Goodman WME0500S User Manual

Page 1
Catalog 604-9 Magnitude
®
Magnetic Bearing Centrifugal Chillers
Model WME 400 to 1500 Tons (1400 to 5300 kW) HFC-134a Refrigerant
Page 2
Introduction..................................3
Technology That Just Makes Sense .............3
Features and Benets Summary ................3
Features and Benets .........................4
The Compressor Technology ...................4
Integrated Variable Frequency Drive .............5
The Control Technology .......................5
Certications and Standards....................6
Factory Testing ..............................7
Dimensions and Weights.......................8
Unit Dimensions and Shipping Weight ............8
Drawing Notes ..............................9
Options and Accessories .....................10
Unit Options ...............................10
Vessel Options .............................10
Controls Options ............................10
Electrical Options ...........................11
Special Order Options........................11
Table of ConTenTs
Table of ConTenTs
Refrigeration Diagram ........................12
Application Considerations....................14
Location Requirements.......................14
Vibration Mounting ..........................14
System Design .............................14
Optimizing Efciency . . . . . . . . . . . . . . . . . . . . . . . . 14
Evaporator ................................15
Condenser ................................15
Retrot Knockdown .........................18
Engineering Guide Specications ..............20
Manufactured in an ISO 9001 & ISO 14001 certied facility
©2015 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to make changes in design and construction at any time without notice.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 2 www.DaikinApplied.com
Page 3

InTroduCTIon

InTroduCTIon
WMC 100 - 400 Tons
Magnitude® Magnetic Bearing Chillers
Model WMC 145-400D
WME 400 - 1500 Tons
Model WME 500-700S
100 300 500 700 900 1100 15001300

Technology That Just Makes Sense

The industry’s next generation of centrifugal chillers is here today with Daikin Magnitude® chillers. The new technology begins with centrifugal compressors utilizing magnetic bearings for oil-free operation, integral variable-frequency
drives, and direct drive technology. The high efciency compressor is matched with highly efcient heat exchanges
to make an impressive chiller. Magnitude® chillers have many important features:
State-of-the-art magnetic bearing compressor with oil-free technology
Unit-mounted Variable Frequency Drive
Positive pressure design
Hermetic, permanent magnet, direct-drive motor
User-friendly MicroTech® controls
Open Choices™ feature for BAS of your choice
HFC-134a refrigerant (Zero ozone depletion and no refrigerant phase out)
AHRI cer tication
Features and Benets Summary
The Compressor Technology
Magnetic bearing system that results in greater efciency and reliability, more sustainable performance, reduced operating and maintenance costs, and low vibration and sound levels compared to traditional oil centrifugals.
Integrated Variable Frequency Drive (VFD)
• Unit-mounted VFD modulates compressor speed to
obtain optimum efciency at all load and lift conditions.
The Control Technology
• Onboard digital electronics provide smart controls and include a regenerative power system, user-friendly operator interface, RapidRestore® and RideThrough options, and Open Choices™ BAS exibility.
Certications and Standards
• Meets ASHR AE Std. 90.1, AHRI 550/590 and IBC/ OSHPD Seismic, and contributes to LEED® credits.
Factory Testing
• Ensures trouble free startup and reliable operation.
Model WME 1000-1500D
®
www.DaikinApplied.com 3 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 4

The Compressor Technology

Model WME’s exceptional efciency and reliability is due
to its cutting-edge permanent magnet motor and magnetic bearing compressor technology. A digitally-controlled magnetic bearing system replaces conventional oil lubricated bearings and a direct drive motor eliminates the need for a lubricated gear box. The compressor shaft, shown in Figure
Figure 1: Magnetic Bearing Compressor Shaft

feaTures and benefITs

feaTures and benefITs
1, levitates on a magnetic cushion and is the compressor’s only major moving component. Sensors at each magnetic bearing provide real-time feedback to the bearing control system. As a result of this sophisticated design, model WME has many advantages over chillers with traditional centrifugal compressors.
2
1
3 4
Oil-Free Compressor Design Benets
No Oil Management System = Greater Reliability
With magnetic bearings operating in a magnetic eld
instead of oil-lubricated bearings, the oil handling equipment is removed. No need for:
oil pumps
oil reservoirs
oil coolers
oil lters
water regulating valves
oil relief valves
oil storage and disposal
oil system controls, starter, piping, heaters, etc.
that are needed to maintain oil quality. These devices can
be a fault source in traditional chillers, and removing them
signicantly increases unit and system reliability.
5
1. Impeller
2. Front Radial Bearing
3. Permanent Magnet Direct Drive Motor
4. Rear Radial Bearing
5. Thrust Bearing
Totally Oil-Free Operation = Greater Efciency
The use of oil-free magnetic bearing technology
signicantly increases chiller efciency by reducing
frictional losses within the bearing system.
In addition, efciency improvements can be realized since
there is no oil to coat the heat transfer surfaces.
No Oil Loss = Sustainable Performance
With no possibility of oil loss at light loads or due to
worn seals, the original energy saving efciency can be
maintained for the life of the chiller.
No Oil System = Low Vibration & Sound Levels
With the use of magnetic bearings, the compressor vibration levels are extremely low, minimizing vibration that could be transmitted to the structure.
With low vibration levels, sound levels are lower compared to traditional centrifugal chillers.
No Oil System = Reduced Maintenance Costs
With oil removed from the system, oil samples, oil changes,
oil system maintenance, oil lter changes, and leaks are
eliminated.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 4 www.DaikinApplied.com
Page 5
feaTures and benefITs
Additional Compressor Design Benets
Model WME’s magnetic bearing compressor design offers
many benets not only because of its oil free design but also
because of its use of a positive pressure refrigerant and a variable frequency drive.
Environmentally Friendly
Over time negative pressure chillers (such as those using HCFC-123) may draw air and moisture into the system, which
can signicantly increase energy consumption. Since the
Magnitude® WME chiller uses a positive pressure refrigerant
(HFC-134a), the industry-leading efciency can be maintained
for the life of the chiller. In addition, HFC-134a has no ozone depletion potential and no phase-out schedule per the Montreal protocol unlike HCFC type refrigerants used in low pressure designs.
Low Operating Costs
Model WME offers world-class full and part load efciency
due to its advanced permanent magnet motor and magnetic
bearing VFD compressor design. This allows for signicant energy savings at off-design conditions compared to xed-
speed chillers. See AHRI Certication on page 6 for more information on part load performance.

Integrated Variable Frequency Drive

A Variable Frequency Drive (VFD) modulates compressor speed in response to load and evaporator/condenser pressure. When minimum speed is reached, moveable inlet
guide vanes redirect the gas ow into the impeller. VFD’s have the following benets:
• Reduced annual energy costs when there are long periods of part load operation and/or low compressor lift (lower condenser water temperature)
• Reduced motor starting inrush current
• Reduced size of backup generators used to provide emergency power to chillers used on mission critical applications
• Increased power factor to reduce utility surcharges
WME Reduced Harmonic Options
The Institute of Electrical and Electronics Engineers (IEEE)
has developed a standard (IEEE519) that denes acceptable limits of site specic system current and voltage distortion.
The designer may wish to consult this standard to ensure acceptable levels of harmonic distortion are maintained. The harmonic characteristics of the standard VFD drive (Motor Code M2) will be acceptable in the vast majority of applications without the use of additional costly harmonic
lters or low harmonic drives.
The low harmonic drives (Motor Codes M3 and M4) are guaranteed to meet the IEEE519 Total Demand Distortion limits if the Isc/IL ratio is greater than 20.
An optional harmonic lter for the WME500 and WME1000
M2 VFD drive is available as a factory mounted option or as
an accessory to be eld mounting and wired. This harmonic lter is also guaranteed to meet the IEEE519 Total Demand
Distortion limits.

The Control Technology

It is only tting that this revolutionary chiller design be
matched with the advanced control technology to give you the ultimate chiller performance. Our control design includes many unique energy-saving features and interface enhancements.
MicroTech® E Controller
The model WME chiller utilizes MicroTech® E digital control electronics to proactively manage unit operation and provide control of external chilled water and cooling tower pumps. The compressor runs at the minimum speed necessary to maintain cooling capacity and lift (which decreases with lower condenser water temperatures), thus minimizing energy usage over the entire range of operating conditions. By constantly monitoring chiller status and real time data, the MicroTech® E controller will automatically take proactive measures to relieve abnormal conditions or shut the unit down if a fault occurs.
The WME chiller includes a regenerative power system that is used to provide power to the controls and bearings during a power loss event. When power is lost, the system extracts energy from the spinning motor. The power extracted from the rotor is fed back into the controls and bearings. As the power is extracted from the rotor, the shaft naturally slows down. Once the rotor is exhausted of its kinetic energy, and the shaft has reached a near zero speed, it gently touches down onto the backup bearings. The backup bearings maintain shaft position when the compressor is in an idle state and serve as a failsafe for the primary magnetic bearing system.
Additional smart features that optimize operating efciency
have been incorporated into our MicroTech® E controls:
• Cooling tower control including on/off, staging, and VFD
• Direct control of water pumps
• Chilled water rest
• Demand limit control
• Staging of multiple WME chillers (for WME 500 and 700)
Operator Interface
Operation simplicity was one of the main considerations in the development of the MicroTech® E control system. The operator interface is a 15-inch, color touch-screen monitor that
is mounted on an adjustable arm. Key operating parameters
and setpoints are easily accessible. For added convenience, the unit Operating and Maintenance Manual is also viewable on the touch-screen panel.
In order to track chiller performance, the MicroTech® E
www.DaikinApplied.com 5 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 6
0
10
20
30
40
50
1007550
25
1 P ercent
42 Percent
45 Percent
12 Percent
Percent Ton-Hour Weighting
Percent Load
feaTures and benefITs
controller can record and plot water temperatures, refrigerant pressures, and motor load. These values can be downloaded through a convenient USB port in the interface and exported into a spreadsheet for further evaluation and record purposes. The trend history screen is shown in Figure 2.
Figure 2: Operator Interface Trend History Screen
®
Table 1: RapidRestore
RapidRestore
Compressor Start
less than 60 sec
after power failure*
* Require s Uninter ruptible Power Su pply (UP S) to the WME c ontrol panel.
** Time i s based on u nit operating at AH RI conditions .
and RideThrough
®
Fast Loading to 80%
Load
75 sec* 5 sec**
®
Times
RideThrough
®
Open Choices™ BAS Flexibility
The exclusive Open Choices™ feature provides seamless integration and comprehensive monitoring, control, and two­way data exchange using industry standard protocols such as LonTalk®, BACnet® or Modbus®. Open Choices™ offers simple
and inexpensive exibility to use the Building Automation
System of your choice without an expensive gateway panel. Open Choices™ benets include:
• Easy to integrate into your BAS of choice
Factory- or eld-installed communications module
• Integrated control logic for factory options
• Easy-to-use local user interface
• Comprehensive data exchange
The controller memory (no batteries required) also retains the fault history for troubleshooting and monitoring unit performance. A time/date stamp is associated with each fault. The fault history can be downloaded through the USB port.
RapidRestore® and RideThrough
®
Mission critical facilities such as data centers and hospitals are demanding stringent capabilities for chillers to restart and reach full load operation quickly in the event of a power loss. With both RapidRestore® and RideThrough® capabilties, model WME chillers are engineered to meet those needs.
RapidRestore® – Quickly restores cooling capacity when power is restored after a power failure
Compressor Star t – Amount of time required for
the chiller to restart
Fast Loading – Amount of time required for the
chiller to reach a certain load condition
RideThrough
®
– The ability to maintain operation during
a momentary power loss event. When RideThrough is enabled and a power loss occurs, the compressor motor maintains rotation and the VFD catches and re-synchronizes with the spinning rotor. This permits the chiller to return to its pre-power loss capacity within seconds of power being restored.
Certications and Standards
As with many other Daikin Applied chiller products, the Magnitude® model WME meets all necessary certications and standards.
AHRI Certication
Part load performance can be presented in terms of Integrated
Part Load Value (IPLV), which is dened by AHRI Standard
550/590. Based on AHRI Standard 550/590, and as shown in Figure 3, a typical chiller can operate up to 99% of the time at off-peak conditions and usually spends most of this time at less than 60% of design capacity.
Figure 3: IPLV Dened by AHRI Standard 550/590
®
RapidRestore® is available for models WME 500 and 700. RideThrough® is available for all WME models. See Table 1 for
specications.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 6 www.DaikinApplied.com
Page 7
WME chillers are rated and certied to AHRI Standard
550/590. The ability of the WME chillers to achieve very high
part load efciencies, as evidenced by their world-class IPLV
ratings, is due primarily to the use of a variable frequency drive and the low friction of the magnetic bearing system. For more information on variable frequency drives, see Integrated Variable Frequency Drive on page 5.
Compliance with ASHRAE Std. 90.1
ASHRAE Standard 90.1 was developed to assist owners and designers make informed choices on a building’s design, systems, and equipment selection. Model WME
can signicantly exceed ASHRAE 90.1 minimum efciency
requirements.
IBC/OSHPD Seismic Certication
Daikin Magnitude® WME chillers have been tested and
certied by an independent agency, experts in seismic
analysis and design to meet IBC seismic and OSHPD pre­approval. Find more information about seismic requirements and HVAC systems at www.DaikinApplied.com.
®
LEED
For building owners who wish to pursue Leadership in Energy and Environmental Design (LEED®) Green Building
Certication, the performance of the WME may contribute
points towards Energy and Atmosphere (EA) Credits 1 and 4.
Points earned for EA Credit 1 are awarded based on overall
building efciency. The high efciency of the WME will
contribute to the total points earned for this credit.
EA Credit 4 qualication is partially determined by tonnage
and refrigerant quantity. Vessel stack and tube count selections will affect the quantity of refrigerant in the chiller. Consult with your Daikin Applied sales representative for more information.
feaTures and benefITs

Factory Testing

All of our centrifugal chillers (50 or 60 hertz) are factory­tested prior to shipment. Operating and safety controls are checked for correct settings and operation. This testing helps
reduce eld start-up issues and maintain critical construction
schedules.
www.DaikinApplied.com 7 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 8

Unit Dimensions and Shipping Weight

L
H
W
Figure 4: WME0500-0700S (2-pass, right-hand conguration, with grooved connections)

dImensIons and WeIghTs

dImensIons and WeIghTs
Figure 5: WME1000-1500D (2-pass, right-hand conguration, with grooved connections)
L
W
H
Table 2: WME0500-1500 Dimensions and Shipping Weights
Model Heat Exchanger
E3012 / C2612 168.5 (4280)
WME0500S
E3012 / C3012 168.5 (4280) 71.3 (1811) 96.8 (2459) 14163 (6424)
Length
in (mm)
E3612 / C3012 170.0 (4318) 77.3 (1963) 96.8 (2459) 16329 (7407)
WME0700S
E3612 / C3012 170.0 (4318) 77.3 (1963) 96.3 (2446) 17726 (8040)
E3612 / C3612 170.0 (4318) 83.0 (2108) 102.3 (2598) 20094 (9115)
WME1000D E4216 / C3616 218.3 (5545) 89.0 (2261) 102.8 (2611) 28172 (12779)
WME1500D E4816 / C4216 230.0 (5842) 101.0 (2565) 109.8 (2789) 38114 (17288)
* Shipping weight is ba sed on unit w ith standard tub e cong uratio n.
** Uni t height does not inc lude hei ght of removable eye bolt.
*** Dimens ion for un it with M2 s tandar d motor (60 Hz 440 /460/4 80V).
*** * Dimens ion for unit with M2 standard motor (50 Hz 380/400/415V, 60Hz 380/575V), M2 st andard m otor (60 Hz 380 /460V) with factory- mounte d harmon ic lter, or M3 l ow THD mot or
(50Hz 380/440/460/480/575V).
Width
in (mm)
68.4 (1737) ***
70.7 (1796) ****
Height **
in (mm)
92.8 (2357) 12864 (5835)
Shipping Weight *
lb (kg)
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 8 www.DaikinApplied.com
Page 9

Drawing Notes

1. Final connections must allow for 0.5-inch +/- (12.7 mm) manufacturing tolerances.
2. 1.00-inch FPT (25.4 mm) evaporator and condenser relief valves must be piped per ANSI / ASHRAE 15. Number of relief valves is 1 per evaporator and 2 per condenser.
3. 0.375-inch (9 mm) suction nozzle relief valve must be piped per ANSI / ASHRAE 15.
4. Minimum Clearances (See Figure 6):
• Check local codes for any additional clearance requirements.
Installation layout should be designed by qualied personnel familiar with local codes.
5. 3.25-inch (83 mm) diameter lifting holes are provided. See installation manual (available at www.DaikinApplied.
com) for lifting instructions.
6. All water connections are given in standard U.S. nominal pipe sizes. Standard connections are suitable for welding or grooved couplings.
7. Unit shown has standard right-hand water connections. Left-hand connections are available for either vessel. For right hand evaporator the inlet and outlet nozzles
are reversed. ANSI-anged nozzle connections are available upon request. When using ANSI-anged connections add 0.5 inch (13 mm) to each anged end.
dImensIons and WeIghTs
8. Dimensions shown are for units (evaporator / condenser) with standard design pressures. The waterside design pressure is 150 psi (1034 kPa). Consult the factory for unit dimensions with higher design pressures.
9. Unit vibration isolator pads are provided for eld installation and when fully loaded are 0.25 inches (6 mm) thick.
10. The shipping skid adds 4.00 inches (105 mm) to the overall unit height.
11. If main power wiring is brought up through the oor, this wiring must be outside the envelope of the unit.
12. The unit is shipped with a full operating charge of refrigerant except with the “Partial Disassembly”
knockdown option (Type B Knockdown for models WME 1000 / 1500 and Type I Knockdown for models WME
500 / 700).
13. Optional marine waterboxes are available upon request.
14. Units with M2 motors and the optional internal harmonic
lter have a two-door power panel in lieu of the standard
single-door.
Figure 6: Minimum Clearances Based on Standard Waterboxes
WME TOP VIEW
Minimum 13’ Clearance on one end for tube service (Models WME 500 and 700) Minimum 17’ Clearance on one end for tube service (Models WME 1000 and 1500)
Minimum 4’ Clearance
in front of control boxes and electrical panels
NOTE: Hinged type waterboxes may require more clearance. Consult your Daikin Applied sales representative for details.
www.DaikinApplied.com 9 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Minimum 3’ Clearance
Minimum 3’ Clearance
Page 10

opTIons and aCCessorIes

opTIons and aCCessorIes

Unit Options

Export Packaging
A wooden skid that aids in moving the unit and tight tting
plastic covering the entire unit to protect it from dirt and grime during transit and storage are standard. Open and closed crating is also offered as an option.
Pumpout Unit
Pumpout units are available in a variety of sizes with single­phase or three-phase power and with or without storage tanks.
Contact your Daikin Applied sales ofce for details.
Extended Warranties
Extended 1, 2, 3, or 4 year warranties for par ts only or for parts and labor are available for the compressor/motor only, the entire unit, or the entire unit including refrigerant.
Witness Performance Test
The specied full and/or part load tests, as ordered, are
performed in the presence of the customer under the supervision of a factory engineer and include compilation of the test data onto an easy-to-read spreadsheet.
Non-Witness Test
The specied full and/or part load tests, as ordered, are
performed under the supervision of a factory engineer; data is
compiled, certied, and transmitted to the customer.
Refrigerant Charge
Unit ships with a full holding charge of HFC-134a as standard. A nitrogen holding charge is available as an option.
Epoxy and Ceramic Coating
Evaporator and condenser heads and marine waterboxes can be coated for corrosion protection with either epoxy or ceramic coatings. Tube sheets may also be ceramic coated.
Single Insulation - Evaporator Shell / Suction Piping
0.75-inch thermal insulation on cold surfaces — excluding heads and waterboxes — is available.
Single Insulation - Evaporator Heads and
Waterboxes
0.75-inch thermal insulation is available.
Double Insulation - Evaporator Shell / Suction
Piping
1.5-inch thermal insulation on cold surfaces — excluding heads and waterboxes — is available.
Double Insulation - Evaporator Heads and
Waterboxes
1.5-inch thermal insulation is available.
Hinged Waterbox Covers and Heads
Hinges for marine waterbox covers or heads (compact waterboxes) are available to aid in heat exchanger maintenance.
Tube Size, Wall Thickness and Material
A wide range of tube options are available to accommodate
most ow rates and uids. Standard wall thickness is 0.025-
inch. Wall thicknesses of 0.028-inch or 0.035-inch are optional.
Knockdown Shipment
Several options for a knockdown shipment to facilitate unit placement are available. See Retrot Knockdown on page 18 for details.

Vessel Options

Marine Waterboxes
Marine waterboxes that allow the end plate of the waterbox to be removed without disconnecting the water piping from the chiller are optional.
Flange Water Connections
A standard unit will have grooved water connections. ANSI
raised face anges on either the evaporator or condenser are optional. Mating anges must be provided by the eld.
300 psi Water Side Vessel Construction
150 psi water side vessels are standard. 300 psi water side vessels are optional.

Controls Options

BAS Interface Module
Factory-installed on the unit controller for the applicable
protocol being used (Can also be retrot):
• BACnet® MS/TP
• BACnet® IP
• BACnet® Ethernet
• LonWorks®
• Modbus® RTU
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 10 www.DaikinApplied.com
Page 11
opTIons and aCCessorIes

Electrical Options

Power Panel High and Ultra High Short Circuit Current Rating
Available short circuit current ratings (SCCR) are shown in Table 3.
Table 3: Short Circuit Current Ratings
Motor Voltage
M2
(3-Ph)
M3 & M4
(6-Ph)
380V - 480V 35 kA 65 kA 100 kA
575V 25 kA 50 kA N/A
380V - 480V 35 kA 65 kA 100 kA
575V N/A N/A N/A
Standard
Panel SCCR
Electro Magnetic Interference (EMI) and Radio
Frequency Interference (RFI) Filter
A lter for EMI and RFI is a factory-installed option.
Ground Fault Protection
Protects equipment from arcing ground fault damage from line-to-ground fault currents less than those required for conductor protection.
Optional
High
SCCR
Optional
Ultra High
SCCR

Special Order Options

The following special order options are available; requiring factory pricing, additional engineering, and possible dimension changes or extended delivery:
1. Non-standard location of nozzle connections on heads (compact waterboxes) or marine waterboxes
2. Clad tube sheets
3. Sacricial anodes in heads (compact waterboxes) or marine waterboxes
4. Spacer rings on heads to accommodate automatic tube brush cleaning systems (installed by others)
5. Remote-mounted refrigerant monitor, including accessories such as 4-20ma signal, strobe light, audible
horn, and air pick-up lter
Input Power Meter
Allows display of input phase amps, volts, power factor, and power on the operator interface screen.
RapidRestore® and RideThrough
Allow chillers to restart and reach full load operation quickly in the event of a power loss event. See RapidRestore® and RideThrough® on page 6 for more details.
®
www.DaikinApplied.com 11 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 12
Figure 7: Refrigeration System Diagram for WME0500-0700S m
Liquid Injection
Motor Stator Cooling
Rotor Cooling
Stepper
Motor
Valve
Controlled By
Compressor Controller
Rotor Liquid Injection
Electronic
Expansion
Valve
Controlled By Chiller
Controller
Check
Valve
Manual Shut Off Valve
T
VFD
controller
T
Filter Dryer
Strainer
Strainer
Solenoid Valve
Controlled By
Compressor Controller
Solenoid Valve
Controlled By
Compressor Controller
Strainer
T
P
T
HPS
T
Suction
Discharge
Motor
Evaporator
Condenser
Compressor
REV 4 - MKG
Jan 2014
Liquid
Line
T
= Temperature Sensor
P
= Pressure Sensor
P
P
T
T
HPS
= High Pressure Switch
Orifice
6 Phase
configuration
shown.
3 Phase version
will have 1 heat
sink and 1
refrigerant circuit
Range Extension Valve
Controlled By Chiller
Controller

refrIgeraTIon dIagram

refrIgeraTIon dIagram
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 12 www.DaikinApplied.com
Page 13
Figure 8: Refrigeration System Diagram for WME1000-1500Dm
refrIgeraTIon dIagram
US01
US03
VALVE
VALVE
CHARGING
3 – WAY PLUG
SENSOR
SENSOR
PRESSURE
TEMPERATURE
CHECK VALVE
(Spring)
VALVE
SOLENOID
CENTRIFUGAL
RELIEF VALVE
COMPRESSOR
SIGHT GLASS
FILTER & DRYER
VALVE
EVAP. FLOW
EXPANSION
ELECTRONIC
EF
SWITCH
COND. FLOW
CF
SWITCH
STEP VALVE
BALL VALVE
SHUTOFF VALVE
VFD 1 & 2
VFD
STRAINER
FLOW CHART LEGEND
LIQUID INJECTION LINE
MOTOR COOLING LINE
ROTOR COOLING LINE
SUCTION LINE
ROTOR DRAIN LINE
STATOR DRAIN LINE
HOT GAS BY PASS
ELECTRONIC
EXPANSION VALVE
UNIT CONTROLLER
US01 CONDENSER PRESSURE
US02 EVAPORATOR ENTERING WATER TEMPERATURE
US03 EVAPORATOR LEAVING WATER TEMPERATURE
US04 CONDENSER ENTERING WATER TEMPERATURE
US05 CONDENSER LEAVING WATER TEMPERATURE
US06 LIQUID LINE TEMPERATURE
BUBBLE NO. DESCRIPTION
US04
Compressor
COMPRESSOR #2
SUCTION LINE
US02
DISCHARGE LINE
ROTOR COOLING LINE
MOTOR COOLING LINE
EF
US03
US02
VFD #1
LIQUID INJECTION LINE
VFD #2
INLET
OUTLET
ROTOR DRAIN LINE
STATOR DRAIN LINE
US06
COMPRESSOR CONTROLLER
COOLING LINE SUPPLY VFD
COOLING LINE SUPPLY VFD
CS01 EVAPORATOR PRESSURE
CS02 DISCHARGE PRESSURE
CS03 COMPRESSOR SUCTION TEMPERATURE
CS04 COMPRESSOR DISCHARGE TEMPERATURE
BUBBLE NO. DESCRIPTION
US01
COMPRESSOR #1
MAIN LIQUID LINE
CF
US04
US07
FLOW DIAGRAM, WME DUAL
334723921 00
US04
MOTOR COOLING LINE
US01
DISCHARGE LINE
US02
US01
US05
US08
INLET
OUTLET
US03
Compressor
LIQUID INJECTION LINE
www.DaikinApplied.com 13 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 14

applICaTIon ConsIderaTIons

applICaTIon ConsIderaTIons

Location Requirements

Daikin WME units are designed only for indoor, weather­protected, non-freezing areas consistent with the NEMA 1 rating on the chiller, controls, and electrical panels. Equipment room temperature for operating and standby conditions is 40°F to 104°F (4.4°C to 40°C).

Vibration Mounting

The Magnitude® WME chiller is almost vibration-free.
Consequently, oor mounted spring isolators are not usually
required. Neoprene mounting pads are shipped with each
unit. It is recommended to continue to use exible piping
connectors to reduce sound transmitted into the pipe and to allow for expansion and contraction.

System Design

Water Piping
Field installed water piping to the chiller must include:
• air vents at the high points.
• a cleanable 20 -mesh water strainer in water inlet lines.
a ow proving device for both the evaporator and condenser to prevent freeze up. Flow switches, thermal dispersion switches, or Delta-P switches can be used.
Note that ow switches are factory installed. Additional ow switches can be used only if they are connected in
series with the ones already provided.
sufcient shutoff valves to allow vessel isolation. The chiller must be capable of draining the water from the evaporator or condenser without draining the complete system.
It is recommended that eld installed water piping to the chiller include:
• thermometers at the inlet and outlet connections of both vessels.
• water pressure gauge connection taps and gauges at the inlet and outlet connections of both vessels for measuring water pressure drop.
Piping must be supported to eliminate weight and strain on
the ttings and connections. Chilled water piping must be
adequately insulated.
NOTE: This product, in its standard conguration, is
equipped with a shell and tube evaporator with carbon steel shell and copper tubes. The water or
other uid used in contact with the wetted surfaces of
the heat exchangers must be clean and non-corrosive to the standard materials of construction. Daikin Applied makes no warranty as to the compatibility
of uids and materials. Non-compatible uids may
void the equipment warranty. If the compatibility of
the uid with the standard materials of construction
is in question, a professional corrosion consultant should administer the proper testing and evaluate compatibility.
Variable Fluid Flow Rates and Tube Velocities
Many chiller system control and energy optimization
strategies require signicant changes in evaporator water ow rates. The Magnitude® chiller line is well suited to take
full advantage of these energy saving opportunities using different combinations of shell sizes, number of tubes, and pass arrangements.
Both excessively high and excessively low uid ow rates should be avoided. Excessively high uid ow rates and correspondingly high tube velocities will result in high uid
pressure drops, high pumping power, and potentially tube
erosion or corrosion damage. Excessively low uid ow rates
and correspondingly low velocities should also be avoided as they will result in poor heat transfer, high compressor power, sedimentation and tube fouling.
Water Volume
All chilled water systems need adequate time to recognize a load change to avoid short cycling of the compressors or loss of control. The potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes.
Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors.
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of “gallons of water volume equal to two to three times the chilled
water gpm ow rate” is often used.
A properly designed storage tank should be added if the
system components do not provide sufcient water volume.
Optimizing Efciency
A key to improving energy efciency for any chiller is
minimizing the compressor pressure lift. Reducing the lift reduces the compressor work and its energy consumption per unit of output.
The optimum plant design must take into account all of the interactions between chiller, pumps, and tower. The Daikin Energy Analyzer™ II program is an excellent tool to investigate
the entire system efciency, quickly and accurately. It is
especially good at comparing different system types and operating parameters. Contact your local Daikin Applied sales
ofce for assistance on your particular application.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 14 www.DaikinApplied.com
Page 15
45
50
55
60
0 10 20 30 40 50 60 70 80 90 100
ECWT (°F)
Percent Load
46°F LWT
44°F LWT
42°F LWT
applICaTIon ConsIderaTIons

Evaporator

Reducing Evaporator Fluid Flow
Several popular chiller plant control practices — including Variable Primary Flow systems — advocate reducing the
evaporator uid ow rate as the chiller capacity is reduced. This practice can signicantly reduce the evaporator pumping
power while having little effect on chiller energy consumption. The Magnitude® WME chillers— with their wide range of shell, tube, and pass combinations— are ideal for application in
variable evaporator ow systems as long as the minimum and
maximum tube velocities are taken into consideration when selecting the chiller.
If it is decided to vary the evaporator water ow rate, the
rate of change should not exceed the minimum or maximum velocity limits. Additionally, the rate of change should not exceed 50% per minute for models WME 500 and 700.
Evaporator Entering Water Temperature
The maximum temperature of water entering the chiller on standby must not exceed 115°F (46.1°C). Maximum temperature entering on start-up must not exceed 90°F (32°C).
Evaporator Leaving Water Temperature
Warmer leaving chilled water temperatures will raise the compressor’s suction pressure and decrease the lift,
improving efciency. Using 45°F (7°C) leaving water instead of the typical 42°F (5.5°C) will signicantly reduce chiller energy
consumption.
Evaporator Water Temperature Difference
The industry standard has been a 10°F (5.5°C) temperature drop in the evaporator. Increasing the drop to 12°F or 14°F
(6.6°C or 7.7°C) can improve chiller efciency and reduce
pump energy consumption.
uid ow, the model WME chiller can operate effectively as
long as the minimum and maximum tube velocities are taken into consideration when selecting the chiller.
Reducing Condenser Entering Water Temperature
As a general rule, a 1°F (0.5°C) drop in condenser entering water temperature will reduce chiller energy consumption by two percent. Cooler water lowers the condensing pressure and reduces compressor work. One or two degrees can make a noticeable difference. The incremental cost of a larger tower can be small and provide a good return on investment.
When the ambient wet bulb temperature is lower than design, the entering condenser water temperature of Magnitude® WME chillers can be lowered to improve chiller per formance.
Chillers can start with entering condenser water temperatures as low as 40°F (4.4°C). For short periods of time during startup, the entering condenser water temperature can even be lower than the leaving chilled water temperature.
Magnitude® WME chillers are equipped with electronic expansion valves (EXV) and will run with entering condenser water temperatures as low as shown in Figure 9 or as calculated from the following equation on which the curves are based:
Min. ECWT = 5.25+(LWT)-0.75*DTFL*(PLD/100)+14 *(PLD/100)2
Where:
ECWT = Entering condenser water temperature
LWT = Leaving chilled water temperature
DTFL = Chilled Water Delta-T at full load
PLD = The percent chiller load point to be checked
Figure 9: WME Minimum Entering Condenser Water Temperature (10°F Range at Full Load)

Condenser

Reducing Condenser Fluid Flow
Several popular chiller plant control practices also advocate
reducing the condenser uid ow rate as the chiller load is reduced. This practice can signicantly reduce the condenser
pumping power, but it may also have the unintended
consequence of signicantly increasing compressor power
since the leaving condenser water temperature is directly related to compressor lift and power. The higher compressor power will typically be larger than the condenser pumping power reduction and will result in a net increase in chiller plant energy consumption. Therefore, before this strategy is applied for energy saving purposes it should be extensively modeled or used in an adaptive chiller plant control system which will take into account all of the interdependent variables affecting chiller plant energy. If it is decided to use variable condenser
www.DaikinApplied.com 15 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
For example; at 44°F LWT, 10°F Delta-T at full load, and 50% full load operation, the entering condenser water temperature could be as low as 49°F. This provides excellent operation with water-side economizer systems.
Page 16
applICaTIon ConsIderaTIons
Depending on local climatic conditions, using the lowest possible entering condenser water temperature may be more costly in total system power consumed than the expected savings in chiller power would suggest, due to the excessive fan power required.
In this scenario, cooling tower fans would continue to operate at 100% capacity at low wet bulb temperatures. The trade-
off between better chiller efciency and fan power should be analyzed for best overall system efciency. The Energy
Analyzer™ II program (available from your Daikin Applied sales representative) can optimize the chiller/tower operation for
specic buildings in specic locales.
Condenser Water Temperature Difference
The industry standard of 3 gpm/ton or about a 9.5°F (5.3°C) delta-T works well for most applications.
Condenser Water Temperature Control
Condenser water control is an important consideration in chiller plant design since condenser water temperature will
directly impact chiller operation and efciency. When the
ambient wet bulb temperature is lower than peak design, the entering condenser water temperature from the cooling tower can be allowed to fall, improving chiller performance. However, operational issues may occur when the condenser water temperatures are either too high or too low. The WME chiller provides several options to assist the chiller plant designer in providing the optimum control of condenser water temperature.
Cooling Tower Control
Control of the cooling tower is required to maintain stability and avoid operational issues. This can be achieved through a BAS or by using the MicroTech® E controller. For systems utilizing a common condenser water loop for multiple purposes, the BAS contractor must provide the control but use of the MicroTech® E output signal is still recommended.
The preferred cooling tower control utilizes a variable speed fan. MicroTech® E will provide a control signal to determine the proper fan speed. It can also control up to three stages of fan cycling. Note that fan cycling can cause cooling tower
water temperature to uctuate as fans stage on/off, potentially
adding instability to the system.
Special consideration must be given to starting the chiller when cold condenser water is present, such as with inverted starts or changeover from free (tower) cooling to mechanical cooling. It is required that some method be used to control the condenser water to maintain proper head pressure as indicated by the MicroTech® E controller.
Acceptable methods include the following (Each of these
options can be controlled by the MicroTech® E or through
a BAS utilizing the MicroTech® E output signals.):
1. Three-Way Bypass Valve Operation
A traditional method for building condenser pressure at startup with colder condenser water is with the use of a three-way bypass valve. The device blends warmer water leaving the condenser with cooler water from the cooling tower at the condenser inlet. The bypass valve
position will change until full ow from the tower to the
condenser is obtained. The MicroTech® E provides only the valve position control signal. Main power to drive the valve’s actuator must be provided by the installer. The three-way valve should be located close to the chiller within the equipment room to minimize the volume of water.
2. Two-Way Valve Operation
Another condenser control method is to use a modulating two-way control valve located on the outlet connection of the condenser. The valve will be nearly
closed at startup to restrict water ow, which keeps
generated heat in the condenser until an acceptable minimum condenser pressure is reached. As heat
builds, the valve will open slowly until a full ow
condition from the cooling tower is established. A separate power source is required to provide power to the valve actuator.
3. VFD Operating with a Condenser Water Pump
A third method of condenser control for startup is utilizing a variable frequency drive with the condenser water pump. The speed will change as directed by the MicroTech® E output signal until design ow is reached. Speed adjustments may be required during the initial chiller startup as determined by the service technician.
NOTE: Not using the MicroTech® E logic to control valves
and variable frequency drives may result in system instability, capacity reduction, and issues starting the chiller with cold condenser water temperature.
Condenser Pump Sequencing
It is recommended to utilize the logic built into the MicroTech® E controller to start the condenser pump. MicroTech® E has the capability to operate a primary pump and a secondary
standby pump. The condenser water ow should be stopped
when the chiller shuts off. This will conserve energy and prevent refrigerant from migrating to the condenser.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 16 www.DaikinApplied.com
Page 17
Lenient Flow Operation
For chiller startup, the condenser control systems can reduce
the ow to low rates, which can make operation of a ow
sensing device unreliable. The MicroTech® E controller has
a “lenient ow” feature that acts as an override of the ow
sensor while protecting the chiller by monitoring a condenser pressure setting that is below the high pressure cutout.
Water Side Economizer Cycle Operation
Water side economizers are commonly used for ASHRAE
90.1 compliance and energy savings. This system utilizes a heat exchanger external to the chiller when cold cooling tower water is available to provide cooling. The most common system has a heat exchanger used in conjunction with the chiller’s evaporator.
The BAS contractor will need to provide controls for the heat exchanger including isolation valves and temperature control. The BAS contractor will also need to control the isolation valves for the chiller. It is important to use slow-acting type
valves to prevent rapid changes in system ows. Changeover
from economizer cooling to mechanical cooling requires one of the methods previously mentioned to maintain suitable condenser head pressure.
Contact your local Daikin Applied representative for more information on this application.
applICaTIon ConsIderaTIons
www.DaikinApplied.com 17 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 18
applICaTIon ConsIderaTIons
Retrot Knockdown
It is estimated that fty percent of retrot applications require partial or complete disassembly of the chiller. Magnitude® WME chillers are relatively easy to disassemble due to the small compressor size, simplied refrigerant piping, and the absence of a
lubrication system with its attendant components and piping. Various knockdown arrangements are available as options.
“Bolt-Together Construction”
Chillers are built and shipped completely assembled with bolt-together construction on major components for eld disassembly
and re-assembly on the job site. “Bolt-Together Construction” applies to the following:
• Type A Knockdown for models WME 1000 and 1500
• Type III Knockdown for models WME 500 and 700
Figure 10: “Bolt-Together Construction”
OITS PANEL BOXED
AND SECURELY STRAPPED
TO UNIT CONTROL BOX
FOR SHIPPING
POWER
BOX
VESSEL
BREAKPOINTS
TYP. (IF NEEDED)
Scope:
• Chiller components are manufactured with bolt-together
construction designed for eld disassembly and re-
assembly on-site.
Suction and discharge lines have bolt-on anges.
• Unit ships with vessel and/or head insulation, if ordered.
• Unit ships with full factory refrigerant charge in the chiller.
UNIT
CONTROL
BOX
NOTE: ALL STEEL PIPING &
COPPER TUBING IS DESIGNED WITH
MECHANICAL BREAKPOINTS
• Unit ships completely assembled to the jobsite.
• Bolt-together construction allows for site disassembly based on required clearances at each jobsite.
• Site disassembly and re-assembly must be supervised or completed by Daikin Applied service personnel.
Ideal for retrot applications.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 18 www.DaikinApplied.com
Page 19
applICaTIon ConsIderaTIons
MISCELLANEOUS ITEMS
“Partial Disassembly”
Compressor(s), power boxes, and control boxes are removed and shipped on separate skids; combined vessel stack is shipped together as a sub-assembly. “Partial Disassembly” applies to the following:
• Type B Knockdown for models WME 1000 and 1500
• Type I Knockdown for models WME 500 and 700
Figure 11: “Partial Disassembly”
MECHANICAL BREAKPOINTS
VESSEL
BLOCKOFF
COMPRESSOR(S)
BLOCKOFF AT
MAIN LIQUID LINE
FOR UNITS WITH
RANGE EXTENSION
VESSEL
BREAKPOINTS
TYP. (IF NEEDED)
VESSEL
BLOCKOFF
UNIT
CONTROL
BOX
GLUE
INSULATION & OTHER MISCELLANEOUS ITEMS
CRATE 1
ROTOR COOLING SUPPLY & RETURN LINES STATOR COOLING SUPPLY & RETURN LINES BOXED OITS PANEL LOOSE INSULATION GLUE
CRATE 2
RANGE EXTENSION PIPING DISCHARGE PIPING SUCTION ELBOW
POWER BOX(ES)
6 Phz. SHOWN
Scope:
• Compressor(s), power boxes, and control boxes are removed (at the factory) and shipped on separate skids; vessel stack is shipped as a complete sub­assembly.
• All associated piping and wiring remain attached, if possible.
• Compressors and vessels receive a Nitrogen holding charge.
• All free piping ends are capped.
• Unit ships with vessel and/or head insulation, if ordered.
• Refrigerant will not be shipped with the chiller and must be procured locally.
• Site re-assembly must be supervised or completed by Daikin Applied service personnel.
Ideal for retrot applications where it is desired that the compressors, power boxes, and control boxes be removed at the factory, prior to shipment, and where refrigerant may be secured locally.
Suction and discharge lines have bolt-on anges and, if possible, remain attached.
“Complete Disassembly”
“Complete Disassembly” is the same as “Partial Disassembly,” except in “Complete Disassembly” all wiring and piping that interconnects the components are removed as well. “Complete Disassembly” ONLY applies to Type II Knockdown for models WME 500 and 700.
www.DaikinApplied.com 19 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 20

engIneerIng guIde speCIfICaTIons

MAGNITUDE® MAGNETIC BEARING CENTRIFUGAL CHILLERS
engIneerIng guIde speCIfICaTIons
PART 1 - GENERAL
1.1 S U M M ARY
A. Section includes design, performance criteria,
refrigerants, controls, and installation requirements for water-cooled centrifugal chillers.
1.2 REFERENCES
A. Comply with the following codes and standards: AHRI
550/590, AHRI 575, NEC, ANSI/ASHRAE 15, OSHA as adopted by the State, ETL, ASME Section VIII
1.3 SUBMITTALS
A. Submittals shall include the following:
1. Dimensioned plan and elevation view, including
required clearances, and location of all eld piping
and electrical connections.
2. Summaries of all auxiliary utility requirements such as: electricity, water, air, etc. Summary shall indicate quality and quantity of each required utility.
3. Diagram of control system indicating points for eld
interface and eld connection. Diagram shall fully depict eld and factory wiring.
4. Manufacturer’s certied performance data at full load plus IPLV or NPLV.
5. Installation and Operating Manuals.
1.4 QUALITY ASSURANCE
A. Regulatory Requirements: Comply with the codes and
standards in Section 1.2.
B. Chiller manufacturer plant shall be ISO 9001 and ISO
14001 Certied.
C. The chiller shall be factory tested at the manufacturer’s
plant prior to shipment on an AHRI approved test stand.
1.5 DELIVERY AND HANDLING
A. Chillers shall be delivered to the job site completely
assembled and charged with refrigerant R134a and be shipped on skids with a weather resistant cover.
-- OR --
A. [For Type A Knockdowns] The unit shall be delivered
to the job site completely assembled and charged with
refrigerant and ready for eld knockdown. Contractor
shall leak test, recover refrigerant, evacuate, and charge with refrigerant after reassembly.
-- OR --
A. [For Type B Knockdowns] The compressor, suction and
discharge piping, VFD power panel and touch screen shall be removed and shipped separately. All wiring and piping shall remain attached where possible. The remaining loose parts shall be packaged in a separate crate. The unit is to be factory tested and shipped with a nitrogen holding charge, evaporator insulated and a kit for compressor insulation. Contractor shall leak test, evacuate and charge with refrigerant after reassembly.
B. Comply with the manufacturer’s instructions for rigging
and transporting units. Leave protective covers in place until installation.
1.6 WARRANTY
A. The chiller manufacturer’s warranty shall cover parts
and labor costs for the repair or replacement of defects in material or workmanship for a period of one year from equipment startup or 18 months from shipment,
whichever occurs rst [OPTION] and also include an
additional extended warranty for one -OR- two- OR­three -OR- four years on the entire unit -OR- on entire unit including refrigerant coverage -OR- compressor only.
1.7 MAINTENANCE
A. Maintenance of the chillers in accordance with
manufacturer’s recommendations as published in the installation and maintenance manuals shall be the responsibility of the owner.
PART 2 - PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
A. Basis of Design - Daikin Magnitude® model WME,
including the standard product features and all special
features required per the plans and specications.
B. Equal Products - Equipment manufactured by [ENTER
MANUFACTURER NAME HERE] may be acceptable
as an equal. Naming these products as equal does not
imply that their standard construction or conguration is acceptable or meets the specications. Equipment proposed “as equal”, must meet the specications
including all architectural, mechanical, electrical, and structural details, all scheduled performance and the job
design, plans and specications.
2.2 UNIT DESCRIPTION
A. Provide and install as shown on the plans a factory
assembled, charged, and tested water-cooled packaged
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 20 www.DaikinApplied.com
Page 21
engIneerIng guIde speCIfICaTIons
centrifugal chiller. Chillers shall have no more than two oil-free, magnetic bearing, semi-hermetic centrifugal compressors (no exceptions). Each compressor shall have an integrated variable-frequency drive operating in concert with inlet guide vanes for optimized full and
part load efciency. On two-compressor units, the
evaporator and condenser refrigerant sides and the expansion valve shall be common and the chiller shall be capable of running on one compressor with the other compressor or any of its auxiliaries inoperable or removed.
2.3 DESIGN REQUIREMENTS
A. General: Provide a complete water-cooled, semi-
hermetic oil-free centrifugal compressor water chiller as
specied herein. The unit shall be provided according
to standards indicated in Section 1.2. In general, unit shall consist of one or two magnetic bearing, completely oil-free centrifugal compressors, refrigerant, condenser and evaporator, and control systems including integrated variable frequency drive, operating controls and equipment protection controls. Chillers shall be charged with refrigerant HFC-134a. If manufacturer offers a chiller using any HCFC refrigerant, manufacturer shall
provide, in writing, documentation signed by an ofcer of
the company assuring refrigerant availability and price schedule for a 20-year period.
B. The entire chiller system, including all pressure vessels,
shall remain above atmospheric pressure during all operating conditions and during shut down to ensure that non-condensables and moisture do not contaminate the refrigerant and chiller system. If any portion of the chiller system is below atmospheric pressure during either operation or shut down, the manufacturer shall include, at no charge:
1. A complete purge system capable of removing non­condensables and moisture during operation and shut-down.
2. A 20-year purge maintenance agreement that provides parts, labor, and all preventative maintenance required by the manufacturer’s operating and maintenance instructions.
3. The manufacturer shall also include at no charge for a period of 20 years an annual oil and refrigerant analysis report to identify chiller contamination due
to vacuum leaks. If the analysis identies water, acid, or other contaminant levels higher than specied by
the manufacturer, the oil and/or refrigerant must be replaced or returned to the manufacturer’s original
specication at no cost to the owner.
4. The manufacturer shall include a factory-installed and wired system that will enable service personnel to
readily elevate the vessel pressure during shutdown to facilitate leak testing.
C. Performance: Refer to chiller performance rating.
D. Acoustics: Sound pressure for the unit shall not exceed
the following specied levels. Provide the necessary
acoustic treatment to chiller as required. Sound data shall be measured in dB according to AHRI Standard 575 and shall include overall dBA. Data shall be the highest levels recorded at all load points.
Octave Band
63 125 250 500 1000 2000 4000 8000
2.4 CHILLER COMPONENTS
A. Compressors:
1. The unit shall utilize magnetic bearing, oil-free, semi­hermetic centrifugal compressors. The compressor drive train shall be capable of coming to a controlled, safe stop in the event of a power failure.
2. The motor shall be of the semi-hermetic type,
of sufcient size to efciently fulll compressor
horsepower requirements. It shall be liquid refrigerant cooled with internal thermal sensing devices in the stator windings. The motor shall be designed for variable frequency drive operation.
a. If the compressor design requires a shaft seal
to contain the refrigerant, the manufacturer shall supply a 20 year parts and labor warranty on the shaft seal and a lifetime refrigerant replacement warranty if a seal failure leads to refrigerant loss, or the chiller manufacturer shall assume all costs to supply and install a self contained air conditioning system in the mechanical space sized to handle the maximum heat output of the open drive motor. The energy required to operate this air conditioning system shall be added to the chiller power at all rating points for energy evaluation purposes.
b. If the compressor/motor uses any form of
antifriction bearing (roller, ball, etc), the chiller manufacturer shall provide the following at no additional charge:
• A 20-year bearing warranty and all
preventative maintenance as specied by
the manufacturer’s published maintenance instructions.
• At start up, a three-axis vibration analysis and written report to establish bearing condition baseline.
• An annual three-axis vibration analysis and
Overall
dBA
www.DaikinApplied.com 21 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 22
engIneerIng guIde speCIfICaTIons
written report indicating bearing condition.
3. The chiller shall be equipped with a refrigerant cooled and integrated Variable Frequency Drive (VFD) to automatically regulate compressor speed in response to cooling load and the compressor pressure lift requirement. If a condenser water-cooled VFD is supplied, the manufacturer shall supply factory
installed dual water lters with a bypass valve and
pressure differential switch factory wired to the chiller
control panel to indicate that a lter has clogged and
requires service. The pressure differential switch shall also provide a separate dry contact which can be connected to the BAS system as a means of notifying operating personnel of the need to service
the lters. If the condenser cooling circuit includes an
intermediate heat exchanger, it must be of the brush cleanable shell and tube style. Brazed plate heat
exchangers which cannot be eld cleaned are not
acceptable. Movable inlet guide vanes and variable compressor speed, shall provide unloading. The chiller controls shall coordinate compressor speed
and guide vane position to optimize chiller efciency.
4. Each compressor circuit shall be equipped with a 5% line reactor to help protect against incoming power surges and help reduce harmonic distortion.
5. [OPTIONAL for WME 500/1000 M2 Motor] The chiller shall be equipped with a factory-mounted
and wired passive harmonic lter guaranteed to meet
the IEEE Standard 519 at an Isc/IL ratio greater than
20.
[OPTIONAL for WME 500/1000 M2 Motor] The chiller shall be supplied with a 460V or 575V
passive harmonic lter shipped loose for eld-
mounting and wiring. It shall be guaranteed to meet the IEEE Standard 519 at an Isc/IL ratio greater than
20.
[OPTIONAL for WME 500/1000 M3 Motor] The chiller shall meet IEEE Standard 519 Total Demand Distortion limits at an Isc/IL ratio greater than 20.
[OPTIONAL for WME 700/1500 M4 Motor] The chiller shall meet IEEE Standard 519 Total Demand Distortion limits at an Isc/IL ratio greater than 20.
B. Evaporator and Condenser:
1. The evaporator and condenser shall be separate vessels of the shell-and-tube type, designed, constructed, tested and stamped according to the requirements of the ASME Code, Section VIII. The tubes shall be individually replaceable and secured to the intermediate supports without rolling.
2. The evaporator shall be ooded type with [0.025
in.] –OR– [0.028 in.] –OR– [0.035 in.] wall [copper] –OR– [90/10 CuNi] tubes rolled into [carbon steel] –OR– [ceramic-coated steel] tubesheets. The water side shall be designed for a minimum of [150 psig] –OR– [300 psig]. The heads shall be [carbon steel] –OR– [epoxy-coated steel] –OR– [Monel-clad] –OR– [Stainless Steel]. Water connections shall be grooved suitable for [grooved couplings] –OR– [anged connections]. The evaporator shall have [dished heads with valved drain and vent connections] – OR– [shall be equipped with marine waterboxes with removable covers and vent and drain connections]. The evaporator shall have [right-hand] –OR– [left­hand] connections when looking at the unit control
panel.
3. The condenser shall have [0.025 in.] –OR– [0.028
in.] –OR– [0.035 in.] wall [copper] –OR– [90/10 CuNi] –OR– [70/30 CuNi] –OR– [stainless steel] –OR– [titanium] tubes rolled into [carbon steel] – OR– [Monel-clad] –OR– [stainless steel clad] –OR– [titanium-clad] – OR– [ceramic-coated] tube sheets.
Water connections shall be [grooved suitable for
grooved couplings]—OR– [anged]. The water side shall be designed for a minimum of [150 psig] –OR– [300 psig]. The condenser shall have [dished heads with valved drain and vent connections] –OR– [shall
be equipped with marine waterboxes with removable
covers and vent and drain connections]. The condenser shall have [right-hand]
–OR– [left-hand] connections when looking at the
unit control panel.
4. Provide sufcient isolation valves and condenser volume to hold the full unit refrigerant charge in the condenser during servicing or provide a separate
pumpout system and storage tank sufcient to hold
the charge of the largest unit being furnished.
5. An electronic expansion valve shall control refrigerant
ow to the evaporator. Fixed orice devices or oat
controls with hot gas bypass are not acceptable
because of inefcient control at low load conditions.
The liquid line shall have moisture indicating sight glass.
6. Re-seating type spring loaded pressure relief valves according to ASHRAE-15 safety code shall be furnished. The evaporator shall be provided with single or multiple valves. The condenser shall be provided with dual relief valves equipped with a transfer valve so one relief valve can be removed for testing or replacement without loss of refrigerant or removal of refrigerant from the condenser. Rupture disks are not acceptable.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 22 www.DaikinApplied.com
Page 23
engIneerIng guIde speCIfICaTIons
7. [OPTIONAL] The evaporator vessel, including suction line and any other component or part of a component subject to condensing moisture (excluding the waterbox), shall be insulated with UL recognized 3/4 inch OR 1 ½ inch closed cell insulation. All joints and seams shall be carefully sealed to form a vapor ba rrie r.
8. [OPTIONAL] The evaporator waterbox shall be insulated with UL recognized 3/4 inch OR 1 ½ inch closed cell insulation. All joints and seams shall be carefully sealed to form a vapor barrier.
9. Provide factory-mounted and wired, thermal-
dispersion water ow switches on each vessel to prevent unit operation with no or low water ow.
C. Vibration Isolation
1. Provide neoprene wafe-type vibration isolators for each corner of the unit.
D. Power Connections
1. Power connection shall be single point to a factory­mounted disconnect switch OR shall be multipoint to each compressor power panel on two-compressor units.
E. Chiller Control
1. The unit shall have a microprocessor-based control system consisting of a 15-inch VGA touch-screen operator interface and a unit controller.
2. The touch-screen shall display the unit operating parameters, accept setpoint changes (multi-level password protected) and be capable of resetting faults and alarms. The following parameters shall be displayed on the home screen and also as trend curves on the trend screen:
• Entering and leaving chilled and condenser water temperatures
• Evaporator and condenser saturated refrigerant pressures
• Percent of 100% speed (per compressor)
• % of rated load amps for entire unit
3. In addition to the trended items above, all other important real-time operating parameters shall also be shown on the touch-screen. These items shall be displayed on a chiller graphic showing each component. At a minimum, the following critical areas must be monitored:
• Compressor actual speed, maximum speed, percent speed
• Evaporator water in and out temperatures, refrigerant pressure and temperature
• Condenser water in and out temperatures, refrigerant pressure and temperature
• Liquid line temperature
• Chilled water setpoint
• Compressor and unit state and input and output digital and analog values
4. A fault history shall be displayed using an easy to decipher, color coded set of messages that are date and time stamped. The alarm history shall be downloadable from the unit’s USB port. An operating
and maintenance manual specic for the unit shall be
viewable on the screen and downloadable.
5. All setpoints shall be viewable and changeable (multi­level password protected) on the touch screen and include setpoint description and range of set values.
6. Automatic corrective action to reduce unnecessary cycling shall be accomplished through preemptive control of low evaporator or high discharge pressure conditions to keep the unit operating through abnormal transient conditions.
7. The chiller shall be capable of sequencing up to two other similar chillers for WME 500 and 700 models. The contractor shall furnish and wire network isolators for n-1 units.
8. The chiller shall be capable of automatic control of: evaporator and condenser pumps (primary and standby), up to 3 stages of cooling tower fan cycling control and a tower modulating bypass valve or cooling tower fan variable frequency drive.
9. Optionally, the factory mounted controller(s) shall support operation on a BACnet®, Modbus® or LonWorks® network via one of the data link / physical
layers listed below as specied by the successful
Building Automation System (BAS) supplier.
• Modbus
®
• BACnet® MS/TP master (Clause 9)
• BACnet® IP, (Annex J)
• BACnet® ISO 8802-3, (Ethernet)
• LonTalk® FTT-10A. The unit controller shall be LonMark® certied.
10. The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring,
control and alarm notication as specied in the unit
sequence of operation and the unit points list.
11. For chillers communicating over a LonMark® network, the corresponding LonMark® eXternal Interface File (XIF) shall be provided with the chiller submittal data.
12. All communication from the chiller unit controller
as specied in the points list shall be via standard
BACnet® objects. Proprietary BACnet® objects shall not be allowed. BACnet® communications shall conform to the BACnet® protocol (ANSI/
www.DaikinApplied.com 23 CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS
Page 24
engIneerIng guIde speCIfICaTIons
ASHRAE135-2001). A BACnet® Protocol Implementation Conformance Statement (PICS) shall be provided along with the unit submittal.
13. [For WME 500-1500] The chiller shall be able to maintain operation during a momentary power loss event lasting up to 5 seconds when operated at standard AHRI load and lift conditions. The chiller shall be able to ride through this momentary power loss event without shutting down. Chillers not able to maintain operation during momentary power loss events lasting up to 5 seconds shall include a properly sized thermal storage tank to maintain temperature stability in the system.
14. [OPTIONAL for WME 500/700] The chiller shall be equipped with the capability to restart and reach full load quickly in the event of a power interruption. The compressor shall be capable of restarting in less than 60 seconds after power is restored and shall reach 80% load within 75 seconds. Chillers not able to restart or load within this time frame shall include a properly sized thermal storage tank to maintain temperature stability in the system.
2.5. OPTIONAL ITEMS
A. The following optional items shall be furnished:
1. Open OR closed export crate
2. Pumpout unit, with or without storage vessel
3. Refrigerant monitor
4. Non-witness performance test (water only) in accordance with procedures and to the tolerances contained in AHRI Standard 550/590.
-- OR --
Witness performance test (water only) in accordance with procedures and to the tolerances contained in AHRI Standard 550/590.
5. OSHPD Certication: The chiller shall be OSHPD
Pre-Approved per OSP–0116-10 and be so labeled.
The chiller shall meet a minimum seismic design spectral response acceleration of 1.60 SDS. The chiller must be mounted to a rigid base and may use
neoprene wafe vibration pads.
-- OR --
IBC Certication: The chiller shall be certied to the
following codes and standards; 2009 IBC, 2010 CBC, ICC-ES AC-156, ASCE 7-05. The chiller must be
mounted to a rigid base and may use neoprene wafe
vibration pads.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Installing contractor to:
1. Install per manufacturer’s requirements, shop drawings, and contract documents.
2. Adjust chiller alignment on foundations, or subbases as called for on drawings.
3. Arrange piping to allow for dismantling to permit head removal and tube cleaning.
4. Coordinate electrical installation with electrical contractor.
5. Coordinate controls with control contractor.
6. Provide all material required for a fully operational and functional chiller.
3.2 START-UP
A. Factory Start-Up Services: Provide for as long a time as
is necessary to ensure proper operation of the unit, but in no case for less than two full working days. During the period of start-up, the start-up technician shall instruct the owner’s representative in proper care and operation of the unit.
CAT 604-9 • MAGNITUDE® MODEL WME CHILLERS 24 www.DaikinApplied.com
Page 25
Page 26
Daikin Applied Training and Development
Now that you have made an investment in modern, efcient Daikin Applied equipment, its care should
be a high priority. For training information on all Daikin Applied HVAC products, please visit us at
www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To nd
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To nd your local parts ofce, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To nd your local service ofce, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com.
Products manufactured in an ISO Certied Facility.
CAT 604-9 (02/15) ©2015 Daikin Applied | (800) 432–1342 | www.DaikinApplied.com
Loading...