Instructions
15H885 Ethernet
Upgrade Kit
311612B
Allows a computer to communicate with the Graco Variable Frequency Drive (VFD).
Important Safety Instructions
Read all warnings and instructions in this manual
and in Variable Frequency Drive manual 311596.
Save these instructions.
Refer to SM-Ethernet User Guide by Control Techniques
for detailed installation and operation instructions.
Installation and Operation
Installation and Operation
Never install or remove the Ethernet module while
power is applied to the VFD.
1. Disconnect power to the VFD.
2. Disable the Hardware Enable input (press Secure
Disable switch).
3. Install Ethernet Module (C) into slot 2 on the VFD
(or slot 1 if slot 2 is not available).
C
save the default address, which will allow the
Ethernet module to use it at every power-up.
b. If IP address must be changed from the default,
change the address, then navigate to Pr MM.00
(Pr 16.00 if installed in slot 2), set its value to
1000, and press the red Stop/Reset switch.
c. For the module to start using the new address,
the module needs to be reset. Navigate to Pr
MM.00 (Pr 16.00 if installed in slot 2), set its
value to 1070, and press the red Stop/Reset
switch to reset the module.
Note that Code 1070 will cause the AppsLite module to reset as well, which will cause the pump to
stop running if it was not stopped prior to the reset.
DHCP (Dynamic Host Configuration Protocol)
DHCP server can provide the SM-Ethernet module
with an IP address:
a. Navigate to Pr MM.05 (Pr 16.05 if installed in
slot 2) and set it to 1, allowing use of DHCP.
4. Apply power to the VFD.
5. If this is the first time Ethernet module is installed
into the VFD, “SL2.dF” fault becomes active. Reset
the fault by pressing the red Stop/Reset switch.
6. Set IP address:
IP address is located in Pr MM.10, MM.11, MM.12,
and MM.13 (Pr 16.10, 16.11, 16.12, and 16.13 if slot
2 is used).
For a Fixed IP address:
a. Default IP address is 192.168.1.100. If default
IP address is acceptable, navigate to Pr MM.00
(Pr 16.00 if installed in slot 2), set its value to
1000, and press the red Stop/Reset switch to
b. Navigate to Pr MM.00 (Pr 16.00 if installed in
slot 2), set its value to 1000, and press the red
Stop/Reset switch to save the change, which
will allow the Ethernet module to use DHCP.
c. For the module to start using DHCP and to
acquire the IP address, the module needs to be
reset. Navigate to Pr MM.00 (Pr 16.00 if
installed in slot 2), set its value to 1070, and
press the red Stop/Reset switch to reset the
module.
Note that Code 1070 will cause the AppsLite module to reset as well, which will cause the pump to
stop running if it was not stopped prior to the reset.
2 311612B