Instructions
15K012 Pneumatic
311606D
VFD/BPR Control
For control of a pneumatic back pressure regulator, using a Graco Variable Frequency
Drive (VFD) or Advanced Control System (ACS) and E-Flo® Electric Circulation Pump.
Important Safety Instructions
Read all warnings and instructions in E-Flo Operation Manual 311593,
Pneumatic Back Pressure Regulator Manual 311595, VFD Manual
311596, and ACS Manual (3A0006). Save these instructions.
See page 2 for Installation and Operation instructions.
EN
Off Production
Air Line
Solenoid-Operated
Air Valve
Solenoid
Air Outlet to BPR
On Production
Air Line
Off Production Air
Regulator (solenoid not
actuated)
On Production Air
Regulator (solenoid
actuated)
Lead wires
ti17978a
Air Inlet
Installation
Do not install equipment approved only for non-hazardous locations in a hazardous area.
See the illustration on page 1. The 15K012 Kit is a preassembled module
which is not intended for use in a hazardous location. Install the kit in a
non-hazardous area only. Mount the panel vertically to protect components
from accumulation of air line contaminants and condensation. See the
mounting hole detail.
Connect a 5/32 in. (4 mm) OD air supply line to the air inlet elbow. Plumb
another 5/32 in. (4 mm) OD air line between the Outlet to BPR port and the
back pressure regulator (BPR), which is located in the hazardous area.
7.5 in. (191 mm)
8.0 in. (203 mm)
0.135 in. (3.4 mm)
Graco VFD: Connect one lead wire to Pin 26 on the VFD. Connect the other
lead wire to Pin 21. See VFD manual 311596 for specific wiring details.
Graco ACS: Connect one lead wire to +24 Vdc power supply. Connect second lead to Terminal 18 of the ACS module. Connect Terminal 17 of ACS to
24 Vdc common of the power supply. See ACS manual 3A0006 for specific wiring details.
3.5 in. (89 mm)
4.0 in. (102 mm)
0.25 in.
(6.3 mm)
Operation
Adjust the air pressure regulator to provide desired system pressures in each operating mode. The kit supplies
higher pressure air to the BPR in normal production mode, or lower pressure air in off production mode. The off production mode reduces energy use, paint shear, and pump/system wear during down times.
The kit allows operation with either solenoid activated or solenoid not activated in production mode. The solenoid
(0.50 W, 24 Vdc, .020 A) is actuated or deactuated by a 24 Vdc input/output signal from the VFD or ACS. When actuated, the solenoid supplies higher air pressure to the BPR to support production requirements. When the solenoid is
not actuated, lower air pressure is supplied to the BPR, reducing the system pressure maintained by the BPR.
Technical Data
Maximum Air Working Pressure. . . . . . . . . . . . . . . . . . . . 120 psi (0.8 MPa, 8.4 bar)
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Vdc
Air Porting Sizes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5/32 OD Tube (4 mm)
Cable Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 ft (2 m)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1 lb (0.95 kg)
Graco Information
For the latest information about Graco products, visit www.graco.com.
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor.
Phone: 612-623-6921 or Toll Free: 1-800-328-0211 Fax: 612-378-35
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2007, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco reserves the right to make changes at any time without notice.
Original instructions. This manual contains English. MM 311606
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
www.graco.com
Revised 9/2011