- Monitors and computes lube cycle lubrication rates -
Part No.: 562870 JIC Enclosure - Not for use in explosive atmospheres!
Part No.: 562871 - Includes Explosion Proof Enclosure
Important Safety Instructions
Read all warnings and instructions in this manual.
Save these instructions.
See Technical Data, page 26 for model information, including power requirements.
313903C
EN
Bulletin: 44701, 555840
Warnings
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. Refer back
to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where
applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric
shock.
•Turn off and disconnect power at main switch before disconnecting any cables and before servicing
equipment.
•Connect only to grounded power source.
•All electrical wiring must be done by a qualified electrician and comply with all local codes and
regulations.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
•Do not operate the unit when fatigued or under the influence of drugs or alcohol.
•Do not exceed the maximum working pressure or temperature rating of the lowest rated system component. See Technical Data in all equipment manuals.
•Do not leave the work area while equipment is energized or under pressure. Turn off all equipment
and follow the Pressure Relief Procedure in this manual when equipment is not in use.
•Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
•Do not alter or modify equipment.
•Use equipment only for its intended purpose. Call your distributor for information.
•Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
•Do not kink or over bend hoses or use hoses to pull equipment.
•Keep children and animals away from work area.
•Comply with all applicable safety regulations.
2313903C
Installation
AUTOMATIC SYSTEM ACTIVATION HAZARD
Unexpected activation of the system could result in serious injury, including skin injection and amputation.
This device has an automatic timer that activates the
pump lubrication system when power is connected or
when exiting the programming function. Before you
install or remove the Lube Sentinel II Monitor from the
system, disconnect and isolate all power supplies and
relieve all pressure.
Grounding
Installation
Electrical Connections
Electrical interference from improperly installed equipment may cause erratic behavior of the device.
When installing the Sentinel II, use 18 - 24 gauge
machine tool wire (MTW). 18 gauge wire is recommended for the input power.
It is also recommended that wiring be run in its own conduit to minimize electrical interference. If the installation
is in an area of high electrical noise/interference, or in
trays with other control wiring, a shielded cable pair is
recommended.
The equipment must be grounded. Grounding reduces
the risk of static and electric shock by providing an
escape wire for the electrical current due to static
build-up or in the event of a short circuit.
Ground connections should not be connected to conduits or other electrical boxes. The ground wire should
be connected to a grounding rod or a grounded bus bar
that is tied to a grounding rod in the earth.
Shielded cable should be used on applications where
engines or heavy-duty motors are in close proximity to
the monitor, wiring or sensors. If shield cable is used,
the shield should stay intact as close to the termination
screws as possible. (Do not remove shielding from cable
if it is in a shared tray).
The shield should be connected to the designated
ground at both the sensor and the monitor.
313903C3
Installation
Circuit Board Connections
(FIG. 1 - FIG. 7 show the circuit board and power connections necessary to install the Lube Sentinel II Monitor in your
lubrication system.)
All electrical connections are made to terminals along both sides and the bottom of the main circuit board, except for
serial communications. Serial communication connections are made via a special plug-in header block.
External Connection Terminals
FIG. 1
4313903C
Terminal Strip -
Ignition Shutdown*
Magneto Grounding
External Flow/No Flow Lights
Energize External Load (relay coil, etc.)
*NOTE: Do not
connect to high
voltage.
Connect to
controls only.
Right Side Power Connections
TerminalsPower Connection
115/230 VAC power input terminals
1 & 2
(polarity insensitive)
3Earth Ground
4+24 VDC Input
50 VDC Input
6+24 VDC Out (for sensor use)
70 VDC Out (for sensor use)
80 VDC Out (for sensor use)
F
Terminal Strip Bottom - Fault Relay Connections
Terminals 9 - 14, Zone 1 Fault Relay:
Installation
IG. 2
The zone fault relay is a double-pole, double-throw (DPDT), Form-C relay. Relay contacts are wired directly to the terminal strip. Pole “A” uses terminals 9 (N.C.), 10 (com) and 11 (N.O.). Pole “B” uses terminal 12 (N.C.), 13 (com) and
14 (N.O.). Power is not supplied to these contacts. Contacts are rated 0.5 ampere at 125VAC and 1.0 ampere at
30VDC. The relays may be programmed to either energize or deenergize during a fault. (See F
Relay data for Zone 2 is the same as for Zone 1. Pole “A” (for Zone 2) uses terminals 15 (nc), 16 (com) and 17 (no).
Pole “B” (for Zone 2) uses terminals 18 (nc), 19 (com) and 20 (no). (See F
IG. 4.)
F
IG. 4: Wiring Examples when Zone 1 and Zone 2 are used.
6313903C
Terminals 21 - 23, Power Failure Relay:
The power-fail relay is a single-pole, single-throw
(SPST) relay rated for 0.5 ampere at 125 VAC or 1.0
ampere at 30 VDC. Terminals are to Form “C” contacts:
21 (nc), 22 (com) and 23 (no). This relay will be energized as long as power supply voltage is active (F
IG. 5).
Terminal Strip Left Side Bottom - Sensor Inputs
TerminalsSensor Inputs
Installation
FIG. 5: Power Failure Relay Connections
+25 & -26For Factory Use
+27 & -28Tachometer Input
+29 & -30Bypass Zone 2
+31 & -32Bypass Zone 1
+33 & -34Reset Alarm
+35 & -36Cycle Switch Zone 2
+37 & -38Cycle Switch Zone 1
F
IG. 6: Typical Input Devices
313903C7
Installation
Terminal Strip Left Side TOP Open Collector Outputs
These outputs are open collector, floating TTL outputs.
There are no protection devices on these drivers. If the
transistor output is connected directly to +24 volts with
no load, these devices may be damaged. These drivers
are optically isolated from the local power supply and
their commons are floating. To utilize these drivers, Terminal 43 must be connected to the common of the voltage supply for the device being driven (such as a PLC
input power supply, input common).
TerminalsSensor Inputs
39+24 VDC Out
40Sensor Echo Zone 1
41Sensor Echo Zone 2
42System Fault
43Floating Drive Common
Safety Set (optional)
The Safety Set is a plug-in option that allows the operator to manually activate the function buttons from outside the enclosure.
1. Disconnect all power to the monitor.
2. Verify that the module is properly aligned and all
pins are in their proper sockets.
3. Place the magnetic Datawand over the Safety Set
target above the desired button to activate the function buttons (F
The Datawand activates the sensor through the window and keeps it activated until the Datawand is
removed.
IG. 8).
F
IG. 7
NOTICE
Use caution when handling and storing the Datawand. It
emits a strong magnetic field. Bringing the Datawand
near magnetic media found on credit cards, floppy diskettes, or audio tape could destroy stored information!
F
IG. 8
8313903C
Installation
Serial Communication
Remote communication (up to 100 feet) can be
achieved using an RS-232-type port.
Information can be read from, or written to the Sentinel II
by a personal computer (or other intelligent device). This
communication is a master/slave protocol with the Sentinel II as the slave and the PC as the master.
NOTE: With the exception of a sign-on message when
powered up, the slave will not send any data or information unless requested by the master.
•Data is sent across the serial port as ASCII characters with leading zeros suppressed.
•A BYTE can be up to 3 characters.
•An INTERGER can be up to 5 characters.
•Each command and each response is terminated
with a carriage return (CR) (ASCII - Hexadecimal
0D or Decimal 13)
Table 1: Serial Pin Data
Pin #Description
1
2
3
Signal Ground57
Read Data23
Send Data32
DB-9F
1
SERIAL
6
PC
J1
PC
DB-25F
•If the data is not presented in the correct format, the
command is not executed. Note that a “read” should
be made after doing a “write” to verify the proper
action has taken place.
NOTE: Changes made through the serial link are active
but not permanent until the “save to E
2
” command (WC)
is issued. If the WC command is not issued, turning the
power off and on restores the originally saved operating
parameters. See page 26 for recommended, user supplied, communication port connectors.
Serial Communication Wiring
•The Serial Communications are wired through a
6-point header on 0.1 inch centers (F
•Only three pins (1 - 3) are used (See Table 1).
•The other end of this cable may be connected to a
personal computer.
✓ Pin 1 (nearest to the transformer) is the signal
ground.
IG. 9).
F
IG. 9
SERIAL PORT PLUG
1 SIG COMMON
2 READ DATA (OUTPUT)
3 XMIT DATA (INPUT
4
5
6
2 RCV DATA (INPUT)
3 XMIT DATA (INPUT)
5 SIGNAL GROUND
TO PC SERIAL PORT
2 XMIT DATA (OUTPUT)
3 RCV DATA (INPUT)
7 SIGNAL GROUND
✓ Pin 2 is an output that connects to received data
at PC.
✓ Pin 3 is an input that connects to transmit data
of the PC.
313903C9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.