Graco 313296J User Manual

Page 1
Instructions - Parts
Warm Melt Supply
313296J
Systems
For use with heated bulk supply of medium to high viscosity sealant and adhesive materials. Not for use in hazardous locations. Intended for indoor use only.
D60 3 inch dual post
60 liter (16 gallon), 30 liter (8 gallon), and 20 liter (5 gallon) sizes
D200 3 inch dual post
200 liter (55 gallon)
EN
D200S 6.5 inch dual post
200 liter (55 gallon)
125 psi (0.9 MPa, 9 bar) Maximum Air Inlet Pressure
Important Safety Instructions
Read all warnings and instructions in this manual. Save these instructions.
See page 4 for model information.
The Graco Control Architecture Electric Components are listed in Intertek’s Directory of Listed Products.
D200s (WM2179) Shown
Page 2
Contents
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Heat Control Zone Selection . . . . . . . . . . . . . . . . . . . . . 7
Component Identification . . . . . . . . . . . . . . . . . . . . . . . . . 8
Single Supply Systems . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tandem Supply Systems . . . . . . . . . . . . . . . . . . . . . . .9
Integrated Air Controls . . . . . . . . . . . . . . . . . . . . . . . . 10
Air Line Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2-Button Interlock Air Controls . . . . . . . . . . . . . . . . . . 11
Communications Gateway Module . . . . . . . . . . . . . . . 11
Fluid Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . 12
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Location Requirements . . . . . . . . . . . . . . . . . . . . . . . . 17
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connect Power Source . . . . . . . . . . . . . . . . . . . . . . . . 18
Install/Adjust Drum Low or Empty Sensor . . . . . . . . . 19
Light Tower Accessory . . . . . . . . . . . . . . . . . . . . . . . . 19
Attach Drum Stops . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Check Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Hose Installation and Care . . . . . . . . . . . . . . . . . . . . . 23
Overview of Temperature Control Settings . . . . . . . . . 23
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Purge System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Set Values on Display Module . . . . . . . . . . . . . . . . . . 24
Load Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
System Heat Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Prime . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Pressure Relief Procedure . . . . . . . . . . . . . . . . . . . . . 28
Trigger Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Start and Adjust Ram . . . . . . . . . . . . . . . . . . . . . . . . . 28
Start and Adjust Pump . . . . . . . . . . . . . . . . . . . . . . . . 28
Automatic Crossover . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Manual Crossover . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Recirculate Function . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Depressurize Function . . . . . . . . . . . . . . . . . . . . . . . . 30
Change Drums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Replace Throat Seals . . . . . . . . . . . . . . . . . . . . . . . . . 32
Platen Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Electrical Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Pump Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Diagnose Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Clear Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Alarm Codes and Troubleshooting . . . . . . . . . . . . . . . 36
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Air Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Displacement Pump . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Disconnect Pump from Platen . . . . . . . . . . . . . . . . . . 50
Connect Pump to Platen . . . . . . . . . . . . . . . . . . . . . . . 51
Replace Pump Heaters . . . . . . . . . . . . . . . . . . . . . . . 51
Replace Platen Heaters and Sensor . . . . . . . . . . . . . 52
Replace Platen Wipers . . . . . . . . . . . . . . . . . . . . . . . . 54
Replace Ram Piston Rod Seals . . . . . . . . . . . . . . . . . 54
Electrical Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Display/User Interface . . . . . . . . . . . . . . . . . . . . . . . . 58
Replace Fluid Control Module . . . . . . . . . . . . . . . . . . 59
Replace Cable Track . . . . . . . . . . . . . . . . . . . . . . . . . 60
Electrical Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Ram A Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
D200 Single Ram Schematic . . . . . . . . . . . . . . . . . . . 61
D200 Ram A Schematic . . . . . . . . . . . . . . . . . . . . . . . 62
D200 Ram B Schematic . . . . . . . . . . . . . . . . . . . . . . . 63
D200 Displacement Pump and Platen Schematics . . 64
D200 Junction Box Schematic . . . . . . . . . . . . . . . . . . 65
D200 Cable Track Schematic . . . . . . . . . . . . . . . . . . . 66
D60 Single Ram Schematic . . . . . . . . . . . . . . . . . . . . 67
D60 Ram A Schematic . . . . . . . . . . . . . . . . . . . . . . . . 68
D60 Ram B Schematic . . . . . . . . . . . . . . . . . . . . . . . . 69
D60 Pump and Platen Schematic . . . . . . . . . . . . . . . . 70
D60 Junction Box Schematic . . . . . . . . . . . . . . . . . . . 71
D60 Cable Harness Schematic . . . . . . . . . . . . . . . . . 72
Electrical Enclosure Schematic . . . . . . . . . . . . . . . . . 73
Electrical Enclosure Schematic . . . . . . . . . . . . . . . . . 74
Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Warm Melt Kits for D200 Systems . . . . . . . . . . . . . . . 78
Warm Melt Kits for D60 Systems . . . . . . . . . . . . . . . . 83
Electrical Enclosure Parts . . . . . . . . . . . . . . . . . . . . . . 90
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Appendix A - User Interface Display . . . . . . . . . . . . . . . 93
Display Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Display Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Setup Mode Screens . . . . . . . . . . . . . . . . . . . . . . . . . 95
Run Mode Screens . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
D200 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
D60 Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . . . . . 108
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
2 313296J
Page 3

Related Manuals

Manuals are available at www.graco.com.
Component Manuals in U.S. English:
Manual Description
313528 Tandem Supply Systems Operation 313529 Tandem Supply Systems Repair-Parts 313526 Supply Systems Operation 313527 Supply Systems Repair-Parts
Check-Mate
312375
Instructions-Parts
Check-Mate
312376
312468
311238 NXT
Instruction-Parts 200 cc Check-Mate Displacement Pump
Repair Parts
312374 Air Controls Instructions-Parts
3A0099
3A0100
Two-Zone Enclosure Expansion Kit Instructions-Parts
Two-Zone and Four-Zone Enclosure Accessory Kits Instructions-Parts
3A0135 Bracket Mounting Kits Parts
®
Displacement Pumps
®
Pump Packages
Air Motor Instructions-Parts
Related Manuals
312491 Pump Fluid Purge Kit Instructions
312492 Drum Roller Kit Instructions
312493 Light Tower Kit Instructions
309160 Heated Hose Instructions-Parts
312396
Hotmelt/Warm Melt Heated Fluid Regula­tor Instructions-Parts
307517 Mastic Fluid Regulator Instructions-Parts
309133
309181
311209
310538
309376
312864
Pressure Compensating Valve Instructions-Parts
Heated Header and Manifold Instructions-Parts
Hot Melt Dispense Guns Instructions-Parts
Therm-O-Flow
®
Automatic Dispense
Valves Instructions-Parts
EnDure
Automatic Dispense Valves
Instructions-Parts Communications Gateway Module
Instructions-Parts Supply System Communications Gate-
313138
way Module Installation Kit Instruc­tions-Parts
406681 Platen Cover Kit Instructions
313296J 3
Page 4

Models

Models
Check the identification plate (ID) for the 6-digit part number of your warm melt supply system. Use the following matrix to define the construction of your system, based on the six digits. For example, Part No. WM2979 represents a Warm Melt
supply system (WM), a carbon steel Check-Mate 200 Severe Duty pump with an NXT 3400 air motor (pump code 29), a 6.5 in. dual post ram with integrated air controls (7) and a 55-gallon, uncoated platen with an EPDM seal (9).
NOTE: Some configurations in the following matrix cannot be built. See the Product Selection guide for available systems.
®
displacement
ID
To order replacement parts, see Parts section in this manual and in manual
313527. The digits in the matrix do not correspond to the Ref. Nos. in the Parts drawings and lists.
WM 29 7
First and
Second Digit
WM
(Warm Melt
Single Supply
System)
TW
(Warm Melt
Tandem
Supply
System)
Third and
Fourth Digit Fifth Digit
Ram Options
DataTra
Pump Code
Size Style
k
Voltage Air Controls
4 3 in. D60 no volt INT
5 3 in. D200 no volt INT
6 3 in D200i no volt
(See Table 1
for 2-digit
Pump Code)
7 6.5 in. D200s no volt INT
8 6.5 in. D200si no volt
Y 3 in. D60i no volt
2-Button Interlock
2-Button Interlock
2-Button Interlock
F
H
L
R
U
Y
8
9
TI11157A
9
Sixth Digit
Platen and Seal Options
Platen
Size
20 L
(5 Gal) F, SW SST
20 L
(5 Gal) F, DW CS
30 L
(8 Gal) F, SW SST
30 L
(8 Gal) F, DW CS
60 L
(16 Gal) F, SW SST
60 L
(16 Gal) F, DW CS
200 L
(55 Gal) DR
200 L
(55 Gal) DR AL EPDM
Platen
Style
Platen
Material
PTFE
coated
AL EPDM
Seal
Material
PTFE
coated
Polyure-
thane PTFE
coated
Polyure-
thane PTFE
coated
Polyure-
thane
Key:
D = Dual post ram i = 2-Button interlock s = 6.5 in. ram INT = Integrated air controls F = Flat SW = Single wiper DW = Dual wiper DR = Dual o-ring
4 313296J
Table 1: Check-Mate Pump Identification Code/Part
Pump
Code
NXT 2200/CM 200 NXT 6500/CM 200
NXT 3400/CM 200
Pump Part No. (see
manual 312376)
21 P23LCS 2L P68LCS 22 P23LCM 2M P68LCM 26 P23LSM 2U P68LSM
29 P36LCS 2A P36LCM 2G P36LSM
Pump
Code
Pump Part No. (see
manual 312376)
Page 5

Warnings

Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. Refer back to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where applicable.
WARNING
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before disconnecting any cables and before servicing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help prevent fire and explosion:
Use equipment only in well ventilated area.
Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop cloths (potential static arc).
Keep work area free of debris, including solvent, rags and gasoline.
Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes are present.
Ground all equipment in the work area.
Use only grounded hoses.
Hold gun firmly to side of grounded pail when triggering into pail.
If there is static sparking or you feel a shock, stop operation immediately. Do not use equipment until you identify and correct the problem.
Keep a working fire extinguisher in the work area.
BURN HAZARD
Equipment surfaces and fluid that’s heated can become very hot during operation. To avoid severe burns:
Do not touch hot fluid or equipment.
Wait until equipment/fluid has cooled completely.
SKIN INJECTION HAZARD
High-pressure fluid from gun, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment.
Do not point gun at anyone or at any part of the body.
Do not put your hand over the dispense outlet.
Do not stop or deflect leaks with your hand, body, glove, or rag.
•Follow Pressure Relief Procedure in this manual, when you stop dispensing and before cleaning, checking, or servicing equipment.
313296J 5
Page 6
Warnings
WARNING
MOVING PARTS HAZARD
Moving parts can pinch or amputate fingers and other body parts.
Keep clear of moving parts.
Do not operate equipment with protective guards or covers removed.
Pressurized equipment can start without warning. Before checking, moving, or servicing equipment, follow the Pressure Relief Procedure in this manual. Disconnect power or air supply.
SPLATTER HAZARD
Hot or toxic fluid can cause serious injury if splashed in the eyes or on skin. During blow off of platen, splatter may occur.
Use minimum air pressure when removing platen from drum.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed.
Read MSDS’s to know the specific hazards of the fluids you are using.
Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
Always wear impervious gloves when spraying or cleaning equipment.
If this equipment is used with isocyanate material, see additional information on isocyanates in Iso­cyanate Conditions Section of this manual.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maximum working pressure or temperature rating of the lowest rated system component. See Technical Data in all equipment manuals.
Do not leave the work area while equipment is energized or under pressure. Turn off all equipment and follow the Pressure Relief Procedure in this manual when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manu­facturer’s replacement parts only.
Do not alter or modify equipment.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
PERSONAL PROTECTIVE EQUIPMENT
You must wear appropriate protective equipment when operating, servicing, or when in the operating area of the equipment to help protect you from serious injury, including eye injury, inhalation of toxic fumes, burns, and hearing loss. This equipment includes but is not limited to:
Protective eyewear
Clothing and respirator as recommended by the fluid and solvent manufacturer
•Gloves
Hearing protection
6 313296J
Page 7

Overview

Overview

System Description

Warm melt supply systems are used for melting and pumping warm melt adhesives and high viscosity seal­ants.
The system consists of an air-powered ram that drives a Check-Mate pump and a heated platen into a drum of material. The heated platen heats the material and the pump removes it from the drum. The material is then pushed through a supply hose to the applicator.
All features of the warm melt supply system are con­trolled by Graco Control Architecture components: Fluid Control Module (FCM), Temperature Control Modules (TCM), and the display module. The FCM controls the motor and pump, and the TCMs control the heaters. The display module provides the user interface for the entire warm melt supply system.

Power Requirements

A 30A (minimum) - 60A (maximum) circuit breaker (not provided) must be installed on the incoming power sup­ply. See Table 1, and Technical Data, page 106, for more information regarding electrical requirements.
Table 1: Electrical Requirements
AC Panel
Voltage HZ Phase
240 50/60 1 57.0
Full Load
Amps

Heat Control Zone Selection

Warm melt supply systems have four heat zones (see F
IG
. 1).
Zones 1 and 2 are always used for the heated platen and the heated pump respectively.
Zones 3 and 4 are used for the heated hose and valve. These zones are rated for 1920 watts at 240 volts.
Heated hoses have a 16-pin connector on the inlet end cable, and an 8-pin connector on the outlet end cable. All heated valves, manifolds, and heaters are equipped with an 8-pin matching connector. Accessory cables are available for other possible combinations.
ZONE 1
Control
Platen
FIG. 1: Heat Control Zone Selection
ZONE 2
Control
Pump
Valve 1
ZONE 3
Control
1920 Watts max
Hose 1
ZONE 4
Control
1920 Watts max
313296J 7
Page 8

Component Identification

Component Identification

Single Supply Systems

D200s Ram Shown
AF
S
Lift Locations
NOTE: Do not use air motor lift ring (S) to lift entire system.
V
AD
C
H
AE
G
J
K
A
U
D
X
Z
E
T
FIG. 2: Single Supply System
Key:
ARam Assembly C Air Motor D Heated Check-Mate Displacement Pump E Heated Platen G Display Module H Electrical Enclosure
IG
J Integrated Air Controls (see F K Fluid Control Module (inside shroud) S Lift Ring (air motor) T Platen Bleed Port U Pump Outlet
8 313296J
. 4)
V Platen Lift Rod XWet Cup Z Main Air Line (not supplied) AD Air Motor Solenoid AE Junction Box AF Cable Track
Page 9

Tandem Supply Systems

D200s Rams Shown
Component Identification
Supply System A
A
H
AF
G
AD
F
Supply System B
B
N
S
V
J
C
K
AE
To heated
X
manifold (243697)
Z
U
D
E
FIG. 3: Tandem Supply System
Key:
ARam A BRam B C Air Motor D Heated Check-Mate Displacement Pump (Ram A and B) E Heated Platen (Ram A and B) F Drum Empty Sensor (partially hidden; Ram A and B) G Display Module (Ram A only) H Electrical Enclosure (Ram A and B) J Integrated Air Controls (Ram A and B); see page 10 K Fluid Control Module (inside shroud, Ram A and B) N CAN Communication Cable S Lift Ring (Air Motor) T Platen Bleed Port U Pump Outlet V Platen Lift Rod
r_wm2179_313269_4a
XWet Cup Z Main Air Line (not supplied) AD Air Motor Solenoid (Ram A and B) AE Junction Box (Ram A and B) AF Cable Track (Ram A and B)
313296J 9
Page 10
Component Identification
NOTE: See F
IG
. 2 and FIG. 3. Before you install the system, you should be familiar with the following compo­nents.
Reference numbers and letters in parentheses in the text refer to the callouts in the figures.
Both rams (A and B) include a Check-Mate Pump (D), platen (E), integrated air controls (J), drum empty sen­sor (F), and fluid control module (K).
Only Ram A includes the display module (G).
Drum empty sensor (F). Signals drum empty condi-
tion. See F
IG
. 11, page 19.
Display module (G). Mounted on Ram A only. Pro-
vides Run Mode status screens, Setup screens, and control keys. See F
Fluid control module (K). See F
Integrated air controls (J). See F
IG
. 8, page 13.
IG
. 7, page 12.
IG
. 4.
Air motor solenoid (AD). Solenoid is on when the
selected ram is on and in Run Mode, Recirculate Mode, or Prime Mode. Solenoid is off when system is shut off or when in Depressurize Mode, or the ram is in an Inactive Ready Mode. The solenoid LED will illuminate when the solenoid is on.
Depressurize/recirculate fluid valve. Depressurizes
system when Depressurize Mode is active. Recircu­lates fluid when Recirculate Mode is active.

Integrated Air Controls

D60, D200, and D200s Models
The integrated air controls include:
Main air slider valve (BA): turns air on and off to the system. When closed, the valve relieves pres­sure downstream.
Ram air regulator (BB): controls ram up and down pressure and blowoff pressure.
Ram director valve (BC): controls ram direction.
Exhaust port with muffler (BD)
Air motor regulator (BE): Controls air pressure to motor.
Air motor slider valve (BF): turns air on and off to the air motor. When closed, the valve relieves air trapped between it and the air motor. Push the valve in to shutoff. The air solenoid (AD), the air motor valve (BF), and the main air slider valve (BA) must be open for air to flow.
Blowoff button (BG): turns air on and off to push the platen out of an empty drum.
BF
BE
To depressurize the system, press the Depressurize
BD
key on the display module and select
when asked if you want to depressurize the system. Follow the Pressure Relief Procedure on page 28.
BG
BC
BB
Shutting off power or removing power from the sys­tem will not depressurize the system.
BA
ti10438a
FIG. 4. Integrated Air Controls
10 313296J
Page 11
Component Identification

Air Line Accessories

See Supply Systems Operation manual.
Air line drain valve. Not included.
Air line filter: removes harmful dirt and moisture from compressed air supply. Not included.
Second bleed-type air valve isolates air line accessories and supply system for servicing. Locate upstream from all other air line accessories. Not included.
Air relief valve: automatically relieves excessive pressure. Not included.

2-Button Interlock Air Controls

D60i, D200i, and D200si Models
Systems that have 2-Button Interlock controls have the following additional components:

Communications Gateway Module

The Communications Gateway Module (CGM) provides a control link between Graco Control Architecture based systems and a selected fieldbus. This provides the means for remote monitoring and control by external automation systems.
Data provided by the CGM to the fieldbus depends on which Graco Control Architecture based system and fieldbus are connected. A data map supplied on a map token is defined for this pairing. Once the data map has been loaded into the CGM, it is stored internally, and the map token is no longer required for operation.
See the Supply System Communications Gateway Mod­ule Installation Kit manual for fieldbus parameter setup instructions and screen descriptions.
CGM Module Status LED Signals
Signal Description
2-Button Module: See the Air Controls manual for information.
Roller switch (CA): shuts off air supply when it contacts the bracket actuator. Operator must push and hold the activation buttons simultaneously to resume ram movement.
Activation Buttons
ti10843a1
F
IG
. 5: 2-Button Module
Bracket actuator (CB): attaches to the platen lift rod. When platen is outside of drum, actuator makes contact with the roller switch.
CA
Green on System is powered up
Yellow Internal communication in progress
Red Solid
*Red (7 flashes)
* The red LED will flash a code, pause, then repeat.
See Communications Gateway Module manual 312864 for diagnostic information. Verify that you are using the correct token for your system and reinstall token. If fails, order new token.
CGM hardware failure
Data map load failure
Incorrect data map for fieldbus type
No data map loaded
CB
ti10846a
IG
. 6: Roller Switch and Bracket Actuator
F
313296J 11
Page 12
Component Identification

Fluid Control Module

Table 2: FCM Sensor Connections
Connection Ram Sensor Description
1 Ram A and Ram B Air motor solenoid (wire labeled 3), drum low (wire labeled 1),
drum empty (wire labeled 2)
2 Ram A Light tower
3 Ram A + B Fluid depressurize/recirculate solenoid
4 not used not used
5 Ram A and Ram B Air motor reed switch, sensors
6 not used not used
7 Ram A Filter pressure at inlet and outlet
CAN communication cable 1
CAN communication cable 2
Ram A From Ram A FCM to display module.
Ram A and Ram B 15 ft (4.57 m) from Ram A FCM to Ram B FCM.
CAN Cable 1
FIG. 7: FCM Sensor Connections
3
4
CAN Cable 2
TI12337A
7
6
5
TI12336A
12 313296J
Page 13

User Interface

FIG. 8: Display Module
Button Function
On/Off
Powers air motor solenoid ON and OFF from Ram Operation screen (F
When ON, the air motor solenoid is ON and the pump of the active ram is pressurized.
Table 3: Display Module Button Functions
Component Identification
IG
. 71, page 100).
Cancel
Setup
Enter
Arrows Left/Right
When OFF, the air motor solenoids are OFF.
CAUTION: Turning the air motor solenoid OFF relieves pressure from the pump motor. It does not depressurize the fluid pressure. Follow the Pressure Relief Procedure, page 28.
NOTE: The ram up/down and blowoff air is independent of the electronic controls and can be operated anytime the main air slider valve is open and air pressure is available.
Powers heat ON and OFF from Heat Run screen (F
When ON, the enabled heat zones are ON.
When OFF, all heat zones are OFF.
Cancel a selection or number entry while in the process of entering a number or making a selection.
Toggle between run and setup screens.
Setup changes can be made while system is operating.
If setup screens are password protected, button toggles between run and password entry screen.
Opens drop down menus on Setup fields. Press to enter changes and make a selection.
Navigate left or right to a new screen. Navigate left or right within a screen while in Jump In mode. See Appendix A - User Interface Display, page 93, for more information.
IG
. 72, page 101).
Arrows Up/Down
313296J 13
Navigate up or down within a screen or to a new screen.
Move between selections within a drop-down menu.
Increment or decrement the selected numerical field within a selection menu.
Page 14
Component Identification
Table 3: Display Module Button Functions
Button Function
Soft Key
Soft keys activate the mode or action represented by the icon above each button in the LCD. See Table 4 for soft key modes and actions.
Table 4: Display Soft Key Icons
Icon Function
Depressurize Depressurize relieves fluid pressure from the pump outlet to below the platen on the currently
active ram.
If system is pressurized, press button.
Pump Prime
When prompted to depressurize the system, select or .
active ram will depressurize both rams.
Depressurizing the
NOTE: If additional user-supplied check valves have been added to the system, only the
active ram will be depressurized. You must perform manual crossover and select depressurize again to depressurize both rams. See Crossover section of this table on page 15.
If system is depressurized, press button.
When prompted to pressurize the system, select or .
Pump Prime
Tandem ram:
Tandem ram:
if pump is off, activates the air solenoid on the active ram; if pump is on, activates the air solenoid on the inactive ram which enables you
to purge air and prime the pump;
Single ram:
activates air solenoid whether or not pump is on;
clears the Pump Not Primed deviation or alarm (depending on setup selection); and
resets the drum volume remaining to the drum fill volume setpoint for pump being primed. Press button.
When prompted to prime the ram, select to prime.
Press button to exit Prime Mode or to reset counter to the prime time.
When prompted to exit Prime Mode, select to exit or to reset prime counter.
Recirculate Recirculate Mode pumps fluid from the drum, through the pump, and back into the drum on the
currently active ram.
Set motor air regulator to 30 psi (0.2 MPa, 2.1 bar) before pressing Recirculate key.
If system is not in Recirculate Mode, press button.
When prompted to turn recirculation on, select or . Adjust motor air regulator to
obtain desired flow rate.
If system is in Recirculate Mode, press button.
When prompted to turn recirculation off, select or .
14 313296J
Page 15
Component Identification
Table 4: Display Soft Key Icons
Icon Function
Crossover Crossover key transitions the active ram to inactive, and inactive ram to active. Available on
Warm Melt Tandem Supply Systems only.
NOTE: If an alarm is present on the inactive ram, crossover will not be successful. Manual crossover is disabled in single ram operation.
Press button.
When prompted to initiate a crossover, select or .
Setback
Setback transitions the heaters into setback mode. The setpoint for each zone will be decreased by the setback amount. See Heater System Setup Screen, page 95, and Heat Run Screen, page 101.
Jump In
In screens that have editable fields, press to access the fields and make changes. See
Appendix A - User Interface Display, page 93, for more information.
NOTICE
To prevent damage to soft key buttons, do not press the buttons with sharp objects such as pens, plastic cards, or fingernails.
313296J 15
Page 16
Component Identification
User Interface Display
NOTE: For details regarding the user interface dis­play see Appendix A - User Interface Display, page
93.
Display Screen Components
The following figure calls out the navigational, status, and general informational components of each display screen.
Current Date and Time
Displays soft keys that are active for particular screen
Soft Keys
F
IG
. 9: Display Screen Components
Navigation
Status
Mode
Function Display
16 313296J
Page 17

Installation

Installation
Accessories are available from Graco. Make certain all accessories are adequately sized and pressure-rated to meet the system’s requirements.
Component Identification illustrations are only a guide for selecting and installing system components and accessories. Contact your Graco distributor for assis­tance in designing a system to suit your particular needs.

Location Requirements

•Refer to Dimensions, page 104, for ram mounting and clearance dimensions.
Install indoors only, and not near water or any other liquid that is sprayed.

Location

NOTICE
Always lift supply system at proper lift locations (see F
IG
. 2) to avoid equipment damage. Do not lift in any
other way.

Grounding

Ground the supply system as instructed here and in the individual component manuals.
The power source conduit is not an adequate ground for the system. The unit must be bonded to either the building ground or a true earth ground. To reduce the risk of static sparking, ground the pump, the object being dispensed to, and all other dispensing equip­ment used or located in the dispensing area. All elec­trical wiring must be done by a qualified electrician and comply with local codes and regulations.
Pump: use a ground wire and clamp. Loosen grounding lug locknut and washer. Insert one end of supplied ground wire into slot in lug and tighten locknut securely. Connect other end of wire to a true earth ground. See F
IG
. 10.
1. Attach a lifting sling at the proper lift spots. Lift off the pallet using a crane or a forklift. See F proper lift locations.
2. Position the ram so the air controls and electrical enclosure are easily accessible. Ensure that there is enough space overhead for the ram to raise fully.
3. Using the holes in the ram base as a guide, drill holes for 1/2 in. (13 mm) anchors.
4. Ensure that the ram base is level in all directions. If necessary, level the base using metal shims. Secure the base to the floor using 1/2 in. (13 mm) anchors that are long enough to prevent the ram from tipping.
IG
. 2 for
ti8250a
F
IG
. 10: Ground Pump
Air and fluid hoses: use only electrically conductive
hoses.
Air compressor: follow manufacturer’s recommenda­tions.
Dispense valve: ground through connection to a prop-
erly grounded fluid hose and pump.
313296J 17
Page 18
Installation
Fluid supply container: follow local code.
Object being sprayed: follow local code.
Solvent pails used when flushing: follow local code.
Use only conductive metal pails, placed on a grounded surface. Do not place the pail on a nonconductive sur­face, such as paper or cardboard, which interrupts grounding continuity.
To maintain grounding continuity when flushing or relieving pressure: hold metal part of the dispense
valve firmly to the side of a grounded metal pail, then trigger the valve.

Connect Power Source

The electrical enclosure comes already attached and wired to the ram; however, before the supply system becomes functional you must connect the electrical
enclosure to a power source.
NOTE: See Power Requirements, page 7, for circuit protection requirements.
1. Open electrical enclosure door and locate power line filter.
2. Have a qualified electrician perform the following steps:
a. Connect your plant power to the electrical
enclosure power line filter according to local codes. A 1-3/8 in. (35 mm) diameter opening is provided on the side of the enclosure adjacent to the label. This opening is suitable for a 1 in. npt conduit or strain relief fitting (supplied).
b. Connect a power protective ground to the cen-
ter post on the line end of the power line filter.
NOTE: Install safety insulation boots (supplied) on the power line. Install 1/4 in. ring lugs (user sup­plied) on the power line and power protective ground line prior to connecting to the power line fil­ter posts.
Have a qualified electrician connect power according to national, state, and local safety and fire codes.
NOTE: Required voltage and amperage is noted on the electrical enclosure label. Also see Table 1. Before running power to the unit, make sure the plant electrical service meets the supply system’s electrical requirements.
18 313296J
Page 19
Installation

Install/Adjust Drum Low or Empty Sensor

1. Position ram at desired level (low or empty).
NOTE: Follow Steps 2 through 4 only if installing the low sensor.
2. Attach the low sensor to the existing sensor bracket (EA), above the existing empty sensor (EE).
D200 Shown
EA
EE
ED
EB
F
IG
. 11: Low or Empty Sensor Kit
4. Attach the sensor to the corresponding connector on the splitter cable. For drum low, attach the sen­sor to connector 1. For drum empty, attach the sen­sor to connector 2.
5. Power system on.
6. Make precise adjustments by moving the sensor within the slot on the sensor bracket. Use the yellow indicator on the sensor cable to indicate a drum low or empty condition.

Light Tower Accessory

Order the 255468 Light Tower Accessory as a diagnos­tic indicator for supply systems. See T description of light tower signals.
Table 5: Light Tower Signals
Signal Description
Yellow flashing A low priority error exists.
Yellow on A medium priority error exists.
Red flashing A high priority error exists.
Red on The system is shut down due to
error conditions.
ABLE
5 for a
3. Replace the existing cable between the empty sen­sor (EE) and FCM connector (see F with the empty/low sensor splitter cable.
IG
. 7, page 12)
313296J 19
Page 20
Installation

Attach Drum Stops

Supply systems are shipped with drum stops in place to help position the drum on the ram. For replacement parts, order Kit 255477. The kit includes two each of capscrews (FA), lock washers (not shown), and drum stops (FB).
D200 Shown
1. Locate the correct set of mounting holes on the ram base.
2. Using the capscrews (FA) and lock washers (not shown), attach the drum stops (FB) to the ram base.
FB
F
IG
. 12: Attach Drum Stops
FA
55 gal (200 L)
30 gal (115 L)
8 gal (30 L)
5 gal (20 L)
IG
. 13: Drum Stop Location
F
20 313296J
Page 21
Installation

Check Resistance

Check the Resistance Between the Supply System and the True Earth Ground
The resistance between the supply system compo­nents and true earth ground must be less than 0.25 ohms.
Have a qualified electrician check the resistance between each supply system component and the true earth ground. The resistance must be less than 0.25 ohms. If the resistance is greater than 0.25 ohms a dif­ferent ground site may be required. Do not operate the system until the problem is corrected.
NOTE: Use a meter that is capable of measuring resistance at this level.
Sensor Resistance Checks
Conduct these electrical checks with the main dis­connect OFF.
NOTE: For dispense valve and hose sensor resis­tance checks, refer to your dispense valve manual or hose manual.
The supply system includes a heat sensor and controller for each of the four heated zones. To check sensor resistance:
1. Make sure the power is off and that the disconnect switch is in the OFF position.
2. Make electrical resistance checks for the compo­nents.
3. Replace any parts that have resistance readings that do not comply with the ranges listed in Table 6.
NOTE: Check resistance at ambient room tempera­ture (63°– 77°F [17°– 25°C]
Table 6: RTD Sensor Resistance
Zone Component Connector Pin Range (ohms)
1 Platen Pin 1 to 3
2 Fluid Pump Pin 1 to 3
FIG. 14: RTD Connector Pins
).
1050-1100
1050-1100
Ω
Ω
313296J 21
Page 22
Installation
Heater Resistance Checks
Conduct these electrical checks with the main power disconnect OFF.
NOTE: For dispense valve and hose sensor resis­tance checks, refer to your dispense valve manual or hose manual.
To check heater resistance:
1. Make sure the power is off and that the disconnect switch is in the OFF position.
2. Make electrical resistance checks for the compo­nents. Refer to Table 7. Heater terminal pins are located on the back of the enclosure (H). See F page 8.
3. Replace any parts whose resistance readings do not comply with the ranges listed in Table 7.
IG
. 2,
NOTE: Check resistance at ambient room tempera­ture (63°– 77°F [17°– 25°C]
).
Table 7: Resistance Chart of All Heaters
Between
Zone Component
1 Platen - D200 1 and 3 240 15 +5/-5 2 Platen - D60 1 and 3 240 80 +10/-10 3 Pump L and N 240 37 +5/-5
Terminals
Unit Voltage
Range (ohms)
1
3
L
FIG. 15: Heater Terminal Pins
N
22 313296J
Page 23
Installation

Hose Installation and Care

NOTE: The warm melt supply system requires Graco single-circuit material hoses rated at a maxi­mum of 1920 Watts.
Hose Installation
1. Connect heated hose to the pump outlet.
2. Use two wrenches to tighten. Torque to 470-550 in-lbs (53.1-62.1 N•m).
3. Wrap exposed fittings on the pump outlet with Nomex insulation and secure insulation using fiber­glass tape.
Mechanical Setup
1. Fill displacement pump wet cup 2/3 full with Graco Throat Seal Liquid (TSL).
2. Turn all air regulators to their full counterclockwise position.
3. Connect a 3/4 in. (19 mm) air line from an air source to the system air inlet. Refer to the pump perfor­mance curves in the Check-Mate Pump Packages manual to determine your air supply flow require­ments.
NOTE: Quick disconnects restrict flow for large air motors.

Overview of Temperature Control Settings

Temperature controls are set in Setup mode. See Setup Mode Screens on page 95 for information about setting
temperature controls.
See Run Mode Screens on page 100 for information on controlling temperatures for each zone.
4. Connect hose adapter to green receptacle on junc­tion box.
FIG. 16: Connect Hose to Junction Box
5. Securely tighten the 16-pin electrical connectors on long heated hose leads into 16-socket receptacles on the end of the hose adapter.
6. Securely tighten the 8-socket electrical connectors on short heated hose leads into 8-pin receptacle located on the dispense valves.
Hose Care Guidelines
Refer to the Hotmelt/Warm Melt Heated Hose manual for details regarding hose care guidelines.
313296J 23
Page 24

Setup

Setup
The pump was tested with lightweight oil, which is left in the fluid passages to protect parts. To avoid contaminat­ing fluid with oil, flush the pump with a compatible sol­vent before use. See Purge System, step 2.

Purge System

Purging the system before the initial use can prevent material contamination, which may cause the material to fail or perform poorly.
NOTICE
Purge the system before performing the initial material loading procedure. The system was factory-tested
using a light soluble oil, a soybean oil, or some other oil as tagged. Flush the system to avoid contaminating the material that has been designated for initial material loading.
To purge the system perform the following procedure:
This equipment should not be used with more than one type of fluid due to potential compatibility issues that could result in an unpredictable reaction. Graco recommends using new hoses when chemicals are changed or care must be taken to assure that all traces of one chemical are removed before introduc­ing a second chemical.
3. Select a container of material that can eliminate the factory-test oil from the system. If necessary, check with Graco or the material supplier for a recom­mended solvent.
4. Before purging ensure the entire system and waste container are properly grounded.
NOTE: Remove any dispense valve orifices before purging. Reinstall after purging has been completed.
1. Select the material for the initial material load.
2. Verify whether the factory-test oil and the initial material load are compatible:
a. If the two substances are compatible, omit the
remaining steps in this procedure and refer to the start up and operation instructions.
b. If the two substances are incompatible, perform
the remaining steps in this procedure to flush
the system at ambient temperature.
Use fluids that are chemically compatible with the equipment wetted parts. See the Technical Data sec­tions in the equipment manuals.
5. Purge the material through the system for approxi­mately 1 to 2 minutes.
6. Remove the container if purge material was used.

Set Values on Display Module

Set desired values on display module Setup menus. See Setup Mode Screens, page 95.
24 313296J
Page 25
Setup

Load Material

Moving parts can pinch or amputate fingers. When the pump is operating and when raising or lowering the ram, keep fingers and hands away from the pump intake, platen, and lip of the drum.
NOTICE
Do not use a drum of material that has been dented or otherwise damaged; damage to the platen wiper can result.
NOTE: Before loading material, ensure that there is a minimum overhead clearance of 105 in. (267 cm) and all air regulators are backed off to their full counterclockwise position.
NOTE: Follow steps below for both rams if using a tandem warm melt supply system.
1. Refer to F lators and air valves.
IG
. 2, FIG. 3, and FIG. 4. Close all air regu-
D200 Shown
J
D
FIG. 17: Heated Platen
8. Set the director valve (BC) to DOWN and lower the ram until fluid appears at the top of the platen bleed port (J). Adjust ram air regulator (BB) as needed. Set the director valve (BC) to neutral and close the platen bleed port (J). 2-Button Interlock: If system has this feature, press and hold both buttons to start lowering the ram. See F
IG
. 5, page 11.
2. Open main air slider valve (BA) and set ram air reg­ulator (BB) to 40 psi (0.28 MPa, 2.8 bar). Set direc­tor valve handle (BC) to UP and let the ram rise to its full height. 2-Button Interlock: If the system has this feature, ram will stop as it nears the top. Press and hold both buttons to raise ram completely. See F
IG
. 5 on page 11.
3. Lubricate the platen seals (D) with grease or other lubricant compatible with the fluid you will pump.
4. Remove the drum cover and smooth the surface of the fluid with a straightedge.
5. Put a full drum of fluid on the ram base, slide it back against the drum stops, and center it under the platen (D). An optional drum roller kit is available to make it easier to load the drum on the base. Order Kit 255627.
6. Remove bleed stick from platen bleed port (J). See F
IG
. 17.
7. If drum has a plastic liner, pull it over edge of drum. Secure liner with tape wrapped around circumfer­ence of drum.
313296J 25
Page 26
Setup

System Heat Up

Never pressurize warm melt supply system while using warm melt materials before turning on heat.
Many warm melt materials tend to expand when heat­ing and may cause a heated hose to burst. Avoid the potential of bursting a hose by opening the dispense valve during system heat up and lock the dispense valve trigger open every time you shut the system down.
NOTE: Operate at the lowest temperature and pres­sure necessary for your application.
1. Turn the main disconnect on the electrical control panel door to the ON position.
2. Press while in the Heat Run screen to turn the
heaters on for enabled heat zones.
F
IG
. 18: Heat Run Screen - Ram A
26 313296J
Page 27
Setup

Prime

1. Make sure the system is at required temperature.
2. Tandem Systems Only: To prime the active ram, ensure that the system is not in Run Mode. To prime the inactive ram, ensure that the system is on and in Run Mode.
3. Single Systems Only: To prime the ram, ensure that the system is on. The system may or may not
be in Run Mode.
(Prime active ram - not Run Mode)
FIG. 21: Prime Confirmation
6. When the timer expires the air motor solenoid LED will turn off.
7. Prime the system until a smooth flow of material dis­penses from the dispense valve.
8. Lock the dispense valve trigger lock.
NOTE: To exit Prime Mode before the timer expires,
press the Pump Prime key . The display
prompts the operator to confirm. See F
IG
. 22. Select
to exit prime.
FIG. 19: Ram Operation Screen - Tandem System
(Prime inactive ram - in Run Mode)
IG
. 20: Ram Operation Screen - Tandem System
F
4. If using a manual dispense valve, unlock the dis­pense valve trigger and place dispense valve over a waste container.
5. Press the Pump Prime key . The display
prompts the operator to confirm. See F
IG
. 21. Select
IG
. 22: Exit Prime Mode Confirmation
F
NOTE: To extend the prime time counter, select
in F
IG
. 22. Display prompts operator to confirm.
IG
See F
. 23. Select to reset.
to begin prime.
IG
. 23: Reset Prime Time Counter Confirmation
F
313296J 27
Page 28

Operation

Operation

Pressure Relief Procedure

This procedure describes how to relieve pressure for the supply system. Use this procedure whenever you shut off the system and before checking or adjusting any part of the system.
1. Lock the dispense valve trigger.
2. Press On/Off key . If system is On, display will
highlight . Select to turn off.
If you suspect that the dispense tip/nozzle or hose is completely clogged, or that pressure has not been fully relieved after following the steps above, very slowly loosen the tip guard retaining nut or hose end coupling and relieve pressure gradually, then loosen completely. Now clear the tip/nozzle or hose.

Trigger Lock

Always engage the trigger lock when you stop dispens­ing to prevent the gun from being triggered accidentally by hand or if dropped or bumped.

Start and Adjust Ram

Moving parts can pinch or amputate fingers. When the pump is operating and when raising or lowering the ram, keep fingers and hands away from the pump intake, platen, and lip of the drum.
FIG. 24: System Function Screen
3. See F
4. Set the ram director valve to DOWN. The ram will
5. Jog the director valve up and down to bleed air from
6. Unlock the dispense valve trigger.
7. Hold a metal part of the dispense valve firmly to the
8. Lock the dispense valve trigger.
9. Open all fluid drain valves on ram(s). Have a con-
IG
. 4, page 10. Close the air motor slider valve
(BF) and the main air slider valve (BA) on ram(s).
slowly drop.
ram cylinders.
side of a grounded metal pail, and trigger the dis­pense valve to relieve pressure.
tainer ready to catch the drainage. Leave fluid drain valves open until ready to dispense again.
To start and adjust the ram(s), follow the Load Material procedure on page 25.

Start and Adjust Pump

NOTE: Follow steps below for both pumps if using a tandem warm melt supply system.
1. Connect pump outlet fittings and hose (not sup­plied).
NOTE: Be sure all components are adequately sized and pressure rated to meet the system’s require­ments.
2. Be sure the pump air valve is closed. Then set the ram air regulator (BB) to 50 psi (0.35 MPa, 3.5 bar). Set the director valve (BC) to DOWN. See F page 10.
IG
. 4,
28 313296J
Page 29
Operation
3. Press while in the Ram Operation screen.
F
IG
. 25: Ram Operation Screen - Tandem System
4. When the confirmation screen appears with a
prompt, select to start the pump.
5. Open the pump air valve (BF) and keep the director valve (BC) set to DOWN while pump is operating.
NOTE: Increase air pressure to the ram if the pump does not prime properly with heavier fluids. Decrease air pressure if fluid is forced out around the top seal or platen.

Manual Crossover

(Tandem Warm Melt Supply System Only)
Manual crossover can only be initiated if the following conditions are met:
inactive ram is not in the drum empty error condi­tion.
pump runaway and not primed alarms do not exist.
To initiate a manual crossover to the inactive ram:
1. From the Ram Operation screen, press the Cross-
over key . The display prompts the operator
to confirm.
2. Select to confirm manual crossover operation
or select to cancel.

Automatic Crossover

(Tandem Supply System Only)
Keep clear of the inactive ram, as automatic cross­over may occur unexpectedly. To repair or adjust the ram, first follow all steps of the Pressure Relief Pro- cedure on page 28.
The automatic crossover feature allows continuous flow and prevents system shutdown. If the active ram encounters a pump runaway or drum empty alarm, it will attempt an automatic crossover to the inactive ram.
The system will generate a crossover error if the active ram attempts an automatic crossover while the inactive ram has a pump runaway, drum empty, or not primed alarm. If this occurs, correct the error and clear the alarm from the Alarm screen. See Alarm Screen, page 103, for details.
FIG. 26: Crossover Function Screen
NOTE: If the active ram has a pump runaway error or drum empty error, the system will attempt an automatic crossover.
313296J 29
Page 30
Operation

Recirculate Function

Recirculate mode pumps fluid from the drum, through the pump, and back into the drum on the currently active ram.
To enter Recirculate mode:
1. Set the motor air regulator to 30 psi (0.2 MPa, 2.1 bar).
2. From the Ram Operation screen, press the Recircu-
late key . The display prompts the operator to
confirm.
3. Select to confirm recirculation or select to
cancel.

Depressurize Function

Follow the Pressure Relief Procedure on page 28. Shutting off power or removing power from the sys­tem will not depressurize the system.
When the system is pressurized the depressurize func­tion relieves fluid pressure from the pump outlet to below the platen on the currently active ram. However, when the system is depressurized pressing the depres­surize key will restore fluid pressure.
Depressurize System
From the Ram Operation screen, press the Depressur-
ize key . The display prompts the operator to con-
firm. Select to confirm depressurize or select
to cancel.
F
IG
. 27: Enter Recirculate Mode
4. Adjust motor air regulator to obtain desired flow rate.
NOTE: While in Recirculate Mode, the manual crossover function cannot be used and the inactive ram can­not be primed.
To exit Recirculate Mode, press the Recirculate key
. The display prompts the operator to confirm.
Select to confirm or select to cancel. See F
27.
NOTE: You must exit Recirculate Mode before depressuriz­ing or initiating a crossover.
IG
F
IG
. 28: Depressurize Function Screen
.
30 313296J
Page 31
Operation
NOTE: Depressurizing the active ram will depressurize both rams. However, if additional user-supplied check valves have been added to the system, only the active ram will be depressurized.
To depressurize both rams perform manual cross­over (see Manual Crossover, page 29), and then
press the Depressurize key again.
Pressurize System
From the Ram Operation screen, press the Depressur-
ize key . The display prompts the operator to con-
firm. Select to confirm pressurize or select to
cancel. See F
IG
. 28.

Change Drums

drum. Use minimum amount of air pressure neces­sary to push the platen out of the drum.
Excessive air pressure in the material drum could cause the drum to rupture, causing serious injury. The platen must be free to move out of the drum. Never use drum blowoff air with a damaged drum.
3. Once the platen clears the drum, release the blow-off air button (BG) and allow the ram to rise to its full height. 2-Button Interlock: If system has this feature, the ram will stop as it nears the top. Press and hold both buttons to raise ram completely. See F
IG
. 5.
4. Remove empty drum.
5. Inspect platen and, if necessary, remove any remaining material or material build–up.
6. Place full drum on ram base.
NOTE: Follow this procedure to change the drum on a fully heated warm melt supply system.
NOTE: Follow this procedure for either ram if using a tandem warm melt supply system.
NOTICE
Do not use a drum of material that has been dented or otherwise damaged; damage to the platen wiper can result.
1. Push in the air motor slider valve (BF) to stop the pump. See F
2. Set ram director valve (BC) to UP to raise the platen (D) and immediately press and hold the blowoff air button (BG) until the platen (D) is completely out of
IG
. 4.
7. Lower the ram and adjust the position of the drum relative to the platen. See Load Material on page
25.
313296J 31
Page 32

Maintenance

Shutdown

Follow the procedure below for normal system shut down, such as at the end of the work day.
NOTICE
Turning the system OFF relieves pressure from the pump motor; however, it does not depressurize the fluid pressure. Follow the Pressure Relief Procedure, page
28.
NOTE: The ram up/down and blowoff air is indepen­dent of the electronic controls and can be operated anytime the main air slider valve is open and air pressure is available.
1. Press while in the Ram Operation screen to
turn off the air motor. Select to confirm.
2. Press while in the Heater Run screen to turn
Maintenance
To reduce the risk of serious injury whenever you are instructed to relieve pressure, always follow the Pres-
sure Relief procedure.

Replace Throat Seals

Quick Coupler
Remove wet cup from displacement pump while attached to the ram to replace throat seals.
1. Ensure displacement pump is at bottom of stroke.
2. Follow the Pressure Relief Procedure on page 28.
3. Remove Quick Coupler: Remove clip (GC), and slide coupling cover (GB) up to remove coupling (GA).
off the heaters. Select to confirm.
3. Follow the Pressure Relief Procedure, page 28.
Many warm melt materials tend to expand when heat­ing and may cause a heated hose to burst. Avoid the potential of bursting a hose by opening the dispense valve during system heat up and lock the dispense valve trigger open every time you shut the system down.
GB
GC
F
IG
. 29: Remove Quick Coupler
4. Lift air motor rod to bring rod to top of stroke.
5. Remove wet cup and packing cartridge according to instructions in displacement pump manual(s).
GA
ti10508a
32 313296J
Page 33
Maintenance

Platen Maintenance

If the platen does not come out of the pail easily when the pump is being raised, the air assist tube or check valve may be plugged. A plugged valve prevents air from reaching the underside of the plate to assist in rais­ing it from the pail.
1. Turn off main disconnect.
2. Relieve pressure and disassemble air assist valve. Refer to Supply Systems Repair-Parts manual.
3. Clear air assist tube in platen. Clean all parts of valve and reassemble. Refer to Supply Systems Repair-Parts manual.
4. Remove bleed stick from platen. Push bleed stick through bleed relieve port (T) to remove material residue. See F
5. Remove platen covers. See F
IG
. 30.
IG
. 30.
Remove and Reinstall Platen Wipers
Refer to Supply Units Repair-Parts manual for instruc­tions.
70
49
Bleed Stick
T
r_wm2179_313296_6a
43
48
a. Remove platen cover fasteners (70) or nuts
(309).
For 55 gallon platen (D200 3 in. and D200s 6.5
b.
in. supply systems):
Remove both platen covers
(49) and ground wire from platen.
For smaller platens (D60 3 in. supply systems):
Disconnect pump for the platen; see Discon- nect Pump from Platen, page 50. Remove screws (323) from upper heater plate (320). Remove upper heater plate.
6. Remove any excess fluid. Use a soft wire brush on heater coils (48) or heater (319). See F
IG
. 30.
7. Inspect platen heater blocks (43 or 320) or heater (48 or 319) for burn or melt spots. Replace platen heater blocks or heater if necessary. See F
IG
. 30.
8. Check for loose connections and damaged wires.
9. Follow steps in reverse order to reassemble platen.
309
Bleed Stick
T
FIG. 30: Remove Platen Covers and Heaters
309
323
320
319
NOTE: Torque platen cover fasteners (70) to 60 +/­10 in-lbs (6.8 +/- 1.1 N•m) for 55 gallon platen. Torque nuts (309) to 45 +/- 5 in-lbs (5.1 +/- 0.6 N•m) for smaller platens.
313296J 33
Page 34
Maintenance

Electrical Enclosure

1. Turn the main disconnect on the electrical control panel door to the OFF position to disconnect power.
Power is still connected to the power line filter (459) even after the main disconnect is open. Avoid con­tact with the power line filter.
2. Open door of electrical enclosure.
459
419
Check Ground Fault Circuit Interrupter
1. With electrical enclosure door still open, switch main disconnect (421) back on.
Have a qualified electrician restore power to main disconnect while electrical enclosure door is open.
2. Press Test button on ground fault circuit interrupter (419). The blue switch should flip to the middle or opposite side.
NOTE: Do not perform this test while the system is in operation.
3. Press blue switch back into place to reset breaker.
419
421
F
IG
. 31: Inside View of Electrical Enclosure
3. Check for damaged or loose wires. Check connec­tions from cable track.
F
IG
. 32: Ground Fault Circuit Interrupter
4. Switch main disconnect off.
34 313296J
Page 35
Maintenance

Pump Heaters

1. Turn the main disconnect on the electrical control panel door to the OFF position to disconnect power.
2. Remove four screws (80 or 257) from back pump shroud (52 or 234).
D200 Shown
80 or 257
4. Check for damaged wires and connections.
5. Ensure heaters (44 or 227) are secure so they can­not rotate on pump.
D200 Shown
44 or 227
F
IG
. 34: Pump Heaters
F
IG
. 33: Remove Pump Shroud
3. Remove pump heater front shroud (51 or 233).
313296J 35
Page 36

Alarms

Alarms
Warm Melt alarms alert you to a problem and help pre-

Diagnose Alarms

vent system shutdown or application errors. If an alarm occurs, operation may stop and the following occurs.
See Alarm Codes and Troubleshooting, page 36, for causes and solutions to each alarm code.
Light tower indication changes (if equipped)
Status bar on the display shows the alarm descrip­tion

Clear Alarms

Alarms are cleared by the solution(s) listed in the follow­ing table or from the screen in which they appear. Refer to Alarm Codes and Troubleshooting, page 36, for details.

Alarm Codes and Troubleshooting

Alarm
Code Alarm Problem Cause Solution Clear Alarm
Fluid Control Module
CB1X A - Communication Error -
Ram A Not Found
CB2X B - Communication Error -
Ram B Not Found
B61X
B62X
Crossover Error (Ram A)
Crossover Error (Ram B)
Ram cannot communicate with FCM A.
Ram cannot communicate with FCM B.
Inactive ram has a Not Primed alarm.
There is a Runaway alarm Correct runaway condition
There is a Drum Empty alarm. Replace empty drum with
Verify that power is sup­plied.
Check that CAN cables are connected.
Verify that selector switch is set correctly.
Replace FCM A.
Verify that power is sup­plied.
Check that CAN cables are connected.
Verify that selector switch is set correctly.
Replace FCM B
Set inactive ram to Prime mode to automatically clear alarm.
and clear alarm on Status screen 1.
full drum to clear.
Alarm automatically cleared by solution.
Alarm automatically cleared by solution.
Cleared from Ram Alarm screen. See Appendix A - User Interface Display, page 93.
36 313296J
Page 37
Alarm
Code Alarm Problem Cause Solution Clear Alarm
Fluid Control Module (continued)
DA1X
DA2X
L11X
L12X
DB1X
DB2X
WJ1X
WJ2X
DK1X
DK2X
L21X
L22X
WK1X
WK2X
ML1X
ML2X
MA1X
MA2X
Pump Runaway A
Pump Runaway B
A - Drum Empty
B - Drum Empty
A - Not Primed
B - Not Primed
A - Air Solenoid Discon­nected
B - Air Solenoid Discon­nected
A - Air Motor Sensor Error
B - Air Motor Sensor Error
A - Drum Low Deviation
B - Drum Low Deviation
A - Fluid Solenoid Discon­nected Deviation
B - Fluid Solenoid Discon­nected Deviation
A - Rebuild Platen Seals
B - Rebuild Platen Seals
A - Rebuild Pump
B - Rebuild Pump
Pump is running faster than set runaway limit due to:
Increased air pressure.
Increased fluid output.
Exhausted fluid supply.
Open fitting, hose, drain, or bleed valve.
Drum empty sensor has been activated.
The pump is not primed. Set ram to Prime mode to
Solenoid unplugged. Check that solenoid cable
Damaged solenoid / wires. Inspect solenoid wires for
System has seen multiple up strokes without a down stroke, or multiple down strokes with­out an up stroke.
Damaged or disconnected air motor sensors.
Drum low sensor has been activated.
Solenoid unplugged. Check that solenoid cable
Damaged solenoid wires. Inspect solenoid cable for
Counter has reached pro­grammed platen maintenance interval.
Counter has reached pro­grammed pump maintenance interval.
Correct runaway condition and clear alarm.
Replace empty drum with full drum to clear.
automatically clear alarm, or manually clear alarm from Ram Alarm screen.
is connected.
damage.
See air motor manual. Cleared from Ram Alarm
Check that air motor sen­sors are connected.
Inspect air motor sensor harness for damage.
Replace empty drum with full drum to clear.
is connected.
damage.
Perform platen mainte­nance; see Supply Sys­tems Repair-Parts manual.
Perform pump mainte­nance. See Check-Mate Displacement Pump man­ual.
Cleared from Ram Alarm screen. See Appendix A - User Interface Display, page 93.
Alarm automatically cleared by solution.
Cleared from Ram Alarm screen or Ram Operation screen. See Appendix A - User Interface Display, page 93.
Alarm automatically cleared by solution.
Alarm automatically cleared by solution.
screen. See Appendix A - User Interface Display, page 93.
Deviation automatically cleared by solution.
Deviation automatically cleared by solution.
Cleared from Maintenance screen. See Appendix A - User Interface Display, page 93.
Cleared from Maintenance screen. See Appendix A - User Interface Display, page 93.
Alarms
313296J 37
Page 38
Alarms
Alarm
Code Alarm Problem Cause Solution Clear Alarm
Fluid Control Module (continued)
DA1X
DA2X
L11X
L12X
DB1X
DB2X
WJ1X
WJ2X
DK1X
DK2X
L21X
L22X
WK1X
WK2X
ML1X
ML2X
MA1X
MA2X
Pump Runaway A
Pump Runaway B
A - Drum Empty
B - Drum Empty
A - Not Primed
B - Not Primed
A - Air Solenoid Discon­nected
B - Air Solenoid Discon­nected
A - Air Motor Sensor Error
B - Air Motor Sensor Error
A - Drum Low Deviation
B - Drum Low Deviation
A - Fluid Solenoid Discon­nected Deviation
B - Fluid Solenoid Discon­nected Deviation
A - Rebuild Platen Seals
B - Rebuild Platen Seals
A - Rebuild Pump
B - Rebuild Pump
Pump is running faster than set runaway limit due to:
Increased air pressure.
Increased fluid output.
Exhausted fluid supply.
Open fitting, hose, drain, or bleed valve.
Drum empty sensor has been activated.
The pump is not primed. Set ram to Prime mode to
Solenoid unplugged. Check that solenoid cable
Damaged solenoid / wires. Inspect solenoid wires for
System has seen multiple up strokes without a down stroke, or multiple down strokes with­out an up stroke.
Damaged or disconnected air motor sensors.
Drum low sensor has been activated.
Solenoid unplugged. Check that solenoid cable
Damaged solenoid wires. Inspect solenoid cable for
Counter has reached pro­grammed platen maintenance interval.
Counter has reached pro­grammed pump maintenance interval.
Correct runaway condition and clear alarm.
Replace empty drum with full drum to clear.
automatically clear alarm, or manually clear alarm from Ram Alarm screen.
is connected.
damage.
See air motor manual. Cleared from Ram Alarm
Check that air motor sen­sors are connected.
Inspect air motor sensor harness for damage.
Replace empty drum with full drum to clear.
is connected.
damage.
Perform platen mainte­nance; see Supply Sys­tems Repair-Parts manual.
Perform pump mainte­nance. See Check-Mate Displacement Pump man­ual.
Cleared from Ram Alarm screen. See Appendix A - User Interface Display, page 93.
Alarm automatically cleared by solution.
Cleared from Ram Alarm screen or Ram Operation screen. See Appendix A - User Interface Display, page 93.
Alarm automatically cleared by solution.
Alarm automatically cleared by solution.
screen. See Appendix A - User Interface Display, page 93.
Deviation automatically cleared by solution.
Deviation automatically cleared by solution.
Cleared from Maintenance screen. See Appendix A - User Interface Display, page 93.
Cleared from Maintenance screen. See Appendix A - User Interface Display, page 93.
38 313296J
Page 39
Alarm
Code Alarm Problem Cause Solution Clear Alarm
Fluid Control Module (continued)
DD1X
DD2X
A - Pump Diving
B - Pump Diving
Pump leak. Worn valve or packings.
See Check-Mate Displace­ment Pump manual.
Ram air pressure set too low. Increase air pressure to
ram until diving stops.
Material flow rate exceeds ability of ram to feed pump.
Temperature Control Modules
Decrease pump air pres­sure to slow cycle rate. Decrease pressure until diving stops.
Cleared from Ram Alarm screen. See Appendix A - User Interface Display, page 93.
The last digit in the temperature control module alarm codes identify the heat zone.
T3A1 T3A2 T3A3 T3A4 T3A5 T3A6 T3A7 T3A8 T3A9 T3A10 T3A11 T3A12
T2A1 T2A2 T2A3 T2A4 T2A5 T2A6 T2A7 T2A8 T2A9 T2A10 T2A11 T2A12
Alarm Above Setpoint
Deviation Above Setpoint
Deviation Below Setpoint Tripped circuit breaker. Visually check circuit
RTD on wrong module. Verify RTD wire and heater
power cord is attached to correct heat module.
Shorted module. Replace module.
breaker for a tripped condi­tion.
Low power. Measure voltage across
input terminals on power line filter. Voltage should measure between 190 and 250 Vac.
Cable unplugged/loose wire. Check for loose or discon-
nected wires and plugs.
Circuit breaker not set for L2 and L3.
Bad heaters. Measure resistance of
GFCI has been tripped. Visually check GFCI for a
Customer supplied main circuit breaker tripped.
Visually check circuit breaker for proper setting of L2 and L3.
heater.
tripped condition.
Measure voltage across the disconnect switch. Voltage should measure between 190 and 275 Vac.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Alarms
313296J 39
Page 40
Alarms
Alarm
Code Alarm Problem Cause Solution Clear Alarm
Temperature Control Modules (continued)
T6A1 T6A2 T6A3 T6A4 T6A5 T6A6 T6A7 T6A8 T6A9 T6A10 T6A11 T6A12
A4A1 A4A2 A4A3 A4A4 A4A5 A4A6 A4A7 A4A8 A4A9 A4A10 A4A11 A4A12
No Temp Rise Tripped circuit breaker. Visually check circuit
breaker for a tripped condi­tion.
Low power. Measure voltage across
input terminals on power line filter. Voltage should measure between 190 and 250 Vac
Cable unplugged/loose wire. Check for loose or discon-
nected wires and plugs.
Circuit breaker not set for L2 and L3.
Bad heater(s). Measure resistance of
GFCI has been tripped. Visually check GFCI for a
Customer supplied main circuit breaker tripped.
Over current Bad heaters. Measure resistance of
Wrong zone type. Ensure zone is set for type
High voltage. Measure voltage across the
Shorted module. If temperature rises for a
Visually check circuit breaker for proper setting of L2 and L3.
heater(s).
tripped condition.
Measure voltage across the disconnect switch. Voltage should measure between 190 and 275 Vac.
heater.
of hardware connected to it.
disconnect switch. Voltage should measure between 190 and 275 Vac.
zone that has been dis­abled, replace heat mod­ule.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
40 313296J
Page 41
Alarm
Code Alarm Problem Cause Solution Clear Alarm
Temperature Control Modules (continued)
A1A1 A1A2 A1A3 A1A4 A1A5 A1A6 A1A7 A1A8 A1A9 A1A10 A1A11 A1A12
A7A1 A7A2 A7A3 A7A4 A7A5 A7A6 A7A7 A7A8 A7A9 A7A10 A7A11 A7A12
T6A1 T6A2 T6A3 T6A4 T6A5 T6A6 T6A7 T6A8 T6A9 T6A10 T6A11 T6A12
Undercurrent Tripped circuit breaker. Visually check circuit
breaker for a tripped condi­tion.
Over temperature protection is activated.
Low power. Measure voltage across
Cable unplugged/loose wire. Check for loose or discon-
Circuit breaker not set for L2 and L3.
Bad heaters. Measure resistance of
GFCI has been tripped. Visually check GFCI for a
Customer supplied main circuit breaker tripped.
Wrong zone type. Ensure zone is set for type
Unexpected Current Shorted module. If temperature rises for a
Invalid RTD Reading Bad RTD. Measure resistance of RTD
Bad RTD connection/loose wire.
Component not plugged in. Ensure a component is
Allow zone to cool down.
input terminals on power line filter. Voltage should measure between 190 and 250 Vac.
nected wires and plugs.
Visually check circuit breaker for proper setting of L2 and L3.
heater.
tripped condition.
Measure voltage across the disconnect switch. Voltage should measure between 190 and 250 Vac.
of hardware connected to it.
zone that has been dis­abled, replace heat mod­ule.
and verify it is within valid range.
Check for loose or discon­nected wires and plugs.
plugged into zone report­ing error. If nothing is plugged in, disable zone.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Alarms
313296J 41
Page 42
Alarms
Alarm
Code Alarm Problem Cause Solution Clear Alarm
T4C1 T4C2 T4C3 T4C4 T4C5 T4C6 T4C7 T4C8 T4C9 T4C10 T4C11 T4C12
V4M1 V4M2 V4M3 V4M4 V4M5 V4M6 V4M7 V4M8 V4M9 V4M10 V4M11 V4M12
V1M1 V1M2 V1M3 V1M4 V1M5 V1M6 V1M7 V1M8 V1M9 V1M10 V1M11 V1M12
V4I1 V4I2 V4I3 V4I4 V4I5 V4I6 V4I7 V4I8 V4I9 V4I10 V4I11 V4I12
PCB Overtemperature Overheated Temperature
Control Module.
High Line Voltage Incoming line voltage is too
high.
No Line Voltage Low Line Voltage
High DC Voltage Faulty DC power supply. Measure that DC supply
Tripped circuit breaker. Visually check circuit
GFCI has been tripped. Visually check GFCI for a
Cable unplugged/loose wire. Check for loose or discon-
Turn heat zone off. Wait a few minutes. If the condi­tion does not clear on its own, replace heater mod­ule.
Measure voltage across disconnect switch. Voltage should measure between 190 and 250 Vac.
breaker for a tripped condi­tion.
tripped condition.
nected wires and plugs.
output is 24V. If not, replace supply.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
42 313296J
Page 43
Alarm
Code Alarm Problem Cause Solution Clear Alarm
Temperature Control Modules (continued)
V1I1 V1I2 V1I3 V1I4 V1I5 V1I6 V1I7 V1I8 V1I9 V1I10 V1I11 V1I12
A4C1 A4C2 A4C3 A4C4 A4C5 A4C6 A4C7 A4C8 A4C9 A4C10 A4C11 A4C12
A1C1 A1C2 A1C3 A1C4 A1C5 A1C6 A1C7 A1C8 A1C9 A1C10 A1C11 A1C12
A7C1 A7C2 A7C3 A7C4 A7C5 A7C6 A7C7 A7C8 A7C9 A7C10 A7C11 A7C12
Low DC Voltage Faulty DC power supply. Measure that DC supply
output is 24V. If not, replace supply.
Broken Temperature Control Module.
High Contactor Current Broken contactor. Replace contactor. Cleared from Heat Run
Low Contactor Current Broken contactor. Replace contactor. Cleared from Heat Run
Disconnected or loose wire. Verify cable 15W902 from
Broken Temperature Control Module.
Unexpected Contactor Cur­rent
Broken Temperature Control Module.
If DC supply is supplying 24V when disconnected from system, check which module is causing short. Check this by connecting one module at a time and then measuring for 24V.
High Power Temperature Control Module is con­nected correctly.
Verify there is 24V between both wires on 15W902. If there is not 24V, replace High Power Temperature Control Module.
Turn heat zone for platen off. If there is still 24V across wires on 15W902, replace Temperature Con­trol Module.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
screen. See Heat Run Screen, page 101.
screen. See Heat Run Screen, page 101.
Cleared from Heat Run screen. See Heat Run Screen, page 101.
Alarms
313296J 43
Page 44

Troubleshooting

Troubleshooting
1. Follow Pressure Relief Procedure, page 28, before disassembling any part of the warm melt supply system.
NOTE: Troubleshooting covered in this manual is specific to warm melt heat functions. Refer to Sup­ply Systems Repair-Parts manual and/or Tandem Supply Systems Repair-Parts manual for ram trou­bleshooting. Refer to Check-Mate Pump Packages manual for pump troubleshooting.
Problem Cause Verification Solution
No power. Customer supplied main
circuit breaker tripped.
GFCI has been tripped. Visually check GFCI for a
No graphics on screen. No graphics are shown on
display screen.
2. Disconnect all power to the warm melt supply sys­tem before repairing.
3. Check all possible problems before disassembling any part of the warm melt supply system.
Measure voltage across disconnect switch; voltage should measure between 190 and 250 Vac.
tripped condition.
Verify green LED on bottom of display is illuminated.
3
24 Rtn
2
24 Vdc+
GCA cable end
Determine cause of the tripped circuit breaker. Then repair fault and reset main circuit breaker.
Determine fault that caused GFCI to trip. Then repair fault and reset GFCI.
If green LED is not illumi­nated:
1. Check for DC power on the GCA cable at the display. Replace faulty cable/component.
2. Replace faulty display module.
If green LED is illuminated, check red LED. If red LED is illuminated, replace dis­play module.
Backlight does not power up.
44 313296J
Can see display, but back­light is not illuminated when a button is pressed.
Replace display module.
Page 45
Troubleshooting
Problem Cause Verification Solution
No heat. Tripped circuit breaker. Visually check circuit
breaker for a tripped condi­tion.
Low power. Measure voltage across
terminals 2T1 and 4T2 on main disconnect. Voltage should measure between 190 and 275 Vac.
Cable unplugged/loose wire.
Check for loose or discon­nected wires and plugs.
GFCI tripped. Visually check GFCI for a
tripped condition.
Zone not enabled. Verify zone is enabled on
Heat Run screen.
Incorrect temperature set point.
Verify zone has a correct temperature setting on Heat Run screen.
Bad heater. Measure resistance of
heater.
Determine cause of tripped circuit breaker. Then repair fault and reset main circuit breaker.
1. If voltage is lower than expected, use electrical schematic to locate faulty wiring or connec­tion.
2. Have a qualified electri­cian service electrical components.
Attach plug/wire.
Determine fault that caused GFCI to trip. Repair fault, and reset GFCI.
Enter Setup screen and enable correct zone.
Enter Setup and enter cor­rect temperature.
1. Unplug suspected heater zone from heater module.
Contactor not closing. Turn on heat for zone A1 or
B1and ensure contactor closes.
2. Follow Heater Resis- tance Checks, page
22.
3. If resistance is outside allowable value, replace heater(s).
1. Verify cable 15W902 from the high power TCM is connected cor­rectly.
2. Verify that there are no other error conditions that would prevent heater from starting.
3. Verify there is 24 Vdc between 2 wires on 15W902. If not, replace high power TCM. See Alarms, page 36.
4. Replace contactor.
313296J 45
Page 46
Troubleshooting
Problem Cause Verification Solution
Missing module. Modules not on network. Verify attached modules
through Advanced Setup screens 4 and 5.
Cable disconnected. Verify all green LEDs are
illuminated and yellow LEDs are flashing.
Module with wrong rotary switch setting.
Verify rotary switch is set correctly.
Enter Setup screen and scroll to Advanced Setup screens 4 and 5. These screens lists all compo­nents corresponding soft­ware revision number on network.
Reconnect/replace faulty cable.
1. Remove power from unit.
2. Remove access cover and visually check rotary switch setting.
3. If incorrect, set to cor­rect setting. See
Upgrade Tempera­ture Control Module Software, page 56, and Upgrade FCM Software, page 59, for
selector switch loca­tions.
Heating is slow. Heater defective. Measure resistance of
heater.
Low power. Measure voltage across
terminals 2T1 and 4T2 on main disconnect. Voltage should measure between 190 and 275 Vac.
Heating over shoots. RTD on wrong module. Verify for given zone that
temperature does not increase when zone is dis-
Shorted module. Replace module.
Does not crossover. Alternate ram has an empty
abled.
Verify ram has material. Replace empty drum.
sensor activated.
Alternate pump is not primed.
Alternate pump has an active alarm.
Verify alternate ram is ready to run.
See Alarm Codes and Troubleshooting, page
36.
4. Replace access cover.
Follow Heater Resistance Checks, page 22.
1. If voltage is lower than expected, use electrical schematic to locate faulty wiring or connec­tion.
2. Have a qualified electri­cian service electrical components.
Verify RTD wire or heater power cord is attached to correct heat module.
Prime pump.
See Alarm Codes and Troubleshooting, page
36.
46 313296J
Page 47

Repair

To reduce the risk of serious injury, follow the Pres­sure Relief Procedure and the Load Material pro-
cedure prior to performing repair procedures.

Air Motor

Remove Air Motor
Remove junction box.
For 55 gallon platen (D200 and D200s supply systems):
Remove two screws (61) securing junction box to air motor. Remove junction box and temporarily secure to
platen rod.
Repair
For smaller platens (D60 3 in. supply systems):
Remove junction box. Remove screws (278) from junc­tion box (255), and remove cover (271). Remove junc­tion box from bracket (258).
61
96
90, 91
F
IG
. 35: Remove D200 and D200s Junction Box
42
71
12
258
IG
. 36: Remove D60 Junction Box
F
3. See Disconnect Displacement Pump in Check-Mate Pump Packages manual.
To reduce the risk of serious injury or damage to equipment, make sure the main disconnect is off before continuing with this procedure.
4. See Supply System repair manual for air motor removal instructions.
255
271
278
313296J 47
Page 48
Repair
Install Air Motor
1. See Supply System repair manual for air motor installation instructions.
2. Reinstall junction box.
For 55 gallon platen (D200 and D200s supply sys­tems):
Remove junction box from platen rod. Rein­stall junction box to air motor using move two screws (61). See F
IG
. 35.
For smaller platens (D60 3 in. supply systems):
Reinstall junction box (255) onto bracket (258). Use screws (278) to attach cover (271). See F
IG
. 36.

Displacement Pump

Remove Displacement Pump
This procedure must be done while the system is still warm. The material and equipment may still be hot.
shrouds (51, 52), pump heaters (44), and RTD sen­sor (46).
51
44
46 44
r_wm2179_313296_7a
52
FIG. 37: D200 and D200s Pump Heater Shrouds
4. Raise air motor. Loosen nut (HB) under ram bar and thread it down the threaded rod (HC) to the lift ring adapter (HD) holding the motor. Use wrench on nut (HA) on top of ram bar to raise air motor.
HC
Refer to your Check-Mate Displacement Pump manual to repair the displacement pump.
If the air motor does not require servicing, leave it attached to its mounting. If the air motor does need to be removed, see Remove Air Motor, page 47.
D200 and D200s Supply Systems
1. Disconnect air hose and ground wire from air motor.
2. See Disconnect Displacement Pump in Check-Mate Pump Packages manual.
3. Follow steps 1- 4 of Replace Platen Heaters and Sensor section, page 52, to remove pump heater
HA
HD
HB
TI10648A
IG
. 38: Raise Air Motor
F
5. See Disconnect Pump from Platen, page 50, to disconnect the displacement pump from the platen.
6. Use two people to carefully lift out the displacement pump. Service displacement pump as needed. See Check-Mate Displacement Pump manual for instructions.
48 313296J
Page 49
Repair
D60 Supply System
1. Disconnect air hose and ground wire from air motor.
2. See Disconnect Displacement Pump in Check-Mate Pump Packages manual.
3. Follow steps 1- 4 of Replace Platen Heaters and Sensor section, page 52, to remove pump heater shrouds (233, 234), pump heaters (227), and RTD sensor (229).
227
229
227
r_wm29yy_313296b_3
233
Install Displacement Pump
D200 and D200s Supply Systems
1. Install displacement pump on platen. See Connect Pump to Platen, page 51.
2. Lower air motor. Use wrench on nut (EA) to lower air motor.
3. Reinstall pump heater shrouds (51, 52). Secure with screws (80).
4. See Reconnect Displacement Pump in Check-Mate Pump Packages manual.
5. Reconnect air hose and ground wire to air motor.
F
IG
. 39: D60 Pump Heater Shrouds
4. See to Disconnect Pump from Platen on page 50 to disconnect displacement pump from platen.
5. Raise ram assembly to lift air motor away from dis­placement pump.
6. Remove displacement pump, and service as needed. See Check-Mate Displacement Pump manual.
TI10515A
F
IG
. 40: Reconnect Air Hose and Ground Wire
D60 Supply System
1. Raise ram to install displacement pump to platen.
2. Connect displacement pump to platen. See Con- nect Pump to Platen, page 51.
3. Reinstall pump heater shrouds (233, 234). Secure with screws (257).
4. See Reconnect Displacement Pump in Check-Mate Pump Packages manual.
5. Reconnect air hose and ground wire to air motor.
313296J 49
Page 50
Repair

Disconnect Pump from Platen

The pump is mounted to the platens by mounting Kit
255392.
55 Gallon Platen
1. Disconnect displacement pump from air motor. See Check-Mate Pump Packages manual.
2. Raise air motor. See Remove Displacement Pump, page 48.
3. Remove four screws (103a) and four clamps (103b).
103a
103b
20, 30, and 60 Liter Platens
1. Disconnect displacement pump from air motor. See Check-Mate Pump Packages manual.
2. Raise air motor. See Remove Displacement Pump, page 48.
3. Remove screws (308) from platen.
308
103c
FIG. 41: 55 Gallon Mounting Kit
4. Use two people to carefully lift pump from platen.
5. Inspect o-ring (103c) for damage. Replace o-ring if necessary.
F
IG
. 42: 20, 30, 60 Liter Mounting
4. Use two people to carefully lift pump from platen. If using a pump with an intake adapter, remove screws, adapter, and o-rings from pump inlet.
5. Inspect o-ring for damage. Replace o-ring if neces­sary.
50 313296J
Page 51
Repair

Connect Pump to Platen

55 Gallon Platen
1. Use two people to set pump onto platen.
2. Secure pump to platen with screws (103a) and clamps (103b). See F
3. Lower air motor.
4. See Reconnect Displacement Pump in Check-Mate Pump Packages manual.
20, 30, and 60 Liter Platen
NOTE: Before installing a 20, 30, or 60 liter platen to a pump with an intake adapter, install adapter and o-ring.
1. Place o-ring on pump intake. See F
IG
. 41.
IG
. 42.

Replace Pump Heaters

1. Turn off main disconnect.
2. Remove screws (80 or 257) from back pump heater
shroud (52 or 234).
D200 Shown
52 or
80 or 257
234
2. Use two people to set pump onto platen.
3. Secure pump to platen with screws (308).
4. Lower air motor.
5. See Reconnect Displacement Pump in Check-Mate Pump Packages manual.
FIG. 43: Remove Pump Shroud
3. Remove ground wires.
4. Remove pump heater front shroud (51 or 233).
313296J 51
Page 52
Repair
5. Remove pump heater bands (44 or 227):
a. Remove screws from both pump heaters.
b. Pry heater bands apart and remove from pump.
c. Disconnect wires from heater bands. Inspect
wires for damage, and replace with new wires (included with pump heaters) if necessary. See Electrical Schematics, page 61.
d. Remove RTD sensor (46 or 229). Loosen screw
on sensor support (45 or 228) and slide RTD out.
44 or 227
45 or 228
46 or 229,
110
44 or 227

Replace Platen Heaters and Sensor

55 Gallon Platen Heater and Sensor
1. Turn off main disconnect.
2. Remove both platen cover fasteners (70).
3. Remove both platen covers (49) and ground wire from platen.
70
49
59
11
43
ti17720a
F
IG
. 44: Remove Pump Heaters
6. Install new pump heater bands and secure with screws.
NOTE: To ease pump heater band installation, first install heater bands on middle of displacement pump. Then slide heater band up or down into cor­rect location.
7. Reinstall RTD sensor and tighten screw on sensor support.
NOTE: Ensure RTD is flush to pump before tighten­ing screw.
8. Reinstall pump heater front shroud.
9. Reinstall ground wires.
10. Reinstall back pump heater shroud, and secure with screws.
64
109
58 82
FIG. 45: Replace Platen Heaters and RTD Sensor
4. Remove platen heater blocks (43).
a. Use a hex wrench to remove three nuts (59)
and washers (11, 64) from each heater block.
b. Remove screws (12) from junction box cover
(96). Loosen strain relief nut (91), and remove junction box cover.
c. Disconnect four platen heater wires (labeled A
dn B) and RTD sensor connector in the terminal box. See Electrical Schematics, page 61.
ti18061a
52 313296J
Page 53
d. Remove screws (58) and washers (82).
Remove platen heater blocks (43) and RTD sensor (46).
5. Install new platen heaters and RTD sensor. Secure RTD sensor with screw and washer. Secure platen heater blocks with nuts and washers.
Repair
324
323
6. Label platen heater wires A and B as shown on page 64. Reroute platen heater wires and platen RTD sensor through the conduit to the junction box. Reconnect the four wires to the appropriate terminal block A and B. Reconnect the platen RTD sensor.
7. Reinstall junction box cover. Secure with screws and tighten strain relief nut.
8. Reconnect ground wire, and install platen covers. Secure platen covers with fasteners. Torque platen cover fasteners to 60 in-lbs +/- 10 in-lbs (6.8 +/- 1.1 N•m)
9. Reconnect displacement pump using screws and clamps.
20, 30, and 60 Liter Platen Heater
1. Disconnect pump from platen.
2. Remove platen heater block (320).
a. Remove screws (278) from junction box cover
(271), and remove junction box cover. See page
86.
Air Fitting Assembly
ti17717b
F
IG
. 46: Replace Platen Heaters
3. Remove platen heater (319).
a. Disconnect two platen heater wires (labeled A
and B) in the terminal box. See D60 Junction Box Schematic, page 71.
b. Remove platen and heater (319).
320
319
318
309
b. Remove strain relief nut (265) from junction box
to allow space for wires. See page 86.
4. Install new platen heater (319) to lower heater plate (318). Install upper heater plate (320). Reconnect ground wire, and secure with screws.
c. Remove air fitting assembly from platen.
5. Label platen heater wires A and B as shown on
d. Remove nuts (309) from the heat shield guard
(324).
page page 70. Reroute platen heater wires through the conduit to the junction box. Reconnect the two wires to the appropriate terminal block A and B.
e. Remove screws (323) from upper heater plate
(320). Remove upper heater plate and ground
6. Reinstall heat shield guard. Secure with nuts. Torque nuts to 45 +/- 5 in-lbs (5.1 +/- 0.6 N•m).
wire.
7. Reconnect displacement pump using screws and clamps.
8. Reinstall junction box cover and strain relief nut. Secure cover with screws.
313296J 53
Page 54
Repair

Replace Platen Wipers

Refer to Supply Systems Repair-Parts manual for instructions.

Replace Ram Piston Rod Seals

1. Support electrical enclosure (13 or 14) using a loop and a hoist.
2. Remove screws from bracket (50 or 232) connect­ing electrical enclosure (13 or 14) to ram piston rod and cable track (42, if applicable).
42
13 or 14
50 or 232
FIG. 47: Replace Rod Seals
3.
For 55 gallon platen (D200 and D200s supply sys­tems):
(50) to side.
For smaller platens (D60 supply systems):
bracket (232).
Gently move cable track (42) and bracket
Remove
4. See Supply Systems Repair-Parts manual for replacement instructions.
5. Follow steps in reverse order to reinstall bracket, cable track (if applicable), and the electrical enclo­sure.
54 313296J
Page 55
Repair

Electrical Enclosure

Prior to repairing any component of the electrical enclo­sure (13 or 14), turn the main disconnect on the electri­cal control panel door to the OFF position to disconnect
power.
Replace Low Power Temperature Control Module(s)
1. Open enclosure door (402). Disconnect the follow-
Power is still connected to the power line filter (459) even after the main disconnect is open. Avoid con­tact with the power line filter.
ing cables from low power TCM (408):
incoming power supply cable (430)
outbound power supply cable (see F
RTD cable
IG
. 49)
408
Outbound Power
RTD
411
Outbound Power
RTD
FIG. 49: Back View of Electrical Enclosure
2. Loosen both captive screws (409) holding low power TCM (408) to base (407); remove low power TCM. See F
3. Follow steps in reverse order to install new low power TCM.
4. Upload the correct TCM software for the system. See Upgrade Temperature Control Module Soft- ware, page 56, for instructions.
IG
. 48.
459
Captive Screw
430
408
Captive Screw
411
431
429
428
432
F
IG
. 48: Internal View of Electrical Enclosure
313296J 55
Page 56
Repair
Replace Base
1. Remove low power TCM. See Replace Low Power Temperature Control Module(s).
2. Disconnect two CAN cables from base (407).
3. Remove four screws (409) and ground screw (410) from base.
4. Replace with new base and secure with screws.
5. Reconnect two CAN cables to base.
6. Set selector switch to:
“0” for TCM labeled “2” on Ram A
“1” for TCM labeled “3” on Ram A
“2” for TCM labeled “4” on Ram A
“5” for TCM labeled “2” on Ram B
“6” for TCM labeled “3” on Ram B
“7” for TCM labeled “4” on Ram B
Selector Switch
TI12361a
IG
. 50: Set Selector Switch
F
7. Reinstall low power TCM. See Replace Low Power Temperature Control Module(s).
NOTE: Reuse brackets (412, 413) to install new high power TCM.
6. Upload the correct TCM software from kit 16C027. See Upgrade Temperature Control Module Soft- ware, page 56, for instructions.
7. Remove cover of new high power TCM and set selector switch to “0” for Ram A or “1” for Ram B.
Selector Switch
TI12360a
IG
. 51: Set Selector Switch
F
Upgrade Temperature Control Module Software
NOTE: Order kit 16C027 for an upgrade token. See
Graco Control Architecture manual for instructions.
Module Programming
NOTE: Reuse brackets (412, 413) to install new high power TCM.
Replace High Power Temperature Control Module
1. Open enclosure door (402). Disconnect outbound power supply and RTD cables from high power TCM (411). See F
2. Remove electrical enclosure side panel (436). See Electrical Enclosure Parts on page 90.
3. Disconnect all four incoming cables (432, 428, 429,
431) from high power TCM. See F
4. Remove both screws (415) that secure brackets (412, 413) of high power TCM to electrical enclo­sure. Remove high power TCM. See Electrical Enclosure Parts on page 90.
5. Follow steps in reverse order to install new high power TCM.
IG
. 49.
IG
. 48.
56 313296J
Page 57
Repair
Replace Circuit Breakers
1. Open enclosure door (402). Disconnect wires from circuit breaker (417, 419).
2. Push in circuit breaker tab and pull out breaker.
417
4. Remove screws (12 or 202) and washers (11 or
201) from bottom bracket (39 or 222) and side bracket (50 or 232) of enclosure.
D200 Shown
plug
11 or 201, 12 or 202
50 or 232
13 or 14
419
417
F
IG
. 52: Circuit Breakers
3. Replace with new circuit breaker. Use tabs on bot­tom of breaker to select L2 and L3.
4. Snap new circuit breaker into place and reconnect wires.
Replace Electrical Enclosure
1. Ensure power to electrical enclosure is discon­nected.
2. Disconnect heater and RTD cables from each TCM.
3. Remove plug and use lift ring (not included) at top of electrical enclosure (13 or 14).
39 or 222
F
IG
. 53: Replace Electrical Enclosure
5. Lift enclosure off and replace with new enclosure.
6. Secure new electrical enclosure to bottom and side brackets with screws and washers.
7. Reconnect heater and RTD cables to each TCM.
8. Reconnect power to power line filter.
Have a qualified electrician reinstall main incoming power to system and electrical enclosure.
313296J 57
Page 58
Repair

Display/User Interface

Upgrade Display Software
NOTICE
To avoid damaging circuit board, wear a grounding strap.
NOTE: Order kit 16C027 for an upgrade token. See
Graco Control Architecture manual for instructions.
Replace Display
NOTE: Order Kit 24F493 for replacement. Software token 16C027 is required to install software before use.
NOTICE
To avoid damaging circuit board, wear a grounding strap.
Module Programming
1. Disconnect power.
2. Pull display (20) out of bracket (22) clips to remove it.
3. Disconnect CAN cable(s) from display (20).
4. Replace with new display. Reconnect CAN cable(s).
5. Load the correct display software for the system. Follow the steps in Upgrade Display Software on page 58.
NOTE: Token is not included with display and must be ordered separately.
58 313296J
Page 59

Replace Fluid Control Module

D
Repair
41 or 224
1. Disconnect power to system.
2. Remove front shroud (16 or 204) and back shroud (17 or 205).
200 Shown
16 or 204
Captive Screws
36 or 220
28 or 215
F
IG
. 55: Remove FCM
6. Replace with new FCM, and secure with screws.
7. Reconnect cables to FCM.
8. Load the correct FCM software for the system. Fol­low the steps in Upgrade FCM Software on page
59.
30 or 217
33 or 219
Replace Base
17 or 205
FIG. 54: Remove Shrouds
3. Disconnect all cables from FCM (36 or 220).
4. Remove access door (41 or 224).
5. Loosen both captive screws from FCM and pull FCM off base (33 or 219).
1. Disconnect power to system.
2. Remove FCM (36 or 220). See Replace Fluid Con- trol Module.
3. Disconnect CAN cable(s) from FCM (36 or 220).
4. Remove screws (28 or 215) and ground screw (30 or 217) from base (33 or 219). See F
5. Replace with new base, and secure with screws.
6. Reconnect CAN cable(s).
7. Set selector switch to “A” for Ram A or “B” for Ram B. See F
8. Reinstall FCM. See Replace Fluid Control Mod- ule.
IG
. 55.
IG
. 55.
Upgrade FCM Software
NOTE: Order kit 16C027 for an upgrade token. See
Graco Control Architecture manual for instructions.
Module Programming
313296J 59
Page 60
Repair

Replace Cable Track

D200 and D200S Supply Systems Only
NOTE: Order Kit 257163 for replacement.
1. Disconnect power to system.
2. Disconnect all 10 cables from back of electrical enclosure (13 or 14).
4. Remove screws (12) from junction box cover (96) and junction box (78).
5. Loosen strain relief nut (90), and remove junction box cover.
6. Disconnect all wires in junction box. Pull wires out of strain relief.
7. Remove mounting screws (71), washer (72), and nut (73) securing cable track assembly (42) to junc­tion box.
42
72 73
FIG. 56: Back View of Electrical Enclosure
3. Remove screws (71) from bracket (50) that connect cable track (42) to electrical enclosure (13 or 14)
and ram.
42
50
71
13 or 14
IG
. 57: Cable Track Bracket
F
61
71
96
91
90
F
IG
. 58: Junction Box
8. Lift out cable track assembly and cables.
9. Replace with new cable track kit. Secure new cable track to junction box using mounting screws.
10. Run wires through strain relief and reconnect all wires in junction box. See D200 Junction Box Schematic, page 65.
11. Reinstall strain relief nut and junction box cover. Secure junction box using screws.
12. Reattach cable track to bracket. Use screws to secure bracket holding cable track to electrical enclosure and ram.
13. Reconnect all 10 cables to back of electrical enclo­sure.
12
14. Reconnect power to system.
60 313296J
Page 61

Electrical Schematics

D200 Single Ram Schematic
(1) Power
(3) COM
(2) Unused
DRUM EMPTY
F
(1)
(3)
(4)
(2)
DRUM LOW or EMPTY OPTION
2
Cable Splitter
M
(1)
(4) SIGNAL
F
(2)
(3)
(1) Solenoid signal
(2) Solenoid RTN
(1)
(2)
3
(4)
(5)
P/N 121235
AIR SOLENOID
DRUM EMPTY
F
DRUM LOW and EMPTY OPTION
(2) Unused
(1) Power
(4) SIGNAL
(3) COM
DRUM LOW
(1)
(3)
(4)
(2)
Cable Splitter
M
(1)
(1) Power
(2) Unused
(1)
(2)
213
(2)
(3)
(3) COM
(3)
(4)
(4) SIGNAL
(4)
(5)
(1) Solenoid signal
F
(1)
AIR SOLENOID
(2) Solenoid RTN
(2)
Electrical Schematics
Warm Melt
Standard Ram
63A
Warm Melt Enclosure
GFCI
Line Filter
FLUID
Motor Pigtail
M
(1)
RAM A
MODULE
CONTROL
Cable 8 Pin
(2)
(3)
(4)
(5)
C/B
8 Amp
24 Vdc P/S
(2) N/C
(3) Motor Reed Up
(1) Linear Input
M
(1)
(2)
(3)
FM
(1)
(2)
(3)
(1)
(2)
(3)
MF
(1)
(1)
Sensor Reed Switch
Top Switch 1
(5) Motor Reed Com5(7) Linear Com
(4) Motor Reed Down
(6) Linear Power
(8) Drain
(4)
(5)
(6)
(7)
(4)
(5)
(6)
(7)
(4)
(5)
(6)
(7)
(2)
(3)
(4)
(2)
(3)
(4)
Top Switch 2
Bottom Switch 1
Bottom Switch 2
LPTCM
Power
Heater
3
(8)
(8)
(8)
8 Amp
Circuit
5
Heater
Power
Fluid Filter Monitor Option
Breaker
Cable
RTD
Input
2
Cable Splitter
(1)
(2)
(3)
Power (1)
Unused (2)
Common (3)
Fluid Pressure Sensor
Cable
LPTCM
7
M
Cable 15 Meter
MF
(4)
Press Signal (4)
Power
Heater
332
(1) Power
(2) Filter Inlet Press.
(3) Common
(4) Filter Outlet Press.
(1)
(2)
(3)
(4)
(5)
(1)
(2)
(3)
(4)
(1)
(2)
(3)
(4)
Fluid Pressure Sensor
8 Amp
Circuit
Breaker
Cable
5
Heater
Power
Fluid Solenoid
Depres/Recirc Option
F
Wire Harness
M
3
(5) Drain
(5) (5)
(1)
(2)
(3)
(4)
Power (1)
Unused (2)
Common (3)
Press Signal (4)
RTD
Input
(1) Signal
(1)
(1)
(2)
Drain (2)
Unused (1)
Cable
(2) Common
(GND) Unused
(2)
(3)
(3)
(4)
Signal (4)
Common (3)
Cable
AIR SOLENOID
F
M
(1)
1
Power (1)
(1) Solenoid signal
(2) Solenoid RTN
(1)
(2)
(5)
(2)
(3)
(4)
Common (3)
Low Sensor (2)
Air Solenoid (5)
Empty Sensor (4)
SHLD (1)
SHLD (1)
+24Vdc (2)
-24Vdc (3)
-24Vdc (3)
+24Vdc (2)
Ferrite Bead
CAN_L (5)
CAN_H (4)
CAN_H (4)
CAN_L (5)
Ferrite Bead
SHLD (1)
SHLD (1)
-24Vdc (3)
CAN_H (4)
CAN_L (5)
+24Vdc (2)
Module
Gateway
Gateway Option
Ferrite Bead
-24Vdc (3)
+24Vdc (2)
CAN_L (5)
CAN_H (4)
Light Tower Option
Light Tower
M
2
(1) Unused
(2) Amber
(1)
(2)
Amber (2)
Unused (1)
(3) Common
(4) Green
(3)
(4)
Green (4)
Common (3)
(5) Red
(5)
Red (5)
Fieldbus
BRAN
EM
CH
M
SW
I
T
E
DISPLAY
MODULE
LAY
I
SP
D
50A
8 Amp
Circuit
Breaker
Cable
5
LPTCM
Heater
Power
RTD
Input
Power
Heater
2
CONTACTOR
Circuit
25 Amp
Cable
Breaker
Cable
HPTCM
Cable
5
Heater
Power
DC
CONTROL
RTD
Input
Power
Heater
3
2
SHLD (1)
SHLD (1)
SHLD (1)
Cable
+24Vdc (2)
+24Vdc (2)
+24Vdc (2)
-24Vdc (3)
-24Vdc (3)
Cable
-24Vdc (3)
CAN_H (4)
CAN_L (5)
CAN_H (4)
CAN_L (5)
CAN_H (4)
CAN_L (5)
2
24 Vdc+
3
24 Rtn
Cable, Volex
J-BOX CABLE TRACK
Cable, Extension
Cable, Volex
Cable, Extension
Cable, Volex
Cable, Extension
Black
Cable,10AWG
Cable, Extension
GRN/YEL
Cable,10AWG
Cable, CAN
SHIELDED CABLE
BUSS BAR
KEY
t
HOSE
t
GUN
t
PUMP
t
PLATEN
313296J 61
Page 62
Electrical Schematics

D200 Ram A Schematic

FLUID
RAM A
MODULE
CONTROL
(2) N/C
(3) Motor Reed Up
(5) Motor Reed Com5(7) Linear Com
(1) Linear Input
(4) Motor Reed Down
(6) Linear Power
(8) Drain
M
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
FM
(5)
(6)
(7)
(8)
(1)
(2)
(3)
(4)
Cable 8 Pin
(5)
(6)
(7)
(8)
(1)
(2)
(3)
(4)
Fluid Filter Monitor Option
Ram “A”
Warm Melt
Motor Pigtail
MF
M
(1)
(2)
(3)
(1)
(2)
(3)
(4)
(4)
(5)
(1)
(2)
(3)
(4)
Sensor Reed Switch
Top Switch 1
Top Switch 2
Bottom Switch 1
Bottom Switch 2
Fluid Pressure Sensor
Cable Splitter
(1)
(2)
Power (1)
Unused (2)
Cable 15 Meter
(3)
(4)
Common (3)
Press Signal (4)
7
(1) Power
(2) Filter Inlet Press.
M
(1)
(2)
(1)
(2)
MF
(1)
(2)
Fluid Pressure Sensor
Depres/Recirc Option
(3) Common
(4) Filter Outlet Press.
(5) Drain
(3)
(4)
(5)
(3)
(4)
(3)
(4)
(5) (5)
(1)
(2)
Power (1)
Unused (2)
Fluid Solenoid
Wire Harness
(3)
(4)
Common (3)
Press Signal (4)
AIR SOLENOID
DRUM EMPTY
(2) Unused
(1) Power
(4) SIGNAL
(3) COM
F
(1)
(3)
(4)
(2)
DRUM LOW and EMPTY OPTION
(1) Solenoid signal
(2) Solenoid RTN
(2) Unused
(1) Power
(4) SIGNAL
(3) COM
DRUM LOW
F
(1)
(3)
(4)
(2)
(1)
(2)
Cable Splitter
213
M
(1)
(2)
(3)
(4)
(5)
“B”
To Ram
Option
|OR|
(2) Unused
(1) Power
(4) SIGNAL
(3) COM
DRUM EMPTY
F
(2)
(1)
(3)
(4)
(1) Solenoid signal
Cable Splitter
M
1
2
(1)
(2)
Power (1)
Low Sensor (2)
F
(1)
3
(5)
(3)
(4)
Common (3)
Empty Sensor (4)
(2) Solenoid RTN
AIR SOLENOID
(2)
Air Solenoid (5)
SHLD (1)
SHLD (1)
+24Vdc (2)
+24Vdc (2)
-24Vdc (3)
-24Vdc (3)
Ferrite Bead
CAN_L (5)
CAN_H (4)
CAN_H (4)
CAN_L (5)
Ferrite Bead
SHLD (1)
SHLD (1)
-24Vdc (3)
CAN_H (4)
CAN_L (5)
+24Vdc (2)
Module
Gateway
Gateway Option
Ferrite Bead
+24Vdc (2)
-24Vdc (3)
Ferrite Bead
CAN_L (5)
CAN_H (4)
Light Tower
(1) Unused
(2) Amber
(3) Common
(4) Green
(1) Signal
(2) Common
(GND) Unused
(3)
(3)
(4)
Signal (4)
Common (3)
Light Tower Option
F
(1)
(2)
M
(1)
(2)
3
Drain (2)
Unused (1)
(5) Red
(5)
M
(1)
(2)
(3)
(4)
Red (5)
2
Green (4)
Amber (2)
Unused (1)
Common (3)
Fieldbus
C
BR
EM
SW
I
H
T
M
E
DISPLAY
MODULE
AN
I
SPL
D
AY
SHLD (1)
SHLD (1)
Cable
+24Vdc (2)
+24Vdc (2)
-24Vdc (3)
-24Vdc (3)
CAN_H (4)
CAN_L (5)
CAN_H (4)
CAN_L (5)
2
24 Vdc+
3
24 Rtn
63A
GFCI
Warm Melt Enclosure
Line Filter
8 Amp
24 Vdc P/S
50A
C/B
8 Amp
Circuit
Breaker
Cable
5
LPTCM
Heater
Power
RTD
Input
Power
Heater
3
2
Cable, Volex
Cable, Extension
8 Amp
Circuit
Breaker
Cable
Cable
5
LPTCM
Heater
Power
RTD
Input
Power
Heater
332
Cable, Volex
Cable, Extension
8 Amp
Circuit
Breaker
Cable
Cable
5
LPTCM
Heater
Power
RTD
Input
Power
Heater
2
Cable, Volex
Cable, Extension
J-BOX CABLE TRACK
CONTACTOR
Circuit
25 Amp
Cable
DC
P/N 255774
Heater
3
Black
Cable,10AWG
Power
CONTROL
Breaker
5
Heater
Power
RTD
Input
2
Cable, Extension
Cable
GRN/YEL
Cable,10AWG
SHLD (1)
Cable, CAN
Cable
-24Vdc (3)
+24Vdc (2)
CAN_H (4)
CAN_L (5)
SHIELDED CABLE
BUSS BAR
Cable
HPTCM
KEY
t
HOSE
t
GUN
t
PUMP
t
PLATEN
62 313296J
Page 63
Electrical Schematics

D200 Ram B Schematic

Warm Melt
Ram “B” Option
63A
GFCI
Cable
Warm Melt Enclosure
Line Filter
J-BOX CABLE TRACK
LPTCM
Power
Heater
3
Cable, Volex
50A
CONTACTOR
Circuit
25 Amp
8 Amp
Circuit
Breaker
Cable
5
Heater
Power
RTD
Input
2
Cable, Extension
8 Amp
Circuit
LPTCM
Power
Heater
332
Cable, Volex
Heater
Breaker
5
Power
Cable
RTD
Input
Cable, Extension
Cable
t
HOSE
8 Amp
Circuit
Breaker
Heater
Cable
5
Power
RTD
Input
2
Cable, Extension
Cable
HPTCM
Cable,10AWG
Cable
LPTCM
Power
Heater
Cable, Volex
t
PUMP
Breaker
5
Heater
Power
RTD
Input
2
Cable, Extension
Cable
GRN/YEL
Cable,10AWG
SHLD (1)
-24Vdc (3)
+24Vdc (2)
CAN_H (4)
CAN_L (5)
Cable, CAN
Cable
Cable
4
DC
Control
Power
Heater
3
Black
t
PLATEN
t
GUN
DRUM LOW and EMPTY OPTION
DRUM LOW
(1)
Cable Splitter
DRUM EMPTY
(1) Power
(2) Unused
(2)
F
(3) COM
(3)
M
(1) Power
(1)
(4) SIGNAL
(4)
(1)
(2) Unused
(2)
213
(2)
(3)
(3) COM
(3)
(4)
(4) SIGNAL
(4)
F
(5)
AIR SOLENOID
(1) Solenoid signal
(2) Solenoid RTN
(1)
(2)
(2) Unused
(1) Power
(4) SIGNAL
(3) COM
DRUM EMPTY
F
(1)
(3)
(4)
(2)
(1) Solenoid signal
(2) Solenoid RTN
Cable Splitter
M
1
2
(1)
(2)
Power (1)
Low Sensor (2)
F
(1)
3
(3)
(4)
(5)
Common (3)
Air Solenoid (5)
Empty Sensor (4)
(2)
AIR SOLENOID
SHLD (1)
SHLD (1)
-24Vdc (3)
+24Vdc (2)
-24Vdc (3)
+24Vdc (2)
CAN_L (5)
CAN_H (4)
CAN_H (4)
CAN_L (5)
Ferrite Bead
Cable, CAN 15m
SHIELDED CABLE
BUSS BAR
KEY
FLUID
CONTROL
Motor Pigtail
M
(1)
RAM “B”
MODULE
Cable 8 Pin
(2)
(3)
(4)
(5)
5
M
FM
(2) N/C
(3) Motor Reed Up
(1) Linear Input
(1)
(2)
(3)
(1)
(2)
(3)
(1)
(2)
(3)
(1)
MF
(1)
Top Switch (1)
(5) Motor Reed Com
(4) Motor Reed Down
(6) Linear Power
(8) Drain
(7) Linear Com
(4)
(5)
(6)
(7)
(8)
(4)
(5)
(6)
(7)
(8)
(4)
(5)
(6)
(7)
(8)
(2)
(3)
(4)
(2)
(3)
(4)
Sensor Reed Switch
Top Switch (2)
Bottom Switch (1)
Bottom Switch (2)
Fluid Solenoid
Depress/Recirc Option
Wire Harness
M
3
F
(1) Signal
(1)
(1)
(2)
Drain (2)
Unused (1)
(2) Common
(GND) Unused
(2)
(3)
(3)
(4)
Signal (4)
Common (3)
To Ram “A”
313296J 63
Page 64
Electrical Schematics

D200 Displacement Pump and Platen Schematics

Platen
Displacement Pump
64 313296J
Page 65

D200 Junction Box Schematic

Electrical Schematics
313296J 65
Page 66
Electrical Schematics

D200 Cable Track Schematic

66 313296J
Page 67

D60 Single Ram Schematic

(2) Unused
(1) Power
(3) COM
DRUM EMPTY
F
(2)
(1)
(3)
DRUM LOW or EMPTY OPTION
2
Cable Splitter
M
(1)
(4) SIGNAL
(4)
(2)
(1) Solenoid signal
F
(1)
3
(3)
(4)
(5)
(2) Solenoid RTN
AIR SOLENOID
(2)
DRUM EMPTY
(1) Power
F
(1)
DRUM LOW and EMPTY OPTION
(2) Unused
(1) Power
(4) SIGNAL
(3) COM
DRUM LOW
(1)
(3)
(4)
(2)
Cable Splitter
M
(1)
(2) Unused
(3)
(2)
213
(2)
(3)
(3) COM
(4)
(4) SIGNAL
(4)
(5)
(1) Solenoid signal
F
(1)
AIR SOLENOID
(2) Solenoid RTN
(2)
Electrical Schematics
Motor Pigtail
Warm Melt
D60 Standard Ram
63A
GFCI
Warm Melt Enclosure
Line Filter
FLUID
CONTROL
M
(1)
(2)
8 Amp
24 Vdc P/S
RAM A
MODULE
(3)
(4)
(5)
C/B
Cable 8 Pin
(2) N/C
(3) Motor Reed Up
(1) Linear Input
M
(1)
(2)
(3)
FM
(1)
(2)
(3)
(1)
(2)
(3)
MF
(1)
(1)
Sensor Reed Switch
Top Switch 1
(5) Motor Reed Com5(7) Linear Com
(4) Motor Reed Down
(6) Linear Power
(8) Drain
(4)
(5)
(6)
(7)
(5)
(6)
(7)
(4)
(5)
(6)
(7)
(4)
(2)
(3)
(4)
(2)
(3)
(4)
Top Switch 2
Bottom Switch 1
Bottom Switch 2
LPTCM
Power
Heater
3
(8)
(8)
(8)
8 Amp
Circuit
5
Heater
Power
Fluid Filter Monitor Option
Breaker
Cable
RTD
Input
2
Cable Splitter
(1)
(2)
(3)
Power (1)
Unused (2)
Common (3)
Fluid Pressure Sensor
Cable
LPTCM
7
M
Cable 15 Meter
MF
(4)
Press Signal (4)
Power
Heater
332
(1) Power
(2) Filter Inlet Press.
(3) Common
(4) Filter Outlet Press.
(1)
(2)
(3)
(4)
(5)
(1)
(2)
(3)
(4)
(1)
(2)
(3)
(4)
Fluid Pressure Sensor
8 Amp
Circuit
Breaker
Cable
5
Heater
Power
Fluid Solenoid
Depres/Recirc Option
F
Wire Harness
M
3
(5) Drain
(5) (5)
(1)
(2)
(3)
(4)
Power (1)
Unused (2)
Common (3)
Press Signal (4)
RTD
Input
(1) Signal
(1)
(1)
(2)
Drain (2)
Unused (1)
Cable
(2) Common
(GND) Unused
(2)
(3)
(3)
(4)
Signal (4)
Common (3)
Light Tower Option
Light Tower
M
2
(1) Unused
(1)
(2)
Amber (2)
Unused (1)
(2) Amber
(3)
Common (3)
(3) Common
(4) Green
(5) Red
(5)
(4)
Red (5)
Green (4)
AIR SOLENOID
(1) Solenoid signal
(2) Solenoid RTN
F
(1)
(2)
Cable
SHLD (1)
SHLD (1)
+24Vdc (2)
-24Vdc (3)
-24Vdc (3)
+24Vdc (2)
Ferrite Bead
CAN_L (5)
CAN_H (4)
CAN_H (4)
CAN_L (5)
Ferrite Bead
SHLD (1)
SHLD (1)
-24Vdc (3)
CAN_H (4)
CAN_L (5)
+24Vdc (2)
Module
Gateway
Gateway Option
Ferrite Bead
-24Vdc (3)
+24Vdc (2)
CAN_L (5)
CAN_H (4)
(5)
M
(1)
(2)
(3)
(4)
1
Power (1)
Common (3)
Low Sensor (2)
Air Solenoid (5)
Empty Sensor (4)
Fieldbus
BRAN
EM
CH
M
SW
I
T
E
DISPLAY
MODULE
LAY
I
SP
D
50A
8 Amp
Circuit
Breaker
Cable
5
LPTCM
Heater
Power
RTD
Input
Power
Heater
2
CONTACTOR
Circuit
25 Amp
Cable
Breaker
Cable
HPTCM
Cable
5
Heater
Power
DC
CONTROL
RTD
Input
Power
Heater
3
2
SHLD (1)
SHLD (1)
SHLD (1)
Cable
-24Vdc (3)
+24Vdc (2)
-24Vdc (3)
+24Vdc (2)
Cable
-24Vdc (3)
+24Vdc (2)
CAN_H (4)
CAN_L (5)
CAN_H (4)
CAN_L (5)
CAN_H (4)
CAN_L (5)
2
24 Vdc+
3
24 Rtn
Cable, Volex
J-BOX CABLE HARNESS
Cable, Extension
Cable, Volex
Cable, Extension
Cable, Volex
Cable, Extension
Black
Cable,10AWG
Cable, Extension
GRN/YEL
Cable,10AWG
Cable, CAN
SHIELDED CABLE
BUSS BAR
KEY
t
HOSE
t
GUN
t
PUMP
t
PLATEN
313296J 67
Page 68
Electrical Schematics

D60 Ram A Schematic

FLUID
RAM A
MODULE
CONTROL
(2) N/C
(3) Motor Reed Up
(5) Motor Reed Com5(7) Linear Com
(1) Linear Input
(4) Motor Reed Down
(6) Linear Power
(8) Drain
M
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
FM
(5)
(6)
(7)
(8)
(1)
(2)
(3)
(4)
Cable 8 Pin
(5)
(6)
(7)
(8)
(1)
(2)
(3)
(4)
Fluid Filter Monitor Option
Warm Melt
D60 Ram “A”
Motor Pigtail
M
MF
(1)
(2)
(3)
(5)
(1)
(2)
(3)
Sensor Reed Switch
Top Switch 1
Top Switch 2
Bottom Switch 1
(4)
(4)
Bottom Switch 2
(1)
(2)
(3)
(4)
Cable Splitter
Fluid Pressure Sensor
(1)
(2)
Power (1)
Unused (2)
7
M
Cable 15 Meter
MF
(3)
(4)
Common (3)
Press Signal (4)
(1) Power
(2) Filter Inlet Press.
(3) Common
(4) Filter Outlet Press.
(1)
(2)
(3)
(4)
(1)
(2)
(3)
(4)
(1)
(2)
(3)
(4)
Fluid Pressure Sensor
Fluid Solenoid
Depres/Recirc Option
F
Wire Harness
M
(1)
3
Unused (1)
(5) Drain
(5)
(5) (5)
(1)
(2)
(3)
(4)
Power (1)
Unused (2)
Common (3)
Press Signal (4)
(1) Signal
(2) Common
(1)
(2)
(2)
Drain (2)
(GND) Unused
(3)
(3)
(4)
Signal (4)
Common (3)
Light Tower Option
DISPLAY
MODULE
Light Tower
M
2
(1) Unused
(2) Amber
(1)
(2)
Amber (2)
Unused (1)
(3) Common
(4) Green
(3)
(4)
Green (4)
Common (3)
DRUM LOW and EMPTY OPTION
DRUM LOW
Cable Splitter
(5) Red
(5)
Red (5)
BRAN
E
M
E
M
I
SPL
D
DRUM EMPTY
F
(2) Unused
(1) Power
(3) COM
(1)
(3)
(2)
M
(1) Power
DRUM EMPTY
F
(1)
Cable Splitter
CH
SW
I
T
AY
(1) Power
(1)
(4) SIGNAL
(4)
(1)
(2)
(2) Unused
(3) COM
(3)
(2)
M
1
Power (1)
(4) SIGNAL
(3) COM
(2) Unused
(3)
(4)
(2)
213
(3)
(4)
(5)
(4) SIGNAL
(4)
F
2
(1)
(2)
(3)
(4)
Common (3)
Low Sensor (2)
Empty Sensor (4)
AIR SOLENOID
(1) Solenoid signal
(2) Solenoid RTN
F
(1)
(2)
(1) Solenoid signal
(2) Solenoid RTN
AIR SOLENOID
(1)
(2)
3
(5)
Air Solenoid (5)
SHLD (1)
SHLD (1)
SHLD (1)
SHLD (1)
+24Vdc (2)
-24Vdc (3)
-24Vdc (3)
+24Vdc (2)
Cable
-24Vdc (3)
+24Vdc (2)
-24Vdc (3)
+24Vdc (2)
To Ram
|OR|
Ferrite Bead
CAN_L (5)
CAN_H (4)
CAN_H (4)
CAN_L (5)
Ferrite Bead
CAN_H (4)
CAN_L (5)
CAN_H (4)
CAN_L (5)
“B”
Option
Ferrite Bead
SHLD (1)
SHLD (1)
CAN_L (5)
-24Vdc (3)
-24Vdc (3)
CAN_H (4)
CAN_L (5)
Module
Gateway
+24Vdc (2)
+24Vdc (2)
CAN_H (4)
Gateway Option
Ferrite Bead
Fieldbus
2
24 Vdc+
3
24 Rtn
50A
CONTACTOR
Circuit
25 Amp
Cable
HPTCM
Cable,10AWG
Breaker
Cable
Cable
Cable
5
Heater
Power
DC
CONTROL
RTD
Input
Power
Heater
3
2
Black
Cable, Extension
GRN/YEL
Cable,10AWG
+24Vdc (2)
SHLD (1)
Cable, CAN
-24Vdc (3)
CAN_H (4)
CAN_L (5)
SHIELDED CABLE
BUSS BAR
63A
GFCI
Warm Melt Enclosure
Line Filter
C/B
8 Amp
24 Vdc P/S
LPTCM
Cable, Volex
J-BOX CABLE TRACK
8 Amp
Circuit
Breaker
Cable
5
Heater
Power
RTD
Input
Power
Heater
3
2
Cable, Extension
8 Amp
Circuit
LPTCM
Cable, Volex
5
Heater
Power
Power
Heater
332
Breaker
Cable
RTD
Cable, Extension
Input
Cable
8 Amp
Circuit
LPTCM
Heater
Cable, Volex
Breaker
Cable
5
Heater
Power
RTD
Input
Power
2
Cable, Extension
Cable
KEY
t
HOSE
t
GUN
t
PUMP
t
PLATEN
68 313296J
Page 69
D60 Ram B
Electrical Schematics
Schematic
Warm Melt
D60 Ram “B” Option
63A
GFCI
Cable
Warm Melt Enclosure
Line Filter
J-BOX CABLE TRACK
LPTCM
Cable, Volex
50A
CONTACTOR
Circuit
25 Amp
8 Amp
Circuit
Breaker
Cable
5
Heater
Power
RTD
Input
Power
Heater
3
2
Cable, Extension
8 Amp
Circuit
Breaker
Cable
LPTCM
Cable, Volex
Heater
Power
Heater
332
Cable
5
Power
Cable, Extension
RTD
Input
t
HOSE
8 Amp
Circuit
Breaker
5
Heater
Power
Cable, Extension
Cable
Cable
HPTCM
RTD
Input
2
Cable,10AWG
Cable
LPTCM
Power
Heater
Cable, Volex
t
PUMP
Breaker
Cable
Cable
4
DC
Control
Power
Heater
3
Black
Cable, Extension
Cable
5
Heater
Power
RTD
Input
2
GRN/YEL
Cable,10AWG
SHLD (1)
-24Vdc (3)
+24Vdc (2)
CAN_H (4)
CAN_L (5)
Cable, CAN
t
PLATEN
t
GUN
DRUM LOW and EMPTY OPTION
DRUM LOW
Cable Splitter
(1) Power
(1)
(2) Unused
(2)
DRUM EMPTY
(1) Power
F
(1)
(4) SIGNAL
(3) COM
(3)
(4)
M
(1)
(2) Unused
(3) COM
(3)
(2)
213
(2)
(3)
(4)
(4) SIGNAL
(4)
F
(5)
AIR SOLENOID
(1) Solenoid signal
(2) Solenoid RTN
(1)
(2)
(2) Unused
(1) Power
(4) SIGNAL
(3) COM
DRUM EMPTY
F
(1)
(3)
(4)
(2)
(1) Solenoid signal
(2) Solenoid RTN
Cable Splitter
M
1
2
(1)
(2)
Power (1)
Low Sensor (2)
F
(1)
3
(3)
(4)
(5)
Common (3)
Air Solenoid (5)
Empty Sensor (4)
(2)
AIR SOLENOID
SHLD (1)
SHLD (1)
-24Vdc (3)
+24Vdc (2)
-24Vdc (3)
+24Vdc (2)
CAN_L (5)
CAN_H (4)
CAN_H (4)
CAN_L (5)
Ferrite Bead
Cable, CAN 15m
SHIELDED CABLE
BUSS BAR
KEY
FLUID
CONTROL
Motor Pigtail
M
(1)
RAM “B”
MODULE
(2)
(3)
(4)
(5)
Cable 8 Pin
5
M
FM
(2) N/C
(3) Motor Reed Up
(1) Linear Input
(1)
(2)
(3)
(1)
(2)
(3)
(1)
(2)
(3)
(1)
MF
(1)
Top Switch (1)
(5) Motor Reed Com
(4) Motor Reed Down
(6) Linear Power
(8) Drain
(7) Linear Com
(4)
(5)
(6)
(7)
(8)
(4)
(5)
(6)
(7)
(8)
(4)
(5)
(6)
(7)
(8)
(2)
(3)
(4)
(2)
(3)
(4)
Sensor Reed Switch
Top Switch (2)
Bottom Switch (1)
Bottom Switch (2)
Fluid Solenoid
Depress/Recirc Option
Wire Harness
M
3
F
Unused (1)
(1)
(1) Signal
(1)
(2) Common
(2)
(2)
(3)
Drain (2)
Common (3)
(GND) Unused
(3)
(4)
Signal (4)
To Ram “A”
313296J 69
Page 70
Electrical Schematics

D60 Pump and Platen Schematic

70 313296J
Page 71

D60 Junction Box Schematic

Electrical Schematics
313296J 71
Page 72
Electrical Schematics

D60 Cable Harness Schematic

72 313296J
Page 73

Electrical Enclosure Schematic

Electrical Schematics
4-Zone Medium Enclosure
313296J 73
Page 74
Electrical Schematics

Electrical Enclosure Schematic

4-Zone RAM ‘B’ Enclosure
74 313296J
Page 75
Electrical Schematics
313296J 75
Page 76

Parts

Parts
D200s Rams Shown
Single Supply System or Supply System A
5
13
3
6
4
Supply System B
5
14
7
7
15
16
3
2
4
76 313296J
6
2
Page 77
Parts
NOTE: See Component Identification, starting on page 8, to identify the components included in your Warm Melt supply system.
Ref. Part Description Qty.
2 RAM ASSEMBLY, D60, 3 in. 1
RAM ASSEMBLY, D60i, 3 in. 1 RAM ASSEMBLY, D200s, 6.5 in. 1 RAM ASSEMBLY, D200si, 6.5 in. 1 RAM ASSEMBLY, D200, 3 in. 1 RAM ASSEMBLY, D200i, 3 in. 1
3 PUMP, Check-Mate; see manual
312375 for parts
4 24D066 PLATEN, 20 liter, double wiper, cst,
polyurethane
24D069 PLATEN, 20 liter, double wiper, sst,
polyurethane
24D067 PLATEN, 30 liter, double wiper, cst,
polyurethane
24D070 PLATEN, 30 liter, double wiper, sst,
polyurethane
24D068 PLATEN, 60 liter, double wiper, cst,
polyurethane
24D071 PLATEN, 60 liter, double wiper, sst,
polyurethane
257748 PLATEN, 55 gal., PTFE-coated o-ring,
EPDM 257749 PLATEN, 55 gal., o-ring, EPDM 1 257750 PLATEN, 55 gal., o-ring, neoprene 1
5 257623 KIT, mounting, pump; 3 in.; 20 liter; for
NXT 2200 air motors 257624 KIT, mounting, pump; 3 in.; 20 liter; for
NXT 3400 and 6500 air motors 255305 KIT, mounting, pump; 3 in.; 55 gal. 1 255315 KIT, mounting, pump; 6.5 in.; 55 gal. 1
6 255392 KIT, mounting; Check-Mate pump 1 7 VALVE, safety relief; located out of
view, on back side of air controls 103347 For systems with pumps: P23xxx or
P36xxx 108124 For systems with pumps: P68xxx
Ref. Part Description Qty.
ENCLOSURE, electrical (see Electrical Enclosure Parts, page 90)
13 257158 For single systems and Ram A 1 14 257291 For Ram B 1 15 KIT, warm melt, with display (see Warm
Melt Kits for D200 Systems, page 78, or Warm Melt Kits for D60 Systems,
page 83) 24D009 D60, Ram, WMxxxx Models 1 24D010 D60, Ram A, TWxxxx Models 1
1
1
1
1
1
1
1
1
24D012 D200, 3 in. Ram, WMxxxx Models 1 24D013 D200, 3 in. Ram A, TWxxxx Models 1 24D015 D200, 6.5 in. Ram, WMxxxx Models 1 24D016 D200, 6.5 in. Ram A, TWxxxx Models 1
16 KIT, warm melt, with no display (see
Warm Melt Kits for D200 Systems,
page 78, or Warm Melt Kits for D60
24D011 D60, Ram B, TWxxxx Models 1 24D014 D200, 3 in. Ram B, TWxxxx Models 1 24D017 D200, 6.5 in. Ram B, TWxxxx Models 1
See Supply Systems Repair-Parts manual for parts.
Systems, page 83)
Stainless Steel Ram Conversion Kits
For converting carbon steel Ram to stainless steel.
1
24K670 D60, Ram, WMxxxx Models
1
24K671 D60, Ram A, TWxxxx Models 24K673 D60, Ram B, TWxxxx Models 24K675 D200, 3 in. Ram, WMxxxx Models 24K676 D200, 3 in. Ram A, TWxxxx Models 24K677 D200, 3 in. Ram B, TWxxxx Models
1
24K678 D200, 6.5 in. Ram, WMxxxx Models 24K679 D200, 6.5 in. Ram A, TWxxxx Models 24K680 D200, 6.5 in. Ram B, TWxxxx Models
313296J 77
Page 78
Parts

Warm Melt Kits for D200 Systems

Kit 24D012 (CST), 24K675 (SST) with Display for D200 and D200i Systems Kit 24D015 (CST), 24K678 (SST) with Display for D200s and D200si Systems Kit 24D013 (CST), 24K676 (SST) with Display for Ram A of Tandem D200 and D200i Systems Kit 24D014 (CST), 24K677 (SST) without Display for Ram B of Tandem D200 and D200i Systems Kit 24D016 (CST), 24K679 (SST) with Display for Ram A of Tandem D200s and D200si Systems Kit 24D017 (CST), 24K680 (SST) without Display for Ram B of Tandem D200s and D200si Systems
Kit 24D016 Shown
16
22
36
20
24
41
33
21
47
12
66
81
11
23
105
27
26
19
65
60
15
32
37
12
35
13
14
50
71, 72, 73
11
18
34
11
12
28
30
76
75
78 313296J
17
r_wm_2179_313296_5a
Page 79
42
72, 73
Parts
78
61, 62
80
54
86
52
101
88
83, 84, 85
11, 12
39
11, 26, 58, 59
40
101
71
53
TI19984a
313296J 79
Page 80
Parts
45, 79
46
107(x2), 108(x2), 110
44
51
87
1
Torque to 60 +/- 10 in-lbs (6.8 +/- 1.1 N•m)
49
103c
103a
103b
57, 99
70
68, 69, 97, 98
ti17719a
63
59
1
43
107
11
64
108
109
48
57, 97, 100, 102
46, 56, 82
80 313296J
ti17718a
Page 81
Parts
116
101
117
59
90
11
59
11
89
112
91
68, 97, 98
95
1159
113
93
94
92
UBFB
D200 Warm Melt Kits
Ref. Part Description Qty.
11 100016 WASHER, lock 29 12 121112 SCREW, cap, sch 15 13 115827 SCREW, cap, hex hd; 7/16-14
unc 14 15X270 WASHER, top hat 1 15 15G347 SUPPORT, hose hanger 1 16 COVER, shroud front 1
†277589 - for 3 in. Ram
277591 - for 6.5 in. Ram
17 COVER, shroud rear 1
†277590 - for 3 in. Ram
277592 - for 6.5 in. Ram 1
18 BRACKET, light tower 1
†255383 - for 3 in. Ram
15R108 - for 6.5 in. Ram 19 100696 WASHER, plain 2 20✿■ 24F493 MODULE, display 1 21✿✓ BRACKET, pendant pivot 1 22✿✓ BRACKET, mounting, assy 1 23✿✓ SCREW, cap, sch; 1/4-20 unc 1 24 102040 NUT, lock, hex 1 25 ‡123328 CABLE, splitter, FCM,
empty/air 15X968 CABLE, FCM, low/hi/air 1 16C377 CABLE, M12, DIN 1
26 110755 WASHER, plain 5 27 121253 KNOB, display 1 28 114417 SCREW, self tap, pan hd 4
Ref. Part Description Qty.
29 SUPPRESSOR, ferrite bead 1 30 121070 SCREW, machine; #8-32 x 1
3/8
31 CABLE, CAN, female/female;
1
0.5 m 121001 121228 Kits 24D014 and 24D017 only
32 101213 NUT, full, hex 1 33 289697 MODULE, cube, base 1 34*‡122716 SENSOR, inductive, M12 1 35*‡ BRACKET, sensor, low/empty 1 36 289696 MODULE, fluid control 1 37*‡ ACTUATOR, sensor,
low/empty
39 BRACKET, mounting, bottom 1
- for 3 in. Ram
◆✠ - for 6.5 in. Ram
40 BRACKET, mounting 1
- for 3 in. Ram
◆✠
- for 6.5 in. Ram
41 277674 ENCLOSURE, cube door 1 42 257163 CABLE, track 1 43 CONDUCTOR, block, heater 2
1
44✛✓★ 121980 HEATER, pump, 725 watt 2 45✛★ 16J890 SUPPORT, sensor 1 46●✛✓✖16D383 SENSOR, RTD, shielded 2
47 119832 BOLT, eye, 3/8-14 x 6 1 48●✓ 15V427 HEATER, coil 2
1
1
1
313296J 81
Page 82
Parts
Ref. Part Description Qty.
49◗●✓✖ COVER, platen front, assy. 2 50 BRACKET, mounting, top 1
- 3 in. Ram
◆✠ - 6.5 in. Ram 51✛✓ ★ 15W706 ENCLOSURE, pump, front 1 52✛✓ ★ 15W707 ENCLOSURE, pump, rear 1 53 CONDUIT; 12.9 mm 4 54 COUPLER, conduit 4 56 117026 SCREW, shcs; m5 x 12 1 57✓★ 116343 SCREW, ground 2 58 SCREW, cap, hex hd 4
100014 - for 3 in. ram
100058 - for 6.5 in. ram 59 100015 NUT, hex mscr 12 60 100133 WASHER, flat 2 61 C19837 SCREW, cap, hex hd 2 62 STUD, 3/8-16 x 1.25 6 63◗● PLUG, finishing; 13/16 in.,
nickel plated 64 176692 WASHER, flat 6 65 100307 NUT, hex 2 66 C34132 HANGER 1 67 15Y051 CABLE, M12 1 68 123507 WIRE, grounding 1 69 16H441 WIRE, grounding 1 70◗● FASTENER, platen, cover 2 71 120223 SCREW, machine, flat hd 4 72 100020 WASHER, lock 4 73 100179 NUT, hex mscr 4 74 111218 CAP, tube 1 75 COVER 1 76 121255 SCREW, countersunk; 6-32 x
0.38 78 16M941 BRACKET, cable and rack 1 79 C31012 CLAMP 1 80 110637 SCREW, machine, pan hd 4 81 119958 SPRING, hose hanger 1 82 110170 WASHER 1 83 O-RING 1 84 CONNECTOR, power, female,
3 pin 85 COVER, connector 1 86 15J075 LABEL, warning 2 87 15H668 LABEL, warning 1 89 RAIL, din, assy. 1 90 BUSHING, strain relief; m40 1 91 NUT, strain relief; m40 1 92 24B810 CONNECTOR, bulkhead; 15
pin 93 113970 SCREW, socket hd cap 4 94 C19208 WASHER, lock 4 95 102794 NUT, hex 4 97 111640 WASHER, lock 6 98 100166 NUT, full hex 5 99 16A355 WIRE, ground, pump 1 100✓✖ 16A356 WIRE, ground, platen 1 101 196548 LABEL, caution 1 102✓✖ 16A574 WIRE, ground 4
Ref. Part Description Qty.
103 255392 KIT, mounting, displacement
pump 103a 102637 SCREW, cap 4 103b 276025 CLAMP 4 103c 109495 O-RING 1
104 STUD 6 106 15Y051 CABLE 1 107 124131 SCREW 4 108 103187 WASHER, lock 4 109✓★ 15B137 SWITCH, thermal 1 110✓★ 16K094 SWITCH, overtemp, horizontal 1 111 114958 STRAP TIE 7 112 16A539 JUNCTION BOX 1 113 16A543 BRACKET 1 114 299653 SHRINK TUBE 1 115 C33037 TAPE, fiberglass 1 116 112788 SCREW 4
1
117 16A541 COVER, junction box 1
Not shown.
Replacement Danger and Warning labels, tags, and cards are available at no cost.
Kit 24D012 only.
Kit 24D015 only.
Kits 24D013 and 24D016 only in tandem supply sys­tems.
Parts included in Hose Hanger Kit 234966 (purchase separately).
2
Parts included in Low or Empty Sensor Kit 255469 (pur­chase separately).
Parts included in Drum Low and Empty Sensor Kit 24C530 (purchase separately).
Parts included in 3 in. Ram Bracket Mounting Kit 24C628 (purchase separately).
1
1
Parts included in 6.5 in. Ram Bracket Mounting Kit 24C660 (purchase separately).
Parts included in Platen Heater Kit 24C493 (purchase separately).
Parts included in Pump Heater Kit 24C495 (purchase separately).
Parts included in Platen Cover Kit 255691 (purchase separately).
Parts only available in Display Mounting Kit 24C653 (purchase separately).
Parts only available in Cover Connector Kit 256883 (purchase separately).
Replacement electronic components do not have Warm Melt specific software installed. Therefore, use software upgrade token 16C027 to install software before use.
1
82 313296J
Page 83

Warm Melt Kits for D60 Systems

Kit 24D009 (CST), 24K670 (SST) with Display for D60 and D60i Systems Kit 24D010 (CST), 24K671 (SST) with Display for Ram A of Tandem D60 and D60i Systems Kit 24D011 (CST), 24K673 (SST) without Display for Ram B of Tandem D60 and D60i Systems
Parts
Kit 24D010 Shown
204
207
211
281
213
208
209
214
202
210
201
203
202
201
279
280
206
201
202
224
219
215
217
220
205
254
253
r_wm29yy_31329b6_5
313296J 83
Page 84
Parts
258
233
257
r_wm_2179_313296_12a
259, 260, 261
237
236
235
84 313296J
Page 85
,
282, 283, 284
234
Parts
227
256
249, 272, 273
228, 229
227
262
239, 274
ti17721a
201, 202
232
223
201, 213, 240, 241
201
202, 222
313296J 85
Page 86
Parts
278
276
271
265
241
201
241
201
264
255
266
248, 272, 273
270
201241
258
268
269
267
UBFB
D60 Warm Melt Kits
Ref. Part Description Qty.
201 100016 WASHER, lock 31 202 121112 SCREW, cap, sch 23 203 288543 BRACKET, hose spring 1 204 277589 COVER, shroud front 1 205 277590 COVER, shroud rear 1 206 255383 BRACKET, light tower 1 207✿■ 24F493 MODULE, display 1 208✿✓ BRACKET, pendant pivot 1 209✿✓ BRACKET, mounting, assy 1 210✿✓ SCREW, shcs; 1/4 unc x 4.25 1 211✿✓ 102040 NUT, lock, hex 1 212
16C377 CABLE, M12;
Kits 24D009/24K670 only
15X968 CABLE, splitter, FCM empty/air;
Kits 24D010. 24D011, 24K671,
24K673 only 213✿✓ 110755 WASHER, plain 1 214✿✓ 121253 KNOB, display 1 215 114417 SCREW, self tap, pan hd 4 216 123375 SUPPRESSOR, ferrite bead 1 217 121070 SCREW, machine; #8-32 x 1 3/8 1 218 121001 CABLE, CAN, female / female; 1m 1 219 289697 MODULE, base 1 220 289696 MODULE, fluid control 1 222 BRACKET, mounting, bottom 1 223 BRACKET, mounting 1
Ref. Part Description Qty.
224 277674 ENCLOSURE, cube door 1 225 16C430 HARNESS 1 227 121980 HEATER, pump; 725 watt 2 228 16J890 SUPPORT, sensor 1 229 16D383 SENSOR, RTD, shielded 1 232 BRACKET, mounting,
accessory box
233 15W706 ENCLOSURE, pump, front 1
16K771 ENCLOSURE, pump, front, SST
234 15W707 ENCLOSURE, pump, rear 1
16K772 ENCLOSURE, pump, rear SST 235 CONDUIT; 12.9 mm 2 ft 236 COUPLER, conduit 3 239 116343 SCREW, ground 1
1
240 100014 SCREW, cap, hex hd 4 241 100015 NUT, hex mscr 8
1
247 15Y051 CABLE, M12, 8 pin, f/m 1 248 123507 WIRE, grounding, panel 1 249 16A574 WIRE, grounding, door 2 250 16H441 WIRE, grounding 1 253 COVER 1 254 121255 SCREW, countersunk, 6-32 x 0.38 2 255 16A539 BOX, junction box 1 256 C31012 CLAMP 1 257 110637 SCREW, mach, pan head 4 258 BRACKET, mount 1 259 O-RING 1 260
CONNECTOR, power,
female, 3 pin
1
1
86 313296J
Page 87
Ref. Part Description Qty.
261 COVER, connector 1 262 15J075 LABEL, warning 1 263★▲ 15H668 LABEL, warning 1 264 RAIL, din, assy 1 265 BUSHING, strain relief; M40
thread 266 NUT, strain relief; M40 thread 1 267 24B810 CONNECTOR, bulkhead, 15 pin 1 268 113970 SCREW, cap, sch 4 269 C19208 WASHER, lock 4 270 102794 NUT, hex 4 271 COVER, junction box 1 272 111640 WASHER, lock, internal 4 273 100166 NUT, full hex 4 274 16A355 WIRE, ground 1 276 196548 LABEL, caution 1 277 114958 STRAP, tie 7 278 112788 SCREW, cap, sch 4 279*‡ BRACKET, sensor, low/empty 1 280*‡122716 SENSOR, inductive, M12 2 281*‡ ACTUATOR, sensor, low/empty 1 282 124131 SCREW 2 283 103181 WASHER, lock 2 284 16K094 SWITCH, overtemp, horizontal 1 285 C33037 TAPE, fiberglass 1 286 106245 SCREW 1 287 157974 WASHER 1 288 16K066 CLAMP, support 1
Not shown.
Replacement Danger and Warning labels, tags, and cards are available at no cost.
* Standard only on tandem supply systems.
1
Kits 24D009, 24D010, 24K670, and 24K671.
Parts included in Low or Empty Sensor Kit 255469 (purchase separately).
Parts included in Drum Low and Empty Sensor Kit 24C530 (purchase separately).
Parts included in 3 in. Ram Bracket Mounting Kit 24C628 (purchase separately).
Parts included in Pump Heater Kit 24C495 (purchase separately).
Parts included in Stainless Steel Pump Heater Kit 24K669 (purchase separately).
Parts only available in Display Mounting Kit 24C653 (purchase separately).
Parts only available in Cover Connector Kit 256883 (purchase separately).
Replacement electronic components do not have Warm Melt specific software installed. Therefore, use software upgrade token 16C027 to install soft­ware before use.
Parts
313296J 87
Page 88
Parts
Heated Platens - 20L, 30L, and 60L
Platen 24D066 (20L) Shown
311
3
335
327
325, 326
1
309
324
323
320
3
322
4
321
333
334 336
328, 329, 330
303
1
Torque to 45 +/- 5 in-lbs (5.1 +/- 0.6 N•m)
2
Apply sealant to all non-swiveling pipe threads.
3
Add lubricant to threads.
302
310
ti17717b
319
318
317
304, 305
301
308
309
307
313
3
1
3
2
4
Ground RTD sleeve to screw (332).
88 313296J
Page 89
Parts
Parts Used on all Heated Platens
Ref. Part Description Qty.
301 BASE, platen 1 305 PLATE, bottom 1 306 121829 O-RING 1 309 NUT, keps, hex hd 12 or 20 311 257697 HANDLE, bleed, sst, assy 1 312 109482 O-RING 1 313 C20350 ELBOW, 90 deg. 1 317 GASKET, heat transfer 1 318 PLATE, heater, lower 1 319 HEATER (includes wiring to
switch 336) 320 PLATE, heater, upper 1 321 HOLDER, RTD sensor 1
1
Ref. Part Description Qty.
322 16D383 SENSOR, RTD, 1k ohm,
shielded 323 NUT, barrel, binding screw 4 324 GUARD, heat shield 1 325 COUPLER, conduit 1 326 CONDUIT, ID 12.9mm 36 327 189930 LABEL, caution 1 328 C38163 WASHER, lock, external 1 329 100166 NUT, full hex 1 330 16A356 WIRE, ground 1 331 16H441 WIRE, ground 1 332 111593 SCREW, grounding 1 335 15K616 LABEL, safety 1 336 15B137 SWITCH, thermal 1 337 104714 SCREW, machine
1
338 103181 WASHER, lock
Replacement Danger and Warning labels, tags, and
cards are available at no cost.
Parts that Vary by Heated Platen Model
Heated Platen Models
24D066, 20L
Ref. Description
302
SPACER, dual wiper
303
WIPER, main
304
WIPER, support
307
PLATE, top
308
SCREW, set, sch
310
VALVE, check
333
WIPER, support
334 SPACER, nylon, 3/4 in. --- --- --- 16J835 16J835 16J835 1
Platen, CS
257694 257695 257696 262873 262874 257684 1
257678 257679 257680 257675 257676 257677 2
257681 257682 257683 257681 257682 257683 1
257686 257687 257688 257698 257699 257725 1
100421 100421 100421 109477 109477 109477 2
122056 122056 122056 501867 501867 501867 1
--- --- --- 15V442 15V443 15V444 1
24D067, 30L
Platen, CS
24D068, 60L
Platen, CS
24D069, 20L
Platen, SST
24D070, 30L
Platen, SST
24D071, 60L
Platen, SST
Qty
313296J 89
Page 90
Parts

Electrical Enclosure Parts

257158 for single supply systems and ram A of tandem supply systems 257291 for ram B of tandem supply systems
257158 Shown
441
445
444
402, 403, 404, 405
436
443, 458
442
433, 434, 435
452
425, 453
407
440
427
457
415, 426
438
437
401
Side View
439
451
439
439
439
459
406
461
415
456
417
466
414
415, 426
420
318
460
422
413
431
415 426
412
432
429
428
408, 409, 410
430
411
90 313296J
416
419
417
421
423
424
Page 91
Parts
Electrical Enclosure Parts
Qty
Ref. Part Description
401 ENCLOSURE 1 402 DOOR, enclosure 1 403 101682 SCREW, cap, sch 4 404 100016 WASHER, lock 4 405 100015 NUT, hex, mscr 4 406 15X754 BRACKET, mounting, electrical 1 407289697 MODULE, cube, base 3 408■★ 256270 MODULE, low power temp 3 409 114417 SCREW, self tap, pan hd 12 410 121070 SCREW, machine, pan hd 3 411■★ 255774 MODULE, high power temp 1 412 15U651 BRACKET, high power temp mod-
ule
413 15R535 BRACKET, mounting, high power
temp module 414 117831 SCREW, machine, pan hd 4 415 100035 SCREW, machine, pan hd 20 416122148 BAR, buss, smissline; 17.125 in. 1 417122619 CIRCUIT, breaker, smissline; 10A
(257291 includes qty. of 3) 418 122129 COVER, buss bar 1 419122128 CIRCUIT, breaker 1 42016A573 WIRE, power 2 421122122 SWITCH, disconnect 1 422 122317 ROD, connecting, on/off 1 423122125 RELAY, contactor 1 424123141 CIRCUIT, breaker, smissline; 25A 1 425 111640 WASHER, lock, internal 2 426 157021 WASHER, lock, internal 10 427 KIT, bar, ground 1 428 257341 HARNESS, wiring, high power
temp module 429121597 CABLE, CAN, 90 female/90 female 2 43015V999 CABLE; 14 in. 3 431 CABLE; M8, male/ferrules 1 432121000 CABLE, CAN, female/female; 0.5 m 1 433 100023 WASHER, flat 4 434 100133 WASHER, lock 4 435 100307 NUT, hex 4 436 PANEL, side, 3 low power heat
modules, 1 hp 437 GASKET, low power heat module 3 438 GASKET, high power heat module 1 439 LABEL, junction box 1 440 CORD, grip; PG-7 1 441 GRIP, cord 1 442121612 CONNECTOR, thru; M12, m x f 1 443 112788 SCREW, cap, socket hd 6 444 LATCH, quarter turn 2 445 15W905 HANDLE, selector, on/off 1 451 SEAL, hole, plug; 0.5 in. 1 452 16H441 WIRE, grounding, door 1 453 100166 NUT, full hex 2 454 123507 WIRE, ground 1 456 277674 ENCLOSURE, cube door 3 457 186620 LABEL, ground 1
Ref. Part Description
458 112905 WASHER, plain 6
.
459123373 FILTER, power line; single phase 1 460123374 SUPPLY, power; 24Vdc, 2.5A,
60W
(included in only 257158) 461 COVER, buss bar, single 1 466 125789 CABLE, CAN, female/female 1 467 123615 TERMINAL, bus bar, L3 (257291
only)
Not shown.
1
1
Replacement Danger and Warning labels, tags, and cards are available at no cost.
Replacement electronic components do not have Warm Melt specific software installed. Therefore, use software upgrade token 16C027 to install soft­ware before use.
4
1
1
Qty
.
1
1
313296J 91
Page 92

Accessories

Accessories
Platen Cover, 255691
Two platen covers. See manual 406681 for more infor­mation for D200 platens.
Two-Zone Expansion Kit, 24C223
For adding two zones of heat to a Warm Melt Supply System. The two extra zones are controlled through the Warm Melt display.
Two-Zone Accessory Kit, 24C222
Controls two zones of heat; up to 212°F (100°C).
Four-Zone Accessory Kit, 24C526
Controls four zones of heat; up to 212°F (100°C).
Light Tower Accessory Kit, 255468
For use with Warm Melt or Tandem Supply Systems.
Low and Empty Sensor Kit, 24C530
Indicates when the drum is low and empty. Includes two sensors: one to be used as a low sensor, and one to be used as an empty sensor. For use with Warm Melt (to add a low sensor), Ambient, and Tandem supply sys­tems.
92 313296J
Page 93

Appendix A - User Interface Display

Appendix A - User Interface Display

Display Overview

The user interface display is divided into two main func­tions: Setup mode and Run mode.
Setup Mode Functions
The setup mode functions enable users to:
set and change the password;
configure system parameters;
set heat zone parameters;
schedule maintenance parameters;
configure system hardware settings;
set and change display units and format for all other screens;
set pump size and drum fill volume;
and view software information for each system component.
Run Mode Functions
The run mode functions enable users to:
view current flow rate and drum volume;
view temperature for heat zones;
view system job totals and grand totals, and reset totals;
view current pressures;
view and reset maintenance counters;
view and clear individual alarms;
and view the alarm log.

Display Details

Power Up Screen
The following screen appears when the display module is powered up. It remains on while the display module runs through initialization and establishes communica­tion with other components in the system.
F
IG
. 59: Power Up Screen
Menu Bar
The menu bar appears at the top of the screen, and consists of the following components.
F
IG
. 60: Menu Bar
Date and Time
The date and time are always displayed in one of the fol­lowing formats. The time is always displayed as a 24-hour clock.
DD/MM/YY HH:MM
MM/DD/YY HH:MM
Navigation
The navigation section, which is to the right of the date and time, indicates the active screen with the center, highlighted icon. The left and right arrows indicate there are more screens that can be accessed within a mode.
313296J 93
Page 94
Appendix A - User Interface Display
Status
The current system status is displayed on the right of the menu bar. If there is an error, an event icon and either a text description of the event or the standard error code for the event is displayed. If there are no errors or deviations, nothing is displayed.
Mode
The mode section displays the current system mode. The current mode is highlighted.
Error
The current system error is displayed in the menu bar. There are four possibilities:
Icon Function
No Icon
No information or no error has occurred
Advisory
Deviation
Alarm
Navigation within Screens
Press to open drop-down menus on Setup
screens. Also, press to enter changes or make a
selection.
Press to navigate to new screens and to
navigate left and right within a screen. Also press
select digits within a field to change.
Press to navigate to new screens and to
navigate up and down within a screen. Also press
to move between fields within a drop-down
menu, and to increment or decrement numbers within a field.
Soft Keys
Icons above the soft keys indicate which mode or action is associated with each soft key. Soft keys that do not have an icon above them are not active in the current screen.
Jump In/Jump Out
In screens that have editable fields, press to
access the fields and make changes. When changes
are complete press to exit edit mode.
94 313296J
Page 95

Setup Mode Screens

Appendix A - User Interface Display
Setup mode screens are divided into six sections: pass­word, system setup, heat zone setup, maintenance setup, hardware setup, and advanced setup.
Password Screen
While in Run mode, press the Setup button. If the
password is not set to 0000, the Password screen will appear. Enter the password to continue to Setup mode.
NOTE: Upon the first system startup, the System Setup screen will display. Otherwise, the last setup screen viewed will display.
Set Password
To set the password, press to enter the screen.
Press to select digit to change. Press
to set value for each digit. Press
again to enter the password.
System Setup
The System Setup screen enables users to configure
system settings for the ram(s). Press to access the
fields and make changes. Press to exit edit mode.
Icon Function
Select tandem operation, ram A only oper­ation, or ram B only operation.
Select if a Not Primed event will issue an alarm or deviation.
Set number of minutes (1-9) for priming.
Set pump cycles per minute that will issue a pump runaway alarm. Set between 0 and 99; default setting is 60 cycles; 00 setting disables this function.
F
IG
. 62: System Setup
F
IG
. 61: Password Screen
Heater System Setup Screen
This screen enables users to set parameters for each
heat zone. Press to scroll through each
heat zone. When the desired heat zone displays, press
to access the fields to make changes. Press
to exit edit mode.
313296J 95
Page 96
Appendix A - User Interface Display
NOTE: Must exit edit mode to scroll through the heat zones.
Icon Function
Displays selected heat zone. Press
to scroll through each heat
zone. Set the temperature setpoint for each heat
zone.
Set the number of degrees the setpoint will be decreased by when the heat zone is in setback mode.
Set the number of degrees the heat zone can go above the setpoint before an alarm is issued.
Set the number of degrees the heat zone can go above the setpoint before a devia­tion is issued.
Select to enable the heat zone; leave blank to disable the heat zone.
Shared zone. Select to enable zone for both ram A and ram B.
Maintenance Setup Screen
The Maintenance Setup screen enables users to set maintenance intervals for rebuilding platen seals and
rebuilding the pump.
Icon Function
Set the number of drums (0-9999) between platen seal maintenance. Setting the num­ber of pump cycles to 0 disables this func­tion. If using a tandem system, set for each ram. A rebuild platen seals error is issued when maintenance is required. See Alarm Codes and Troubleshooting on page 36.
Set the number of pump cycles (0-9999) between pump maintenance. Setting the number of pump cycles to 0 disables this function. If using a tandem system, set for each pump. A rebuild pump error is issued when maintenance is required. See Alarm
Codes and Troubleshooting on page 36.
F
IG
. 64: Maintenance Setup
F
IG
. 63: Heater System Setup Screen
96 313296J
Page 97
Appendix A - User Interface Display
Hardware Setup Screens
The Hardware Setup screens enable users to specify if specific hardware is installed on the system and to
adjust hardware settings. Press to scroll
through the Hardware Setup screens. Once in the
desired Hardware Setup screen, press to access
the fields to make changes. Press to exit edit
mode.
NOTE: Must exit edit mode to scroll through the Hardware Setup screens.
Hardware Setup Screen 1
This screen enables users to specify if a fluid filter moni­tor is installed, and set the high and low limits for the
pressure drop across the filter.
Icon Function
Select what type of error will be issued if fil­ter pressure drops below the low limit or
raises above the high limit. Select to
Monitor the filter pressure readings through the normal range of flow with a clean filter to establish the initial limit settings.
FIG. 65: Hardware Setup Screen 1 (Filter)
Hardware Setup Screen 2
This screen enables users to specify if a fluid solenoid is installed, and if a drum low sensor is installed. The fluid
solenoid controls the depressurize/recirculate valve.
Icon Function
Select if fluid solenoid is installed on sys­tem. Set for A and B rams.
disable filter monitoring or if there is no fil­ter installed on the system.
Set low limit (0-1000 psi) for pressure drop that will issue an error. Set the low limit to detect a filter element collapse or a missing element.
Set high limit (0-5000 psi) for pressure drop that will issue an error. Set the high limit to detect a clogged filter.
Select if drum low sensor is installed on system. Set for A and B rams.
F
IG
. 66: Hardware Setup Screen 2
313296J 97
Page 98
Appendix A - User Interface Display
Advanced Setup Screens
The Advanced Setup screens enable users to set units, adjust values, set formats, and view software informa-
tion for each component. Press to scroll
through the Advanced Setup screens. Once in the
desired Advanced Setup screen, press to access
the fields to make changes. Press to exit edit
mode.
Advanced Setup Screen 2
This screen enables users to set the pump size (in cc/cycle) and the drum fill volume (in volume units). The drum fill volume is the amount of material in a new drum, which is used to calculate the volume of material remaining during operation.
NOTE: These values must be entered accurately for the volume remaining estimates on the Ram Opera­tion screen to be accurate.
NOTE: Must exit edit mode to scroll through the Advanced Setup screens.
Advanced Setup Screen 1
This screen enables users to set units that display on other screens.
NOTE: On two-zone and four-zone enclosure acces-
sory kit, only and settings are available.
Icon Function
Select units of measurement for volume. Select between cycles/gal. gal., oz., and liters/cc.
Set units of measurement for maintenance intervals. Select between cycles, drums, gal., and liters.
Set units of measurement for pressure. Select between psi and bar.
Set the password. Use digits 0-9999; 0000 = no password.
Icon Function
Set pump size (cc/cycle) for each ram. Check-Mate: Select between 60, 100, 200, 250, and 500. Dura-Flo: Select between 145, 180, 220, 290, 430, 580, and 1000.
Set fill volume for each drum. Use dig­its 1-9999.
Change between a Check-Mate or Dura-Flo pump.
Set units of measurement for temperature. Select between °F and °C.
F
IG
. 67: Advanced Setup Screen 1
98 313296J
F
IG
. 68: Advanced Setup Screen 2
Page 99
Appendix A - User Interface Display
Advanced Setup Screen 3
This screen enables users to set the date, time, and date format.
Icon Function
Set date format. Select between MM-DD-YYYY and DD-MM-YYYY.
Set current date.
Set current time.
Advanced Setup Screens 4 and 5
These screens display the software part number and version information for the system components. Only system components that are detected via the system
data bus will be displayed on these screens.
Icon Function
Controller software part number and ver­sion.
Display software part number and version.
Fieldbus gateway software part number and version.
Temperature controller software part num­ber and version.
F
IG
. 69: Advanced Setup Screen 3
F
IG
. 70: Advanced Setup Screens 4 and 5
313296J 99
Page 100
Appendix A - User Interface Display

Run Mode Screens

Run mode screens are divided into six sections: ram operation, heat zone operation, current system status, preventative maintenance schedule, current alarms, and error reports. The system starts in Run mode. If the sys-
tem is in Setup mode, press to enter Run mode.
Ram Operation Screen
The Ram Operation screen displays which ram (A or B) is active, and how much volume remains in each drum. This screen also displays the flow rate of the active ram. When the fluid line is shown filled the system is on.
Depending on the current system status, users can per­form the following procedures from the Ram Operation screen:
turn the air motor on and off;
depressurize and pressurize the system;
recirculate fluid within the active ram;
prime the pump(s);
and perform a manual crossover on tandem sys­tems.
See Operation, page 28, for instructions on all of these procedures.
Active ram is highlighted
Vol­ume Remain
Current mode
Flow rate
Fluid line shown filled when system is Run Mode
FIG. 71: Ram Operation Screen - Tandem System
The Ram Operation screen will display the appropriate icon and highlight the corresponding soft key if the sys­tem is:
depressurized ,
in Recirculate mode ,
or if a ram is in Prime mode .
100 313296J
Loading...