Monitors pressures to provide ratio assurance on XP plural-component sprayers. For
professional use only. Not approved for use in explosive atmosphere locations.
Important Safety Instructions
Read all warnings and instructions in this manual
and the XP sprayer operation manual.
Save these instructions.
Models
262940:
Line Power Pressure Monitor Kit with Light Tower
262942:
Air Turbine Power Pressure Monitor Kit with Light Tower
Technical Data ...................................................29
Graco Standard Warranty.................................... 30
2
3A1331C
Overview
Operating Window
Below Minimum Spray Pressure
Topics Covered in this Chapter
♦ Operating Window
The purpose of the pressure monitor kit is to
shutdown the sprayer if abnormal pressure conditions
are detected to prevent spraying material that is not
mixed on ratio.
Two pressure transducers are added to read the A
and B fluid pressures in the outlet manifold and send
the readings back to the Local Control Module (LCM).
The control watches the difference between the A and
B pressures. The control will alarm if the pressures
split because of a plug, leak, or running out of fluid.
When an alarm indicates that the sprayer may be
off ratio, the air solenoid shuts off the air supply to
the proportioner motor. The light tower will indicate
an alarm has occurred, and the alarm code will
be on the LCM display. For more information see
Advisories and Alarms, page 11.
The following alarms can occur:
• Differential Pressure (B>A)
The air motor is allowed to automatically operate in
Circulation Mode with a yellow light anytime the fluid
pressures are below the minimum spray pressure.
This allows for loading the system and circulating the
fluids without alarms or shutdowns.
Above Minimum Spray Pressure
When the control sees the fluid pressures above the
minimum spray pressure for 3–30 seconds, and the
pressures are balanced within the pre-set limits, it
will automatically start the monitor mode, and the
green light on the light tower will change to solid
on. If the control does not see balanced pressures
within 30 seconds of going above the minimum spray
pressure, it will alarm and shut off the air motor. The
default minimum spray pressure is 2000 psi (14 MPa,
138 bar). Enter Setup Mode to change the minimum
spray pressure as necessary.
Maximum Spray Pressure
The control will alarm and shutdown if it sees either A
or B above the maximum working pressure of 7250
psi (50 MPa, 500 bar). Enter Setup Mode to reduce
the maximum allowable pressure set point.
• Differential Pressure (A>B)
• Pressure A High
• Pressure B High
• Air Solenoid Disconnected
• Pressure A Disconnected
• Pressure B Disconnected
3A1331C3
Component Identification
Topics Covered in this Chapter
♦ 262940 Line Power Kit
♦ 262942 Air Turbine Kit
♦ User Interface
262940 Line Power Kit
Figure 1
SD
SA
SL
SB
D
F
E
SG
A
SH
B
SC
SE
SJ
SF
C
G
Table .2 System Component Identification Table
Table .1 Cable Identification Table
Ref.CableIdentification Label
A
BAPressure
Power SupplyCAN
6–Blue
Transducer
C
BPressure
7–Red
Transducer
D
E
LCM Cable
Solenoid Extension
1–Blue
3–Red
Cable
F
Solenoid Cable
3–Red
GLightTower4–Green
4
Ref.System Component
SAXP Motor Air Controls (reference)
SBLocal Control Module (LCM)
SCPower Entry Fuses and Switch
SDMotor Air Solenoid Valve, 24 Volt
SEPower Supply, 24 Volt
SF
Light Tower, 24 Volt
SGXP Air Inlet Assembly (reference)
SH
Breakout Module
SJXP Fluid Manifold (reference)
SLMotor Air Hose
3A1331C
262942 Air Turbine Kit
SA
SD
SL
SB
D
F
E
SN
A
H
SH
SK
SF
H
J
SM
C
SG
Figure 2
Table .3 Cable Identification Table
Ref.CableIdentification Label
A
BAPressure
Power SupplyCAN
6–Blue
Transducer
CBPressure
7–Red
Transducer
D
E
LCM Cable
Solenoid Extension
1–Blue
3–Red
Cable
F
G
Solenoid Cable
Light Tower
HAir Tubing
JAir Exhaust
3–Red
4–Green
—
—
B
SJ
G
Table .4 System Component Identification Table
Ref.System Component
SAXP Motor Air Controls (reference)
SBLocal Control Module (LCM)
SDMotor Air Solenoid Valve, 12 Volt
SFLight Tower, 12 Volt
SGXP Air Inlet Assembly (reference)
SH
Breakout Module
SJXP Fluid Manifold (reference)
SK
SL
Turbine Air Regulator
Motor Air Hose
SMAir Powered Alternator, 12 Volt
SNAlternator Power Shutoff Valve
3A1331C5
User Interface
Figure 3
NOTICE
To prevent damage to soft key buttons, do not
press the buttons with sharp objects such as pens,
plastic cards, or fingernails.
Table .5 LCM Button Functions
ButtonFunction
ModeSelect between Run and Setup
Modes.
SprayStart and stop the air motor. The
motor will stay on indefinitely if
pressures are below minimum
spray pressure. Monitor mode
will start within 30 seconds if the
pressures are above the minimum
spray pressure and no errors exist.
All errors are ignored for up to the
first 30 seconds. Default is 2000
psi (138 MPa, 138 bar)
Arrows
Up/Down
Navigate up or down within a
screen or to a new screen.
Soft Keys
Soft keys activate the mode or
action represented by the icon next
to each soft key.
See Table 2 for soft key icons and
actions.
Top Soft Key: Edit data, accept
edited data, or move right within a
number field.
Bottom Soft Key: Enter a screen,
exit a screen, or cancel edited data.
63A1331C
Display Components
Table .6 Display Components
The following tables identify components shown on
the spray mode active, circulation mode active, alarm
active, and deviation active run screens. For more
information see Run Mode Details, page 25.
Spray Mode Active Screen
Figure 4
Circulation Mode Active Screen
Figure 5
IconFunction
Actual spray pressures
Differential pressure alarm
bar graph
Selected pressure units.
Indicates that you are in
spray mode.
Indicates that you are in
circulation mode.
Indicates that there is an
active alarm.
Indicates that there is an
active deviation.
Table .7 Display Soft Key Icons
IconFunction
Alarm Active Screen
Figure 6
Deviation Active Screen
Figure 7
Enter ScreenIn screens that have editable fields,
press to access the fields and
make changes.
Exit ScreenIn screens that have editable fields,
press to exit edit mode.
Enter
Right
CancelCancel a selection or edited data.
Clear Error
Log
In screens that have editable fields,
press to make data selections or
to enter changes.
In screens that have editable fields,
press to move to the right while in
afield.
Returns to the original data.
Clear entire error log..
3A1331C
7
Installation
Topics Covered in this Chapter
♦ Location
♦ Install Air Solenoid
♦ Install Electronics Box and LCM
♦ Install Pressure Transducers
♦ Connect Air Hoses and Cables
Shutdown the XP Sprayer before installing your
pressure monitor kit. Follow the Shutdown and
Pressure Relief Procedure in the XP Sprayer
operation manual. All electrical wiring must be
done by a qualified electrician and comply with all
local codes and regulations.
The procedures in this section are specific to each
component of the pressure monitor kit. For sprayer
installation instructions, refer to the XP70 Sprayer
Operation manual.
Install Air Solenoid
1. Disconnect the upper swivel and remove the
motor air line from the lower air manifold.
Note
On early XP sprayers, to remove the
existing air hose, it may be necessary to
remove the air filter assembly from the
XP and put it in a vice. New models XP
sprayers have an additional hose union.
2. For the turbine powered kit 262942, remove a
plug from the air manifold and install the 5/16 in.
x 4 ft (1.2 m) air hose.
Location
These pressure monitoring kits are not approved
for use in hazardous atmosphere locations.
Installing this kit on a XP Sprayer that is EX
approved, voids the approval. The EX mark should
be removed from the machine ID plate when this
kit is installed.
NOTICE
Do not store a XP Sprayer with a pressure monitor
kit outside in the rain. Use protective bag 16J717
to prevent damage to the electronic components,
used with the pressure monitor kit, when stored
outside.
Figure 8
3. Connect the air solenoid valve and new motor
air hose to the air inlet assembly. Ensure that
the air solenoid valve cable faces the back of
the machine.
83A1331C
Install Electronics Box and LCM
Early XP carts have two mounting holes and new XP
carts have three mounting holes. Complete steps 1
and 2 to drill a third mounting hole for the pressure
monitor kit. Complete step 2 if you have a new XP
cart.
1. Early XP carts with two mounting holes
a. Use two screws (61) and two nuts (62) to
mount the electronics box to the top of the
cart.
b. Use a marker to mark the bracket’s third
mounting hole.
c. Loosen the nuts (62) below the cart shelf and
remove the screws (61), and box bracket.
Center punch and drill a 5/16 in. hole in the
top of the cart.
2. New XP carts with three mounting holes.
a. Use three screws (61) and three nuts (62) to
mount the box bracket to the cart.
b. For power supply kits, install the appropriate
power supply cord(s). US, European, and
Australia/Asia cord adapters are supplied.
See Technical Data, page 29.
Early XP Cart Installation
Figure 9
Insta
1. Remove plugs from the circulation manifold.
2. Connect pressure transducer (4), with blue
ll Pressure Transducers
Note
Keep plugs if you will ever remove the
pressure monitor kit.
#6 label, with black o-ring (13) to the A side
of the circulation manifold. Connect pressure
transducer (4), with red #7 label, with black o-ring
(13) to the B side of the circulation manifold.
Tighten to 40–50 ft-lb (54–67 N•m) before
applying fluid pressure.
ssure Transducers
Pre
ure 10
Fig
3A1331C9
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.