You need at least one 50 ft (15.2 m) main hose, one fluid temperature sensor (FTS), and one whip hose or one wire
harness jumper (part no. 261821) to make a complete heated hose assembly. Be sure the selected hose meets your
maximum pressure and hose diameter requirements.
Whip Hoses
ETL
Approval /
Hose
Assembly
2000 psi (13.8 MPa, 138 bar)
24605010 (3)1/4 (6)
2495863 (0.9)1/4 (6)
3500 psi (24.1 MPa, 241 bar)
24605510 (3)1/4 (6)
24605610 (3)3/8 (10)
5000 psi (34.5 MPa, 345 bar)
25870110 (3)1/4 (6)
◆
Individual heated A and B lines.
Length
ft (m)
ID
in. (mm)Heated
Standard
Braided
Scuff
Guard
✔✔
✔✔
✔✔
✔✔
✔✔
XtremeWrap
Scuff
Guard
Hose Fittings
“A”
inlet (f)/
outlet (m)
-5 JIC-6 JIC
-5 JIC-6 JIC
-5 JIC-6 JIC
-5 JIC-6 JIC
-5 JIC-6 JIC
“B”
inlet (f)/
outlet (m)
Series B
✔
✔
Adapter Fittings
Use adapter fittings to connect a hose assembly to a fluid manifold and/or a FTS. Use JIC swivel fittings to connect a
female FTS to male end hoses and/or npt female ball valves on mix manifold inlets.
Fluid Temperature Sensor Kits (FTS, RTD;
for use with GCA Controlled Systems)
“A” Side“B” Side
Part No.
5000 psi (34.5 MPa, 345 bar)
24K207-5 JIC-5 JIC
7250 psi (50 MPa, 500 bar)
24M9441/2 npt (f)1/2 (npt (f)
FTS kits contain:
•FTS Sensor
InletOutletRTD ProbeInletOutletRTD Probe
✔
✔
-6 JIC-6 JIC
1/2 npt (f) 1/2 (npt (f)
✔
•FTS coupler fitting (5b) for equal length on other line.
•Adapter fittings as necessary. See Adapter Fittings, page 3.
•Foam tube insulation to cover fittings and FTS.
•3.75 in. (95.25 mm) air line jumper hose (except kit 261670).
6309572ZAG
Page 7
Warnings
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. When
these symbols appear in the body of this manual, refer back to these Warnings. Product-specific hazard symbols and
warnings not covered in this section may appear throughout the body of this manual where applicable.
WARNING
WARNINGWARNINGWARNING
ELECTRIC SHOCK HAZARD
The hoses must be grounded. Improper grounding, set-up, or usage of hoses can cause electric
shock.
•Turn off and disconnect power before installing or servicing hoses.
•Connect only to grounded power source.
•All electrical wiring must be done by a qualified electrician and comply with all local codes and
regulations.
•Never cut or puncture a hose cover.
•Do not expose to rain. Store indoors.
SKIN INJECTION HAZARD
High-pressure fluid from hose leaks, or ruptured components will pierce skin. This may look like just a
cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment.
•Inspect hose before each use for cuts, bulges, kinks or any other damage.
•Replace damaged hose immediately.
•Replace hoses proactively at regular intervals based on your operating conditions.
•Tighten all fluid connections before operating the equipment.
•Keep clear of leaks.
•Do not stop or deflect leaks with your hand, body, glove, or rag.
•Never exceed hose Maximum Pressure or Temperature ratings.
•Only use chemicals that are compatible with hose materials. See Technical Data in this manual.
Read Safety Data Sheet (SDS) and fluid and solvent manufacturer’s recommendations.
•Follow the Pressure Relief Procedure when you stop spraying/dispensing and before cleaning,
checking, or servicing equipment.
THERMAL EXPANSION HAZARD
Fluids subjected to heat in confined spaces, including hoses, can create a rapid rise in pressure due to
the thermal expansion. Over-pressurization can result in equipment rupture and serious injury.
•Open a valve to relieve the fluid expansion during heating.
•Replace hoses proactively at regular intervals based on your operating conditions.
BURN HAZARD
Equipment surfaces and fluid that is heated can become very hot during operation. To avoid severe
burns:
•Do not touch hot fluid or equipment.
309572ZAG7
Page 8
Warnings
WARNING
WARNINGWARNINGWARNING
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled or
swallowed.
•Read Safety Data Sheet (SDS) for handling instructions and to know the specific hazards of the fluids
you are using, including the effects of long-term exposure.
•When spraying, servicing equipment, or when in the work area, always keep work area well ventilated and always wear appropriate personal protective equipment. See Personal Protective Equip-ment warnings in this manual.
•Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. Paint or solvent flowing through the equipment can cause static sparking. To help prevent fire and explosion:
•Use equipment only in well ventilated area.
•Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop
cloths (potential static sparking).
•Ground all equipment in the work area. See Grounding instructions.
•Never spray or flush solvent at high pressure.
•Keep work area free of debris, including solvent, rags and gasoline.
•Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes
are present.
•Use only grounded hoses.
•Hold gun firmly to side of grounded pail when triggering into pail. Do not use pail liners unless they
are anti-static or conductive.
•Stop operation immediately if static sparking occurs or you feel a shock. Do not use equipment
until you identify and correct the problem.
•Keep a working fire extinguisher in the work area.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
•Do not operate the unit when fatigued or under the influence of drugs or alcohol.
•Do not exceed the maximum working pressure or temperature rating of the lowest rated system component. See Technical Data in all equipment manuals.
•Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all
equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information
about your material, request Safety Data Sheet (SDS) from distributor or retailer.
•Do not leave the work area while equipment is energized or under pressure.
•Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
•Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
•Do not alter or modify equipment. Alterations or modifications may void agency approvals and create
safety hazards.
•Make sure all equipment is rated and approved for the environment in which you are using it.
•Use equipment only for its intended purpose. Call your distributor for information.
•Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
•Do not kink or over bend hoses or use hoses to pull equipment.
•Keep children and animals away from work area.
•Comply with all applicable safety regulations.
8309572ZAG
Page 9
Important Isocyanate (ISO) Information
WARNING
WARNINGWARNINGWARNING
PERSONAL PROTECTIVE EQUIPMENT
Always wear appropriate personal protective equipment and cover all skin when spraying, servicing
equipment, or when in the work area. Protective equipment helps prevent serious injury, including
long-term exposure; inhalation of toxic fumes, mists or vapors; allergic reaction; burns; eye injury and
hearing loss. This protective equipment includes but is not limited to:
•A properly fitting respirator, which may include a supplied-air respirator, chemically impermeable
gloves, protective clothing and foot coverings as recommended by the fluid manufacturer and local
regulatory authority.
•Protective eyewear and hearing protection.
Important Isocyanate (ISO) Information
Isocyanate Conditions
Spraying or dispensing fluids that contain isocyanates creates potentially harmful mists, vapors, and atomized
particulates.
•Read and understand the fluid manufacturer’s warnings andSafety Data Sheet (SDS) to know specific hazards and
precautions related to isocyanates.
•Use of isocyanates involves potentially hazardous procedures. Do not spray with this equipment unless you are trained,
qualified, and have read and understood the information in this manual and in the fluid manufacturer’s application
instructions and SDS.
•Use of incorrectly maintained or mis-adjusted equipment may result in improperly cured material.which could cause off
gassing and offensive odors. Equipment must be carefully maintained and adjusted according to instructions in the
manual.
•To prevent inhalation of isocyanate mists, vapors and atomized particulates, everyone in the work area must wear
appropriate respiratory protection. Always wear a properly fitting respirator, which may include a supplied-air respirator.
Ventilate the work area according to instructions in the fluid manufacturer’s SDS.
•Avoid all skin contact with isocyanates. Everyone in the work area must wear chemically impermeable gloves, protective clothing and foot coverings as recommended by the fluid manufacturer and local regulatory authority. Follow all
fluid manufacturer recommendations, including those regarding handling of contaminated clothing. After spraying,
wash hands and face before eating or drinking.
•Hazard from exposure to isocyanates continues after spraying. Anyone without appropriate personal protective equipment must stay out of the work area during application and after application for the time period specified by the fluid
manufacturer. Generally this time period is at least 24 hours.
•
Warn others who may enter work area of hazard from exposure to isocyanates. Follow the recommendations of the fluid
manufacturer and local regulatory authority. Posting a placard such as the following outside the work area is recom-
mended:
TOXIC FUMES
HAZARD
DO NOT ENTER DURING
SPRAY FOAM APPLICATION
OR FOR ___ HOURS AFTER
APPLICATION IS COMPLETE
DO NOT ENTER UNTIL:
DATE:
____________
TIME:
____________
309572ZAG9
Page 10
Important Isocyanate (ISO) Information
For all applications except spray
foam
Spraying or dispensing fluids that contain isocyanates creates potentially harmful mists, vapors, and
atomized particulates.
•Read and understand the fluid manufacturer’s
warnings and Safety Data Sheet (SDS) to know
specific hazards and precautions related to isocyanates.
•Use of isocyanates involves potentially hazardous procedures. Do not spray with this equipment unless you are trained, qualified, and have
read and understood the information in this
manual and in the fluid manufacturer’s application instructions and SDS.
•Use of incorrectly maintained or mis-adjusted
equipment may result in improperly cured material. Equipment must be carefully maintained
and adjusted according to instructions in the
manual.
Material Self-ignition
Some materials may become self-igniting if applied
too thick. Read material manufacturer’s warnings and
Safety Data Sheet (SDS).
Keep Components A and B
Separate
Cross-contamination can result in cured material in fluid
lines which could cause serious injury or damage
equipment. To prevent cross-contamination:
•Never interchange component A and component B
wetted parts.
•Never use solvent on one side if it has been contaminated from the other side.
•To prevent inhalation of isocyanate mists,
vapors, and atomized particulates, everyone in
the work area must wear appropriate respiratory
protection. Always wear a properly fitting respirator, which may include a supplied-air respirator. Ventilate the work area according to
instructions in the fluid manufacturer’s SDS.
•Avoid all skin contact with isocyanates. Everyone in the work area must wear chemically
impermeable gloves, protective clothing and
foot coverings as recommended by the fluid
manufacturer and local regulatory authority. Follow all fluid manufacturer recommendations,
including those regarding handling of contaminated clothing. After spraying, wash hands and
face before eating or drinking.
10309572ZAG
Page 11
Important Isocyanate (ISO) Information
Moisture Sensitivity of
Isocyanates
Exposure to moisture (such as humidity) will cause ISO
to partially cure, forming small, hard, abrasive crystal
that become suspended in the fluid. Eventually a film will
form on the surface and the ISO will begin to gel,
increasing in viscosity.
NOTICE
Partially cured ISO will reduce performance and the
life of all wetted parts.
•Always use a sealed container with a desiccant
dryer in the vent, or a nitrogen atmosphere. Never
store ISO in an open container.
•Keep the ISO pump wet cup or reservoir (if
installed) filled with appropriate lubricant. The
lubricant creates a barrier between the ISO and
the atmosphere.
•Use only moisture-proof hoses compatible with
ISO.
•Never use reclaimed solvents, which may contain
moisture. Always keep solvent containers closed
when not in use.
•Always lubricate threaded parts with an appropriate lubricant when reassembling.
Changing Materials
NOTICE
Changing the material types used in your equipment
requires special attention to avoid equipment damage
and downtime.
•When changing materials, flush the equipment
multiple times to ensure it is thoroughly clean.
•Always clean the fluid inlet strainers after flushing.
•Check with your material manufacturer for chemical compatibility.
•When changing between epoxies and urethanes
or polyureas, disassemble and clean all fluid components and change hoses. Epoxies often have
amines on the B (hardener) side. Polyureas often
have amines on the B (resin) side.
NOTE: The amount of film formation and rate of crystallization varies depending on the blend of ISO, the
humidity, and the temperature.
Foam Resins with 245 fa
Blowing Agents
Some foam blowing agents will froth at temperatures
above 90°F (33°C) when not under pressure, especially
if agitated. To reduce frothing, minimize preheating in a
circulation system.
309572ZAG11
Page 12
Installation
Installation
Description
This hose must be used with an FTS and
cable to provide grounding.
The heated hose maintains proper fluid temperature while spraying.
Fluid hoses are marked with red tape for
ISO/hardener/minor volume side, blue tape for
RES/resin/major volume side. Fittings have
different sized threads to prevent incorrect
connection, which can cause fluid crossover
and permanently damage the hose.
Hoses are 50 ft (15.2 m) or 25 ft (7.6 m) long.
The whip hose is 10 ft (3 m) long or less.
To heat the major volume hose only in a
wide ratio system, see 15F144 Hose Wire Jumper, page 29.
12309572ZAG
Page 13
Connect Whip Hose to Gun or Gun Manifold
Install hose in a helix configuration for:
•Easy gun movement
•Large spraying motion
•Ability to spray in tight areas and odd angles
•Reduced operator fatigue
•Maximum hose life
Installation
1. Overlap A and B component hoses and
assemble to gun or gun manifold fittings as
shown in FIG. 1.
Tighten
Tighten
Tighten
2. Tighten fittings to A and B component
hoses. Ensure hose remains flat after fittings are tightened. Loosen and retighten
fittings as necessary to eliminate any
torque on hoses. This will help achieve a
flat profile on the hose.
TI12158aTI14721a
F
IG
. 1
309572ZAG13
Page 14
Installation
Connect Heated Hoses
1. Lay heated hoses end to end, matching the
color coding. Red for component A (ISO),
blue for component B (RES).
B
A
TI2678B
1
2
FIG. 3
Do not connect the main air supply at
this time.
Some insulated heated hoses do not
contain an air hose.
TI2679B
FIG. 2
2. Connect fluid hoses (1, 2) and tighten. See
maximum torque specifications below and
FIG. 3. Do not over-torque.
Torque 1/4 in. (6.4 mm) and 3/8 in. (9.5 mm)
ID hoses to:
•A side to 14 ft-lb (19 N•m).
•B side to 20 ft-lb (27 N•m).
Torque 1/2 in.(13 mm) ID hoses to:
•A side to 43 ft-lb (58 N•m).
•B side to 55 ft-lb (74 N•m).
3. Connect air hoses (3).
FIG. 4
12
3
TI2682B
14309572ZAG
Page 15
Installation
4. Connect electrical wires.
NOTE: Newer Series B hoses have a
pre-crimped ferrule. If using a Series B
hose, skip to step 5.
a. Ensure electrical wires ends are 5/8 in.
(15.9 mm) long. If they are not, use a
sharp scissors to strip all four wire ends
to the correct length. See Strip Length
Gauge for correct length.
Strip Length
This illustration is not to scale.
5/8 in.
(0.625 mm)
FIG. 5
TI9733a
b. If wire is short of ferrule end, adjust strip
length accordingly. If bare wire is protruding from ferrule, trim flush to ferrule
IG
end. See F
. 6.
Incorrect
Correct
Incorrect
FIG. 6
c. Remove ferrule and apply oxide inhibi-
tor to bare wire. See F
IG
. 7.
d. Reinsert wire in ferrule and apply more
oxide inhibitor to ferrule and wire end.
TI9768a
Be careful not to cut or nick copper
strands. If more than five strands are cut
or nicked, trim wire and re-strip.
New hoses are pre-stripped at correct
length; remove insulation to expose bare
wire.
a. Ensure strip length is correct by fitting
ferrule over exposed wire. Ferrule
should be flush with wire end. See FIG.
6.
On some older heated hoses wire insulation will not fit inside ferrule insulator. In
these cases, use scissors to split and
remove ferrule insulator.
TI9769A
FIG. 7
309572ZAG15
Page 16
Installation
5. Connect the hoses to each other. Pair electrical wires as follows: A-Hose to A-Hose;
B-Hose to B-Hose.
When connecting first hose section to
proportioner, wire pairing does not make
a difference.
When connecting hose to the proportioner, always check the hoses for leaks
(see page 21).
a. Insert one wire from heated hose into
connector. Ensure that ferrule is mating
with connector insert. See FIG. 8.
c. Insert remaining wire from pair into con-
nector; ensure proper insertion depth.
Thread setscrew and torque to 60 in-lbs
(6.78 N•m); see sub-step B. See FIG. 8
and FIG. 9.
d. Repeat sub-steps A through C for
remaining wire pair.
e. Re-torque all four setscrews to 60 in-lbs
(6.78 N•m).
When torqued to 60 in-lbs (6.78 N•m)
setscrews will be approximately flush
with connector. See FIG. 10.
f.Insert cap plugs over setscrews. See
FIG. 10.
Cap plugs
FIG. 8: Insert Wire and Setscrew
b. Thread in setscrew and use hex wrench
to torque setscrew to 60 in-lbs (6.78
N•m).
To reach approximately 60 in-lbs (6.78
N•m), complete 4.5 revolutions with hex
wrench after setscrew comes in contact
with ferrule.
TI9779A
IG
. 9: Torque Setscrew
F
TI9770A
Setscrews
TI9771A
FIG. 10
g. Wrap connector and wire on each side
of connector in black electrical tape to
help seal out moisture. Ensure 1 in.
(25.4 mm) of wire on each side of connector is wrapped.
16309572ZAG
Page 17
6.
For non-RTD hoses only,
connect
thermocouple cables (4). Slide insulator
sleeves (S) over connection. Leave slack
in cables as stress relief to prevent cable
failure.
S
4
FIG. 11
Installation
TI2683B
7.
For RTD 2-component hoses only,
connect
RTD cables (4) and CAN cables (5) if present.
4
5
TI18358a
IG
. 12
F
8. Repeat for additional hoses.
9. See Connect FTS and Heated Dual Whip
Hose, page 18, or Connect FTS with a
Non-Heated Whip Hose or Remote Mix
Manifold, page 20.
309572ZAG17
Page 18
Installation
Connect FTS and Heated Dual Whip Hose
NOTICE
To prevent damage to probe, do not kink or
excessively bend hose. Do not coil hose
tighter than the minimum bend radius of 3 ft
(0.9 m). Do not subject hose to excessive
weight, impact, or other abuse.
See FIG. 13 on page 19.
For 1/2 in. (13 mm) ID fluid hoses
only: Prior to connecting the FTS,
remove the adapters from the proportioner fluid manifold and install them on
the male ends of the hoses (1 and 2).
Torque the A side hose to a maximum
of 43 ft-lbs (58 N•m) and the B side
hose to a maximum of 55 ft-lbs (74
N•m). Continue on to step 1.
1. Assemble JIC swivel fitting (5e) in female
end of temp sensor (5a). Do not bend or
kink probe. Torque connection to 14 ft-lbs
(19 N•m). Do not over-torque. Assemble
JIC swivel fitting (5d) into female end of B
hose coupler (5b). Torque to a maximum of
20 ft-lbs (27 N•m). Do not over-torque.
2. Carefully inset FTS probe into the A hose
(1) section from the proportioner. Do not
bend or kink probe. Connect to A side whip
(6a). Torque fitting connections to 14 ft-lbs
(19 N•m). Do not over-torque.
4. Connect ground wire (K) of whip hose to
the ground screw on the FTS (5a).
A grounding wire must be used to provide
grounding.
Whip hose ground wire (K) must be
connected to the ground screw on the
FTS (5a) in order to drain static from the
gun. If the FTS is not directly connected
to the whip hose, a hose that includes a
separate ground wire must be used
between the FTS and whip hose. Connect ground through a hose marked as
not having the FTS cable selected from
the “Standard 2 Component Hose” table
in the front of this manual.
5. Connect the electrical connectors (12).
6. Connect the FTS air line coupler (5c)
between air hoses (3 and 8).
7. Connect the sensor cable of the hose (4) to
the sensor cable of the FTS (5a). For
non-RTD hoses, slide the insulator sleeves
(S) over the connection. Leave slack in the
cables to provide stress relief and to prevent cable failure or errors.
8. See Connect Hoses to Proportioner,
page 21.
9. Cover the FTS and spacer with split foam
NOTICE
To avoid damage to FTS sensor cable,
rotate FTS body so the cable lays between
both fluid hoses to protect it from abrasive
damage during use.
3. Connect the B hose coupler to the B hose
section (2) and B side whip (6b). Torque fitting connections to 20 ft-lbs (27 N•m). Do
not over-torque.
18309572ZAG
(provided) and tape closed.
Page 19
Installation
Non-RTD Thermocouple 2-Component Hoses
5d
To Proportioner
4
S
S
2
1
3
5b
5a
12
K
5c
6b
8
5e
To Gun
9
6a
TI17091b
FIG. 13
RTD 2-Component Hoses
4
2
1
14
5d
3
5b
5e
5a
12
K
5c
6b
6a
8
TI18392b
309572ZAG19
Page 20
Installation
Connect FTS with a Non-Heated Whip Hose or Remote Mix
Manifold
NOTICE
To prevent damage to probe, do not kink or
excessively bend hose. Do not coil hose
tighter than the minimum bend radius of 3 ft
(0.9 m). Do not subject hose to excessive
weight, impact, or other abuse.
1. Carefully extend FTS probe (H) into the
hose section from the proportioner. Do not
bend or kink probe. Insert probe in major
volume (resin) side on systems which
are not 1:1 mix ratio.
2. Connect FTS (5) to mating assembly.
3. Connect fluid hoses to FTS.
To use 1/2 in. (13 mm) ID fluid hoses,
remove the adapters from the proportioner fluid manifold and install them in
the FTS swivel inlets.
4. Install one connector (12) between wires.
Refer to page 14 for instructions.
5. Connect hose assembly cable (4) to FTS
cable (part of 5). Slide insulator sleeves (S)
over connection. Leave slack in cables as
stress relief, to prevent cable failure.
6. Connect appropriate ground wire.
7. See Connect Hoses to Proportioner,
page 21.
To
Proportioner
To Mix Manifold or
5
non-heated whip
hose
S
4
S
H
12
TI2684E
20309572ZAG
Page 21
Installation
Connect Hoses to Proportioner
1. Grease with Fusion® grease and connect fluid
hoses to proportioner fluid manifold (M). Red
for hardener (ISO), blue for resin (RES).
The manifold hose adapters (N, P) allow use
of 1/4 in (6.4 mm). and 3/8 in. (9.5 mm) ID
fluid hoses. To check adapter tightness,
torque 1/4 in. and 3/8 in. ID hoses to:
•A side (N) to 14 ft-lb (19 N•m).
•B side (P) to 20 ft-lb (27 N•m).
To use 1/2 in. (13 mm) ID fluid hoses,
remove the adapters (N, P) from the proportioner fluid manifold and install them in the
FTS or 3/8 in. ID hose inlets. Torque 1/2 in.
ID hoses to:
•A side (N) to 43 ft-lb (58 N•m).
•B side (P) to 55 ft-lb (74 N•m).
M
2. Connect hose power wires to terminal block (C)
on termination box (TB). Remove box cover (D)
and loosen lower strain relief (E). Route wires
through strain relief and fully insert into terminal
block (A and B hose wire positions are not
important). Torque terminal connector screws
(C) to 26-30 in-lb (2.9-3.3 N•m). Fully tighten
strain relief screws and replace cover.
3. Connect hose power wires to electrical splice
connectors (12) from proportioner or accessory
control box. See Connect Heated Hoses,
page 14, step 5. Connect FTS hose cable (4) to
cable from proportioner or accessory control
box. Wrap connections with electrical tape.
N
P
NOTE: For proportioners with termination box
(TB), follow step 2, For proportioners with electrical
splice connectors (12) follow step 3.
If thermocouple (non-RTD) FTS connectors are
provided, fully tighten connectors and slide
connector covers over the joint.
5. Check that all equipment is properly grounded.
See proportioner manual.
309572ZAG21
Page 22
Installation
Fluid Temperature Sensor
(FTS) Calibration
(Non-RTD Versions)
Calibrate the FTS ONLY at initial startup
(the first time the unit is operated) and
any time the hose length changes.
1. Before turning on the unit, ensure all hoses
and cables are properly connected. To
ensure that the FTS in the hose is at the
same temperature as the heaters, keep
heat off and store the hose FTS near the
machine for several minutes.
2. While holding down the temperature unit
button (Fahrenheit - “F” or Celsius - “C”)
turn the proportioner main power ON.
3. Hold the temperature unit button until temperature is shown on the display. The fluid
temperature sensor is now correctly calibrated.
Protective Covering
1. Wrap all fluid hose connections with
electrical tape.
2. Fold FTS cable wire back on hose to
ensure adequate strain relief. Wrap all
electrical connections and cable connections with electrical tape to protect them
from pulling apart and abrasion.
FIG. 14
Check Hoses for Leaks
1. Pressure check hose. See proportioner
manual for priming instructions.
2. After all lines are free of air, check for
leaks. If there are leaks, relieve pressure
as instructed in proportioner manual.
3. Tighten connections, then pressurize again
to ensure leaks have stopped. Relieve
pressure.
Leave CAN cable connector (if used)
accessible at whip hose joint for connector to the Remote Display Module Kit (if
ordered).
3. Install protective cover (see Accessories,
page 31), or wrap hose bundle with duct
tape to protect foam.
FIG. 15
22309572ZAG
Page 23
Operation
4. For hoses that include the standard braided
protective scuff cover, unroll excess cover
over hose and electrical connections. Tape
securely.
5. For hoses that include Xtreme-Wrap protective scuff sleeve, pull just enough
excess length over hose and electrical connections. Tape securely.
NOTE: Xtreme-Wrap protective scuff sleeve
will shorten in dry conditions. Use only as
much length as necessary to cover connections and allow excess to remain slack.
Operation
Do not operate a coiled hose. A coiled hose
creates uneven heat buildup which can result
in hose rupture and cause serious injury,
including fluid injection.
Maximum hose operating temperature is
180°F (82°C). If using hose without an FTS,
measure hose temperature to ensure it does
not exceed 180°F (82°C).
1. Connect air hose (3) to main air supply, if
equipped.
2. Connect to spray gun. NOTE: For best
handling of gun, see page 13 for proper
hose connection.
3. Connect whip air hose to gun air inlet if
equipped. See gun manual.
4. Follow setup, startup, and operation
procedures in proportioner manual.
Maintenance
1. Before disconnecting or repairing hoses,
relieve all fluid pressure and shut off electrical power to proportioner. See proportioner
operation manual.
2. Be sure fluid is cool before disconnecting
hoses.
Instructions for Replacing
Hose must be properly supported to avoid
Individual A or B Hose
excessive strain due to weight, bending,
sharp edges, or stress caused by running
over a roof edge.
Fluids subjected to heat in confined spaces,
including hoses, can create a rapid rise in
pressure due to the thermal expansion.
Over-pressurization can result in equipment
rupture and serious injury.
• Open a valve to relieve the fluid
expansion during heating.
• Replace hoses proactively at regular
intervals based on your operating
conditions.
309572ZAG23
Before disconnecting hoses, relieve all fluid
pressure and shut off electrical power to proportioner. See proportioner operation manual.
Disconnect electrical wire from connectors
(12). Disconnect fluid hose and remove from
bundle.
Install new hose in bundle, wrapping around
other fluid hose and air hose. Connect fluid
hoses, see page 14.
Wrap all connections with electrical tape, see
page 22.
Page 24
Parts
Parts
Using 261669 Fluid Temperature Sensor (JIC to JIC fittings)
Whip Hose
Fluid Temperature Sensor
12
5b
5d
2
Heated Fluid Hose
Ref. Part DescriptionQty
1HOSE, component A (ISO); see
tables starting on page 4
2HOSE, component B (RES); see
tables starting on page 4
315B295 HOSE, air; 50 ft (15.2 m)1
24F179 HOSE, air; 25 ft (7.6 m)1
424J523 CABLE, FTS; 50 ft (15.2 m)1
24J524 CABLE, FTS; 25 ft (7.6 m)1
5261669 KIT, FTS, coupler1
5aSENSOR, fluid temperature; -5 JIC1
5bFITTING, FTS coupler; -6 JIC1
5c 24V454 HOSE, air; 4.75 in. (120.65 mm)1
5d 127596 FITTING, swivel; -6 JIC x -6 JIC, mxf1
5e 127597 FITTING, swivel; -5 JIC x -5 JIC, mxf1
4
1
5a
9
6
8
5c
5e
3
Ref. Part DescriptionQty
6HOSE, whip; see Whip Hoses, page 31
1
815B280 HOSE, whip, air; 10 ft (3 m)1
1
9SCUFF GUARD; included on some
12261821 CONNECTOR, electrical; on main
13▲ 15B679 LABEL, safety, English; not shown1
▲ 16M219 LABEL, safety, Spanish/French; not
▲
Replacement Danger and Warning labels, tags, and
cards are available at no cost.
hoses, see Accessories on page 31
hose sections
shown
WLE
1
1
1
24309572ZAG
Page 25
Using 24M943 Fluid Temperature Sensor (NPT to NPT fittings)
815B280 HOSE, whip, air; 10 ft (3 m)1
9SCUFF GUARD; included on some
hoses; see Accessories on page 31
12261821 CONNECTOR, electrical; on main
hose sections
13▲ 15B679 LABEL, safety, English; not shown1
▲ 16M219 LABEL, safety, Spanish/French; not
15★CONNECTOR, manifold4
▲
Replacement Danger and Warning labels, tags, and
shown
1
1
1
cards are available at no cost.
★ Not included. Order connector fittings that connect to
the A and B component hoses. See
Adapter Fit-
tings, page 3.
309572ZAG25
Page 26
Parts
Using 24K207 RTD 2-Component Hose Fluid Temperature Sensor
(JIC to JIC fittings)
Fluid Temperature Sensor
2
4
1
Heated Fluid Hose
14
5d
5b
12
5a
5c
5e
3
Whip Hose
9
6
8
TI18392b
Ref. Part DescriptionQty
1HOSE, component A (ISO); see
tables starting on page 4
2HOSE, component B (RES); see
tables starting on page 4
315B295 HOSE, air; 50 ft (15.2 m)1
424N450 CABLE, RTD; 50 ft (15.2 m)1
524K207 KIT, FTS, coupler1
5aSENSOR, FTS-RTD1
5bCOUPLER1
5c 24V454 HOSE, air; 4.75 in. (120.65 mm)1
5d 127596 FITTING, swivel; -6 JIC x -6 JIC, mxf1
5e 127597 FITTING, swivel; -5 JIC x -5 JIC, mxf1
Ref. Part DescriptionQty
6HOSE, whip; see Whip Hoses, page 31
1
815B280 HOSE, whip, air; 10 ft (3 m)1
1
9SCUFF GUARD; included on some
hoses, see Accessories on page 31
12261821 CONNECTOR, electrical; on main
hose sections
13▲ 15B679 LABEL, safety, English; not shown1
▲ 16M219 LABEL, safety, Spanish/French; not
14* 24N449 CABLE, CAN; 50 ft (15.2 m)1
▲
Replacement Danger and Warning labels, tags, and
cards are available at no cost.
*Included only in hoses with CAN cable. See RTD
2-Component Hose (for use with GCA Controlled
Reactors), page 4.
shown
1
1
1
26309572ZAG
Page 27
Parts
Using 24M944 RTD 2-Component Hose Fluid Temperature Sensor
(NPT to NPT fittings)
Fluid Temperature Sensor
2
4
Heated Fluid Hose
Whip Hose
12
5b
5a
15
1
14
15
9
6
15
8
5c
15
3
TI19092b
Ref. Part DescriptionQty
1HOSE, component A (ISO); see
tables starting on page 4
2HOSE, component B (RES); see
tables starting on page 4
315B295 HOSE, air; 50 ft (15.2 m)1
424N450 CABLE, RTD; 50 ft (15.2 m)1
524M944 KIT, FTS, coupler1
5aSENSOR, FTS-RTD1
5bCOUPLER1
5cHOSE, air; 3.75 in. (95.3 mm)
6HOSE, whip; see Whip Hoses, page 31
Ref. Part DescriptionQty
815B280 HOSE, whip, air; 10 ft (3 m)1
1
9SCUFF GUARD; included on some
1
12261821 CONNECTOR, electrical; on main
13▲ 15B679 LABEL, safety, English; not shown1
▲ 16M219 LABEL, safety, Spanish/French; not
14* 24N449 CABLE, CAN; 50 ft (15.2 m)1
15★CONNECTOR, manifold4
-
▲
Replacement Danger and Warning labels, tags, and
cards are available at no cost.
*Included only in hoses with CAN cable. See RTD
2-Component Hose (for use with GCA Controlled
Reactors), page 4.
★ Not included. Order connector fittings that connect to
the A and B component hoses. See
tings, page 3.
hoses, see Accessories on page 31
hose sections
shown
Adapter Fit-
1
1
1
309572ZAG27
Page 28
Parts
Using 261670 Fluid Temperature Sensor (JIC to NPT fittings)
Fluid Temperature Sensor
5
5b
Heated Fluid Hose
4
1
5c
12
5a
5d
2
Ref.PartDescriptionQty
1HOSE, component A (ISO); see
tables starting on page 4
2HOSE, component B (RES); see
tables starting on page 4
424J523 CABLE, FTS; 50 ft (15.2 m)1
24J524 CABLE, FTS; 25 ft (7.6 m)1
5261670 FLUID TEMPERATURE SENSOR;
includes items 5a-5d
5a156823 . SWIVEL; 1/4 npt (m x 1/4 npsm1
5b117595 . SWIVEL; 1/4 npt(m) x -5 JIC (f)1
Ref.PartDescriptionQty
5c117506 . SWIVEL; 1/4 npt(m) x -6 JIC (f)1
1
5d157705 . SWIVEL; 1/4 npt(m) x 3/8 npsm1
12261821 CONNECTOR, electrical; on main
1
13▲ 15B679 LABEL, safety, English; not shown1
▲ 16M219 LABEL, safety, French/Spanish;
1
▲
Replacement Danger and Warning labels, tags, and
hose sections
not shown
cards are available at no cost.
TI2684E
1
1
28309572ZAG
Page 29
Parts
15F144 Hose Wire Jumper
Use the 15F144 Hose Wire Jumper to heat
only the major volume hose, in a wide ratio
system.
To build one complete 50 ft single side heated
hose bundle, order the following parts:
Ref. PartDescriptionQty.
10015F144JUMPER, hose wire1
101HOSE, resin, heated; 50 ft
10224J523CABLE, FTS1
104261670FLUID TEMPERATURE
105pur-
chase
locally
106pur-
chase
locally
(15.2 m) minimum; see tables
starting on page 4
SENSOR; see page 24
HOSE, hardener, unheated; 50
ft (15.2 m) minimum; customer
supplied
CONNECTORS, fluid; as
required to complete assembly; not shown
1
1
1
as
req’d
Install as follows:
This hose must be used with an FTS and
cable to provide grounding.
1. Wrap hose wire jumper (100) around resin
hose (101) in a spiral fashion.
2. Connect resin hose wire (101a) to other
side of Power-Lock connector (100a); see
page 14.
3. Wrap FTS cable (102) around resin hose
(101) in a spiral fashion.
4. Twist hoses (101 and 105) together to provide strain relief.
5. Repeat steps 1-4 for each length of hose
(101). Connect hoses, electrical connectors, and cables; see Connect Heated Hoses, page 14.
6. Install one -Lock connector (100a) between
wires; see page 14.
7. Connect FTS with a Non-Heated Whip Hose or Remote Mix Manifold, page 20.
309572ZAG29
Page 30
Parts
8. Install whip hose and gun. Ensure that gun
is grounded.
9. Connect hoses to proportioner.
10.Insulate and protect hoses. See Protective Covering, page 22.
Some previous models include transformers with tap settings.
Set transformer wire taps, using the following
table. Transformer tap wire connections vary
depending on length of heated hose. See proportioner operation manual for further information. Verify that tap wire connections are
correct.
Single Side Heated
Hose Length, ft (m)
50 (15.2)50
100 (30.5)50
150 (45.7)100
200 (61.0)100
250 (76.2)150
300 (91.5)150
Tap Terminal
Label (ft)
100a
105
101a
100
350 (106.8)200
400 (122.0)200
102
FTS
101a
100a
101
100
TI5872D
30309572ZAG
Page 31
Accessories
Scuff Guard
Use to keep hose clean and protect it from
damage.
PartDescription
2460777 ft (2.1 m) braided polyester
mesh. For whip hose. Fold back
over itself for easy installation.
24607850 ft (15.2 m) braided polyester
mesh.
Fold back over itself for easy
installation.
24680525 ft (7.6 m) braided polyester
mesh.
Fold back over itself for easy
installation.
24645650 ft (15.2 m) polyethylene bag.
Inflate with air for easy installation.
24T2438 ft (2.4 m) Xtreme-Wrap abra-
sion-resistant woven nylon sleeve
for whip hose
24T24455 ft (16.8 m) Xtreme-Wrap abra-
sion-resistant woven nylon sleeve
Accessories
309572ZAG31
Page 32
Technical Data
Technical Data
Power-Lock Heated Hose
USMetric
Maximum Air Working Pressure130 psi 0.9 MPa, 9 bar
Maximum Fluid Operating Temperature180°F 82°C
Wetted PartsNylon, Zinc-Plated Carbon Steel, 303 Stainless Steel
Total Heating Load (2 Hoses)
1/4 in. diameter:11 watts/foot36 watts/meter
3/8 in. diameter:13 watts/foot43 watts/meter
1/2 in. diameter:15 watts/foot49 watts/meter
Whip Hose Maximum Fluid Working Pressure
246050*2000 psi14 MPa, 138 bar
246055*3500 psi24 MPa, 241 bar
2460563500 psi24 MPa, 241 bar
2495862000 psi14 MPa, 138 bar
2587015000 psi35 MPa, 345 bar
Standard 2 Component Hose Maximum Fluid Working Pressure
2460452000 psi14 MPa, 138 bar
2460462000 psi14 MPa, 138 bar
2460472000 psi14 MPa, 138 bar
2460482000 psi14 MPa, 138 bar
2460492000 psi14 MPa, 138 bar
2460523500 psi24 MPa, 241 bar
2460533500 psi24 MPa, 241 bar
2460543500 psi24 MPa, 241 bar
2460742000 psi14 MPa, 138 bar
2460752000 psi14 MPa, 138 bar
2460762000 psi14 MPa, 138 bar
2466782000 psi14 MPa, 138 bar
2466793500 psi24 MPa, 241 bar
2495872000 psi14 MPa, 138 bar
2495883500 psi24 MPa, 241 bar
2565483500 psi24 MPa, 241 bar
2565492000 psi14 MPa, 138 bar
2613282000 psi14 MPa, 138 bar
2613325000 psi35 MPa, 345 bar
2613353500 psi24 MPa, 241 bar
2622035000 psi35 MPa, 345 bar
24Y549*2000 psi14 MPa, 138 bar
24Y678*2000 psi14 MPa, 138 bar
24Y679*3500 psi24 MPa, 241 bar
32309572ZAG
Page 33
Power-Lock Heated Hose
USMetric
RTD 2 Component Hose (For GCA Reactors) Maximum Fluid Working Pressure
24K2402000 psi14 MPa, 138 bar
24K2413500 psi24 MPa, 241 bar
24K3942000 psi14 MPa, 138 bar
24K3953500 psi24 MPa, 241 bar
24N0002000 psi14 MPa, 138 bar
24N0012000 psi14 MPa, 138 bar
24N0023500 psi24 MPa, 241 bar
24N0033500 psi24 MPa, 241 bar
24T8392000 psi14 MPa, 138 bar
24U7433500 psi24 MPa, 241 bar
24Y240*2000 psi14 MPa, 138 bar
24Y241*3500 psi24 MPa, 241 bar
24Y394*2000 psi14 MPa, 138 bar
24Y395*3500 psi24 MPa, 241 bar
Airless 2 Component Hose Maximum Fluid Working Pressure
2489075000 psi35 MPa, 345 bar
2489085000 psi35 MPa, 345 bar
2627275000 psi35 MPa, 345 bar
2627285000 psi35 MPa, 345 bar
2627305000 psi35 MPa, 345 bar
Custom Application 2 Component Hose Maximum Fluid Working Pressure
2471643500 psi24 MPa, 241 bar
2550892000 psi14 MPa, 138 bar
2613363500 psi24 MPa, 241 bar
2613373500 psi24 MPa, 241 bar
24N5243500 psi24 MPa, 241 bar
FTS Maximum Fluid Working Pressure
2616695000 psi35 MPa, 345 bar
2616705000 psi35 MPa, 345 bar
24M9437250 psi50 MPa, 500 bar
FTS (For GCA Systems) Maximum Fluid Working Pressure
24K2075000 psi35 MPa, 345 bar
24M9447250 psi50 MPa, 500 bar
Technical Data
*These models include the Xtreme-Wrap Scuff
Guard.
309572ZAG33
Page 34
Graco Standard Warranty
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in
material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty
published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by
Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written
recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty
installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of
non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with
structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or
maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of
the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned
to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs
will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT
LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy
(including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or
consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT
MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to
the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these
warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or
the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the
negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into,
given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la
rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés, à la suite
de ou en rapport, directement ou indirectement, avec les procédures concernées.
Graco Information
For the latest information about Graco products, visit www.graco.com.
TO PLACE AN ORDER,
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2002, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
contact your Graco distributor, or call this number to identify the distrib-
utor closest to you: 1-800-328-0211 Toll Free
612-623-6921
612-378-3505 Fax
Graco reserves the right to make changes at any time without notice.
Forpatent information,see www.graco.com/patents.
Original instructions. This manual contains English. MM 309572
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
www.graco.com
Revision ZAG, June 2015
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.