300 psi (2.1 MPa, 21 bar) Maximum Fluid Working Pressure
Meter Part No.SeriesModelFlow Range
249426BG2500.02 to 1.0 gpm (75 to 3800 cc/min)
249427BG250HR0.01 to 0.5 gpm (38 to 1900 cc/min)
High Pressure Fluid Meters
4000 psi (28 MPa, 280 bar) Maximum Fluid Working Pressure
Meter Part No.SeriesModelFlow Range
289813BG30000.02 to 1.0 gpm (75 to 3800 cc/min)
289814BG3000HR0.01 to 0.5 gpm (38 to 1900 cc/min)
26A119AG3000A0.02 to 1.0 gpm (75 to 3800 cc/min)
Meter Models
High Pressure Solvent Meter
3000 psi (21 MPa, 210 bar) Maximum Fluid Working Pressure
Meter Part No.SeriesModelFlow Range
258718BS30000.01 to 0.42 gpm (38 to 1600 cc/min)
Meter Kits
G3000 Fluid Meter Kits
For use with ProMix 2KS Wall Fluid Panel. Kits include
meter, cable, fluid tube, check valve, mounting bracket
and hardware.
Kit Part No.Meter
15V804Part No. 289813 G3000 Meter
15V827Part No. 289814 G3000HR Meter
826216Part No. 26A119 G3000A Meter
Solvent Meter Kit
For use with ProMix 2KS Wall Fluid Panel. Kit includes
meter, cable, fluid hose, check valve, fittings, mounting
bracket and hardware.
Kit Part No.Meter
280555Part No. 258718 S3000 Solvent Meter
308778Y3
Page 4
Warnings
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When
these symbols appear in the body of this manual, refer back to these Warnings. Product-specific hazard symbols and
warnings not covered in this section may appear throughout the body of this manual where applicable.
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help prevent
fire and explosion:
•Use equipment only in well ventilated area.
•Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop
cloths (potential static arc).
•Keep work area free of debris, including solvent, rags and gasoline.
•Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes
are present.
•Ground all equipment in the work area. See Grounding instructions.
•Use only grounded hoses.
•Hold gun firmly to side of grounded pail when triggering into pail. Do not use pail liners unless they
are antistatic or conductive.
•Stop operation immediately if static sparking occurs or you feel a shock. Do not use equipment
until you identify and correct the problem.
•Keep a working fire extinguisher in the work area.
INTRINSIC SAFETY
Intrinsically safe equipment that is installed improperly or connected to non-intrinsically safe equipment
will create a hazardous condition and can cause fire, explosion, or electric shock. Follow local regulations and the following safety requirements.
•Be sure your installation complies with national, state, and local codes for the installation of electrical
apparatus in a Class I, Group D, Division 1 Hazardous Location, including all of the local safety fire
codes, NFPA 33, NEC 500 and 516, and OSHA 1910.107.
•Equipment that comes in contact with the safety barrier’s intrinsically safe terminals must be rated
for Intrinsic Safety. This includes DC voltage meters, ohmmeters, cables, and connections. Remove
the unit from the hazardous area when troubleshooting.
•If a printer, computer, or other electrical component is connected, it must be used in conjunction with
a safety barrier.
•Without the safety barrier, the equipment is no longer intrinsically safe and must not be operated in
hazardous locations, as defined in article 500 of the National Electrical Code (USA) or your local
electrical code.
•Do not install equipment approved only for a non-hazardous location in a hazardous area. See the
ID label for the intrinsic safety rating for the flow meter sensor.
•Ground the intrinsically safe power supply. A voltage limiting safety barrier must be properly
grounded to be effective. For proper grounding, use the ground wire provided (or a 12 gauge minimum ground wire), and the barrier’s ground must be within 1 ohm of true earth ground.
•Do not operate the safety barrier module with the cover removed.
•Never use the flow meter with an electrostatic gun isolation stand.
4308778Y
Page 5
Warnings
SPECIAL CONDITIONS FOR SAFE USE
Equipment must comply with the following conditions to avoid a hazardous condition which can cause
fire, explosion, or electric shock:
•Sensor housing is of aluminum construction. Precautions must be taken to avoid impacts or contact
with moving parts.
SKIN INJECTION HAZARD
High-pressure fluid from gun, hose leaks, or ruptured components will pierce skin. This may look like just
a cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment.
•Do not spray without tip guard and trigger guard installed.
•Engage trigger lock when not spraying.
•Do not point gun at anyone or at any part of the body.
•Do not put your hand over the spray tip.
•Do not stop or deflect leaks with your hand, body, glove, or rag.
•Follow the Pressure Relief Procedure when you stop spraying and before cleaning, checking, or
servicing equipment.
•Tighten all fluid connections before operating the equipment.
•Check hoses and couplings daily. Replace worn or damaged parts immediately.
PRESSURIZED EQUIPMENT HAZARD
Fluid from the equipment, leaks, or ruptured components can splash in the eyes or on skin and cause
serious injury.
•Follow the Pressure Relief Procedure when you stop spraying/dispensing and before cleaning,
checking, or servicing equipment.
•Tighten all fluid connections before operating the equipment.
•Check hoses, tubes, and couplings daily. Replace worn or damaged parts immediately.
308778Y5
Page 6
Warnings
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
•Do not operate the unit when fatigued or under the influence of drugs or alcohol.
•Do not exceed the maximum working pressure or temperature rating of the lowest rated system
component. See Technical Data in all equipment manuals.
•Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all
equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information
about your material, request MSDS from distributor or retailer.
•Do not leave the work area while equipment is energized or under pressure.
•Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
•Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
•Do not alter or modify equipment. Alterations or modifications may void agency approvals and create
safety hazards.
•Make sure all equipment is rated and approved for the environment in which you are using it.
•Use equipment only for its intended purpose. Call your distributor for information.
•Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
•Do not kink or over bend hoses or use hoses to pull equipment.
•Keep children and animals away from work area.
•Comply with all applicable safety regulations.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or
swallowed.
•Read MSDSs to know the specific hazards of the fluids you are using.
•Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
•Always wear chemically impermeable gloves when spraying, dispensing, or cleaning equipment.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including
eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective equipment includes but is
not limited to:
•Protective eyewear, and hearing protection.
•Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer.
6308778Y
Page 7
Installation
Cable
(see Table 1 on page 9
for available cables)
Electronic Sensor
Flow Meter
Fluid Line
Fluid Shutoff Valve
on outlet side
Ground Sheath
Check Valve
Fluid Shutoff Valve
on inlet side
7379A
Improper wiring can cause fire and explosion, electric
shock, or other serious injury.
•Disconnect power source before installing.
Installation
Installing the Flow Meter
NOTE: You must assemble the meter sensor to the
meter body before connecting the cable to the sensor for
the meter to function properly.
•Flow volume can only be measured at the location
where the flow meter is installed.
•All electrical equipment must only be installed by
a qualified electrician.
•Understand and follow your local code and safety
regulations for hazardous location wiring of intrinsically safe circuits.
Dust and Foreign Matter
Avoid having dust or foreign matter enter the flow meter
by taking the following precautions:
•Thoroughly flush the fluid supply lines before installing the flow meter.
•When installing fittings, make sure that no sealing
tape overlaps into the inside of the pipe.
•Install a 100 mesh fluid filter upstream of the flow
meter.
•The Fluid Flow Meters are intrinsically safe for Hazardous (Classified) Locations, when installed with
an intrinsically safe power device and wiring:
Class I, Div I, Group D, T3 (US and Canada)
Class I, Zone I Group IIA T3 (ATEX only)
TA = 0°C to 60°C
Refer to ANSI standards ISA-RP12.6, NEC Article
504 and the Canadian Electrical Code Appendix F.
•Do not use more than 200 ft. (61 m) of cable.
•Refer to F
connectors, and fluid shutoff valves. Install a check
valve to prevent backflow. The arrows on the flow
meter and check valve show the direction of fluid
flow.
•The shutoff valves allow you to isolate the meter for
service.
•Refer to Dimensions on page 20 and Technical Data on page 22 for dimension, inlet/outlet size,
temperature and other specifications.
CLASS I, DIV I, GROUP D, T3 (US AND CANADA)
CLASS I, ZONE I GROUP IIA T3 (ATEX ONLY)
TA = 0°C TO 60°C
Safety
Barrier
Flow Meter Body
G3000
G3000HR
G250
G250HR
S3000
G3000A
250 VAC Maximum
Supply Voltage
Power 10-30 Vdc (Red), Ref. to Common
Sensor - 24W650
24W651
Ground
(Grounded thru meter
mounting bracket to
system ground.)
NOTE: See Intrinsically Safe Installation Requirements above.
WARNING: Substitution of components may impair intrinsic safety. For installation,
maintenance or operation instructions, see instruction manual.
ADVERTISSEMENT: La substitution de composants peut compromettre la securite
intrinseque.
ATEX CERTIFICATE #ITS12ATEX27565X
SYSTEM ASSEMBLY CERTIFICATE
Ground
System
Common (Black)
Signal 0-30 Vdc (White), Ref. to Common
Cable Shield
Sensor Entity Parameters
(per barrier channel):
Ui/Umax = 30 Vdc
Ii/Imax = 110 mA
Ci = 0.4 microFarads
Li = 0.01 mH
Pi = 0.8 W
24M600
Control Drawing
Intrinsically Safe Installation
Requirements
See FIG. 2.
1. The non-intrinsically safe terminals must not be connected to any device which uses or generates more
than 250 Vrms or dc unless it has been determined
that the voltage has been adequately isolated.
2. The installation must meet the requirements of the
National Electric Code, Canadian Electrical Code
Part I, NFPA 70, Article 504 Resp., Article 505 and
ANSI/ISA 12.06.01.
3. Multiple earthing of components is allowed only if
high integrity equipotential system is realized
between the points of bonding.
4. Do not operate system with safety barrier cover
removed.
5. For ATEX, install per EN 60079-14 and applicable
local and national codes.
6. Cable used to connect sensor and safety barrier
must take capacitance and inductance into account.
The maximum capacitance of the barrier is to be
greater than the cable capacitance plus the sensor
capacitance (Ci). The maximum inductance of the
barrier is to be greater than the cable inductance
plus the sensor inductance (Li).
Find cable capacitance and inductance by:
a. Using the most exacting electrical parameters
provided by the cable manufacturer.
b. Using the electrical parameters determined by
measurement of a sample.
7. Product meets 500 Vac isolation test between the
intrinsically safe circuits and earth ground.
F
IG. 2. Intrinsically Safe Installation
8308778Y
Page 9
Grounding
TI26838a
1+10-30 Vdc Supply (red)
2Ground (black)
3Signal Out (white)
1
3
2
The equipment must be grounded to reduce the
risk of static sparking and electric shock. Electric or
static sparking can cause fumes to ignite or
explode. Improper grounding can cause electric
shock. Grounding provides an escape wire for the
electric current.
1. Ground the flow meter by connecting a grounded
cable to the meter housing or sensor.
Have a qualified electrician check the electrical
grounding continuity between the flow meter sensor
and a true earth ground; remove the cable connector from the sensor and measure the resistance
from the cable connector Pin 2 to true earth ground.
Refer to F
IG. 3.
Installation
a. Mount the meter to a grounded conductive sur-
face, or
b. Connect the conductive fluid hose to the meter
inlet and outlet, or
c. Connect a ground wire to the meter's M6
mounting holes.
3. Never use the flow meter with an electrostatic gun
isolation stand.
If the resistance is greater than 25 ohms, check the
cable ground connection. Refer to F
IG. 3. Reconnect
the ground sheath or replace the cable. Do not operate the system until the problem is corrected.
2. Always ground the meter, using one of the following
options:
Table 1: Meter Cables
Cable Part No.LengthFerritePlatform
17C7435 ft (1.52 m)Various
17C91042 in. (1029 mm)15D906ProMix 2KS
17C8876 ft (1.83 m)Various
17C88850 ft (15.25 m)Various
17C889150 ft (45.75 m)Various
24Y434 Adaptor - Not included with cables (see note)
NOTE: These cables have a metal connector, which will only mate with a sensor that
also has a metal connector. Adaptor 24Y434 is required to connect an existing cable
with a plastic connector to a replacement sensor, which has a metal connector.
FIG. 3
Meter Cables and Adaptor
See Table 1 for available meter cables or the adaptor for
use with cables with a black plastic connector and a
replacement sensor.
308778Y9
Adaptor 24Y434 purchased separately.
Page 10
Operation
Operation
Pressure Relief Procedure
This equipment stays pressurized until pressure is
manually relieved. To help prevent serious injury from
pressurized fluid, such as skin injection, splashing
fluid and moving parts, follow the Pressure Relief Procedure when you stop spraying and before cleaning,
checking, or servicing the equipment.
1. Shut off the fluid supply to the meter.
2. Shut off all electrical power to the fluid system.
3. Follow the Pressure Relief Procedure for your fluid
system dispensing device.
Flow Meter Function
This is a positive displacement, gear flow meter. The
gear flow meter is highly accurate, even with low flow
rates. The fluid flowing through the meter rotates the
gears. The gear tooth is picked up by a sensor device,
which produces an impulse for every gear tooth passing
by.
Flow Volume Range
The G3000v G3000A, and G250 meters flow volume
range is 0.02-1.0 gal./min. (75-3800 cc/min.).
The G3000HR and G250HR meters flow volume range
is 0.01-0.5 gal./min. (38-1900 cc/min.).
The S3000 solvent meter flow volume range is
0.01-0.42 gpm (38-1600 cc/min).
NOTICE
The flow meter gears and bearings can be damaged
if they rotate at excessive speeds. To avoid high
speed rotation, open the fluid valve gradually. Do not
over-speed the meter with air or fluid. Do not use
compressed air to rotate flow meter gears. Do not
exceed the meter’s maximum flow rate.
Checking the Meter Accuracy
1. To check the accuracy of the meter, turn your gun
fan and atomizing air off, then trigger the fluid into a
graduated cylinder; dispense at least 500 cc of fluid.
2. Measure the volume of fluid in the beaker in
cubic-centimeters (cc) and read the volume on the
flow meter monitor.
G3000, G3000A, and G250: If the flow meter scale
Recommended Usage
Do not exceed the maximum working pressure of your
meter or any component or accessory in your system.
•See the Technical Data on page 22 for fluid and
ambient temperature limits.
•Only use the flow meter with fluids that are compatible with the “Wetted Parts” listed in the Technical Data.
10308778Y
factor is not between 0.112-0.140 cc/pulse, follow
the cleaning procedure on page 13, then recalibrate
the flow meter.
G3000HR and G250HR: If the flow meter scale factor is not between 0.05-0.07 cc/pulse, follow the
cleaning procedure on page 13, then recalibrate the
flow meter.
S3000: If the solvent meter scale factor is not
between 0.019-0.022 cc/pulse, follow the cleaning
procedure on page 13, then recalibrate the flow
meter.
Page 11
Troubleshooting
ProblemCauseSolution
Troubleshooting
Before servicing this equipment always make sure to
relieve the pressure.
NOTE: The sensor is not a serviceable part. Replace it if
it is malfunctioning.
No flow volume displayed at monitoring unit.
Fluid is not flowing.Clogs in fluid line or in meter.Clean fluid line and/or meter; see
Flow volume is too low to measure.Increase flow volume.
Fluid is not flowing.Repair.
Damaged cable.Replace cable.
Improper input voltage to sensor.Make sure input voltage is 10-30
Vdc.
Damaged sensor.Replace sensor if it is malfunctioning.
Maintenance on page 12.
Gears worn or damaged.Repair meter; see Maintenance on
page 12.
308778Y11
Page 12
Maintenance
Maintenance
Improper wiring can cause fire and explosion, electric
shock, or other serious injury.
Flushing
•Disconnect power source before installing.
•All electrical equipment must only be installed by
a qualified electrician.
•Understand and follow your local code and safety
regulations for hazardous location wiring of intrinsically safe circuits.
NOTICE
Do not immerse the meter in solvent with the electronic sensor installed. Solvent could damage the
electrical components.
Air purge is not recommended for any gear-type flow
meter. Air purges do not provide the lubrication the
meter gears require.
Residue Build-up on the Meter
Gears
Residue build-up may cause the meter gears to bind or
stop rotating, which decreases the meter accuracy and
makes meter recalibration necessary. As more build-up
occurs, recalibration is required more often.
Flush the fluid supply line and meter fluid reservoir daily
with a compatible solvent as instructed below.
1. Follow the Pressure Relief Procedure, on page 10.
2. Connect the fluid line to the solvent supply unit.
3. Flush the meter until it is clean.
4. Follow the Pressure Relief Procedure, then disconnect the fluid line from the solvent supply unit.
5. Reconnect the fluid line to the fluid (paint) supply.
6. Turn on the fluid supply.
7. Operate until the meter and fluid line are free of solvent.
The frequency that your meter requires cleaning
depends on the type of fluid being used. Excessive residue build-up usually means that you are using improper
cleaning solvents and/or cleaning sequences or processes.
•Check the meter routinely to develop the correct
cleaning schedule.
•Use the proper cleaning solvent for the fluid being
metered.
12308778Y
Page 13
Maintenance
Cleaning or Servicing the Meter
Chamber
NOTICE
Clean and service the meter at a clean workbench.
Use only lint-free cloth on parts.
Installing and servicing this equipment requires
access to parts that may cause electric shock or other
serious injury if the work is not performed properly. Do
not install or service this equipment unless you are
trained and qualified.
Use only genuine Graco replacement parts. Substitution of components may impair intrinsic safety. This
could result in a failure which causes serious injury
and/or substantial property damage.
NOTICE
To avoid damaging the shafts, keep the housings parallel to each other when separating them; do not rock
the housings from side to side. Do not use chisels or
screwdrivers to split and pry apart the housings.
7. Remove and inspect the gears and shafts. Clean
the meter parts with solvent.
8. Reassemble the gears and shafts into the lower
housing in the position they were removed from.
Check the gears for free and easy rotation.
9. Make sure the two locating pins are in place.
10. Assemble the two meter housings, making sure to
keep them parallel to each other.
11. Install the screws. Tighten them oppositely and
evenly. Tighten to 12 ft-lb (16 N•m) for 289813,
289814, and 26A119. Tighten to 42 in-lb (4.7 N•m)
for 249426 and 249427. Do not over-tighten.
12. After re-assembling the meter, test the gear rotation
by applying a brief air blast to the meter inlet. You
should clearly hear the gears spin.
1. Follow the Pressure Relief Procedure, on page 10.
Then close the fluid shut-off valve on each side of
the meter.
2. Disconnect the cable from the electronic sensor
device.
3. Disconnect both fluid line fittings and remove the
meter from the fluid line.
4. Loosen the two screws and remove the electronic
sensor device from the flow meter upper housing.
See the Parts drawings, pages 16-18.
5. Loosen the screws. Keep a few threads of two
opposing bolts engaged to minimize the torque
stress on the shafts when you separate the meter
housings.
6. Hold onto the upper housing and gently tap the
opposing bolts to separate the lower housing.
13. Set the electronic sensor on the upper housing and
tighten the two screws hand-tight, about 27-57 in-lb
(3.1-6.4 N•m). Do not over-tighten.
14. Attach fluid lines and sensor cable.
15. Open fluid shut-off valves.
Replacing the Electronic Sensor
1. Follow the Pressure Relief Procedure, on page 10.
Then close the fluid shut-off valve on each side of
the meter.
2. Disconnect the cable from the electronic sensor
device.
3. Loosen the two screws and remove the electronic
sensor device from the flow meter upper housing.
See the Parts drawings, pages 16-18.
4. Set the electronic sensor on the upper housing and
tighten the two screws hand-tight, about 27-57 in-lb
(3.1-6.4 N•m). Do not over-tighten.
308778Y13
5. Attach sensor cable.
Page 14
Maintenance
.09 mm stack {
One ShimThree Shims
0.1 mm
TI16684aTI16685a
(shims may be
in any order)
Cleaning or Servicing the
Solvent Meter
NOTICE
Clean and service the meter at a clean workbench.
Use only lint-free cloth on parts.
Installing and servicing this equipment requires
access to parts that may cause electric shock or other
serious injury if the work is not performed properly. Do
not install or service this equipment unless you are
trained and qualified.
Use only genuine Graco replacement parts. Substitution of components may impair intrinsic safety. This
could result in a failure which causes serious injury
and/or substantial property damage.
NOTE: See F
Some meters use one 0.1 mm shim (3c) above each
gear (3d) and one below. Other meters stack three
shims (.02 and .05 mm, for a total shim height of .09
mm) above and below each gear. When replacing
shims, always maintain the configuration used on your
meter.
FIG. 4. Shim Configurations
7. Remove the o-ring (3e). Carefully remove the
gear/bearing assemblies (3d). Remove the shims
(3c).
IG. 4. Two shim configurations are used.
1. Follow the Pressure Relief Procedure, on page 10.
Then close the fluid shut-off valve on each side of
the meter.
2. Disconnect the cable from the electronic sensor
device.
3. Disconnect both fluid line fittings and remove the
meter from the fluid line.
4. Loosen the two screws and remove the electronic
sensor device from the flow meter upper housing.
See the Parts drawing, page 18.
5. Unscrew the 8 screws (3a) from the base (3b) of the
meter.
6. Carefully remove the cover (3f). Turn it over and
remove the shims (3c).
NOTE: Do not remove the gear shafts (S) or the gear
bearings (B).
8. Clean the meter parts with solvent. Do not use
aggressive cleaning agents. Ultrasonic cleaning is
recommended for the gear/bearing assemblies. Dry
all parts thoroughly after cleaning.
9. Place the bottom shims (3c) on the shafts (S). Maintain the configuration used on your meter.
10. Install the gear/bearing assemblies (3d) on the
shafts. Install the top shims (3c). Maintain the configuration used on your meter.
11. Insert the o-ring (3e) in the groove of the cover (3f).
Carefully mount the cover on the base (3b).
12. Install the screws (3a). Tighten them oppositely and
evenly, to 11 ft-lb (15 N•m). Do not over-tighten.
13. After tightening all screws, insert a plastic pick
through the meter inlet or outlet and check that the
gears can turn freely.
14. Set the electronic sensor on the cover and tighten
the two screws hand-tight, about 27-57 in-lb
(3.1-6.4 N•m). Do not over-tighten.
14308778Y
Page 15
Parts
101
104
109
108
105
106
110
TI12427a
101
104
109
108
105
106
110
TI14676b
102
103
Flow Meter Kits, for ProMix 2KS Wall Fluid Panel
Parts
15V804 G3000 Meter Kit
826212 G3000A Meter Kit
15V827 G3000HR Meter Kit
Ref.
No.Part No. DescriptionQty
101289813
26A119
289814
104501867
24T894
10517C910HARNESS, cable, with connector1
106114182SCREW, machine, hex flange hd;
10815U749BRACKET, mounting1
10915U750TUBE, assembly; sst; 1/2 in. (13
25A517HOSE (826212)1
110C19798SCREW, cap, socket-hd; 1/4-20 x
111121907FITTING, NIPPLE, HEX
METER, gear, G3000; used on
15V804; see page 16
METER, gear, G3000A; used on
826212; see page 16
METER, gear, G3000HR; used on
15V827; see page 16
VALVE, check
VALVE, check (826212)
M6 x 10; 16 mm
mm) OD tube x 1/4 npt
3/8 in. (10 mm)
1/4 npt 316 sst (826212)
280555 S3000 Solvent Meter Kit
Ref.
No.Part No. DescriptionQty
101258718 METER, gear, S3000; used on
280555; see page 18
102114339 UNION, swivel; 1/4 npt(m) x 1/4
1
103166846 ADAPTER; 1/4 npt x 1/4 npsm
1
104501867 VALVE, check1
1
10517C910 HARNESS, cable, with connec-
1
106551295 SCREW, machine, pan hd;
1
10815U749 BRACKET, mounting1
2
109512616 HOSE; ptfe; 1/4 in. (13 mm) ID;
1
110C19798 SCREW, cap, socket-hd;
4
2
npsm(f)
(mbe)
tor
M6 x 1; 8 mm
1/4 npsm(f); 1.5 ft (0.46 m)
1/4-20 x 3/8 in. (10 mm)
1
1
1
1
2
1
4
308778Y15
Page 16
Parts
1
Torque to 27-57 in-lb (3.1-6.4 N•m).
Torque to 12 ft-lb (16 N•m).
1
2
TI11580a
1
2
4
5
7
8
10
11
Item 3, Gear
Meter Assembly
includes items
4-11
2
9
Bare Meter Assemblies
289813 G3000 Meter
26A119 G3000A Meter
289814 G3000HR Meter
*Included in Shim Kit 24G735. Order separately. Kit
includes 4 each of 0.1 mm and .05 mm sizes, and 8
of .02 mm size. Use sizes appropriate for your meter.
Discard unused sizes. See page 14 for shim installation instructions.
** Replacing this part will also require adaptor 24Y434
or a replacement cable if the existing cable has a
black plastic coupler.
† Included in Gear/Shim Kit 24G736. Order separately.
Kit includes 2 gear/bearing assemblies with appropriate size shims.
‡ Included in O-Ring Kit 24G737. Order separately.
18308778Y
Page 19
Parts
308778Y19
Page 20
Dimensions
G3000, G3000A, and G3000HR
Mounting Holes (bottom
Part Nos. 289813, 289814, and 26A119
1.73 in.
(43.94 mm)
M6
1/4-18 npt(f)
inlet/outlet
2.97 in.
(74.44 mm)
2.16 in.
(54.86 mm)
4.00 in.
(101.6 mm)
TI11579a
TI7382a
G250 and G250HR
Mounting Holes (bottom
Part Nos. 249426 and 249427
M6
1.73 in.
(43.94 mm)
1/4-18 npt(f)
inlet/outlet
2.47 in.
(62.74 mm)
3.75 in.
(95.25 mm)
1.92 in.
(48.77 mm)
TI13043a
TI13042a
Dimensions
20308778Y
Page 21
Dimensions
Part No. 258718
1/4-18 npt(f)
inlet/outlet
3.15 in.
(80 mm)
1.96 in.
(49.8 mm)
3.71 in.
(94.2 mm)
Solvent Meter
Mounting Holes (bottom
1.75 in.
(44.45 mm)
M6
TI14674b
2.36 in.
(60 mm)
TI14680a
Part No. 15U749
0.44 in. (11 mm) slots for
mounting the meter
Kit Mounting Bracket
TI18200a
2.40 in.
(61 mm)
3.25 in.
(83 mm)
4.40 in.
(112 mm)
1.25 in.
(32 mm)
308778Y21
Page 22
Technical Data
Technical Data
Volumetric Fluid Flow Meters
U.S.Metric
Maximum Fluid Working Pressure
G3000, G3000A, and G3000HR4000 psi28 MPa, 276 bar
S3000 Solvent Meter3000 psi21 MPa, 210 bar
G250 and G250HR300 psi2.1 MPa, 21 bar
Flow Range
G3000, G3000A, and G2500.02-1.0 gal/min75-3800 cc/min
G3000HR and G250HR0.01-0.5 gal/min38-1900 cc/min
S3000 Solvent Meter0.01-0.42 gal/min38-1600 cc/min
Fluid Temperature Range
Maximum Ambient Temperature
Fluid Viscosity Range
G3000, G3000A, and G3000HR20-3000 cps (see Pressure Drop Curve on page 23)
S3000 Solvent Metersolvent and light viscosity clear fluids (20-50 cps)
G250 and G250HR20-3000 cps (see Pressure Drop Curve on page 23)
Maximum Cable Length
Flow Meter Inlet/Outlet
Resolution
G3000, G3000A, and G2500.119 cc/pulse
G3000HR and G250HR0.061 cc/pulse
S3000 Solvent Meter0.021 cc/pulse
Accuracy
G3000, G3000A, G3000HR,
G250, and G250HR
S3000 Solvent Meter+/- 2.5% through communicated flow range.
G3000, G3000A, and G3000HR6 lb2.7 kg
S3000 Solvent Meter6 lb2.7 kg
G250 and G250HR2.6 lb1.8 kg
+/- 0.5% through communicated flow range for most commonly used coat-
ings. Accuracy will diminish at low viscosities and low flow rates.
40-180°F4-82°C
140°F60°C
200 ft61 m
1/4 npt(f)
10-30 Vdc
V max = 30 V; I max = 15 mA;
Ci = 0.4 microfarads; Li = .01 mH
See front cover
303, 304, 17-4, and 17-7 Stainless Steel, PTFE
22308778Y
Page 23
Pressure Drop Curve
G3000/G3000A
G250
PSI
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
0.00.10.20.30.40.50.60.7
0.8
0.91.01.1
G3000HR/G250HR
gal/min
gal/min
0.00.050.100.150.200.250.300.35
0.40
0.450.50 0.55
500 cps
400 cps
300 cps
200 cps
100 cps
50 cps
800 cps
3000 cps
2000 cps
1500 cps
1000 cps
S3000
gal/min
0.00.025 0.050.065 0.076 0.083 0.100.13
0.16
0.190.22 0.25
Pressure Drop Curve
308778Y23
Page 24
Graco Standard Warranty
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in
material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty
published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by
Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written
recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty
installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of
non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with
structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or
maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of
the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned
to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will
be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED
TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy
(including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or
consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT
MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to
the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these
warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or
the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the
negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into,
given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la
rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés, à la suite
de ou en rapport, directement ou indirectement, avec les procédures concernées.
Graco Information
For the latest information about Graco products, visit www.graco.com.
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor.
Phone: 612-623-6921 or Toll Free: 1-800-328-0211 Fax: 612-378-3505
All written and visual data contained in this document reflects the latest product information available at the time of publication.
Graco reserves the right to make changes at any time without notice.
Original instructions. This manual contains English. MM 308778
International Offices: Belgium, China, Japan, Korea
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 1997, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco Headquarters: Minneapolis
www.graco.com
Revision Y, August 2018
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.