Graco 3A2347T User Manual

Instructions - Parts
InvisiPac
HM25 Tank-Free
3A2347T
Hot Melt Delivery System
1200 psi (8.3 MPa, 83 bar) Maximum Working Pressure 400°F (204°C) Maximum Fluid Operating Temperature 100 psi (0.7 MPa,7 bar) Maximum Air Inlet Pressure
Important Safety Instructions
Read all warnings and instructions in this manual and in the gun and hose manuals. Save all instructions.
EN
ti20440b
9902471
Certified to
CAN/CSA C22.2 No. 88
Conforms to ANSI/UL 499
Contents
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Component Identification . . . . . . . . . . . . . . . . . . . . 8
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Attach Components . . . . . . . . . . . . . . . . . . . . . 14
Recommended Air Setup . . . . . . . . . . . . . . . . . 18
Connect Electrical Cord . . . . . . . . . . . . . . . . . . 19
480V Electrical Circuits . . . . . . . . . . . . . . . . . . . 21
208V Electrical Circuits . . . . . . . . . . . . . . . . . . . 21
Select ADM Settings . . . . . . . . . . . . . . . . . . . . . 21
Guns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
PLC Connection . . . . . . . . . . . . . . . . . . . . . . . . 24
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Initial Startup and Prime . . . . . . . . . . . . . . . . . . 26
Manual Refill . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Automatic Refill . . . . . . . . . . . . . . . . . . . . . . . . . 28
Dispense . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Pressure Relief Procedure . . . . . . . . . . . . . . . . 30
Drain the System . . . . . . . . . . . . . . . . . . . . . . . 30
Flush . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Operation Tips to Minimize Charring . . . . . . . . 33
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Replace Outlet Filter . . . . . . . . . . . . . . . . . . . . . 34
Replace Inlet Filter . . . . . . . . . . . . . . . . . . . . . . 34
Replace Funnel Filter . . . . . . . . . . . . . . . . . . . . 35
Filter Maintenance Guidelines* . . . . . . . . . . . . . 36
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . 37
ADM Error Code Table . . . . . . . . . . . . . . . . . . . 37
MZLP Troubleshooting . . . . . . . . . . . . . . . . . . . 50
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Melter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Multi-Zone Low Power Temperature Control Module
(MZLP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Air Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Air Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Software Update Procedure . . . . . . . . . . . . . . . 71
Electrical Schematics . . . . . . . . . . . . . . . . . . . . . . 72
Incoming Power and Terminal Jumpers . . . . . . 72
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Non-Graco Gun Adapter Cables . . . . . . . . . . . . 90
Air Adjustment Lock, 24R084 . . . . . . . . . . . . . . 90
System Stand, 24R088 . . . . . . . . . . . . . . . . . . . 91
Caster for Stand, 120302 . . . . . . . . . . . . . . . . . 91
Adapter Plate, 24R083 . . . . . . . . . . . . . . . . . . . 91
30 Gallon Vibrating Hopper, 24R136 . . . . . . . . . 92
Light Tower Kit, 24R226 . . . . . . . . . . . . . . . . . . 94
Air Reservoir Kit, 16W366 . . . . . . . . . . . . . . . . . 95
Air Metric Fitting Kit, 24W637 . . . . . . . . . . . . . 103
Appendix A - ADM . . . . . . . . . . . . . . . . . . . . . . . . 104
General Operation . . . . . . . . . . . . . . . . . . . . . . 104
Icon Identification . . . . . . . . . . . . . . . . . . . . . . . 104
Appendix B - USB Downloading, Uploading . . . 110
Download Procedure . . . . . . . . . . . . . . . . . . . . 110
Accessing Files . . . . . . . . . . . . . . . . . . . . . . . . 110
Upload Procedure . . . . . . . . . . . . . . . . . . . . . . 110
USB Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
System Settings File . . . . . . . . . . . . . . . . . . . . 111
System Language File . . . . . . . . . . . . . . . . . . . 112
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Graco Extended Warranty . . . . . . . . . . . . . . . . . . 120
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . 120
2 3A2347T

Related Manuals

Manuals are available at www.graco.com. Component manuals in English:
Part Description
3A2805 InvisiPac GS35 Hot Melt Gun Instructions -
Parts
332072 InvisiPac Heated Hose Instructions - Parts

Required Tools

Related Manuals
Standard allen wrench set
Metric allen wrench set
Various sizes of crescent wrenches
11/16 in. wrench
3/8 in. ratchet
3/8 in. socket
5/16 in. driver
7/16 in. socket
7/8 in. deep well socket
1 in. socket
13 mm socket
10 mm socket
1/2 in. ratchet
Side cutter
Phillips head screwdriver
Flat head screwdriver
Multimeter
Tubing cutter
3A2347T 3

Models

Models
NOTICE
To prevent system damage, verify terminal jumpers are installed correctly before applying power.
Model Channels Voltage
24P260 2 200-240VAC
24P261 4 200-240VAC
24P262 2 350-415VAC Y
24P263 4 350-415VAC Y
24P264 2
24P265 4
24U132 6 200-240VAC
24U133 6 350-415VAC Y
24U134 6
200-240VAC
200-240VAC
200-240VAC
Δ
Δ
Δ
Φ
1
Φ
/ PE
Φ
/ PE
1
Φ
/ Neutral / PE
3
3
Φ
/ Neutral / PE
3Φ / PE
3Φ / PE
1
Φ
/ PE
Φ
/ Neutral / PE
3
3Φ / PE
Type Description Frequency
•1-Phase
• 200-240VAC
• 2 wire and PE
• 3-Phase with Neutral
• 350-415 VAC Line to Line
• 200-240VAC Line to Neutral
• 3 wire and Neutral and
PE
• 3-Phase without Neutral
• 200-240 VAC Line to Line
• 3 wire and PE
•1-Phase
• 200-240VAC
• 2 wire and PE
• 3-Phase with Neutral
• 350-415 VAC Line to Line
• 200-240VAC Line to Neutral
• 3 wire and Neutral and
PE
• 3-Phase without Neutral
• 200-240 VAC Line to Line
• 3 wire and PE
50/60 Hz 32A
50/60 Hz 40A
50/60 Hz 16A
50/60 Hz 16A
50/60 Hz 27A
50/60 Hz 27A
50/60 Hz 40A
50/60 Hz 30A
50/60 Hz 40A
Max
Amps
4 3A2347T

Warnings

Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When these symbols appear in the body of this manual or on warning labels, refer back to these Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before disconnecting any cables and before servicing or installing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
BURN HAZARD
Equipment surfaces and fluid that’s heated can become very hot during operation. To avoid severe burns:
Do not touch hot fluid or equipment.
SKIN INJECTION HAZARD
High-pressure fluid from dispensing device, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical
treatment.
+
Do not point dispensing device at anyone or at any part of the body.
Do not put your hand over the fluid outlet.
Do not stop or deflect leaks with your hand, body, glove, or rag.
•Follow the Pressure Relief Procedure when you stop dispensing and before cleaning, checking, or servicing equipment.
Tighten all fluid connections before operating the equipment.
Check hoses and couplings daily. Replace worn or damaged parts immediately.
MOVING PARTS HAZARD
Moving parts can pinch, cut or amputate fingers and other body parts.
Keep clear of moving parts.
Do not operate equipment with protective guards or covers removed.
Pressurized equipment can start without warning. Before checking, moving, or servicing equipment, follow the Pressure Relief Procedure and disconnect all power sources.
3A2347T 5
Warnings
WARNING
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maximum working pressure or temperature rating of the lowest rated system
component. See Technical Data in all equipment manuals.
Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information about your material, request MSDS from distributor or retailer.
Do not leave the work area while equipment is energized or under pressure.
Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manu­facturer’s replacement parts only.
Do not alter or modify equipment. Alterations or modifications may void agency approvals and create safety hazards.
Make sure all equipment is rated and approved for the environment in which you are using it.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help prevent fire and explosion:
Do not use solvent-based adhesives that can create an explosive atmosphere when processed.
Use equipment only in well ventilated area.
Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop cloths (potential static arc).
Keep work area free of debris, including solvent, rags and gasoline.
Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes are present.
Ground all equipment in the work area. See Grounding instructions.
Use only grounded hoses.
Stop operation immediately if static sparking occurs or you feel a shock. Do not use equipment until you identify and correct the problem.
Keep a working fire extinguisher in the work area.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed.
Read MSDSs to know the specific hazards of the fluids you are using.
Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
6 3A2347T
Warnings
WARNING
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective equipment includes but is not limited to:
Protective eyewear, and hearing protection.
Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer
PRESSURIZED ALUMINUM PARTS HAZARD
Use of fluids that are incompatible with aluminum in pressurized equipment can cause serious chemical reaction and equipment rupture. Failure to follow this warning can result in death, serious injury, or prop­erty damage.
Do not use 1,1,1-trichloroethane, methylene chloride, other halogenated hydrocarbon solvents or fluids containing such solvents.
Many other fluids may contain chemicals that can react with aluminum. Contact your material sup­plier for compatibility.
3A2347T 7

Component Identification

Component Identification
G3
G2
G4
A
G
G1
H
F
E
C
D
B
K
L
Key:
A Advanced Display Module (ADM) B Electrical Enclosure C Pump Air Pressure Regulator D Pump Air Pressure Gauge E Vacuum Transfer Air Pressure Regulator F Vacuum Transfer Air Pressure Gauge GShaker Tube G1 Shaker Head G2 Vacuum Transfer Tube G3 Vacuum Transfer Inlet Funnel G4 Vacuum Transfer 3/8 in. OD Air Supply H Main Power Switch J System Air Inlet K Vacuum Transfer (Shaker) Inlet L Air Motor and Pump M Incoming Power Strain Relief N Heated Fluid Manifold (Melter) P Multi-Zone Low Power Temperature Control Module (MZLP) R Fluid Outlets for connection to Heated Hoses (numbered 1-4) S Customer I/O Cable (optional)
R
P
ti20441b
N
M
S
J
FIG. 1
8 3A2347T
Heated Fluid Manifold
AB
Z
U
X
T
Component Identification
Y
R
AA
NOTE: System shown with plastic and metal shrouds removed.
FIG. 2
Key:
T Electrical Enclosure Front Access Door UMelter W1 Drain Port W2 Drain Tray X Inlet Filter (Low Pressure - Before Pump) Y Outlet Filter (High Pressure - After Pump)
W1
W2
ti20442b
Z Adhesive Pellets Level Sensor AA Power and RTD Harness Connection to Heated Hose and
Gun (harness connects from system to heated hose then from heated hose to gun)
AB Inlet Funnel Screen
3A2347T 9
Component Identification
Electrical Enclosure
AC
AJ
FIG. 3
Key:
P Multi-Zone Low Power Temperature Control Module
(MZLP) AC Incoming Power Connection AF Chassis Ground
P
ti20907b
AH
AG
AF
AG Terminal Blocks and Jumpers AH Heater Relay AJ Incoming Power Terminal Jumpers. See page 19.
10 3A2347T
Advanced Display Module (ADM)
Component Identification
User Interface
NOTICE
To prevent damage to soft key buttons, do not press the buttons with sharp objects such as pens, plastic cards, or fingernails.
NOTE: See Appendix A - ADM on page 104 for com­plete ADM operation details.
BB
BC
BA
BD
BE
BF
B
Ke yFunction
BA Heating system and pump enable/disable
BB System status indicator (LED)
BC Stop all system processes
BD Defined by icon next to softkey
BE Abort current operation
BF Accept change, acknowledge error, select item,
toggle selected item
BG Toggle between Operation and Setup screens
BH Navigate within a screen or to a new screen
BK
BL
BH
FIG. 4
BG
TI12362a1
BR
BM
BN
BP
FIG. 5
Key:
BK Part Number Identification Label BL USB Interface BM CAN Cable Connection (Power Supply and Communica-
tion) BN Module Status LEDs BP (Not used) BR Software Token Access Panel
3A2347T 11
Component Identification
Screen Components
Current date and time
Operating Mode
Hose and Gun
Heating Status
Hose Actual Temperature
FIG. 6: Main Screen Components
Operating Mode Description Component Status
System Off
Inactive
Warm Up
Active
The system doesn’t have power.
The heating system and pumps are disabled.
The system is increasing the material to the set temperature.
The system is ready to dispense material.
Screens Order
Gun Actual Temperature
No System Status Indicator LED on the ADM
No heat
Pump is off
Yellow system status indicator LED on the ADM
No heat
Pump is off (manually changed)
Flashing green system status indicator LED on the ADM
Heat is increasing to setpoint temperature
Pump is off
Solid green system status indicator LED on the ADM
Heat is at setpoint temperature
Pump is on
Faults, Status
Melter Heating Status
Melter Actual Temperature
12 3A2347T
Component Identification
3A2347T 13

Setup

Setup
Grounding
The equipment must be grounded to reduce the risk of electric shock. Improper grounding can cause electric shock. Grounding provides an escape wire for the electric current.
The InvisiPac system is equipped with a ground termi­nal. Have a qualified electrician ground the system using this terminal. See Connect Electrical Cord on page 19.
Location
Ambient temperature must be 32-120°F (0-49°C).
The supplied vacuum transfer hose length is 10 ft (3 m). The maximum vacuum transfer hose length available is 30 ft (9.1 m). The adhesive pellets container must be located within reach of the vacuum transfer hose and no more than 30 ft (9.1 m).
Attach Components
To reduce the risk of electric shock, do not connect electrical cord until after this Attach Components procedure is complete.
1. Place the base system in the desired operating
location and orientation. See Location on this page.
The bottom of the electrical enclosure has holes for securing the InvisiPac system to a surface. The holes are accessible through the bottom access doors in the three rear walls of the electrical enclo­sure.
To install the InvisiPac system in place of a
non-Graco hot melt system, purchase Adapter Plate, 24R083. See installation instructions on
page 91.
The gun(s) must be located no more than 25 ft (7.6 m) from the melter.
Place the base system on a surface that is eye-level for easiest operation. Use System Stand, 24R088, to install system at eye-level. See page 91.
If installing the system in place of a non-Graco hot melt system, purchase Adapter Plate, 24R083. See page 91.
Optional 30 Gallon Vibrating Hopper, 24R136, avail­able (purchase separately). See page 92.
To make repairing the system easier, locate the system so that all sides are easily accessible and have sufficient lighting.
To raise the system to eye-level, purchase System Stand, 24R088. See installation instructions on page 91.
NOTE: Supplied vacuum transfer hose must reach from the system to the adhesive pellets container. Supplied heated hose must reach from system to gun(s).
2. Install vacuum transfer inlet funnel (G3) onto sys­tem. See F
a. Slide funnel through the bracket connected to
the air motor.
b. Position the funnel so the funnel inlet faces the
desired direction.
c. Connect 5/32 in. OD air line to funnel.
IG
. 7.
14 3A2347T
Setup
d. Install supplied hose clamp around the air motor
bracket and funnel base then tighten.
G2
G3
G4
ti21130b
FIG. 7
3. Insert 1.3 in. (33 mm) OD clear vacuum transfer hose (G2) into vacuum transfer funnel (G3) inlet and secure with supplied hose clamp. See F
IG
. 7.
6. Apply pipe sealant to threads then attach steel shaker tube (G) to shaker head (G1). See F
IG
. 8.
NOTICE
To prevent shaker head (G1) galling to the shaker tube (G), do not overtighten shaker head onto shaker tube. These should be hand-tightened.
G2
G6
G5
G
G4
4. Connect the long supplied 3/8 in. OD air line (G4) to the 3/8 in. push-to-connect fitting on the air line from the system. See F
IG
. 7.
NOTE: In the following steps, when routing the vacuum transfer hose, ensure there are no tight coils, turns, or dips in the vacuum hose. These will inhibit optimal func­tioning of the vacuum transfer system.
NOTE: Maximum vacuum hose length is 30 ft (9.1 m). Use horizontal hose routing as much as possible. The vacuum hose must not rise more than 10 ft (3.0 m), measured from the vacuum inlet. Any vertical rise will lower the maximum flow rate of the vacuum transfer system.
5. Route the 1.3 in. (33 mm) OD clear vacuum transfer hose from the system to the adhesive pellets con­tainer location.
G1
ti21131a
FIG. 8
7. Attach 1.3 in. (33 mm) clear vacuum transfer hose (G2) to steel shaker tube (G) and secure with sup­plied hose clamp. See F
IG
. 8.
8. Route the 3/8 in. OD air line (G4) alongside the
1.3 in. (33 mm) clear vacuum transfer hose (G2) and secure at multiple points with the supplied zip ties (G5). See F
IG
. 8.
9. If desired, secure the 1.3 in. (33 mm) clear vacuum transfer tube and 3/8 in. OD air line with zip ties to a supporting structure at various points in the routing.
10. Attach the other end of the long 3/8 in. OD air line (G4) to the 3/8 in. push-to-connect fitting on the shaker head (G1).
11. Ensure the adhesive pellets container is in the desired operating location. The location should be chosen to make it easy to fill the container with pel­lets.
3A2347T 15
Setup
12. Place shaker assembly in an empty adhesive pel­lets container then fill the container with adhesive pellets.
NOTE: To promote optimal system performance, pur­chase 30 Gallon Vibrating Hopper, 24R136. See installation instructions on page 92.
NOTE: If static buildup on feed tube (G) is excessive, install optional feed tube ground kit 24R708 to feed tube end (G6). See F
13. Install heated hoses, see F
IG
. 8.
IG
. 9:
To reduce the risk of fire and explosion, only use Graco heated hoses with the InvisiPac system. Use of non-Graco hoses will void agency approvals.
N
247
Gun
68
d. Remove plug (247) from the lowest numbered
outlet on the melter. Do not use the drain plug (W1). See F
IG
. 9.
NOTE: In the following step, the o-ring side of the hydraulic fitting (68) faces the system. See F
IG
. 9.
e. Install the supplied hydraulic fitting (68) with an
o-ring into the open port and tighten with an 11/16 in. wrench or socket.
f. Install hose onto hydraulic fitting (68) with male
electrical connector side toward the system. Use 11/16 in. wrench to tighten hose onto hydraulic fitting (68).
g. Locate MZLP (AA) connector marked with same
number as the hose fluid outlet port. Remove that connector cover then install connector from heated hose. See F
IG
. 9.
h. Repeat the procedure for the remaining chan-
nels. Use the bottom melter ports first to ease installation.
W1
W2
AA
ti21132a
FIG. 9
a. Place a rag on the drain tray (W2) attached to
the melter. Residual oil may be in the system from the factory. See F
IG
. 9.
b. Use a 1/4 in. allen wrench to remove the drain
IG
port plug (W1). See F
. 9.
NOTE: A 1/4 in. allen wrench is shipped loose with the system.
c. When fluid stops draining, re-install drain port
IG
plug (W1) then remove rag. See F
. 9.
i. Install cap on any unused MZLP electrical con-
nectors.
NOTE: Fluid outlet port 1 must be used and electrical connector from that hose must be connected to MZLP connector 1. The system will not operate unless a hose is connected to MZLP connector 1. If a hose is not con­nected to connector 1, “Invalid Sensor - hose/gun” faults will result.
14. Install gun(s), see F
IG
. 9:
NOTE: Use of a Graco gun is not required with this sys­tem. However, all guns attached to the system must be rated for 1200 psi (8.3 MPa, 83 bar), 400°F (204°C), have an RTD type sensor, and use no more than 400W.
a. Connect heated hose fluid outlet to gun fluid
inlet. Use 11/16 in. wrench to tighten. See F
IG
.
9.
b. For Graco guns, attach gun electrical connector
IG
to heated hose electrical connector. See F
. 9.
16 3A2347T
Setup
c. For non-Graco guns, attach gun electrical con-
nector to adapter harness (16T916, 16T917, or 16Y828) then attach adapter harness connector to heated hose connector. See Non-Graco Gun Adapter Cables on page 90 to determine which adapter cable to use with your valve.
d. Repeat for any additional guns.
15. If necessary, set up the valve controller to control
opening and close the gun. See gun manual.
NOTE: The system controls gun heating only. A sepa­rate gun controller must be set up to open and close the guns.
16. Install the supplied air inlet bleeding ball valve and air filter kit (Graco Part No. 24R707) at the 1/4 NPT female system air inlet (J). See F
IG
. 10.
17. If using the same air for the gun(s), make sure to
install the tee in the air line before the ball valve. There should not be anything between the ball valve and the system. See gun manual for gun air pres­sure requirements, and use a regulator before the gun to decrease the air pressure, if necessary.
18. Close the ball valve.
WLE
ti21147a
FIG. 11
19. Attach a 3/8 in. minimum air supply line to air filter. See F
IG
. 11.
J
WLE
ti21133a
FIG. 10
NOTE: The system must have a bleed-type ball valve
that bleeds pressure downstream when closed. Other­wise, the supplied air will need to be disconnected from the system whenever the pressure is relieved.
NOTE: The system must use an air filter with a mini­mum flow rate of 30 scfm.
NOTE: Air supply pressure must be between 80 psi (550 kPa, 5.5 bar) and 100 psi (690 kPa, 6.9 bar). Rec­ommended pressure is 100 psi (690 kPa, 6.9 bar). If air pressure is expected to drop below 80 psi (0.5 MPa, 5 bar), there is an air reservoir kit that allows the system to operate down to 60 psi (0.4 MPa, 4 bar). See Air Reservoir Kit, 16W366, on page 95.
20. To lock access to the air pressure adjustments, pur­chase Air Adjustment Lock, 24R084. See installa­tion instructions on page 90.
21. To install a light tower that illuminates red when a
system error occurs, purchase Light Tower Kit, 24R226. See installation instructions on page 94.
22. To upgrade a 2 channel system to a 4 channel sys­tem, purchase 4 Channel Upgrade Kit, 24R237.
See installation instructions on page 96.
23. Install MZLP electrical connector caps on all unused channels.
3A2347T 17
Setup
Recommended Air Setup
Main Air Line
Air In: Less than 50 ft (15.2 m): 3/8 in. More than 50 ft (15.2 m): 1/2 in. 80-100 psi (5.5-6.8 bar, 0.55-6.8 MPa) 30 scfm capacity.
Air Filter/Ball Valve at
System Air Inlet
(Graco Kit 24R707,
included)
Vacuum:
40 - 80 psi
(2.8-5.5 bar,
0.28-0.55 MPa);
and at least 65% of
hopper shaker air
pressure, if used
No dips in vacuum transfer hose
Ensure funnel air is connected
Pump: 20-100 psi (1.4-6.8 bar,
0.14-0.68 MPa)
Air In:
3/8 in.,
100 psi
(6.8 bar, 0.68 MPa),
30 scfm capacity
WLE
Air to guns
Regulator set to
70 psi
(4.8 bar, 0.48 MPa)
FIG. 12
18 3A2347T
Setup
Connect Electrical Cord
NOTE: See Grounding section on page 14.
Improper wiring may cause electric shock or other serious injury if work is not performed properly. Have a qualified electrician perform any electrical work. Be sure your installation complies with all National, State and Local safety and fire codes.
To reduce the risk of electric shock, perform the entire Attach Components procedure beginning on page 14 prior to connecting electrical cord.
NOTE: The installed strain relief bushing (106) fits a
0.708-1.260 in. OD electrical cord. See F needed, use a wrench to tighten the strain relief bushing until it is snug on the cable.
For 480V Electrical Circuits, see page 21.
IG
. 14. If
Terminal Block Jumper Installation Guide
Terminal Block Location
Voltage
200-240VAC,
1 phase
350-415VAC,
3 phase,
WYE
200-240VAC,
3 phase,
DELTA
Jumper
Wire
127201
Not used Not used 3-5 6-10
Not used
3-7
2-Terminal
Jumper
126814
5-6,
8-9
4-5,
9-10
3-Terminal
Jumper
126815
2-4 Not used
6-8 Not used
5-Terminal
Jumper
126816
NOTE: The jumpers only need to be changed if using a
different phase or voltage from what the system was designed for at the factory.
NOTE: All necessary jumpers are supplied with the sys­tem in a bag located behind the electrical enclosure front access panel. Keep unused jumpers in bag.
2-Terminal
126814
3-Terminal
126815
5-Terminal
126816
1. Turn main power switch OFF.
2. Disconnect cable from ADM, push cable through plastic shroud, then remove plastic shroud from sys­tem.
3. Remove electrical enclosure access door (T). See F
IG
. 2 on page 9.
4. Ensure the terminal block jumpers are in the correct locations for the phase and voltage used. If neces-
IG
sary, change them to match F See the following table, F
. 15 on page 20.
IG
. 13, and FIG. 15.
NOTICE
To prevent system damage, verify terminal jumpers are installed correctly before going on to the next step.
ti21182a
Wire
127201
FIG. 13: Jumpers
NOTE: Use the supplied hard metal 2, 3, and 5 terminal
jumpers and jumper wire for terminals 2C-10C. Use the red, plastic jumpers for terminals 11-14.
5. Insert electrical cord through electrical enclosure strain relief bushing (106). See F
IG
. 14 on page 20.
a. Alternate electrical cord routing: using conduit,
run electrical cord from access port (X) through hole (Y). Conduit is required when routing wires near compressed air components.
3A2347T 19
Setup
6. Attach insulated ferrules to the end of each wire. 7. Connect ground wire to chassis ground (AF). See F
IG
. 14.
106
8. Connect L1, L2, L3, and N as shown in F
IG
. 15. Not
all models use all 4 wires.
9. Use zip ties to secure the electrical cord to the tie-downs located on the top of the inside of the electrical enclosure.
Y
X
10. Tighten screw-terminals to at least 10 in-lb (1.1 N•m).
11. Install electrical enclosure door.
FIG. 14
AF
ti20907b
12. Perform Select ADM Settings on page 21 prior to turning on heat.
FIG. 15
20 3A2347T
Setup
480V Electrical Circuits
For 480V electrical supply, a 480V to 240V step-down transformer must be installed by a qualified electrician.
Transformer Sizing
For single-phase power, 480V to 240V transformer 24U169 (purchase separately) may be used. See Sin- gle-Phase 480V to 240V Transformer, 24U169 on page 100.
Minimum transformer rating can be calculated by taking output voltage times the ADM breaker setting.
Single Phase, 20A ADM Breaker Setting Example:
240 volts x 20 amps = 4800 watts
Three Phase, 20A ADM Breaker Setting Example:
240 volts x 20 amps x
(3) = 8315 watts
208V Electrical Circuits
For 208V electrical supply, a qualified electrician can install a 208V to 240V step-up transformer to improve startup times.
Transformer Sizing
Minimum transformer rating can be calculated by taking transformer output voltage times the ADM breaker set­ting.
3. On the System 2 screen:
a. Check the box in the “Installed” column for each
channel that has a heated hose and gun installed.
b. Select the RTD type used on each installed
gun. See gun manual.
NOTE: An incorrect RTD setting will cause the system to be incapable of maintaining the temperature setting.
NOTE: The supported RTD types are Ni, 100 ohm; Ni, 120 ohm; NiFe, 604 ohm; Pt, 100 ohm (385), Pt, 100 ohm (392); and Pt, 1000 ohm. An “Auto” selection is available but should only be used when the specific RTD type cannot be identified. Using the “Auto” RTD setting may result in inaccurate temperatures.
Single Phase, 20A ADM Breaker Setting Example:
240 volts x 20 amps = 4800 watts
Three Phase, 20A ADM Breaker Setting Example:
240 volts x 20 amps x SQRT(3) = 8315 watts
To prevent fire and explosion, a qualified electrician must determine the proper circuit breaker size to use for the power supplied to the system.
4. On the System 3 screen:
Select ADM Settings
NOTE: See Appendix A - ADM on page 104 for
detailed ADM information, including general operation.
1. Turn main power switch ON .
2. When the ADM is finished starting up, press to switch from the Operation screens to the Setup
screens. Use , , , and to navigate
between screens.
3A2347T 21
a. Enter the main circuit breaker size used. This is
the circuit breaker installed external to the sys­tem for the system power supply.
Setup
NOTE: If using a 480V to 240V transformer, the breaker size entered will be two times the 480V rating. If using transformer 24U169, the breaker size should be set to 30 amps and power type should be set to single phase.
NOTE: The InvisiPac system limits the amount of power it pulls based on the input circuit breaker size. This impacts the startup times because it affects the heating energy used to warm up the materials.
b. Select the incoming power type.
5. On the Advanced 1 screen, set the system date and time.
6. On the Advanced 2 screen, set the temperature and mass units.
NOTE: The Schedule function enables the system to automatically enable and disable heating at specified times so that the system is already up to temperature when a shift begins.
8. If desired, set any remaining settings in the Setup
screens before going on to the next steps that use the Operation screens. These are not required for system operation but include useful functions. See Appendix A - ADM, beginning on page 104, for detailed information about each setup item.
9. Press to switch from the Setup screens to the
Operation screens. Use , , , and to
navigate between screens.
10. On the Targets screen, use and , shown
next to , to adjust system melter setting.
Also, the desired temperature setting can be typed in using the numeric keypad.
7. To setup the optional Schedule function, see Schedule on page 29.
22 3A2347T
11. On the Targets screen, adjust heated hose and gun temperature settings:
NOTE: InvisiPac is a high powered tank-free system that delivers heat faster than traditional tank systems. Tanks are often run at a lower temperature than the application temperature to avoid excessive adhesive degradation since a large volume of adhesive sits at temperature.
a. Press to select the channel.
b. Use and , shown next to , to
adjust gun temperature setting to the desired setting for that channel.
NOTE: If a higher applicator temperature is desired, adjust all zones to the higher temperature or adjust only the applicator in small increments.
Setup
c. Use and , shown next to ,
to adjust heated hose temperature setting to the desired setting for that channel.
NOTE: Alternatively, use the physical up and down
arrow push-buttons on the ADM keypad until is next to the temperature setting to change then use the
numeric keypad to enter the desired temperature.
NOTICE
Set melter, hose, and gun to the same setpoint tem­perature for best performance. Do not set the hose temperature higher than the melter. Running the hose at a setpoint higher than the melter is unnecessary in this tank-free system and could lead to adhesive deg­radation in the hose. Short adhesive residence time in the melter eliminates the need to set the melter at a lower setpoint than other zones. See Operation Tips
to Minimize Charring, page 33.
NOTE: Alternatively, use the physical up and down
arrow push-buttons on the ADM keypad until is next to the temperature setting to change then use the numeric keypad to enter the desired temperature.
Guns
Gun heating is controlled by the system, but the system does not control opening and closing the valves. Setup a separate gun controller to open and close the valves.
3A2347T 23
Setup
PLC Connection
A PLC can control and monitor all items shown in the dropdown menus on the System 1 screen in the Setup screens.
Customer Input Dropdown Options
Option Description
Disable Not used.
Heater On/Off Turn on or off the heating system and
pump.
Channel 1, 2, 3, or 4 Enable/Dis­able
Customer Output Dropdown Options
Option Description
Disable Not used.
System Ready Indicates when the system is up to tem-
Error (Alarm) Indicates when there is an active alarm.
Error (Devia­tion/Advisory)
Maintenance Due Indicates when the maintenance total
Enable or disable hose and gun heat­ing for that individual channel.
perature and the pump is stalled at pressure.
An active alarm will disable the heating system and pump.
Indicates when there is an active devia­tion or advisory. An active deviation or advisory will NOT disable the heating system and pump.
has reached the preset notification value.
NOTE: The InvisiPac system ships with two screw-terminal connectors that plug into MZLP connectors H1 and H2. Connectors are located in a bag on the inside of the electrical enclosure front access door. To replace the connectors, order kit 24P176.
1. On the System 1 screen (in the Setup screens) select the function of each input on MZLP connector H1 and each output on MZLP connector H2.
2. Turn main power switch OFF.
3. Remove electrical enclosure front access door.
4. Route I/O cable through strain relief in electrical enclosure. See Customer I/O Cable (S) in F
IG
. 1 on
page 8.
5. Remove power from PLC.
6. Connect the PLC to connectors H1 and H2.
NOTE: Each connector has four signals. The MZLP board specifies the input range for each signal. See the following table for pin assignments.
J1
J2
F1
F2 F3
F4
F5
F6
F7
F8
F9
F10
J7
J6
J5
J3
H1
H2
FIG. 16: MZLP Board
H1 - Customer Input H2 - Customer Output
Signal Pin Signal Pin
1 1, 2 1 1, 2
2 3, 4 2 3, 4
3 5, 6 3 5, 6
4 7, 8 4 7, 8
NOTE: All outputs are normally open when power is OFF. For Error (Alarm) output, the contacts open when an alarm occurs. For all others, contacts close.
Inputs: High: 10-30 Vdc, Low: 0-5 Vdc. Inputs function without concern for polarity. Applying “high” voltage will turn the heaters on and enable channels. Removing voltage will turn the heaters off and disable channels.
Outputs: 0-250 Vac, 0-30 Vdc, 2A.
24 3A2347T
Setup
PLC Connection Block Diagrams
The following block diagrams show how to connect customer inputs and outputs to the InvisiPac MZLP. For conve­nience, each InvisiPac ships with connector kit 24P176. If a connector is lost or damaged, order kit 24P176 for replacements.
FIG. 17: Customer Input
MZLP Customer In
MZLP Customer Out
Customer Output
Vin (no polarity) 30 VDC Max
Customer In
FIG. 18: Customer Output
250 VAC, 2A Max
To Customer Input
3A2347T 25

Operation

Operation
Heating and dispensing hot melt adhesive may create potentially harmful vapors. Read material manufacturer’s warnings and material MSDS to know specific hazards and precautions. Ventilation of the work area may be required.
NOTE: See Appendix A - ADM on page 104 for detailed ADM information.
NOTICE
To prevent damage to soft key buttons, do not press the buttons with sharp objects such as pens, plastic cards, or fingernails.
NOTE: Only 1/4 in. (6 mm) round hot melt adhesive pel­lets can be used in the InvisiPac system. PSA-type adhesive pellets will not work in the InvisiPac system.
1. Direct the guns into an appropriate waste container.
2. Verify the shaker inlet is at the bottom of the empty adhesive pellets container. Optional vibrating adhe­sive pellets container, part 24R136, is available. See Accessories on page 89.
NOTE: The shaker inlet must be completely covered in adhesive pellets to effectively pull pellets into the tube.
3. Fill adhesive pellets container with hot melt adhe­sive pellets.
NOTE: See Appendix B - USB Downloading, Upload­ing on page 110 for detailed USB information.
Overview
The system includes a vacuum transfer system that pulls the adhesive pellets into the system as needed. Once melted, the adhesive enters the pump where it is pumped into the heated hoses then to the heated guns. The gun then briefly opens to dispense the desired quantity of adhesive.
Even though the system rises to operating temperature quickly, there is a Schedule function in the ADM that eliminates waiting for the system to heat up. The Sched­ule function automatically enables the heating system at the user-specified times so the system is ready to dis­pense when a shift begins. The Schedule function also disables the heating system at user-specified times to ensure the heating system is disabled when not being used.
4. Turn main power switch ON .
5. Open system air inlet ball valve.
WLE
6. Use pump air pressure regulator (C) to adjust pump air pressure to 0. See F
7. Use vacuum transfer air pressure regulator (E) to adjust vacuum transfer air pressure setting to 40-100 psi (280-690 kPa, 2.8-6.9 bar). Recom­mended setting is 60 psi (414 kPa, 4.1 bar). See
IG
. 1 on page 8.
Initial Startup and Prime
NOTE: All setup procedures must be completed prior to initial startup. See Setup on page 14.
26 3A2347T
Operation
FIG. 1 on page 8.
NOTE: Vacuum transfer will not begin operating until pump reaches operating temperature.
To prevent fire and explosion, never exceed the cleaning fluid’s rated temperature. If the system was just flushed, residual cleaning fluid is still in the system until the system is primed with adhesive. Do not raise temperature above cleaning fluid rated temperature until system is primed with adhesive.
NOTE: A new system may have residual oil due to test­ing at the factory prior to shipping. To prevent smoking, make sure to perform the following step.
8. On new systems only: temporarily adjust the melter
temperature to 250°F (121°C). See Select ADM Settings on page 21 for instructions.
9. Press to enable the heaters and pump.
12. With the guns open and the system up to tempera­ture, slowly increase pump air pressure until the pump begins to run very slowly. Approximately 20 psi (140 kPa, 1.4 bar) should be sufficient.
NOTE: Operation may be erratic below 20 psi (140 kPa,
1.4 bar).
13. Continue running the pump until clean, air-free material is dispensed from each gun.
14. When each gun is fully primed, adjust pump to desired pressure setting:
a. Adjust pump pressure to between 20-100 psi
(140-690 kPa, 1.4-6.9 bar).
b. Use separate gun controller to repeatedly open
and close each gun while inspecting the dis­pense pattern.
c. Repeat until desired dispense pattern is
achieved.
NOTE: When system is up to temperature, the pump will be activated automatically but will not start because there is no air pressure supplied to the pump.
NOTE: When the melter is up to temperature, the auto-fill function will initiate to fill the funnel with pellets.
10. On new systems only: After the melter has reached
250°F (121°C) and the funnel is filled with pellets, set the melter temperature back to the desired oper­ating temperature. See Select ADM Settings on page 21 for instructions.
11. Use separate gun controller to open the guns and keep them open.
NOTICE
In the following step, to prevent damage to the pump due to pump cavitation, do not supply more than 20 psi (140 kPa, 1.4 bar) air pressure to the pump until the system is fully primed.
Manual Refill
NOTE: Use Automatic Refill whenever possible. The
system uses Automatic Refill by default and must be manually changed to Manual Refill. Only use Manual Refill if the Automatic Refill system is not functioning properly and cannot be fixed in a timely manner. Per­form service to automatic feed system as soon as possi­ble to limit debris buildup on feed cap.
It is recommended to maintain a minimum flow rate of
1.5 lb/hour to prevent material from melting within the feed cap and funnel. If production rate is below
1.5 lb/hour or system sits at temperature without dis­pensing for extended periods of time, use manual refill­ing with caution. System flow rate can be monitored by enabling the Diagnostic screen.
1. On the System 3 screen (in the Setup screens), select “Manual” from the Refill mode dropdown.
2. Remove the phillips head screws then remove the funnel cap from the funnel.
3A2347T 27
Operation
3. Fill the funnel with adhesive pellets.
ti21154a
FIG. 19
4. Refill the funnel as needed to maintain the required dispense rate.
5. When finished dispensing for the day, dispense into a waste container until the material level is down to the smallest diameter section of the funnel then con­tinue purging material through the valve for an addi­tional 75 pump strokes.
NOTE: This will lower the adhesive level within the feed cap to the correct level to prevent any issues upon startup the following production day.
Automatic Refill
The system uses automatic refill by default. If the auto­matic refill system is malfunctioning and cannot immedi­ately be fixed, Manual Refill can be used.
To use automatic refill:
1. On the System 3 screen (in the Setup screens), select “Automatic” from the Refill mode dropdown.
2. Verify shaker and tube are connected to the system. See Attach Components on page 14.
3. Verify shaker inlet (K) is at the bottom of the adhe­sive pellets container that is filled with hot melt adhesive pellets. See F
NOTE: The shaker inlet must be completely covered in adhesive pellets in order for it to effectively pull pellets into the tube.
4. If not already set, use vacuum transfer air pressure regulator (E) to adjust vacuum transfer air pressure setting to 40-100 psi (280-690 kPa, 2.8-6.9 bar). Recommended setting is 60 psi (414 kPa, 4.1 bar). See F
IG
. 1 on page 8.
NOTE: The system will automatically transfer the pellets to the system as necessary.
IG
. 1 on page 8.
NOTE: Pump strokes can be monitored on the Mainte­nance screen, or by counting pump changeovers. To count pump changeovers, listen to the air motor exhaust pulses; two exhaust pulses equals one pump cycle (two strokes).
ti21154a
FIG. 20
Dispense
NOTE: Only hot melt adhesive pellets can be used in
the InvisiPac system.
1. If the system is empty or has air in the lines, perform Initial Startup and Prime procedure on page 26.
2. If main power switch is OFF, turn main power switch
ON .
NOTE: The main power switch should be left ON at all times when using the Schedule function.
3. Prepare for dispensing:
a. Verify air inlet ball valve (J) is open. See F
on page 8.
IG
. 1
28 3A2347T
Operation
b. Check pressure gauges (D, F) to verify vacuum
transfer and pump air pressures are set as desired. See F
c. If using Automatic Refill, see Automatic Refill
on page 28.
d. If using Manual Refill, see Manual Refill on
page 27.
e. Verify guns are closed.
4. Press to enable the heaters and pump.
NOTE: If using the Schedule function, the heaters and pump will be enabled automatically at the set time. You
will not need to press if using the Schedule func-
tion unless you wish to enable the heating system before the set time.
NOTE: When system is up to temperature, the pump will begin running automatically. It will stall at pressure unless a gun is open. Material will be dispensed when­ever a gun is open after the system is up to temperature.
5. When the system is up to temperature, use sepa-
rate gun controller to open and close the guns as desired to dispense material.
IG
. 1 on page 8.
Shutdown
Press to disable the heaters and pump. The
screen will say “Inactive”. If using the Schedule function, the heaters and pump will be disabled automatically at
the set time. You will not need to press if using the
Schedule function unless you wish to disable the heat­ing system before the set time. If the heaters were man­ually disabled, the Schedule function will automatically enable them at the next set time.
Do not turn the main power switch OFF if using the Schedule function.
Schedule
The Schedule function allows the user to specify times when the system will automatically turn ON and OFF the heaters and pump.
NOTE: While operating the system, the actual tempera­tures of the hose, gun, and system melter are displayed on the Home screen.
Set Schedule Times
NOTE: Times are set using a 24-hour clock. Several on
and off times can be set each day.
1. On the Schedule screen (in the Setup screens), set the ON times for each day of the week.
2. Set the OFF times for each day of the week.
3A2347T 29
Operation
Enable Schedule Function
The Schedule function is automatically enabled when values are entered in the Schedule screen. To disable the Schedule function, delete all values on the Schedule screen or turn the main power switch OFF to prevent system from automatically enabling and disabling the heaters.
How to Use the Schedule Function
At the end of the work day leave main power switch ON
. The Schedule function will automatically enable
and disable the heaters and pump at the specified times.
Pressure Relief Procedure
Follow the Pressure Relief Procedure whenever you see this symbol.
Drain the System
NOTE: The system must be drained prior to flushing
and prior to some maintenance and repair procedures.
1. On the System 3 screen (in the Setup screens), change the Refill Setting to “Manual”.
2. If the heating system is disabled, press to
enable the heaters and pump.
This equipment stays pressurized until pressure is manually relieved. To help prevent serious injury from pressurized fluid, such as skin injection, splashing fluid and moving parts, follow the Pressure Relief Procedure when you stop spraying and before cleaning, checking, or servicing the equipment.
1. Turn main power switch OFF .
2. Close the inlet air supply ball valve.
NOTE: Manually verify the pressure is relieved by open­ing the gun and ensuring no adhesive is dispensed.
3. Decrease pump air pressure to 0.
4. Close system air inlet ball valve.
5. Disconnect hose from gun inlet then place hose out­let in a waste container. Repeat for all hoses. Keep hose to gun electrical connector connected.
6. Open gun to allow residual fluid in gun to drain.
7. When system is at operating temperature, slowly increase pump air pressure until fluid begins flowing into the waste container.
NOTE: It may take several minutes to empty the sys­tem. When there is no melter fluid at the pump, the pump will begin to cycle faster.
8. When the pump begins to cycle faster, close the system air inlet ball valve.
9. Press to disable the heaters and pump.
10. Remove melter drain plug (W1). See F
9.
IG
. 2 on page
11. Disconnect hose from melter outlet.
30 3A2347T
Loading...
+ 90 hidden pages