Graco 313877E User Manual

Page 1
Setup - Operation
PD44
Control Box
Meter, mix and dispense system for precise two-component micro-dispensing of sealants and adhesives. Not for use in explosive atmospheres.
Read all warnings and instructions in this manual. Save these instructions.
See page 3 for model information, including maximum working pressure and approvals.
313877E
EN
Micrometer PD44 and LRT PD44 Control Box shown
Page 2
Contents
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Component Identification . . . . . . . . . . . . . . . . . . . . 6
Control Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PD44 Dispense Valve . . . . . . . . . . . . . . . . . . . . . 8
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Micrometer and LRT PD44 Only . . . . . . . . . . . . 10
Motor Driven PD44 Only . . . . . . . . . . . . . . . . . . 11
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dispensing Operation . . . . . . . . . . . . . . . . . . . . . . 13
HMI Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Screen Navigation Diagrams . . . . . . . . . . . . . . 14
Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Posidot Control Screen
(Micrometer PD44 and
LRT PD44 only) . . . . . . . . . . . . . . . . . . . . . 17
Metering Valve Control Screen
(Motor Driven PD44 only) . . . . . . . . . . . . . . 18
Shot Size Screen
(LRT PD44 only) . . . . . . . . . . . . . . . . . . . . . 20
Shot Size Screen
(Motor Driven PD44 Only) . . . . . . . . . . . . . 21
Level 1 Control Screen . . . . . . . . . . . . . . . . . . . 22
Level 2 Control Screen . . . . . . . . . . . . . . . . . . . 23
Purge Timer Screen . . . . . . . . . . . . . . . . . . . . . 25
Status Screen . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Motor Status Screen
(Motor Driven PD44 only) . . . . . . . . . . . . . . 30
Motor Error Codes Screen
(Motor Driven PD44 Only) . . . . . . . . . . . . . 32
Supervisor Screen
(LRT PD44 Only) . . . . . . . . . . . . . . . . . . . . 33
Supervisor Screen
(Motor Driven PD44 Only) . . . . . . . . . . . . . 34
Supervisor Help Screen
(Motor Driven PD44 Only) . . . . . . . . . . . . . 35
Calibration Screen
(LRT PD44 Only) . . . . . . . . . . . . . . . . . . . . 36
Pressure Relief Procedure . . . . . . . . . . . . . . . . . . 38
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Optional Customer Inputs . . . . . . . . . . . . . . . . . . . 39
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . 42
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . . 42
2 313877E
Page 3

Related Manuals

PD44 Manuals
Part Description
313876 PD44 Dispense Valve Operation - Parts
Feed System Manuals
306565 Air-Driven, Stainless Steel Agitators
307043
308116 Severe-Duty, UHMWPE/PTFE or PTFE
308167 Low Volume Air Regulators
308168 High Volume Air Regulators
308169 Air Filters, Lubricators and Kits
309306
312376 Stainless Steel Agitator Kit
313526
406088
Monark
Packed Stainless Steel Pumps
Air-Operated Husky
Check-Mate
Check-Mate
®
Air Motor
®
Pump Packages
®
Ram Packages
Diaphragm Pumps
Related Manuals

Models

Max Air Working
PD44 Control Box
Model
Linear Resistive
Transducer (LRT)
Micrometer
Motor Driven
* If a custom PD44 is ordered, it will not be CE
approved unless otherwise noted.
Pressure
psi (MPa, bar) Voltage CE Approved*
100 (0.7, 7) 120/240V,
100 (0.7, 7) 120/240V,
100 (0.7, 7) 120/240V,
50/60Hz
50/60Hz
50/60Hz
313877E 3
Page 4

Warnings

Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. Refer back to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where applicable.
WARNING
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed.
Read MSDS’s to know the specific hazards of the fluids you are using.
Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
Always wear impervious gloves when spraying or cleaning equipment.
If this equipment is used with isocyanate material, see additional information on isocyanates in Iso­cyanate Conditions Section of this manual.
PERSONAL PROTECTIVE EQUIPMENT
You must wear appropriate protective equipment when operating, servicing, or when in the operating area of the equipment to help protect you from serious injury, including eye injury, inhalation of toxic fumes, burns, and hearing loss. This equipment includes but is not limited to:
Protective eyewear
Clothing and respirator as recommended by the fluid and solvent manufacturer
•Gloves
Hearing protection
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help prevent fire and explosion:
Use equipment only in well ventilated area.
Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop cloths (potential static arc).
Keep work area free of debris, including solvent, rags and gasoline.
Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes are present.
Ground all equipment in the work area. See Grounding instructions.
Use only grounded hoses.
Hold gun firmly to side of grounded pail when triggering into pail.
If there is static sparking or you feel a shock, stop operation immediately. Do not use equipment until you identify and correct the problem.
Keep a working fire extinguisher in the work area.
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause elec­tric shock.
Turn off and disconnect power cord before servicing equipment.
Use only grounded electrical outlets.
Use only 3-wire extension cords.
Ensure ground prongs are intact on power and extension cords.
Do not expose to rain. Store indoors.
4 313877E
Page 5
Warnings
WARNING
PRESSURIZED EQUIPMENT HAZARD
Fluid from the gun/dispense valve, leaks, or ruptured components can splash in the eyes or on skin and cause serious injury.
Follow Pressure Relief Procedure in this manual, when you stop spraying and before cleaning, checking, or servicing equipment.
Tighten all fluid connections before operating the equipment.
Check hoses, tubes, and couplings daily. Replace worn or damaged parts immediately.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maximum working pressure or temperature rating of the lowest rated system component. See Technical Data in all equipment manuals.
Do not leave the work area while equipment is energized or under pressure. Turn off all equipment and follow the Pressure Relief Procedure in this manual when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manu­facturer’s replacement parts only.
Do not alter or modify equipment.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
PLASTIC PARTS CLEANING SOLVENT HAZARD
Use only compatible water-based solvents to clean plastic structural or pressure-containing parts. Many solvents can degrade plastic parts and cause them to fail, which could cause serious injury or property damage. See Technica l Data in this and all other equipment instruction manuals. Read fluid and solvent manufacturer’s warnings.
313877E 5
Page 6

Component Identification

Component Identification

Control Boxes

AB C
D
ST
Key:
A Emergency Stop B Control Power Switch C Touch Panel D Alarm Speaker E Power Input F Start Options Connection GCustom I/O H A Tank Level Controls Connection J B Tank Level Controls Connection
HJGFE
A TANK
B TANK
CUSTOMER I/O
START
2
5 34
7
617
PG-3
LEVEL CONTROLS
2
5 34
PG-4
SPOOL VALVE
108 107
LOAD
SIGNAL CONNECTION
1
2
1
1
6
3
2
5 34
4
7
6
PG-2
PG-8
AIR
CYLINDER
106
105
RET
DISP
EXT
LEVEL CONTROLS
KMain Air Inlet L Dispense Valve I/O Connection M Spool Valve Load Connection N Spool Valve Dispense Connection P Air Cylinder Extend Connection R Air Cylinder Retract Connection S Air Pressure Regulator T Air Pressure Gauge
100V TO 250V AC
MACHINE I/O
L
12563
7
4
11 8
129131014
PG-1
KM NPR
FIG. 1: Micrometer and LRT PD44 Control Box
6 313877E
Page 7
BAC
CONTROL POWER
Component Identification
D
AUDIO ALARM
START OPTIONS
1
24
3
MOTOR
VALVE I/O
F
VERIFY INCOMING VOLTAGE
WITH VOLTAGE SWITCH SETTING
BEFORE CONNECTING POWER
L
Key:
A Emergency Stop B Control Power Switch C Touch Panel D Alarm Speaker E Power Input
FIG. 2: Motor Driven PD44 Control Box
U
E
F Start Options Connection H A Tank Level Controls Connection J B Tank Level Controls Connection L Dispense Valve I/O Connection U Motor Connection
J
H
313877E 7
Page 8
Component Identification

PD44 Dispense Valve

See PD44 Operation manual 313876 for detailed dis­pense valve component identification and instructions.
F
IG. 3: PD44 Micrometer Dispense Valve
8 313877E
Page 9

Grounding

This product must be grounded. In the event of an elec­trical short circuit, grounding reduces the risk of electric shock by providing an escape wire for the electric cur­rent.
Grounding plug units: this product is equipped with a cord having a grounding wire with an appropriate grounding plug. The plug must be plugged into an outlet that is properly installed and grounded in accordance with all local codes and ordinances.
Hard-wired units: the grounding wire must be used. All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
Grounding
Air and fluid hoses: use only electrically conductive hoses.
Fluid supply container: follow local code.
Solvent pails used when flushing: follow local code.
Use only conductive metal pails, placed on a grounded surface. Do not place the pail on a non-conductive sur­face, such as paper or cardboard, which interrupts grounding continuity.
313877E 9
Page 10

Setup

Setup

Micrometer and LRT PD44 Only

1. Connect air supply to main air inlet on control box. Air supply must include a shut-off/bleed valve that bleeds pressure past the shut-off/bleed valve and an air-water separator/filter.
A TANK
B TANK
CUSTOMER I/O
START
CYLINDER
100V TO 250V AC
1
3
2
4
PG-8
MACHINE I/O
12563
7
4
11 8
129131014
PG-1
AIR
105
RET
2
5 34
7
617
PG-3
LEVEL CONTROLS
2
5 34
PG-4
SPOOL VALVE
108 107
LOAD
SIGNAL CONNECTION
2
1
1
5 34
7
6
6
PG-2
106
DISP
EXT
LEVEL CONTROLS
2. Connect air lines from control box to dispense valve. Match the number and color codes on the fittings and connections. See the following table and illus­tration.
3. Connect Dispense Valve I/O, and Start Options logic cables. If level controls are installed, connect Level Controls logic cables.
NOTICE
Feed system and main logic control system must use separate air supplies.
A TANK
B TANK
CUSTOMER I/O
START
106
EXT
CYLINDER
100V TO 250V AC
1
3
2
4
PG-8
MACHINE I/O
12563
7
4
11 8
129131014
PG-1
AIR
105
RET
LEVEL CONTROLS
2
5 34
7
617
PG-3
LEVEL CONTROLS
2
5 34
PG-4
SPOOL VALVE
108 107
LOAD
SIGNAL CONNECTION
2
1
1
5 34 7
6
6
PG-2
DISP
4. Adjust air pressure regulator to 80 psi (0.6 MPa, 6bar).
5. Perform Setup procedure for dispense valve and feed system components. See Related Manuals on page 3.
Connection Color
Connection Description
Red Extend Blue Retract Yellow Dispense Green Reload
A TANK
B TANK
CUSTOMER I/O
START
CYLINDER
100V TO 250V AC
1
3
2
4
PG-8
MACHINE I/O
12563
7
4
11 8
129131014
PG-1
AIR
105
RET
2
5 34
7
617
PG-3
LEVEL CONTROLS
2
5 34
PG-4
SPOOL VALVE
108 107
LOAD
SIGNAL CONNECTION
2
1
1
5 34
7
6
6
PG-2
106
DISP
EXT
LEVEL CONTROLS
10 313877E
Page 11

Motor Driven PD44 Only

1. Connect Dispense Valve I/O, Start Options, and Motor logic cables. If level controls are installed, connect Level Controls logic cables.
NOTICE
Feed system and main logic control system must use separate air supplies.
AUDIO ALARM
START OPTIONS
1
24
3
MOTOR
VALVE I/O
VERIFY INCOMING VOLTAGE
WITH VOLTAGE SWITCH SETTING
BEFORE CONNECTING POWER
Setup
2. Adjust customer supplied air pressure regulator to 80 psi (0.6 MPa, 6 bar).
3. Perform Setup procedure for dispense valve and feed system components. See Related Manuals on page 3.
313877E 11
Page 12

Startup

Startup
NOTE: See HMI Operation starting on page 14 for
detailed HMI instructions.
1. Press the Control Power On button.
2. On Micrometer and LRT PD44s, navigate to the Posidot
On Motor Driven PD44s, navigate to the Metering Valve Control screen.
3. Under Posidot Mode, press the Retract button.
NOTE: On LRT and Motor Driven PD44s, when there is an Emergency Stop condition or the system power is lost, the shot selection resets to “0”. The operator must then select a shot.
®
Control screen.
NOTE: On Micrometer PD44s, skip steps 4-7.
4. Navigate to the Shot Size screen.
5. Select a shot number.
6. Navigate to the Pump Mode screen.
7. Press the Shot button to select Shot Mode.
8. Verify air pressure is set to 80 psi (5.6 bar).
9. Perform feed system startup procedure(s). See Related Manuals on page 3.
10. Perform dispense valve startup procedure. See Related Manuals on page 3.
12 313877E
Page 13

Dispensing Operation

Dispensing Operation
NOTE: See HMI Operation on page 14 for detailed HMI instructions.
The foot switch, the “Start” button, and the optional Cus­tomer Start Signal can be used to initiate shots. These are referred to as start devices.
Perform a Shot
1. On Micrometer and LRT PD44s, navigate to the Posidot Control screen. On Motor Driven PD44s, navigate to the Metering Valve Control screen.
2. Under Posidot Mode, press the Retract button.
3. Press the Shot button to select Shot Mode.
4. Press and release the start device to perform one shot.
Retract Piston
1. On Micrometer and LRT PD44s, navigate to the Posidot Control screen. On Motor Driven PD44s, navigate to the Metering Valve Control screen.
2. Under Posidot Mode, press the Retract button.
Extend Piston
1. On Micrometer and LRT PD44s, navigate to the Posidot Control screen. On Motor Driven PD44s, navigate to the Metering Valve Control screen.
2. Under Posidot Mode, press the Extend button.
Dispense Continuously
The valve dispenses continuously until the end of the stroke is reached.
1. On Micrometer and LRT PD44s, navigate to the Posidot Control screen. On Motor Driven PD44s, navigate to the Metering Valve Control screen.
2. Under Posidot Mode, press the Retract button.
3. Press the Continuous button.
4. On Micrometer and LRT PD44s, press and release the start device. Under Posidot Mode, press the Retract button to stop dispensing and retract the metering rods. On Motor Driven PD44s, press and hold the start device to dispense continuously. Release the start device to stop dispensing and retract the metering rods.
313877E 13
Page 14

HMI Operation

HMI Operation

Screen Navigation Diagrams

Micrometer PD44
Main Screen
Status
Purge Timer
Level 1 Control Level 2 Control
FIG. 4
LRT PD44
Main Screen
Posidot Control
Posidot Control
Shot Size/Flow Rate
Level 1 Control
Purge Timer
Status
Supervisor
Level 2 Control
Calibration
Calibration Help
FIG. 5
14 313877E
Page 15
Motor Driven PD44
Main Screen
HMI Operation
Metering Valve Control
Shot Size/Flow Rate
FIG. 6
Level 1 Control
Level 2 Control
Purge Timer
Status
Motor Status Motor Error Codes
Supervisor Supervisor Help
313877E 15
Page 16
HMI Operation

Main Screen

NOTE: The Error Code button is shown on every screen
on the Motor Driven PD44.
Motor Driven PD44 Main Screen shown
Screen Access Buttons
All buttons on the main screen except for the Password and Error Code buttons open a new specified screen. For example, pressing the “Status” button opens the Status screen. The Password and Error Code buttons are only on the Motor Driven PD44 screens.
Password (Motor Driven PD44 only)
The password button enables the user to changes values in certain screens.
To access the password press the Password Access button (shown as “=0000”). When the keyboard appears enter password “5810”
then press the Enter key.
Error Code (Motor Driven PD44 only)
NOTE: The Error Code button is shown on every screen
on the Motor Driven PD44.
On all screens that it is shown, the Error Code button resets the error seen in the error string (shown as “<0000000000”) and the error code number (shown as “<000”). See the Motor Error Codes screen for more information, page 32.
16 313877E
Page 17
HMI Operation
Posidot Control Screen
(Micrometer PD44 and LRT PD44 only)
NOTE: A “1” indicates that the button is in the “ON” position. A “0” indicates that the button is in the “OFF” position.
LRT PD44 Posidot Control screen shown
Start button
When the Start button is pressed, the machine starts the cycle for the selected Pump Mode.
Pump Mode
NOTE: The metering rods must be retracted prior to changing any setting under Pump Mode. See Retract Piston, page 13.
Retract Mode
The air cylinder and pumps immediately retract and remain in the retracted position. This is used for mainte­nance purposes only.
Extend Mode
The air cylinder and pumps immediately extend and remain in the extended position. This is the position that must be selected when the pump is idle for a long period of time.
Shot Mode
The machine fully cycles the number of times displayed in the Cycle Counter field when the start device is pressed and released. The machine cycles continuously when the start device is pressed and held.
Continuous Mode
The machine continually cycles the pumps when the START DEVICE is pressed.
Purge Timer On /Off
See Purge Timer screen for definition, page 25.
Dwell Timer (LRT and Motor Driven Only)
See Purge Timer screen for definition, page 25.
Cycle Counter On /Off (Micrometer PD44 Only)
Cycle Counter not shown. See Purge Timer screen for definition, page 25.
Select Shot Size (LRT PD44 Only)
See Shot Size screen for definition, page 20.
Number of Strokes (LRT PD44 Only)
See Shot Size screen for definition, page 20.
Amount per Stroke (LRT PD44 Only)
See Shot Size screen for definition, page 20.
313877E 17
Page 18
HMI Operation
Metering Valve Control Screen
(Motor Driven PD44 only)
NOTE: A “1” indicates that the button is in the “ON” posi-
tion. A “0” indicates that the button is in the “OFF” posi­tion.
NOTE: The Error Code button is shown on every screen on the Motor Driven PD44. See the Main screen for def­inition.
Start button
When the Start button is pressed, the machine starts the cycle for the selected Pump Mode.
Pump Mode
NOTE: The metering rods must be retracted prior to changing any setting under Pump Mode. See Retract Piston, page 13.
Retract Mode
The air cylinder and pumps immediately retract and remain in the retracted position. This is used for mainte­nance purposes only.
Extend Mode
The air cylinder and pumps immediately extend and remain in the extended position. This position must be selected when the pump is idle for a long period of time.
Shot Mode
The machine cycles the number of times displayed in the Cycle Counter field when the start device is pressed and released. The machine cycles continuously when the start device is pressed and held.
Continuous (Operator Control) Mode
In this mode, the machine to dispense while the start device is pressed. When the start device is released the metering rods retract to the home position.
18 313877E
Page 19
DV Valve Mode
This mode actuates an optional dispense valve.
OPEN
In this mode, the dispense valve is held in the open posi­tion, allowing material to pass through.
AUTO
In this mode, the dispsense valve opens automatically whenever the pump is cycled.
CLOSE
In this mode, the dispense valve is held closed.
HMI Operation
313877E 19
Page 20
HMI Operation
Shot Size Screen
(LRT PD44 only)
NOTE: This section describes the Shot Size screen for
the LRT PD44 only. See page 21 for the Motor Driven PD44 Shot Size screen.
NOTICE
Erratic operation results if the shot size value entered is not greater than the absolute value of the Shot Size Off­set setting. For example, if the Shot Size Offset setting is -1%, a shot size greater than 1% must be entered. See Supervisor screen, page 33.
Shot Size 1 – 10
The Shot Size 1 - 10 buttons allow the operator to pro­gram 10 different shot sizes. Shot size is percent of stroke. Once the shot sizes are programmed the shot number can be selected using the Select Shot Size but­ton.
To change the Shot Size 1-10 setting, perform the fol­lowing steps.
1. Select one of the Shot Size 1-10 buttons. A numeric keypad appears.
2. Enter the desired material shot size volume in per­cent of stroke. For example, enter “150” to dispense material volume equivalent to 1.5 strokes.
Select Shot Size button
The Select Shot Size button allows the operator to choose one of the ten preset shot sizes seen in the Shot Size 1 - 10 section.
Number of Strokes
This displays the number of strokes needed to perform the selected shot. If the Shot Size selected is 150% then Number of Strokes displays a “2” because the machine performs two strokes at 75% of the full stroke.
Amount per Stroke in %
This displays the percent of stroke used to perform the selected shot. If the Shot Size selected is 150% then the Amount per Stroke in % displays “75” because the machine performs 2 strokes using 75% of the full stroke length.
3. Press the button. The keypad disappears. The new shot size percentage appears in the Shot Size field.
20 313877E
Page 21
Shot Size Screen
(Motor Driven PD44 Only)
NOTE: This section describes the Shot Size screen for
the Motor Driven PD44 only. See page 20 for the LRT PD44 Shot Size screen.
HMI Operation
NOTICE
Erratic operation results if the shot size value entered is not greater than the absolute value of the Shot Size Off­set setting. For example, if the Shot Size Offset setting is -1%, a shot size greater than 1% must be entered. See Supervisor screen, page 34.
Select Shot Size/Flow Rate Combination
Use this to change the selected shot by entering a num­ber between 1 and 7. The selected shot size and flow rate is shown in the Shot Size (percent) section and Flow Rate (mm/sec) section.
Number of Strokes
This displays the number of shots of material when the machine is dispensing.
For example, if the purge shot size is set at 150%, Num­ber of Strokes displays a “2”, and the Amount Per Stroke % displays “75.00”.
Amount Per Stroke %
Shot Size (percent), Flow Rate (mm/sec)
These are the 7 preset Shot Size (percent) and Flow Rate (mm/sec) values. Shot size is in percent of stroke. The preset values can be selected using Select Shot Size/Flow Rate Combination.
To edit the preset Shot Size or Flow Rate values, log-in as the supervisor. See Main Screen, page 16.
Below is the minimum and maximum field allowance for this design.
Shot Size:
Minimum = 2.5% Maximum = 500.0%
Flow Rate:
Minimum = 0.50 mm/second Maximum = 25.00 mm/second
This displays the stroke per shot in percent of stroke.
For example, if the purge shot size is set at 340%, Amount Per Stroke % displays “85.00” and Number of Strokes During Purge displays a “4”.
313877E 21
Page 22
HMI Operation

Level 1 Control Screen

NOTE: The Error Code button is shown on every screen
on the Motor Driven PD44. See the Main screen for def­inition, page 16.
NOTE: If ‘A Tank Status’ and ‘B Tank Status’ both dis­play 'Levels Not Active' then the level control feature is not installed on this machine.
Micrometer PD44 and LRT PD44 Level 2 Control screen shown
A Tank Status, B Tank Status
This displays information about each component tank filling process. The following are the possible messages.
Message Description
Material High
Material Low
Filling The tank is currently refilling in the tank refilling
Material Present
Level Sen­sor Fault
Levels Not Active
Fill Fault The tank began refilling and the fluid level did not
The tank level is at or above the high level sen­sor.
The tank level is below the low level sensor.
process.
The tank level is between the high and the low level sensors.
The machine senses material at the high level sensor but not at the low level sensor.
Level sensors are not installed for the tank.
reach the high level sensor within the preset time entered into the Fill Timer button seen in the Level2 Control screen. Tank has stopped refilling.
Start Fill A, Start Fill B button
When this button is pressed the transfer pump fills the tank until the material level reaches the high level sen­sor on that tank.
NOTE: The Start Fill A, Start Fill B and the Stop Fill but­tons are inoperable if the high level automatic tank refill­ing feature was not purchased with this machine.
Stop Fill button
This button stops the automatic tank refilling process for both the A and B component material tanks.
Silence Alarm button
This button silences the audible alarm when pressed.
22 313877E
Page 23

Level 2 Control Screen

NOTE: A “1” indicates that the button is in the “ON” posi-
tion. A “0” indicates that the button is in the “OFF” posi­tion.
NOTE: The Error Code button is shown on every screen on the Motor Driven PD44. See the Main screen for def­inition, page 16.
NOTE: In the Level 1 Control Screen, if ‘A Tank Status’ and ‘B Tank Status’ both display 'Levels Not Active' then the level control feature is not installed on this machine. Press the Main button to exit from this screen.
HMI Operation
Micrometer PD44 and LRT PD44 Level 1 Control screen shown
Low Level Shutdown button
When this button displays ‘1’ and the material level of either the ‘A’ component tank or the ‘B’ component tank goes below the low level sensor, the machine shuts down. To recover, refill the component tank with material to above the low level sensor. When ‘0’ is displayed, the low level shutdown feature is disabled.
Alarm Engage button
When this button displays ‘1’ and the material level of either the ‘A’ component tank or the ‘B’ component tank goes below the low level sensor the audible alarm is activated.
Auto Fill Engage button
When this button displays ‘1’ the automatic filling func­tion is activated.
Clear Fill Fault button
This button clears the Fill Timer Fault message dis­played in the corresponding ‘A Tank Status’ or ‘B Tank Status’ field in the Level 1 Control screen.
Silence Alarm button
Press this button to silence the low fluid level audible alarm. The audible alarm will be activated again when the low level condition reoccurs.
313877E 23
Page 24
HMI Operation
Shutdown Timer button/indicator
NOTE: If the level control option has not been pur-
chased the Shutdown Timer button is disabled.
This changes the delay before the Fill Timer Fault mes­sage is displayed in the corresponding ‘A Tank Status’ or ‘B Tank Status’ field on the Level 1 Control screen. If the material level is below the low level sensor for more than the duration of the Shutdown Timer setting, the machine shuts down.
To change the Shutdown Timer setting, perform the fol­lowing steps.
1. Select the Shutdown Timer button (shown as “=00000”). A numeric keypad appears.
2. Enter the desired Shutdown Timer setting in tenths of a second.
NOTE: For example, if 15 is entered, the shutdown time is 1.5 seconds.
3. Press the button. The new Shutdown Timer set­ting is shown.
NOTE: For example, if 15 is entered, the Fill Timer set­ting is 1.5 seconds.
3. Press the button. The new Fill Timer setting appears in the Fill Timer field.
NOTE: The current Fill Timer time is shown by “<00000”. This counts up to the preset time.
NOTE: The current time of the Shutdown Timer is shown by “<00000”. This counts up to the preset time.
Fill Timer
NOTE: If the automatic refilling option has not been pur-
chased the Fill Timer function is disabled.
This changes the delay before the Fill Timer Fault mes­sage is displayed to the corresponding ‘A Tank Status’ or ‘B Tank Status’ field in the Level 1 Control screen. If the material level reaches the tank high level sensor before the preset fill time elapses, the ‘Tank High Level’ message is displayed in the Tank Status field and the Fill Timer is reset. If the preset fill time expires before mate­rial reaches the high level sensor, “Fill Timer Fault” appears in the Level1 Control Screen.
To change the Fill Timer setting, perform the following steps.
1. Select the Fill Timer button (shown as “=00000”). A numeric keypad appears.
2. Enter in the Fill Timer time in tenths of a second.
24 313877E
Page 25

Purge Timer Screen

NOTE: The Error Code button is shown on every screen
on the Motor Driven PD44. See the Main screen for def­inition, page 16.
NOTE: On the Micrometer PD44, the “Purge Timer screen” is named the “Timer/Counter Screen.”
HMI Operation
Motor Driven PD44 Purge Timer Screen Shown
Cycle Counter On/Off button (Micrometer PD44 Only, Not Shown)
The Cycle Counter switch is used to enable/disable the cycle counter.
OFF: The Cycle Counter is disabled.
ON: If Shot Mode is selected, when the Cycle Counter is
enabled the number of cycles entered are dispensed.
To change the Cycle Counter value, perform the follow­ing steps.
1. Select the Cycle Counter button. A numeric keypad appears.
2. Enter in the desired number of counts for the Cycle Counter.
3. Press the Enter button. The current number of cycles appears in the Cycle Counter field.
Purge Timer On /Off
Always set the dwell/alarm timer to a value that will give the user adequate warning that the machine is about to dispense a purge shot.See Dwell / Alarm Timer section on page 26.
The Purge Timer On/Off switch is used to enable/dis­able the Purge Timer.
OFF: The Purge Timer is disabled.
ON: The Purge Timer is enabled. The machine initiates
a purge shot when the purge timer expires provided the fluid ball valves are open, Shot Mode is selected, and no errors exist.
313877E 25
Page 26
HMI Operation
Enter Purge Time Button
The Enter Purge Time button is shown as “=000.0” below the Purge Timer On /Off button. The Enter Purge Time button allows the operator to set the required time between cycles. When the Purge Timer switch is in the ON position and the Pump Mode switch is in the Shot or Operator Control position, the purge timer unit counts up to the preset time. When it reaches the preset time, a purge shot is initiated.
The timer then automatically resets and continues with the sequence of cycling and resetting. It continues until the Purge Timer is turned to the OFF position.
To change the Purge Timer setting, perform the follow­ing steps.
1. Select Purge Timer button. A numeric keypad appears.
2. Enter the desired purge time in seconds. Use the “.” button to enter tenths of a second.
3. Press the button. The Purge Timer screen appears. The new purge time appears in the Purge Timer button.
NOTE: The current Purge Timer time is shown in the bottom text box below the Purge Timer button.
Calculating the Purge Timer Setting
If the shot size is larger than the mixer volume, set the timer for one-half the gel time of the material. If the shot size is smaller, use the following formula to determine the Purge Timer setting.
Gel Time X Shot Size
= Timer Setting
2 X Mixer Volume
Dwell / Alarm Timer
Always set the dwell/alarm timer to a value that will give the user adequate warning that the machine is about to dispense a purge shot.
This changes the duration that the audible alarm is active prior to the purge shot being initiated.
To change the Dwell Timer, perform the following steps.
1. Select the Dwell Timer button. A numeric keypad appears.
2. Enter the desired Dwell Timer time in seconds. Use the “.” button to enter tenths of seconds.
3. Press the button. The new Dwell Timer time appears in the Dwell Timer field.
NOTE: The current Dwell Timer time is shown by <000.0.
Purge Shot Size % button (LRT and Motor Driven PD44 only)
This button shows the Shot Size volume in percent of stroke. This volume is dispensed during the ratio check.
To change the Purge Shot Size % volume, perform the following steps.
1. Select Purge Shot Size % button. A numeric keypad appears.
2. Enter the desired material shot size volume.
For example, with mixer volume = 13.3cc, shot size = 10cc, gel time = 10 minutes, use the following equation.
3. Press the button. The Purge Timer screen appears. The new shot size percentage appears in the Purge Shot Size % field.
10 min X 10 cc
2 X 13.3 cc
100 cc*min
26.6 cc
= 3.76 min=
Number of Strokes During Purge button/indicator (LRT and Motor Driven PD44 only)
This displays the number of strokes used during the purge shot.
For example, if the purge shot size is set at 150%, Num­ber of Strokes During Purge displays “2” and Amount Per Stroke % displays “75”.
26 313877E
Page 27
Amount Per Stroke % (LRT and Motor Driven PD44 only)
This displays the percent of the stroke used during a shot.
For example, if the shot size is set at 150%, Number of Strokes During Purge displays “2” and Amount Per Stroke % displays “75”.
HMI Operation
313877E 27
Page 28
HMI Operation

Status Screen

NOTE: A “1” indicates that the button is in the “ON” posi-
tion. A “0” indicates that the button is in the “OFF” posi­tion.
NOTE: The Error Code button is shown on every screen on the Motor Driven PD44. See the Main screen for def­inition, page 16.
Micrometer PD44 and LRT PD44 Status Screen Shown
Maintenance Totalizer
This counter increments each time the machine cycles. Press the Reset Maintenance Totalizer button to reset. This counter is used for maintenance purposes.
# Of Times Maintenance Totalizer has been Reset
This counter increments each time the Reset Mainte­nance Totalizer button is pressed.
Reset Maintenance Totalizer button
This button resets the Maintenance Totalizer.
Cycle Totalizer
This counter increments each time the machine cycles.
Number of Strokes (Motor Driven PD44 Only, not shown)
This displays the number of strokes needed to perform the currently selected shot size. If the selected shot size is 150%, Number of Strokes displays a “2”.
Amount per Stroke in % (Motor Driven PD44 Only, not shown)
This displays the amount of stroke used to perform the currently selected shot. If the shot size is 150%, Amount per Stroke in % displays “75%”.
Dispense Ready
This displays “1” if the metering rods are loaded with material and ready to dispense. It displays a “0” if the metering tube is reloading or at the end of the dispense cycle. Customer Signal Integration Kit 80/2450/CS/50, which uses this output, can be ordered separately. The Customer Signal Integration Kit is standard on Motor Driven PD44s.
28 313877E
Page 29
Dispense Complete
This displays “1” if the metering rods are reloaded with material or at the end of the dispense cycle, and dis­plays a “0” if the metering tube is loaded with material and ready to dispense. Customer Signal Integration Kit 80/2450/CS/50, which uses this output, can be ordered separately. The Customer Signal Integration Kit is stan­dard on Motor Driven PD44s.
Contrast + button
This button increases the contrast of the screen.
Contrast - button
This button decreases the contrast of the screen.
PX-CSV Reload
This displays the status of the reload spool proximity switch. If this displays a “1” the switch is activated and if this displays a “0” the switch is deactivated. See Compo­nent Identification section in dispense valve manual. See Related Manuals on page 3.
HMI Operation
PX-OSV Dispense
This displays the status of the dispense spool proximity switch. If this displays a “1” the switch is activated. If this displays a “0” the switch is deactivated. See component identification section in dispense valve manual. See
Related Manuals on page 3.
PLC Program (Micrometer and LRT PD44 only)
This gives the currently installed PLC program version and revision level.
HMI Program (Micrometer and LRT PD44 only)
This gives the currently installed HMI program version and revision level.
313877E 29
Page 30
HMI Operation
Motor Status Screen
(Motor Driven PD44 only)
NOTE: A “1” indicates that the button is in the “ON” posi-
tion. A “0” indicates that the button is in the “OFF” posi­tion.
NOTE: The Error Code button is shown on every screen on the Motor Driven PD44. See the Main screen for def­inition, page 16.
To navigate to the Motor Status screen, press the “Motor Status” button on the Status screen.
CSV Switch (Closed Spool Valve Switch)
This displays “1” when the spool valve is in the closed or reload position.
OSV Switch (Open Spool Valve Switch)
This displays “1” when the spool valve is in the open or dispense position.
Home Switch (Home Limit Switch)
This displays “1” when the metering valve rod home switch is activated.
Upper Switch (Upper Over Limit Switch, Extend)
This displays “1” when the metering valve rod upper over-travel limit switch is activated. The dispense valve is in the most-retracted position.
Lower Switch (Lower Over Limit Switch, Retract)
This displays “1” when the metering valve rod lower over-travel limit switch is activated. The dispense valve is in the most-extended position. Put the dispense valve in this position when it is idle for a long period of time.
Motor Position (Steps)
This gives the motor step position in terms of transducer steps.
Shot Size %
This shows the Shot Size volume in percent of stroke.
Flow Rate (mm/sec)
This allows the operator to view the current flow rate in millimeters per second.
30 313877E
Page 31
Shot Mode Step #
This gives the current step in the shot mode program. This is used for troubleshooting.
Reload Mode Step #
This gives the current step in the reload mode program. This is used for troubleshooting.
Oper. Mode Step #
This gives the current step in the operator mode pro­gram. This is used for troubleshooting.
HMI Operation
313877E 31
Page 32
HMI Operation
Motor Error Codes Screen
(Motor Driven PD44 Only)
These screens give descriptions of the motor error codes.
32 313877E
Page 33
Supervisor Screen
(LRT PD44 Only)
NOTE: This section describes the Supervisor screen for
the LRT PD44 only. See page 34 for the Motor Driven PD44 Supervisor screen.
HMI Operation
Pump Reload
Pump Reload sets a transducer point where the machine will reload. The point is relative to the rod stroke mechanical limits.
Reload 3% Shot Size Offset -1%
Most
Retracted
Position
To change the Pump Reload setting, perform the follow­ing steps.
1. Press Enter Password button.
2. Enter password.
3. Press the Enter button.
4. Press the Pump Reload Position button.
5. Enter the desired reload position.
Most
Extended
Position
Shot Size Offset Button
The Shot Size Offset button sets the transducer point where the metering rods will retract. The factory setting is -1.
To change the Shot Size Offset setting, perform the fol­lowing steps.
1. Press Enter Password button.
2. Enter password.
3. Press the Enter button.
4. Press the Shot Size Offset button.
5. Enter the desired Shot Size Offset.
6. Press the Enter button.
7. Press the Enter Data button.
6. Press the Enter button.
7. Press the Enter Data button.
313877E 33
Page 34
HMI Operation
Supervisor Screen
(Motor Driven PD44 Only)
NOTE: This section describes the Supervisor screen for the Motor Driven PD44 only. See page 34 for the LRT PD44
Shot Size screen.
NOTE: A “1” indicates that the button is in the “ON” position. A “0” indicates that the button is in the “OFF” position.
NOTE: To change the values on this screen, log-in as
the supervisor. See Main Screen, page 16.
Error Code button
This button resets the error in the error string (shown as “<0000000000”) and the error code number (shown as “<000”). See the Motor Error Code screen for more information, page 32.
Reload Setup
Only one of the three Reload Setup Options can be enabled at any given time.
Reload After Each Shot button
In this mode, the metering rods retract after every shot. This is the default system setup.
Reload After Multiple Shots button
In this mode, the metering rods retract only when the metering rods are about to reach the end of the stroke. This feature is only available when in Operator Control mode.
For example, if the selected shot size is 30% of the metering rods stroke, three shots will be taken (90% of the stroke) then the metering rods will retract. The rods retract after three shots because it cannot do another shot without going over 100% stroke. If the selected shot size is greater than 50% of the metering rods stroke, the metering rods will retract after every shot.
Manual Reload W/ Customer Signal button
In this mode, the customer must send a signal to reload the valve before the lower switch is activated. Otherwise, the dispense valve will initiate a shot using the selected shot size and flow rate combination.
NOTE: This can be linked with a PLC input for system integration. See the logic drawings for more information.
Reload Speed (mm/sec) button
This allows the operator to change the retract or reload speed in millimeters per second.
Feed Setup
This allows the operator to choose the low level setting for the feed system with tanks or a feed system with car­tridge or syringes. This inverts the switch function in the PLC logic.
34 313877E
Page 35
Supervisor Help Screen
(Motor Driven PD44 Only)
This screen describes the various reload and shot options in the Supervisor screen.
To get to the Setup Help screen, press the “Help” button on the Supervisor screen.
HMI Operation
313877E 35
Page 36
HMI Operation
Calibration Screen
(LRT PD44 Only)
Calibrate Mode button
When this button is selected machine calibration starts.
Extend Pumps button
This extends the air cylinder for the calibration sequence. The most-extended position is recorded when the Teach button is then pressed.
Retract Pumps button
This retracts the air cylinder for the calibration sequence. The most-retracted position is recorded when the Teach button is then pressed.
Teach button
This “teaches” or stores various data collected during calibration mode.
Done button
This button exits Calibration mode.
Transducer Position in %
This shows the transducer position in percent of stroke.
To calibrate the pumps, perform the following steps.
1. From the Calibration screen, select Calibration Mode.
2. Press the Extend Pumps button. Pumps extend.
3. Press the Teach button.
4. Press the Retract Pumps button. Pumps retract.
5. Press the Teach button.
6. Press the Done button.
Shot Size Offset
The Shot Size Offset allows the operator to view the shot size offset percentage. The factory default is -1%. See the Supervisor screen, page 33.
Reload Position
Reload Position allows the operator to view the reload position. The factory setting is 3%.
Transducer Position
This shows the transducer position in transducer units.
36 313877E
Page 37
Calibration Screen Help
This screen describes the calibration procedure.
HMI Operation
313877E 37
Page 38

Pressure Relief Procedure

Pressure Relief Procedure
1. Turn main air supply shut-off/bleed valve to the off position. This will bleed air from the system.
2. Perform feed system pressure relief procedure. See Related Manuals on page 3.
3. Perform dispense valve pressure relief procedure. See Related Manuals on page 3.

Shutdown

1. On Micrometer and LRT PD44s, go to the Posidot Control screen. On Motor Driven PD44s, go to the Metering Valve Control screen.
2. Press the Retract button.
3. Press the Extend button.
4. Press the Emergency Stop button. Ensure every­thing is off.
5. Twist Emergency Stop to reset.
6. Perform Pressure Relief Procedure.
7. Perform feed system shutdown procedure. See Related Manuals on page 3.
8. Perform dispense valve shutdown procedure. See Related Manuals on page 3.
38 313877E
Page 39

Optional Customer Inputs

Optional Customer Inputs
Micrometer PD44 and LRT PD44
Name Description
Ready to Dispense Signal (Output)
Cycle-Complete (Output) In Shot Mode, changes state for one second after the retract switch is tripped. Customer Start (Input) In any mode, operates in parallel to the footswitch. Provide a dry contact clo-
Motor Driven PD44
Name Description
Customer Start (Input) When a momentary contact closure is applied to this input, the start device is
Customer Purge Start (Input)
Customer SS/FR Bit 1,2,3 (Input)
Customer Signal Done (Output)
Customer Signal Dis­pense Ready (Output)
Customer Signal Time to Purge (Output)
Customer Signal Open Auxiliary Dispense Valve (Output)
Customer Signal Reload (Input)
In Shot Mode, changes state when pump is retracted and LS-EXT is tripped.
sure between black and white wires on the customer signal cable to actuate machine.
activated. When a momentary contact closure is applied to this input, the purge shot is
activated. When these inputs are activated in the proper sequence, the machine acti-
vates the Shot Size and Flow Rate Combination seen on the Shot Sizes screen. See the machine logic drawings for more information.
This output activates for 2 seconds after the dispense cycle is complete.
This output is active when the machine is in the Shot Mode and the dispense valve is retracted and loaded with material. This output deactivates when the dispense valve is dispensing or if the machine is not in the shot mode.
If the Manual Reload W/ Customer Signal button under the Supervisor screen is selected, this output is active when it is time for the machine to take a purge shot. NOTE: The dispense valve will not perform a purge shot until the start device is activated.
This is to be used only when there is a metering valve feeding an on/off type dispense valve. This signal is used to open and close the dispense valve.
When in customer reload mode, after each shot the dispense “Done” signal is turned on for 2 seconds. During this time the customer can toggle the cus­tomer reload signal to reload the system. If the timer expires, the machines assumes the customer does not want to reload and finishes the sequence then turns on the ready signal and does not allow another reload until after the next shot.
313877E 39
Page 40

Maintenance

Maintenance
NOTE: If material is leaking, see Troubleshooting on
page 40.
See Related Manuals on page 3 for dispense valve and feed system maintenance schedule and procedures.
Air-Water Separator/Filter
Drain water once a shift or as necessary.

Troubleshooting

Perform Pressure Relief Procedure before perform­ing any troubleshooting procedure.
All Machines
Problem Cause Solution
Dispense valve stalling and no mate­rial being dispensed despite ade­quate input pressure
Dispense valve not discharging nor­mal or full volume
Material leaks past spool valves Spool valve worn or damaged Replace the spool valve and sleeve
Improper material mixing Mixer not clean or free Remove and replace the mixer
Material leaks around mixer while dispensing
Motor Driven PD44 Only
Problem Cause Solution
The horn beeps after each shot Dispense is longer than the dispense
The horn beeps continuously If the low level sensors are on, the
Blocked mixer Check mixer for cured material,
replace mixer as required
Flow control valve closed Open
Low material level in reservoirs Fill material reservoirs and prime the
machine
Air in material tanks Fill reservoirs and prime machine
Cured material in mixer Check mixer for cured material,
replace mixer
Check mixer for cured material
limit timer
Check level screen for low level con-
system may be low on material
dition, if low level condition is present, fill tank with material
40 313877E
Page 41

Technical Data

Maximum Ambient Temperature. . . . . . . . . . . . . . . . . . . . 110°F (43°C)
Maximum Operating Temp . . . . . . . . . . . . . . . . . . . . . . . . 150°F (65°C)
Maximum Air Working Pressure . . . . . . . . . . . . . . . . . . . . 100 psi (0.7 MPa, 7 bar)
Supplied Air Requirements. . . . . . . . . . . . . . . . . . . . . . . . 1 to 3 cfm at 80 psi to 100 psi
Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 120/240V, 50/60 Hz
Fuses Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Micrometer and LRT PD44 Control Box:
5 x 20 mm, 2A, time delay (Graco part 81/1053-2/11, Qty = 1)
Motor Driven PD44 Control Box:
5 x 20 mm, 10A, fast, type F, 250 VAC (Graco part V-21610P, Qty = 2)
Maximum Amperage . . . . . . . . . . . . . . . . . . . . . . . . . . . . Micrometer and LRT PD44 Control Box:
2 amps
Motor Driven PD44 Control Box:
10 amps
Dimensions (H x L x W) . . . . . . . . . . . . . . . . . . . . . . . . . . Micrometer and LRT PD44 Control Box:
13 in. x 12 in. x 15 in. (330 mm x 305 mm x 381 mm)
Motor Driven PD44 Control Box:
20 in. x 8 in. x 20 in. (508 mm x 203 mm x 508 mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Micrometer and LRT PD44 Control Box:
30 lb (13.6 kg)
Motor Driven PD44 Control Box:
60 lb (27.2 kg)
Technical Data
313877E 41
Page 42

Graco Standard Warranty

Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to
the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés, à la suite de ou en rapport, directement ou indirectement, avec les procédures concernées.

Graco Information

For the latest information about Graco products, visit www.graco.com.
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor. Toll Free: 1-800-746-1334 or Fax: 330-966-3006
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2009, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco reserves the right to make changes at any time without notice.
For patent information, see www.graco.com/patents
Original instructions. This manual contains English. MM 313877
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
www.graco.com
Revised July 2013
Loading...