Gossen Metrawatt ENERGYMID Operating Instructions

Operating Instructions
!
M16
1948
EBY
8
16
Prototype test certificate
Accuracy class / operating temperature
Pulse output
Type designation (article number)
Energy export / energy import
Nominal voltage Imin - In (Imax.) / nominal frequency
Warning
Protective insulation
Symbol for system type
Year o f m a n u f a c t u r e
Metrology mark
LED constant
2D code or calibration mark (feature P9)
EBY
8
16
Serial number
Up key
Enter key
Current/voltage transformer ratio
Anti-reversing for
the registers in both energy directions
Bidirectional meter
L2
L1
L3
Voltage Voltage
Current Current Current
Voltage
CurrentCurrent Current
N
Voltage
Voltage Voltage
Current Current Current
L3
L2L1 N
Current
CurrentCurrent
Ta ri f f
Connections
W1: LON W2: M-Bus W4: TCP/IP W7: Modbus RTU V1 ... 9: SØ pulse output
Tb Tn Ta
TCP/IP
R
L
+
24
23/25
U
t
External Voltage Source
Energy type*
Max. 40 V
R
L
24
23/25
U
t
AC/DC
Energy type*
Max. 375 V
~
24 V DC
I = max. 100 mA
I = max. 27 mA
U U
External Voltage Source
Standard pulse duration: 30 ms + 5%, interpulse period: > 30 ms V7/V8 pulse duration: 130 ms + 5%, interpulse period: > 130 ms
V3 / V4
Main display
(active energy* in kWh or MWh)
Auxiliary display 1 (active power* in kW or MW)
* EM238x transformer meter: CT and VT are taken into account
Auxiliary display 2 (e.g. IN, OUT for import or export) In case of error: error code alternates with current display
(M2/M3: reactive energy* in kVArh or MVArh)
(M2/M3: reactive energy or power in kVAr(h) or MVAr(h)*)
Power: negative sign for export
Enable Key
ENERGYMID
Electronic Energy Meters Direct conn. EM2281/EM2289 Transformer conn. EM2381/2387/2389
3-349-868-03
3/6.17
Technical data, dimensional drawings, connector pin assignments and order information can be found on the Internet at www.gossenmetrawatt.com under:
> Englisch > Products > Industrial Measurement > Energy Meters > EM2281 ... EM2389
1Scope of Delivery
1Energy meter 2 Operating instructions (German and English) 1 Calibration certificate (with feature P9 only)
Operating instructions including safety precautions can be found in each respective language at
www.gossenmetrawatt.com/english/produkte/ em2281-em2389.htm > Operating Instructions >> GB >> F >> I
2 Safety Precautions – Symbols
– Check the specified nominal voltage on the serial
plate before placing the instrument into service. – Observe maximum pulse output voltage. – When wiring the instrument, make sure the connec-
tor cables are not damaged, and that they are volt-
age-free. – If it can be assumed that safe operation is no longer
possible, the instrument must be immediately
removed from service (disconnect input voltage!).
Safe operation can no longer be relied upon if the
instrument demonstrates visible damage.
The device may not be placed back into operation
until troubleshooting and repair have been per-
formed, and calibration and dielectric strength have
been tested and approved at our factory or an autho-
rized service center. – Voltage conducting parts may be exposed if the
cover is opened.
If balancing, maintenance or repair of a live open
instrument is required, this may only be carried out by
trained personnel who are familiar with the dangers
involved. – When connecting measuring current, it is important
to provide for low-ohmic contact and to select an
appropriate conductor diameter.
Meanings of Symbols on the Instrument
DE MTP 17 B 002 MI-003 (EM228x) DE MTP 16 B 004 MI-003 (EM238x)
Prototype test certificate
Total insulation, protection class II device
Warning concerning a point of danger (attention, observe documentation!)
This device may not be disposed of with the trash. Further information can be accessed on the Internet at www.gossenmetrawatt.com by entering the search term “WEEE”.
Metrology mark with indication of year (M16) and register no. of the notified body for module D, country-specific calibration validity period
Marking with stamp of the federally approved test laboratory
(for recalibration only)
Tamper-Proof Sealing – Opening the Meter / Repairs Tamper-Proof Calibration Sealing
with Manufacturer’s Seal
(at the side) If the manufacturer’s seal is damaged or removed, all
guarantee claims are rendered null and void. The meter may only be opened by authorized, trained per-
sonnel in order to ensure flawless operation and to assure that the guarantee is not rendered null and void. If it can be ascertained that the
meter
has been opened by unauthorized personnel, no guarantee claims can be honored by the manufacturer with regard to personal safety, measuring accuracy, compliance with applicable safety measures or any consequential damages.
Tamper-proof sealing for the terminal cover may be attached either to the left or the right of the terminal cover.
3 Rating Plate Entries
4 Connector Pin Assignments and Wire Gauge
Note: Observe the wiring diagrams in the top and bot-
tom terminal covers.
Connections Direct, EM228X Transformer, EM238X
Current input Solid wire 16 sq. mm
Voltage input
SØ pulse output Bus output, tariff input (power utility pulse)
TCP/ IP
Fine wire 25 mm 16 mm2 with wire end ferrule Tightening torque: 3-4 Nm
N: solid wire 2.5 sq. mm Tightening torque: 0,4 Nm
Solid wire 2.5 sq. mm Tightening torque: 0,4 Nm
Solid wire 4 sq. mm
2
Tightening torque:
or

0,5-0,6 Nm
Solid wire 4 sq. mm Tightening torque: 0,5-0,6 Nm
Solid wire 2.5 sq. mm Tightening torque: 0,4 Nm
RJ45 (8P8C)
Meas. Inputs, EM228X Direct Meter (top & bottom terminals)
Meas. Inputs, EM238X Transf. Meter (bottom terminals)
Connections (top terminals)
5 Pulse Output – Bus Interfaces
Default setting: active energy Terminal 23 (S01) import, terminal 25 (S02) export
* Type of energy can also be selected with feature V2, V4.
Pulse Rates V1/V3,
Direct
Transformer
CT x VT = 1 (Q0) 1000 CTxVT=1(Q0)U6/7 CTxVT=1(Q0) U3 1000 CT, VT, progr. (Q1) 1000 CT, VT, progr. (Q1)U6/7 CT, VT, progr. (Q1)U3 CTxVT; CT, VT, fixed
(Q9)
2 10 1000 100 — — 1 1000 pls/kWh
11 100 100 10 — — 0.1 100 pls/kWh
101 1000 10 1 — — 0.01 10 pls/kWh
1001 10,000 1 100 — — 1 1000 10,001  100,000 100,0011,000,000
Underlined values are default values.
V7
fixed
1000 100 — — 1 1000 pls/kWh
1000
1000 1000
f (primary)
0.1 10 — — 0.1 100 pls/MWh
0.01 1 — — 0.01 10 pls/MWh
V8 V9,
[pulses per kWh]
100
1000
100
1000
100
1000
100
1000
100
1000
100
1000
V2/V4, programmable
fixed
U228x
U2381 / U238x f (secondary)
100 ...
50000 1

20000 1

50000 1

50000 1

20000 1

50000 1

1000 1000 1000 1000 1000 1000
f (primary)
     
10,000 pls/kWh 10,000 pls/kWh 10,000 pls/kWh 50,000 pls/kWh 50,000 pls/kWh 50,000 pls/kWh
pls/MWh
Repair and Replacement Parts Service Recalibration
Recalibration can be conducted at any time by our fed­erally approved test laboratory (EBY-8).
GMC-I Service GmbH Service Center Thomas-Mann-Str. 20 D-90471 Nuremberg, Germany Phone +49-911-817718-0 Fax +49-911-817718-253 e-mail service@gossenmetrawatt.com www.gmci-service.com
This address is only valid in Germany. Please contact our representatives or subsidiaries for service in other coun­tries.
Industrial Product Support
If required please contact:
GMC-I Messtechnik GmbH
Industrial Product Support Hotline
Phone +49-911-8602-500 Fax +49-911-8602-340 e-mail support.industrie@gossenmetrawatt.com
Edited in Germany • Subject to change without notice • PDF version available on the Internet
GMC-I Messtechnik GmbH Südwestpark 15 90449 Nürnberg, Germany Phone +49-911-8602-111 Fax +49 911 8602-777 e-mail info@gossenmetrawatt.com www.gossenmetrawatt.com
6 Display and Control Panel
6.3 Meanings of Symbols at the LCD
6.1 Test LEDs
The
test LEDs
are located above the control keys. The left­hand LED indicates energy export, and the right-hand LED energy import. LED blinking frequency increases along with measured power. If all currents are smaller than start­ing current, both LEDs light up continuously.
LED Constant
EM228x: 10,000 pls/kWh (direct meter) EM238x: 100,000 pls/kWh (transformer meter)
6.2 Resolution, Main Display (large characters) Energy Import
Intern wird mit erhöhter Auflösung gezählt. Hierdurch kann bei Mehrtarifnutzung das Gesamtregister in der letzten Stelle einige Digit über der Summe der Einzelregister liegen.
Meter / Feature
U2281, U2289
* An additional place to the right of the decimal point is included
** In the case of Q1, the secondary display can be calibrated Q0,
CTxVT
CTxVT
min.
max.
123456.78 23456.789 kWh
Q0
Q9
U238x
Q1 **
for the calibration display in the case of a main display which can be calibrated (Q0 or Q9). And thus the leading digit is eliminated in the case of an 8-place display.
for which reason display overflow is based on the secondary display. The normal display is shifted one place to the left if necessary.
1 1 12345.678 2345.6789 kWh
2 4 12345.678 2345.6789 kWh
5 40 123456.78 3456.7890 kWh
41 400 1234567.8 34567.890 kWh
401 4000 12345678 345678.90 kWh
4001 40000 123456.78 3456.7890 MWh
40001 400000 1234567.8 34567.890 MWh
400001 1000000 12345678 345678.90 MWh
1 4 u12345.67 ** kWh
5 40 u123456.7 ** kWh
41 400 u1234567 ** kWh
401 4000 u12345.67 ** MWh
4001 40000 u123456.7 ** MWh
40001 100000 u1234567 ** MWh
Normal dis­play
Calibration display *
Unit
u Main display
programmable CT/VT, see section 6.2). T1 ... T8: active tariff
Display of instantaneous power in 4 quad­rants: positive or negative active power P, positive or negative reactive power Q.
Correct connection: Continuous illumination of the phase symbols where P
Phase failure:
Symbol for affected phase is cleared from the display.
Incorrect phase sequence:
Phase symbols blink in following order: 3 - 2 - 1.
Negative power:
Respective phase symbol blinks.
For bus connection: appears when the meter transmits a data packet.
Key symbols for parameters configuration (see next column)
, not calibrated (feature Q1,
0
Key Symbols for Parameters Configuration
for Feature Q1 and V2, V4:
Key and 2nd key bit blanked: Parameter CT, VT and SØ configurable according to features, disabling with enable key.
Key displayed with one bit: Parameter CT, VT and SØ disabled, change after activating the enable key.
Remaining feature combinations:
Key blanked, 2nd key bit displayed: parameters CT, VT or SØ (which are or can be cali­brated) are preset at the factory, can be queried in the display mode, other parameters can be set by the user. Key displayed with 2nd bit: parameters which are or can be calibrated are preset at the factory; other parameters are disabled with the enable key and must be reset after clearing disabling.
Values which are preset at the factory are printed addi­tionally on the rating plate.
6.4 LCD Background Illumination
Background illumination is activated each time a key is activated. Background illumination goes off after about 2 minutes.
Background illumination colors indicate various display menus: – White: query menus
– Red: display of firmware version – Pink: parameters display and setting menu – Blinking red: in case of error
6.5 Key Operation
Querying Parameter Values
In addition to the LCD test, the UP and ENTER keys also make it possible to query currently set parameter val­ues, as well as to change parameters for certain fea­tures after first pressing the enable key.
If no keys are pressed for a period of 1 minute, the meter is returned automatically to its standard display.
Parameters can be changed for the following meters:
Parameters CT and VT for U238x with feature Q1, Parameter SØ for U228x/U238x with feature V2/V4
Further parameters in accordance with interface descri­tion.
a) Enabling Parameter Changes
The enable key makes it possible to enable or disable parameter changes. It’s located underneath the top ter­minal cover between terminals 21 and 22 and is acti­vated with a pointed object (e.g. a ballpoint pen).
Pressing the enable key activates the “change parame­ters” operating mode (key off):
Pressing the enable key again disables the “change parameters” operating mode (key on):
If no keys are pressed for a period of about 2 minutes, the “change parameters” operating mode is exited auto­matically and disabled (key on).
b) Changing Parameter Values
Briefly press the enabling key as described in point
a) above (this activates the “change parameters” operating mode).
See the operating overview on the back with regard
to changing the parameters.
Press and hold the ENTER key until the firmware ver-
sion appears (red background).
Press the UP key. The display test appears.
Briefly press and hold the ENTER key in order to dis- play two further test patterns.
Then repeatedly press the UP key until the parame-
ter to be changed appears at the display.
Briefly press the ENTER key in order to access the
setting menu.
The input cursor blinks at the leftmost entry posi-
tion. Each tine the ENTER key is pressed the cursor is advanced to the next position to the right. The value of the blinking digit can be increased by pressing the UP key. When the rightmost digit is ac­knowledged by pressing the ENTER key, the se­lected value is accepted and SAVinG appears briefly at auxiliary display 2. If no keys are pressed for a period of about one minute, the setting menu is exited.
Press and hold the ENTER key or wait for one minute
in order to change to the normal display.
Press the enable key once again. This disables the
“change parameters” operating mode. Disabling takes place automatically after 2 minutes.
7 Switching Amongst Tariffs
!!!!!!!!!
!!!
12345. 678
4567
kWh
W
1 n a
Calibration
Firmware
Normal display
Pulse rate
Pulse Duration
U238x with feature Q1
U238x with feature Q1
Feature V2/V4
Feature V2/V4
12345. 678
678
kVArh
VAr
1
n R
CT
VT
112345
.
6
7
8
4567
kWh
W
0 u t a-
12345
.
6
7
8
678
kVArh
VAr
0 u t R-
12345
.
6
7
8
1
2345.
678
kWh
kVArh
1 n
Reactive energy import, total (M2/M3)
1 123
4
2 1
234
W
3 1
234
Active power / phase
1 230.0
2
230
.
4
V
3 230
.
4
Phase voltages
23456.7
8
d 15 13 : 30
kWh
16.10.16
Query load profile
12345
.
6
7
8
1
2345.
678
kWh
kVArh
0 u t
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t1 : 0 u t
Export, total
Active energy import, total
Tariff (T1)
Tariff (T1)
Power displays M1/M3 only
1 1234
2
1234
VAr
3 1234
1 1 234
2
1234
VA
3 1234
1234
1234
VA
VAr
1234
Reactive power / phase
Apparent power / phase
Total power
Mains monitor M1/M3 only
12 400.4
23
400
.
4
V
31 : 400
.
4
Line-to-line voltage
Switching Between Active and Reactive Energy – Display Tests – Calibration Display – Setting Transformer and S0 Interface Parameters Switching Amongst Tariffs, Active and Reactive Energy, as well as Power Displays and Mains Monitor, Optional Display of the Load Profile
1
Total active power (kW) appears at auxiliary display 2
2
Not approved for billing purposes in Switzerland
Measuring Function (Display) Feature
Measured Quantity Accuracy M0 M1 M2
2
M3
2
Active energy (kWh) 1EP1...EP8, EPtot 1%
••••
Reactive energy (kVArh)
EQ1...EQ8, EQtot
2%
—— • •
Star voltage (V) U1N, U2N, U3N0.5% 1 d
—•—•
Delta voltage (V) U12, U23, U13 0.5% 1 d
—•—•
Current per phase (A) I1, I2, I3 0.5% 1 d
—•—•
N conductor current (A) I
N
1%  1 d, typ.
—•—•
Active power (kW) P1, P2, P3, Ptot 1% 1 d
—•—•
Reactive energy (kVAr) Q1, Q2, Q3, Qtot 1% 1 d
—•—•
Apparent power (kVA) S1, S2, S3, Stot 1% 1 d
—•—•
Power factor (cos phi)
PF1, PF2, PF3, PFtot
1% 1 d
—•—•
Frequency (Hz) f 0.05% 1 d
—•—•
RMS distortion value THD U1, U2, U3
—•—•
THD I1, I2, I3
—•—•
Blinking cursor
Identifies the current entry position. Position selection via ENTER. The value at the cursor position can be changed with the UP key (upward arrow).
Abbreviations
ct Transformation ratio, current I
N
N conductor current (calculated) SØ SØ pulse output THD Distortion component (for voltage and current) vt Transformation ratio, voltage
Features
M1 Multifunctional variant:
measurement of U, I, P, Q, S, PF, f, THD, In M2 Measurement of reactive energy M3 Multifunctional variant:
measurement of U, I, P, Q, S, PF, f, THD, In, reactive energy Q1 Programmable transformation ratios Q2 Fixed transformation ratios V2/V4 Programmable SØ V9 Customer-specific SØ rate W1 ... 7 Bus connections Z1 Load profile (only possible with bus)
Keys
ENTER key (press briefly)
ENTER key (press and hold)
UP key (press briefly)
long
Pulse source
4 pulse sources for pulse outputs SØ1 and SØ2:
– Active energy import (+) kWh or export – kWh – Reactive energy import (+) kVAr or export – kVAr
2 states: SØ switch “
C l o s e d” or “0 p e n”
Operating Overview
W
Feature V2/V4
Transformation ratios (EM238x only)
T4, feature W1 ... W7: T5 ... T8
Active energy import
Active energy export
Fixed display and illumination – live values
12345
.
6
7
8
1
2345.678
kWh
kVArh
1 n
Active energy import, total
12345
.
6
7
8
1
2345.678
kWh
kVArh
0 u t
Active energy export, total
Date (DD.MM.YY)
Increment (dt) / time (hh:mm)
Query load profile:
Each time the UP key is pressed, the next older load profile is displayed along with its date and time.
2 additional
Display test
Pulse rate
Number of pulses to be read out per kWh
Pulse duration
Duration of the pulse for the on state or the high value: at least 30 ms, e.g. 70 ms in case of processing problems
version
1 .0 0
2345. 6789
1234.5678
kWh
kWh
1234
W
2345. 6789
1234.5678
kWh
kWh
hold
10000
c t
10000
c t
set
1000
u t
1000
u t
set
50 1000
per kWh
50 1000
per kWh
set
50 0.100
sec
50 0.100
sec
set
50 srC1/2
+ / – kWh
50 srC1/2
+ / – kWh
set
SØ pulse output (with W0 only)**
test patterns
8888:88:88
8888:88:88
kWh
kWh
88:88:88
Information for manufacturing
All Tariffs *
Active tariff (here T1)
Reactive energy import, total (M2/M3 only) Reactive energy export, total (M2/M3)
Reactive energy, capacitive (M2/M3 only) Reactive power, capacitive (M2/M3 only)
Active energy export Active power export
Reactive energy, inductive (M2/M3 only) Reactive power, inductive (M2/M3 only)
Active energy import Active power import
* Max. 4 tariffs with S0 (V1 ... V9),
or 8 tariffs with bus (W1 ... W7)
T1 T1 T1 T1 T1T3 T1T3
T2T4 T2T4
long
** See corresponding interface description for additional menus in case of bus connections (feature W1 ... W7) – set load profile (Z1) can be found underneath query load profile.
Q0: CT = VT = 1 Q1: Programmable CT, VT Q9: Fixed CT, VT (default)
CT x VT 1 million
T1T3
T1T3
T1
T1
pf1 : 1
.
00
2
: 1. 00
3 : 1
.
00
Power factor / phase
pf : 1
.
00
50.00 H
z
Power factor
T1
T1
T1
T1
T1
T1
1 1
.
234
2
1. 234
A
3 1
.
234
1n1.234 A
50.00 hz
kW
dv1 : 0.120
2
: 0. 042
3 : 0
.
050
THD U1, U2, U3
d11 : 0
.
476
2
: 0. 120
3 : 0
.
092
THD I1, I2, I3
T1
T1
T1
T1
T1
T1
Phase currents
Line frequency
4-wire only4-wire only
4-wire only4-wire only4-wire only4-wire only
Active Tariff (here T1)
3/4-wire
2-wire
1234
1234
VA
VAr
1234
Apparent/reactive/active power
W
pf : 1
.
00
50.00 H
z
Power factor
T1
T1
123.4
1
.
234
V
A
50.00 H
z
Voltage/current/frequency
dv : 0
.
028
d1
: 0. 082
THD U, I
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 0 u t
Tariff (T2)
Tariff (T2)
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 0 u t
Tariff (T3)
Tariff (T3)
T1
T1
12345
.
6
7
8
1
234567
kWh
W
1 n a
1 5
dt dt
set
Load profile feature Z1 only, (only with bus feature: W1 ... W7)
2/3/4-wire
long
long
version
1
.
0 0
Set load profile
Normal display
Set demand integration period:
Increment dt can be set with the UP key to 1, 2, 3, 4, 5, 10, 15, 30 or 60 minutes. Integration takes place syn­chronous to clock time.
Setting menu, increment
T1 T1
1 5
T1
T1
T1
Query load profile, see above
long
12345
.
6
7
8
1
2345.
678
kWh
kVArh
t1 : 1 n
Reactive energy (M2/M3)
12345
.
6
7
8
1
2345.
678
kWh
kVArh
t1 : 0 u t
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 2 : 0 u t
Tar iff (T1)
Active energy
Tar iff (T2)
Tar iff (T2)
Feature W1 ... W7: T5 ... T8
T1
T1
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 3 : 0 u t
Tar iff (T3)
Tar iff (T3)
T1
T1
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 4 : 1 n
12345
.
6
7
8
1
2345
.
678
kWh
kVArh
t 4 : 0 u t
Tar iff (T4)
Tar iff (T4)
T1
T1
T2T4
T2T4
Q1: secondary calibrated
Tariff (T1)
N current (4-wire only)
Return to main menu
display
1.8.1
3.8.1
2.8.1
4.8.1
1.8.2
3.8.2
2.8.2
4.8.2
1.8.3
3.8.3
2.8.3
4.8.3
1.8.4
3.8.4
2.8.4
4.8.4
OBIS
1.8.1
3.8.1
2.8.1
4.8.1
1.8.2
3.8.2
2.8.2
4.8.2
1.8.3
3.8.3
2.8.3
4.8.3
1.8.0
3.8.0
2.8.0
4.8.0
Hardware Controlled
Tariff Input Tb Ta
Tariff 1 0 0
Tariff 2 0 1
Tariff 3 1 0
Tariff 4 1 1
Tariff inputs Ta and Tb are each connected with refer­ence to Tn.
Level 0: < 12 V Level 1: > 45 V (max. 265 V permissible!)
Software Controlled (not included in MID scope of approval)
In the case of meters with bus (featureW1 … W7), four further tariffs can be selected (software controlled).
8 Overview of Bus Systems
LON-Bus (feature W1) – M-Bus (feature W2) – Modbus TCP (feature W4) – Modbus RTU (feature W7)
Interface descriptions for energy meters with bus connection can be found on the Internet at www.gossenmetrawatt.com.
9 Error Messages – Reset
Display
If an error occurs, the respective error code and active energy or instantaneous power are displayed alter­nately.
Error Code Meaning Cause / Remedy
0L0volt 0VHi1
0 VHi 2
0 VHi3
1Hi1
1Hi2
1Hi3
0SYnc 0C0m
EnErgY
0cALib 0
LOVoLt error
In case of LOVoLt error (phase voltages too low), back­ground illumination, and if applicable the bus connec­tion, are deactivated. The load profile (featureZ1) cannot be viewed as long as the error is pending.
Phase voltage < 75% Check connection Maximum value for U1
exceeded Maximum value for U2
exceeded Maximum value for U3
exceeded Maximum value for I1
exceeded Maximum value for I2
exceeded Maximum value for I3
exceeded Frequency measuring
error Interface error
Meter defective Balancing required DC offset too high
AnALog
Check connection
Check connection
Check connection
Check connection
Check connection
Check connection
Meter connected to direct voltage
Check connection
Send device to repair service
10 Repair and Recalibration
Note for Test Laboratories Direct measuring meter: Testing is only possible with
source which supply currents superimposed on volt­ages.
Calibration Display
Display of energy values with increased resolution can be selected for testing or calibration purposes.
Press and hold the ENTER key once to this end. The
firmware version is displayed with a red back­ground.
Press the UP key twice. The calibration display ap-
pears with a pink background.
See section 6.2 with regard to resolution depending on type and feature.
Recalibration can be conducted at any time by our fed­erally approved test laboratory (EB-8) (see repair and service address on the back of the folder). Calibration capability is valid for 8 years in Germany.
11 Manufacturer’s Guarantee
The energy meters are guaranteed for a period of 3 years after shipment. The manufacturer’s guarantee covers materials and workmanship. Damages resulting from use for any other than the intended purpose or operating errors, as well as any and all consequential damages, are excluded.
12 Ambient Conditions
Operating temperature range –25 ... +55 °C
Storage temperature range –25 ... +70 °C
Relative humidity < 75% annual average
Elevation to 2000 m
Deployment Indoors
mechanical classification M1
electromagnetical classification E2
Protection (built-in device) front panel: IP 51
Protection terminal area IP20
13 Return and Environmentally Sound Disposal
The instrument is a category 9 product (monitoring and control instrument) in accordance with ElektroG (Ger­man electrical and electronic device law). This device is subject to the RoHS directive. Furthermore, we make reference to the fact that the current status in this regard can be accessed on the Internet at www.gos­senmetrawatt.com by entering the search term WEEE.