Gorman-Rupp Pumps SE1-1-2A3A User Manual

Page 1
OM−06489−01
August 15, 2011
INSTALLATION, OPERATION,
AND MAINTENANCE MANUAL
SE SERIES PUMP
MODEL
SE1 1/2A3A 115V 1P
THE GORMAN-RUPP COMPANY MANSFIELD, OHIO
GORMAN-RUPP OF CANADA LIMITED ST. THOMAS, ONTARIO, CANADA Printed in U.S.A.
www.grpumps.com
2011 The Gorman-Rupp Company
Page 2
Register your new
Gorman-Rupp pump online at
www.grpumps.com
Valid serial number and e-mail address required.
RECORD YOUR PUMP MODEL AND SERIAL NUMBER
Please record your pump model and serial number in the spaces provided below. Your Gorman-Rupp distributor needs this information when you require parts or service.
Pump Model:
Serial Number:
Page 3
TABLE OF CONTENTS
INTRODUCTION PAGE I − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY - SECTION A PAGE A − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION − SECTION B PAGE B − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL INFORMATION PAGE B − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PREINSTALLATION INSPECTION PAGE B − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP SEAL PAGE B − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LUBRICATION PAGE B − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP INSTALLATION PAGE B − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump Motor Specifications PAGE B − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump Dimensions PAGE B − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lifting PAGE B − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Positioning the Pump PAGE B − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Piping PAGE B − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL CONNECTIONS PAGE B − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump Power Cable Connections PAGE B − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Cable Grounding Test PAGE B − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liquid Level Devices PAGE B − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATION − SECTION C PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
GENERAL INFORMATION PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump Performance PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pump Controls PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP OPERATION PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Liquid Temperature and Overheating PAGE C − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Impeller Rotation PAGE C − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
STARTING, STOPPING, AND OPERATIONAL CHECKS PAGE C − 3. . . . . . . . . . . . . . . . . . . . . . . . .
Starting And Stopping PAGE C − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operational Checks PAGE C − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LIQUID LEVEL PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COLD WEATHER PRESERVATION PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LUBRICATION PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Draining Oil PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Condition Of Oil PAGE C − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adding Oil PAGE C − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING − SECTION D PAGE D − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL TESTING PAGE D − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test Equipment PAGE D − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltage Imbalance PAGE D − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor And Motor Power Cable Continuity PAGE D − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Insulation Resistance PAGE D − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram PAGE D − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP MAINTENANCE AND REPAIR - SECTION E PAGE E − 1. . . . . . . . . . . . . . . . .
STANDARD PERFORMANCE CURVE PAGE E − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP MODEL S1 1/2A3 115V 1P PARTS LIST PAGE E − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP AND SEAL DISASSEMBLY AND REASSEMBLY PAGE E − 4. . . . . . . . . . . . . . . . . . . . . . . . .
i
Page 4
TABLE OF CONTENTS
(continued)
PUMP END DISASSEMBLY PAGE E − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Strainer And Impeller Cover Removal PAGE E − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Draining Oil From Seal Cavity PAGE E − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Positioning Pump For Disassembly PAGE E − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Impeller Removal PAGE E − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Seal Removal PAGE E − 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PUMP END REASSEMBLY PAGE E − 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cleaning And Inspection Of Pump Parts PAGE E − 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Seal Installation PAGE E − 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Impeller Installation PAGE E − 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Impeller Clearance PAGE E − 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Strainer Installation PAGE E − 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MOTOR DISASSEMBLY PAGE E − 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Head And Power Cable Removal PAGE E − 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rotor And Shaft Removal PAGE E − 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bearing Removal PAGE E − 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centrifugal Switch Actuator Removal PAGE E − 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stator Removal PAGE E − 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MOTOR REASSEMBLY PAGE E − 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Stator Installation PAGE E − 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Centrifugal Switch Actuator Installation PAGE E − 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bearing Installation PAGE E − 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Rotor And Shaft Installation PAGE E − 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Head And Power Cable Installation PAGE E − 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VACUUM/PRESSURE TESTING PAGE E − 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LUBRICATION PAGE E − 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Seal Cavity PAGE E − 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor Cavity PAGE E − 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
Page 5
SE SERIES OM−06489

INTRODUCTION

Thank You for purchasing a Gorman-Rupp pump. Read this manual carefully to learn how to safely
install and operate your pump. Failure to do so could result in personal injury or damage to the pump.
This is an SE Series submersible pump. The basic material of construction is cast iron, with stainless steel hardware and fittings. The pump is light weight and portable, making it ideally suited to many domestic and industrial applications where low capacity dewatering or irrigation is required. The pump is powered by an integral, thermally­protected electric motor which is not explosion­proof. The pump may be operated fully or partially submerged. Do not operate the pump in a hazard­ous atmosphere.
All repairs to the pump motor must be performed by a Gorman-Rupp authorized submersible repair facility or the factory. Any repairs to the motor as­sembly performed by the customer or an unautho­rized repair facility negates the warranty.
Gorman-Rupp of Canada Limited
70 Burwell Road
St. Thomas, Ontario N5P 3R7
Phone: (519) 631−2870
The following are used to alert maintenance per­sonnel to procedures which require special atten­tion, to those which could damage equipment, and to those which could be dangerous to personnel:
Immediate hazards which WILL result in severe personal injury or death. These instructions describe the procedure re­quired and the injury which will result from failure to follow the procedure.
Because pump installations are seldom identical, this manual cannot possibly provide detailed in­structions and precautions for every aspect of each specific application. Therefore, it is the re­sponsibility of the owner/installer of the pump to ensure that applications not addressed in this manual are performed only after establishing that neither operator safety nor pump integrity are com­promised by the installation. Pumps and related equipment must be installed and operated ac­cording to all national, local and industry stan­dards.
If there are any questions regarding the pump or its application which are not covered in this man­ual or in other literature accompanying this unit, please contact your Gorman-Rupp distributor, or The Gorman-Rupp Company:
The Gorman-Rupp Company
P.O. Box 1217
Mansfield, Ohio 44901−1217
Phone: (419) 755−1011
or:
Hazards or unsafe practices which COULD result in severe personal injury or death. These instructions describe the procedure required and the injury which could result from failure to follow the procedure.
Hazards or unsafe practices which COULD result in minor personal injury or product or property damage. These instructions describe the requirements and the possi­ble damage which could result from failure to follow the procedure.
NOTE
Instructions to aid in installation, operation, and maintenance or which clarify a procedure.
PAGE I − 1INTRODUCTION
Page 6
SE SERIES OM−06489
SAFETY − SECTION A
This information applies to SE Series submersible motor driven pumps.
Because pump installations are seldom identical, this manual cannot possibly provide detailed instructions and pre­cautions for each specific application. Therefore, it is the owner/installer’s re­sponsibility to ensure that applications not addressed in this manual are per­formed only after establishing that nei­ther operator safety nor pump integrity are compromised by the installation.
Before attempting to open or service the pump:
1. Familiarize yourself with this man­ual.
2. Unplug the power cable from its re­ceptacle to ensure that the pump will remain inoperative.
3. Allow the pump to completely cool if overheated.
5. Close the discharge valve (if used).
This pump is not designed to pump vol­atile, explosive, or flammable materials. Do not attempt to pump any liquids for which you pump is not approved, or which may damage the pump or endan­ger personnel as a result of pump fail­ure. Consult the factory for specific ap­plication data.
The electrical power used to operate
this pump is high enough to cause inju­ry or death. Make certain that the power cable receptacle is properly grounded before installation.
The electrical power used to operate this pump is high enough to cause inju­ry or death. Make certain that the plug on the pump power cable is discon­nected from its receptacle before ser­vicing.
The electrical power used to operate this pump is high enough to cause inju­ry or death. Obtain the services of a qualified electrician to make all electri­cal connections.
Never attempt to alter the length or re­pair any power cable with a splice. The pump motor and cable must be com­pletely waterproof. Injury or death may result from alterations.
All electrical connections must be in ac­cordance with The National Electric Code and all local codes. If there is a conflict between the instructions pro­vided and N.E.C. Specifications, N.E.C. Specifications shall take precedence. All electrical equipment supplied with this pump was in conformance with N.E.C. requirements in effect on the
SAFETY
PAGE A − 1
Page 7
OM−06489 SE SERIES
date of manufacture. Failure to follow applicable specifications, or substitu­tion of electrical parts not supplied or approved by the manufacturer, can re­sult in severe injury or death and void warranty.
After the pump has been installed, make certain that the pump and all piping or hose connections are secure before op­eration.
Obtain the services of a qualified elec-
trician to troubleshoot, test and/or ser­vice the electrical components of this pump.
Do not attempt to lift the pump by the motor power cable or discharge hose. Attach proper lifting equipment to the lifting device fitted to the pump.
Pumps and related equipment must be installed and operated according to all na­tional, local and industry standards.
PAGE A − 2 SAFETY
Page 8
OM−06489 SE SERIES
INSTALLATION − SECTION B
GENERAL INFORMATION
Review all SAFETY information in Section A.
Since pump installations are seldom identical, this section is intended only to summarize general rec­ommendations and practices required to inspect, position, and arrange the pump and piping. If there are any questions concerning your specific instal­lation, contact your Gorman-Rupp distributor or the Gorman-Rupp Company.
Nuts, bolts and screws used on this pump are metric and do not match standard SAE measurement threads. If any threaded hardware is replaced, it must be replaced with metric type. Attempting to force in a fastener with SAE threads will damage the mating threads. An optional discharge adaptor is available to convert the metric pipe threads in the discharge flange to the SAE threads.
PREINSTALLATION INSPECTION
The pump assembly was inspected and tested be­fore shipment from the factory. Before installation, check for damage which may have occurred dur­ing shipment. Check as follows:
a. Inspect the pump assembly for cracks, dents,
damaged threads, and other obvious dam­age.
e. Carefully read all tags, decals, and markings
on the pump, and perform all duties indicated.
f. Check for oil leaks. If there is any indication of
an oil leak, see LUBRICATION at the end of this manual.
g. If the pump has been stored for more than 12
months, some of the components or lubri­cants may have exceeded their maximum shelf life. These must be inspected or re- placed to ensure maximum pump service.
If the maximum shelf life has been exceed, or if anything appears to be abnormal, contact your Gorman-Rupp distributor or the factory to determine the repair or updating policy. Do not put the pump into service until appropri­ate action has been taken.
PUMP SEAL
The pump is equipped with a single faced seal as­sembly. It is designed to prevent the liquid being pumped from entering the lubrication cavity at the impeller end. A lip seal is used to prevent moisture or lubrication oil from entering the motor housing cavity at the motor end.
The seal is lubricated by premium quality submers­ible pump oil.
LUBRICATION
The pump is equipped with one double-faced seal assembly. It is designed to prevent the liquid being pumped from entering the lubrication cavity at the impeller end, and to prevent moisture or lubrication oil from entering the motor housing cavity at the motor end.
b. Check for and tighten loose attaching hard-
ware. Since gaskets tend to shrink after dry­ing, check for and tighten loose hardware at the mating surfaces.
c. Inspect the power cable for cuts or any other
obvious damage.
d. Check that amperes, phase, voltage and
hertz indicated on the name plate match the ratings on the control box and incoming pow­er.
This pump was fully lubricated when shipped from the factory. However, lubrication levels must be
checked before installing the pump (see LU­BRICATION in the MAINTENANCE AND REPAIR MANUAL). If the oil level is abnormally low, deter-
mine the cause before putting the pump into ser­vice.
Refer to Table B-2 for the oil capacity and position for filling the seal cavity in the pump. Refer to LU- BRICATION, Section C for lubrication specifica­tions and intervals.
PAGE B − 1INSTALLATION
Page 9
SE SERIES
PUMP INSTALLATION
Pump Motor Specifications
See Tables B-1 and B-2 for pump specifications.
Table B-1. Pump Specifications
OM−06489
Model Voltage/
Phase
SE1 1/2A3A 115/1 YES 5.4 4.0 29.51/3 HP 3420
Pump Model
Voltage/
Phase
115/1SE1 1/2A3A
Liquid
Level
Control
50 (23) 6 (3) 7 (0,2) HORIZONTAL
Pump
HP/ KW
Table B-2. Additional Specifications
Approximate
Weight − Lbs. (kg)
Pump
Motor Speed (RPM)
50 Ft. Cable
When installing or servicing the pump or controls, follow all requirements for the installation of wiring or electrical equipment as outlined in the National Electric Code. Follow all safety require­ments. Failure to observe these require­ments could result in injury or death to personnel.
Full
Load
Amperes
Seal
Cavity
Lifting
Pump unit weights will vary depending on the mounting and drive provided. Check the shipping tag on the unit packaging for the actual weight, and use lifting equipment with appropriate capacity. Drain the pump and remove all customer-installed equipment such as suction and discharge hoses or piping before attempting to lift existing, installed units.
No
Load
Amperes
Oil Capacity
Ounces (Liters)
Locked
Rotor
Amperes
Motor
Cavity
−−−
Discharge
Size
(NPT)
1 1/2 INCH w/BARBED
ADAPTOR
Seal Cavity
Filling
Position
(H)orizontal
NOTE
Refer to the performance curve in Section E, Main­tenance and Repair when determining the most efficient piping installation. The recommended maximum submergence depth is 23 feet. Great­er depths could result in damage to the pump
Pump Dimensions
For the approximate physical dimensions of your pump, refer to the pump specification data sheet or contact your Gorman-Rupp distributor or the Gorman-Rupp Company.
PAGE B − 2 INSTALLATION
Do not attempt to lift the pump by the motor power cable or the piping. Attach proper lifting equipment or a rope to the lifting device fitted to the pump.
Positioning the Pump
The pump is designed to operate fully or partially submerged. The rotating parts are oil lubricated, and the motor is cooled by a constant flow of liquid or air discharged through internal passages.
The pump will operate if positioned on its side, but this is not recommended because the motor
Page 10
OM−06489 SE SERIES
torque could cause the pump to roll during opera­tion.
The pump should be independently secured and supported by the lifting device fitted on the pump. If the application involves a lot of debris, protect the pump from excessive wear and clogging by sus­pending it in a perforated barrel or culvert pipe. If
the bottom is heavily sludge-covered, rest the pump on support blocks or suspend it from a raft or similar device near the surface of the liquid. See Figure B-1 for typical pump installations.
All liquid entering the pump must pass through a strainer screen. Any spherical solids which pass through the screen will pass through the pump.
BY BAIL IN PERFORATED CULVERT PIPE ON SUPPORTS
Figure B-1. Typical Pump Installations
Piping
No suction piping is required in a standard installa­tion. This pump is provided with a suction strainer to prevent large solids from clogging the impeller.
To determine the size of the discharge connection, see Table B-1. Either hose or rigid pipe may be used. To facilitate mobility and maintenance, it is recommended that the discharge line be fitted with a quick disconnect fitting near the pump. The dis­charge line must be independently supported to avoid strain and vibration on the pump.
Either hose or rigid pipe may be used to make dis­charge connections. For maximum pumping ca­pacity, keep the line as short and straight as pos­sible. Elbows and fittings used in discharge lines increase friction loss, minimize their use.
It is recommended that a check valve or throttling valve be installed in the discharge line to control si­phoning or back flow when the pump is shut off.
ELECTRICAL CONNECTIONS
Install and operate this pump in accor­dance with the National Electrical Code and all local codes. Have a qualified electrician perform all checks and con­nections in this section.
Never attempt to alter the length of the pump motor cable or to repair it with a splice. The power cable and pump mo­tor must be kept completely waterproof.
PAGE B − 3INSTALLATION
Page 11
SE SERIES
OM−06489
Serious damage to the pump and injury or death to personnel can result from any alteration to the cable.
Field Wiring Connections (Incoming Power)
The pump is designed to operate with a 115 volt, 1 phase, 60 hertz power supply. The voltage avail­able at the motor must be within the range indi­cated in Table B-3.
To calculate the voltage available at the motor, pro­ceed as follows:
a. Measure the voltage while the pump is oper-
ating at full capacity. See wiring diagrams at the end of this section.
b. Next, subtract the motor cable voltage drop
(see Table B-4, Pump Power Cable Specifi- cations).
c. Do not continue to operate the pump if this
voltage is not within the recommended limits. Obtain the services of a qualified electrician to determine the correct field wiring size and oth­er details to ensure an adequate voltage sup­ply to the pump.
Pump Power Cable Connections
The electrical power used to operate this pump is high enough to cause inju­ry or death. Obtain the services of a qualified electrician to make all electri­cal connections. Make certain that the pump and receptacle are properly grounded.
The pump is provided with a 50 ft. (15,2 m) power cable (see Table B-4 for standard power cable specifications) with one end wired into the pump head. The other end terminates in a grounded power plug. Power to the receptacle must be di­rected through a fused circuit, and the receptacle must be controlled by a positive ON/OFF switch.
The use of extension cords is not recommended. If extension cords are used, they must have three­wire single phase construction and have adequate carrying capacity for their length.
Table B-3. Pump Voltage Requirements
NOMINAL
VOLTAGE
Pump
Model
When necessary to service the pump, make cer­tain the power cable is unplugged from the recep­tacle.
PHASE
1115 110 120
Voltage/
Phase
115/1
MINIMUM
VOLTAGE
Table B-4. Pump Power Cable Specifications
A.W.G
Cable
Size
16 13* SO 5.12SE1 1/2A3A 0.43 (11) 0.06 (1,5) 4.49
MAXIMUM
VOLTAGE
Cable
O.D.
Inches
(mm)
Conductor
Never attempt to alter the length or re­pair any power cable with a splice. The pump motor and cable must be com­pletely waterproof. Injury or death may result from alternations.
DC
Dia.
Inches
(mm)
Amp
Rating
(See Note
Below)
Cable
Type
Resistance
(ohms) at
225_C (77_F)
per 1000 ft.
(305 m)
Voltage
Drop
per 100 ft. (30,5m) at Max. Load
PAGE B − 4 INSTALLATION
Page 12
OM−06489 SE SERIES
Motor Cable Grounding Test
The electrical power used to operate this pump is high enough to cause inju­ry or death. Make certain that the power cable receptacle is properly grounded after installation.
Using a volt-ohm meter, connect one lead to the motor cable green/yellow ground lead. Connect the other lead to an uninsulated point on the pump body. The test circuit should close.
If the test circuit does not close, there is a defect in the cable or motor which must be corrected.
Liquid Level Devices
The pump is furnished with built-in devices to auto­matically regulate liquid level by filling and dewa-
tering. When liquid level reaches the on-point (up­per) device, the pump will switch on and continue to run until liquid level falls below the off-point (low­er) device.
NOTE
Distilled water or uncontaminated rain water may fail to provide conductivity necessary to trigger the automatic liquid level sensing devices built into the pump. If this occurs, ground the on-point assembly to convert the pump to manual operation, and install a float level control system.
Overheating will occur if the liquid level falls below the level required to cool the pump motor (see LIQUID LEVEL in Operation, Section C).
PAGE B − 5INSTALLATION
Page 13
SE SERIES OM−06489
OPERATION − SECTION C
GENERAL INFORMATION
Review all SAFETY information in Section A.
This pump is designed to handle most non-volatile, non-flammable liquids. Do not attempt to pump any liquids for which your pump is not approved, or which may damage the pump or endan­ger personnel as a result of pump fail­ure. Consult the factory for specific ap­plication data.
The pump motor and optional accesso­ries are not designed to be explosion­proof. Do not operate in an explosive at­mosphere.
Follow the instructions on all tags, labels and de­cals attached to the pump.
Pump Performance
Refer to the pump performance curve on page E-1 for the specific performance for your pump.
Pump Controls
The pump is driven by an integral 115 VAC, 60 hertz, 1 phase motor equipped with thermal motor overheat protection.
operational problems exists. See TROUBLE-
SHOOTING, Section D.
The pump motor is not designed to be explosion-proof. Do not operate in an explosive atmosphere. Improper opera­tion could result in destruction of equip­ment, injury or death to personnel.
See the operating instructions furnished with any optional accessoriesbefore attempting to start the pump.
PUMP OPERATION
Liquid Temperature and Overheating.
Overheated pumps can cause severe burns and injury. If the pump becomes overheated:
1. Stop the pump immediately.
2. Unplug the power cable from its re­ceptacle to ensure that the pump will remain inoperative.
3. Allow the pump to completely cool if overheated.
4. Close the discharge valve (if used).
5. Refer to instructions in this manual before restarting the pump.
When the pump power cable is plugged into an electrical receptacle, the pump will start and stop automatically as the liquid level rises and falls.
Short circuit protection for the electrical receptacle is provided by a customer-furnished fuse or break­er within the circuit. If the breaker trips repeatedly,
Do not start the pump more than 6 times per hour. If the motor does not cool be­tween starts it will overheat, resulting in damage to the motor windings.
PAGE C − 1OPERATION
Page 14
OM−06489 SE SERIES
The maximum liquid temperature for this pump is 120F (490C). Do not apply it at a higher operat­ing temperature.
Overheating can occur if the pump is made to start and stop repeatedly without time to cool off be­tween starts, the liquid level is allowed to fall too low to sufficiently cool the motor, or if the circuit breaker or fuse fails to provide adequate protec­tion. Operating the pump against a closed dis­charge valve for an extended period will also cause the pump to overheat.
Approach the pump cautiously after it has been running. Although the motor is cooled by the liquid being pumped, nor­mal operating temperatures can be high enough to cause burns. The tempera­ture will be especially high if operated against a closed discharge valve. Never operate against a closed discharge valve for long periods of time.
If overheating does occur, stop the pump immedi­ately and allow it to cool before servicing it. Ap-
proach any overheated pump cautiously.
4. Check the temperature before ser­vicing.
5. Vent the pump slowly and cau­tiously
6. Refer to instructions in this manual before restarting the pump.
Impeller Rotation
Check impeller rotation as follows before operation to ensure that the impeller is rotating in the correct direction.
While checking impeller rotation, secure the pump to prevent the power cable from coiling.
Suspend the pump from the lifting device fitted on the pump.
NOTE
For Autostart models, place a jumper wire across the on-point and off-point sensing devices before applying power to check pump rotation.
As viewed from the top, the pump should kick in a counterclockwise direction; this will indicate that impeller rotation is correct.
Overheated pumps can cause severe burns and injuries. If overheating of the pump occurs:
1. Stop the pump immediately.
2. Ventilate the area.
3. Allow the pump to completely cool.
PAGE C − 2 OPERATION
If the pump kicks in a clockwise direction, impeller rotation is incorrect and the pump must be re­turned to the factory or a Gorman-Rupp authorized Submersible Repair Center. Remove the jumper wire. Since the pump is powered by a single-phase motor, the direction of rotation can not be altered by interchanging motor leads at the control box.
Page 15
SE SERIES OM−06489
Operational Checks
Check the pump for proper operation when first started and periodically thereafter to identify minor
DIRECTION OF
KICKBACK
AT STARTUP
Figure C-1. Checking Pump Rotation
problems.
Check the pump for unusual noises or excessive vibration while it is operating. If noise or vibration is excessive, stop the pump and refer to the trou­bleshooting chart for possible causes.
Check the pump strainer screen for clogging caused by stones, sticks, or other debris. Clean the strainer screen when required. In some cases, stopping the pump momentarily may back flush the strainer screen, purging most of the debris from it. If this fails to clean the screen, remove the pump from the sump and remove the debris manu­ally. See PUMP DISASSEMBLY in the Mainte- nance And Repair manual.
STARTING, STOPPING, AND OPERATIONAL CHECKS
Starting And Stopping
Pump operation is controlled by the built-in liquid sensing devices. When liquid level reaches the on­point (upper) device, the pump will switch on and continue to run until liquid level falls below the off­point (lower) device.
NOTE
Distilled water or uncontaminated rain water may fail to provide conductivity necessary to trigger the automatic liquid level sensing devices built into the pump. If this occurs, ground the on-point assembly to convert the pump to manual operation, and install a float level control system.
It is recommended that a check valve or throttling valve be installed in the discharge line if there is any possibility of siphoning or back flow when the pump is shut off.
Never introduce air or steam pressure into the pump casing to remove a block­age. This could result in personal injury or damage to the equipment. If back­flushing is absolutely necessary, limit liquid pressure input to 50% of the maxi­mum permissible operating pressure shown in the pump performance curve (refer to the accompanying Parts List Manual).
Check the pump for overheating. Overheating can occur if the pump is made to start and stop repeat­edly without time to cool off between starts, the liq­uid level is allowed to fall too low to sufficiently cool the motor, or if the circuit breaker or fuse fails to provide adequate protection. Operating the pump against a closed discharge valve for an extended period will also cause the pump to overheat.
Check the oil level(s) as indicated in the following
LUBRICATION section.
PAGE C − 3OPERATION
Page 16
OM−06489 SE SERIES
LIQUID LEVEL
Overheating will occur if the liquid falls be­low the level required to cool the pump mo­tor.
The pump will operate fully or partially submerged. However, since the motor is cooled by the liquid being pumped, overheating will occur if the liquid is pumped below the required to cool the motor.
Auto-start models will shut down before the liquid level falls too low.
COLD WEATHER PRESERVATION
LUBRICATION
Do not remove plates, covers, gauges, pipe plugs or fittings from an over­heated pump. Vapor pressure within the pump can cause parts being disen­gaged to be ejected with great force. Al­low the pump to completely cool before servicing.
On a new pump, check the oil level in the seal cav­ity before initial startup. Drain and replace the oil af­ter the first 200 hours of operation. Following this, check the oil level in the seal cavity after the first two weeks of operation, and every month thereafter.
Before installing or removing the lubrication plug, always clean the area around the plug to prevent contamination.
Do not attempt to thaw the pump by us­ing a torch or other source of flame. This could damage gaskets, O-rings or heat the oil in the seal housing above critical temperatures, causing the pump to rup­ture or explode.
The pump will not freeze as long as the casing is submerged in liquid. If the casing is not sub­merged, or if the liquid begins to freeze, remove the pump from the sump or wet well and dry it thor­oughly. Run the pump for two or three minutes to dry the inner walls.
If the pump does freeze while it is out of the liquid, submerge it until thawed; if the liquid is near freez­ing, the pump must be submerged for an extended period of time. Check thawing by starting the pump and checking that the shaft rotates freely. If the pump remains frozen, allow additional thawing time before attempting to restart.
If submerging does not thaw the pump, move it into a warm area until completely thawed.
Draining Oil
Refer to Section E, Maintenance and Repair for drain plug location.
It is not necessary to drain the oil from the seal cav­ity unless the pump casing will be separated from the motor housing.
Lay the pump horizontal on a flat work surface with the seal cavity drain plug facing up. Remove the drain plug slowly to release any pressure. Install a short pipe nipple in the hole. Place a clean contain­er under the plug and roll the pump on its side to drain the seal housing.
Condition Of Oil
Check the condition of the oil drained from the pump. Clear oil indicates that the pump seal is functioning properly. If the oil is milky or contains a small amount of water, it must be changed.
If the oil contains a large amount of water, it must be changed, and the seal must be checked before the pump is put back in operation (refer to Section E, Maintenance and Repair).
PAGE C − 4 OPERATION
Page 17
SE SERIES OM−06489
Adding Oil
Refer to Table B-2 in INSTALLATION for pump oil capacities.
The grade of lubricant used is critical to the opera­tion of this pump. Use SAE No. 10 non-detergent oil. Oil must be stored in a clean, tightly closed con­tainer in a reasonably dry environment.
When lubricating the seal cavity, remove the lu­brication plug as indicated in Draining Oil. Add the non-detergent oil through this plug hole. With the pump positioned horizontally, sight down the plug hole and check that the oil level is high enough to cover the seal spring.
Install and tighten the lubrication plug.
PAGE C − 5OPERATION
Page 18
TROUBLESHOOTING − SECTION D
OM−06489SE SERIES
Review all SAFETY information in Section A.
The following precautions should be taken before attempting to service the pump; otherwise, injury or death could result.
1. Familiarize yourself with this man­ual.
2. Unplug the power cable from its re­ceptacle to ensure that the pump will remain inoperative.
3. Allow the pump to completely cool if overheated.
4. Check the temperature before opening any covers, plates or plugs.
Table 1. Trouble Shooting Chart
5. Close the discharge valve (if used).
The electrical power used to operate this pump is high enough to cause inju­ry or death. Obtain the services of a qu­alified electrician to troubleshoot, test and/or service the electrical compo­nents of this pump.
NOTE
Many of the probable remedies listed below re­quire use of electrical test instruments; for specific procedures, see ELECTRICAL TESTING following the chart.
TROUBLE POSSIBLE CAUSE PROBABLE REMEDY
PUMP FAILS TO START, OVERLOAD UNIT NOT TRIPPED (MANUAL MODE)
(AUTOMATIC MODE)
Power source incompatible with pump motor.
No voltage at line side of power cable connection.
Open circuit in motor windings or power cable.
Defective motor.
Liquid level device or control circuits improperly connected to main con­trol box.
Level sensing device(s) improperly positioned.
Level sensing device(s) fouled with mud or foreign material.
Float type sensing device(s) tangled or obstructed.
Correct power source.
Check power source for blown fuse, open breaker, broken lead, or loose connection.
Check continuity.
Check for and replace defective unit.
Check wiring diagrams; correct or tighten connections.
Position device(s) at proper level.
Clean sensing device(s).
Check installation for free movement of float.
TROUBLESHOOTING PAGE D − 1
Page 19
SE SERIES OM−06489
Table 1. Trouble Shooting Chart (cont.)
TROUBLE POSSIBLE CAUSE PROBABLE REMEDY
(AUTOMATIC MODE) (CONT’D.)
MOTOR RUNS, BUT PUMP FAILS TO DELIVER RATED DISCHARGE
Defective liquid level sensing de­vice(s) or control panel.
Discharge head too high.
Low or incorrect voltage.
Repair or replace defective unit(s).
Reduce head.
Measure control box voltage, both when pump is running and when shut-off.
PUMP RUNS WITH EXCESSIVE NOISE OR VIBRATION
Discharge throttling valve partially closed; check valve installed im­properly.
Discharge line clogged or re­stricted; hose kinked.
Liquid being pumped too thick.
Strainer screen or impeller clogged.
Insufficient liquid in sump or tank.
Worn impeller vanes; excessive im­peller clearance.
Pumping entrained air.
Damaged or unbalanced impeller.
Discharge piping not properly sup­ported.
Impeller jammed or loose.
Open discharge valve fully; check piping installation.
Check discharge lines; straighten hose.
Dilute liquid if possible.
Clear clog(s). Stop pump; back flow may flush away debris.
Stop pump until liquid level rises.
Check impeller and clearance. See PUMP END REASSEMBLY.
Check liquid level in sump; check position of pump and liquid level sensing device(s).
Replace impeller.
Check piping installation.
Check impeller.
Motor shaft or bearings defective.
Pump cavitation.
ELECTRICAL TESTING
If you suspect that pump malfunctions are caused by defects in the motor, power cable or control box, perform the following checks to help isolate the de­fective part.
Obtain the services of a qualified elec-
Disassemble pump and check mo­tor and bearings.
Reduce discharge head, or restrict flow on low head applications.
trician to troubleshoot, test and/or ser­vice the electrical components of this pump.
Be certain to refer to the wiring diagram(s) in the Installation Operations manual be­fore reconnecting any electrical compo­nents which have been disconnected.
TROUBLESHOOTINGPAGE D − 2
Page 20
OM−06489SE SERIES
Test Equipment
A volt/amp/ohmmeter and megohmeter of ade­quate range and quality will be required to conduct the following electrical tests. The suggested equip­ment indicated below is commercially available, or an equivalent substitute may be used.
Equipment Use
Ammeter To check AC Voltage
and current (amperage)
Ohmeter To measure resistance
(ohms) to ground
Motor And Motor Power Cable Continuity
To check continuity, zero-balance the ohmmeter set at the RX1 scale, and test as follows:
e. If no break is found in the power cable, con-
nect the test leads to the stator leads. If the test reading indicates an open or broken cir­cuit, there is an open circuit in the motor.
NOTE
It is recommended that a pump with a defective mo­tor be returned to Gorman-Rupp, or to one of the Gorman-Rupp authorized Submersible Repair Centers.
f. Be certain to reconnect all leads as indi-
cated in the Wiring Diagram, Figure D-1 and seal the connections with the male and fe­male connector sleeves before reassem­bling the pump head to the motor housing.
If insulation resistance is to be checked, do not as­semble the pump head to the motor housing at this time.
Insulation Resistance
a Disconnect the power cable plug from its re-
ceptacle.
b. Connect the test leads to the two power
cable leads (not to the green ground lead). If there is a high resistance reading on the ohmmeter, there is an open or broken circuit caused by a break in the power cable or mo­tor windings, or by a bad connection be­tween the motor and the power cable.
c. If an open or broken circuit is indicated,
check the power cable for obvious damage, and replace as necessary (see MAINTE- NANCE AND REPAIR). The entire motor power cable must be replaced; splicing or other means of repair are not recom­mended.
d. If the power cable appears undamaged, see
Head and Power Cable Removal, sepa­rate the pump head from the motor housing, and disconnect the power cable leads from the auto control device leads. Separately test each of the cable leads, (including the green ground lead) for continuity. If any of the power cable leads do not check out for continuity, replace the entire power cable.
To check insulation, zero-balance the ohmmeter set at the RX100K scale, and test as follows:
a. Disconnect the power cable plug from its re-
ceptacle.
b. Connect one test lead to the power cable
plug grounding prong and touch the other test lead to each of the two power prongs in turn.
c. The reading obtained will indicate resis-
tance values in both the power cable and the motor windings. If the resistance reading is infinity (1), the insulation is in good condi­tion. If the reading is between infinity (1) and 1 megohm, the insulation is acceptable but should be rechecked periodically. If the reading is less than 1 megohm, the insula­tion should be checked more closely. A reading of zero indicates that the power cable or the motor is grounded.
d. To determine whether the power cable or
the motor is grounded, separate the pump head from the motor housing (see Head
and power Cable Removal/Installation in MAINTENANCE AND REPAIR section) and
disconnect the power cable leads. Test the
TROUBLESHOOTING PAGE D − 3
Page 21
SE SERIES OM−06489
power cable leads and motor leads sepa­rately.
e. Be certain to reconnect all leads as indi-
cated in the Wiring Diagram, Figure D-1 and seal the connections with the male and fe­male connector sleeves before reassem­bling the pump head to the motor housing.
Figure D-1. Wiring Diagram
TROUBLESHOOTINGPAGE D − 4
Page 22
SE SERIES
OM−06489
PUMP MAINTENANCE AND REPAIR − SECTION E
MAINTENANCE AND REPAIR OF THE WEARING PARTS OF THE PUMP WILL MAINTAIN PEAK OPERATING PERFORMANCE.
STANDARD PERFORMANCE FOR PUMP MODEL SE1 1/2A3A 115V 1P
Based on 70F (21C) clear water at sea level with minimum suction lift. Since pump installations are seldom identical, your performance may be dif­ferent due to such factors as viscosity, specific gravity, elevation, temperature, and impeller trim.
Pump speed and operating condition points must be within the continuous per­formance range shown on the curve.
MAINTENANCE & REPAIR PAGE E − 1
Page 23
OM−01686 S SERIES PUMP
SECTION DRAWING

PARTS PAGE

Figure E-1. Pump Model SE1 1/2A3A 115V 1P
MAINTENANCE & REPAIRPAGE E − 2
Page 24
SE SERIES
PARTS LIST
Pump Model SE1 1/2A3A 115V 1P
(From S/N 1483930 Up)
ITEM
PART NAME PART
NO.
1 VOLUTE CASING 26815−033 −−− 1 2 IMPELLER 26815−045 −−− 1 3 SEAL ASSY 26815−115 −−− 1 4 DISCH FLANGE GASKET 26815−154 −−− 1
5 DISCH FLANGE 26815−432 −−− 1 6 HEX HD CAPSCREW 26815−308 −−− 2 7 LOCKWASHER 26815−368 −−− 2 8 HOSE ADAPTOR 26815−421 −−− 1
9 PUMP SPEC DECAL 38814−037 −−− 1 10 MOTOR HOUSING 26815−822 −−− 1 11 TERMINAL 26815−560 −−− 2 12 RD HD PHIL SCREW 26815−335 −−− 2 13 −W/LOCKWASHER 2 14 CENT SWITCH CONTACT 26815−194 −−− 1 15 RD HD PHIL SCREW 26815−340 −−− 2 16 −W/LOCKWASHER 2 17 FLAT WASHER 26815−374 −−− 2 18 MOUNTING PLATE 26815−163 −−− 1 19 HEX HD PHIL SCREW 26815−356 −−− 4 20 −W/LOCKWASHER 4 21 GROMMET 26815−292 −−− 1 22 GROUND WIRE 26815−601 −−− 1 23 TERMINAL 26815−562 −−− 1 24 RD HD PHIL SCREW 26815−340 −−− 1 25 −W/LOCKWASHER 1 26 FLAT WASHER 26815−374 −−− 1 27 HEAD 26815−007 −−− 1 28 AUTO CONTROL DEVICE 26815−902 −−− 1 29 CABLE LOCK 26815−441 −−− 1 30 POWER CABLE 26815−243 −−− 1 31 −W/CABLE LOCK PLATE 26815−451 −−− 1 32 HEX HD PHIL SCREW 26815−355 −−− 2 33 −W/LOCKWASHER 2 34 NAME PLATE 2613EF 13990 1 35 LIFTING ROPE 26815−650 −−− 1 36 HANDLE 26815−082 −−− 1 37 HEX HD PHIL SCREW 26815−355 −−− 2 38 −W/LOCKWASHER 2 39 MALE CONN SLEEVE 26815−927 −−− 3 40 PLUG 26815−925 −−− 3 41 FEMALE CONN SLEEVE 26815−926 −−− 3 42 RECEPTACLE 26815−924 −−− 3 43 PRESSURE TEST PLUG 26815−406 −−− 1 44 MALE CONN SLEEVE 26815−927 −−− 2 45 PLUG 26815−925 −−− 2
NUMBER
INDICATES PARTS RECOMMENDED FOR STOCK
MAT’L CODE
QTY ITEM
NO.
46 FEMALE CONN SLEEVE 26815−926 −−− 2 47 RECEPTACLE 26815−924 −−− 2 48 SOCKET 26815−929 −−− 2 49 SOCKET HOUSING 26815−928 −−− 2 50 PIN CONTACT 26815−922 −−− 1 51 PIN HOUSING 26815−922 −−− 1 52 ON POINT ASSY 26815−220 −−− 1 53 RD HD PHIL SCREW 26815−345 −−− 2 54 −W/LOCKWASHER 2 55 RD HD PHIL SCREW 26815−340 −−− 4 56 −W/LOCKWASHER 4 57 ON POINT LABEL 26815−481 −−− 1 58 OVERLOAD PROTECTOR 26815−202 −−− 1 59 RD HD PHIL SCREW 26815−342 −−− 2 60 FLAT WASHER 26815−374 −−− 2 61 HEAD GASKET 26815−156 −−− 1 62 BEARING SHIM 26815−134 −−− 1 63 BALL BEARING 23253−003 −−− 1 64 DUST SEAL 26815−123 −−− 1 65 CENT SWITCH ACTUATOR26815−184 −−− 1 66 ROTOR W/SHAFT 26815−851 −−− 1
67 SHAFT SLEEVE 26815−271 −−− 1 68 STATOR 26815−841 −−− 1 69 IMPELLER KEY 26815−054 −−− 1 70 OFF POINT LABEL 26815−482 −−− 1 71 BALL BEARING 23253−006 −−− 1 72 OFF POINT ASSY 26815−230 −−− 1 73 RD HD PHIL SCREW 26815−345 −−− 2 74 −W/LOCKWASHER 2 75 HEX HD PLUG 26815−400 −−− 1 76 VOLUTE CASING O-RING 26815−146 −−− 1
77 IMP COVER GASKET 26815−155 −−− 1 78 HEX HD PHIL SCREW 26815−350 −−− 4 79 −W/LOCKWASHER 1 80 IMPELLER COVER 26815−062 −−− 1 81 IMPELLER WASHER 26815−052 −−− 1 82 LOCKWASHER 26815−368 −−− 1 83 IMPELLER LOCK NUT 26815−053 −−− 1 84 STRAINER 26815−073 −−− 1 85 HEX HD PHIL SCREW 26815−350 −−− 3 86 −W/LOCKWASHER 3 87 HEX HD PHIL SCREW 26815−356 −−− 3 88 −W/LOCKWASHER 3
NOT SHOWN:
OM−06489
PART NAME PART
NUMBER
3 PRONG MALE PLLUG S2221 −−− 1
MAT’L CODE
QTY
MAINTENANCE & REPAIR PAGE E − 3
Page 25
OM−06489 SE SERIES

PUMP AND SEAL DISASSEMBLY AND REASSEMBLY

Review all SAFETY information in Section A.
Follow the instructions on all tags, label and decals attached to the pump.
This pump requires little service due to its rugged, minimum-maintenance design. However, if it be­comes necessary to inspect or replace the wearing parts, follow these instructions which are keyed to the sectional view (see Figure E-1) and the accom­panying parts list.
This manual will alert personnel to known proce­dures which require special attention, to those which could damage equipment, and to those which could be dangerous to personnel. However, this manual cannot possibly anticipate and provide detailed precautions for every situation that might occur during maintenance of the unit. Therefore, it is the responsibility of the owner/maintenance per­sonnel to ensure that only safe, established main- tenance procedures are used, and that any proce­dures not addressed in this manual are performed only after establishing that neither personal safety nor pump integrity are compromised by such prac­tices.
Before attempting to service the pump, disconnect or lock out incoming power and take precautions to ensure that it will remain inoperative. Close any valves in the discharge line.
The electrical power used to operate this pump is high enough to cause inju­ry or death. Make certain that the plug on the pump power cable is discon­nected from its receptacle before ser­vicing.
Nuts, bolts, and screws used on this pump are metric and do not match standard En­glish-measurement threads. If any threaded hardware is replaced, it must be replaced with metric type. Attempting to force in a fastener with English threads will damage the mating threads. An optional discharge adaptor is available to convert the metric pipe threads in the discharge flange to American pipe threads.
Use the lifting rope (35) to remove the pump from the wet well or sump, and move it to a location where the discharge line can be removed. It is not necessary to disconnect the discharge hose be­fore removing the pump.
Pump motor maintenance may be per­formed only by a Gorman-Rupp autho­rized repair facility or the factory. Other­wise, the pump warranty will be ne­gated, and damage to the pump, and in­jury or death to personnel can result. Contact the factory for the authorized repair facility closest to you.
PUMP END DISASSEMBLY
Follow the instructions on all tags, label and decals attached to the pump.
Do not attempt to lift the pump by the motor power cable or the piping. Use the lifting rope fitted to the pump. If chains or cable are wrapped around the pump to lift it, make certain that they are positioned so as not to damage the pump, and so that the load will be bal­anced.
Select a suitable location, preferably indoors, to perform the degree of maintenance required. If the motor housing is to be opened, the work must be done in a clean, well-equipped shop. All mainte­nance functions must be done by qualified person­nel.
Check the chart in TROUBLESHOOTING, Section D, to determine the nature of the pump problem. If
MAINTENANCE & REPAIRPAGE E − 4
Page 26
SE SERIES
OM−06489
the problem is mechanical in nature, such as worn pump parts, seal replacement, lubrication, etc., re­fer to PUMP END DISASSEMBLY for instructions.
If the problem is electrical, complete disassembly may not be required. Refer to Electrical Testing in TROUBLESHOOTING, Section B, and have a qualified electrician check the control box, cable and head. If the problem is determined to be in the motor, proceed with PUMP END DISASSEMBLY, followed by MOTOR DISASSEMBLY. Otherwise, see Head And Power Cable Disassembly.
Carefully inspect any O-rings or gaskets before re­moval and cleaning to determine if a proper seal and compression existed prior to disassembly. If sealing was faulty or questionable, the cause must be determined and corrected before reassembly. All gaskets and most O-rings must be replaced if disturbed (see the Parts List).
Strainer And Impeller Cover Removal
within a hot pump could cause the oil to spray out when the plug is removed. Re­move the plug slowly and permit pressure to vent to atmosphere.
Lay the pump on its side with the drain/fill plug (75) facing up. Clean any dirt from around the plug. Re­move the plug. Tip the pump and drain the seal oil into a clean container. Inspect the oil for water, dirt, or cloudy condition which could indicate lower seal failure or poor gasket seal.
Positioning Pump For Disassembly
It is recommended that the pump be positioned upside-down during disassembly. To hold the pump in the inverted position, rest the pump se­curely on blocks. Be careful not to damage the head (27) and power cable (30) while in this posi­tion.
Impeller Removal
To remove the strainer (84), disengage the hard­ware (85 and 86) securing the strainer to the impel­ler cover (77). To remove the impeller cover, re­move the hardware (78 and 79) securing it to the pump casing (1). Remove the cover gasket (77).
NOTE
Carefully inspect any O-rings or gaskets before re­moval and cleaning to determine if a proper seal and compression existed prior to removal. If seal­ing was faulty or questionable, determine the cause and correct it before reassembly. Replace any parts as required.
If the impeller (2) is clogged, the debris can usually be removed without further disassembly.
Draining Oil From Seal Cavity
The oil should be drained from the seal cavity be­fore performing any further disassembly
Wedge a piece of wood between the vanes of the impeller (2) and the pump casing to prevent shaft rotation. Remove the impeller hardware (81, 82 and 83).
Remove the wood block and use a suitable puller to pull the impeller off the shaft. Retain the impeller key (69).
Seal Removal
(Figures E-1 and E-2)
Remove the hardware (87 and 88) securing the pump casing (1) to the motor housing (10). Care­fully slide the pump casing, dust seal (64) and shaft sleeve (67) off the shaft. Press the shaft sleeve out of the pump casing from the back side.
NOTE
The shaft sleeve (67) may not come free of the shaft when the seal chamber is removed. It may be nec­essary to heat the sleeve and tap it off the shaft.
Remove the pump casing O-ring (76).
The lower stationary seal seat and element will re-
Let the pump cool before removing the seal cavity drain/fill plug. Pressure built up
MAINTENANCE & REPAIR PAGE E − 5
main in the pump casing bore when removed. To remove the stationary portion of the seal, place the
Page 27
OM−06489 SE SERIES
pump casing on a clean cloth with the seal bore side down. Use a drift pin or dowel to press on al­ternate sides of the stationary seat until the station­ary element and seat are forced out of the bore.
Inspect the dust seal (64) and, if replacement is re­quired, use a drift pin or dowel to press the dust seal out of the pump casing bore.
Lubricate the rotor shaft (66) adjacent to the bel­lows assembly, and pull the rotating portion of the seal from the shaft.
Slide a pair of stiff wires with hooked ends along the shaft and use the wires to pull the upper sta­tionary seal seat and element from the motor hous­ing (10).
NOTE
Do not disassemble the motor unless it is neces­sary and a clean, well-equipped shop is available. If the motor housing components are to be serviced, see MOTOR DISASSEMBLY in this section. Do not reassemble the pump end components at this time.
If no further disassembly is required, proceed to the appropriate areas in PUMP END REASSEMB- LY.
be determined and corrected before reassembly. Replace any parts as required.
Thoroughly clean all reuseable parts with a soft cloth soaked in cleaning solvent. Remove all O­rings and gaskets, and clean the sealing surfaces of dirt or gasket material. Be careful not to scratch gasket surfaces.
Most cleaning solvents are toxic and flammable. Use them only in a well ven­tilated area free from excessive heat, sparks, and flame. Read and follow all precautions printed on solvent contain­ers.
Inspect the rotor shaft (74) for damaged threads, scoring, or nicks. Remove nicks and burrs with a fine file or emery cloth to restore original contours. If the shaft is bent or severely damaged, the rotor and shaft must be replaced as an assembly (see
MOTOR DISASSEMBLY).
Seal Installation
(Figures E-1 and E-2)
PUMP END REASSEMBLY
NOTE
Reuse of old O-rings, gaskets, or shaft seal parts will result in premature leakage or reduced pump performance. It is strongly recommended that new gaskets and shaft seal assemblies be used during reassembly (see the parts lists for numbers).
Cleaning And Inspection Of Pump Parts
With the pump inverted, stuff a clean tissue into the stationary seal seat bore of the motor housing (10) or wrap a small rag around the shaft to prevent for­eign material from entering the motor cavity.
Carefully inspect any O-rings or gaskets before re­moval and cleaning to determine if a proper seal and compression existed prior to disassembly. If sealing was faulty or questionable, the cause must
The shaft seal assembly (3) should not be reused because wear patterns on the finished faces can­not be realigned during reassembly. This could re­sult in premature failure. If necessary to reuse an old seal in an emergency, carefully wash all me­tallic parts in fresh cleaning solvent and allow to dry thoroughly.
Handle the seal parts with extreme care to prevent damage. Be careful not to contaminate the preci­sion finished faces; even fingerprints on the faces can shorten seal life. If necessary, clean the faces with a non-oil based solvent and a clean, lint-free tissue. Wipe lightly in a circular pattern to avoid scratching the faces.
Inspect the seal components for wear, scoring, grooves, and other damage that might cause leak­age. If any components are worn, replace the com­plete seal; never mix old and new seal parts.
Install the shaft seal as illustrated in Figure E-2.
MAINTENANCE & REPAIRPAGE E − 6
Page 28
SE SERIES
OM−06489
ROTOR SHAFT
MOTOR HOUSING
BELLOWS AND CAGE ASSY
STATIONARY SEAT
PUMP CASING
DUST SEAL
STATIONARY SEAT
STATIONARY ELEMENT
ROTATING ELEMENT
SPRING
ROTATING ELEMENT
STATIONARY ELEMENT
SHAFT SLEEVE
IMPELLER KEY
Figure E-2. Seal Assembly
This seal is not designed for operation at temperatures above 120 F (49 C). Do not use at higher operating temperatures.
Do not unwrap a new seal assembly until time of installation. Cleanliness of seal components is criti­cal, especially the seal faces.
Carefully remove the material stuffed into the seat bore (or unwrap the shaft). Be sure no debris stopped by the material falls into the mounting plate.
NOTE
When pressing seal components onto the shaft, use hand pressure only. A push tube cut from a length of plastic pipe will aid in installing seal com­ponents. The I.D. of the push tube should be ap­proximately the same as the I.D. of the seal spring.
IMPELLER
Unpack the stationary seat and stationary element. Place a clean tissue over the sealing face of the sta­tionary element and subassemble the stationary element into the stationary seat.
Apply a light coating of oil to the seal seat bore in the motor housing (10). Position the stationary subassembly in the motor housing bore with the sealing face up and cover the seal face with a clean tissue. Use your thumbs to press the assembly into the bore. Apply equal pressure on opposite sides until the seat contacts the bore shoulder. Remove the tissue and inspect the seal face to ensure that it is clean and dry. If cleaning is necessary, use clean tissue to wipe lightly in a concentric pattern. After cleaning, apply a drop light oil to the seal face.
Unpack the rotating portion of the seal. Be certain the sealing faces of the rotating elements are free of grit or surface damage. Make sure the drive grooves of the rotating elements fully engage the drive lugs of the bellows retainer.
Apply a light coating of oil to the I.D. of the bellows. Slide the rotating portion of the seal onto the shaft until the upper sealing faces contact. The seal
MAINTENANCE & REPAIR PAGE E − 7
Page 29
OM−06489 SE SERIES
spring cannot be compressed and held in place until the pump casing is installed.
Unpack the lower stationary seat and element. Place a clean tissue over the sealing face of the sta­tionary element and subassemble the stationary element into the stationary seat.
Apply a light coating of oil to the seal seat bore in the pump casing (2). Position the stationary subas­sembly in the pump casing bore with the sealing face up and cover the seal face with a clean tissue. Use your thumbs to press the assembly into the bore. Apply equal pressure on opposite sides until the seat contacts the bore shoulder. Remove the tissue and inspect the seal face to ensure that it is clean and dry. If cleaning is necessary, use clean tissue to wipe lightly in a concentric pattern. After cleaning, apply a drop light oil to the seal face.
Inspect the face of the lower rotating element to make certain that it is clean. If cleaning is neces­sary, use a clean tissue to wipe lightly in a circular pattern. After cleaning, apply a drop of light oil to the seal face.
Carefully position the assembled pump casing, stationary seat and element over the shaft until the sealing faces contact. Secure the pump casing to the motor housing by tightening the hardware (87 and 88) in an alternating pattern.
Position the shaft sleeve (67) on the shaft with the chamfer on the O.D. toward the impeller end of the pump, and slide the sleeve onto the shaft until fully seated.
Postion the dust seal (64) in the pump casing bore as shown in Figure E-1 and press it into the pump casing until fully seated.
Install the impeller hardware (81, 82 and 83). Wedge a block of wood between the vanes of the impeller to prevent shaft rotation, and tighten the impeller lock nut (83).
Remove the block of wood, and turn the impeller to check for free rotation. Check the front clearance after installing the impeller cover (80).
Install the impeller cover gasket (77). Position the impeller cover (80) over the pump casing (1) and secure the cover with the hardware (78 and 79).
Impeller Clearance
For best performance, there should be a clearance of .010 to .020 inch (0,25 to 0,51 mm) between the impeller cover and the face of the impeller. Use a feeler gauge to measure this clearance.
If the impeller scrapes against the back of the im­peller cover when the impeller is turned by hand, remove the impeller cover and add another impel­ler cover gasket (77). Reinstall the impeller cover, and recheck clearance.
Strainer Installation
Inspect the strainer (84) for cracks, distortion or erosion, and replace it if defective.
Position the strainer squarely on the shoulder of the impeller cover (80) and secure with the hard­ware (85 and 86). Make certain that the strainer seats properly against the shoulder of the impeller cover.
See VACUUM/PRESSURE TESTING and LU- BRICATION before putting the pump back into service.
MOTOR DISASSEMBLY
Impeller Installation
Inspect the impeller (2) for cracks, broken vanes, or wear from erosion, and replace it if damaged. Clean the threads on the rotor shaft to remove any old thread locking material.
Install the impeller key (69) in the shaft keyway, align the impeller keyway, and press the impeller onto the shaft until it seats firmly against the shaft sleeve.
Disassembly of the motor is rarely required except to replace the rotor, stator, bearings or motor hous­ing. Do not disassemble the motor unless it is nec­essary and a clean, well-equipped shop is avail­able.
NOTE
It is recommended that a pump with a defective mo­tor be returned to Gorman-Rupp, or to one of the Gorman-Rupp authorized Submersible Repair Centers.
MAINTENANCE & REPAIRPAGE E − 8
Page 30
SE SERIES
The electrical power used to operate this pump is high enough to cause inju­ry or death. Make certain that the plug on the pump power cable is discon­nected from its receptacle before ser­vicing.
Carefully inspect any O-rings or gaskets before re­moval and cleaning to determine if a proper seal and compression existed prior to disassembly. If sealing was faulty or questionable, the cause must be determined and corrected before reassembly. Replace any parts as required.
Head And Power Cable Removal
Total disassembly of the head (27) and power ca­ble (30) is not always required. Disassemble and replace only the parts proven defective by inspec­tion or testing. See Electrical Testing in TROUBLESHOOTING.
The head and power cable may be serviced with­out disassembling the motor housing or pump end, or without draining the oil from the motor cav­ity. However, the oil must be drained before at­tempting to disassemble the motor housing and components.
Secure the pump in an upright position. Remove the hardware (19 and 20) securing the head to the motor housing (10). Raise the head for access to the electrical connections.
Pull the male and female connector sleeves (39 and 41) apart, then pull the lead plugs (40) from the auto control device (28) and ground lead (22) out of the cable receptacles (42). Disengage the white wire from the socket housing (49) to the on point assembly (52).
OM−06489
If necessary, remove the remaining hardware (37 and 38) securing the handle to the head.
If the auto control device (28) requires replace­ment, pull the male and female connector sleeves (44 and 46) apart, then pull the lead plugs (45) from the red stator lead and overload protector (58) out of the receptacles (47) on the auto control device leads. Disengage the hardware (55 and 56) secur­ing the auto control device to the mounting plate (18).
To remove the auto control device, separate any re­maining connector sleeves, plugs and recep­tacles. Separate the pin and socket housings (49 and 51). If necessary, remove the socket and pin contacts (48 and 50).
Remove the hardware (59 and 60), disconnect the motor lead and remove the overload protector (58).
Using caution not to strain any electrical leads, lift the mounting plate (18) while guiding the electrical leads through the grommet (21) to access the cen­trifugal switch contact (14). Remove the hardware (12 and 13) and separate the motor lead terminals (11) from the contact. Disengage the hardware (15 and 16) to remove the centrifugal switch contact.
Carefully remove the mounting plate; the bearing shim (62) will become a free part. If required, disen­gage the hardware (24 and 25) securing the green ground lead (22) to the mounting plate.
NOTE
The centrifugal switch actuator (65) is a press fit onto the rotor shaft and cannot be removed until the rotor is removed.
See Head And Power Cable Installation if no fur- ther disassembly is required.
Rotor And Shaft Removal
Remove the assembled head and power cable. Remove the head gasket (61).
To disconnect the power cable from the head, re­move the hardware (32 and 33) securing the cable lock (29) and handle (36) to the head. Remove the hardware (37 and 38) and pull the cable out of the head.
MAINTENANCE & REPAIR PAGE E − 9
See PUMP END DISASSEMBLY and remove all pump end components and Head And Power Cable Removal and remove the head and cable.
Carefully lift the rotor/shaft (66) with assembled bearings (63 and 71) and centrifugal switch actua­tor (65) from the motor housing. Use caution to pre­vent the rotor from falling on the stator windings. If
Page 31
OM−06489 SE SERIES
necessary, tap the impeller end of the rotor shaft with a block of wood or soft-faced mallet to loosen the seal between the bearing and the motor hous­ing bore.
Bearing Removal
To prevent damage during removal from the shaft, it is recommended that bearings be cleaned and inspected in place. It is strongly recommended that the bearings be replaced any time the shaft and rotor assembly is removed.
Before removing the bearings from the rotor shaft, clean and inspect the bearings in place as follows.
Clean the bearings thoroughly in fresh cleaning solvent. Dry the bearings with filtered compressed air and coat with light oil.
location of the actuator on the shaft. Use a suitable puller to remove the actuator from the shaft.
Stator Removal
Do not remove the stator (68) unless it is defective (open windings, insulation resistance low, or stator core damaged).
To remove the stator, position an expandable tool, such as a split disc, approximately 2 inches (51 mm) inside the stator, and expand it tightly and squarely on the I.D. Attach a lifting device to the lift­ing eye of the tool, and raise the assembly approxi­mately 1 inch (25 mm) off the work surface. Take care not to damage the stator end turns.
The motor housing (10) must be heated with a torch to expand it enough for the stator to be re­moved. Apply heat evenly to the outside of the mo­tor housing; excessive heat is not required. When the motor housing is sufficiently heated, use a soft­faced mallet to rap alternate edges of the motor housing, and walk" the stator out. Continue this process until the stator clears the motor housing.
Most cleaning solvents are toxic and flammable. Use them only in a well ven­tilated area; free from excessive heat, sparks, and flame. Read and follow all precautions printed on solvent contain­ers.
Rotate the bearings by hand to check for rough­ness or binding. If rotation is rough, replace the bearings.
The bearing tolerances provide a tight press fit onto the shaft and a snug slip fit into the upper and lower mounting plates. Replace the shaft and rotor (as an assembly) or the mounting plates if the proper bearing fit is not achieved.
If replacement is required, use a bearing puller to remove the bearings from the rotor shaft.
Centrifugal Switch Actuator Removal
Remove the snap ring securing the switch actuator to the shaft. Use a felt tip ink marker to scribe the
Use caution not to damage the stator end turns during removal from the motor hous­ing.
After the stator has been removed, wrap it in clean, dry rags or other suitable material until reassembly. The stator must be kept clean and dry. When han­dling the stator, do not set it on the end windings; lay it on its side.
Do not attempt to rewind the stator. Wind­ing tolerances and materials are closely controlled by the manufacturer, and any deviation can cause damage or operating problems. Replace the stator, or return it to one of The Gorman-Rupp Authorized Sub­mersible Repair Centers or The Gorman­Rupp factory, if defective.
MAINTENANCE & REPAIRPAGE E − 10
Page 32
SE SERIES
OM−06489
MOTOR REASSEMBLY
NOTE
Reuse of old O-rings, gaskets, shaft seal parts will result in premature leakage or reduce pump per­formance. It is strongly recommended that new gaskets and shaft seal assemblies be used during reassembly (see the parts lists for numbers).
Clean all gasket and O-ring surfaces, completely removing any old gasket and cement material. In­spect the sealing surfaces for burrs, nicks and pits which could cause a poor seal, and replace defec­tive parts as required.
Thoroughly clean the inside of the motor housing (10) with fresh solvent. The interior must be dry and free of dirt or lint.
that no damage has occurred during transit or han­dling.
NOTE
Remove any drops of varnish from the ends of the stator before installation to ensure proper stack-up height when assembled.
Position an expandable tool, such as a split disc, approximately 2 inches (51 mm) down inside the stator (opposite the lead wire end), and expand it tightly and squarely on the I.D. Attach a lifting de­vice to the lifting eye of the tool, and carefully lift the assembly. Take care not to damage the stator end turns. Slip a sleeve over the stator leads, or tape them together to protect them during installation.
NOTE
Stator installation involves heating the motor hous­ing. This process must be done quickly to allow the stator to slide into the motor housing before the housing cools.
Most cleaning solvents are toxic and flammable. Use them only in a well ven­tilated area, free from excessive heat, sparks, and flame. Read and follow all precautions printed on solvent contain­ers.
Stator Installation
NOTE
Stator installation involves heating the motor hous­ing. This process must be done quickly, therefore it is recommended that these steps be performed by two people to promote efficient installation of the stator.
After the motor housing is thoroughly cleaned, po­sition it on a flat surface with the discharge end down. Do not unwrap the stator (68) until the motor housing has been prepared for stator installation. The stator must be kept clean and dry. When han­dling the stator, do not set it on the end windings; lay it on its side and block it from rolling.
Test the new stator as indicated in Electrical Test- ing in TROUBLESHOOTING, Section B, to ensure
Heat the motor housing with a torch to expand it enough for the stator to be installed; when heating the motor housing, make sure that the stator is clear to avoid a fire hazard or damage to the wind­ings. Apply heat evenly to the outside of the hous­ing; excessive heat is not required.
When the motor housing is sufficiently heated, po­sition the stator so that the leads are in line with the terminal opening. Carefully lower the stator into the motor housing until fully seated against the hous­ing shoulder. Be careful not to damage the stator lead insulation during reassembly. If the stator cocks" in the motor housing, remove it and try again.
After the stator is fully and squarely seated on the motor housing shoulder, remove the expandable disc tool. Untape or remove the protective sleeve from the stator leads.
Cover the motor housing with a clean, lint-free cloth while the rotor is being assembled.
Centrifugal Switch Actuator Installation
Press the centrifugal switch actuator (65) on the ro­tor shaft so that the actuator flange sits just flush with the snap ring groove. The lower side should
MAINTENANCE & REPAIR PAGE E − 11
Page 33
OM−06489 SE SERIES
align with the scribed mark on the shaft. Secure the switch with the snap ring.
Bearing Installation
Inspect the rotor shaft for damaged threads, scor­ing in the seal area, and a nicked or damaged keyway. If the bearings were removed, inspect the bearing areas for scoring or galling. Remove nicks and burrs with a fine file or emery cloth. Inspect the rotor area for separated laminations. If the shaft is bent or damaged, or if the laminations are sepa­rated, replace the shaft and rotor (a single assem­bly).
To prevent damage during removal from the shaft, it is recommended that bearings be cleaned and inspected in place. It is strongly recommended that the bearings be replaced any time the shaft and rotor assembly is removed.
The bearings may be heated to ease installation. An induction heater, hot oil bath, electric oven, or hot plate may be used to heat the bearings. Bear­ings should never be heated with a direct flame or directly on a hot plate.
After the bearings have been installed and allowed to cool, check to ensure that they have not moved out of position in shrinking. If movement has oc­curred, use a suitably sized sleeve and a press to reposition the bearings. Make certain that they are seated squarely against the shaft shoulders.
If heating the bearings is not practical, use a suit­ably sized sleeve and an arbor (or hydraulic) press to install the bearings on the shaft.
When installing the bearings onto the shaft, never press or hit against the outer race, balls, or ball cage. Press only on the inner race.
Rotor And Shaft Installation
With the stator installed and the motor housing up­right, carefully ease the rotor/shaft (66) and as­sembled bearings through the stator so that the lower bearing (71) seats squarely in the bore of the motor housing (10).
Wrap the impeller end of the shaft in a clean cloth to protect it during installation of the head and power cable.
NOTE
If a hot oil bath is used to heat the bearings, both the oil and the container must be absolutely clean. If the oil has been previously used, it must be thor- oughly filtered.
Heat the bearings (63 and 71) to a uniform tem­perature no higher than 250F (120C). Slide the bearings onto the shaft, one at a time, until they are fully seated against the shaft shoulders. This should be done quickly, in one continuous motion, to prevent the bearings from cooling and sticking on the shaft.
Use caution when handling hot bearings to prevent burns.
Head And Power Cable Installation
The electrical power used to operate this pump is high enough to cause inju­ry or death. Make certain that the plug on the pump power cable is discon­nected from its receptacle.
Clean the exterior of the power cable with warm water and mild detergent. Check for obvious physi­cal damage. Check the cable for continuity and in­sulation resistance (see Electrical Testing in TROUBLESHOOTING). Do not attempt repairs except to cut off either end of the cable; splicing is not recommended. Reinstall any wire tags or ter­minals which may have been removed.
MAINTENANCE & REPAIRPAGE E − 12
Page 34
SE SERIES
Never attempt to alter the length or re­pair any power cable with a splice. The pump motor and cable must be com­pletely waterproof. Injury or death may result from alterations.
Secure the centrifugal switch contact (14) to the mounting plate (18) with the hardware (15 and 16). Secure the terminals (11) of the blue stator leads to the centrifugal switch contact.
Inspect the mounting plate grommet (21) and re­place if required. Feed the remaining leads from the stator through the grommet and mounting plate.
Position the bearing shim (62) on the upper bear­ing (63), then carefully slide the mounting plate down over the bearing shim and upper bearing. Make certain that the bearing seats squarely in the bore.
Install the head gasket (61) on the mounting plate.
OM−06489
Install the cable lead plugs (40) in the stator lead receptacles (42), then secure with the male and fe­male connector sleeves (39 and 41). Make certain that the green power cable ground lead is securely connected to the short ground cable, and that the ground cable is firmly attached to the mounting plate.
Refer to the wiring diagram in Section D, Trouble- shooting, and make all electrical connections. Cover all electrical lead connections with the male and female connector sleeves.
NOTE
Check the wiring diagram in Troubleshooting, Section D to make sure that all electrical leads are
correctly installed.
Position the head (27) on the motor housing (10) and secure with the hardware (19 and 20).
See PUMP END REASSEMBLY to reassemble the pump end components.
See VACUUM TESTING followed by LUBRICA- TION.
Secure the overload protector (58) to the mounting plate with the hardware (59 and 60). Secure the green ground lead to the mounting plate with the hardware (24, 25 and 26).
Connect the terminal of the green ground wire to the mounting plate and secure with the hardware (23, 24 and 25). Make certain the terminal makes good contact with the plate.
Feed the red, yellow, white and gray auto control device leads from the bottom of the device up through the hole in the device. If required, install the socket contacts (48) on the white and gray auto control device leads, and install the contacts in the socket housing (49). Secure the auto control de­vice to the mounting plate with the hardware (55 and 56).
Install the cable lock (28) on the power cable (37). Lubricate the bore of the head (27) and install the power cable through the bore. Secure the cable to the head with the cable lock plate (31) and hard­ware (37 and 38). Secure the cable lock and han­dle (36) to the head with the hardware (32 and 33).
VACUUM/PRESSURE TESTING
To ensure the water-tight integrity of the pump, it is recommended that the motor and seal cavities be vacuum and pressure tested any time the seal and/ or motor are serviced. The seal cavity must be pressurized to prevent separation of the seal faces or unseating the stationary seal seat between the seal and motor cavities. Use a manometer with a range of 30 to 0 to 30 inches of mercury to perform the vacuum test. Do not use a vacuum gauge. Vac­uum gauges are not sensitive enough to detect mi­nor leaks.
Drain all of the oil from both the seal and motor cavities before performing the test. Oil within the motor cavity will be drawn into the system, result­ing in damage to the vacuum pump or manometer.
It is recommended that a vacuum pump be used to draw the vacuum on the motor cavity. If a vacuum pump is not available, a compressor/venturi sys­tem may be used. If the compressor/venturi cannot draw the vacuum level shown in Table E-1, draw the motor cavity vacuum down as far as the system
MAINTENANCE & REPAIR PAGE E − 13
Page 35
OM−06489 SE SERIES
will allow, then pressurize the seal cavity so the dif­ferential between the two cavities is the same as the differential between the readings shown in the table.
If a compressor/venturi system is used, install full­closing ball-type shutoff valves with quick-discon­nect fittings in the pipe plug holes in both the motor
Vacuum Pump
Venturi
Air Compressor
Manometer
Tee
Quick Disconnect Fitting
and seal cavities. This will allow the pressure (or vacuum) to be maintained while using the com­pressor to perform the second portion of the test.
Figure E-3 shows a simple schematic for setting up either a vacuum pump or a venturi/compressor test system.
Quick Disconnect Fitting
Full-Closing Ball-Type Shutoff Valve
Use Compressor to Pressure Test Seal Cavity
Vacuum Test Motor Cavity
Submersible Pump
Figure E-3. Vacuum/Pressure Test System
Table E-1 shows the motor cavity vacuum and seal cavity pressure readings for the test, and the dura­tion to maintain each reading. Any change in the
Table E-1. Vacuum/Pressure Test Data
Pump
Model
S1 1/2A3A 30 1 15 1
Motor Cavity
Vacuum
(In. Hg.)
(Minutes)
LUBRICATION
Seal Cavity
Check the oil level in the seal cavity before initial startup, after the first two weeks of operation, and every month thereafter.
readings during the test indicates a leak which must be identified and corrected before putting the pump back into service.
Duration
seal cavity can cause hot oil to be ejected as the plug is removed.
To check the seal cavity oil, lay the pump on its side and remove the seal cavity drain/fill plug (75) in the motor housing. Tip the pump and drain off a small amount of oil into a transparent cup. If the oil level is abnormally low, or the color milky or dark, refer to Draining Oil From Seal Cavity in this section for instructions and troubleshooting tips.
Seal Cavity
Pressure
(PSI)
Duration
(Minutes)
Check the oil level only when the pump is cool. If the oil level plug is removed when the pump is hot, pressure in the
MAINTENANCE & REPAIRPAGE E − 14
Page 36
SE SERIES
OM−06489
To fill the seal cavity, remove the seal cavity drain/fill plug (75) and add 7 ounces (0,2 liter) of SAE No. 10 non-detergent oil. Refer to Section B, Installation , for positioning of the pump during filling of the seal cavity. Apply ‘Loctite Pipe Sealant With Teflon No.
592.’ or equivalent to the threads of the pipe plug,
before reinstalling the plug.
Motor Cavity
The motor cavity is cooled by the liquid being pumped. No further lubrication is required.
MAINTENANCE & REPAIR PAGE E − 15
Page 37
For U.S. and International Warranty Information,
Please Visit www.grpumps.com/warranty
or call:
U.S.: 419−755−1280
International: +1−419−755−1352
For Canadian Warranty Information,
Please Visit www.grcanada.com/warranty
or call:
519−631−2870
THE GORMAN-RUPP COMPANY MANSFIELD, OHIO
GORMAN-RUPP OF CANADA LIMITED ST. THOMAS, ONTARIO, CANADA
Loading...