix head operating parameters. See the Mix Head Operating Details Screen on page 74.
Selecting the dispense valve will limit the system maxi
mum working pressure to the maximum working pres
sure of the dispense valve. See System Screen 1 on
page 73.
313997ZAA73
Post Dispense Shot Disable is a feature where the user
can disable shot requests for zero to five seconds after
the completion of a dispense. This feature is not applica
ble for P2/Fusion Dispense Valves. This feature can not
be active if the Pre Dispense Delay feature is active.
Page 74
Appendix B - ADM Setup Screens Overview
Pre Dispense Delay is a feature where the HFR can
delay the start of a dispense until the user has pressed
and held the foot switch for the duration entered. For
example, if the user enters a five second duration, the
footswitch must be held on continuously for five seconds
before the HFR will start a dispense. This feature is not
available for recirculation systems or applicable for
P2/Fusion Dispense Valve application s. T his fe at ur e
can not be active if the Post Dispense Shot Disable fea
ture is active.
Mix Head Operating Details Screen
This screen allows the user to define the mix head oper
ating parameters.
•Low Pressure Circulation: The percentage of set
point at which the system will run during low pres
sure circulation.
•Pre-Dispense Circulation: The time for which the
system will circulate at high pressure prior to dis
pensing when the dispense command is triggered
while the system is in low pressure circulation.
•Post-Dispense Circulation: The time duration that
the system will remain in high pressure circulation
after a dispense before dropping into low pressure
circulation.
•Idle Position: Applies to an L-Head only. The posi
tion of the clean out rod when the mix head is idle.
•Clean Out Open: Applies to an L-Head only. The
amount of time the clean out rod will remain open
immediately after the completion of a dispense.
•Clean Out Closed: Applies to an L-Head in a Nor
mally Open configuration only. The amount of time
the clean out rod will remain closed when it closes
after the completion of a dispense (after the clean
out open time delay).
•Anti-Seize Delay: Applies to an L-Head in a Nor
mally Closed configuration only. After a shot occurs
and the cleanout piston closes, the first anti-seize
delay will count down then the cleanout piston will
open and close to break loose from any curing
material. The second anti-seize timer will then begin
counting down and the cleanout piston will open and
close again to break loose from any remaining cur
ing material. If a shot occurs before both anti-seize
timers elapse, the anti-seize timers restart.
74313997ZAA
Press to go back to the System Screen 2.
Page 75
Appendix B - ADM Setup Screens Overview
Pressure
Imbalance
Setting
System Screen 3
This screen allows the user to edit the labels for the A
(Red) and B (Blue) sides of the machine. The labels set
for the A (Red) and B (Blue) sides of the machine are
displayed throughout the screens. Labels are limited to
five characters.
To edit a label:
1. Press .
2. To edit the A (Red) label, press .
To edit the B (Blue) label, press the down arrow
then press . The keyboard will appear on the
screen. See Keyboard Screen on page 75.
3. Use arrow keys to select the desired letter and
press to accept the letter. To erase all text,
press the Eraser softkey. To go back one letter,
press the Back Arrow softkey.
Keyboard Screen
This screen is used to edit the A (Red) and B (Blue)
labels on the ADM. Use arrow keys to select the desired
letter and press to accept the letter.
1. Use arrow keys to select the desired letter and
press to accept the letter. To erase all text,
press . To delete one letter, press . To
4. When finished enterin g the ne w lab el, pre ss
the button twice.
The pressure imbalance setting may be set from this
screen. Pressure imbalance is the allowable difference
in pressure between the two materials before an alarm
is triggered. The input range is 250-2000 psi (2 -14 MPa,
17-138 bar).
The flowmeter types are defined on this screen. The
ratio deviation value is the allowable percentage before
the machine displays a pop-up notification. The ratio
alarm value is the allowable percentage difference
before the machine will stop a dispense.
This screen allows the user to enter material specific
gravities.
move the cursor one letter to the left, press . To
move the cursor one letter to the right, press .
To toggle the letters from upper/lower case, press
.
2. When finished entering the new label, press .
Flow Meter Calibration
Refer to the HFR Flow Meter Kits manual for instruc
tions on how to calibrate the flow meters.
313997ZAA75
Page 76
Appendix B - ADM Setup Screens Overview
Maintenance Screen
This screen shows shot number, sequence position, and
dispense valve counters. Press and navigate to the
drop down box. Press and scroll to a range of count
ers to view. Press again to select the range of
counters and display them on the screen.
Counters may be erased individually. Navigate to the
counter you want to erase and press . Alternatively,
each counter displayed on the page may be erased
simultaneously by pressing .
Supply Screen
This screen allows the user to specify the operating
parameters for off-board, integrated tanks and indicate
which positions have level sensors installed. See the
Tank Feed Systems manual for information about
installing level sensors, see Related Manuals on
page 3. The user may select from the following refill set
tings: Disabled, Monitor, Manual, Auto Top-Off, Auto
Full-Volume.
NOTE: Use the “Disabled” setting if off-board tanks are
not installed.
The following describes system operation when each
tank mode is selected.
•Disabled
•Disables tank operation
•Monitor
•The top sensor generates a high level deviation
and the bottom sensor generates a low level
alarm
•Refill is not supported, no button is provided on
the run screens to initiate refill
•Errors will clear when the corresponding condi
tion clears
•Manual
•The low level sensor will generate a low level
alarm
•A button is provided to the user on the run
screens to instigate a manual refill operation at
any time
•Manual refill will run until either the high level
sensor sees material, the user aborts the refill
via the refill button on the run screens, or the
refill time-out expires
•The low level alarm will clear when the condition
clears
•Auto Top-Off
•The low level sensor will generate a low level
alarm
76313997ZAA
Page 77
Appendix B - ADM Setup Screens Overview
•When the high level sensor does not see mate
rial, automatic refill will begin and continue until
either the high level sensor sees material or
until the refill time-out expires
•The low level alarm will clear when the condition
clears
•A button is provided to the user on the run
screens to instigate an automatic refill operation
at any time, this button can also be used to
abort a refill operation
•Auto Full-Volume
•The low level sensor will initiate an automatic
refill when it does not see material
•Automatic refill will continue until either the high
level sensor sees material or until the refill
time-out expires
•The low level alarm will clear when the condition
clears
•A button is provided to the user on the run
screens to instigate an automatic refill operation
at any time, this button can also be used to
abort a refill operation
Refill Setting
If a refill setting other than Disabled is selected, the user
must set at least two level sensor locations as installed
by checking the check box on the screen. If all three
locations are set to installed, the system will default to
the Auto-Top Off refill setting and operate as follows:
Refill Sensor Type
The Low-Temp Sensor setting limits tank temperatures
to 150°F (66°C). And the High-Temp Sensor setting lim
its tank temperatures to 190°F (88°C).
NOTICE
If you are using low temperature sensors and
select the High-Temp Sensor setting and set the
temperature above 150°F (66°C), damage to the
level sensors will occur.
Conditioning Screen 1
This screen allows the user to select which temperature
conditioning components are installed in the system.
Check the box next to the component type for the appro
priate side of the system to indicate that a component is
installed. A maximum of four components may be
selected. A maximum of four components and two mon
itoring zones may be selected.
•The low level sensor will generate a low level alarm.
•The high level sensor will generate a high level devi
ation and abort any automatic refill operation.
•When the middle sensor is not satisfied, automatic
refill will begin and will run until either the middle
sensor is satisfied, the high level sensor generates
a deviation (if the middle sensor fails), or the refill
time-out expires.
•The low level alarm and the high level deviation will
clear when the condition clears.
•A button is provided to the user on the Run screens
to instigate an automatic refill operation at any time.
This button can also be used to abort a refill opera
tion.
Refill Timeout
The refill time-out setting may b e set by the user as a
means to abort the refill in the case of a high level sen
sor failure. When an automatic refill begins, the time-out
counter will begin to count down. If the timer expires
before the high level sensor is satisfied, the refill will
abort.
313997ZAA77
Page 78
Appendix B - ADM Setup Screens Overview
Conditioning Screen 2
This screen shows the fluid path for the temperature
conditioning components and temperature setpoints for
each component.
NOTE: If tank blanket heaters or inline heaters are
installed along with hose heat, the hose heat setting will
be limited to at or below the inline or tank heat setting.
To edit the temperature setpoint and alarms for a partic
ular component:
2. Press to display the setpoint and alarm values
associated with that component.
3. Edit the setpoint and alarm values and then press
to return to Conditioning Screen 2.
NOTE: The high alarm and low alarm values m ust be at
least +/-9°F (5°C) than the material temperature value.
1. Press then use the arrow keys to navigate to
the component you wish to edit.
78313997ZAA
Page 79
Appendix B - ADM Setup Screens Overview
Conditioning Screen 3
This screen allows the user to configure Night Mode
operation. In Night Mode, the system will cycle on and
off periodically or turn on at a preset time. Press
and select periodic or time schemes.
When the system is in Night Mode and in an “On” cycle,
the system will circulate in low pressure. The installed
conditioning zones will be on and controlling to their
respective setpoints. When the system is in Night Mode
and in an “Off” cycle, the system will be idle. The system
will not be circulating, and the conditioning zones will not
be actively controlling temperature. When in Night
Mode, supply tanks will not fill.
Time Based Night Mode Conditioning Screen
This screen allows the user to set a specific time each
day to turn the machine on or off. The times can be set
on or off by either each day separately, Monday through
Friday where each day has the same on or off times, or
Sunday through Saturday where each day has the same
on or off times. The days can be selected by pressing
the left or right arrow keys once entered into the screen.
To set the on/off machine times:
1. Press to ente r th e scre e n
2. Press left or right arrow keys to highlight the day
selection column. Continue to press the left or right
arrow keys to select the desired day, work week
(Monday thru Friday), or full week (Sunday thru Sat
urday) duration.
3. Press the up or down arrow keys to select the
desired hour to schedule the on or off machine
times.
4. Press to enter the selected hour and select the
desired time (15 minute increments) for either
machine on or off to occur.
5. Press and select either on or off for the time
duration selected.
Bar ColorDescription
GreenMachine is ON
RedMachine is OFF
313997ZAA79
6. To erase times, repeat steps 1 thru 3 and press
once the desired time duration has been selected.
Page 80
Appendix B - ADM Setup Screens Overview
NOTE: If times are entered in the weekly schedule, indi
vidual days can not be erased.
Cold Start Up Mode
Allows the user to select what mode the machine will
enter once the cold start-up is complete. Selecting no
change will leave the machine in either standby or night
modes circulating at the set low pressure percentage.
Auto High Pressure
Changes the machine to high pressure circulation when
the mode is changed from either standby or night
modes.
Calender Time Based Night Mode Conditioning
Screen
This screen shows a summary of Time Based Night
Mode on or off times that were set by the Time Based
Night Mode Conditioning Screen.
Advanced Screen 1
This screen allows the user to set the language, date
format, current date, time, setup screens password,
screen saver delay, and turn on or off silent mode.
•Language: Available languages are English, Span
ish, French, German, Chinese, Japanese, Korean,
Russian, and Italian.
•Time: formatted in 24 hour time.
•Password: Enables the setup screens to be pass
word protected. Entering “0000” disables the fea
ture.
•Screen Saver: Enter the amount of time until the
backlight turns off. Entering “0” leave it constantly
on.
•Silent Mode: Check this box to turn off the buzzer
for key presses.
Advanced Screen 2
This screen allows the user to set the units of measure.
80313997ZAA
Page 81
Appendix B - ADM Setup Screens Overview
Numbers shown are for reference only and may
be different on your system.
Advanced Screen 3
This screen allows the user to control the availability of
some key system features.
•Disable Dispensing From Display: Check this box
to disable dispensing from the ADM. A footswitch,
dispense valve trigger, or other external signal will
be the only way to initiate a dispense.
•Disable Modifying Temp Setpoint: Check this box
to disable modifying temperature setpoints from the
Run screens. This is only applicable if temperature
control items are installed and enabled.
•Disable Operator Mode Adjustments: When this
box is checked, the user will not be able to adjust
the dispense settings in Operator Mode.
•Low Heater Temp Disables Dispense: When this
box is checked, the system will reject dispense
requests when any enabled heat zones are below
their setpoint.
•High Chiller Temp Disables Dispense: When this
box is checked, the system will disable dispensing
when any enabled chiller zones are above their set
point.
•Operator Mode Cavitation Alarm: Check this box
to enable cavitation alarms in Operator Mode. Clear
this box to disable cavitation alarms in Operator
Mode.
•Complete Dispense with Setpoint Error: When
this box is checked, the shot will continue dispens
ing even if the system never reaches the desired
setpoint.
•Enable Shot Aborted Notification: When this box
is checked, a pop-up notification will be displayed
when a shot is aborted.
•Enable Ratio Check Weight Mode Entry: This
option is for machines without flow meters. When
this box is checked, after any ratio check shot a
popup window will appear asking the user to enter
the dispensed weights. Press the Cancel button to
abort the entry or press the Enter button to record
the new values.
Advanced Screen 4
•Limit Rate on Stall to Pressure: Check this box to
allow the HFR to increase to stalling pressure at a
slower, more controlled rate.
•Enable Diagnostic Screen: Check this box to
enable the optional ADM screens, enabling USB log
downloading, and erasing USB logs. For more infor
mation about USB operation, see Appendix F - USB Operation on page 102. For more information
about the optional screens, see Diagnostic screen
on page 87.
•Low Material Disables Dispense: When this box is
checked, the current dispense will terminate and
prevent additional dispenses when the supply sys
tem indicates a low level.
Advanced Screen 5
This screen displays software information.
313997ZAA81
Page 82
Appendix C - ADM Run Screens Overview
Maintenance
HomeStatusEvents #1
Events #2
Events #...
Errors #1
Errors #2
Errors #...
* Supply tanks shown for reference only. Your sys
tem may not include supply tanks.
Appendix C - ADM Run Screens Overview
Run screens are divided into five major sections: status,
errors, events, and maintenance. The following diag ram
demonstrates the flow of the Run screens beginning
with the Home screen.
IG. 23: Run Screens Navigation Diagram
F
Home Screen
The Home screen is the first screen that displays in the
Run screens. It shows the current fluid pressure on the
A (Red) and B (Blue) fluid outlets of the pump and if
there are any active errors. If tanks are installed in the
system, the fill level is shown on each tank. The ratio is
also displayed as either Red:1 or Blue:1 depending on
which display has been setup.
To select an operating mode, press the Select Mode
button repeatedly until the desired mode is shown
then press the Enter button to select the mode.
Alternately, press the Select Mode button and use the
up and down arrow keys until the desired mode is
shown, then press the Enter button to select the
mode. The available operating modes are operator,
sequence, shot, standby, night, and disabled.
Home Screen, Disabled Mode
When this mode is selected, the machine will not be
able to dispense or condition (heat/cool) material. The
setup screens cannot be accessed while in Disabled
mode. Use the Select mode button to exit Disabled
mode.
82313997ZAA
Page 83
Appendix C - ADM Run Screens Overview
Target Flow
Ratio
Target recipe time
Home Screen, Standby Mode
In Standby Mode, the user can enable heating, park the
pumps, refill the tanks, circulate materials.
Press to change operating modes.
Press to move the pumps all the way to the left and
turns the hydraulic power pack off.
Home Screen, Shot Mode
This mode allows the user to select one of 100 pre
defined shot numbers. See Shots Screen on page 69
for information about editing shot definitions.
To use a predefined shot:
1. Enter shot mode.
2. Press and use the numeric keypad to enter
the desired shot number.
3. Press to select the shot number.
4. Press to initiate a dispense. The system will go
to high pressure mode and dispense a shot after the
pre-dispense timer, see Mix Head Operating
Details Screen on page 74, expires.
NOTE: There is a three second delay after a dispense
before another dispense can be initiated
Press or to initiate a tank refill. If a tank is fill
ing, pressing either button will abort the filling operation.
Press to stop or start the hydraulic power pack and
run the start-up process.
5. Press to switch between low and high pressure
modes without dispensing.
6. During a dispense, press to abort the dispense.
7. See Home Screen, Standby Mode on page 83 for
other button functions.
313997ZAA83
Page 84
Appendix C - ADM Run Screens Overview
Target
Flow/Pressure
Ratio
Target dispense amount
(time/volume/weight depending
on Dispense Mode)
Total of resetta
ble material
counters
B (Blue) reset
table material
counter
A (Red) resetta
ble material
counter
Operator
Setting
Ratio
Home Screen, Sequence Mode
This mode allows the user to select one of five
sequences (A-E). The progress bar on the bottom of the
screen shows the progress of a shot dispensing from
the selected sequence. See Sequences Screen on
page 71 for information about editing sequ ence defini
tions.
To use a predefined sequence:
1. Enter Sequence Mode.
2. Press the sequence letter/position selection button.
3. Use the left and right arrows to toggle between letter
and position selection. When selecting a sequence
letter (A-E), use the up and down arrow keys to
scroll through the available letters. When selecting a
sequence position, type in the desired position with
the numeric keypad. The system will reject invalid
letter/position selections.
4. Press to accept the sequence letter/position.
Home Screen, Operator Mode
This mode allows users to set a pressure or flow rate to
dispense material without using predefined shot infor
mation. Pressure or flow rate availability is dependent
on the Control Mode selection, see System Screen 2
on page 73.
1. To edit the flow rate, press . The value to
change will now be highlighted. Type the new value
then press to accept it.
5. Press the Dispense button to begin dispensing.
6. Press to skip to the next sequence position.
7. Press to abort the sequence.
8. See Home Screen, Shot Mode on page 83 for
other button functions.
2. Press to initiate a dispense. The system will go
to high pressure mode and dispense a shot after the
pre-dispense timer, see Mix Head Operating
Details Screen on page 74, expires. Press the
to stop the dispense.
NOTE: There is a three second delay after a dispense
before another dispense can be initiated.
3. If an external trigger is used, press an hold the trig
ger to initiate a dispense. Release the trigger to stop
the dispense.
4. See Home Screen, Shot Mode on page 83 for
other button functions.
84313997ZAA
Page 85
Appendix C - ADM Run Screens Overview
Home Screen, Night Mode
In Night Mode, the system will cycle on and off
periodically. The recirculation on/off cycle begins
automatically upon entering Night Mode. See
Conditioning Screen 3 on page 79.
Home Screen, Disabled Mode
When this mode is selected, the machine will not be
able to dispense or condition (heat/cool) material. The
setup screens cannot be accessed while in Disabled
mode. Use the Select mode button to exit Disabled
mode.
Status Screen
The status screen provides all of the operational func
tionality of the Home screen except for operating mode
selection. Refer to the Home screen and operating
mode descriptions for information on this functionality.
In addition to the functionality provided by the Home
screen, the Status screen also provides material condi
tioning information and control.
No setpoint box will be displayed if selected as moni
tor zone.
313997ZAA85
Page 86
Appendix C - ADM Run Screens Overview
All zones shown for reference. Only four zones may
be active at one time.
Status Screen, Conditioning Control
This screen allows users to turn on and off heat zones
individually or all at once. When a zone is on it is
actively controlling temperature. Refer to the table below
for color code definitions.
Zone
SettingColorDefinition
BlackDispense Disabled
OFF
ON
GreyDispense Allowed
YellowDispense Disabled
GreenDispense Allowed
To turn a single zone on/off:
1. Press to enter the Conditioning Control screen.
2. Use the arrows keys to navigate to the desired
zone.
3. Press to turn the selected zone on. When a
zone is on, the button will be selected. Press the
button again to turn the zone off.
To turn all zones on/off:
1. Press to enter the Conditioning Control screen.
Errors Screens
This screen shows users a list of errors that have
occurred in the system. Each error entry includes a
description and error code along with a date and time
stamp. There are 5 pages, each holding 10 errors. The
50 most recent errors are shown.
Refer to the Troubleshooting section on page 58 for a
detailed description of all of the system errors.
Events Screens
This screen shows users a list of events that have
occurred in the system. Each event includes a descrip
tion and event code along with a date and time stamp.
There are 20 pages, each holding 10 events. The 200
most recent events are shown.
2. Press the to turn on all zones. When one or
more zones are on, the button will be selected.
Press the button again to turn all zones off.
No setpoint box will be displayed if selected as moni
tor zone.
Refer to the Troubleshooting section on page 58 for a
detailed description of all of the system events.
86313997ZAA
Page 87
Appendix C - ADM Run Screens Overview
Maintenance Screen 1
This screen displays historical information for each
pump in the system. The Batch counters are resettable
and count both material usage and pump cycles. The
Total counters are not resettable by the user. They also
count both material usage and pump cycles. For mate
rial usage counters, units are displayed next to the vol
ume/weight indicator icons.
To erase a batch counter, press the Enter Screen button
and navigate to the field to be erased. Press the Erase
Single button to erase that data point. Alternatively, the
Erase All button may be pressed to erase all of the
batch data points simultaneously.
Optional Screens
The optional Diagnostic screen can be enabled in the
Advanced Screen 4 screen, see page 81.
Diagnostic
The Diagnostic screen shows status information for var
ious system components.
NOTE: In a circulation system, the pumpline must be
stopped to erase counters.
313997ZAA87
Page 88
Appendix D - ADM Error Codes
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Mix Head
A4H3
Motor
Overload
Soft Stop
DEH3
Asserted
Low Mix
MBH3
Head Oil
Level
Low
P1H3
Accumulator
Pressure
High
P4H3
Accumulator
Pressure
High Mix
T4H3
Head Oil
Temp.
M1 Material
WDF3
Rod Shift Fail
M1 Cleanout
WDD3
Rod Shift Fail
The three point calibration data
is invalid, system will operate
in weight mode but will attempt
to volumetrically calculate
weight. This will lead to
consistent shots which will be
offset for the desired dispense
amount.
Pump velocity is too low.Advisory
An over current was detected
on the output
High current has been
detected on a phase and has
been shutdown to prevent
damage
Too much current is being
drawn
from the wall
0500
02D0
A4A6
A4B5
A4A3
A4B1
A4A2
A4B4
A4A7
A4B8
A4H1
A4M1
Invalid
Weight Cal.
Data
Low Flow
Advisory
Red Blanket
Overcurrent
Blue Blanket
Overcurrent
Red Inline
Overcurrent
Blue Inline
Overcurrent
Red Hose
Overcurrent
Blue Hose
Overcurrent
Red Chiller
Overcurrent
Blue Chiller
Overcurrent
Motor Over
Current
Motor Over
ent
Curr
Error
TypeCauseSolution
Refer to AC Power Pack manual
Deviation Invalid dataRe-calibrate the machine
Pump flow setpoint is
Alarm
Alarm
Alarm
lower than one eighth of
the total pump volumes
Bad heatersMeasure resistance of heater
High voltage
Shorted Temperature
Control Module
Bad internal wiring of the
motor
Short circuit of motor
wiring
Low voltage from the wall
during load
Increase the pump flow setpoint
Measure voltage across the disconnect switch.
Voltage should measure between 190 and 264 Vac.
If temperature rises for a zone that has been disabled,
replace Temperature Control Module
Replace motor
Check wiring to the motor to ensure no bare wires are
touching and that no wires are shorted to ground
Make sure the supply line is properly sized for the
load and is above the minimum voltage requirements
88313997ZAA
Page 89
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Motor Over
A4N1
Current
Red Blanket
A7A6
Control Fault
Blue Blanket
A7B5
Control Fault
Red Inline
A7A3
Control Fault
Blue Inline
A7B1
Control Fault
Red Hose
A7A2
Control Fault
Blue Hose
A7B4
Control Fault
Red Chiller
A7A7
Control Fault
Blue Chiller
A7B8
Control Fault
No Red
A8A6
Blanket
Current
No Blue
A8B5
Blanket
Current
No Red Inline
A8A3
Current
No Blue Inline
A8B1
Current
No Red Hose
A8A2
Current
No Blue Hose
A8B4
Current
No Red
A8B7
Chiller
Current
No Blue
A8B8
Chiller
Current
Motor Over
A9C1
Current
B9C0
Small Shot
Request
B9C1The requested dispense
A hardware current fault has
occurred causing a system
shutdown
Unexpected current to
heater/chiller
No current to the conditioning
zone
A software error has occurred
commanding too much current
equested dispense
The r
amount is be
amount of the system (25% of
the combined pump volumes is
the minimum)
amount (time/volume/weight)
is below the minimum amount
of the system
low the minimum
Error
TypeCauseSolution
Alarm
Alarm
Alarm
Alarm
Deviation
Short circuit of motor
wiring
Motor rotor has become
locked
Shorted Temperature
Control Module
Tripped circuit breakerVisually check circuit breaker for a tripped condition
Low power
Cable unplugged/loose
power
Bad heater(s)Measure resistance of heater(s)
Bad Motor Control
Module code
Pumps are defined with
the wrong size
Requested shot is below
the capabilities of the
current pump setup
Short shot sizeIncrease the time/volume/weight of the shot
Check wiring to the motor to ensure no bare wires are
touching and that no wires are shorted to ground
Unplug the directional valve (so pressure will not
build) and try to move the motor again. If this
succeeds then the power pack may need to be
replaced. If the motor is still unable to move, the
bearings or hydraulic pump have likely failed in the
motor and will need to be replaced.
If temperature rises for a zone that has been disabled,
replace Temperature Control Module
Measure voltage across input terminals on power line
filter. Voltage should measure between 190 and 264
Vac
Check for loose or disconnected wires or plugs
Check for MCM software update, load latest MCM
software, if problem persists contact Graco
On the ADM go into the Setup screens to the System
screens then make sure that the pump sizes are
defined correctly
If the user has to be able to take the shot the system
must be fitted with smaller pumps
313997ZAA89
Page 90
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Comm. Error
CAA2
Red Hose
Comm. Error
CAA3
Red Inline
Comm. Error
CAA6
Red Blanket
Comm. Error
CAA7
Red Chiller
Comm. Error
CAB1
Blue Inline
Comm. Error
CAB4
Blue Hose
Comm. Error
CAB5
Blue Blanket
Comm. Error
CAB8
Blue Chiller
Comm. Error
CAC1
Motor
CAC2
CAC3
CAC4
CAC5
CAC6
CAC7
CACN
CACP
CACR
CUCN
D1A1
D4A1
D2A1
D3A1
Comm. Error
MCM
Comm. Error
Red Tank
Comm. Error
Blue Tank
Comm. Error
Mix Head
Comm. Error
Mix Head 2
Comm. Error
Ratio Monitor
Comm. Error
Gateway
Comm. Error
DGM
Comm. Error
Remote
Pendant
Gateway
Heartbeat
Error
Setpoint Not
Reached
Setpoint
Exceeded
Setpoint Not
Reached
Setpoint
Exceeded
Communication errorAlarm
Heartbeat ErrorAlarm
The set point was not reached
and the pump was shutdown
The maximum cycles per
minute of the pump has been
exceeded
The set point was not reached Deviation
The set point was exceededDeviation
Error
TypeCauseSolution
Module missing powerCheck power supply connection
Module not programmed Program the module
Module badReplace module
Deviation
Deviation
PLC is not maintaining
heartbeat
Module missing powerCheck power supply connection
Module not programmed Program the module
Module BadReplace module
Material restriction too
high for requested flow
Restriction for the pump
is not sufficient
Pump cannot reach the
requested pressure
Pump cannot reach the
requested flow
System und
change that caused a
la
rge drop in restriction
(such as new orifices)
No material in pumps
erwent a
Ensure PLC is triggering the heartbeat
Reduce flow request
Increase the restriction or lower the set point
Increase restriction in the system
Decrease restriction in the system
Erase learned System Data, found in the setup
screens under calibration
Make sure the material lines are open and have
proper feed pressure
90313997ZAA
Page 91
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
This calibration lets the MCM
know where the ends of the
Invalid Learn
D5A1
Mode Data
Position
D6A1
Sensor Fault
Red Pump
DDA1
Cavitation
Blue Pump
DDB2
Cavitation
Pump Not
DFA1
Parked
Check Flow
DR6A
Meter Red
Check Flow
DR6B
Meter Blue
Pumps Not
DSC0
Defined
F1A0
Low Flow
Red
F2A0Deviation
F1B0
Low Flow
Blue
F2B0Deviation
F4A0
High Flow
Red
F3A0Deviation
F4B0
High Flow
Blue
F3B0Deviation
Pump Failed
F7D1
to Stall
Red Low
L111
Material Level
Blue Low
L122
Material Level
Red High
L311
Material Level
Blue High
L322
Material Level
Red Auto
L6A1
Refill Timeout
Blue Auto
L6B2
Refill Timeout
pump are. If the data gathered
during this process is outside
of normal parameters the
machine will operate with a
greatly reduced stroke.
The linear position sensor is
returning data that should not
be possible during normal
operation
Cavitation was detected on the
given pump
The pump failed to reach the
park position
Flow Meter has caused a fault Deviation
The type or size of the Red or
Blue material pumps have not
been defined
Flow is below the defined low
limit
Flow is above the defined low
limit
When the pump tried to stall to
pressure the pump traveled
more than it should in normal
operation (only applies to
dead-headed system)
Low material level in tanksDeviation
High material level in tanksDeviation Defective fill valve
The tank stand has been filing
for a time greater than
expected
Error
TypeCauseSolution
Deviation
Alarm
Deviation
Deviation
Alarm
Alarm
Alarm
Alarm
Alarm
Deviation
Deviation
Recalibrate the machine Rerun the learn mode calibration
Loose/bad connection
Bad linear position
sensor
Loose/bad connection to
linear position sensor
Bad linear position
sensor
Linear position sensor
may be loose where
attached to pump
housing
Insufficient material
being supplied or
insufficient material
pressure on feed system
Debris or packout in the
incoming fluid filter
Orifices blockedClear blockage
Hose blockedClear or replace hose as necessary
Dispense valve failed to
open
Cogs in flow meter are
not turning
Cable unplugged/loose
power
Properly setup the
system
Cogs in flow
not tur
Cable unplugged/loose
power
Cogs in flow meter are
turning rapidly
Failure of the dispense
valve
Material leak
Out of materialFill tanks
Tanks low on materialFill tanks with material
Loose/broken connection
Bad level sensorReplace level sensor
No material is actually
being fed
Loose level sensor
connection
Bad level sensorReplace level sensor
meter are
ning
Check to ensure the pressure transducer is properly
installed and all wires are properly connected
Verify pump moves to limits, if problem persists
replace linear position sensor
Check to ensure the linear position sensor is properly
installed and all wires are properly connected
Replace linear position sensor
Re-tighten the sensor and re-calibrate the machine
Verify that incoming ball valves are open
Verify that feed pumps are supplying material
Inspect filter for debris of filler packout and clean or
replace as necessary
Check to make sure the dispense valve is properly
configured and connected to the MCM
Check that flow meter is matched to nominal pump
output
check of loose or disconnected wires or plugs
On the ADM go into the setup screens -> System->
then make sure that the pump type and size are set
(not --)
Check that flow meter is matched to nominal pump
output
Check for loose or disconnected wires or plugs
Check that flow meter is matched to nominal pump
output
Ensure the valve has a proper air supply and seals
properly. If not, service the valve as necessary.
Visually inspect the machine and hoses for sign of
leakage. NOTE: This error will display after 2 full
piston strokes so the leak will be substantial.
If the tanks appear to have plenty of material check to
make sure the level sensor is connected to the proper
port and that the cord is not damaged
If the tanks appear to have plenty of material check to
make sure the level sensor is connected to the proper
port and that the cord is not damaged
Make sure the feed pumps are operating properly
Check for loose or disconnected wires or plugs
313997ZAA91
Page 92
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Red Tank
L8A1
Sensor
Failure
Blue Tank
DR6B
Sensor
Failure
MBH1 Low Oil Level
Low Motor
MBN1
Performance
USB Logs
MMUX
Full
Material
N1D0
Dispense
Below Alarm
Material
Dispense
N2D0
Below
Deviation
Material
Dispense
N3D0
Above
Deviation
Material
N4D0
Dispense
Above Alarm
Pump Failed
N4A1
to Move
Thermal
P400
Pressure
Rise
A level sensor had ceased
working
The volume of oil in the tank is
below the minimum level
needed for the system to
properly operate
The motor magnetism has
decreased to the point where
performance is greatly reduced
USB log has reached the
maximum entries
Material dispense is below the
defined limit
Material dispense is above the
defined limit
The MCM attempted to move
the pump but no movement
was detected
Pressure has risen to an
unsafe level due to thermal
expansion of materials. All
conditioning zones have
automatically been turned off.
Error
TypeCauseSolution
Deviation Bad level sensorReplace level sensor
Low oil levelCheck oil level and if low add more hydraulic fluid
Loose/bad connection
Bad level sensorReplace sensor
Alarm
Leak in hydraulic driver
Leak in the hydraulic
reservoir, heat
exchanger
Advisory
Advisory
Alarm
Deviation
Deviation
Alarm
Deviation
Deviation High pressure
Prolonged exposure to
heat or high voltage
USB logs have not been
downloaded
Cogs in flow meter are
not turning
Cable unplugged/loose
power
Motor failure
Hydraulic pow
failure
Loose/bad connection to
the linear position sensor
Failure of the linear
position sensor
Motor no longer coupled
to hydraulic pump
Supply tube from
hydraulic pump to
manifold is loose or
broken
Broken motor shaftReplace motor
Over-pressure valve
dumping to tank
er pack
Check to ensure the hydraulic oil level sensor is
properly connected to the MCM and that the wire has
not been damaged
Inspect hydraulic driver end seals and early leak
detection tubing. Replace seals as necessary and
replace lost oil.
Inspect the hydraulic reservoir fittings and filter for
leaks. Repair or replace as necessary and replace
lost oil.
If error persists and performance can no longer
satisfy the user requirements the motor will need to
be replaced
Download USB logs to a memory stick
Uncheck the Enable USB errors on Advanced screen
4
Check that flow meter is matched to nominal pump
output
check for loose or disconnected wires or plugs
Visually check to ensure the pump is moving, if not
ensure the motor is wired properly
If motor is moving
building they hydraulic power pack may need
servicing
Check to ensure the linear position sensor is properly
connected to the MCM and the wiring has not be
damaged
Replace the linear position sensor
Reset coupler per specifications and retighten set
screws
Retighten or replace supply tube
Verify that no outside forces are stopping the pump
from moving, then inspect over-pressure valve for
damage or debris
Open the dispense valve manually or open the valves
to bleed pressure
but pump is not and pressure is not
92313997ZAA
Page 93
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Red Pressure
P4A1
Shutdown
The material pump pressure
exceeded the maximum
operating pressure as defined
in the setup screens
The pressure difference
between the Red and Blue
material is greater than the
defined amount
The pressure sensor is
providing invalid/no pressure
readings
Ratio monitor has detected an
out of ratio condition
P4B2
P4D0
P6A1
P6B2
R1D0
R4D0
R2D0
R3D0
Blue
Pressure
Shutdown
Pressure
Imbalance
Red Pressure
Sensor Fault
Blue
Pressure
Sensor Fault
Low Ratio
Alarm
High Ratio
Alarm
Low Ratio
Deviation
High Ratio
Deviation
Error
TypeCauseSolution
Dispense valve failed to
open
Bad dispense valveReplace dispense valve
Restriction in the
material lines
Alarm
Alarm
AlarmLoose/bad connection
Alarm
Alarm
Deviation
Invalid maximum
pressure defined
Orifices blockedClear blockage
Hose blockedClear blockage or replace hose as necessary
Dispense valve failed to
open
Dispense line is clogged
Pressure imbalance is
defined too low
Orifice blocks closed off
too much on one or both
sides
Debris in the orifice block
Material fillers may have
packed out in an orifice
Out of materialFill tanks with material
Feed system defectiveReplace defective item
Bad sensorReplace pressure transducer
No material in pumpFill tanks
Material A to Material B
is out of ratio
Check to make sure the dispense valve is properly
configured and connected to the MCM
Check to ensure there is no blockage
Make sure the requested pressure is within the max
operating pressure, which can be found on the setup
screen System 1
Check to make sure the dispense valve is properly
configured and connected to the MCM
Ensure the material flow is equally restricted on both
material lines
On the ADM go into the setup screens -> System->
and ensure the pressure imbalance value is the
maximum acceptable to prevent unnecessary alarms
which will abort dispenses
Verify that one or both of the orifice blocks dispense
when adjusted to the fully open position then adjust
accordingly
Relieve system pressure then remove the orifice from
the orifice block and inspect for debris in the cavity
Relieve system pressure and remove the orifice from
the orifice block and inspect for pack out. Clean or
replace as necessary.
Check to ensure the pressure transducer is properly
installed and all wires are properly connected
Check feed system
313997ZAA93
Page 94
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Red Tank
T1A6
Low Fluid
Temp.
Blue Tank
T1B5
Low Fluid
Temp.
Red Inline
T1A3
Low Fluid
Temp.
Blue Inline
T1B1
Low Fluid
T1A2
T1B4
T1A7
T1B8
T20X
T30X
Temp.
Red Hose
Low Fluid
Temp.
Blue Hose
Low Fluid
Temp.
Red Chiller
Low Fluid
Temp.
Blue Chiller
Low Fluid
Temp.
Dispensing
Disabled Low
Temp
Dispensing
Disabled High
Temp
Fluid temperature is below the
defined low alarm limit
Dispensing disabled because
of temperature
Error
TypeCauseSolution
Tripped circuit breakerVisually check circuit breaker for a tripped condition
Alarm
Measure voltage across input terminals on power line
Advisory
Low power
Cable unplugged/loose
power
Bad heater(s)Measure resistance of heater(s)
Temperature is out of
alarm limits
filter. Voltage should measure between 190 and 264
Vac
Check for loose or disconnected wires or plugs
Check temperature alarm limits
94313997ZAA
Page 95
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Red Hose
T2AA
Low Fluid
Temp.
Red Tank
T2AE
Low Fluid
Temp.
Red Chiller
T2AF
T2BC
T2BD
T2BG
T3AA
T3AE
T3AF
T3BC
T3BD
T3BG
T3H1
T3N1
Low Fluid
Temp.
Blue Hose
Low Fluid
Temp.
Blue tank Low
Fluid Temp.
Blue Chiller
Low Fluid
Temp.
Red Hose
High Fluid
Temp.
Red Tank
High Fluid
Temp.
Red Chiller
High Fluid
Temp.
Blue Hose
High Fluid
Temp.
Blue Tank
High Fluid
Temp.
Blue Chiller
High Fluid
Temp.
Oil Temp.
Cutback
Motor Temp.
Cutback
Fluid temperature for a monitor
zone is below the defined low
alarm limit
Fluid temperature for a monitor
zone is above the defined high
alarm limit
The hydraulic oil temperature
is approaching a level where
damage is possible so the
Motor Control Module is
limiting the output to a safe
level
Motor temperature is
approaching a level where
damage is possible so the
motor control module is limiting
the output to a safe level
Error
TypeCauseSolution
Deviation
Deviation
Advisory
Temperature is out of
alarm limits
Cable unplugged/loose
power
Inline heater is not turned
on
No power to fanCheck cord to make sure fan has power
Debris is fan or fan grill Clear debris from fan/fan grill
Low air volume from fan
No power to fanCheck cord to make sure fan has power
Debris is fan or fan grill clear debris from fan/fan grill
Low air volume from fan
Ambient environmental
conditions are too hot
Motor/pump coupler may
be rubbing on hydraulic
pump
Check temperature alarm limits
Check for loose or disconnected wires or plugs
Turn on inline heater
Try to stop fan by lightly pressing on the center with a
pencil eraser. If the fan slows down easily it will need
to be replaced
Try to stop fan by lightly pressing on the center with a
pencil eraser. If the fan slows down easily it will need
to be replaced
Move machine to an area below 120°F
Reset coupler per specifications and retighten set
screws
313997ZAA95
Page 96
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Red Hose
T4A2
High Fluid
Temp.
Red Inline
T4A3
High Fluid
Temp.
Red Tank
T4A6
High Fluid
Temp.
Red Chiller
T4A7
High Fluid
T4B1
T4B4
T4B5
T4B8
T4C1
T4H1
T4N1
T6A6
T6B5
T6A3
T6B1
T6A2
T6B4
T6A7
T6B8
Temp.
Blue Inline
High Fluid
Temp.
Blue Hose
High Fluid
Temp.
Blue Tank
High Fluid
Temp.
Blue Chiller
High Fluid
Temp.
Motor Control
High Temp.
Oil Temp.
Shutdown
Motor Temp.
Shutdown
Red Tank
RTD Fault
Blue Tank
RTD Fault
Red Inline
RTD Fault
Blue Inline
RTD Fault
Red Hose
S F
FT
Blue Hose
FTS Fault
Red Chiller
RTD Fault
Blue Chiller
RTD Fault
Fluid temperature is above the
defined high alarm limit
The temperature the MCM has
reached a level where product
life will be decreased
drastically and has been
shutdown for protection
The hydraulic oil is at a
temperature where
performance is impacted
significantly and has resulted
in a system shutdown
Motor temperature is too high
and system has been
shutdown to prevent possible
damage
RTD 1 is giving no or invalid
data
ault
Error
TypeCauseSolution
Alarm
Alarm
Alarm
Alarm
Alarm
Defective Temperature
Control Module
Defective RTDReplace RTD
Loose connectionsTighten connections
No power to fanCheck cord to make sure fan has power
Debris is fan or heatsink Clear debris from fan or heatsink
Low air volume from fan
Motor may be damaged Replace motor
Debris is packed in the
MCM’s heat sink fins
No Power to FanCheck cord to make sure fan has power
Debris in fan or fan grill Clear debris from fan/fan grill
Low air volume from fan
No power to fanCheck cord to make sure fan has power
Debris is fan or fan grill Clear debris from fan/fan grill
Low air volume from fan
Ambient environmental
conditions are too hot
Motor may be damaged Motor may need to be replaced
Loose or bad connection Check RTD wiring
Bad RTDReplace RTD
Replace Power Temperature Control Module
Try to stop fan by lightly pressing on the center with a
pencil eraser. If the fan slows down easily it will need
to be replaced
Clear debris from MCM heat sink fins
Try to stop fan by lightly pressing on the center with a
pencil eraser. If the fan slows down easily it will need
to be replaced
Try to stop fan by lightly pressing on the center with a
pencil eraser. If the fan slows down easily it will need
to be replaced
Move machine to an area below 120°F
96313997ZAA
Page 97
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Red Blanket
T6C6
RTD Fault
Blue Blanket
T6C7
T6C8
T8A6
T8A3
T8B1
T8A2
T8B4
T8A7
T8B8
T9A6
T9B5
T9A3
T9B1
T9C6
T9C5
T9C3
C1
T9
T9C2
T9C4
T9C7
T9C8
RTD Fault
Red Chiller
RTD Fault
Blue Chiller
RTD Fault
No Heat Red
Tank
No Heat Blue
Tank
No Heat Red
Inline
No Heat Blue
Inline
No Heat Red
Hose
No Heat Blue
Hose
No Cooling
Red Chiller
No Cooling
Blue Chiller
Red Blanket
Temp. Cutoff
Blue Blanket
Temp. Cutoff
Red Inline
Temp. Cutoff
Blue Inline
Temp. Cutoff
Red Blanket
Ctrl
Shutdown
Blue Blanket
Ctrl
Shutdown
Red Inline
Ctrl
Shutdown
Blue In
Ctrl
Shutdown
Red Hose Ctrl
Shutdown
Blue Hose
Ctrl
Shutdown
Red Chiller
Ctrl
Shutdown
Blue Chiller
Ctrl
Shutdown
RTD 2 is giving no or invalid
data
No temperature riseAlarm
No temperature declineAlarm
Heater overtemperature cutoff Alarm
line
PCB over temperatureAlarm
Error
TypeCauseSolution
Loose or bad connection Check RTD wiringT6C5
Alarm
Bad RTDReplace RTD
Tripped circuit breakerVisually check circuit breaker for a tripped conditionT8B5
Measure voltage across input terminals on power line
Low Power
Cable unplugged/loose
power
Bad heater(s)Measure resistance of heater(s)
Tripped circuit breakerVisually check circuit breaker for a tripped condition
Defective cooling valve
Chilled water supply off Turn on chilled water supply
Loose or bad connection Check RTD wiring
Defective RTDReplace RTD
Defective High Power
Temperature Control
Module
Loose connectionsTighten connections
Overheated
Temperature Control
Module
filter. Voltage should measure between 190 and 264
Vac
Check for loose or disconnected wires or plugs
Disconnect the valve and measure the voltage across
the wires when the chiller is running to ensure 24V is
being delivered to the valve. If so, the cooling valve
will likely need replacing.
Replace High Power Temperature Control Module
Turn conditioning zone off. Wait a few minutes. If the
condition does not clear or regenerates consistently,
replace heater module
313997ZAA97
Page 98
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
The voltage to the MCM has
dropped to a level where
performance is greatly affected
High line voltageAlarm
The voltage to the MCM has
reached an unsafe level and
has been shutdown in an
attempt to prevent damage
The ADM tried to upload a
system settings file but failed
An error has been detected on
the motor position sensor
The material rod failed to move
on a straight head
The motor has reached a
speed that should not be
reached in normal operation
and was shutdown to prevent
possible damage
V1H1
V4A6
V4B5
V4A3
V4B1
V4A2
V4B4
V4A7
V4B8
V4H0
W0U0
WBH1
WDF1
WKH1
Motor Control
Undervoltage
Red Blanket
Overvoltage
Blue Blanket
Overvoltage
Red Inline
Overvoltage
Blue Inline
Overvoltage
Red Hose
Overvoltage
Blue Hose
Overvoltage
Red Chiller
Overvoltage
Blue Chiller
Overvoltage
Motor Control
Overvoltage
USB Update
Failed
Motor
Encoder Fault
M1 Material
Rod Shift Fail
High Motor
Speed
Error
TypeCauseSolution
Tripped circuit breakerVisually check circuit breaker for a tripped condition
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Supply lines providing
low voltage
Incoming line voltage is
too high
Supply lines providing
high voltage
System Settings file is
corrupt
System Settings file is
intended for another
system
Failing sensorsIf error persists the motor will need to be replaced
Loose connection
Stuck material rodCheck that material rod is able to freely move
No power to directional
valve
No power to directional
valve
Bad directional valve
connection
Directional valve failure The directional valve will nee d to be replaced
Hydraulic power pack
failure
Defective encoderReplace encoder
Motor no longer coupled
to hydraulic pump
Supply tube from
hydraulic pump to
manifold is loose or
broken
Broken motor shaftReplace motor
Check incoming voltage to ensure it is above the
minimum operating voltage
Measure voltage across disconnect switch. Voltage
should measure between 190 and 264 Vac.
Check incoming voltage to ensure it is below the
maximum operating voltage
Replace the system settings file with a backup or new
file
Ensure that the first line in the settings.txt file contains
the text GMS
system update file.
Ensure the d-sub connector to the motor is connected
and the wiring is intact
Make sure the directional valve has power
Make sure the directional valve has power
Make sure the cord to the directional valve is
connected to the correct port and the cord is not
damaged
The hydraulic power pack will need repair
Reset coupler per specifications and retighten set
screws
Retighten or replace supply tube
™
. If not replace the file with the proper
98313997ZAA
Page 99
Appendix D - ADM Error Codes
Error
Code Error Name Error Description
Red Tank
WM06
Con. Fault
Blue Tank
WM05
Con. Fault
Red Inline
WM03
Con. Fault
Blue Inline
WM01
WM02
WM04
WM07
WM08
WMA6
WMB5
WMC6
WMC5
WMC3
WMC1
WMC2
WMC4
WMC7
WMC8
WMH1
WSC0
Con. Fault
Red Hose
Con. Fault
Blue Hose
Con. Fault
Red Chiller
Con. Fault
Blue Chiller
Con. Fault
Red Blanket
High Temp.
Blue Blanket
High Temp.
Red Tank
Con. Fault
Blue Tank
Con. Fault
Red Inline
Con. Fault
Blue Inline
Con. Fault
Red Hose
Con. Fault
Blue Hose
Con. Fault
Red Chiller
Con. Fault
Blue Chiller
Con. Fault
Motor
Controller
Fault
Invalid
Setpoint
Request
Invalid Gel
Timer
Definition
High current to relay 1AlarmBroken contactorReplace contactor
Tank blanket is above the
defined high alarm limit
Unexpected current to relay 1 AlarmShorted module
A general fault has occurred
within the MCM
The requested controlling
value (pressure or flow) is
outside the limits of the system
The shot that was entered for
the gel timer is not a valid shot.
This must be fixed before the
gel timer will function properly
Error
TypeCauseSolution
Defective RTDReplace RTD
Alarm
Deviation Inter nal hardware failure
Deviation
Deviation
Defective High Power
Temperature Control
Module
Loose connectionsTighten connections
System incorrectly setup
Shot incorrectly defined
Gel timer shot is below
the minimum dispense
amount or set for a
invalid pressure/flow
The MCM has
mined that the gel
deter
timer shot will not be able
to be executed based
para
meters entered in
the ADM
Replace High Power Temperature Control Module
If temperature is being affected by a zone that has
been disabled, replace heat module
Cycle power, if the error persists the MCM will need to
be replaced
On the ADM go into the setup screens -> System->
and ensure that all pages have properly defined
values
Redefine shot with control parameters within the limits
of the system
Select a different shot or modify existing shot data
If you are certain that the shot is within parameters,
try running the Learn Mode routine found in the setup
screen Calibration. If the error persists, a gel shot with
reduced control parameters is required.
313997ZAA99
Page 100
Appendix E - System Events
Appendix E - System Events
Event Code and
StringTriggers
REL00: System Pow
ered On
REM00: System Pow
ered Off
REB00: Stop Button
Pressed
RECH0: Learn Mode
Executed
RENN0: Automatic
Cal. Performed
RECA1: Red Material
SG Modified
RECB2: Blue Material
SG Modified
RENC1: Cal. Point 1
Weight Entered
RENC2: Cal. Point 2
Weight Entered
RENC4: Cal. Point 1
Weight Erased
RENC5: Cal. Point 2
Weight Erased
REND0: Ratio Check
Dispense
REA00: Disp.
Occurred (Shot #)
REH00: Gel Timer
Dispense
RER01: Shot Count
Reset
RER02: Seq. Posi
tion Count Reset
RERA1: Red Material
Volume Reset
RERB1: Blue Material
Volume Reset
RERA2: Red Material
Weight Reset
RERB2: Blue Material
Weight Reset
RERA3: Red Cycle
Count Reset
RERB3: Blue Cycle
Count Reset
REQU1: Settings
Downloaded
The System was powered on.
The System was powered off.
The Red stop button was pressed on
the Advanced Display Module.
A learn mode calibration was suc
cessfully completed.
The system was successfully charac
terized with the Automatic calibration.
The Red materials specific gravity
was modified.
The Blue materials specific gravity
was modified.
A value for the first point in the three
point calibration was entered.
A value for the second point in the
three point calibration was entered.
The running average for point one of
the three point calibration was erased.
The running average for point two of
the three point calibration was erased.
A ratio check shot was dispensed
from the ratio check calibration
screen.
A dispense has occurred of the given
shot number.
The gel timer expired and the system
automatically took the gel shot.
A counter from the shot counters
maintenance page was erased
A counter from the sequence counters
maintenance page was erased
The resettable totalizer for the Red
material volume was reset to zero.
The resettable totalizer for the Blue
material volume was reset to zero.
The resettable totalizer for the Red
material weight was reset to zero.
The resettable totalizer for the Blue
material weight was reset to zero.
The resettable cycle counter for the
Red pump was reset to zero.
The resettable cycle counter for the
Blue pump was reset to zero.
The system settings were success
fully transferred from the ADM to a
USB drive.
Event Code and
StringTriggers
REQU2: Settings
Uploaded
REQU3: Language
Downloaded
REQU4: Language
Uploaded
REQU5: Logs Down
loaded
REAR0: Night Mode
Recirc On
REBR0: Night Mode
Recirc Off
The system settings file was success
fully transferred from the USB drive to
the ADM.
The custom language file was suc
cessfully transferred from the ADM to
a USB drive.
The custom language file was suc
cessfully transferred from the USB
drive to the ADM.
The Error/Event and Shot data logs
were successfully transferred from the
ADM to a USB drive.
While in night mode the system has
automatically entered a low recircula
tion mode and attempted to turn on all
enabled conditioning zones.
While in night mode the system has
automatically stopped the low recircu
lation mode and turned off all condi
tioning zones.
100313997ZAA
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.