Graco 313903C User Manual

Instructions
ti14387
ti14386
Model: 562870
Model: 562871
Lube Sentinel II Monitor
- Monitors and computes lube cycle lubrication rates -
Part No.: 562870 JIC Enclosure - Not for use in explosive atmospheres! Part No.: 562871 - Includes Explosion Proof Enclosure
Read all warnings and instructions in this manual. Save these instructions.
See Technical Data, page 26 for model information, including power requirements.
313903C
EN
Bulletin: 44701, 555840

Warnings

Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. Refer back to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before disconnecting any cables and before servicing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maximum working pressure or temperature rating of the lowest rated system com­ponent. See Technical Data in all equipment manuals.
Do not leave the work area while equipment is energized or under pressure. Turn off all equipment and follow the Pressure Relief Procedure in this manual when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manu­facturer’s replacement parts only.
Do not alter or modify equipment.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
2 313903C

Installation

AUTOMATIC SYSTEM ACTIVATION HAZARD
Unexpected activation of the system could result in seri­ous injury, including skin injection and amputation.
This device has an automatic timer that activates the pump lubrication system when power is connected or when exiting the programming function. Before you install or remove the Lube Sentinel II Monitor from the system, disconnect and isolate all power supplies and relieve all pressure.

Grounding

Installation

Electrical Connections

Electrical interference from improperly installed equip­ment may cause erratic behavior of the device.
When installing the Sentinel II, use 18 - 24 gauge machine tool wire (MTW). 18 gauge wire is recom­mended for the input power.
It is also recommended that wiring be run in its own con­duit to minimize electrical interference. If the installation is in an area of high electrical noise/interference, or in trays with other control wiring, a shielded cable pair is recommended.
The equipment must be grounded. Grounding reduces the risk of static and electric shock by providing an escape wire for the electrical current due to static build-up or in the event of a short circuit.
Ground connections should not be connected to con­duits or other electrical boxes. The ground wire should be connected to a grounding rod or a grounded bus bar that is tied to a grounding rod in the earth.
Shielded cable should be used on applications where engines or heavy-duty motors are in close proximity to the monitor, wiring or sensors. If shield cable is used, the shield should stay intact as close to the termination screws as possible. (Do not remove shielding from cable if it is in a shared tray).
The shield should be connected to the designated ground at both the sensor and the monitor.
313903C 3
Installation

Circuit Board Connections

(FIG. 1 - FIG. 7 show the circuit board and power connections necessary to install the Lube Sentinel II Monitor in your lubrication system.)
All electrical connections are made to terminals along both sides and the bottom of the main circuit board, except for serial communications. Serial communication connections are made via a special plug-in header block.
External Connection Terminals
FIG. 1
4 313903C
Terminal Strip -
Ignition Shutdown*
Magneto Grounding
External Flow/No Flow Lights
Energize External Load (relay coil, etc.)
*NOTE: Do not
connect to high voltage. Connect to controls only.
Right Side Power Connections
Terminals Power Connection
115/230 VAC power input terminals
1 & 2
(polarity insensitive) 3 Earth Ground 4 +24 VDC Input 5 0 VDC Input 6 +24 VDC Out (for sensor use) 7 0 VDC Out (for sensor use) 8 0 VDC Out (for sensor use)
F
Terminal Strip Bottom - Fault Relay Connections
Terminals 9 - 14, Zone 1 Fault Relay:
Installation
IG. 2
The zone fault relay is a double-pole, double-throw (DPDT), Form-C relay. Relay contacts are wired directly to the ter­minal strip. Pole “A” uses terminals 9 (N.C.), 10 (com) and 11 (N.O.). Pole “B” uses terminal 12 (N.C.), 13 (com) and 14 (N.O.). Power is not supplied to these contacts. Contacts are rated 0.5 ampere at 125VAC and 1.0 ampere at 30VDC. The relays may be programmed to either energize or deenergize during a fault. (See F
IG. 3.)
FIG. 3: Examples of Wiring for Zone 1 Faults
313903C 5
Installation
Ignition Shutdown Magneto Grounding
External Flow/No Flow Lights Energize External Load (relay coil, etc.)
Terminals 15 - 20, Zone 2 Fault Relay:
Relay data for Zone 2 is the same as for Zone 1. Pole “A” (for Zone 2) uses terminals 15 (nc), 16 (com) and 17 (no). Pole “B” (for Zone 2) uses terminals 18 (nc), 19 (com) and 20 (no). (See F
IG. 4.)
F
IG. 4: Wiring Examples when Zone 1 and Zone 2 are used.
6 313903C
Terminals 21 - 23, Power Failure Relay:
The power-fail relay is a single-pole, single-throw (SPST) relay rated for 0.5 ampere at 125 VAC or 1.0 ampere at 30 VDC. Terminals are to Form “C” contacts: 21 (nc), 22 (com) and 23 (no). This relay will be ener­gized as long as power supply voltage is active (F
IG. 5).
Terminal Strip Left Side Bottom - Sensor Inputs
Terminals Sensor Inputs
Installation
FIG. 5: Power Failure Relay Connections
+25 & -26 For Factory Use +27 & -28 Tachometer Input +29 & -30 Bypass Zone 2 +31 & -32 Bypass Zone 1 +33 & -34 Reset Alarm +35 & -36 Cycle Switch Zone 2 +37 & -38 Cycle Switch Zone 1
F
IG. 6: Typical Input Devices
313903C 7
Installation
Terminal Strip Left Side TOP ­Open Collector Outputs
These outputs are open collector, floating TTL outputs. There are no protection devices on these drivers. If the transistor output is connected directly to +24 volts with no load, these devices may be damaged. These drivers are optically isolated from the local power supply and their commons are floating. To utilize these drivers, Ter­minal 43 must be connected to the common of the volt­age supply for the device being driven (such as a PLC input power supply, input common).
Terminals Sensor Inputs
39 +24 VDC Out 40 Sensor Echo Zone 1 41 Sensor Echo Zone 2 42 System Fault 43 Floating Drive Common

Safety Set (optional)

The Safety Set is a plug-in option that allows the opera­tor to manually activate the function buttons from out­side the enclosure.
1. Disconnect all power to the monitor.
2. Verify that the module is properly aligned and all pins are in their proper sockets.
3. Place the magnetic Datawand over the Safety Set target above the desired button to activate the func­tion buttons (F
The Datawand activates the sensor through the win­dow and keeps it activated until the Datawand is removed.
IG. 8).
F
IG. 7
NOTICE
Use caution when handling and storing the Datawand. It emits a strong magnetic field. Bringing the Datawand near magnetic media found on credit cards, floppy dis­kettes, or audio tape could destroy stored information!
F
IG. 8
8 313903C
Installation

Serial Communication

Remote communication (up to 100 feet) can be achieved using an RS-232-type port.
Information can be read from, or written to the Sentinel II by a personal computer (or other intelligent device). This communication is a master/slave protocol with the Senti­nel II as the slave and the PC as the master.
NOTE: With the exception of a sign-on message when powered up, the slave will not send any data or informa­tion unless requested by the master.
Data is sent across the serial port as ASCII charac­ters with leading zeros suppressed.
A BYTE can be up to 3 characters.
An INTERGER can be up to 5 characters.
Each command and each response is terminated with a carriage return (CR) (ASCII - Hexadecimal 0D or Decimal 13)
Table 1: Serial Pin Data
Pin # Description
1
2
3
Signal Ground 5 7
Read Data 2 3
Send Data 3 2
DB-9F
1
SERIAL
6
PC
J1
PC
DB-25F
If the data is not presented in the correct format, the command is not executed. Note that a “read” should be made after doing a “write” to verify the proper action has taken place.
NOTE: Changes made through the serial link are active but not permanent until the “save to E
2
” command (WC) is issued. If the WC command is not issued, turning the power off and on restores the originally saved operating parameters. See page 26 for recommended, user sup­plied, communication port connectors.
Serial Communication Wiring
The Serial Communications are wired through a
6-point header on 0.1 inch centers (F
Only three pins (1 - 3) are used (See Table 1).
The other end of this cable may be connected to a
personal computer.
Pin 1 (nearest to the transformer) is the signal
ground.
IG. 9).
F
IG. 9
SERIAL PORT PLUG
1 SIG COMMON
2 READ DATA (OUTPUT)
3 XMIT DATA (INPUT
4
5
6
2 RCV DATA (INPUT)
3 XMIT DATA (INPUT)
5 SIGNAL GROUND
TO PC SERIAL PORT
2 XMIT DATA (OUTPUT)
3 RCV DATA (INPUT)
7 SIGNAL GROUND
Pin 2 is an output that connects to received data
at PC.
Pin 3 is an input that connects to transmit data
of the PC.
313903C 9
Loading...
+ 19 hidden pages