Graco CGM 25B127, CGM 26A701, CGM 26A700, CGM 26A702 Instructions - Parts Manual

Instructions - Parts
ti11985a
CGM with DeviceNet connector shown
Communications Gateway Module
3A6338B
Installation Kit
For use with Electric Fixed Ratio (EFR) systems to provide fieldbus communications abilities. For professional use only.
Read all warnings and instructions in this manual and in your system manual before using the equipment. Save these instructions.
EN
B
C
AA
AB
Contents
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
CGM Software . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
EFR and PLC Connection . . . . . . . . . . . . . . . . . . 5
Gateway Screens . . . . . . . . . . . . . . . . . . . . . . . . 5
Available Internal Data . . . . . . . . . . . . . . . . . . . . . . 8
Automation Inputs (signals from EFR system to
PLC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Automation Outputs (signals from PLC to EFR
system) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CGM General Timing Diagrams . . . . . . . . . . . . 12
Appendix A - I/O Signal Descriptions . . . . . . . . . 19
Automation Inputs (signals from EFR system to
PLC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Automation Outputs (signals from PLC to EFR
System) . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Appendix B - Data Exchanged . . . . . . . . . . . . . . . 24
EFR Data Exchange Elements . . . . . . . . . . . . . 25
Appendix C - Sequence Step Data Exchange . . . 30
EFR Sequence Step Data Exchange Elements 31
Appendix D - Error Number Requiring
Acknowledgment . . . . . . . . . . . . . . . . . . . . . . 32
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . 34
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . . 34
Overview
The Communications Gateway Module (CGM) provides a control link between the Electric Fixed Ratio (EFR) system and a selected fieldbus. This provides the means for report monitoring and control by external automation systems.
NOTE: The following system network configuration files are available at help.graco.com.
EDS file: DeviceNet or Ethernet/IP fieldbus networks
GSD file: PROFIBUS fieldbus networks
GSDML: PROFINET fieldbus networks
ACD file: DeviceNet or Ethernet/IP fieldbus networks
The following components are included in the CGM Installation Kit.
Ref. Description Qty.
ACGM Kit
AA Gateway Module
AB Mounting Bracket B Screw, #10-32 x .50 C Washer, #10, Nylon D Communication Cable (not shown)
1 1 1 2 2 1
Related Manuals
Manual Description
312864
3A6165
406987 GCA CAN Cables, Reference
Models
Part Description
25B127 DeviceNet CGM Kit
26A700 EtherNet/IP CGM Kit
26A701 PROFIBUS CGM Kit
26A702 PROFINET CGM Kit
2 3A6338B
Communications Gateway Module, Instructions - Parts
Electric Fixed Ratio Proportioner, Setup ­Operation
FIG. 1
CGM Software
The following software is must be installed on the CGM module to work properly with the EFR CGM map 19A796.
17P796, version 3.01.004
Installation
WARNING
F
E
G
A
B
C
CAN H
J
ELECTRIC SHOCK HAZARD
To avoid electric shock, make sure the system power is OFF before connecting or disconnecting CAN cables.
PRESSURIZED FLUID HAZARD
This equipment stays pressurized until pressure is manually relieved. To help prevent serious injury from pressurized fluid, such as skin injection, splashing fluid and moving parts, follow Pressure Relief Procedure when you stop spraying and before cleaning, checking or servicing the equipment.
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns.
Installation
3. Mount the CGM Kit (A) inside the system frame with two screws (B) and washers (C).
FIG. 3
4. Secure cables (CAN, J) to the frame using the cable ties (H) provided, and route them through the
protected opening as shown in F
IG. 4.
1. Ensure the system power is OFF and pressure has been relieved. Follow the Pressure Relief Procedure in the Electric Fixed Ratio Proportioner, Setup ­Operation manual.
2. Remove the pump yoke shroud (F) and frame cover (G) from the EFR system.
FIG. 4
FIG. 2
3A6338B 3
Installation
CAN
Connector 1
ti11972a
CAN Connector 2
ti11985a
5. Connect the CAN cable from either CAN connection on the CGM to port 2 on the EFR.
NOTICE
Ensure the CAN cable is connected to the appropriate CAN connection. Failure to connect the CAN cable to the correct CAN connection can result in damage to the CGM module.
FIG. 5: Cable Connections
6. If used, connect the Ethernet, DeviceNet, or PROFIBUS cable (J) to the CGM as applicable. Connect the other end of the cable to the FieldBus
device.
7. Reinstall the pump yoke shroud (F) and the frame cover (G) onto the EFR system.
8. Perform the Install or Update Data Map procedure in the Communications Gateway Module, Instructions – Parts manual.
9. See Available Internal Data on page 8 for details regarding the FieldBus pinout setup.
10. Perform the Setup procedure on page 5 to configure the fieldbus.
NOTE: To produce an accurate dispense, the dispense valve must be controlled directly by the EFR. See the Electric Fixed Ratio Proportioner, Setup - Operation manual for I/O integration of the dispense valve with the EFR.
NOTE: See Automation Outputs (signals from PLC to EFR System) on page 22 for information on
triggering a dispense through the EFR using the CGM.
FIG. 6: Cable Connections
4 3A6338B
Setup
Setup
EFR and PLC Connection
Verify the PLC connection parameters are setup correctly.
NOTE: The connection between the EFR and PLC will not be made if the PLC connection parameters are not set up correctly.
Standard Gateway Map: 19A796
Comm. Format Data-SINT
Input Assembly Instance 100
Input Byte Size 42
Output Assembly Instance 150
Output Byte Size 22
Gateway Screens
The Gateway screens are used to configure the fieldbus. These screens are shown only if a CGM is correctly installed in your system. See Installation on page 3.
PROFIBUS Fieldbus Screens
These screens are shown only if a PROFIBUS Fieldbus CGM is installed.
Screen 1
This screen enables the user to set the device address, install date, location tag, function tag, and description.
FIG. 8: PROFIBUS Fieldbus Screen 1
Screen 2
1. With the system on and enabled, press to
access the Setup screens.
2. Press the left arrow key once to navigate to the main Gateway screen. See F
FIG. 7: Example Fieldbus Screen
IG. 7.
This screen displays the hardware revision, system serial number, and data map identification information.
FIG. 9: PROFIBUS Fieldbus Screen 2
3A6338B 5
Setup
PROFINET Fieldbus Screens
These screens are shown only if a PROFINET Fieldbus CGM is installed.
Screen 1
This screen enables the user to set the IP Address, DHCP settings, subnet mask, gateway, and DNS
information.
Screen 3
This screen displays the hardware revision, system serial number, and data map identification information.
FIG. 12: PROFINET Fieldbus Screen 3
FIG. 10: PROFINET Fieldbus Screen 1
Screen 2
This screen enables the user to set the station name, install date, location tag, function tag, and description.
FIG. 11: PROFINET Fieldbus Screen 2
6 3A6338B
Setup
EtherNet/IP Fieldbus Screens
These screens are shown only if an EtherNet/IP Fieldbus CGM is installed.
Screen 1
This screen enables the user to set the IP address, DHCP settings, subnet mask, gateway, and DNS
information.
FIG. 13: EitherNet/IP Fieldbus Screen 1
DeviceNet Fieldbus Screen
This screen is shown only if a DeviceNet Fieldbus CGM is installed.
This screen enables the user to set the device address and baud rate, as well as view the hardware revision, system serial number, and data map identification
information.
FIG. 15: DeviceNet Fieldbus Screen
Screen 2
This screen displays the hardware revision, system serial number, and data map identification information.
FIG. 14: EtherNet/IP Fieldbus Screen 2
3A6338B 7
Available Internal Data
Available Internal Data
See Appendix A - I/O Signal Descriptions on page 19 for additional details regarding each input/output. Unless stated otherwise:
In each instance, bytes are stored in little endian order (most significant to least significant).
PROFIBUS and PROFINET data must be mirrored by the PLC to get the correct data out on the PLC side. When the data is mirrored, the least significant byte is inserted into the most significant spot, and the most significant byte is inserted into the least significant spot.
- Example: If the data is a binary number with
0011100110110111, mirroring it to get the correct data out of the PROFIBUS or PROFINET will result in 0111101110010011.
Values are subject to the same maximum and minimum restrictions as the ADM.
NOTE: Automation Outputs can be monitored by the corresponding Automation Inputs to verify the EFR received the data correctly.
8 3A6338B
Automation Inputs (signals from EFR system to PLC)
Available Internal Data
Instance ID Description Data Type BIT
1 Heartbeat To PLC Boolean 0 2 System On Boolean 1 3 System Ready Boolean 2 4 Active Alarms Boolean 3 5 Active Deviations Boolean 4 6 Active Advisories Boolean 5 7 Current Sequence is Playing Boolean 6 8 Current Sequence is Paused Boolean 7
9 Current Sequence is Stopped Boolean 8 10 Dispense Valve Open Boolean 9 11 System is Priming Boolean 10 12 System is Purging Boolean 11 13 System is Parking Boolean 12 14 System is Depressurizing Boolean 13 15 Gel Shot is Running Boolean 14 16 EFR is Dispensing Boolean 15 17 {Reserved Bits} Boolean 16-23 2 18 {Reserved Bits} Boolean 24-31 3 19 Current Active Sequence uint8 0-7 4 20 Current Step of the Active Sequence uint8 0-7 5
21 Time Remaining to Complete Step (XX.X s) uint16
22 Red Pump Outlet Pressure (XXXX.X bar) uint16
23 Blue Pump Outlet Pressure (XXXX.X bar) uint16
24 Red Pump Inlet Pressure (XXXX.X bar) uint16
25 Blue Pump Inlet Pressure (XXXX.X bar) uint16
26 Pump Flow Rate (XXXX cc/min) uint16
27 Active Error Number Requiring Acknowledgment uint8 0-7 18
28
29 Data Exchanged Element Selected uint8 0-7 21
30 Data Exchanged Element Value uint16
31 Selected Step of the Active Sequence uint8 0-7 24
32 Selected Step Amount (XXXX.XX) uint32
Active Operator Mode Dispense Flow Rate (XXXX cc/min)
uint16
0-7 6
8-15 7
0-7 8
8-15 9
0-7 10
8-15 11
0-7 12
8-15 13
0-7 14
8-15 15
0-7 16
8-15 17
0-7 19
8-15 20
0-7 22
8-15 23
0-7 25
8-15 26 16-23 27 24-31 28
Input Byte
Index’s
0
1
3A6338B 9
Available Internal Data
Instance ID Description Data Type BIT
33 Selected Step Shot Type uint8 0-7 29
34 Selected Step Flow Rate (XXXX cc/min) uint16
35 Selected Step Calibration (XX.XX) uint16
0-7 30
8-15 31
0-7 32
8-15 33
0-7 34
36 Total Sequence Amount Requested (XXXX.XX cc) uint32
8-15 35 16-23 36 24-31 37
0-7 38
37 Total Sequence Amount Dispensed (XXXX.XX cc) uint32
8-15 39 16-23 40 24-31 41
Input Byte
Index’s
10 3A6338B
Automation Outputs (signals from PLC to EFR system)
Available Internal Data
Instance ID Description Data Type BIT
1 System Enable Request Boolean 0 2 System Shutdown Request Boolean 1 3 Start Current Sequence/Step, Trigger Operator Mode Boolean 2 4 Pause Current Sequence Boolean 3 5 Stop Current Sequence Boolean 4 6 Priming Request Boolean 5 7 Purge Request Boolean 6 8 Parking Request Boolean 7
9 Depressurizing Request Boolean 8 10 {Reserved Bits} Boolean 9-15 11 {Reserved Bits} uint8 0-7 2 12 Desired Active Sequence uint8 0-7 3 13 Acknowledging of the Active Error Number uint8 0-7 4
14
15 Data Exchanged Element Desired uint8 0-7 7
16
17 Desired Step of the Active Sequence uint8 0-7 10
19
19 Desired Step Shot Type uint8 0-7 15
20
21
22
Desired Operator Mode Dispense Flow Rate (XXXX cc/min)
Data Exchanged Element Desired Value
Desired Step Amount (XXXX.XX)
Desired Step Flow Rate (XXXX cc/min)
Desired Step Calibration (XX.XX)
{Reserved Word}
uint16
uint16
uint32
uint16
uint16
uint16
0-7 5
8-15 6
0-7 8
8-15 9
0-7 11
8-15 12 16-23 13 24-31 14
0-7 16
8-15 17
0-7 18
8-15 19
0-7 20
8-15 21
Output Byte
Index’s
0
1
3A6338B 11
Loading...
+ 23 hidden pages