Goodman WCC113 User Manual

Centrifugal Compressor Water Chillers Catalog 605-5
Models WSC, WDC, WCC, HSC
Contents
Modbus
Contents
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overview of Water-Cooled Product Line . . . . . . . . 3
World-Class Design Leader . . . . . . . . . . . . . . . 4
Design Features. . . . . . . . . . . . . . . . . . . . . . . . 4
Dual Compressor Centrifugal Chillers . . . . . . . . . . 6
Heat Recovery Models . . . . . . . . . . . . . . . . . . . . . . . 9
Templifier Heat Pump Water Heaters . . . . . . . 9
Heat Recovery Models . . . . . . . . . . . . . . . . . . . . . . 10
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
MicroTech® II Controls . . . . . . . . . . . . . . . . . 11
Application Considerations. . . . . . . . . . . . . . . . . . 14
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Starters and VFDs . . . . . . . . . . . . . . . . . . . . . . . . . 26
Motor Starters . . . . . . . . . . . . . . . . . . . . . . . . 26
Variable Frequency Drives (VFD) . . . . . . . . . 26
Selection Procedures . . . . . . . . . . . . . . . . . . . . . . 28
IPLV/NPLV Defined . . . . . . . . . . . . . . . . . . . 29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . 49
Options and Accessories . . . . . . . . . . . . . . . . . . . 52
Refrigerant Recovery Units and Monitors . . . . . 54
Pump Out Units. . . . . . . . . . . . . . . . . . . . . . . 54
Refrigerant Monitors . . . . . . . . . . . . . . . . . . . 54
Retrofit Disassembly (Knockdown Options) . . . 55
Specifications (WSC) . . . . . . . . . . . . . . . . . . . . . . 59
Specifications (WDC) . . . . . . . . . . . . . . . . . . . . . . 65
Specifications (WCC) . . . . . . . . . . . . . . . . . . . . . . 71
Starter Types and Descriptions . . . . . . . . . . . 26
Hazard Identification
DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
On the cover: WSC 087, 600 Tons, with Compressor VFD
Document: Issue Date: October 1999 Revision Date: Replaces:
CAT 605-5
September 2015 August 2015
© 2015 Daikin Applied. Illustrations and data cover the Daikin product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: LEED is a registered trademark of the U.S. Green Building Council; BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a license granted by Echelon Corporation; Modbus from Schneider Electric; MicroTech II, Open Choices from Daikin.
2 Cat 605-5
Engineered for flexibility and performance
Centrifugal Compressor Water Chillers Catalog 605-2
Models WSC, WDC, WCC, HSC Includes Higher Voltage (10/11kV) WDC/WCC models
Introduction
Overview of Water-Cooled Product Line
Introduction
Included in this manual:
Centrifugal Products included in separate manuals:
Model WSC
Capacity: 200-1250 tons (AHRI conditions)
Excellent full load performance
Model WDC
Capacity: 400-2500 tons (AHRI conditions)
Outstanding part load performance
Redundancy for increased reliability
Some sizes available with 10/11kV50Hz power option
Model WCC
Capacity: 1200-2700 tons (AHRI conditions)
Two refrigerant circuits for true counterflow
Outstanding full load performance
Some sizes available with 10/11kV50Hz power option
Magnitude™ Magnetic Bearing Compressor Chillers
Magnitude™ Model WMC
• Capacity: 145-400 tons
• Oil-free, frictionless compressor
• Excellent part-load performance
• See CAT 602 for more information
Magnitude™ Model WME
Capacity: 400-1500 tons
• Oil-free, frictionless compressor
• Outstanding efficiency
• See CAT 604 for more information
Templifier™ Model TSC Water Heater
• Recovers waste heat from process applications
• 5,000 - 19,000 MBH
Model HSC
Recycles heat normally lost in cooling towers
• Hot water - 140
See Templifier CAT 614 for more information
o
; COP as high as 7
Produces simultaneous heating and cooling
Cat 605-5 3
Features and Benefits
Features and Benefits
World-Class Design Leader
As part of Daikin Industries, a Fortune 1000 company, Daikin is the second largest air conditioning, heating, ventilating and refrigeration company in the world. We have earned a worldwide reputation for providing a full line of quality products and expertise to meet the demands of our customers. The engineered flexibility of our products allows you to fine tune your HVAC system to meet the specific requirements of your application. You benefit from lower installed and operating costs, high energy efficiency, quiet operation, superior indoor air quality (IAQ) and low cost maintenance and service.
Daikin Centrifugal Compressor Water Chillers are engineered for flexibility and performance - offering choices, options and features that provide the
right solution for your specific application-and have been doing so for over fifty years. Some highlights of our world-class centrifugal design are:
Design Features
Excellent Performance
Daikin offers a wide range of centrifugal vessel and component combinations to provide the right solution for your specific application. The single compressor WSC offers excellent full load performance, however, in most applications, chillers spend about 99% of their operating hours at part-load condidtions. Our dual compressor WDC chillers offer many attractive benefits, including outstanding part-load efficiency, and system redundancy similar to two separate chillers, with a lower total installed cost. WCC models also offer the dual compressor advantage but with counterflow vessels, and a separate refrigerant circuit for each compressor. WCC chillers excel at full load efficiency. Contact your Daikin representative for detailed information to decide which model is right for your job requirements.
Table 1: Centrifugal Models & Possible Applications
Application
Cooling <1250 tons, most hours at full load WSC Cooling >1250 tons, most hours at full load WCC Cooling, most hours at part load WDC Heating Application TSC Templifier™ Simultaneous Cooling and Heating HSC Optimized Part Load Performance Optional VFD
Positive Pressure Design
Positive pressure systems offer numerous advantages over
ve pressure design. In a negative pressure system, leaks
negati allow air, moisture, and other contaminants to seep into system, which will gradually decrease performance, as well as cause corrosion which must be removed. The Daikin positive pressure design eliminates this worry, providing sustainable performance and trouble-free ownership for the life of the unit under normal operation.
Daikin Model
Gear Driven Advantage
Daikin’s precision-engineered gear driven design allows for lighter components, less vibration, and ability to
select gear ratios that will provide the optimum impeller speed for your application. Older direct-drive designs must use large, heavy impellers to reach similar tip speeds, which cause more vibration and greater stress on shaft and motor during unexpected electrical interruptions.
The compact design and lighter weight components allow for efficient hydrodynamic bearings to be used. This means that
operation, the shaft is supported on a film of lubricant,
during with no shaft-to-bearing contact, providing theoretical infinte life bearings under normal circumstances. The design simplicity of the Daikin centrifugal compressors provides increased durability and reliable performance.
Smart Refrigerant
HFC-134a refrigerant contains no chlorine and has zero Ozone Depletion Potential (ODP), making it an environmentally superior alternative to other refrigerants such as HCFC-123. It also has an A1 ASHRAE Safety Classificiation - the lowest toxicity and flammability rating. R-134a provides the assurance of a safe, smart, and sustainable solution.
R-123 requires about 6 times the gas flow rate (cfm/ton) of R­134a, which means that the suction and discharge
piping must also be six times larger. Using R-134a allows Daikin to provide you with a smaller footprint chiller.
Table 2: Refrigerant Comparison
HFC-134a HCFC-123
No Ozone Depletion
Potential
No Refrigerant Phase Out
Date
ENVIRONMENTAL
Physically smaller, requiring
less mechanical room space.
In the event of a small leak,
refrigerant escapes, allowing
easy detection and repair
No purge unit required
No oil change is required
INSTALLATION AND MAINTENANCE
A1 ASHRAE Safety
Classification -
lowest
toxicity/flammability
SAFETY
RefrigerantResourceCenter for references and more information.
rating
See www.DaikinApplied.com /Daikin/DesignSolutions/
Ozone-depleting substance
Montreal Protocol requires
phase out in new equipment by
2020; production cease by 2030
Requires larger refrigerant flow
rate, with subsequent increase in
component and unit size.
In the event of a small leak, air
leaks into the chiller, making
detection and repair difficult. Can
degrade efficiency
Added cost and additional space
for a purge unit. Must
periodically purge unit to remove
contaminants
Annual oil change is
recommended
B1 ASHRAE Safety
Classification- higher toxicity
level
4 Cat 605-5
Features and Benefits
Unmatched Unloading
Daikin pioneered the use of moveable discharge geometry to lower the surge point of centrifugal which the compressor enters a stall or surge condition generally limits compressor unloading. Chillers with a fixed discharge will experience stall or surge at low loads due to refrigerant re-entering the impeller. When in a stall condition, the refrigerant gas is unable to enter the volute due to its low velocity and remains stalled in the impeller. In a surge condition the gas rapidly reverses direction in the impeller causing excessive vibration and heat. Daikin compressors reduce the discharge area as load decreases to maintain gas velocity and greatly reduce the tendency to stall or surge.
Figure 1: Fixed vs. Movable Discharge Geometry
In Figure 1, above, the drawing on the left shows a cross­section view of the operation at full load of a unit with a fixed compressor discharge. At full load, a large quantity of gas is discharged with a fairly uniform discharge velocity as indicated by the arrows.
The center drawing shows a fixed compressor discharge at reduced capacity. Note that the velocity is not uniform and the refrigerant tends to reenter the impeller. This is caused by low velocity in the discharge area and the high pressure in the condenser, resulting in unstable surge operation and with noise and vibration generated.
The following cutaway picture shows the unique Daikin movable discharge geometry. As the capacity reduces, the movable unloader piston travels inward, reducing the discharge cross section area and maintaining the refrigerant velocity. This mechanism capacity reduction.
allows our excellent unloading
compressors. The point at
Figure 2: Movable diffuser closes impeller discharge area as load decreases.
Controls Flexibility
MicroTech II® controls with our Open ChoicesTM feature allow easy integration with the BAS of choice using LonTalk®, BACnet® or Modbus® protocol
Retrofit Flexibility
Easy to retrofit with flexible knock-down options. See page 55 for details.
Trouble-Free Startup
All Daikin chillers are factory tested on AHRI qualified computer-controlled test stands. Each chiller is run-tested under load conditions for a minimum of one hour with evaporator and condenser water flow at job conditions (excluding glycol applications). Operating controls are checked and adjusted, and the refrigerant charge is adjusted for optimum operation and recorded on the unit nameplate. Units operating with 50-Hz power are tested with a 50-Hz power supply. The testing helps ensure correct operation prior to shipment, and allows factory calibration of chiller operating controls.
All domestic Daikin centrifugal chillers are commissioned by Daikin Factory Service personnel, or by authorized and experienced ensure that proper starting and checkout procedures are employed and helps in a speedy commissioning process, giving you confidence that your chiller is operating as expected.
Lubrication System
A separately driven electric oil pump assembly supplies lubrication at controlled temperature and pressure to all bearing surfaces and is the source of hydraulic pressure for the capacity control system.
Daikin startup technicians. This procedure helps
The control system will not allow the compressor to start until oil pressure, at the proper temperature, is established. It also allows the oil pump to operate after compressor shutdown to provide lubrication during coast-down. Lubricant from the pump is supplied to the compressor through a water-cooled, brazed-plate heat exchanger and single or dual five-micron oil filters internal to the compressor. All bearing surfaces are
Cat 605-5 5
Dual Compressor Centrifugal Chillers
pressure lubricated. Drive gears operate in a controlled lubricant mist atmosphere that efficiently cools and lubricates them.
Lubricant is made available under pressure from the compressor oil filter to the unit capacity control system and is used to position the inlet guide vanes in response to changes in leaving chiller water temperature.
If a power failure occurs, an emergency oil reservoir provides adequate lubrication flow under pressure, and prevents damage that could occur during the coast-down period with the oil pump stopped.
Since the Daikin chillers are positive pressure, there is no need to change the lubricant or filter on a regular basis. As with any equipment of
this type, an annual oil check is
recommended to evaluate the lubricant condition.
Figure 3: Lubrication System Schematic
is gas rapidly reversing direction through the impeller). A number of things can contribute to this condition including inadequate maintenance of condenser tube cleanliness, a cooling tower or control malfunction, or unusual ambient temperatures among others.
For these abnormal conditions, Daikin compressor designers have developed a protective control system that senses the potential for a surge, looks at the entire chiller system operation and takes corrective action if possible;
or stops the compressor, to help prevent any damage from occurring. This protection is provided as standard on all Daikin centrifugal compressors.
Dual Compressor Centrifugal Chillers
Dual Compressor Experience
Daikin is the expert when it comes to dual centrifugal compressor technology. We
have been successfully building dual compressor centrifugal chillers since 1971. Daikin is the only company that builds them with either a single refrigerant circuit (Model WDC) or two refrigerant circuits (Model WCC).
Benefits of Dual Compressor Chillers
Superior Efficiency
When coupled with a variable frequency drive, the extremely efficient Dual Compressor Chillers are considerably more efficient than single compressor chillers in the same size range, with IPLVs (Integrated Part Load Value) as low as 0.3 kW per ton. IPLV conditions are set by AHRI and subject to stringent testing. Insist on AHRI-certified IPLV efficiency when making efficiency comparisons.
Enhanced Surge Protection
When centrifugal compressors operate at part load, the volume of refrigerant gas entering the impeller is reduced. At the reduced flow, the impeller's capacity to develop the peak load head is also reduced. At conditions of low refrigerant flow and high compressor head (pressure difference), stall and/or surge can occur (a stall is gas static in the impeller, a surge condition
The Redundancy Feature
Daikin dual centrifugal chillers have two of everything connected to the evaporator and condenser - two compressors, two lubrication systems, two control systems, and two starters.
If any component on a compressor system fails, the component can be removed or repaired without shutting down the other compressor; providing an automatic back-up with at least 60 percent of the chiller design capacity available on WDC units and 50 percent on WCC units.
Redundancy is also built into the distributed control system, which consists of a unit controller, a compressor controller for each compressor and an operator interface touch screen. The chiller will operate normally without the touch screen being functional. If a compressor controller is unavailable, the other compressor will operate normally and handle as much of the load as possible.
Lower Installed Costs
The redundancy feature pays off in lower installed costs. An example of how to incorporate dual compressor chillers into a system requiring redundancy:
6 Cat 605-5
Dual Compressor Centrifugal Chillers
WSC Single Compressor Chillers WDC Dual Compressor Chillers
(2)
600 ton (2100 kW) On Line Units
(2)
750 ton (2100 kW) Units with
+(1)
600 (2100 kW ) t on Standby Unit 1,200 (4200 kW ) On Line tons
*
1,800 ton (6300 kW) Installed Capacity 1500 ton (52 50 kW ) Ins ta lled Capacit y
Job requirement: 1,200 tons (4200 kW), 50% Backup
*One 750-ton (2100 kW) dual chiller running on two compressors for 750 tons (2100 kW), plus one 750-ton (2100 kW) dual chiller running on one compressor for 60% of 750 tons (2100 kW) = 450 tons (1575 kW), for a total of 1200 tons (4200 kW) on any 3 of the 4 total compressors.
The elimination of the extra pumps, valves, piping, controls, rigging, and floor space can result in as much as a 35% reduction in the installation cost for a chiller plant, plus the savings on the chillers themselves.
Dual Compressor Chiller Overview
There are subtle but important differences between the single circuit WDC and two circuit WCC chillers.
Dual Circuit WCC Counterflow Chillers
These chillers have a separate refrigerant circuit for each compressor. They are available in single pass only. They provide the high full load efficiency advantage of two separate chillers arranged for counterflow operation in a single, compact unit.
Single Circuit WDC Chillers
These chillers have a single-refrigerant circuit for the evaporator and condenser with two compressors running in parallel and are available in one, two or three-pass configurations. Their salient feature is that at single­compressor, part load operation, the running compressor can utilize the entire chiller's heat transfer surface, providing outstanding part load performance.
Application of Dual Compressor Chillers
Designers and owners must decide which chiller type, or combination of chiller types, is best for their installation. Considerations include first cost, system efficiency, system reliability, space requirements, and total owning costs.
Use WCC chillers when:
Project requirement is lowest kW per ton performance at full load with high electrical demand charges.
Project has a large central plant where cycling chillers for system capacity reduction is expected (three or more chillers).
High chilled water delta-T and low water pressure drops are desired.
Built-in redundancy is required. A single compressor will provide 50% of the unit's full load capacity.
High efficiency and large capacity is required with series flow. Use two WCC units in series-counterflow in the 3,000 to 4,000 ton range.
Use WDC chillers when:
Project requirement is overall lowest energy consumption with best part load performance.
Project has smaller chilled water plant where unit unloading is expected versus cycling of chillers associated with large multi-chiller plants.
Floor space is limited (16-foot vessel length compared to 20­foot for WCC).
Two or three pass vessels are required, typical of retrofit applications.
Built-in redundancy is required. A single compressor will provide 60% of the unit's full load capacity.
Use a combination of WDC and WCC chillers when:
Peak overall system efficiency is important; for example, use three WCC and one WDC chiller, all in parallel. The WCC units are optimized for running at full load and the WDC is optimized for part load operation. The WCC units cycle on and off and the WDC unit (consider variable frequency drives on this unit) trims the load, running between five and one hundred percent capacity.
Why a Compressor Motor Failure Will Not Contaminate the Common Refrigerant Circuit on WDC dual chillers
Some people are concerned with the result of a motor burnout on a single-circuit dual compressor chiller. This is not a problem on the Daikin WDC chillers because of compressor construction and chiller layout.
The compressor motor is isolated from the main refrigerant flow circuit so that any contaminants generated by a motor failure will not pass into the main refrigerant circuit. Moisture, acid and/or carbon particles will be automatically trapped within the compressor's dedicated coolant feed and exit lines.
Internally, the compressor motor compartment is separated and sealed from the main refrigerant compression chamber. A double shaft seal on the motor side of the gear housing prevents cross flow of refrigerant along the motor shaft. The motor coolant feed line is equipped with both a solenoid valve and a check valve. These mechanical components, plus the higher pressure of the liquid refrigerant, prevent back feed into the main refrigerant system. Refrigerant vapor exiting the motor compartment must pass through a high pressure drop filter-drier, sized to immediately plug up and seal off the motor compartment. Both the coolant feed and return lines are equipped with manual shutoff valves to permit component service.
Cat 605-5 7
Dual Compressor Centrifugal Chillers
Over 30 years of field experience have proven the reliability of these compressor motors. Despite the reliability inherent in the motor design and the protective control, electrical distribution system faults and lightning strikes can occur that are beyond the control of the most conscientious designer. The coolant protective system protects the unit charge from being contaminated.
Special WDC Warranty: In the unlikely event of a motor burnout, the chiller refrigerant charge will not be
Figure 4: Motor Cooling
contaminated. This is so well proven that it is guaranteed for five years. In areas supported by Daikin Factory Service, if a motor burnout occurs in one compressor and contaminates the refrigerant circuit, any resultant damage to the other compressor will be repaired and the refrigerant charge replaced at no cost to the customer for parts and labor. The terms of the original chiller warranty apply to the original burned out compressor.
Efficiency
Chillers usually spend 99% of their operating hours under part load conditions, and most of this time at less than 60% of design capacity. One compressor of a dual WDC chiller operates with the full heat transfer surface of the entire unit. For example, one 500-ton (1,750 kW) compressor on a 1,000 ton (3,500 kW) dual chiller utilizes 1,000 tons (3500 kW) of evaporator and condenser surface. This increases the compressor's capacity and also results in very high efficiency.
Typical efficiencies for a WDC dual chiller, taken from a selection computer run, look like this:
Full load efficiency: 0.550 kW per ton (6.5 COP)
60% load, one compressor: 0.364 kW per ton (9.6 COP)
IPLV: 0.415 kW per ton (8.5 COP)
The addition of VFDs to the WDC dual produces an astonishing AHRI certified IPLV of 0.340 for the above case. Specific selections can vary up or down from this example. IPLV is defined in the Selection section of this manual beginning on page 28 .
8 Cat 605-5
compressor chiller
WCC chillers, with their counterflow design, excel at full load efficiency. Each of the two compressors operates at a lower head (pressure differential) than single compressor chillers in parallel. With any pump or compressor, lower head means lower power for a given flow. As shown on the right, the #2 (downstream compressor) makes 42 F water but has only 89 F condenser water leaving instead of 95 F typical of a single compressor unit. The #1 compressor has 95 F condenser water leaving, but only has to make 47.6 F chilled water.
The Replacement Market Advantage
Bolt-together construction on single and dual compressor chillers along with factory disassembly available as an option simply the tough entrance situations.
Put 20% or more tons in the same footprint.
Add dual compressor redundancy.
Greatly reduce chiller energy consumption.
Install a refrigerant with no phase-out date.
Opens many options for multiple chiller plants using WSC,
WDC and WCC combinations.
Heat Recovery Models
EVAPORATOR
TOW E R
COND ENSER
RE COV E RY
COND E N SE R
AUXILI ARY
HE ATER
HEAT L OAD
TCTCCOO LI N G
LOAD
OPEN CI RC UI T TOWER
HEAT REC OVERY
CHI LLER
LEGEND
TC TEMPERATURE CONTROL POINT
PUMP
Typical Building Types
Hotels/Motels Health Care Athletic Facilities Resorts Schools Food Service Nursing Homes
Typical Applications
Space Heating Outside Air Heating Reheat Service Hot Water Laundries Kitchens
G
TOWER
)
G
HEATER
R
R
CONDENSER
R
COOLING
R
90° F
(35°C)
F
CHILLER
TC
TC
C
Heat Recovery Models
Heat Recovery Models
For decades, Daikin has pioneered the use of heat recovery chillers and the unique Daikin Water Heater to reduce energy costs. These products have become more important than ever with the current emphasis on total building efficiency. ASHRAE Efficiency Standard
90.1 mandates the use of heat recovery equipment of this type in a wide range of buildings.
Heat Recovery Chillers
Model HSC heat recovery chillers, with a single compressor, have a single condenser with split bundles, i.e., two separate water passages divided by separate water heads as shown in the photograph to the right. The inboard water connections are connected to the cooling tower, the other water side is connected to the heating system.
The economic feasibility of hot water generated with these units depends on heating and cooling load profiles and on the relative cost of the available energy sources. A compressor's kW per ton is heavily influenced by the pressure head it is pumping against. During heat recovery operation, the entire cooling load is operating against the high head required by the
Templifier Heat Pump
hot water temperature. For this reason, it is desirable to maximize the percentage of the
total rejected heat used for the heating load. Daikin's economic evaluation program, Energy Analyzer , available on CD from your local Daikin sales office, is the perfect tool to determine the economic feasibility of using this proven technology.
Figure 5: Heat Recovery Chiller Piping Schematic
Templifier Heat Pump Water Heaters
Model TSC: 5,000 to 19,000 MBH
The Model TSC Templifier was developed in the 1970s, after the 1973 oil embargo, as a device to replace fossil-fired water heaters with electric heaters. The concept was simple; direct a stream of warm waste heat to the evaporator of a refrigeration unit, amplify the temperature of the heat through the compression cycle, and then deliver the heat from the condenser, at a higher useful temperature, to a heating load.
The flow diagram shown to the left illustrates just how the Templifier unit is placed decision to include a Templifier water heater is almost always a financial one. Evaluation of load profiles, energy costs, and owning costs is made simple by using the Daikin Energy Analyzer evaluation program to determine if the return on investment meets the owner's requirements.
When there is sufficient waste heat available, Templifier units can be very attractive where fossil fuels are not available, or where their use is restricted due to pollution problems or other reasons. Compared to electric resistance heating, the energy cost for a Templifier unit to heat domestic water, for example, could be 7 to 8 times less!
Where to Use Templifier Water Heaters:
in a chilled water system. The
Table 3: Typical COP’s
Hot Water
Temperatures
COP (Based on 85F off Chiller to Templifier)
110F 120F130F 140F
8.3 6.8 6.0 4.5
Figure 6: Templifier Heat Pump Water Heater Schematic
COOLI N
85°
(29°C)
55°F
(13°C)
EVAPO RATO
12 5°F (52°C
45°F (7 ° C )
95 °F
HEATIN
LOAD
TEMPLI FI ER HEAT
PUMP WAT ER HEATE
T
SUPPLE-
MENTAL
CONDE NSE
EVAPORAT O
TEMPE RATURE CONTRO L
13 5°F (57°C)
(32° )
Cat 605-5 9
LOA D
Heat Recovery Models
Intermediate Heat Exchanger
Ground Water Heat Source
Service Hot Water Piping
CONDENSER
EVAPORATOR
ST OR AG E
TA N K
140°F (60°C)
TEMPLIFIER
HEAT
SOURCE
140°F
(60°C)
140°F
(60°C)
RETURN /
MAKEUP
OUTP UT
STANDBY /
A UXI LI AR Y HE AT
T- C
Figure 7: Typical Templifier Applications
Heat Recovery Models
10 Cat 605-5
Controls
Controls
MicroTech® II Controls
Daikin Centrifugal chillers are equipped with the proven reliability of the MicroTech® II controls system with touch­screen interface. The control system is designed for easy and intuitive operation, and configured for efficient and reliable operation. Plus, Daikin's Open Choices™ feature allows integration with your building automation system (BAS) through an optional communication module (see Options and Accessories section, page 52).
Designed with the System Operator in Mind
Reliable, economic use of any chiller depends on an easy operator interface. That's why operation simplicity was one of the primary considerations MicroTech® II controller and Operator Interface Touch-Screen (OITS). The 15-inch color touch-screen is mounted on a fully adjustable arm. The chiller is graphically displayed, with key operating parameters viewable on the screen. Alarm history and operation setpoints are easily accessed through intuitive touch-screen buttons. The chiller operating manual is also viewable on the touch screen and can be downloaded via USB.
MicroTech® II Controls Enhance Operating Economy
Many features have been integrated into MicroTech II controls to ensure optimum operating economy. In addition to replacing normal relay logic circuits, we've enhanced the controller's energy saving capabilities with the following features:
• Direct control of water pumps Optically isolated, digital output relays provide automatic lead-lag of the evaporator and condenser pumps, permitting pump operation only when required.
• User-programmable compressor soft loading Prevents excessive power draw during pull down from high chilled water temperature conditions.
in the development of the
• Chilled-water reset Reset the leaving water temperature based on the return water temperature. Raising the chilled water setpoint during periods of light loads dramatically reduces power consumption.
• Demand limit control Maximum motor current draw can be set on the panel, or can be adjusted from a remote 4-20ma or 1-5 VDC BAS signal. This feature controls maximum demand charges during high usage periods.
• Condenser water temperature control Capable of four stages of tower fan control, plus an optional analog control of either a three-way tower-bypass valve or variable speed tower-fan motor. Stages are controlled from condenser-water temperature. The three-way valve can be controlled to a different water temperature or track the current tower stage. This allows optimum chilled water plant performance based on specific job requirements.
• Staging Options (Multiple Chiller Installations) The MicroTech® II controller is capable of compressor staging decisions and balancing compressor loads between up to four WSC,WDC or WSC Daikin chillers using defaults or operator-defined staging.
• Plotting Historic Trends Past operation of the chiller can be plotted as trend lines and even downloaded to a spreadsheet for evaluation and analysis.
Proactive Controls
MicroTech® II controls constantly monitor chiller status, and automatically take
proactive measures to relieve abnormal conditions or shut the unit down if a fault occurs. For example, if a problem occurs in the cooling tower and discharge pressure starts to rise, the controller will automatically hold the load point and activate an alarm signal. A further rise in pressure will initiate compressor unloading in an effort to maintain the setpoint pressure. If the pressure continues to rise, the unit will shut off at the cutout pressure setting to protect the unit.
Table 4: Daikin MicroTech® II Controls Features and Benefits
FEATURE BENEFIT
Open Choices™ Option
Touch-screen Interface
Alarm/Fault History and Trend Logging Historical trend data can be downloaded from an onboard USB port
Precise 0.2 F chilled water controls Provides stability in chilled water system
Proactive Controls
Integrated lead/lag pump control
Condenser Water Temperature Control Provides tower fan control /modulation based on system conditions
Multiple language capability -
Metric or IP units of measure
Cat 605-5 11
Easy integration into a building management system via a factory or field-installed
module communicating with BACnet , LONMARK or Modbus protocols.
Easy to read, adjustable, large 15-inch, color touch screen;
See chiller operation at a glance; easily view and change setpoints
Proactive correction of “unusual conditions” allows chiller to stay online; activates
alarm and modifies chiller operation to provide maximum possible cooling
Automatic control of chilled water and condenser water pumps; permits pump
operation only when required
Great asset for world-wide applications
Controls
Alarm History for Easy Troubleshooting
The controller memory can retain and display the cause of the current fault and the last twenty-five fault conditions. This feature is extremely useful for troubleshooting and maintaining an accurate record of unit performance and history.
The Home Screen shown below is the primary viewing screen on the Operator Interface Touch Screen (OITS). It gives real­time data on unit status, water temperatures, chilled water setpoint and motor amp draw.
Figure 8: OITS Home Screen
Trend Logging
Ever wonder how your chiller performed last night? Were you holding the correct chilled water temperature? What kind of cooling load did the chiller have? The Daikin MicroTech® II controller can provide the answers, thanks to its huge memory, and plot water temperatures, refrigerant pressures, and motor load data. These values can also be downloaded through a convenient USB port (located on the unit control panel) into a spreadsheet for detailed evaluation and analysis.
Figure 10: OITS Trend History Screen
If an alarm occurs, a red button appears on the screen that leads to the Active Fault Screen whichgives complete fault information so that the fault can be corrected and cleared.
Changing Setpoints
Changing setpoints is easy with the MicroTech II control. For example, to change the chilled water setpoint, press SET button from any screen, then press WATER and this screen appears, now press button #1, Leaving Water Temperature, and you are ready to input a password and a new value. (The controller features a three-level password security system to provide protection against unauthorized use.)
Figure 9: OITS Setpoint Screen
WDC/WCC Chiller Controls
Dual compressor model centrifugal chillers feature a MicroTech® II unit controller and a separate controller for each compressor. This distributed control scheme allows the operation of each compressor in Performance data for each compressor is monitored separately by each controller, and can be controlled and monitored on the interface panel.
Compressor staging and the load balance function are standard features the compressor with the fewest number of starts first, and will only start remaining compressors when sufficient load has been established. The staging function will stop the compressor with the most run-hours as the load decreases to single compressor range. During two-compressor operation, the load balance function will equalize the load between each compressor, providing optimum unit efficiency.
Versatile Communications For Even More Control
For flexibility there are three ways to interface with the MicroTech® II controller:
Direct entry via Operator Interface Touch-Screen.
Direct entry as above, plus remote digital and analog input/
of MicroTech® II controllers. Smart scheduling starts
output signals for certain functions such as enable run input, alarm signal output, chilled water reset and load limiting, outputs for pump and tower fan control, for variable speed tower fan and/or tower bypass valve.
dependently from the other.
12 Cat 605-5
Controls
Interface with a building automation system (BAS) with optional modules, communicating directly with BACnet,
have received LONMARK certification with the optional LONWORKS communication module.
LONMARK or Modbus protocols.
Protocol Options
Building Automation Systems
All MicroTech II®
controllers are capable of communication with BAS, providing seamless integration and comprehensive monitoring, control, and two-way data exchange with industry standard protocols such as LONMARK , Modbus or BACnet .
•BACnet MS/TP
•BACnet IP
• BACnet Ethernet
• LONWORKS (FTT-10A)
• Modbus RTU
Open Choices Benefits
• Easy to integrate into your building automation system
• Factory- or field-installed communication modules
The BAS communication module can be ordered factory­mounted with your chiller, or can be field-installed at any time after the chiller is installed.
• Comprehensive point list for system integration, equip­ment monitoring and alarm notification
• Comprehensive data exchange
Electric Power Options
In order for the BAS to read the full complement of power data on low and medium voltage solid state, across-the-line, and
Integration Made Easy
Daikin unit controllers strictly conform to the interoperability guidelines of the LONMARK Interoperability Association and the BACnet Manufacturers Association. They
Table 5: Typical BAS Read/Write Data Points
Typical Data Points Active Setpoint R Cond EWT R Evap Water Pump Status R Actual Capacity R Cond Flow Switch Status R Heat Recovery EWT R Capacity Limit Output R Cond LWT R Heat Recovery LWT R Capacity Limit Setpoint W Cond Pump Run Hours R Heat Setpoint W
Chiller Enable W Cond Refrigerant Pressure
Chiller Limited R Cond Sat. Refrigerant Temp
Chiller Local/Remote R Cond Water Pump Status R Liquid Line Refrigerant Temp R Chiller Mode Output R Cool Setpoint W Maximum Send Time W Chiller Mode Setpoint W Current Alarm R Minimum Send Time W Chiller On/Off R Default Values W Network Clear Alarm W Chiller Status R Evap EWT R Oil Feed Pressure R Compressor Discharge Temp R Evap Flow Switch Status R Oil Feed Temp R Compressor Percent RLA R Evap LWT for Unit R Oil Sump Pressure R Compressor Run Hours R Evap LWT for Compressor R Oil Sump Temp R Compressor Select W Evap Pump Run Hours R Outdoor Air Temp Compressor Starts R Evap Refrigerant Pressure R2 Pump Select W Compressor Suction Line Temp R Evap Sat. Refrigerant Temp R2 Run Enabled R
1.) Data points available are dependent upon options selected
2.) Per compressor
wye-delta starters, the optional Field Metering Package must be ordered with the chiller. Otherwise the BAS will only read the average unit amps. This power data is not available to a
BAS on all other starter voltages and types.
1
(W = Write, R = Read)
2
Ice Setpoint W
R
2
Liquid Line Refrigerant Pressure
R
Cat 605-5 13
Application Considerations
Application Considerations
Location
These chillers are intended only for installation in an indoor or weather protected area consistent with the NEMA 1 rating on the chiller, controls, and electrical panels. If indoor sub­freezing temperatures are possible, special precautions must be taken to avoid equipment damage. Equipment room temperature for operating and standby conditions is 40°F-
122°F (4.4°C-50°C)
CAUTION
Daikin Centrifugal Chillers are intended only for installation in indoor areas protected from temperature extremes. Failure to comply may result in equipment damage and may void the manufacturer warranty.
Operating/Standby Limits
Table 6: Operating/Standby Limits
Equipment room operating temperature: 40°-104°F (4.4°-40°C)
Equipment room temperature, standby, with water in vessels and oil cooler:
Equipment room temperature, standby, without water in vessels and oil cooler:
Maximum entering condenser water temperature, startup:
Maximum entering condenser water temperature, operating:
Minimum entering condenser water temperature, operating:
Minimum leaving chilled water temperature:
Minimum leaving chilled fluid temperature with correct anti-freeze fluid:
Maximum entering chilled water temperature, operating:
Maximum oil cooler entering temperature:
Minimum oil cooler entering temperature:
Piping
Piping must be adequately supported to remove weight and strain on the chiller's fittings and connections. Do not use PVCor CPVC piping. Be sure piping is adequately insulated. Install a cleanable 20-mesh water strainer upstream of the evaporator and condenser. Install enough shutoff valves to permit draining water from the evaporator or condenser
without draining the complete system.
CAUTION
Freeze Notice: The evaporator and condenser are not self­draining. Both must be blown out to completely remove water to help prevent freeze-up
.
Include thermometers and pressure gauges at the chiller inlet and outlet connections and air vents at the high points of piping. The water heads can be interchanged (end for end), allowing water connections to be made at either end of the
40°-104°F (4.4°-40°C)
0°F-122F (-18°C-50°C)
design + 5°F (2.7°C)
job-specific design temperature
see this page.
38°F (3.3°C)
15°F (9.4°C)
90°F (32.2°C)
80°F (26.7°C)
42°F (5.6°C)
unit. Use new head gaskets when interchanging water heads. When water pump noise is objectionable, use rubber isolation sections at both the inlet and outlet of the pump. Vibration eliminator sections in the condenser inlet and outlet water lines are not normally required. Where noise and vibration are critical and the unit is mounted on spring isolators, flexible piping and conduit connections are necessary. If not factory installed, a flow switch or pressure differential switch must be installed in the leaving chilled water line in accordance with the flow switch manufacturer's instructions.
Note: Victaulic connections are AWWA C-606. Field supply
transitions if Victaulic brand AGS® (Advanced Groove System) type grooves are used on the field piping.
Optimum Water Temperatures and Flow Rates
A key to improving energy efficiency for any chiller is minimizing the lift, or pressure difference, between the compressor suction and discharge pressures. Reducing the lift reduces the compressor work, and hence its energy consumption per unit of output. The chiller typically has the largest motor of any component in a chilled water system.
Higher leaving chilled water temperatures
Warmer leaving chilled water temperatures will raise the compressor's suction pressure and decrease the lift, improving efficiency. Using 45 F (7.0 C) leaving water instead of 42 F (5.5 C) will make a significant improvement.
Evaporator temperature drop
The industry standard has been a ten-degree temperature drop in the evaporator. Increasing the drop to 12 or 14 degrees will improve the evaporator heat transfer, raise the suction pressure, and improve chiller efficiency. Chilled water pump energy will also be reduced.
Condenser entering water temperature
As a general rule, a one-degree drop in condenser entering water temperature will reduce chiller energy consumption by two percent. Cooler water lowers the condensing pressure and reduces compressor work. One or two degrees can make a noticeable difference. The incremental cost of a larger tower can be small and provide a good return on investment.
Minimum Condenser Water Temperature Operation
When ambient wet bulb temperatures are lower than design, the condenser water temperature can be allowed to fall. Lower temperatures will improve chiller performance.
Up to 600 Tons
Daikin centrifugal chillers up to 600 Tons are equipped with electronic expansion valves (EXV) and will start and run with entering
condenser water temperatures as low as shown in Figure 11 (based on a 10 degree F condenser Delta-T) or as calculated from the following equation on which the curves are based
14 Cat 605-5
Application Considerations
LChWT
42 LChWT
Min. ECWT = 5.25 + 0.88*(LWT) - DT
FL*
(PLD/100) + 22 *(PLD/1 00)2
ECWT = E nt erin g c ond en ser water te mperat ur e LWT = Leaving chilled water temperature DT
FL
= Ch ille d Wate r D elta -T at full l oad
PL D = The pe rc ent ch ille r load poin t to b e chec ked
For example; at 44F LWT, 10 degree F Delta-
water temperature could be as low as 44.5F. This provides excellent operation with water­economizer systems.
Figure 11: Minimum Entering Condenser Water Temperature (With Electronic Expansion Valve)
Minimum Entering Condenser Water Temperature - 10 F Range
65.0
60.0
55.0
50.0
F ,
T W C
E
45.0
40.0
35.0
30.0 0 10 20 30 40 50 60 70 80 90 100 110
44
Percent Load
T, and 50% full load operation, the entering condenser
Cat 605-5 15
side
Application Considerations
44 LChW T
Over 600 Tons
Chillers over approximately 600 Tons are equipped with thermal expansion valves (TXV) and will start and run with entering condenser water temperatures as low as calculated by the following equation and shown in the chart following.
"ECWT = Entering condenser water temperature
"LWT = Leaving chilled water temperature
"DTFL = Chilled Water Delta-T at full load
"PLD = The percent chiller load point to be checked
Min. ECWT = 7.25 + LWT- 1.25* DTFL(PLD/100) +
65. 0
60. 0
55. 0
50. 0
45.0
40. 0
2
Minimu m Ent er ing C ond ens er Wate r Temp er atur e - 10 F R an ge
42
LChWT
22*(PLD/100)
Figure 12: Minimum Entering Condenser Water Temperature (Thermal Expansion Valve)
F ,
T W C
E
35. 0
30. 0 0 102030405060708090100110
Percen
t Load
For example; at 44 F LWT, 10 degree F Delta-T, and 50% full load operation, the entering condenser water temperature could be as low as 50.5 F. This provides excellent operation with water-side economizer systems.
Depending on local climatic conditions, using the lowest possible entering condenser water temperature may be more costly in total system power consumed than the expected savings in chiller power would suggest, due to the excessive fan power required.
Cooling tower fans must continue to operate at 100% capacity at low wet bulb temperatures. As chillers are selected for lower kW per ton, the cooling tower fan motor power becomes a higher percentage
of the total peak load chiller power. Daikin's Energy Analyzer program can optimize the chiller/ tower operation for specific buildings in specific locales.
Even with tower fan control, some form of water flow control, such as tower bypass, is recommended.
Condenser water temperature rise
The industry standard of 3 gpm/ton or about a 9.5-degree delta-T works well for most applications. Reducing condenser water flow to lower pumping energy will increase the water temperature rise, resulting in an increase in the compressor's
condensing pressure and energy consumption. This is usually not a productive strategy.
System analysis
Although Daikin is a proponent of analyzing the entire system, it is generally effective to place the
chiller in the most efficient mode because it is, by far, a larger energy consumer than pumps. The Daikin Energy Analyzer program is an excellent tool to investigate the entire system efficiency, quickly and accurately. It is especially good at comparing different system types and operating parameters. Contact your local Daikin sales office for assistance on your particular application.
For Best Chiller Efficiency
The designer must determine the proper chiller efficiency for a given application. The most efficient chiller is not always the best. A life cycle analysis (as performed by Daikin's Energy Analyzer program, for example) is the only way to be sure of the best selection. Utility costs, load factors, maintenance costs, cost of capital, tax bracket; in other words, all the factors affecting owning cost, must be considered.
Generally, the attempts to save the last few full load kW are very costly. For example, the cost to go from 0.58 to 0.57 kW/
16 Cat 605-5
Application Considerations
ton could be very costly because of the large number of copper tubes that would have to be added to the heat exchangers.
Table 7:
Vessel Activity Example
Evaporator
Evaporator
Evaporator Lower flow rates
Condenser
Condenser
Higher leaving water Temperatures
Higher water temperature drops
Lower entering water temperature
Higher flow rates (3.0 gpm/ ton or higher)
44F instead of 42F
12°F instead of 10°F
2.4 gpm/ton instead of
3.0 gpm/ton
84F instead of 85F
3.0 gpm/ton instead of
2.5 gpm/ton
Mixing Single and Dual Compressor Chillers
WDC dual compressor chillers excel at part load operation, while single compressor chillers usually have better full load efficiency. A good chiller plant strategy is to install one dual and one or more single compressor units. Run the dual until it is fully loaded, then switch to the single compressor unit and run it only at full load, using the dual to trim the load.
Series Counterflow and Series Parallel Chillers
The design of piping systems can greatly impact chiller performance. A popular system is to place the evaporators in series with the chilled water flowing from one evaporator to the next as shown in Figure 13 and Figure 14. Two different condenser water piping arrangements can be used. Parallel flow (Figure 13) divides the total condenser flow between the two condensers. The counterflow system (Figure 14) puts all of the condenser water through the condenser of the lag chiller (chiller producing the coldest evaporator leaving water) and then through the lead chiller (chiller seeing the warmest evaporator water temperatures).
tons) combines counterflow design into one unit. See page 6 for details.
Figure 13: Series Parallel Flow
Figure 14: Series Counterflow Flow
Typically, since the lead machine will see the warmest evaporator water, it will have the greater capacity and larger portion of the total system evaporator temperature drop. Again referring to Figure 13 and Figure 14, the lead machine has an
8.4 degree drop (56.0 degree drop (47.6
°F-47.6°F) and the lag machine has a 5.6
°F - 42.0°F).
Condenser water flow is important to overall system efficiency. With parallel flow (Figure 13), the condensers have identical flow conditions (95 to 85 degrees in this example) with the compressor lift shown. With counterflow arrangement the lift on the lead machine is significantly lower, reducing compressor work and making the overall system efficiency about 2% better. Even though the chiller performance is different, it is good practice to use the same chiller models.
Both the WSC and WDC chillers are suitable for series counterflow arrangement and include controls specifically designed for series chillers. For more information, please refer to Application guide AG -31-003: Chiller Plant Design. Daikin's model WCC dual compressor chiller (1200 to 2700
Cat 605-5 17
Application Considerations
CHILLER
OIL COOLER
STOP VALVE
STRAI NER
MAX. 40 MESH
SOLENO ID
VA LV E
DRA IN VALVE OR PLUG
PUMP
OPEN
DRAIN VALVE
OR PLUG
SOL EN OID
VA LVE
OIL COOLE R
STRAINE R
MAX. 40
MESH
DISCHARGE ABOVE HI GH EST POSSIBLE WATER LEVEL
Oil Coolers
Daikin centrifugal chillers have a factory-mounted, water­cooled oil cooler with a temperature controlled water regulating v Cooling water connections are located at the rear of the unit, near the compressor and are shown on the specific unit certified drawings. Models WDC 063 through 087 and all WCC have the cooling water connections in the lower portion of one tube sheet.
WDC 063, 079, 087, 100 and 126 dual compressor chillers are equipped as above, but the water piping for the two oil coolers is factory piped to a common inlet and outlet connection.
Field water piping to the inlet and outlet connections must be installed according to good piping practices and must include stop valves to isolate the cooler for servicing. A 1" minimum cleanable filter (40 mesh maximum) and drain valve or plug must also be field installed. The water supply for the oil cooler must be from the chilled water circuit, or from an independent clean source such as city water. When using chilled water, it is important that the water pressure drop across the evaporator is greater than the pressure drop across the oil cooler or insufficient oil cooler flow will result. If the pressure drop across the evaporator is less than the oil cooler, the oil cooler must be piped across the chilled water pump, provided that its pressure drop is sufficient. The water flow through the oil cooler will be adjusted by the unit's regulating valve so that the temperature of oil supplied to the compressor bearings (leaving the oil cooler) is between 90
C).
43
NOTE: The system must be designed for the highest cooling water temperature possible, which may occur for a short time during startup.
alve and solenoid valve for each compressor.
F and 110F (32C and
Table 9: WSC with VFD Oil Cooler Data
Hot Side POE Lub.
Cold Side Water
WSC/HSC 063 - 087
Flow, gpm 9.9 13.4 4.0 2.9 2.3 Inlet Temperature, F 118.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 90.3 99.6 103.1 105.6 Pressure Drop, ft. - 30.5 6.7 4.8 3.6
WSC/HSC 100 - 126
Flow, gpm 15.8 24.4 7.0 5.0 4.0 Inlet Temp., F 120.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 89.8 100.1 103.6 106.2 Pressure Drop, ft. - 30.6 15.7 11.4 9.3
NOTES:
1WDC and WCC units have twice the cooling water flow rate
of the comparable WSC chiller.
2
Pressure drops include valves on the unit.
When supplied with city water, the oil piping must discharge through a trap into an open drain to prevent draining the cooler by siphoning. The city water can also be used for cooling tower makeup by discharging it into the tower sump from a point above the highest possible water level.
Note: Particular attention must be paid to chillers with variable
chilled water flow through the evaporator. The pressure drop available at low flow rates can very well be insufficient to supply the oil cooler with enough water. In this case an auxiliary booster pump can be used or city water employed.
Cooling Water Connection Sizes: WDC/WCC 100/126 have 1­1/2 in. FPT connections, all other WDC and WSCs are 1 in. FPT.
Figure 15: Oil Cooler Piping Across Chilled Water Pump
Compressors using chilled water for oil cooling will often start with warm "chilled water" in the system until the chilled water loop temperature is pulled down. With cooling water in the
F to 55F (4C to 13C) range, considerably less water will
40
R
S
be used and the pressure drop will be greatly reduced. The following table contains oil cooler data at various inlet water temperatures.
Table 8: WSC Oil Cooler Data
Hot Side POE
Lube
Cold Side Water
WSC 063 - 087
Flow, gpm 9.9 11.9 2.9 2.0 1.54 Inlet Temperature, F 118.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 87.3 94.5 98.3 101.4 Pressure Drop, psi - 4.3 0.3 0.14 0.09
WSC 100 - 126
Flow, gpm 15.8 21.9 5.11 3.5 2.7 Inlet Temperature, F 120.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 87.0 95.0 99.0 102.3 Pressure Drop, psi - 3.78 0.23 0.11 0.07
18 Cat 605-5
Figure 16: Figure 17, Oil Cooler Piping With City Water
R
S
COOLING TOWER
COOLING TOWER MAKEUP
DRA IN
STOP VALU E
Application Considerations
5.0
2
....
2
2
2
1
 
 
n
DDD
Common
D
Pumps
Model WSC, WDC and WCC chiller compressor motors operate at 3600 rpm on 60 Hz power (3000 rpm on 50 Hz). When VFDs are employed, the hertz/speed can be reduced by 70%. To avoid the possibility of objectionable harmonics in the system piping, 4-pole, 1800/1500 rpm system pumps should be used. The condenser water pump(s) must be cycled off when the last chiller of the system cycles off. This will keep cold condenser water from migrating refrigerant to the condenser. Cold liquid refrigerant in the condenser can make start-up difficult. In addition, turning off the condenser water pump(s) when the chillers are not operating will conserve energy.
Include thermometers and pressure gauges at the chiller inlet and outlet connections and air vents at the high points of piping. The water heads can be interchanged (end for end), allowing water connections to be made at either end of the unit. Use new head gaskets when interchanging water heads. When water pump noise is objectionable, use rubber isolation sections at both the inlet and outlet of the pump. Vibration eliminator sections in the condenser inlet and outlet water lines are not normally required. Where noise and vibration are critical and the unit is mounted on spring isolators, flexible piping and conduit connections are necessary. If not factory installed, a flow switch or pressure differential switch must be installed in the leaving chilled water line in accordance with the flow switch manufacturer's instructions.
Victaulic connections are AWWA C-606 on 14-inch and larger sizes. Field supply transitions if Victaulic brand AGS® (Advanced Groove System) type grooves are used on the field piping.
Filtering and Treatment
Owners and operators must be aware that if the unit is operating wit cooling tower is required. Make sure tower blow-down or bleed-off is operating. Atmospheric air contains many contaminants, which increases the need for water treatment. The use of untreated water will result in corrosion, erosion, slime buildup, scaling, or algae formation. A water treatment service should be used. Daikin is not responsible for damage or faulty operation from untreated or improperly treated water.
Machine Room Ventilation
In the market today, centrifugal c either hermetic or open type motors. Hermetic motors are cooled with refrigerant and dissipate their heat through the cooling tower. On the other hand, open motors circulate equipment room air across themselves for cooling and reject the heat to the equipment room. Daikin chillers have hermetic motors and DO NOT require additional ventilation.
For chillers with open-drive type, air-cooled motors, good engineering practice dictates that the motor heat be removed to
h a cooling tower, cleaning and flushing the
hillers are available with
prevent high equipment room temperatures. In many applications this requires a large volume of ventilation air, or mechanical cooling to properly remove this motor heat.
EXAMPLE: 1000 tons x 0.6 kW/Ton x 0.04 motor heat loss x
0.284 Tons/kW = 7 tons (24 kW) cooling
The energy and installation costs of ventilation or mechanical cooling equipment must be considered when evaluating various chillers. For a fair comparison, the kW used for the ventilation fans, or if mechanical cooling is required, the additional cooling and fan energy must be added to the open motor compressor energy when comparing hermetic drives. Additionally, significant costs occur for the purchase, installation, and maintenance of the ventilation or air handling units.
Equipment room ventilation and safety requirements for various refrigerants is a complex subject and is updated from time to time. The latest edition of ASHRAE 15 should be consulted.
Thermal Storage
Daikin chillers are designed for use in thermal storage systems. The chillers must be considered. The first is normal air-conditioning
The second condition occurs during the ice making process when leaving fluid temperatures are in the 22
(-5.6
°C to -3.3°C) range.
The MicroTech II control system will accommodate both operating points. The ice mode can be started or stopped by an input signal to the microprocessor from a BAS or through a chilled water reset signal. When a signal is received to change from the ice mode to the normal operating mode, the chiller will shut down until the system fluid temperature rises to the higher setpoint. The chiller will then restart and continue operation at the higher leaving fluid temperature. When changing from normal cooling to the ice mode, the chiller will load to maximum capacity until the lower setpoint is reached.
Computer selections must be made to check that the chiller will operate at both conditions. If the "ice mode" is at night, the pressure differentials between the evaporator and condenser are usually similar to normal cooling applications. The leaving fluid temperature is lower, but the condensing temperature is also lower because the cooling tower water is colder. If the ice mode can also operate during the day, when cooling tower water temperatures are high, a proper selection becomes more difficult because the two refrigerant pressure differentials are significantly different.
A three-way condenser water control valve is always required.
have two operating conditions that
duty where leaving evaporator fluid temperatures range from 40 (4.4
°F to 45°F
°C to 7.2°C).
°F to 26°F
Cat 605-5 19
Application Considerations
Variable Speed Pumping
Variable speed pumping involves changing system water flow relative to cooling load change chillers are designed for this duty with two limitations.
First, the rate of change in the water flow needs to be slow, not greater than 10% of the change per minute. The chiller needs time to sense a load change and respond.
Second, the water velocity in the vessels must be 3 to 10 fps (0.91 and occurs which reduces heat transfer. Above 10 fps (3.0 m/sec), excessively high pressure drops and tube erosion occur. These flow limits can be determined from the Daikin selection program.
We recommend variable flow only in the evaporator because there is virtually no change in chiller efficiency compared to constant flow. In other words, there is no chiller energy penalty. Although variable speed pumping can be done in the condenser loop, it is usually unwise. The intent of variable flow is to reduce pump horsepower. However, reducing condenser water flow increases the chiller's condensing pressure, increasing the lift that the compressor must overcome which, in turn, increases the compressor's energy use. Consequently, pump energy savings can be lost because the chiller operating power is significantly increased.
Low condenser flow can cause premature tube fouling and subsequent increased compressor power consumption. Increased cleaning and/or chemical use can also result.
Vibration Mounting
Every Daikin chiller is run tested and compressor vibration is measured and limited to a maximum rate second, which is considerably more stringent than other available compressors. Consequently, floor-mounted spring isolators are not usually required. Rubber mounting pads are shipped with each unit. It is wise to continue to use piping flexible connectors to reduce sound transmitted into the pipe and to allow for expansion and contraction.
AHRI Standard 575 Sound Ratings
Sound data in accordance with AHRI Standard 575 for individual units are available from your local Daikin representative. Due to the large number of combinations and variety of applications, sound data is not included in this catalog.
3.0 m/sec). Below 3 fps (0.91 m/sec), laminar flow
s. Daikin centrifugal
of 0.14 inches per
component
Discharge Line Sound Packages
For extremely sensitive projects, an optional discharge line sound package is offered consisting of sound insulation installed on the unit's discharge line. An additional 2 to 4 dbA reduction normally occurs.
System Water Volume
All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize, without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes.
Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors.
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of "gallons of water volume equal to two to three times the chilled water gpm flow rate" is often used.
A properly designed storage tank should be added if the system components do not provide sufficient water volume.
Relief Valves
Relief valve connection sizes are 1-inch quantity shown in Table 10 for the evaporator and condenser. In addition, there is a relief valve (3/8 inch flare) on the top of the oil sump of all units.
All relief valves (including the oil sump) must be piped to the outside of the building in accordance with ANSI/ASHRAE 15-
2001. The new 2001 standard has revised the calculation method compared to previous issues.
Twin relief valves, mounted on a transfer valve, are used on the condenser so that one relief valve can be shut off and removed for testing or replacement, leaving the other in operation. Only one of the two valves is in operation at any time. Where 4 valves are shown, on some large vessels, they consist of two relief valves mounted on each of two transfer valves. Only two relief valves of the four are active at any time.
FPT and are in the
20 Cat 605-5
Application Considerations
Figure 17: Typical Vent Piping
Vent piping is sized for only one valve of the set since only one can be in operation at a time.
Relief Pipe Sizing (ASHRAE Method)
Daikin centrifugal chillers have the following relief valve settings and discharge capacity:
WSC/WCC evaporator (1 valve) and condenser (2 valves piped together to common vent pipe) = 200 psi, 75.5 lb of air/min
WDC evaporator (1) = 180 psi, 68.5 lb of air/min
WDC condenser(2) = 225 psi, 84.4 lb of air/min
Note: some large condensers have 4 relief valves
Since the pressures and valve size are fixed for Daikin chillers, the ASHRAE equation can be reduced to the simple tabl
e shown below.
Table 10: Relief Valve Piping Sizes
Pipe Size inch
(NPT)
Moody Factor
Equivalent length (ft)
Note: A 1-inch pipe is too small to handle these valves. A pipe
increaser must be installed at the valve outlet.
1.25 1.5 2 2.5 3 4
0.0209 0.0202 0.0190 0.0182 0.0173 0.0163
2.2 18.5 105.8 296.7 973.6 4117.4
Per ASHRAE Standard 15, the pipe size cannot be less than the relief device. The discharge from more than one relief valve can be run into a common header, the area of which shall not be less than the sum of the areas of the connected pipes. For further details, refer to ASHRAE Standard 15.
The above information is a guide only. Consult local codes and/or latest version of ASHRAE Standard 15 for sizing data.
Relief valve pipe sizing is based on the discharge capacity for the given evaporator or condenser and the length of piping to be run.
Cat 605-5 21
Application Considerations
MODEL CODE EXAM PLE: W S C - 063M - AQ - 18S / E2012- E - 2 * A / C1812- B L Y Y - 2 * A Y Y Y R / 134B
Packaged Water Cooled Centrifugal Chiller
S = Single Compressor D = D ual Compressor C = Dual Counterflow
Hermet ic Co mpressor Model
Compressor/Impeller Code
Gear Ratio
Motor/Voltage Code
Evaporator Shell Description [Diameter (in.), Length (ft.)]
Tube Count Code
Tube Type Code
Number of Passes (1, 2, 3)
Water Inlet Location (R = Right Inlet; L = Left Inlet)
Connection Type
Condenser Shell Description [Diameter (in.), Length (ft.)]
Tube Count Code
Type Type Code
Tube Count Code (Heat Recovery Condenser)
Tube Type Code (Heat Recovery Conderser)
Number of Passes (1, 2, 3)
Water Inlet Location (R = Right Inlet; L = Left Inlet)
Connection Type
Number of Passes (Heat Recovery Condenser)
Water Inlet Location (Heat Recovery Condenser)
Connection Type (Heat Recovery Condenser)
Motor Manufacturer
Refrigeration Type (134 = HFC-134a)
COMPRESSOREVAPORATOR
CONDENSER
R
Figure 18: Chiller Identification (Code String Index)
22 Cat 605-5
Electrical Data
Wiring and Conduit
Wire sizes must comply with local and state electrical codes. Where total amperes require larger conductors than a single conduit would permit, limited by dimensions of motor terminal box, two or more conduits can be used. Where multiple conduits are used, all three phases must be balanced in each conduit. Failure to balance each conduit will result in excessive heating of the conductors and unbalanced voltage.
An interposing relay can be required on remote mounted starter applications when the length of the conductors run between the chiller and starter is excessive.
Note: On WDC and WCC dual compressor units, dual power leads are standard, requiring separate power leads properly sized and protected to each compressor starter or VFD. Separate disconnects must be used.
Use only copper supply wires with ampacity based on 75°C conductor rating. (Exception: for equipment rated over 2000 volts, 90°C or 105°C rated conductors shall be used).
Power Factor Correction Capacitors
Do not use power factor correction capacitors with centrifugal chillers with a compressor VFD. Doing so can cause harmful electrical resonance in the system. Correction capacitors are not necessary since VFDs inherently maintain high power factors.
Control Power
The 115-volt control power can be supplied from the starter or a transformer (meeting the
requirements of Daikin Starter
Electrical Data
Specification 359999 Rev 29) separate from the starter. Either source must be properly fused with 25-amp dual element fuses or with a circuit breaker selected for motor duty. If the control transformer or other power source for the control panel is remote from the unit, conductors must be sized for a maximum voltage drop of 3%. Required circuit ampacity is 25 amps at 115 volts. Conductor size for long runs between the control panel and power source, based upon National Electrical Code limitations for 3% voltage drop, can be determined from the table below.
Control Power Line Sizing
Maximum Length, ft (m)
0 (0) to 50 (15.2) 12 120 (36.6) to 200 (61.0) 6
50 (15.2) to 75 (22.9) 10 200 (61.0) to 275 (83.8) 4
75 (22.9) to 120 (36.6) 8 275 (83.8) to 350 (106.7) 3
Wire Size
(AWG)
Maximum Length, ft (m)
Notes:
1 Maximum length is the distance a conductor will traverse
between the control power source and the unit control panel.
2 Panel terminal connectors will accommodate up to
number 10 AWG wire. Larger conductors will require an intermediate junction box.
Starters and VFDs
Information on starters and VFDs can be found in Daikin Catalog CAT 608.
Wire Size
(AWG)
Cat 605-5 23
Electrical Data
NOTES for Following Wiring Diagram
1 Compressor motor starters are either factory mounted
and wired, or shipped separate for field mounting and wiring. If provided
by others, starters must comply with Daikin specification 359999 Rev 29. All line and load side power conductors must be copper.
2 If starters are freestanding, then field wiring between the
starter and the control panel is required. Minimum wire size for 115
Vac is 12 GA for a maximum length of 50 feet. If greater than 50 feet, refer to Daikin sales office for recommended wire size minimum. Wire size for 24 Vac is 18 GA. All wiring to be installed as NEC Class 1 wiring system. All 24 Vac wiring must be run in separate conduit from 115 Vac wiring. Main power wiring between starter and motor terminal is factory­installed when units are supplied with unit-mounted starters. Wiring of free-standing starter must be wired in accordance with NEC and connection to compressor motor terminals must be made with copper wire and copper lugs only. Control wiring on free-standing starters is terminated on a terminal strip in the motor terminal box (not the unit control panel). Wiring from the unit control panel to the motor terminal is done in the factory.
3 For optional sensor wiring, see unit control diagram. It is
recommended that dc wires be run separately from 115 Vac wiring.
4 Customer furnished 24 or 120 Vac power for alarm relay
coil can be connected between UTB1 terminals 84 power and 51 neutral of the control panel. For normally open contacts, wire between 82 & 81. For normally closed contacts, wire between 83 & 81. The alarm is operator programmable. The maximum rating of the alarm relay coil is 25 VA.
5 Remote on/off control of unit can be accomplished by
installing a set of dry contacts between terminals 70 and
54.
6 Evaporator and condenser flow switches are required and
must be wired as shown. If field supplied pressure differential switches are used then these must be installed across the vessel and not the pump.
7 Customer supplied 115 Vac, 20 amp power for optional
evaporator and condenser water pump control power and tower fans is supplied to unit control terminals (UTBI) 85 power / 86 neutral, PE equipment ground.
8 Optional customer supplied 115 Vac, 25 VA maximum
coil rated chilled water pump relay (EP 1 & 2) can be wired as shown. This option will cycle the chilled water pump in response to building load.
9 The condenser water pump must cycle with the unit. A
customer supplied 115 Vac 25 VA maximum coil rated
condenser water pump relay (CP1 & 2) is to be wired as shown.
10 Optional customer supplied 115 Vac, 25 VA maximum
coil rated cooling tower fan relays (CL - C4) can be wired as shown. This option will cycle the cooling tower fans in order to maintain unit head pressure.
11 Auxiliary 24 Vac rated contacts in both the chilled water
and condenser water pump starters can be wired as shown for additional protection.
12 For VFD, Wye-Delta, and solid state starters connected
to six (6) terminal motors, the conductors between the starter and motor carry phase current and their ampacity must be based on 58 percent of the motor rated load amperes (RLA) times 1.25. Wiring of free-standing starter must be in accordance with the NEC and connection to the compressor motor terminals shall be made with copper wire and copper lugs only. Main power wiring between the starter and motor terminals is factory-installed when chillers are supplied with unit­mounted starters.
13 Optional Open Choices BAS interfaces. The locations
and interconnection requirements for the various standard protocols are found in their respective installation manuals, obtainable from the local Daikin sales office and also shipped with each unit: Modbus IM 743-0LonWorks IM 735-0BACnet IM 736-0.
14 The "Full Metering" or "Amps Only Metering" option
will require some field wiring when free-standing starters are used. Wiring will depend on chiller and starter type. Consult the local Daikin sales office for information on specific selections.
24 Cat 605-5
Figure 19: Typical Field Connection Diagram
SCHEM. 330387903 REV.0E
A
H
C
CP1
CWI-1
A
H
C
CP2
CWI-2
A
H
C
EP1
EWI-1
A
H
C
EP2
EWI-2
NOTE 11
NOTE 11
NOTE 11
NOTE 11
*NOTE 8
*NOTE 8
*NOTE 9
*NOTE 9
(NOTE 6)
COND.
DELTA P.
OR FLOW
SWITCH
*CONDENSER
WATER
PUMP
STARTERS
*CHILLED
WATER
PUMP
STARTERS
(NOTE 6)
EVAP.
DELTA P.
OR FLOW
SWITCH
* REMOTE
ON/OFF
(NOTE 5)
74
55
80
70
86
85
PE
MODE SWITCH
*
54
86
85
73
78
70
EF1
EF1
77
76
75
70
CF1
CF1
81
82(NO)
83(NC)
84
79
A
H
C4
*NOTE 10
527171
53
A
H
C3
*NOTE 10
A
H
C2
*NOTE 10
A
H
C1
*NOTE 10
MJ NOTE 11
MJ NOTE 11
POWER
* NOTE 4
* ALARM RELAY
(NOTE 4)
* COOLING TOWER BYPASS VALUE
* COOLING TOWER VFD
* COOLING
TOWER
FIRST
STAGE
STARTER
NEUTRAL
* NOTE 7
POWER
GND
MICROTECH CONTROL
BOX TERMINALS
UTB1
(115V)
(24V)
0-10-VDC
0-10-VDC
COMMON
* COOLING
TOWER
SECOND
STAGE
STARTER
* COOLING
TOWER
THIRD
STAGE
STARTER
* COOLING
TOWER
FOURTH
STAGE
STARTER
.
L1
L2
L3
CP1
CP2
23(5A)
24(5)
25
1
2
346
11
12
22
GND
VM
W
T1
-COMPRESSOR TERMINALS -
-STARTER LOAD SIDE TERMINALS -
VFD
T6 T2 T4 T3 T5
T1 T2 T3 T4 T5 T6
T1 T2 T3
T4 T5 T6
-COMPRESSOR TERMINALS -
-STARTER LOAD SIDE TERMINALS-
WYE - DE LTA
T2T1
T3
T1
-COMPRESSOR TERMINALS-
-STARTER LOAD SI DE TERMINALS-
SOLID STATE
T6 T2 T4 T3 T5
T1
T3
T1
T2
T3
-STARTER LOAD SIDE TERMINALS-
MEDIUM AND HIGH VOLT AGE
T2
-COMPRESSOR TERMINALS -
NOTE 12
A
1
234
111112
22
MICROTECH
COMPRESSOR
CONTROL
BOX TERMINALS
CTB1
115VAC
PE
L1L2232425
LESS
THAN
30V
OR
24VAC
NOTE 2
NOTE 2
2L1
2L2
2L3
2L1
2L2
2L3
WTC ONLY
MICROTECH
COMPRESSOR
CONTROL
BOX TERMINALS
CTB3
* FIELD SUPPLIED ITEM
NOTE 2
COMPRESSOR
MOTOR
STARTER
(NOTE 1)
UNIT
COMP.
EXPANSION
LEGEND
3303421XX
3303422XX
3303430XX
WCS/WDC
3325787XX
3325788XX
3326512XX
3325789XX
WTC
-LINE-
FOR DC VOLTAGE AND 4-20 MA
CONNECTIONS (SEE NOTE 3)
FOR DETAILS OF CONTROL REFER
TO CONTROL SCHEMATIC
SCHEM. 330387903 REV.0E
CENTRIFUGAL UNI TS
FIELD CONNECTION DIAGRAM
NOTES:
1.
A
H
C
CP1
CWI-1
A
H
C
CP2
CWI-2
A
H
C
EP1
EWI-1
A
H
C
EP2
EWI-2
NOTE 11
NOTE 11
NOTE 11
NOTE 11
*NOTE 8
*NOTE 8
*NOTE 9
*NOTE 9
(NOTE 6)
COND.
DELTA P.
OR FLOW
SWITCH
*CONDENSER
WATER
PUMP
STARTERS
*CHILLED
WATER
PUMP
STARTERS
(NOTE 6)
EVAP.
DELTA P.
OR FLOW
SWITCH
* REMOTE
ON/OFF
(NOTE 5)
74
55
80
70
86
85
PE
MODE SWITCH
*
54
86
85
73
78
70
EF1
EF1
77
76
75
70
CF1
CF1
81
82(NO)
83(NC)
84
79
A
H
C4
*NOTE 10
527171
53
A
H
C3
*NOTE 10
A
H
C2
*NOTE 10
A
H
C1
*NOTE 10
MJ NOTE 11
MJ NOTE 11
POWER
* NOTE 4
* ALARM RELAY
(NOTE 4)
* COOLING TOWER BYPASS VALUE
* COOLING TOWER VFD
* COOLING
TOWER
FIRST
STAGE
STARTER
NEUTRAL
* NOTE 7
POWER
GND
MICROTECH CONTROL
BOX TERMINALS
UTB1
(115V)
(24V)
0-10-VDC
0-10-VDC
COMMON
* COOLING
TOWER
SECOND
STAGE
STARTER
* COOLING
TOWER
THIRD
STAGE
STARTER
* COOLING
TOWER
FOURTH
STAGE
STARTER
.
L1
L2
L3
CP1
CP2
23(5A)
24(5)
25
1
2
346
11
12
22
GND
VM
W
T1
-COMPRESSOR TERMINALS -
-STARTER LOAD SIDE TERMINALS -
VFD
T6 T2 T4 T3 T5
T1 T2 T3 T4 T5 T6
T1 T2 T3
T4 T5 T6
-COMPRESSOR TERMINALS -
-STARTER LOAD SIDE TERMINALS-
WYE - DE LTA
T2T1
T3
T1
-COMPRESSOR TERMINALS-
-STARTER LOAD SI DE TERMINALS-
SOLID STATE
T6 T2 T4 T3 T5
T1
T3
T1
T2
T3
-STARTER LOAD SIDE TERMINALS-
MEDIUM AND HIGH VOLT AGE
T2
-COMPRESSOR TERMINALS -
NOTE 12
A
1
234
111112
22
MICROTECH
COMPRESSOR
CONTROL
BOX TERMINALS
CTB1
115VAC
PE
L1L2232425
LESS
THAN
30V
OR
24VAC
NOTE 2
NOTE 2
2L1
2L2
2L3
2L1
2L2
2L3
WTC ONLY
MICROTECH
COMPRESSOR
CONTROL
BOX TERMINALS
CTB3
* FIELD SUPPLIED ITEM
NOTE 2
COMPRESSOR
MOTOR
STARTER
(NOTE 1)
UNIT
COMP.
EXPANSION
LEGEND
3303421XX
3303422XX
3303430XX
WCS/WDC
3325787XX
3325788XX
3326512XX
3325789XX
WTC
-LINE-
FOR DC VOLTAGE AND 4-20 MA
CONNECTIONS (SEE NOTE 3)
FOR DETAILS OF CONTROL REFER
TO CONTROL SCHEMATIC
Electrical Data
S SUPPLIED TO UNIT CONTROL TERMINALS (UTB1) 85 POWER / 86 NEUTRAL , PE EQUIPMENT GROUND.
IS SUPPLIED TO UNI T CONTROL TERMINALS (UTB1) 85 POWER / 86 NEUTRAL, PE EQUIPMENT GROUND.
I
CONDENSER WATER PUMP RELAY (CP1 & 2 ) IS TO BE WIRED AS SHOWN. UNITS WITH F REE COOLING MUST HAVE CONDENSER
SHOWN. THIS OPTIONAL WILL CYCLE THE CHILLED WATER PUMP IN RESPONSE TO CHILLER DEMAND.
CONDENSER WATER PUMP RELAY (CP1 & 2 ) IS TO BE WIRED AS SHOWN. UNITS WITH F REE COOLING MUST HAVE CONDENSER
WATER ABOVE 60° BEFORE STARTING.
SHOWN. THIS OPTIONAL WILL CYCLE THE CHILLED WATER PUMP IN RESPONSE TO CHILLER DEMAND.
8. OPTIONAL CUST OMER SUPPLIED 115 VAC 25 VA MAXIMUM COIL RATED CHILLED WATER PUMP RELAY (EP1 & 2) M AY BE WIRED AS
8. OPTIONAL CUST OMER SUPPLIED 115 VAC 25 VA MAXIMUM COIL RATED CHILLED WATER PUMP RELAY (EP1 & 2) M AY BE WI RED AS
WATER ABOVE 60° BEFORE STARTING.
9. THE CONDENSER WATER PUMP MUST CYCL E WITH THE UNIT. A CUSTOMER SUPPLIED 1 15 VAC 25 VA MAXIMUM COIL RATED
9. THE CONDENSER WATER PUMP MUST CYCL E WITH THE UNIT. A CUSTOMER SUPPLIED 1 15 VAC 25 VA MAXIMUM COIL RATED
and and 200 VA200 VACC 115115IIFF ST STARARTTEERS ARRS ARE FE FRREE STEE STANDIANDI NGNG,, TTHHEN FEN FIIELELD WD WII RIRINGNG BETBETWWEENEEN T THHE STE STARARTTEER AND R AND TTHHE CONTE CONTROLROL PANE PANE LL I ISS REQU REQUII RREEDD.. MIMINNIIMUM WMUM WIIRREE SI SI ZZ EE F FOORR V VAAC C
EE STANDING
7. CUSTOMER SUPPLIED 115 VAC 20 AMP POWER FOR OPTIONAL EVAP AND COND WATER PUMP CONTROL POWER AND TOWER FANS
7. CUSTOMER SUPPLIED 115 VAC 20 AMP POWER FOR OPTIONAL EVAP AND COND WATER PUMP CONTROL POWER AND TOWER FANS
CONNECTED TO SIX (6) TERMINAL MOTORS. THE CONDUCTORS BETWEEN THE
CONNECTED TO SIX (6) TERMINAL MOTORS. THE CONDUCTORS BETWEEN THE
UNIT HEAD PRESSURE.
C3 – C4 OPTIONAL) MAY BE WI RED AS SHOWN. THIS OPTION WILL CYCLE T HE COOLING TOWER FANS IN ORDER TO MAINTAI N
C3 – C4 OPTIONAL) MAY BE WI RED AS SHOWN. THIS OPTION WILL CYCLE T HE COOLING TOWER FANS IN ORDER TO MAINTAI N
UNIT HEAD PRESSURE.
11. AUXILI ARY 24 VAC RATED CONTACTS IN BOTH THE CHILL ED WATER AND CONDENSER WATER PUMP STARTERS SHOULD BE
11. AUXILI ARY 24 VAC RATED CONTACTS IN BOTH THE CHILL ED WATER AND CONDENSER WATER PUMP STARTERS SHOULD BE
10. OPTIONAL CUSTOMER SUPPLIED 115 VAC 25 VA MAXIMUM COI L RATED COOLING TOWER FAN RELAYS (C1 – C2 ST ANDARD,
10. OPTIONAL CUSTOMER SUPPLIED 115 VAC 25 VA MAXIMUM COI L RATED COOLING TOWER FAN RELAYS (C1 – C2 ST ANDARD,
NALS MUST BE MADE WITH COPPER WIRE AND COPPER L UGS ONLY.
NALS MUST BE MADE WITH COPPER WIRE AND COPPER L UGS ONLY.
THE STARTER AND MOTOR TERMI NALS IS FACTORY INSTALLED WHEN CHILL ERS ARE SUPPLIED WITH UNIT MOUNTED STARTERS.
COMPRESSOR MOTOR TERMINALS SHAL L BE MADE WITH COPPER WIRE AND COPPER LUGS ONLY. MAIN POWER WI RING BETWEEN
WIRED AS SHOWN AND REMOVE MJ.
AMPERES (RLA). WI RING OF FREE STANDING STARTER MUST BE I N ACCORDANCE WITH THE NEC AND CONNECTION TO THE
WIRED AS SHOWN AND REMOVE MJ.
THE STARTER AND MOTOR TERMI NALS IS FACTORY INSTALLED WHEN CHILL ERS ARE SUPPLIED WITH UNIT MOUNTED STARTERS.
STARTER AND MOTOR CARRY PHASE. CURRENT AND SELECTION SHALL BE BASED ON 58 PERCENT OF THE MOT OR RATED LOAD
COMPRESSOR MOTOR TERMINALS SHAL L BE MADE WITH COPPER WIRE AND COPPER LUGS ONLY. MAIN POWER WI RING BETWEEN
STARTER AND MOTOR CARRY PHASE. CURRENT AND SELECTION SHALL BE BASED ON 58 PERCENT OF THE MOT OR RATED LOAD
AMPERES (RLA). WI RING OF FREE STANDING STARTER MUST BE I N ACCORDANCE WITH THE NEC AND CONNECTION TO THE
12. FOR VFD, WYE- DELTA, AND SOLID STATE STARTERS
12. FOR VFD, WYE- DELTA, AND SOLID STATE STARTERS
CENTRIFUGAL UNI TS
FIELD CONNECTION DIAGRAM
RIINNG MUSTG MUST BE RUN I BE RUN INN SEPARAT SEPARATE CONE CONDDUUIITT F FRROM OM 111155 VAC A VAC AND ND
R
I
I
COMPRCOMPRESSOR MESSOR MOOTTOOR STR STAARRTTEERS ARRS ARE EIE EITTHHERER F FAACTCTORYORY MOU MOUNNTTEED AND WD AND WIIRREED OR SHD OR SHIIPPED SEPPED SEPARATPARATEE F FOOR FR FIIELELD D MOUNTMOUNTIINNGG AND W AND WIIRRIINGNG.. IIFF PR PROVIOVIDDEED BD BYY OT OTHERSHERS
NOTES:
VAC W
VAC W 0
0 2
2 L
L AL
AL .
. EM
EM ST
ST
NG SY
NG SY
I
I R
R
I
I W
W 1
1
ASS
ASS
NEC CL
NEC CL S
S
D A
D A E
E L
L AL
AL ST
ST N
N
BE I
BE I O
O T
T NG
NG RI
RI
I
I
CONDUCONDUCCTTOOR RATR RATIINGNG.. ( (EEXCXCEPTEPTII ONON:: FFOOR EQUIR EQUIPPMMENTENT RA RATTEED OVERD OVER 2 200 0000 VOLVOLTTSS,, 9900°°CC O ORR 11 0055°°C RC RAATTEED COND CONDUCTDUCTOORSRS SHALSHALLL BE BE USED USED..
STSTARTARTEERS MUSTRS MUST COMPL COMPLYY WWIITTHH MCQ MCQUAY SPECUAY SPECIIFFII CATCATIIONON 335599AA999999.. ALALLL L LIINE NE AND LAND L OOADAD SI SIDE POWER CONDDE POWER COND UCTUCTOORS MRS MUUSTST BE C BE COPPEROPPER,, WIWITTHH AMPA AMPACICITYTY B BAASESEDD O ONN 75° 75°CC
W
W
IISS 1122 G GAA.. FFOOR A R A MAXI MAXIMUMMUM L LEENGTNGTHH OFOF 5500 F FEEETET.. IIFF G GRREAEATTEER TR THHANAN 5 500 FFEEETET R R EEFFEER TR TOO MCQUAY MCQUAY FFOOR RECOR RECOMMENDMMENDEEDD
WIRING BETWEEN STARTER AND MOT OR TERMINAL IS FACTORY INSTALLED WHEN UNI TS ARE SUPPLIED WITH UNIT MOUNTED STARTERS. WIRING OF FREE STANDING
WIRING BETWEEN STARTER AND MOTOR T ERMINAL IS FACTORY INSTALLED WHEN UNI TS ARE SUPPLIED WITH UNIT MOUNTED STARTERS. WIRING OF FR
STARTER MUST BE WIRED I N ACCORDANCE WITH NEC AND CONNECTION TO COMPRESSOR MOTOR T ERMI
STARTER MUST BE WIRED I N ACCORDANCE WITH NEC AND CONNECTION TO COMPRESSOR MOTOR TERMI
2.
2.
1.
Cat 605-5 25
ALARM RELAY COIL MAY BE CONNECTED BET WEEN UTB1 TERMINALS 84 POWER AND 81 NEUTRAL OF THE CONTROL
ALARM RELAY COIL MAY BE CONNECTED BET WEEN UTB1 TERMINALS 84 POWER AND 81 NEUTRAL OF THE CONTROL
TC UNITS AND OPTI ONAL ON WSC & WDC . PADDLE SWITCHES MAY ALSO BE FIELD INSTAL LED IF DESIRED.
RATING OF THE ALARM REL AY COIL IS 25VA.
PANEL. FOR NORMALLY OPEN CONTACT S WIRE BETWEEN 82 & 81. FOR NORMALLY CLOSED WIRE BETWEEN 83 & 81. THE ALARM IS OPERATOR PROGRAMMABLE. MAXIMUM
RATING OF THE ALARM REL AY COIL IS 25VA.
PANEL. FOR NORMALLY OPEN CONTACT S WIRE BETWEEN 82 & 81. FOR NORMALLY CLOSED WIRE BET WEEN 83 & 81. THE ALARM IS OPERATOR PROGRAMMABLE. MAXIMUM
DIFFERENTIAL SWITCHES ARE USED THEN THESE MUST BE INSTALLED ACROSS THE VESSEL AND NOT THE PUMP . FACTORY MOUNTED FLOW SWITCHES ARE STANDARD
ON WTC UNITS AND OPTIO NAL ON WSC & WDC. PADDLE SWITCHES MAY ALSO BE FIELD INSTALL ED IF DESIRED.
DIFFERENTIAL SWITCHES ARE USED THEN THESE MUST BE INSTALLED ACROSS THE V ESSEL AND NOT THE PUMP. FACTORY MOUNTED FLOW SWI TCHES ARE STANDARD
4. A CUSTOMER FURNISHED 24 OR 120 VAC POWER FOR
3. FOR OPTIONAL S ENSOR WIRING SEE UNIT CONTROL DIAGRAM. I T IS RECOMMENDED THAT DC WIRES BE RUN SEPARATELY FROM 155 V AC AND 200 VAC WIRING.
4. A CUSTOMER FURNISHED 24 OR 120 VAC POWER FOR
3. FOR OPTIONAL S ENSOR WIRING SEE UNIT CONTROL DIAGRAM. I T IS RECOMMENDED THAT DC WIRES BE RUN SEPARATELY FROM 155 VAC AND 200 VAC WIRING.
ON W
6. EVAPORATOR AND CONDENSER FLOW SWI TCHES ARE REQUIRED. FIELD I NSTALLED FLOW SWITCHES MUST BE WIRED AS SHOWN. I F FIELD SUPPLIED PRESSURE
6. EVAPORATOR AND CONDENSER FLOW SWI TCHES ARE REQUIRED. FIELD I NSTALLED FLOW SWITCHES MUST BE WIRED AS SHOWN. IF FIELD SUPPLIED PRESSURE
5. REMOTE ON/OFF CONTROL OF UNIT CAN BE ACCOMPLISHED BY INSTALL ING A SET OF DRY CONTACTS BETWEEN TERMINALS 70 AND 54 .
5. REMOTE ON/OFF CONTROL OF UNIT CAN BE ACCOMPLISHED BY INSTALL ING A SET OF DRY CONTACTS BETWEEN TERMINALS 70 AND 54 .
Starters and VFDs
0.337
0.365
0.403
0.505
0 0.1 0.2 0.3 0.4 0.5 0.6
WDC w/ VFD
WSC w/ VFD
WDC
WSC
Model
IPLV
Starters and VFDs
Motor Starters
Daikin has a wide variety of starter types and options to fit virtually all applications. The specifics of the final selection of size, enclosure, and options are covered in the catalog Cat Starter available on www.DaikinApplied.com . Please consult the local Daikin sales office or the starter catalog for details. This section contains a general overview only.
Mounting Options, Low Voltage, 200 to 600 Volts
Factory-mounted
Starters are furnished, mounted and wired in the factory. Due to shipping width limitations, the starters for WSC 100 through 126 are shipped loose with cable kits and mounting brackets for field installation on the unit by others.
Freestanding
Furnished by Daikin and shipped to the job site for setting and wiring by others.
Starters by others
Starters furnished by others must meet Daikin Specification 359999 Rev 29, available from the local Daikin sales
office. The starters are furnished and installed by others.
Table 11: Low Voltage Starter Mounting Options
Size
WSC/WDC 063-087 X X
WSC/WCC 100-126 X X
WDC 100-126 X
WCC 100-126 X X
Factory­Mounted
X
Free-
Standing
Brackets & Cables
The traditional method of controlling centrifugal compressor capacity is by inlet guide vanes. Capacity can also be reduced by slowing the compressor speed and reducing the impeller tip speed, providing sufficient tip speed is retained to meet the discharge pressure requirements. This method is more efficient than guide vanes by themselves.
In actual practice a combination of the two techniques is used. The microprocessor slows the compressor (to a fixed minimum percent of full load speed) as much as possible, considering the need for tip speed to make the required compressor lift. Guide vanes take over to make up the difference in required capacity reduction. This methodology provides the optimum efficiency under any operating condition.
Impact of Variable Frequency Drives
The chart below illustrates the relative IPLV efficiencies of various Daikin options for a typical 500-ton selection. The chiller cost increases as the efficiency improves.
Figure 20: IPLV Comparison by Model
Mounting Options, Medium Voltage, 2300 to 6000 Volts
All starter types in these voltages are for field setting and wiring only.
Starter Types and Descriptions
Solid state starters are available for both low and medium voltages and are similar in construction and features regardless of voltage. For low voltage application, Wye-Delta Closed Transition starters are available, in addition to solid state. For medium voltage application, autotransformer, primary reactor reduced voltage and across-the-line starters are offered in addition to solid state.
Variable Frequency Drives (VFD)
A VFD modulates the compressor speed in response to load and evaporator and condenser pressures. Due to the outstanding part load efficiency, and despite the small power penalty attributed to the VFD, the chiller can achieve outstanding overall efficiency. VFDs really prove their worth when there is reduced load combined with low compressor lift (lower condenser water temperatures) dominating the operating hours.
The IPLV values (defined on page 29) are AHRI Certified Ratings based on AHRI Standard 550/590, Standard for Water Chilling Packages Using the Vapor Compression Cycle. Full load is at 44 F chilled water temperature with 2.4 gpm/ton, 85 F entering condenser water temperatures with 3 gpm/ton. Part load points of 75%, 50%, and 25% employ condenser water temperature relief (reduction) per the standard.
26 Cat 605-5
General Arrangement
Starters and VFDs
VFD Mounting
VFDs can be factory-mounted on the same units and in the same location as conventional starters or can be free-standing as shown below. Dimensions begin on page 30.
Table 12: VFD Mounting Options
Chiller Model
WSC/WDC 063-087 X X
WSC 100-126
WDC 100-126 X
WCC 100-126
1: VFD sizes 15 to 81 (380V-480V) and 30-65 (575V) may be either unit
mounted or free-standing. Larger sizes are free-standing only. 2: Unit mounted in the field option includes interconnecting brackets and cables shipped with unit.
Unit Mounted
at Factory
X
X X
X
Unit Mounted
in Field
X
X
X
Free-
Standing
X
x
VFDs and Distortion
Despite the many benefits, applying
VFDs
due
to
care must be taken when
the
impact
th
ey may have on the
that building’s electrical system. VFDs can cause distortion of the AC line because they are nonlinear loads; that is, they don't draw sinusoidal current from the line. They instead only draw current during the peaks of the AC line. This flattens the top of the voltage waveform. Most other modern electronic equipment is also a nonlinear load, but VFDs tend to have a greater impact because of their large power demand. Although harmonics are associated with non-linear loads, it is extremely rare that VFD generated harmonics are an issue in systems with a minimum of 5% internal impedance. Power line harmonic distortion can be a concern for a number of reasons:
Current harmonics can cause additional heating of
1
transformers, conductors, and switchgear. They can
.
also cause nuisance tripping of circuit breakers and clearing of fuses.
2
Voltage harmonics may disrupt the operation of
.
devices which require a smooth, sinusoidal voltage waveform.
3
High-frequency components of voltage distortion can
.
interfere with signals which are transmitted on the AC power line.
The harmonics of concern are often the 5th, 7th, 11th, and 13th. Even harmonics, harmonics divisible by three, and harmonics above the 13th harmonic are usually not a problem for three-phase power systems.
The Daikin Drive Passive filter Package provides a broader range of harmonic reduction performance than VFDs which use active rectifiers. This is particularly true at reduced loads, where VFDs provide the greatest energy savings.
Current Harmonics
An increase in reactive impedance in front of the VFD helps reduce the harmonic currents. Reactive impedance can be added in the following ways:
1 Mount the drive far from the source transformer.
2 Add line reactors.
3 Use an isolation transformer.
Voltage Harmonics
Voltage distortion is caused by the flow of harmonic currents through a source impedance. A reduction in source impedance to the point of common coupling (PCC) will result in a reduction in voltage harmonics. This may be done in the following ways:
1 Keep the PCC as far from the drives (close to the power
source) as possible.
2 Increase the size (decrease the impedance) of the source
transformer.
3 Increase the capacity (decrease the impedance) of the
busway or cables from the source to the PCC.
4 Make sure that added reactance is downstream (closer to
the VFD than the source) from the PCC.
The IEEE 519 Standard
The Institute of Electrical and Electronics Engineers (IEEE) has developed a standard that recommends distortion limits for both power utilities and their customers. The purpose of these limits is to ensure that the voltage distortion of the utility’s public power grid is maintained at an acceptable level. To accomplish this, IEEE 519 presents recommended harmonic current distortion limits for utility customers. These limits are based on the peak demand of the customer. This is called the Total Demand Distortion (TDD). This standard provides a sliding scale for the recommended TDD limit for each utility customer. The greater the demand that a customer places on the utility, the more stringent the recommended TDD limits. IEEE 519-2014 clearly states that the TDD is to be measured at the point where a utility customer connects to the public utility. It does not apply to any points inside the customer’s facility; it only applies to the point where another utility customer could connect to the public power grid. If the utility’s customers comply with the TDD limits stated in IEEE 519-2014, it is then the utility’s responsibility to provide voltage to its customers that meets the harmonic voltage recommendations of this standard.
Cat 605-5
27
Selection Procedures
Selection Procedures
Many combinations of compressor configuration and condensers and evaporators are available for a given capacity. The units range from low first cost and relatively high kW per ton (COP) to high first cost and low kW per ton (COP). An example illustration of the performance vs. cost display is shown below. Optimum unit selection for maximum operating return on the invested first cost is in the area identified by the red “X”.
Actual optimum unit selection will vary with building application and system hours of operation cannot justify a very low kW per ton (COP) unit. Applications with high hours of operation will justify high part load as well as full load efficiency units. For optimum selection an energy analysis is available through your local Daikin Sales Representative.
design. Applications with minimal
and performance tolerances of all units that fall within the scope of the program. All chillers that fall within the scope of AHRI Standard 550/590 will have an AHRI certification label at no cost to the owner. Equipment covered includes all water­cooled chilling packages rated up to 2500 tons (8793 kW), operating within the range shown in Table 13, with either an hermetic or open drive, with electric driven motor not exceeding 5000 volts, and cooling water (glycol applications are outside the scope AHRI Standard 550/590). he program excludes the following applications: air and evaporative cooled chillers, capacity exceeding 2500 tons (8793 kW), voltages above 5000 volts, brine and special fluids other than water and
heat recovery units.
Table 13: Application Condition Range of AHRI 550/590
Leaving chilled water temperature:
Entering condenser water temperature:
40°F to 48°F (4.4°C
to 8.9°C)
60°F to 95°F
(15.6°C to 35°C)
Published certified ratings at AHRI standard rating conditions (shown in include the following values :
• Capacity, tons (kW)
• Power, kW/ton (COP)
• Pressure drop, ft. of water (kPa)
• Integrated Part Load Value (IPLV) or Non-Standard Part Load Value (NPLV)
The standard rating conditions are:
Table 14: AHRI Standard Rating conditions
Basic unit selections
All Daikin centrifugal chillers are computer selected to optimize the cooling output and total kW. Computer selection allows for the specification
of leaving chilled water temperature, entering condenser water temperature, evaporator and condenser flow rates, number of passes, and fouling factors. Glycol applications can also be specified.
Glycol operation
The addition of glycol to the chilled water system for freeze protection can be required for special applications. Glycol solutions are required where the evaporating temperatures are below 33°F (1°C).
AHRI Certification
Daikin is committed to supplying chillers that perform as specified. Subsequently ,
Daikin centrifugal chillers are part of the AHRI Certification program. On-going performance verification of chiller capacity and power input plus AHRI certified computerized selection output provide the owner with the assurance of specified performance.
Scope of Certification Program
AHRI Standard 550/590 for Centrifugal or Screw Water­Chilling Packages defines certification and testing procedures
Leaving chilled water temperature:
Evaporator waterside field fouling allowance:
Chilled water flow rate:
Entering condenser water temperature:
Condenser waterside field fouling allowance:
Condenser water flow rate:
44°F (6.7°C)
0.0001 ft
(0.0176 m
2.4 gpm/ton (0.043 l/s / kW) 85°F (29.4°C)
0.00025 ft
(0.044 m
3.0 gpm/ton (0.054 l/s / kW)
2
x hr x°F/BTU
2
x °C/kW)
2
x hr x°F/BTU
2
x °C/kW)
Daikin SelectTools (MST) for Centrifugal Chillers is the selection program used to custom select and rate chillers for specific job conditions. It is part of the AHRI certification program, and the certified program version number and issue date is listed in the AHRI Directory of Certified Applied Air­Conditioning Products available at www.ahridirectory.org. MST ratings are available from your local Daikin Sales Representative.
Full AHRI 550/590 participation and certification has been an on-going commitment at Daikin. The AHRI
label affixed to certified units certifies that the unit will meet the specified performance. This equipment is certified in accordance with AHRI Standard 550/590, latest edition,
28 Cat 605-5
provided the application ratings are within the scope of the
IPLV/NPLV Defined
Part load performance can be presented in terms of Integrated Part Load Value (IPLV), which is based on AHRI standard rating conditions (listed above), or Non­Standard Part Load Values (NPLV), which is based on specified or job site conditions. IPLV and NPLV are based on the following weighting equation from AHRI 550/590:
Using kW/ton, where:
A = kW/ton (or COP) at 100% B = kW/ton (or COP) at 75% C = kW/ton (or COP) at 50% D = kW/ton (or COP) at 25%
Weighting
The percent of annual hours of operation at the four load points are as follows:
100% Load at 1% of operating time 75% Load at 42% of operating time 50% Load at 45% of operating time 25% Load at 12% of operating time
Tolerances
The AHRI test tolerance, per AHRI Standard 550/590-98, for capacity (tons), power input per ton (kW/ton), and heat balance is:
Where:
FL = Full Load
DTFL = Chilled Water Delta-T at Full Load This formula results in a 5% tolerance on tons and kW/
ton at the 100% load point and AHRI conditions.
DCBA
IPLVorNPLV
12.0
+
45.0
+
42.0
+
01.0
1
=
%.(.%)
%
Tolerance x FL
DTFLx FL

 
 
10 5 0 07
1500
certification program.
Figure 21: IPLV/NPLV Defined
Selection Procedures
Cat 605-5 29
Dimensions
Dimensions
Figure 22: WSC063 (160-300 tons/ 560 to 1050 kW) See Drawing Notes page 44
VESSEL CODE OVERALL LENGTH
EVAP COND
E2009 C1809
E2012 C1812
E2209 C2009
E2212 C2012
E2209 C2209
E2212 C2212
E2609 C2209
E2612 C2212
E2609 C2609
E2612 C2612
E3012 C2612
E3009 C2609
1&3-
PASS
AA A B C XY ZDEFG
134
(3404)
169
(4293)
134
(3404)
169
(4293)
134
(3404)
169
(4293)
134
(3404)
169
(4293)
134
(3404)
169
(4293)
175
(4445)
140
6)
(355
2-PASS
128
(3251)
163
(4140)
129
(3277)
164
(4166)
129
(3277)
164
(4166)
129
(3277)
164
(4166)
129
(3277)
164
(4166)
167
(4242)
132
(3353)
HEAD CONN.
BOTH ENDS
(3404)
(4293)
(3404)
(4
(3404)
(4293)
(3404)
(4
(3404)
(4293)
(4445)
(3556)
134
169
134
169
293)
134
169
134
169
293)
134
169
175
140
76
76
76
76
76
76
80
80
86
86
90
91
OVERALL
WIDTH W/O
STARTER
CENTER OF GRAVITY FOOTPRINT
68 (1727)
68 (1727)
68 (1727)
36
(914)17(432)
34
(864)17(432)
34
(864)17(432)
)25(635)
OVERALL
HEIGHT
(1930)42(1067)50(1270)37(940)16(406)
(1930)42(1067)
(1930)42(1067)50(1270)36(914)17(432)
(1930)42(1067)
(1930)42(1067)51(1295)35(889)17(432)
(1930)42(1067)
(2032)46(1168)51(1295)37(940)20(508)
(2032)46(1168)69(1753)35(889)20(508)
(2184)48(1219)51(1295)40(1016)20(508)
(2184)48(1219)69(1753)38(965)21(533)
(2286)53(1346)67(1702)41(1041)21(533)
(2235)52(1321)52(1321)41(1041
113
(2870)
148
(3759)
113
(2870)
148
(3759)
113
(2870)
148
(3759)
113
(2870)
148
(3759)
113
(2870)
148
(3759)
148
(3759)
113
(2870)
111
(2819)42(1067)34(864)
145
(3683)42(1067)34(864)
111
(2819)42(1067)34(864)
14
5
(3683)42(1067)34(864)
111
(2819)42(1067)34(864)
145
(3683)42(1067)34(864)
111
(2819)46(1168)38(965)
14
5
(3683)46(1168)38(965)
111
(2819)48(1219)40(1016)
145
(3683)48(1219)40(1016)
145
(3683)53(1646)45(1143)
111
(2819)56(1422)48(1219)
CONNECTIONS
EVAP
2-PASS
COND
2-PASS
66
66
86
86
88
88
88
88
88
88
10 8
10 8
30 Cat 605-5
Figure 23: WSC079/087 (300-600 tons/ 1050 to 2110 kW) See Drawing Notes page 44
Dimensions
VESSEL CODE “A” OVERALL LENGTH
EVAP COND
5
E2209
C2209
5
E2212
C2212
E2609 C2209
E2612 C2212
E2609 C2609
2612 C2612
E
E3009 C2609
E3009 C3009
E3012 C2612
E
C3012
3012
E3609 C3009
E3612 C3012
6
C3612
E3612
1&3
PASS2PASS
AA A B C X YZDEFG
134
5
(3404)
169
5
(4293)
134
(3404)
169
(4293)
134
(3404)
169
(4293)
140
(3556)
140
(3556)
175
(4445)
175
(4
445)
140
(3556)
175
(4445)
175
6
(4445)
129
(3277)
164
(4166)
129
(3277)
164
(4166)
129
(3277)
164
(4166)
132
(3353)
132
(3353)
167
(4242)
7
16
(4242)
133
(3378)
168
(4267)
168
(4267)
HEAD CONN.
BOTH ENDS
134
(3404)
169
(4293)
134
(3404)
169
(4293)
134
(3404)
169
(4293)
140
(3556)
140
(3556)
175
(4445)
175
(4445)
140
(3556)
175
(4445)
175
(4445)
OVERALL
HEIGHT
74
(1880)
74
(1880)
78
(1981)
78
(1981)
83
(2108)
83
(
2108) 88
2235) 93
(2362)
88
(2235)
93
(2362)
94
(2388)
94
(2388)
105
(2667)
OVERALL
WIDTH W/O
STARTER
45
(1143)
45
(1143)
49
(1245)
49
(1245)
52
(1321)
52
(1321)
56
(1422)
58
(1473)
56
(1422)
58
(1473)
74
(1880)
74
(1880)
80
(2032)
CENTER OF GRAVITY FOOTPRINT
50
(1270)35(889)18(457)
68
(1727)34(864)18(457)
51
(1295)40(1016)22(559)
69
(1753)35(889)21(533)
51
(1295)37(940)21(533)
69
(1753)38(965)22(559)
52
(1321)41(1041)25(635)
52
(1321)43(1092)26(660)
69
(1753)40(1016)25(635)
70
(1778)41(1041)26(660)
52
(1321)43(1092)34(864)
70
(1778)41(1041)34(864)
70
(1778)46(1168)38(965)
113
(2870)
(3759)
(2870)
(3759)
(2870)
(3759)
(2870)
(2870)
(3759)
(3759)
(2870)
(3759)
(3759)
111
(2819)45(1173)37(9398)
148
145
(3683)45(1173)37(9398)
113
111
(2819)49(1245)41(1041)
148
145
(3683)49(1245)41(1041)
113
111
(2819)52(1321)441118)
148
145
(3683)52(1321)441118)
113
111
(2819)56(1422)48(1219)
113
111
(2819)58(1473)50(1270)
148
145
(3683)56(1422
148
145
(3683)58(1473)50(1270)
113
111
(2819)74(1880)66(1676)
148
145
(3683)74(1879)66(1676)
148
145
(3683)80(2032)72(1829)
)48(1
219)
CONNECTIONS
EVAP
2-PASS
COND
2-PASS
88
88
88
88
88
88
10 8
10 10
10
10 10
12 10
12 10
12 12
8
Cat 605-5 31
Dimensions
Figure 24: WSC100/113/126 (600-1250 tons/ 2100 to4400 kW) See Drawing Notes page 44
VESSEL CODE OVERALL LENGTH
EVAP COND
E3612 C3012
E3612 C3612
E4212 C3612
E4212 C4212
E4812 C4212
E48127C4812
1&3
PASS2PASS
AA A B C XYZDEFG
175
(4445)
(4445)
(4445)
(4445)
(4597)
7
(4597)
175
175
175
181
181
(4267)
(4267)
(4318)
(431
(4445)
(4445)
168
168
170
170
175
175
HEAD CONN
BOTH ENDS
8)
175
(4445)
175
(4445)
175
(4445)
175
(4445)
181
(4597)
181
(4597)
OVERALL
HEIGHT
99
(2515)
99
(2515)
99
(2515)
102
(2591)
106
(2692)
106
(2692)
OVERALL
WIDTH W/O
STARTER
74
(1880)68(1727)47(1194)27(686)
80
(2032)68(1727)46(1168)31(787)
86
(2184)69(1753)45(1143)35(889)
92
(2
337)69(1753)45(1143)37(940) 98
(2489)69(1753)46(1168)421067)
104
(2642)70(1778)46(1168)46(1168)
CENTER OF GRAVITY FOOTPRINT
148
(3759)
(3759)
(3759)
(3759)
(3759)
(3683)
145
(3683)74(1880)66(1676)
148
145
(3683)80(2032)72(1829)
148
145
(3683)86(2184)78(1981)
148
145
(3683)922337)84(2134)
148
145
(3683)982489)90(2286)
145
145
(3683)
104
(2642)96(2438)
CONNECTIONS
(NOTE 10)
EVAP
2-PASS
COND
2-PASS
12 10
12 12
14 12
14 14
18 14
18 18
32 Cat 605-5
Figure 25: WDC063 (400-600 tons / 1400-2100 kW) See Drawing Notes page 44
Dimensions
VESSEL CODE OVERALL LENGTH
HEAD CONN WIDTH W/O
BOTH ENDS STARTER
214
(5426)
214
(5426)
214
(5426)
214
(
5426) 214
(5445)
218
(5518)
218
(5544)
218
(5544)
218
(5544)
218
(5544)
221
(5623)
224
(5685)
EVAP COND
E2416 C2416
E2416 C2616
E2616 C2416
E2616 C2616
E3016 C3016
E3616 C3616
1&3
PASS2PASS
AA A B C XY Z D E F G
218
(5544)
218
(5544)
218
(5544)
218
(5544)
221
(5623)
224
(5685)
OVERALL
HEIGHT
80
(2032)
80
(2032)
80
(2032)
80
2)
(203
90
(2280)
106
(2686)
OVERALL
58
(1470)
58
(1470)
58
(1470)
58
(1470)
64
(1619)95(2410)
75
(1886)
CENTER OF GRAVITY FOOTPRINT
91
(2318)36(911)17(425)
91
35
35
40
17¼
(438)
16
(419)
21
(537)
(2324)
(2324)36(911)
(2340)
(895)
91
92
(899)17(435)
(1029)
(2) (2) (2)
199
(5048)
199
(5048)
199
(5048)
199
(5048)
199
(5048)
199
(5048)
196
(4972)58(1470)50(1267)
196
(4972)58(1470)50(1267)
196
(4972)58(1470)50(1267)
196
(4972)58(1470)50(1267)
196
(4972)64(1619)56(1416)
196
(4972)
75
(1886)67(1682)
CONNECTIONS
COND
EVAP
PASS
10 10
12 12
2
2
PASS
88
88
88
88
Cat 605-5 33
Dimensions
Figure 26: WDC079/087 (600-1200 tons/ 2100-4220 kW) See Drawing Notes page 44
VESSEL CODE OVERALL LENGTH
HEAD CONN WIDTH W/O
BOTH ENDS STARTER
214
218
218
219
5556)
(5620)
(5696)
(5698)
(5698)
EVAP COND
E3016 C3016
E3616 C3016
E3616 C3616
E4216 C4216
1&3
PASS2PASS
AA A B C XYZDEFG
221
(5620)
(5696)
(5698)
(5698)
224
224
224
(5442)
(5531)
(5531)
(
221
224
224
224
OVERALL
HEIGHT
95
(2413)
100
(2530)
106
(2686)
93
62)
(23
OVERALL
57
(1454)
71
(1808)94(2388)
74
(1886)
(2362)97(2458)
(2369)
(2392)
93
CENTER OF GRAVITY FOOTPRINT
93
44
19
199
196
(4974)57(1453)49(1250)
199
196
(4974)71(1803)63(1600)
199
196
(4974)74(1886)66(1682)
199
196
(4974)93(2343)84(2134)
94
(1127)
(1149)32(803)
(1232)
(1127)47(1172)
45
48
44
(492)
32
(822)
(5050)
(5050)
(5050)
(5050)
CONNECTIONS
COND
EVAP
2
PASS
10 10
12 10
12 12
14 14
2
PASS
34 Cat 605-5
Dimensions
Figure 27: WDC100 - 16’ Shells (1200-1700 tons/ 4200-5950 kW) Medium Voltage (<7kV) ONLY (See Drawing Notes page 44)
WDC113 - 16’ shells (1400-1900 tons / 4900-6700 kW) Medium Voltage (<7kV) ONLY (See Drawing Notes page 44)
WDC126 - 16’ shells (1600-2700 tons / 5600-9450 kW) Medium Voltage (<7kV) ONLY (See Drawing Notes page 44)
VESSEL CODE OVERALL LENGTH
1&3 2 HEAD CONN WIDTH W/O
EVAP COND PASS PASS BOTH ENDS STARTER
AA A B C X Y Z DEF G
224
E3616 C3616
E4216 C4216
E4816 C4816
(5692)
224
(5692)
230
(5848)
218
(5528)
219
(5554)
224
(5703)
224
(5692)
224
(5692)
230
(5848)
OVERALL
HEIGHT
105
(2667)
108
(2743)
115
(2921)
OVERALL
95
(2419)93(2353)51(1292)40(1003)
100
(2545)94(2381)50(1254)44(1105)
110
(2792)95(2400)52(1318)51(1292)
CENTER OF GRAVITY
W/O STARTER FOOTPRINT
199
(5050)
(5050)
(5050)
196
(4974)95(2419)87(2216)
199
196
(4974)
199
196
(4974)
100
(2545)92(2342)
110
(2792)
102
(2589)
CONNECTIONS
COND
EVAP
PASS
12 12
14 16
18 18
2
2
PASS
Cat 605-5 35
Dimensions
EVAPORATOR
CONDENSER
Y
X
B
D
1.5” FPT OIL COOLER CONNECTI ON
INT ERFA CE PANE L
UNIT
CONTROL
BO X
FOOTPRIN
1
V
Figure 28: WDC100 - 20’ Shells (1200-1700 tons/ 4200-5950 kW) Medium Voltage (<7kV) ONLY (See Drawing Notes page 44)
WDC113 - 20’ Shells (1400-1900 tons / 4900-6700 kW) Medium Voltage (<7kV) ONLY (See Drawing Notes page 44)
WDC126 - 20’ Shells (1600-2700 tons / 5600-9450 kW) Medium Voltage (<7kV) ONLY (See Drawing Notes page 44)
ADJUSTABLE OPERATOR
” FPT VESSEL RELIEF
ALVE CONNECTIONS
A
OUT
IN
OUT
T
Y
Z
IN
C
VESSEL CODE OVERALL LENGTH
EVAP COND
E4220 C4220
E4820 C4820
1&3 2 HEAD CONN WIDTH W/O
PASS PASS BOTH ENDS STARTER
AA A B C X Y Z DEF G
272
(6909)
276
(7010)
267
(6772)
271
(6890)
272
(6909)
276
(7010)
OVERALL
HEIGHT
102
(2591)
110
(2794)
OVERALL
92
(2343)
104
(2648)
CENTER OF GRAVITY FOOTPRINT
117
(2991)46(1165)
118
(3007)49(1238)
36
(921)
43
(1105)
247
(6269)
(6269)
244
(6193)92(2343)84(2140)
247
244
(6193)
(2648)96(2444)
104
CONNECTIONS
EVAP
COND
2
PASS
2
PASS
14 16
18 18
36 Cat 605-5
Figure 29: WCC100/113/126 (1200-2700 tons / 4220 to9450 kW) See Drawing Notes page 44
Dimensions
EVAP COND
E3620 C3620
E4220 C3620
E4220 C4220
E4820 C4220
E4820 C4820
OVERALL LENGTH OVERALL
1 PASS
EVAP
AA1B C C1 XYZXYZ
272 1/4 272 1/4 100 3/8 80 1/4 72 1/4 115 48 3/4 30 1/2 115 3/4 47 1/4 30 7/8
(6915) (6915) (2550) (2038) (1835) (2921) (1238) (775) (2940) (1200) (784)
272 1/4 272 1/4 101 7/8 86 1/4 78 1/4 115 3/4 47 1/2 34 1/8 116 1/2 46 1/8 34 1/8
(6915) (6915) (2588) (2191) (1988) (2940) (1207) (867) (2959) (1172) (867)
272 1/4 272 1/4 104 5/8 92 1/4 84 1/4 116 1/4 48 38 117 1/4 45 7/8 38 3/4
(6915) (6915) (2658) (2343) (2140) (2953) (1219) (965) (2978) (1165) (984)
278 1/4 272 1/4 108 1/4 98 1/4 90 1/4 116 3/4 49 40 3/4 117 1/2 47 1/2 40 7/8
(7068) (6915) (2750) (2496) (2292) (2965) (1245) (1035) (2985) (1207) (1038)
278 1/4 278 1/4 110 3/8 104 1/4 96 1/4 117 3/8 48 7/8 45 1/2 118 47 3/8 45 5/8
(7068) (7068) (2804) (2648) (2445) (2981) (1241) (1156) (2997) (1203) (1159)
1 PASS
COND
UNIT
HEIGHT
OVERALL
WIDTH W/O
STARTERS
WIDTH
MTG. HOLES
ON FOOT
CENTER OF GRAVITY
(SHIPPING)
CENTER OF GRAVITY
(OPERATING)
Cat 605-5 37
Dimensions
(A9)
(A10)
(A7) and (A8)
(Z6)
(Z7)
(Z8)
(Z9)
(A5)
(A6)
6.20 157
(C)
CONDENSER
EVAPORATOR
Z
X
TOP VIEW
3/8-INCH FLARE[9MM] OIL PUMP RELIEF VALVE TYPE.(2X)
UNIT CONTROL BOX (MICRO TECH II)
ADJUSTABLE OPERATOR INTERFACE TOUCH-SCREEN PANEL (REMOVED FOR SHIPPING)
6
TERMINAL BOXES ARE TAKEN OFF DURING SHIPPING
TYP.2X
(Y3)
TYP.2X
(Y2)
(B)
(E) REF.
(A)
EVAPORATOR
CONDENSER
FRONT VIEW
1.00-INCH FPT [25MM] RELIEF VALVE ON BACKSIDE OF UNIT TYP.(2X)
1.00-INCH FPT [25MM] RELIEF VALVE TYP.(2X)
5
5
X
Z
13
7, 11
3, 11
WDC UNIT INFO
333658601 00 NONE
DRAWING NUMBER REV. SCALE
Figure 30: WDC 100/113/126 (Higher Voltage Models - 10/11kV only) continued next page
Note: This drawing for high-voltage models only. See drawing notes Figure 36, page 44.
38 Cat 605-5
40.20
TYP. 2X
1021
(Y6)
(Z4)
(Z5)
4.00
TYP.
102
COMPRESSOR MOTOR TYP.2X
COND
EVAP
Y
Z
1.50-INCH FPT [25mm] OIL COOLER CONNECTIONS
LEFT VIEW
7, 15, 16
8
(D)
(F)
(G)
(E)
17.35
TYP. 2X
441
38.18
TYP. 2X
970
X
Z
COMPRESSOR MOTOR TERMINAL BOX - TYP.2X
TOP VIEW MOUNTING
COMPRESSOR #1 COMPRESSOR #2
7, 15, 16
(Z3)
(Y7)
4.00 102
(Y4)
(Y5)
(Z1)
(Z2)
Y
Z
EVAP
COND
IN
OUT
OUT
IN
RIGHT VIEW
WDC UNIT INFO
333658601 00 NONE
DRAWING NUMBER REV. SCALE
Figure 31: WDC 100/113/126 (Higher Voltage Models - 10/11kV only) continued
Dimensions
Note: This drawing for high-voltage models only. See drawing notes Figure 36, page 44.
Cat 605-5 39
Dimensions
WDC UNIT INFO
333658601 00 NONE
DRAWING NUMBER REV. SCALE
Figure 32: WDC 100/113/126 High-Voltage Models (10/11kV) Dimension Details
Note: This drawing for high-voltage models only. See drawing notes Figure 36, page 44.
40 Cat 605-5
Figure 33: WCC 100/113/126 Higher Voltage Models (10/11kV) only (continued on next page)
(A8)
(A7)
(A10)
(A9)
TYP.2X
(Z7)
TYP.2X
(Z8)
(C)
CONDENSER
EVAPORATOR
Z
X
CIRCUIT #1
CIRCUIT #2
UNIT CONTROL BOX (MICRO TECH II)
#1 #2
3/8-INCH FLARE[9MM] OIL PUMP RELIEF VALVE TYPE.(2X)
TOP VIEW
6
ADJUSTABLE OPERATOR INTERFACE TOUCH­SCREEN PANEL (REMOVED FOR SHIPPING)
TERMINAL BOXES ARE TAKEN OFF DURING SHIPPING
Y
X
(A5)
(A6)
(E) REF.
6.20 157
(B)
TYP.2X
(Y3)
TYP.2X
(Y2)
(A3)
(A4)
(A)
EVAPORATOR
CONDENSER
CIRCUIT #1 CIRCUIT #2
1.00-INCH FPT [25MM] RELIEF VALVE ON BACKSIDE OF UNIT ­TYP.(2X)
1.00-INCH FPT [25MM]
RELIEF VALVE
TYP.(2X)
FRONT VIEW
7, 11
5
13
5
3, 11
WCC UNIT INFO
333658501 00 NONE
DRAWING NUMBER REV. SCALE
Dimensions
Note: This drawing for high-voltage models only. See drawing notes Figure 36, page 44.
Cat 605-5 41
Dimensions
(Y6)
40.20
TYP.2X
1021
(Z4)
(Z5)
4.00 102
COMPRESSOR MOTOR TYP.2X
COND
EVAP
IN
OUT
Y
Z
LEFT VIEW
8
1.50-INCH FPT [25mm] OIL COOLER CONNECTIONS
7, 15, 16
38.18
TYP.2X
970
17.35
TYP. 2X
441
4.00
TYP.
102
(E)
(D)
(G)
(F)
X
Z
#1 #2
COMPRESSOR MOTOR TERMINAL BOX - TYP.2X
TOP VIEW MOUNTING
7, 15, 16
4.00 102
(Z6)
(Y7)
(Y5)
(Y4)
(Z1)
(Z2)
Y
Z
EVAP
COND
IN
OUT
RIGHT VIEW
WCC UNIT INFO
333658501 00 NONE
DRAWING NUMBER REV. SCALE
Figure 34: WCC 100/113/126 Higher Voltage Models (10/11kV) only (continued)
Note: This drawing for high-voltage models only. See drawing notes Figure 36, page 44.
42 Cat 605-5
Figure 35: WCC 100/113/126 High-Voltage Models (10/11kV) Dimension Details
WCC UNIT INFO
333658501 00 NONE
DRAWING NUMBER REV. SCALE
Dimensions
Note: This drawing for high-voltage models only. See drawing notes Figure 36, page 44.
Cat 605-5 43
Dimensions
WCC-WDC UNIT INFO
333658701 00 NONE
DRAWING NUMBER REV. SCALE
General Drawing Notes:
1 Drawings included in this section are for rough layout
purposes only. Detailed certified drawings, as pdf files or paper copies,
are available from the local Daikin sales office. Do not use catalog drawings for final construction.
2 Dimensions in inches (mm). A 1-inch manufacturing
tolerance must be accounted for in the design and installation process. Final connections must allow for .500 inch [12.7mm] manufacturing tolerances. See Physical Data and Weights section for component and unit weights.
3 The connections shown are for one possible default
configuration; your unit may be configured differently. Orientation (left/right) is determined while facing the control panel. Certain WSC models with a 2-pass configuration and copper tubing may have an "over/ under" connection configuration on the evaporator. Consult the Certified Drawings sheet for exact configuration and detailed dimensions of water, oil cooler, and relief valve connections.
Figure 36: WDC & WCC Drawing Notes
4 Allow three (3) feet of service access on all four sides,
plus allow the length of the tube plus two feet on one end for tube removal. The last two numbers in the vessel code are the tube length in feet. The NEC may require more than 3 feet clearance in front of control panels or starting equipment depending voltage and layout.
5 E2209/C2209 and E2212/C2212 available on WSC079
only.
6 E3612/C3612 combination available on WSC 087 only. 7 E4812/C4812 available on WSC 126 only. 8 The optional unit-mounted starter is shipped separate for
field mounting, brackets and interconnecting cables are shipped with the unit.
9 The adjustable control interface panel is shipped un-
mounted from the unit. When mounted, it can be folded back within the confines of the unit width and height and still be viewable.
10 Victaulic connections 14-inch and larger are AWWA C-
606. Field piping using the Victaulic brand AGS® groove system will require a field-supplied transition.
44 Cat 605-5
Figure 37: WCC Head Connection Dimensions - See Notes
Dimensions
EVAPORATOR HEADS
A2 Y4 Z1
EVAP COND
E3620 C3620
E4220 C362
E4220 C422
E4820 C422
E4820 C482
NOTES:
CONNECTIONS
0
0
0
0
1 PASS
16.00 14 1/4 46 1/8 16 16.00 (406) (362) (1172) (406) (406) (362) (572) (1426)
20.00 14 1/4 43 1/8 19 16.00 (508) (362) (1096) (483) (406) (362) (572) (1578)
20.00 14 1/4 45 7/8 19 20.00 (508) (362) (1165) (483) (508) (362) (641) (1654)
24.00 17 1/4 46 7/8 22 20.00 (610) (438) (1191) (559) (508) (362) (641) (1807)
24.00 17 1/4 49 22 24.00 (610) (438) (1245) (559) (610) (438) (718) (1883)
1 All dimensions are in Inches and [Millimeters] unless noted otherwise. 2 Final connections must allow for .500 inch [12.7mm] manufacturing
tolerances.
3 1.00-inch FPT [25.4 mm] evaporator and condenser relief valves must
be piped per ANSI / ASHRAE 15. Number of relief valves is 2 per evaporator (1 each circuit) and 4 per condenser (2 each circuit).
4 .375 inch [9 mm] oil pump relief valve, 1 per oil pump must be piped
per ANSI / ASHRAE 15.
5 243 inches is required at either end of the tube sheet for tube
maintenance. 36 inches [914 mm] is recommended on all other sides and top for service clearance.
6 1.50-inch FPT [38 mm] oil cooler water connections. 7 3.25-inch [95 mm] diameter lifting holes are provided. See installation
manual for lifting instructions.
8 All water connections are given in standard U.S. pipe sizes. Standard
connections are suitable for welding or victaulic couplings.
9 Standard 1 pass heads with victaulic connections are shown on both the
evaporator and condenser. Units with anged connections add .500 [12.7
CONDENSER HEADS
CONNECTIONS
1 PASS
mm] at each end for the overall unit length. Standard flanges are ANSI Class 150.
A3 Y5 Z2
14 1/4 22 1/2 56 1/8
14 1/4 22 1/2 62 1/8
14 1/4 25 1/4 65 1/8
14 1/4 25 1/4 71 1/8
17 1/4 28 1/4 74 1/8
10 Dimensions shown are for units (evaporator / condenser) with standard
design pressures. The refrigerant side design pressure is 200 PSI {1380 kPa} and the waterside design pressure is 150 PSI {1034 kPa}.
11 Consult the factory for unit dimensions with higher design pressures. 12 Vibrator Isolator pads are provided for eld installation - .250 inches [6
mm] thick when fully loaded.
13 These values are for units with standard wall thickness copper tubing
only.
14 The shipping skid when used adds 4.00 inches [105 mm] to the overall
unit height.
15 If main power wiring is brought up through the floor, this wiring must
be outside the envelope of the unit.
16 Typical wiring hookup to the compressor is either the top or bottom of
the compressor terminal box
17 The units pump down capacity is determined in accordance with ANSI
/ ASHRAE 15 for the maximum tube count.
18 These values are for the units corner weights. 19 The unit is shipped with an operating charge of oil and refrigerant.
Cat 605-5 45
Dimensions
GGG
TYP.
FFF
BBB
TYP.
AAA
OUT
IN
CCC
DDD
EEEEEE
DDD
CCC
TYP.
FFF
BBB
GGG
TYP.
AAA
OUT
IN
*
NOTE:
Certain WSC models with a 2-pass configuration and copper tubing will have an “over/under” connection configuration on the evaporator.
Consult your Certified Drawings for your unit configuration.
Figure 38: Marine Water Box Dimensions (WSC/WCC)
REAR FACING ONLY
REAR FACING ONLY
REAR FACING ONLY
Note: Marine water boxes are an available option on all evaporator and condenser sizes. Epoxy coating of the water boxes and clad
tube sheets are available for extreme duty applications. See Notes on Next Page.
Table 15:
Dimensions with Victaulic or Flanged Connections (150 PSI Non-ASME - Victaulic Connection)
Evap.
Dia.
'AAA' 'BBB 'CC 'DD 'EEE 'AAA 'BBB' 'CC 'DD 'EEE 'FFF' 'GG 'AAA 'BBB 'CC 'DD 'EEE 'FFF' E18 8.63 15.0 19.2 18.0 9.00 6.63 15.00 19.0 18.0 9.00 4.78 21.0 4.50 15.0 19.2 18.0 9.00 5.85 E20 8.63 16.0 19.2 18.0 9.00 6.63 16.00 19.0 18.0 9.00 5.63 16.0 4.50 16.0 19.2 18.0 9.00 6.69 E22 10.7 17.0 21.2 20.0 10.0 8.63 17.00 21.0 20.0 10.0 5.59 23.0 5.56 17.0 21.2 20.0 10.0 7.12 E26 10.7 19.0 21.2 20.0 10.0 8.63 19.00 21.2 20.0 10.0 7.07 19.0 6.63 19.0 21.2 20.0 10.0 8.07
E26* - - - - - 8.63 19.00 21.2 20.0 10.0 13.5 19.0 - - - - -
E30 14.0 21.0 28.5 26.5 13.2 10.7 21.00 28.5 26.5 13.2 8.13 21.0 6.63 21.0 28.5 26.5 13.2 10.1
E30* - - - - - 10.7 22.00 28.5 26.5 13.2 16.0 22.0 - - - - -
E36 16.0 24.0 29.5 28.0 14.0 12.7 24.00 29.5 28.0 14.0 9.75 24.0 8.63 24.0 29.5 28.0 14.0 11.8
E36* - - - - - 12.7 25.00 29.5 28.0 14.0 19.5 25.0 - - - - -
E42 20.0 27.0 34.7 33.0 16.5 14.0 27.00 34.7 33.0 16.5 11.6 27.0 10.7 27.0 34.7 33.0 16.5 13.2
E42* - - - - - 14.0 28.00 34.7 33.0 16.5 22.7 28.0 - - - - -
E48 24.0 30.0 38.5 36.5 18.2 18.0 30.00 38.5 36.5 18.2 12.5 36.0 12.7 30.0 38.5 36.5 18.2 15.1
E48* - - - - - 18.0 32.50 38.5 36.5 18.2 26.8 32.5 - - - - -
Cond.
Dia.
'AAA' 'BBB 'CC 'DD 'EEE 'AAA 'BBB' 'CC 'DD 'EEE 'FFF' 'GG 'AAA 'BBB 'CC 'DD 'EEE 'FFF' C16 8.62 14.0 15.2 14.0 7.00 5.56 14.00 15.0 14.0 7.00 4.35 14.0 C18 8.62 15.0 19.2 18.0 9.00 6.63 15.00 19.0 18.0 9.00 4.78 15.0 C20 8.62 16.0 19.2 18.0 9.00 6.63 16.00 19.0 18.0 9.00 5.63 16.0 C22 10.7 17.0 21.2 20.0 10.0 8.63 17.00 21.0 20.0 10.0 5.59 23.0 C26 10.7 19.0 21.2 20.0 10.0 8.63 19.00 21.2 20.0 10.0 7.07 19.0 C30 14.0 21.0 28.5 26.5 13.2 10.7 21.00 28.5 26.5 13.2 8.13 21.0 C36 16.0 24.0 30.2 28.0 14.0 12.7 24.00 30.2 28.0 14.0 9.75 24.0 C42 20.0 27.0 32.5 30.0 15.0 14.0 27.00 32.5 30.0 15.0 11.6 27.0 C48 24.0 30.0 39.5 36.0 18.2 18.0 30.00 39.5 36.5 18.2 12.5 36.5
1 PASS 2 PASS 3 PASS
1 PASS 2 PASS 3 PASS
Consult local sales office
46 Cat 605-5
Marine Waterbox Dimension (WDC)
2 and 4 Pass Cond. (Excep t 18 in. 2 Pass)
Cover Thickness
“C”
“A”
“B”
“F”
Evap. And Cond. 1 Pass
Nozzle Flanges Are Optional
“D”
.50
2 an d 4 Pass Cond. (Except 18 in. 2 Pass)
Nozzle Flanges Are Opt ion al
Nozzle Flanges Are Opt ional
.50
“D”
“E”
“E”
.50
“E”
“E”
Dimensions
FIGURE 2FIGURE 1
FIGURE 4FIGURE 3
All 2 Pass Evap. - All 4 Pass Cond.
18 in. 2 Pass Cond.
Note: Evaporator connections are front facing; condenser connections are rear facing only.
Shell
Vessel
O.D.
Evap 5 13.00 14.00 14.50 - - - - - 22.50 - - - - - 6.94 15.00
16
Cond 5 13.00 14.00 14.50 16.50 22.50 4.35 6.94 15.00
Evap 7 17.25 18.00 22.50 - - - - - 22.50 - - - - - 7.94 19.25
18
Cond 7 17.25 18.00 16.50 - - - - - 22.50 - - - - - 7.06 19.25
AB C
20 Evap 7 17.25 18.00 22.50 - - - - - 22.50 - - - - - 7.88 19.25 1.25 8 6 5 4
Evap 8 19.50 20.00 22.50 - - - - - 22.50 - - - - - 10.12 21.50
22
Cond 8 19.50 20.00 22.50 22.50 22.50 5.62 9.93 21.50
Evap 8 19.50 20.00 22.50 - - - - - 22.50 - - - - - 11.69 21.50
26
Cond 8 19.50 20.00 22.50 22.50 22.50 7.07 11.69 21.50
Evap 12 27.75 28.00 24.50 - - - - - 24.50 - - - - - 13.62 29.75
30
Cond 12 27.75 28.00 27.50 27.50 27.50 8.12 13.00 29.75
Evap 12 28.00 28.00 27.50 - - - - - 27.50 - - - - - 16.50 30.00
36
Cond 12 28.00 28.00 27.50 27.50 27.50 9.75 16.33 30.00
Evap 12 28.00 28.00 - - - - - - - - - - 25.50 - - - - - 19.54 30.00
36*
Cond 12 28.00 28.00 27.50 27.50 27.50 9.75 16.33 30.00
Evap 13 30.50 30.00 27.50 - - - - - 35.50 - - - - - 19.38 33.00
42
Cond 13 30.50 30.00 27.50 27.50 27.50 11.63 11.63 33.00
Evap - - - - - - - - 36.00 36.00 - - - - - 40.00 - - - - - 22.64 39.25
48
Cond - - - - - - - - 36.00 36.00 36.00 - - - - - 11.50 - - - - - 39.25
Flanges are ANSI raised face, mating flanges by others. Some flanges have staggered connections due to interference. Victaulic connections 14-inch and larger are AWWA C-606. Field piping using AGS grove system requires a customer transition. * Applies only to units under 800 tons with an E 3612 2-pass evaporator and copper tubing.
“D”
Outline Dimensions (inches)
DEFPipe Size For Passes
Fig 2 Fig 3 Fig 4 Fig 3 Fig 4 1P 2P 3P 4P
Cover
Thick-
ness
1.00 8 5 4 4
Connections
1.25 8 6 5 4
1.50 10 8 6 5
1.50 10 8 8 6
1.75 14 10 8 8
2.00 16 12 10 8
2.00 16 12 10 8
2.00 20 16 12 10
2.75 - - - 18 - - - - - -
Cat 605-5 47
Physical Data
Physical Data
Evaporator
Refrigerant side design pressure is 200 psi (1380 kPa) on WSC and WCC units. WDC evaporators are 180 psi (1242 kPa) and condensers are 225 psi (1552 kPa). Standard water-side design pressure is 150 psi (1034 kPa) on all vessels. 300 psi (2068 kPa) is available as an option
The standard insulation used is UL recognized (File # E55475) 3/4" thick ABS/PVC flexible foam with skin having a K factor of 0.28 at 75°F. The sheet insulation is fitted and cemented in place forming a vapor barrier, then painted with a resilient epoxy finish that resists cracking.
The insulation complies to appropriate requirements or has been tested in accordance with the following:
Optional Insulation
The optional insulation of cold surfaces includes the evaporator and non-connection water head, suction piping, compressor inlet, motor housing, and motor coolant suction line. Available options are:
Single insulation, ¾-inch, on evaporator, suction piping, an motor barrel - For normal machine room applications.
Double insulation, 1-½ inch, on evaporator, suction piping,
• ASTM-
• ASTM-C-534 Type 2
• ASTM-D-1056-91-2C1
•ASTM E 84
d
•UL 94-5V
• CAN/ULC S102-M88
.
C-177
and motor barrel -For high humidity locations and ice making applications
Table 16: Evaporator Physical Data
Evaporator
Code
E2009 X 31 (117) 82 (7.6) 2543 (1152) 478 (217) 148 (67) 1 E2012 X 37 (139) 84 (7.8) 2862 (1296) 478 (217) 148 (67) 1 E2209 X 38 (145) 66 (6.1) 2708 (1227) 600 (272) 175 (79) 1 E2212 X 45 (170) 90 (8.3) 3071 (1391) 600 (272) 175 (79) 1 E2212 X 63 (240) 90 (8.3) 3550 (1609) 600 (272) 175 (79) 1 E2216 X 79 (301) 144 (13.4) 4200 (1903) 600 (272) 175 (79) 1 E2412 X 88 (335) 131 (12.1) 4410 (1999) 700 (317) 240 (109) 1 E2416 X 110 (415) 157 (14.6) 5170 (2343) 700 (317) 240 (109) 1 E2609 X 61 (231) 76 (7.1) 3381 (1532) 899 (407) 302 (137) 1 E2612 X 72 (273) 102 (9.4) 3880 (1758) 899 (407 302 (137) 1 E2612 X 101 (381) 102 (9.4) 4745 (2150) 899 (407 302 (137) 1 E2616 X 126 (478) 162 (15.0) 5645 (2558) 899 (407 302 (137) 1 E3009 X 74 (281) 86 (8.0) 4397 (1992) 1386 (628) 517 (234) 1 E3012 X 89 (336) 115 (10.6) 5075 (2299) 1386 (628) 517 (234) 1 E3016 X 157 (594) 207 (19.2) 7085 (3211) 1386 (628) 517 (234) 2 E3609 X 128 (484) 155 14.4) 5882 (2665) 2115 (958) 805 (365) 1 E3612 X 152 (574) 129 (11.9) 6840 (3099) 2115 (958) 805 (365) 1 E3616 X 243 (918) 239 (22.2) 9600 (4351) 2115 (958) 805 (365) 2 E3620 X 219 (827) 207 (19.2) 8298 (3764) 2115 (958) 805 (365) 2 E4212 X 222 (841) 148 (13.7) 8922 (4042) 2836 (1285) 1181 (535) 1 E4216 X 347 (1313) 264 (24.5) 12215 (5536) 2836 (1285) 1181 (535) 2 E4220 X 481 (1819) 330 (30.6) 15045 (6819) 2836 (1285) 1181 (535) 2 E4220 X 319 (1208) 242 (22.5) 10853 (4923) 2836 (1285) 1181 (535) 2 E4812 X 327 (1237) 169 (15.6) 11125 (5040) 4578 (2074) 1837 (832) 2 E4816 X 556 (2106) 302 (281) 16377 (7429) 4578 (2074) 1837 (832) 2 E4820 X 661 (2503) 377 (35.0) 17190 (7791) 4578 (2074) 1837 (832) 2 E4820 X 456 (1728) 276 (25.6) 14618 (6630) 4578 (2074) 1837 (832) 2
Note 1: Water capacity is based on standard tube configuration and standard heads. Note 2: Vessel weight includes the shell, maximum tubes, and standard heads, no refrigerant. Note 3: MWB, marine water box, weight add is the water box weight minus a standard dished head weight.
WSC WDC WCC
Water
Volume
gal (L)
Insulation
Area
sq ft (m2)
Vessel Dry
Weight
lb (kg)
Add for MWB
lb (kg)
MWB Cover
Only, Weight
lb (kg)
Number of
Relief
Valves
48 Cat 605-5
Condenser
With positive pressure systems, such as those used in Daikin centrifugal chillers, the pressure variance with temperature is always predictable, and the vessel design and relief protection are based upon pure refrigerant characteristics. Our vessels are ASME designed, inspected and stamped.
Refrigerant side design pressure is 200 and WCC units and 225 psi (1552 kPa) on WDC units. Standard water side design pressure is 150 psi (1034 kPa) on all vessels. 300 psi (2068 kPa) is available as an option.
Table 17: Condenser Physical Data
psi (1380 kPa) on WSC
Physical Data
down
Pump
To facilitate compressor service, all Daikin centrifugal chillers are designed to of the entire refrigerant charge in the unit’s condenser.
WDC dual compressor units, and single compressor units equipped with a special suction shut-off valve, which requires additional cost and extended lead time, can also be pumped down into the evaporator.
permit pumpdown and isolation
Condenser
Code
C1809 X 597 (271) 34 (128) 1835 (831) 402 (182) 124 (56)
C1812 X 845 (384) 44 (166) 2183 (989) 402 (182) 124 (56)
C2009 X 728 (330) 47 (147) 2230 (1010) 478 (216) 148 (67)
C2012 X 971 (440) 62 (236) 2677 (1213) 478 (216) 148 (67)
C2209 X 822 (372) 60 (228) 2511 (1137) 478 (216) 148 (67)
C2212 X 1183 (537) 76 (290) 3031 (1373) 478 (216) 148 (67)
C2212 X 1110 (504) 89 (337) 3075 (1395) 478 (216) 148 (67)
C2216 X 1489 (676) 114 (430) 3861 (1751) 478 (216) 148 (67)
C2416 X 1760 (799) 143 (540) 4647 (2188) 685 (310) 230 (104)
C2609 X 1242 (563) 89 (335) 3210 (1454) 902 (408) 302 (137)
C2612 X 1656 (751) 111 (419) 3900 (1767) 902 (408) 302 (137)
C2616 X 2083 (945) 159 (603) 5346 (2425) 902 (408) 302 (137)
C3009 X 1611 (731) 114 (433) 4356 (1973) 1420 (643) 517 (234)
C3012 X 2148 (975) 144 (545) 5333 (2416) 1420 (643) 517 (234)
C3016 X 2789 (1265) 207 (782) 6752 (3063) 1420 (643) 517 (234)
C3612 X 2963 (1344) 234 (884) 7508 (3401) 2115 (958) 805 (364)
C3616 X 3703 (1725) 331 (1251) 9575 (4343) 2115 (958) 805 (364)
C3620 X 4991 (2264) 356 (1347) 10540 (4781) 2115 (958) 805 (364)
C4212 X 3796 (1722) 344 (1302) 10267 (4651) 2836 (1285) 1181 (535)
C4216 X 5010 (2273) 475 (1797) 12662 (5743) 2836 (1285) 1181 (535)
C4220 X 5499 (2494) 634 (2401) 17164 (7785) 2836 (1285) 1181 (535)
C4220 X 6487 (2942) 524 (1983) 14160 (6423) 2836 (1285) 1181 (535)
C4812 X 4912 (2228) 491 (1855) 13077 (5924) 4578 (2074) 1837 (8320
C4816 X 5581 (2532) 717 (2715) 18807 (8530) 4578 (2074) 1837 (8320
C4820 X 7034 (3191) 862 (3265) 23106 (10481) 4578 (2074) 1837 (8320
C4820 X 8307 (3768) 727 (2753) 18907 (8576) 4578 (2074) 1837 (8320
Note 1: Condenser pumpdown capacity based on 90% full at 90F. Note 2: Vessel weight includes the shell, maximum tubes, and standard heads, no refrigerant. Note 3: MWB, marine water box, weight add is the water box weight minus a standard dished head weight
WSC WDC WCC
Pumpdown
Capacity
lb (kg)
Water
Volume
gal (L)
Vessel Dry
Weight
lb (kg)
Add for MWB
lb (kg)
MWB Cover
Only, Weight
lb (kg)
Number of Relief
Valves
2
2
2
2
2
2
2
2
2
2
2
2
2
4
2
4
4
2
4
4
4
4
4
4
4
2
Compressor
Table 18: Compressor Weights
Compressor 063 079 087 100 113 126
Weight lb (kg)
Cat 605-5 49
2000 (908) 3200 (1440) 3200 (1440) 6000 (2700) 6000 (2700) 6000 (2700)
Physical Data
Complete Unit
Table 19: Unit Weights, Single Compressor, WSC
Unit
WSC063 2009 / 1809 410 (186) 8412 (3816) 8949 (4059) 9612 (4360) 10149 (4604) WSC063 2012 / 1812 539 (244) 9284 (4211) 9955 (4516) 10484 (4756) 11155 (5060) WSC063 2209 / 2009 479 (217) 9119 (4136) 9841 (4464) 10319 (4681) 11040 (5008) WSC063 2212 / 2012 631 (286) 10182 (4619) 11077 (5025) 11382 (5163) 12277 (5569) WSC063 2209 / 2209 495 (224) 9416 (4271) 10235 (4643) 10616 (4815) 11435 (5187) WSC063 2212 / 2212 651 (295) 10557 (4789) 11570 (5248) 11757 (5333) 12770 (5792) WSC063 2609 / 2209 651 (295) 10248 (4648) 11258 (5107) 11448 (5193) 12458 (5651) WSC063 2612 / 2212 859 (389) 11577 (5251) 12817 (5806) 12777 (5796) 14017 (6358) WSC063 2609 / 2609 686 (311) 10984 (4982) 12228 (5547) 12184 (5527) 13428 (6091) WSC063 2612 / 2612 905 (410) 12494 (5667) 14020 (6359) 13694 (6203) 15220 (6904) WSC063 3009 / 2609 825 (374) 12892 (5848) 14246 (6462) 14092 (6392) 15446 (7006) WSC063 3012 / 2612 1098 (497) 13903 (6306) 15569 (7062) 15103 (6851) 16769 (7606) WSC079 2209 / 2209 495 (224) 10140 (4600) 10959 (4971) 11340 (5144) 12159 (5515) WSC079 2212 / 2212 651 (295) 11281 (5117) 12294 (5577) 12481 (5661) 13494 (6121) WSC079 2609 / 2209 651 (295) 10980 (4981) 11990 (5439) 12180 (5525) 13190 (5983) WSC079 2612 / 2212 859 (389) 12309 (5592) 13548 (6145) 13509 (6128) 14749 (6690) WSC079 2609 / 2609 686 (311) 11716 (5314) 12960 (5879) 12916 (5859) 14160 (6423) WSC079 2612 / 2612 905 (410) 13226 (5999) 14752 (6692) 14426 (6544) 15952 (7236) WSC079 3009 / 2609 825 (374) 12892 (5848) 14246 (6462) 14092 (6392) 15446 (7006) WSC079 3012 / 2612 1098 (497) 14635 (6638) 16301 (7394) 15835 (7183) 17501 (7938) WSC079 3009 / 3009 855 (387) 14076 (6385) 15644 (7096) 15276 (6929) 16844 (7640) WSC079 3012 / 3012 1147 (520) 16119 (7312) 18061 (8192) 17319 (7856) 19261 (8737) WSC079 3609 / 3009 1173 (531) 15913 (7218) 17929 (8133) 17113 (7762) 19129 (8677) WSC079 3612 / 3012 1563 (708) 18340 (8319) 20807 (9438) 19540 (8863) 22007 (9982) WSC087 2609 / 2209 651 (295) 10980 (4981) 11990 (5439) 12180 (5525) 13190 (5983) WSC087 2612 / 2212 859 (389) 12309 (5583) 13549 (6146) 13509 (6128) 14749 (6690) WSC087 2609 / 2609 686 (311) 11716 (5314) 12960 (5879) 12916 (5859) 14160 (6423) WSC087 2612 / 2612 905 (410) 13226 (5999) 14752 (6692) 14426 (6544) 15592 (7073) WSC087 3009 / 2609 825 (374) 12892 (5848) 14246 (6462) 14092 (6392) 15446 (7006) WSC087 3012 / 2612 1098 (497) 14635 (6638) 16301 (7394) 15835 (7183) 17501 (7938) WSC087 3009 / 3009 862 (390) 14076 (6385) 15644 (7096) 15276 (6929) 16844 (7640) WSC087 3012 / 3012 1147 (520) 16118 (7311) 18060 (8192) 17318 (7855) 19260 (8736) WSC087 3609 / 3009 1173 (531) 15913 (7218) 17929 (8133) 17113 (7762) 19129 (8677) WSC087 3612 / 3012 1563 (708) 18339 (8319) 20806 (9438) 19539 (8863) 22006 (9982) WSC087 3612 / 3612 1635 (740) 20584 (9337) 23799 (10795) 21784 (9881) 24999 (11340) WSC100 3612 / 3012 1563 (708) 21578 (9788) 24045 (10907) 22778 (10332) 25245 (11451) WSC100 3612 / 3612 1635 (740) 23826 (10807) 27041 (12266) 25026 (11352) 28241 (12810) WSC100 4212 / 3612 2081 (943) 26457 (12001) 30260 (13726) 27657 (13545) 31460 (14270) WSC100 4212 / 4212 2164 (980) 29298 (13290) 34024 (15433) 30498 (13834) 35224 (15978) WSC100 4812 / 4212 2688 (1217) 32024 (14526) 37623 (17066) 33224 (15070) 38823 (17610)
WSC113 3612 / 3012 1563 (708) 21578 (9788) 24045 (10907) 22778 (10332) 25245 (11451) WSC113 3612 / 3612 1635 (740) 23826 (10807) 27041 (12266) 25026 (11352) 28241 (12810) WSC113 4212 / 3612 2081 (943) 26457 (12001) 30260 (13726) 27657 (13545) 31460 (14270) WSC113 4212 / 4212 2164 (980) 29298 (13290) 34024 (15433) 30498 (13834) 35224 (15978) WSC113 4812 / 4212 2688 (1217) 32024 (14526) 37623 (17066) 33224 (15070) 38823 (17610)
WSC113 4812 / 4812 2867 (1299) 35016 (15883) 41817 (18968) 36216 (16427) 43017 (19513) WSC126 3612 / 3012 1563 (708) 21680 (9834) 24147 (10953) 22880 (10378) 25347 (11497) WSC126 3612 / 3612 1635 (740) 23928 (10854) 27143 (12312) 25128 (11398) 28343 (12856) WSC126 4212 / 3612 2081 (943) 26457 (12001) 30260 (13726) 27657 (12545) 31460 (14270) WSC126 4212 / 4212 2164 (980) 29298 (13290) 34024 (15433) 30498 (13834) 35224 (15978) WSC126 4812 / 4212 2164 (980) 32024 (14526) 37623 (17066) 33224 (15070) 38823 (17610) WSC126 4812 / 4812 2867 (1299) 35016 (15883) 41817 (18968) 36216 (16427) 43017 (19513)
Note: 1, With starters (factory mounted) applies only to low voltage (200 to 600 volts) equipment.
Evaporator /
Condenser
Unit Refrig.
Charge (1)
Max. Unit Weight Without Starter Max. Unit Weight With Starter
Shipping Operating Shipping Operating
50 Cat 605-5
Physical Data
Table 20: Dual Compressor, WDC/WCC
Unit
WDC063 2416 / 2416 18673 (8470) 20422 (9263) 21407 (9710) 23156 (10503) WDC063 2416 / 2616 19365 (8784) 21294 (9577) 22099 (10024) 23848 (10817) WDC063 2616 / 2416 19282 (8746) 21207 (9639) 22016 (9986) 23763 (10779) WDC063 2616 / 2616 20025 (9083) 22091 (9939) 22759 (10323) 24646 (11179) WDC063 3016 / 3016 23545 (10680) 26405 (11830) 26279 (11920) 28815 (13070) WDC063 3616 / 3016 27763 (12604) 31018 (14082) 30163 (13694) 33418 (15172) WDC063 3616 / 3616 32027 (14540) 35115 (15942) 33427 (15176) 37515 (17032) WDC079 3016 / 3016 25131 (11399) 27671 (12551) 27531 (12488) 30071 (13640) WDC079 3616 / 3016 28763 (13047) 32018 (14523) 31163 (14135) 34418 (15612) WDC079 3616 / 3616 32027 (14527) 36115 (16382) 34427 (15616) 38515 (17470) WDC079 4216 / 4216 44470 (20189) 51463 (23364) 47204 (21431) 54197 (24605) WDC087 3016 / 3016 26157 (11865) 28697 (13017) 28891 (13105) 31431 (14257) WDC087 3616 / 3016 29789 (13512) 33044 (14989) 32523 (14752) 35778 (15322) WDC087 3616 / 3616 33053 (14993) 37141 (16847) 35787 (16233) 39875 (18087) WDC087 4216 / 4216 44470 (20189) 51463 (23364) 47204 (21431) 54197 (24605)
WDC100, 113 3616 / 3616 41816 (18967) 46513 (21098) See Note 2 See Note 2 WDC100, 113, 126 (<7kV) 4216 / 4216 50470 (22893) 57463 (26065) See Note 2 See Note 2 WDC100, 113, 126 (<7kV) 4816 / 4816 59185 (26846) 68996 (31296) See Note 2 See Note 2 WDC100, 113, 126 (<7kV) 4220 / 4220 54802 (24858) 63248 (28689) See Note 2 See Note 2 WDC100, 113, 126 (<7kV) 4820 / 4820 65964 (29921) 77698 (35243) See Note 2 See Note 2 WCC100, 113, 126 (<7kV) 3620 / 3620 37645 (17091) 41334 (19268) See Note 2 See Note 2 WCC100, 113, 126 (<7kV) 4220 / 3620 41320 (18759) 45609 (21317) See Note 2 See Note 2 WCC100, 113, 126 (<7kV) 4220 / 4220 45314 (20573) 50281 (23767) See Note 2 See Note 2 WCC100, 113, 126 (<7kV) 4820 / 4220 49759 (22590) 56173 (26305) See Note 2 See Note 2 WCC100, 113, 126 (<7kV) 4820 / 4820 55927 (25391) 62528 (29876) See Note 2 See Note 2
WDC100, 113, 126 (10/11kV) 4216/4216 55760 (25292) 63536 (28219) See Note 2 See Note 2 WDC100, 113, 126 (10/11kV) 4220/4220 62136 (28184) 71426 (32398) See Note 2 See Note 2 WDC100, 113, 126 (10/11kV) 4820/4820 73526 (33351) 86282 (39137) See Note 2 See Note 2 WCC100, 113, 126 (10/11kV) 4220/4220 55987 (25395) 63262 (28695) See Note 2 See Note 2 WCC100, 113, 126 (10/11kV) 4820/4820 65768 (29832) 75761 (34365) See Note 2 See Note 2
Note: 1. With starters (factory mounted) applies only to low voltage (200 to 600 volts) equipment. Note: 2. Unit not available with factory mounted starters.
Evaporator / Condenser
Size
Max. Unit Weight Without Starter Max. Unit Weight With Starter (1)
Shipping
lbs. (kg)
Operating
lbs. (kg)
Shipping
lbs. (kg)
Operating
lbs. (kg)
Cat 605-5 51
Options and Accessories
Options and Accessories
Vessels
Marine water boxes
Provides tube access for inspection, cleaning, and removal without dismantling water piping.
Flanges (Victaulic connections are standard)
ANSI raised face flanges on either the evaporator or condenser. Mating flanges are by others.
0.028 or 0.035 in. tube wall thickness
For applications with aggressive water conditions requiring thicker tube walls.
Cupro-nickel or titanium tube material
For use with corrosive water conditions, includes clad tube sheets and epoxy coated water heads.
Water-side vessel construction of 300 psi (150 psi is standard)
For high-pressure water systems, typically high-rise building construction.
Water differential pressure switches
This option provides evaporator and condenser water thermal dispersion flow sensors as a factory mounted and wired option. A proof-of-flow device is mandatory in both the chilled water and condenser water systems.
Single insulation
¾-inch, on evaporator, suction piping, and motor barrel; For normal machine room applications.
Double insulation
1-½ inch, on evaporator, suction piping, and motor barrel; For high humidity locations and ice making applications.
Electrical
Optional starters for factory or field mounting
See details in the Motor Starter section of this manual and catalog PM Starter.
Variable frequency drives (VFD)
The variable frequency drive option is a technology that has been used for decades to control motor speed on of motor-drive applications. When applied to centrifugal compressor motors, significant gains in compressor part load performance can be realized. The improvement in efficiency and reduction of annual energy cost is maximized when there are long periods of part load operation, combined with low compressor lift (lower condenser water temperatures). When atmospheric conditions permit, Daikin chillers equipped with VFDs can operate with entering condenser as low as 50F (10 C), which results in extremely low kW/ton values.
a wide variety
Water-Side Economizers: Free cooling systems utilizing cold cooling tower water to remove system through a heat exchanger are becoming popular because the ability of a chiller to move seamlessly from mechanical cooling to the free cooling mode is an important operational feature. When equipped with a VFD, Daikin chillers can operate with condenser water down to 50F (10 C) at which point the economizer heat exchanger can be activated and the free cooling can go into effect.
Starting Inrush: The use of a VFD on centrifugal chillers also provides an excellent method of reducing motor starting inrush, even better than solid-state starters. Starting current can be closely controlled since both the frequency and voltage are regulated. This can be an important benefit to a building's electrical distribution system.
Sound: The sound level of centrifugal compressors is largely dependent on the impeller tip speed. By reducing compressor speed the sound level is also reduced.
NEMA 4 watertight enclosure
heat from the chilled water
For use where there is a possibility of water intrusion into the control panel.
NEMA 12 Dust tight enclosure
For use in dusty areas.
Controls
English or Metric Display
Either English or metric units for operator ease of use.
BAS Interface Module
Factory-installed on the unit controller (can also be retrofitted). See page 13 for details.
Unit
Export packaging
Can be either slat or full crate for additional protection during shipment. Units normally shipped in containers.
Pumpout Unit, Model RRU with or without storage vessel
Available in a variety of sizes. Details under the Pumpout section on page 54.
Refrigerant monitor
For remote mounting, including accessories such as 4-20ma signal, strobe light, audible horn, air pick-up filter. Details on
page 54.
52 Cat 605-5
Options and Accessories
Hot gas bypass
Reduces compressor cycling and its attendant chilled water temperature swings at very low loads.
Sound attenuation package
For extremely sensitive projects, an optional discharge line sound package is offered consisting of sound insulation installed on the unit's discharge line. An additional 2 to 4 dbA reduction normally occurs.
Extended warranties
Extended 1, 2, 3, or 4-year warranties for parts only or for parts and labor are available for the entire unit or compressor/ motor only.
Optional Certified Test
A Daikin engineer oversees the testing, certifies the accuracy of the computerized results, and then translates the test data onto an easy-to-read spreadsheet. The tests can be run at AHRI load points and are run to AHRI tolerance of capacity and power. 50 Hz units are run tested at 60 Hz to their maximum motor power.
Optional Witness Test
A Daikin engineer oversees the testing in the presence of the customer or their designate and translates the easy-to-read spreadsheet. The tests can be run at AHRI load points and are run to AHRI tolerance of capacity and power. Allow two to three hours of test time per load point
test data onto an
specified. Units built for 50 Hz power can be run-tested using an onsite 50 Hz generator.
Special Order Options
The following special order options are available; requiring factory pricing, additional engineering changes or extended delivery: Consult the Daikin sales office for other possible specials.
Non-standard location of nozzle connections on heads (compact water boxes) or marine water boxes
Special corrosion inhibiting coatings on any "wetted surface" including tubesheets, heads (compact water boxes), marine water boxes, or nozzles
Clad tube sheets
Sacrificial anodes in heads (compact water boxes) or marine
water boxes
Eddy current testing and report used to verify baseline tube condition
Special NEMA enclosures
Hinges for marine water box covers or heads (compact water boxes)
Accelerometer and vibration monitoring pickup mounting (WSC/WDC/WCC/HSC)
Spacer rings on heads to accommodate automatic tube brush cleaning systems (installed by others)
and possible dimension
Cat 605-5 53
Refrigerant Recovery Units and Monitors
Refrigerant Recovery Units and Monitors
Pump Out Units
Although Daikin ch charge into the condenser and valve it off, there are occasions when pumpout units are required, due purely to specification requirements or unusual job considerations. Daikin offers two sizes of refrigerant recovery units (Model RRU) and one recovery unit that is factory mounted on a storage vessel (Model PRU). Recovery units are ETL listed. Capacities for R-22 are AHRI certified. The storage tank is designed, constructed and stamped in accordance with ASME standards.
Model RRU134
illers can pump the entire refrigerant
Large 1 ½-HP open drive compressor, ½-inch lines, two­point vapor extraction and oversized air-cooled condenser speed recovery on smaller size chillers. Purging and switching from liquid to vapor recovery only involves turning 3-way valves-no switching of hoses is necessary. Capacity with R­134a is 55 lb/min liquid, 1.34 lb/min vapor.
MODEL RRU570
Recovers at R-134a at 300 lb/ min liquid and 5.7 lb/min vapor, ideal for the medium size chiller job. Rugged 3 hp open-drive compressor provides years of reliable service, even on refrigerants heavily contaminated with oil, air, moisture, or acids. Purging and switching from liquid to vapor recovery only involves
turning 3-way valves-no switching of hoses is necessary. Suitable for most high­pressure refrigerants and blends. Equipped with air-cooled condenser.
Refrigerant Monitors
ANSI/ASHRAE 15-2001 recommends that every machine room with refrigeration equipment should have a refrigerant leak detection system, especially if the .
54 Cat 605-5
Retrofit Disassembly (Knockdown Options)
Retrofit Disassembly (K nockdown Options)
Many retrofit applications require partial or complete disassembly of the chiller. On WSC chillers, Daikin offers two solutions to this problem t
o best fit job conditions. Contact local Daikin Factory Service for price quotation and scheduling.
On-site disassembly
The major components (evaporator, condenser, and compressor) are shipped fully assemb
led and charged and can be taken apart at the site to facilitate difficult rigging work. The chillers are shipped assembled from the factory after testing, and then disassembled and reassembled on site under supervision of authorized Daikin service personnel. Contact local Daikin Factory Service for price quotation and scheduling. Individual component weights are shown in the Physical Data section of this catalog, beginning on page 48.
Shipped disassembled
Chillers can be shipped knocked down from the factory.
The evaporator, condenser and oil pump are shipped bolted together and easily unbolted at the job site into the pieces shown in page 56. Other options, such as shipping less compressor or less compressor and control panel are also available. Site reassembly must be supervised by Daikin startup personnel.Contact local Daikin Factory Service for price quotation and scheduling.
TYPE I Knockdown
Daikin provides ease of installation without requiring construction alterations of entryways to your building. The compressor and compressor control box are removed and put on a skid. All associated wiring and piping will remain attached if possible. The remaining loose
parts will be
packaged in a separate crate.
1 Blockoffs will cover all openings on the compressor and
vessels.
2 The compressor and vessels will receive a helium
holding charge.
3 The compressor will not be insulated at the factory. An
insulation kit will be shipped with the unit.
4 The starter will ship loose. Bracket and cable kit to be
included for unit-mounted starters and/or cableway for mini-cabinet.
5 The evaporator will be insulated at the factory.
6 Refrigerant will not be shipped with the unit and must
secured locally and furnished and installed by the installer.
7 Oil will be shipped in containers from the factory for
field installation.
8 All field-piping connections will be victaulic, o-ring face
seal or copper brazing.
9 All free piping ends will be capped.
10 Touch-up paint will be included.
11 The unit will undergo the standard, rigorous, full factory
test program.
Contact local Daikin Facto schedu
ling.
Service for price quotation and
ry
Type III Knockdown
The units are shipped
fully assembled, factory charged, run­tested, insulated and painted. Included are the vessel bolt-on connection brackets, discharge line bolt
-on flanges at the condenser and bolt-on oil pump assembly. Site disassembly and reassembly must be supervised by Daikin startup personnel. Contact local Daikin Factory Service for price quotation and scheduling.
Cat 605-5 55
Retrofit Disassembly (Knockdown Options)
STARTER
COMPRESSOR
OIL PUM P
UNIT
EVAPORATOR
CONDENSER
SUPPORT
Figure 39: Knockdown Components
CONTROLLER
56 Cat 605-5
Retrofit Disassembly (Knockdown Options)
Table 21: Type I Knockdown Dimensions and Weights
UNIT
SIZE
063 E2009 / C1809 57.1 (1450.6) 61.6 (1564.4) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 5212 (2366)
063 E2209 / C2009 57.1 (1450.6) 64.0 (1624.8) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 5919 (2687)
063 E2209 / C2209 57.1 (1450.6) 64.0 (1624.8) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 6216 (2882)
063 E2609 / C2209 57.1 (1450.6) 67.5 (1715.0) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 7048 (3200)
063 E2609 / C2609 57.1 (1450.6) 73.1 (1857.8) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 7784 (3534)
063 E3009 / C2609 56.8 (1441.7) 75.7 (1922.0) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 9692 (4400)
063 E2012 / C1812 57.1 (1450.6) 61.6 (1564.4) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 6084 (2762)
063 E2212 / C2012 57.1 (1450.6) 64.0 (1624.8) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 6982 (3170)
063 E2212 / C2212 57.1 (1450.6) 64.0 (1624.8) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 7357 (3340)
063 E2612 / C2212 57.1 (1450.6) 67.5 (1715.0) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 8377 (3803)
063 E2612 / C2612 57.1 (1450.6) 73.1 (1857.8) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 9294 (4219)
063 E3012 / C2612 56.8 (1441.7) 75.7 (1922.0) 44.0 (1118.6) 25.1 (638.3) 3200 (1452) 10703 (4859)
079 E2209 / C2209 50.2 (1274.6) 62.3 (1581.7) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 6940 (3151)
079 E2609 / C2209 52.7 (1338.3) 63.9 (1622.8) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 7780 (3532)
079 E2609 / C2609 52.7 (1338.3) 69.5 (1765.6) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 8516 (3866)
079 E3009 / C2609 57.1 (1449.8) 74.0 (1878.6) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 9692 (4400)
079 E3009 / C3009 59.0 (1499.4) 79.4 (2016.8) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 10876 (4938)
079 E3609 / C3009 74.7 (1896.1) 78.8 (2001.0) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 12713 (5772)
079 E2212 / C2212 50.2 (1274.6) 62.3 (1581.7) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 8081 (3669)
079 E2612 / C2212 52.7 (1338.3) 63.9 (1622.8) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 9109 (4135)
079 E2612 / C2612 52.7 (1338.3) 69.5 (1765.6) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 10026 (4552
079 E3012 / C2612 57.1 (1449.8) 74.0 (1878.6) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 11435 (5191)
079 E3012 / C3012 59.0 (1499.4) 79.4 (2016.8) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 12919 (5865)
079 E3612 / C3012 74.7 (1896.1) 78.8 (2001.0) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 15140 (6874)
087 E2609 / C2209 52.7 (1338.3) 65.2 (1656.3) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 7780 (3532)
087 E2609 / C2609 52.7 (1338.3) 70.8 (1799.1) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 8516 (3866)
087 E3009 / C2609 57.1 (1449.8) 68.8 (1746.5) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 9692 (4400)
087 E3009 / C3009 59.5 (1510.5) 78.7 (1998.0) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 10876 (4938)
087 E3609 / C3009 74.7 (1896.1) 78.8 (2001.0) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 12713 (5772)
087 E2612 / C2212 52.7 (1338.3) 65.2 (1656.3) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 9109 (4135)
087 E2612 / C2612 52.7 (1338.3) 70.8 (1799.1) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 10029 (4553)
087 E3012 / C2612 57.1 (1449.8) 68.8 (1746.5) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 11435 (5191)
087 E3012 / C3012 59.5 (1510.5) 78.7 (1998.0) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 12918 (5865)
087 E3612 / C3012 74.7 (1896.1) 78.8 (2001.0) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 15139 (6873)
087 E3612 / C3612 80.7 (2049.3) 89.2 (2264.4) 43.6 (1108.2) 25.1 (638.3) 3200 (1452) 17384 (7892)
100 E3612 / C3012 77.2 (1961.6) 77.6 (1971.5) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 15587 (7076)
100 E3612 / C3612 83.2 (2114.0) 77.6 (1971.5) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 17826 (8093)
100 E4212 / C3612 86.2 (2190.5) 76.4 (1940.8) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 20487 (9301)
100 E4212 / C4212 92.2 (2342.9) 86.7 (2202.7) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 23298 (10577)
100 E4812 / C4212 98.2 (2495.3) 90.6 (2300.2) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 26024 (11815)
113 E3612 / C3012 77.2 (1961.6) 77.6 (1971.5) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 15578 (7072)
113 E3612 / C3612 83.2 (2114.0) 77.6 (1971.5) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 17826 (8093)
113 E4212 / C3612 86.2 (2190.5) 76.4 (1940.8) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 20457 (9287)
113
113 E4812 / C4212 98.2 (2495.3) 90.6 (2300.2) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 26024 (11815)
113 E4812 / C4812 104.2 (2647.7) 90.6 (2300.2) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 29016 (13173)
126 E3612 / C3012 77.2 (1961.6) 77.6 (1971.5) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 15680 (7119)
126 E3612 / C3612 83.2 (2114.0) 77.6 (1971.5) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 17826 (8093)
126 E4212 / C3612 86.2 (2190.5) 76.4 (1940.8) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 20457 (9287)
126 E4212 / C4212 92.2 (2342.9) 86.7 (2202.7) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 23298 (10577)
126 E4812 / C4212 98.2 (2495.3) 90.6 (2300.2) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 26024 (11815)
126 E4812 / C4812 104.2 (2647.7) 90.6 (2300.2) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 29016 (13173)
Note: All dimensions shown in inches (mm); weights are shown in lbs (kg). Allow 1 inch manufacturing tolerance on all dimensions.The overall vessel
VESSEL
CODE
E4212 / C4212 92.2 (2342.9) 86.7 (2202.7) 44.0 (1117.9) 31.5 (800.1) 6000 (2724) 23298 (10577)
dimensions may vary slightly depending on the specified tube length, pass arrangement, and configuration. Consult the Daikin certified submittal drawings, or unit dimensions beginning on page 30 for specific vess
UNIT
WIDTH
UNIT
HEIGHT
COMPRESSOR
WIDTH HEIGHT
el lengths.
COMPRESSOR
WEIGHT
SHIPPING WEIGHT
w/o COMPRESSOR
Cat 605-5 57
Specifications (WSC)
SECTION 15XXX CENTRIFUGAL CHILLERS (SINGLE COMPRESSOR)
PART 1 — GENERAL
1.1 SUMMARY
A Section includes design, performance criteria, refrigerants,
controls, and installation requirements for water-cooled centrifugal chillers.
1.2 REFERENCES
A Comply with the following codes and standards
1 AHRI 550/590
2 NEC
3 ANSI/ASHRAE 15
4 OSHA as adopted by the State
5 ASME Section VIII
1.3 SUBMITTALS
A Submittals shall include the following:
1 Dimensioned plan and elevation view drawings,
including motor starter cabinet, required clearances, and location of all field piping and electrical connections.
2 Summaries of all auxiliary utility requirements such as:
electricity, water, air, etc. Summary shall indicate quality and quantity of each required utility.
3 Diagram of control system indicating points for field
interface and field connection. Diagram shall fully depict field and factory wiring.
4 Manufacturer’s certified performance data at full load
plus IPLV or NPLV.
5 Before shipment, submit a certification of satisfactory
completion of factory run test signed by a company officer. The test shall be performed on an AHRI­qualified test stand and conducted according to AHRI Standard 550/590.
6 Installation and Operating Manuals.
1.4 QUALITY ASSURANCE
A Qualifications: Equipment manufacturer must specialize in
the manufacture of the products specified and have five years experience with the equipment and refrigerant offered.
B Regulatory Requirements: Comply with the codes and
standards in Section 1.2.
C Chiller manufacturer plant shall be ISO Registered.
1.5 DELIVERY AND HANDLING
A Chillers shall be delivered to the job site completely
assembled and charged with refrigerant and oil.
B Comply with the manufacturer’s instructions for rigging
and transporting units. Leave protective covers in place until installation.
Specifications (WSC)
1.6 WARRANTY
A The refrigeration equipment manufacturer’s warranty shall
be for a period of (one) -- OR -- (two) --Or-- (five) years from date of equipment start up or 18 months from shipment whichever occurs first. The warranty shall include parts and labor costs for the repair or replacement of defects in material or workmanship.
1.7 MAINTENANCE
A Chiller maintenance shall be the responsibility of the owner
with the following exceptions:
1 The manufacturer shall provide the first year scheduled
oil and filter change if required.
2 The manufacturer shall provide first year purge unit
maintenance if required.
PART 2 — PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
A Daikin
B (Approved Equal)
2.2 UNIT DESCRIPTION
A Provide and install as shown on the plans a factory-
assembled, factory charged water-cooled packaged chiller. Each unit shall be complete with a single-stage hermetic centrifugal compressor with lubrication and control system, factory mounted starter, evaporator, condenser, refrigerant control device and any other components necessary for a complete and operable chiller package.
B Each chiller shall be factory run-tested under load
conditions for a minimum of one hour on an AHRI qualified test stand with evaporator and condenser waterflow at job conditions (excluding glycol applications). Operating controls shall be adjusted and checked. The refrigerant charge shall be adjusted for optimum operation and recorded on the unit nameplate. Units operating with 50-Hz power shall be tested with a 50-Hz power supply. Any deviation in performance or operation shall be remedied prior to shipment and the unit retested if necessary to confirm repairs or adjustments. Manufacturer shall supply a certificate of completion of a successful run­test upon request.
C Electrical components shall be housed in NEMA 1
enclosures, designed for clean, indoor locations.
2.3 DESIGN REQUIREMENTS
A General: Provide a complete water-cooled hermetic
centrifugal compressor water-chilling package as specified herein. Machine shall be provided according to referenced standards Section 1.2. In general, unit shall consist of a compressor, condenser, evaporator, lubrication system, starter and control system. Note: Chillers shall be charged with a refrigerant such as R-134a, not subject to the Montreal Protocol and the U. S. Clean Air Act.
Cat 605-5 58
Specifications (WSC)
Sound Pressure (at 30 feet)
63
Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA
Sound Power
63 Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA
One-third Octave Band Sound Power
50Hz63Hz80Hz100HZ125Hz160Hz200Hz250Hz315Hz400Hz500Hz630Hz800Hz1000Hz1250Hz1600Hz2000Hz2500Hz3150Hz4000Hz5000Hz6300Hz8000Hz10
kHz
B Performance: Refer to schedule on the drawings. The
chiller shall be capable of stable operation to ten percent of full load with standard AHRI entering condensing water relief without the use of hot gas bypass.
C Seismic Certification:
1 Chiller shall be certified to IBC 2009.
2 Chiller shall be OSHPD Pre-Approved. Chiller to meet a
minimum seismic response factor of 1.60 S
. Chiller
DS
shall be installed as rigid base mounted only or with RIS isolators as these configurations are inherently more
stable than spring mounted installations for seismic applications.
D Acoustics: Sound pressure levels for the complete unit shall
not exceed the following specified levels. Provide the necessary acoustic treatment to chiller as required. Sound data shall be measured according to AHRI Standard 575. Data shall be in dB. Data shall be the highest levels recorded at all load points. Test shall be in accordance with AHRI Standard 575.
2.4 CHILLER COMPONENTS
A A.Compressor:
1 Unit shall have a single-stage hermetic centrifugal
compressor. Casing design shall ensure major wearing parts, main bearings, and thrust bearings are accessible for maintenance and replacement. The lubrication system shall protect machine during coast down period resulting from a loss of electrical power.
2 The impeller shall be statically and dynamically
balanced. The compressor shall be vibration tested and not exceed a level of 0.14 IPS.
3 Movable inlet guide vanes actuated by an internal oil
pressure driven piston shall accomplish unloading. Compressors using an unloading system that requires penetrations through the compressor housing or linkages, or both that must be lubricated and adjusted are acceptable provided the manufacturer provides a five­year inspection agreement consisting of semi-annual inspection, lubrication, and annual change out of any compressor seals. A statement of inclusion must accompany any quotations.
4 If the compressor is not equipped with guide vanes for
each stage and movable discharge diffusers, then furnish hot gas bypass and select chillers at 5% lower kW/ton than specified to compensate for bypass inefficiency at low loads.
5 For open motor units, an oil reservoir shall collect any oil
and refrigerant that leaks past the seal. A float device shall be provided to open when the reservoir is full, directing the refrigerant/oil mixture back into the compressor housing.
6 Manufacturer shall warrant the shaft seal, reservoir, and
float valve system against leakage of oil and refrigerant to the outside of the refrigerating unit for a period of 5 years from the initial start-up including parts and labor to replace a defective seal and any refrigerant required to trim the charge original specifications.
B Lubrication System: The compressor shall have an
independent lubrication system to provide lubrication to all parts requiring oil. Provide a heater in the oil sump to maintain oil at sufficient temperature to minimize affinity of refrigerant, and a thermostatically controlled water­cooled oil cooler. Coolers located inside the evaporator or condenser are not acceptable due to inaccessibility. A positive displacement oil pump shall be powered through the unit control transformer.
C Refrigerant Evaporator and Condenser:
1 Evaporator and condenser shall be of the shell-and-tube
type, designed, constructed, tested and stamped according to the requirements of the ASME Code, Section VIII. Regardless of the operating pressure, the refrigerant side of each vessel will bear the ASME stamp indicating compliance with the code and indicating a test pressure of 1.1 times the working pressure, but not less
59 Cat 605-5
Specifications (WSC)
than 100 psig. Provide intermediate tube supports at a maximum of 24 inch spacing.
2 Tubes shall be enhanced for maximum heat transfer,
rolled into steel tube sheets and sealed with Locktite or equal sealer. The tubes shall be individually replaceable.
3 The water sides shall be designed for a minimum of 150
psi or as specified elsewhere. Vents and drains shall be provided.
4 Evaporator minimum refrigerant temperature shall be
33F.
5 An electronic or thermal refrigerant expansion valve
shall control refrigerant flow to the evaporator. Fixed orifice devices or float controls with hot gas bypass are not acceptable because of inefficient control at low load conditions. The liquid line shall have a moisture indicating sight glass.
6 The evaporator and condenser shall be separate shells. A
single shell containing both vessel functions is not acceptable because of the possibility of internal leaks.
7 Reseating type spring loaded pressure relief valves
according to ASHRAE-15 safety code shall be furnished. The evaporator shall be provided with single or multiple valves. The condenser shall be provided with dual relief valves equipped with a transfer valve so one valve can be removed for testing or replacement without loss of refrigerant or removal of refrigerant from the vessel. Rupture disks are not acceptable.
8 The evaporator, suction line, and any other component or
part of a component subject to condensing moisture shall be insulated with UL recognized 3/4 inch closed cell insulation. All joints and seams shall be carefully sealed to form a vapor barrier.
9 Provide factory-mounted thermal dispersion flow
switches on each vessel to prevent unit operation with no flow.
D Prime Mover: Squirrel cage induction motor of the
hermetic type of sufficient size to efficiently fulfill compressor horsepower requirements. Motor shall be liquid refrigerant cooled with internal thermal overload protection devices embedded in the winding of each phase. Motor shall be compatible with the starting method specified hereinafter. If the Contractor chooses to provided an open drive motor or compressor, verify in the submittal that the scheduled chiller room ventilation system will accommodate the additional heat and maintain the equipment room at design indoor temperature based on 95F outdoor ambient ventilation air available. If additional cooling is required, manufacturer shall be responsible for the installation, wiring and controls of a cooling system. Chi
ller selection shall compensate for tonnage and
ficiency loss to make certain the owner is not penalized.
ef
E Motor Starter:
1 The main motor starter is to be factory mounted and fully
wired to the chiller components and factory tested during the run test of the unit.
-- OR --
The main motor starter is to be furnished by the chiller manufacturer and shipped loose for floor mounting and field wiring to the chiller package. It shall be free-standing with NEMA-1 enclosure designed for top entry and bottom exit and with front access.
2 For open drive air-cooled motors the chiller
manufacturer shall be responsible for providing the cooling of the refrigeration machinery room. The sensible cooling load shall be based on the total heat rejection to the atmosphere from the refrigeration units.
3 The starter must comply with the codes and standards in
Section 1.2.
4 Low Voltage (200 through 600 volts) controllers are to
be continuous duty AC magnetic type constructed according to NEMA standards for Industrial Controls and Systems (ICS) and capable of carrying the specified current on a continuous basis. The starters shall be:
Solid-State Reduced Voltage
- Starters shall be furnished with silicon controlled rectifiers (SCR) connected for starting and include a bypass contactor. When operating speed is reached, the bypass contactor shall be energized removing the SCRs from the cir­cuit during normal running.
-- OR --
Wye-Delta Closed Transition
- The starter s shall be equipped with properly sized resistors to provide a smooth transition. The resistors shall be protected with a transition resistor protector, tripping in a maximum of two seconds, locking out the starter, and shall be manually reset. A clearly marked tran­sition timer shall be adjustable from 0 to 30 seconds or a current sensing devise shall initiate transition when starting current drops to 90% of RLA.
a All starters shall be coordinated with the chiller
package(s) making certain all terminals are properly marked according to the chiller manufacturer’s wiring diagrams.
b The starters shall be equipped with redundant motor
control relays (MCR). The relays shall interconnect the starters with the unit control panels and directly operate the main motor contactors. The MCRs shall constitute the only means of energizing the motor starter.
c The main contactors shall have a normally open and a
normally closed auxiliary contact rated at 125VA pilot duty at 115 VAC. An additional set of normally open contacts shall be provided for each MCR.
Cat 605-5 60
Specifications (WSC)
d There shall be electronic overloads in each phase
which will permit continuous operation at 107% of the rated load amps of each motor. The overloads shall have a must-trip setting at 125% of the RLA. Overloads shall be manual reset and shall de-energize the main contactors when the overcurrent occurs. The overloads shall be adjustable and selected for mid­range. Overloads shall be adjustable, manual reset, ambient compensated, and set for class 10 operation.
e Each starter shall have a current transformer and
adjustable voltage dropping resistor(s) to supply a 5.0 VAC signal at full load to the unit control panels.
f Each starter shall be equipped with a line to 115 VAC
control transformer, fused in both the primary and secondary, to supply power to the control panels, oil heaters and oil pumps.
g Each starter shall include phase failure, phase
undervoltage and phase reversal protection.
-- OR --
Variable Frequency Drive
a The chiller shall be equipped with a Variable Frequency
Drive (VFD)
to automatically regulate each compressor speed in response to cooling load and compressor pressure lift. The chiller control shall coordinate compressor speed and guide vane position to optimize chiller efficiency. b The VFD and options are UL
tm
508A listed. The drive and options are designed to comply with the applicable requirement of the latest standards of ANSI, NEMA, National Electric Code NEC, and FCC Part 15 Subpart J. c The VFD shall have 110% continuous overload of continuous amp rating with no time limit, PWM (pulse width modulated) output, IGBT (insulated gate bipolar transistors) power technology and full power rating at 2kHz, DC bus inductor (choke), and wireless construction. d The VFD has the following basic features:
e. The VFD includes the following
protective circuits and
features:
i. Output phase-to-phase short circuit condition ii. Total ground fault protection under
any operating
condition.
iii. High input line voltage detection. iv. Low input line voltage detection. v. Loss of input or output phase.
vi. External fault. (This protective circuit shall permit wiring of remote a NC safety contact to shut down the drive).
vii. Metal oxide varistors for surge suppression at the VFD input terminals.
viii. Maintenance counters (6)
ix. External Start Interlocks
x. Communication loss
xi.
Keypad Communication loss xii. Motor Stall Detection xiii. Auto Fault Reset
-- OR --
4 Medium Voltage (601 through 7200 volts). The starter
shall be:
Solid-State Reduced Voltage
- Starter shall be furnished with silicon controlled rectifiers (SCR) connected for start­ing and include a bypass contactor. When operating speed is reached, the bypass contactor shall be energized remov­ing the SCRs from the circuit during normal running.
a The starter shall be coordinated with the chiller
package(s) making certain all terminals are properly marked according to the chiller manufacturer’s wiring diagrams.
b The starters shall be equipped with redundant motor
control relays (MCR). The relays shall interconnect the starters with the unit control panels and directly
.
i. An
overload
circuit
to
protect an AC motor operated
by the VFD output from extended overload operation on an
time basis.
inverse
ii. 0.98 power
factor at full
load and provides power
factor correction at lighter loads
iii. An LCD Keypad display
1. Frequency output
2. Voltage output
3. Motor Current
4. % current
5. Output kW
6. Fault log of 16 most recent faults
iv. 3% minimum impedance AC line reactor v. Fan cooled drives and cabinet vi. Molded case disconnect with fusing or CB
disconnect
61 Cat 605-5
with fusing
vii. 100,000 amp
interrupting capacity
operate the main motor contactors. The MCRs shall constitute the only means of energizing the motor contacts.
c The main contactors shall have a normally open
auxiliary contact rated at 125VA pilot duty at 115 VAC. An additional set of normally open contacts shall be provided on the MCR.
d There shall be electronic overloads in each phase set
at 107% of the rated load amps of each motor. Overloads shall be manual reset and shall de-energize the main contactors when the overcurrent occurs. The overloads shall be adjustable and selected for mid­range. Overloads shall be adjusted for a locked rotor trip time of 8 seconds at full voltage and must trip in 60 seconds or less at reduced voltage (33% of delta LRA).
Specifications (WSC)
e Each starter shall have a current transformer and
adjustable voltage dropping resistor(s) to supply a 5.0 VAC signal at full load to the unit control panels.
f Each starter shall be equipped with a line-to-115 VAC
control transformer, fused in both the primary and secondary, to supply power to the control panels, oil heaters and oil pumps.
g Each starter shall include phase under/over voltage
protection, phase failure and reversal protection, a load break disconnect switch and current limiting power fuses
-- OR --
Across-the-Line
type with primary contactor allowing
locked rotor amps to reach the motor when energized and including items 1 through 7 above
-- OR --
Autotransformer
type factory wired to the 65% tap with drawout magnetic, three-pole, vacuum break shorting con­tactor, drawout magnetic, two-pole, vacuum break starting contactor, and open delta starting auto-transformer factory set at 65% and including items 1 through7 above with a iso­lating safety switch in lieu of a load-break disconnect switch.
-- OR --
Primary Reactor
type with drawout magnetic, three-pole, vacuum break shorting assembly, and three-phase starting reactor, factory set at the 65% tap and including items 1 through7 above with a isolating safety switch in lieu of a load-break disconnect switch.
All medium and higher voltage starters shall have the fol­lowing components:
Main Control Relays
A motor control relay shall be provided to interlock the starter with the chiller. The relay shall constitute the only means of energizing the motor starter. No other devices (manual or automatic) with the capability of energizing the starter can be used. The starter is to be controlled by the unit microprocessor.
Motor Protection and Overloads
The starter shall include overload protection functions. These controls include:
• Solid state overload (overcurrent) protection
• Phase unbalance protection
• Phase reversal and phase loss protection.
• Adjustable overload to closely match motor performance
• Three current transformers to measure motor current and a fourth current transformer for input to the chiller microprocessor.
Undervoltage (UV) Relay
The undervoltage relay is an adjustable three-phase protec­tion system that is activated when the voltage falls below a predetermined safe value and is factory set at 85% of nomi­nal.
Control Voltage Transformer
The starter is to be provided with a 3KVA control trans­former with both secondary and primary fuses to supply control power to the chiller.
Additional Standard Components
• Mechanical type solderless connectors to hand
le wire
sizes indicated by NEC.
• Three isolated vertical line contactors
• Three-pole, gang operated non-load break isolating switch
• Three vertically mounted current limiting power fuse blocks (fuses included)
• Magnetic three-pole, vacuum break contactor
• Single phase control circuit transformer
• Vertically mounted control circuit primary current limit­ing fuses
• Current transformers
• Control circuit terminal blocks and secondary fuses
• Phase failure and reversal relay
F Chiller Controller
1 Control enclosures shall be NEMA 1. The chiller shall
have distributed control consisting of a unit controller, a compressor controller and a 15-inch super VGA color touch screen for operator interface with the control system.
The touch screen shall have graphics clearly depicting the
chiller status, operating data, including water tempera­tures, percent RLA, water setpoint, alarm status and have STOP and AUTO control buttons.
The operator interface touch screen shall have inherent
trend logging capabilities, which are transferable to other PC management systems such as an Excel spreadsheet via a USB port. Active trend logging data shall be avail­able for viewing in 20 minute, 2 hour or 8 hour intervals. A full 24 hours of history is downloadable via a USB port. The following trended parameters shall be dis­played:
62
Cat 605-5
Specifications (WSC)
• Entering and leaving chilled water temps
• Entering and leaving condenser water temps
• Evaporator saturated refrigerant pressure
• Condenser saturated refrigerant pressure
• Net oil pressure
• % rated load amps In addition to the trended items above, other real-time oper­ating parameters are also shown on the touch screen. These items can be displayed in two ways: by chiller graphic showing each component or from a color-coded, bar chart format. At a minimum, the following critical areas must be monitored:
• Oil sump temperature
• Oil feed line temperature
• Evaporator saturated refrigerant temperature
• Suction temperature
• Condenser saturated refrigerant temperature
• Discharge temperature
• Liquid line temperature Unit setpoints shall be viewable on screens and changeable after insertion of a password. Complete unit operating and maintenance instructions shall be viewable on the touch screen and be downloadable via an onboard USB port. Automatic corrective action to reduce unnecessary cycling shall be accomplished through pre-emptive control of low evaporator or high discharge pressure conditions to keep the unit operating through ancillary transient conditions. System specific, chiller plant architecture software shall be employed to display the chiller, piping, pumps and cooling tower. Multi-chiller interconnection software for up to 4 WSC or WDC chillers shall be included also providing automatic control of: evaporator and condenser pumps (pri­mary and standby), up to 4 stages of cooling tower fans and a cooling tower modulating bypass valve and/or cooling tower fan variable frequency drives. There shall be five possible tower control strategies:
• Tower fan staging only – up to 4 stages controll
ed by either the entering condenser water temperature or lift dif
ferential temperature between the conden
ser and
evaporator saturated temperatures.
• Tower fan staging plus low limit - controlled as in # 1 plus tower bypass valve set at a minimum entering con­denser water temperature
• Tower staging with staged bypass control – similar to # 2 with additional control of the bypass valve between fan staging to smooth control and minimize fan staging.
• VFD staging only – in this mode, a variable
speed drive controls the first fan with up to 3 more fans to be staged on and off and there is no bypass valve.
• VFD and Valve Staging – same as # 4 plus bypass valve control
Factory mounted DDC controller(s) shall support operation on a BACnet®, Modbus® or LONMARKS ® network via one of the data link / physical layers listed below as speci­fied by the successful Building Automation System (BAS) supplier.
• BACnet MS/TP master (Clause 9)
• BACnet IP, (Annex J)
• BACnet ISO 8802-3, (Ethernet)
• LONMARKS FTT-10A. The unit controller shal
l be
LONMARKS® certified. The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring, control and alarm notification as specified in the unit sequence of oper­ation and the unit points list. eXternal Interface File (XIF) shall be provided with the chiller submittal data. All communication from the chiller unit controller as speci­fied in the points list shall be via standard BACnet objects. Proprietary BACnet objects shall not be allowed. BACnet communications shall conform to the BACnet protocol (ANSI/ASHRAE135-2001). A BACnet Protocol Imple­mentation Conformance Statement (PICS) shall be pro­vided along with the unit submittal.
2.5. MISCELLANEOUS ITEMS
A Pumpout System: If the design of the unit does not allow
the charge to be transferred to and isolated in the main condenser, it shall be equipped with an ASME pumpout system complete with a transfer pump, condensing unit, and storage vessel . The main condenser shall be sized to contain the refrigerant charge at 90F according to ANSI­ASHRAE 15.A.
B Purge System (Negative Pressure Chillers Only):
1 The chiller manufacturer shall provide a separate high
efficiency purge system that operates independently of
the unit and can be operated while the unit is off. The
system shall consist of an air-cooled condensing unit,
purge condensing tank, pumpout compressor and control
system.
2 A dedicated condensing unit shall be provided with the
purge system to provide a cooling source whether or not the chiller is running. The condensing unit shall provide a low purge coil temperature to result in a maximum loss of 0.1 pounds of refrigerant per pound of purged air.
3 The purge tank shall consist of a cooling coil, filter-drier
cores, water separation tube, sight glass, drain, and air discharge port. Air and water are separated from the refrigerant vapor and accumulated in the purge tank.
4 The pumpout system shall consist of a small compressor
and a restriction device located at the pumpout compressor suction connection.
5 The purge unit shall be connected to a 100% reclaim
device.
Cat 605-5 63
Specifications (WSC)
C C.Vacuum Prevention System (negative pressure chillers
only): Chiller manufacturer shall supply and install a vacuum prevention system for each chiller. The system shall constantly maintain 0.05 psig inside the vessel during non-operational periods. The system shall consist of a precision pressure controller, two silicon blanket heaters, a pressure transducer, and solid-state safety circuit.
D D.Refrigerant Detection Device (negative pressure chillers
only): Chiller manufacturer shall supply and install a refrigerant detection device and alarm capable of monitoring refrigerant at a level of 10 ppm. Due to the critical nature of this device and possible owner liability, the chiller manufacturer shall guarantee and maintain the detection monitor for five years after owner acceptance of the system.
E E.Waffle type vibration pads for field mounting under unit
feet.
F IBC Certification: The chiller shall be certified to the
following codes and standards; 2009 IBC, 2010 CBC, ICC­ES AC-156, ASCE 7-05. The chiller must be mounted to a rigid base and may use neoprene waffle vibration pads.
G OSHPD Certification: The chiller shall be OSHPD Pre-
Approved per OSP-0116-10 and be so labeled. The chiller shall meet a minimum seismic design spectral response acceleration of 1.60 S
rigid base and may use neoprene waffle vibration pads.
. The chiller must be mounted to a
DS
PART 3 — EXECUTION
3.1 INSTALLATION
A Install according to manufacturer’s requirements, shop
drawings, and Contract Documents.
B Adjust chiller alignment on concrete foundations, sole
plates or subbases as called for on drawings.
C Arrange the piping on each vessel to allow for dismantling
the pipe to permit head removal and tube cleaning.
D Furnish and install necessary auxiliary water piping for oil
cooler.
E Coordinate electrical installation with electrical contractor.
F Coordinate controls with control contractor.
G Provide all materiel required to ensure a fully operational
and functional chiller.
3.2 START-UP
A Units shall be factory charged with the proper refrigerant
and oil.
B Factory Start-Up Services: The manufacturer shall provide
factory authorized supervision for as long a time as is necessary to ensure proper operation of the unit, but in no case for less than two full working days. During the period of start-up, the start-up technician shall instruct the owner’s representative in proper care and operation of the unit.
64 Cat 605-5
Specifications (WDC)
SECTION 15XXX CENTRIFUGAL CHILLERS (DUAL COMPRESSOR)
PART 1 — GENERAL
1.1 SUMMARY
A Section includes design, performance criteria, refrigerants,
controls, and installation requirements for water-cooled centrifugal chillers.
1.2 REFERENCES
A Comply with the following codes and standards
1 AHRI 550/590
2 NEC
3 ANSI/ASHRAE 15
4 OSHA as adopted by the State
5 ASME Section VIII
Specifications (WDC)
1.6 WARRANTY
A The refrigeration equipment manufacturer’s warranty shall
be for a period of (one) -- OR -- (two) --Or-- (five) years from date of equipment start up or 18 months from shipment whichever occurs first. The warranty shall include parts and labor costs for the repair or replacement of defects in material or workmanship. [WDC: The refrigerant charge shall be warranted against contamination from a motor burnout for five years.]
1.7 MAINTENANCE
A Chiller maintenance shall be the responsibility of the owner
with the following exceptions:
1 The manufacturer shall provide the first year scheduled
oil and filter change if required.
2 The manufacturer shall provide first year purge unit
maintenance if required.
1.3 SUBMITTALS
A Submittals shall include the following:
1 Dimensioned plan and elevation view drawings,
including motor starter cabinet, required clearances, and location of all field piping and electrical connections.
2 Summaries of all auxiliary utility requirements such as:
electricity, water, air, etc. Summary shall indicate quality and quantity of each required utility.
3 Diagram of control system indicating points for field
interface and field connection. Diagram shall fully depict field and factory wiring.
4 Manufacturer’s certified performance data at full load
plus IPLV or NPLV.
5 Before shipment, submit a certification of satisfactory
completion of factory run test signed by a company officer. The test shall be performed on an AHRI­qualified test stand and conducted according to AHRI Standard 550/590.
6 Installation and Operating Manuals.
1.4 QUALITY ASSURANCE
A Qualifications: Equipment manufacturer must specialize in
the manufacture of the products specified and have five years experience with the equipment and refrigerant offered.
B Regulatory Requirements: Comply with the codes and
standards in Section 1.2.
C Chiller manufacturer plant shall be ISO Registered.
PART 2 — PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
A Daikin
B (Approved Equal)
2.2 UNIT DESCRIPTION
Provide and install as shown on the plans a factory assem­bled, charged water-cooled packaged chiller. Each unit shall be complete with two single-stage hermetic centrifu­gal compressors each having independent lubrication and control systems, factory mounted starters, and isolation valves. The evaporator, condenser, and refrigerant control device of each unit shall be common to the compressors. The chiller unit shall be capable of running on one com­pressor with the other compressor or any of its auxiliaries removed. Each chiller shall be factory run-tested under load condi­tions for a minimum of one hour on an AHRI qualified test stand with evaporator and condenser waterflow at job con­ditions (excluding glycol applications). Operating controls shall be adjusted and checked. The refrigerant charge shall be adjusted for optimum operation and recorded on the unit nameplate. Units operating with 50-Hz power shall be tested with a 50-Hz power supply. Any deviation in perfor­mance or operation shall be remedied prior to shipment and the unit retested if necessary to confirm repairs or adjust­ments. Manufacturer shall supply a certificate of comple­tion of a successful run-test upon request. Electrical components shall be housed in NEMA 1 enclo­sures, designed for clean, indoor locations.
1.5 DELIVERY AND HANDLING
A Chillers shall be delivered to the job site completely
assembled and charged with refrigerant and oil.
B Comply with the manufacturer’s instructions for rigging
and transporting units. Leave protective covers in place until installation.
Cat 605-5 65
2.3 DESIGN REQUIREMENTS
A General: Provide a complete water-cooled dual hermetic
compressor centrifugal water chiller as specified herein. Machine shall be provided according to standards, Section
1.2. In general, unit shall consist of two compressors, refrigerant condenser and evaporator, two lubrication
Specifications (WDC)
Sound Pressure (at 30 feet)
63
Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA
Sound Power
63 Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA
One-third Octave Band Sound Power
50Hz63Hz80Hz100HZ125Hz160Hz200Hz250Hz315Hz400Hz500Hz630Hz800Hz1000Hz1250Hz1600Hz2000Hz2500Hz3150Hz4000Hz5000Hz6300Hz8000Hz10
kHz
systems, two starters and two control systems. Note: Chillers shall be charged with a refrigerant such as HFC-134a, not subject to the Montreal Protocol and the U. S. Clean Air Act.
B Performance: Refer to schedule on the drawings. The
chiller shall be capable of stable operation to five percent of full load with standard AHRI entering condensing water relief without hot gas bypass.
C Acoustics: Sound pressure for the unit shall not exceed the
following specified levels. Provide the necessary acoustic treatment to chiller as required. Sound data shall be measured according to AHRI Standard 575 and shall be in dB. Data shall be the highest levels recorded at all load points. Test shall be in accordance with AHRI Standard
575.
2.4 CHILLER COMPONENTS
A A.Compressors:
1 Unit shall have two single-stage hermetic centrifugal
compressors. Casing design shall ensure major wearing parts, main bearings and thrust bearings are accessible for maintenance and replacement. Lubrication system shall protect machine during coast down resulting from a
compressor housing. Manufacturer shall warrant the shaft seal, reservoir, and float valve system against leakage of oil and refrigerant to the outside of the refrigerating unit for a period of 5 years from the initial start-up including parts and labor to replace a defective seal and any refrigerant required to trim the charge original specifications.
loss of power.
B Lubrication System: Each compressor shall have an
independent lubrication system to provide lubrication to all parts requiring oil. Provide a heater in the oil sump to maintain oil at sufficient temperature to minimize affinity of refrigerant, and a thermostatically controlled water­cooled oil cooler. Coolers located inside the evaporator or condenser are not acceptable due to inaccessibility. A positive displacement submerged oil pump shall be powered through the unit control transformer.
C Refrigerant Evaporator and Condenser:
1 The evaporator and condenser shall be single circuit and
be of the shell-and-tube type, designed, constructed, tested and stamped according to the requirements of the ASME Code, Section VIII. Regardless of the operating pressure, the refrigerant side of each vessel will bear the ASME stamp indicating compliance with the code and indicating a test pressure of 1.1 times the working pressure but not less than 100 psig. Provide intermediate tube supports at a maximum of 18 inch spacing.
2 Tubes shall be enhanced for maximum heat transfer,
rolled into steel tube sheets and sealed with Locktite or
2 Impellers shall be statically and dynamically balanced.
The compressor shall be vibration tested and not exceed
0.14 IPS.
3 Movable inlet guide vanes actuated by an internal oil
pressure driven piston shall accomplish unloading. Compressors using an unloading system that requires penetrations of the compressor housing or linkages, or both, that must be lubricated and adjusted are acceptable provided the manufacturer provides a five-year inspection agreement consisting of semi-annual inspection, lubrication, and annual changeout of compressor seals. A statement of inclusion must accompany any quotations.
4 If compressors are not equipped with guide vanes for
each stage and movable discharge diffusers, then furnish hot gas bypass and select chillers at 5% lower kW/ton than specified to compensate for bypass inefficiency at low loads.
5 For open motor unit, an oil reservoir shall collect any oil
and refrigerant that leaks past the seal. A float device shall be provided to open when the reservoir is full, directing the refrigerant/oil mixture back into the
66 Cat 605-5
Specifications (WDC)
equal sealer. The tubes shall be individually replaceable and secured to the intermediate supports without rolling.
3 The water sides shall be designed for a minimum of 150
psig or as specified elsewhere. Vents and drains shall be provided.
4 Chilled water minimum refrigerant temperature shall be
33F.
5 An electronic or thermal refrigerant expansion valve
shall control refrigerant flow to the evaporator. Fixed orifice devices or float controls with hot gas bypass are not acceptable because of inefficient control at low load conditions. The liquid line shall have a moisture indicating sight glass.
6 The evaporator and condenser shall be separate shells. A
single shell containing both vessel functions is not acceptable because of the possibility of internal leaks.
7 Interstage economizers shall be used between each
compressor stage for increased efficiency.
8 Reseating type spring loaded pressure relief valves
according to ASHRAE-15 safety code shall be furnished. The evaporator shall be provided with single or multiple valves. The condenser shall be provided with dual relief valves equipped with a transfer valve so one valve can be removed for testing or replacement without loss of refrigerant or removal of refrigerant from the vessel. Rupture disks are not acceptable.
9 The evaporator, suction line, and any other component or
part of a component subject to condensing moisture shall be insulated with UL recognized 3/4 inch closed cell insulation. All joints and seams shall be carefully sealed to form a vapor barrier.
10 Provide Factory-mounted thermal dispersion flow
switches on each vessel to prevent unit operation with no flow, furnished, installed and wired by the contractor.
D Prime Mover: Squirrel cage induction motor of the
hermetic type of sufficient size to efficiently fulfill compressor horsepower requirements. Motor shall be liquid refrigerant cooled with internal thermal overload protection devices embedded in the winding of each phase. Motor shall be compatible with the starting method specified hereinafter. If the Contractor chooses to provided an open drive motor or compressor, verify in the submittal that the scheduled chiller room ventilation system will accommodate the additional heat and maintain the equipment room at design indoor temperature based on 95F outdoor ambient ventilation air available. If additional cooling is required, manufacturer shall be responsible for the installation, wiring and controls of a cooling system. Chiller selection shall compensate for tons and efficiency loss to make certain the owner is not penal­ized.
E E.Motor Starter:
1 The main motor starter is to be factory mounted and fully
wired to the chiller components and factory tested during the run test of the unit.
-- OR -­The main motor starter is to be furnished by the chiller manufacturer and shipped loose for floor mounting and field wiring to the chiller package. It shall be free-standing with NEMA-1 enclosure designed for top entry and bottom exit and with front access.
2 For open drive air-cooled motors the chiller
manufacturer shall be responsible for providing the
cooling of the refrigeration machinery room. The
sensible cooling load shall be based on the total heat
rejection to the atmosphere from the refrigeration units.
3 The starter must comply with the codes and standards in
Section 1.2.
4 Low Voltage (200 through 600 volts) controllers are to
be continuous duty AC magnetic type constructed
according to NEMA standards for Industrial Controls
and Systems (ICS) and capable of carrying the specified
current on a continuous basis. The starters shall be:
Solid-State Reduced Voltage
- Starters shall be fur­nished with silicon controlled rectifiers (SCR) connected for starting and include a bypass contactor. When operat­ing speed is reached, the bypass contactor shall be ener­gized removing the SCRs from the circuit during normal running.
-- OR -­Wye-Delta Closed Transition
- The starter s shall be equipped with properly sized resistors to provide a smooth transition. The resistors shall be protected with a transition resistor protector, tripping in a maximum of two seconds, locking out the starter, and shall be manu­ally reset. A clearly marked transition timer shall be adjustable from 0 to 30 seconds or a current sensing devise shall initiate transition when starting current drops to 90% of RLA.
a All starters shall be coordinated with the chiller
package(s) making certain all terminals are properly marked according to the chiller manufacturer’s wiring diagrams.
b The starters shall be equipped with redundant motor
control relays (MCR). The relays shall interconnect the starters with the unit control panels and directly operate the main motor contactors. The MCRs shall constitute the only means of energizing the motor starter.
c The main contactors shall have a normally open and a
normally closed auxiliary contact rated at 125VA
pilot duty at 115 VAC. An additional set of normally open contacts shall be provided for each MCR.
Cat 605-5 67
Specifications (WDC)
d There shall be electronic overloads in each phase
which will permit continuous operation at 107% of the rated load amps of each motor. The overloads shall have a must-trip setting at 125% of the RLA. Overloads shall be manual reset and shall de-energize the main contactors when the overcurrent occurs. The overloads shall be adjustable and selected for mid­range. Overloads shall be adjustable, manual reset, ambient compensated, and set for class 10 operation.
e Each starter shall have a current transformer and
adjustable voltage dropping resistor(s) to supply a 5.0 VAC signal at full load to the unit control panels.
f Each starter shall be equipped with a line to 115 VAC
control transformer, fused in both the primary and secondary, to supply power to the control panels, oil heaters and oil pumps.
g Each starter shall include phase failure, phase
undervoltage and phase reversal protection.
-OR-
Variable Frequency Drive
a The chiller shall be equipped with a Variable Frequency
Drive (VFD) to automatically regulate each compressor speed in response to cooling load and compressor pressure lift. The chiller control shall coordinate compressor speed
guide vane position to optimize chiller efficiency.
and b The VFD and options are UL
tm
508A listed. The drive and options are designed to comply with the applicable requirement of the latest standards of ANSI, NEMA, National Electric Code NEC, and FCC Part 15 Subpart J. c The VFD shall have 110% continuous overload of continuous amp rating with no time limit, PWM (pulse width modulated) output, IGBT (insulated gate bipolar transistors) power technology and full power rating at 2kHz, DC bus inductor (choke), and wireless construction. d The VFD has the following basic features:
by
the VFD
i. An
output
overload
from extended overload operation on an
circuit
to
protect
an
motor operated
AC
inverse time basis.
ii. 0.98 power factor at full load and provides power
factor correction at lighter loads
iii. An LCD Keypad display
1. Frequency output
2. Voltage output
3. Motor Current
4. % current
5. Output kW
6. Fault log of 16
iv. 3% minimum impedance AC line
most recent faults
reactor v. Fan cooled drives and cabinet vi. Molded case disconnect with fusing or C
B
disconnect with fusing
vii. 100,000 amp interrupting
capacity
e. The VFD includes the following protective circuits and features:
i. Output phase-to-phase short circuit
condition.
ii. Total ground fault protection under any operating
condition.
iii. High input line voltage detection. iv. Low input line voltage detection. v. Loss of input or output phase.
vi. External fault. (This protective circuit shall permit wiring of remote a NC safety contact to shut down the drive).
vii. Metal oxide varistors for surge suppression at the VFD input terminals.
viii. Maintenance counters (6)
ix. External Start Interlocks
x. Communication loss
xi. Keypad Communication loss
xii. Motor Stall Detection
xiii. Auto Fault Reset
-- OR --
4 Medium Voltage (601 through 7200 volts).
The starter shall be:
Solid-State Reduced Voltage
- Starter shall be furnished with silicon controlled rectifiers (SCR) connected for start­ing and include a bypass contactor. When operating speed is reached, the bypass contactor shall be energized remov­ing the SCRs from the circuit during normal running.
a The starter shall be coordinated with the chiller
package(s) making certain all terminals are properly marked according to the chiller manufacturer’s wiring diagrams.
b The starters shall be equipped with redundant motor
control relays (MCR). The relays shall interconnect the starters with the unit control panels and directly operate the main motor contactors. The MCRs shall constitute the only means of energizing the motor contacts.
c The main contactors shall have a normally open
auxiliary contact rated at 125VA pilot duty at 115 VAC. An additional set of normally open contacts shall be provided on the MCR.
d There shall be electronic overloads in each phase set
at 107% of the rated load amps of each motor. Overloads shall be manual reset and shall de-energize the main contactors when the overcurrent occurs. The overloads shall be adjustable and selected for mid­range. Overloads shall be adjusted for a locked rotor trip time of 8 seconds at full voltage and must trip in 60 seconds or less at reduced voltage (33% of delta LRA).
68
Cat 605-5
Specifications (WDC)
e Each starter shall have a current transformer and
adjustable voltage dropping resistor(s) to supply a 5.0 VAC signal at full load to the unit control panels.
f Each starter shall be equipped with a line-to-115 VAC
control transformer, fused in both the primary and secondary, to supply power to the control panels, oil heaters and oil pumps.
g Each starter shall include phase under/over voltage
protection, phase failure and reversal protection, a load break disconnect switch and current limiting power fuses
-- OR --
Across-the-Line
locked rotor amps to reach the motor when energized and including items 1 through 7 above
-- OR --
Autotransformer
drawout magnetic, three-pole, vacuum break shorting con­tactor, drawout magnetic, two-pole, vacuum break starting contactor, and open delta starting auto-transformer factory set at 65% and including items 1 through7 above with a iso­lating safety switch in lieu of a load-break disconnect switch.
-- OR --
Primary Reactor
vacuum break shorting assembly, and three-phase starting reactor, factory set at the 65% tap and including items 1 through7 above with a isolating safety switch in lieu of a load-break disconnect switch. All medium and higher voltage starters shall have the fol­lowing components:
Main Control Relays
A motor control relay shall be provided to interlock the starter with the chiller. The relay shall constitute the only means of energizing the motor starter. No other devices (manual or automatic) with the capability of energizing the
starter can be used. The starter is to be controlled by the unit microprocessor.
Motor Protection and Overloads
The starter shall include overload protection functions. These controls include:
• Solid state overload (overcurrent) protect
• Phase unbalance protection
• Phase reversal and phase loss protection.
• Adjustable overload to closely match motor performance
• Three current transformers to measure motor current and a fourth current transformer for input to the chiller microprocessor.
type with primary contactor allowing
type factory wired to the 65% tap with
type with drawout magnetic, three-pole,
ion
Undervoltage (UV) Relay
The undervoltage relay is an adjustable three-phase protec­tion system that is activated when the voltage falls below a predetermined safe value and is factory set at 85% of nomi­nal.
Control Voltage Transformer
The starter is to be provided with a 3KVA control trans­former with both secondary and primary fuses to supply control power to the chiller.
Additional Standard Components
• Mechanical type solderless connectors to hand sizes indicated by NEC.
• Three isolated vertical line contactors
• Three-pole, gang operated non-load break isolating switch
• Three vertically mounted current limiting power fu blocks (fuses included)
• Magnetic three-pole, vacuum break contactor
• Single phase control circuit transformer
• Vertically mounted control circuit primary current limit­ing fuses
• Current transformers
• Control circuit terminal blocks and secondary fuses
• Phase failure and reversal relay
F CHILLER CONTROLLER
The chiller shall have distributed control consisting of a unit controller, a compressor controller for each compres­sor and a 15-inch super VGA color touch screen for opera­tor interface with the control system. The touch screen shall have graphics clearly depicting the chiller status, operating data, including water temperatures, percent RLA, water setpoint, alarm status and have STOP and AUTO control buttons. The operator interface touch screen shall have inherent trend logging capabilities, which are transferable to other PC management systems such as an Excel spreadsheet via a USB port. Active trend logging data shall be available for viewing in 20 minute, 2 hour or 8 hour intervals. A full 24 hours of history is downloadable via a USB port. The fol­lowing trended parameters shall be displayed:
ntering and leaving chilled water temps
• E
• Entering and leaving condenser water temps
• Evaporator saturated refrigerant pressure
• Condenser saturated refrigerant pressure
• Net oil pressure for each compressor
• % rated load amps for entire unit
le wire
se
69
Cat 605-5
Specifications (WDC)
In addition to the trended items above, other real-time oper­ating parameters are also shown on the touch screen. These items can be displayed in two ways: by chiller graphic showing each component or from a color-coded, bar chart format. At a minimum, the following critical areas must be monitored:
• Oil sump temperature per compressor
• Oil feed line temperature per compressor
• Evaporator saturated refrigerant temperature for unit
• Suction temperature for unit
• Condenser saturated refrigerant temperature for unit
• Discharge temperature for unit
• Liquid line temperature for unit The unit operating and maintenance instructions shall be viewable on the touch screen and downloadable via an onboard USB port. Complete fault history shall be displayed using an easy to decipher, color coded set of messages that are date and time stamped. The last 20 faults shall be downloadable from the USB port. Automatic corrective action to reduce unnecessary cycling shall be accomplished through pre-emptive control of low evaporator or high discharge pressure conditions to keep the unit operating through ancillary transient conditions. System specific, chiller plant architecture software shall be employed to display the chiller, piping, pumps and cooling tower. Chiller interconnection softw for up to 4 WSC or WDC chillers shall be included also providing automatic control of: evaporator and condenser pumps (primary and standby), up to 4 stages of cooling tower fans and a cooling tower modulating bypass valve or cooling tower variable frequency drives. There shall be five possible tower control strategies:
• Tower fan staging only – up to 4 stages controll either the entering condenser water temperature or lift differential temperature between the condenser and evaporator saturated temperatures.
• Tower fan staging plus low limit - controlled as in # 1
s tower bypass valve set at a minimum entering con-
plu denser water temperature.
• Tower staging with staged bypass control – similar to # 2 with additional control of the bypass valve between fan staging to smooth control and minimize fan staging.
• VFD staging only – in this mode, a variable speed drive controls the first fan with up to 3 more fans to be staged
off and there is no bypass valve.
on and
VFD and Valve Staging – same as # 4 plus bypass valve
control.
ed by
Factory mounted DDC controllers shall support operation on a BACnet, Modbus or LONWORKS network via a fac­tory-installed communication module. Factory mounted DDC controller(s) shall support operation on a BACnet®, Modbus® or LONMARKS ® network via one of the data link / physical layers listed below as speci­fied by the successful Building Automation System (BAS) supplier.
• BACnet MS/TP master (Clause 9)
• BACnet IP, (Annex J)
• BACnet ISO 8802-3, (Ethernet)
• LONMARKS FTT-10A. The unit controller shal LONMARKS® certified.
The information communicated between the BAS and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring, control and alarm notification as specified in the unit sequence of oper­ation and the unit points list. For chillers communicating over a LONMARK network, the corresponding LONMARK eXternal Interface File (XIF) shall be provided with the chiller submittal data. All communication from the chiller unit controller as speci­fied in the points list shall be via standard BACnet objects. Proprietary BACnet objects shall not be allowed. BACnet communications shall conform to the BACnet protocol (ANSI/ASHRAE135-2001). A BACnet Protocol Imple­mentation Conformance Statement (PICS) shall be pro­vided along with the unit submittal.
2.5. MISCELLANEOUS ITEMS
A Pumpout System: If the design of the unit does not allow
the charge to be transferred to and isolated in the main condenser, it shall be equipped with an ASME pumpout system complete with a transfer pump, condensing unit, and storage vessel . The main condenser shall be sized to contain the refrigerant charge at 90°F according to ANSI­ASHRAE 15.A.
B Purge System (negative pressure chillers only):
1 The chiller manufacturer shall provide a separate high
efficiency purge system that operates independently of the unit and can be operated while the unit is off. The system shall consist of an air-cooled condensing unit, purge condensing tank, pumpout compressor and control system.
2 A dedicated condensing unit shall be provided with the
purge system to provide a cooling source whether or not the chiller is running. The condensing unit shall provide a low purge coil temperature to result in a maximum loss of 0.1 pounds of refrigerant per pound of purged air.
3 The purge tank shall consist of a cooling coil, filter-drier,
water separation tube, sight glass, drain, and air discharge port. Air and water are separated from the refrigerant vapor and accumulated in the purge tank.
l be
Cat 605-5 70
Specifications (WDC)
4 The pumpout system shall consist of a small compressor
and a restriction device located at the pumpout compressor suction connection.
5 The purge unit shall be connected to a 100% reclaim
device.
C Vacuum Prevention System (Negative pressure chillers
only): Chiller manufacturer shall supply and install a vacuum prevention system for each chiller. The system shall constantly maintain 0.05 psig inside the vessel during non-operational periods. The system shall consist of a precision pressure controller, two silicon blanket heaters, a pressure transducer, and solid-state safety circuit.
D Refrigerant Detection Device (negative pressure chillers
only): Chiller manufacturer shall supply and install a refrigerant detection device and alarm capable of monitoring refrigerant at a level of 10 ppm. The chiller manufacturer shall guarantee and maintain the detection monitor for five years.
E Waffle type vibration pads for field mounting under unit .
F OSHPD Certification: The chiller shall be OSHPD Pre-
Approved per OSP-0116-10 and be so labeled. The chiller shall meet a minimum seismic design spectral response acceleration of 1.60 S
rigid base and may use neoprene waffle vibration pads.
G IBC Certification: The chiller shall be certified to the
following codes and standards; 2009 IBC, 2010 CBC, ICC­ES AC-156, ASCE 7-05. The chiller must be mounted to a rigid base and may use neoprene waffle vibration pads.
. The chiller must be mounted to a
DS
PART 3 — EXECUTION
3.1 INSTALLATION
A Install per manufacturer’s requirements, shop drawings,
and Contract Documents.
B Adjust chiller alignment on foundations, or subbases as
called for on drawings.
C Arrange piping to allow for dismantling to permit head
removal and tube cleaning.
D Furnish and install necessary auxiliary water piping for oil
cooler.
E Coordinate electrical installation with electrical contractor.
F Coordinate controls with control contractor.
G Provide all materiel required for a fully operational and
functional chiller.
3.2 START-UP
A Units shall be factory charged with the proper refrigerant
and oil.
B Factory Start-Up Services: The manufacturer shall provide
factory authorized supervision for as long a time as is necessary to ensure proper operation of the unit, but in no case for less than two full working days. During the period of start-up, the start-up technician shall instruct the owner’s representative in proper care and operation of the unit.
71 Cat 605-5
Specifications (WCC)
SECTION 15XXX - CENTRIFUGAL CHILLERS COUNTERFLOW, DUAL COMPRESSORS
PART 1 — GENERAL
1.1 SUMMARY
A Section includes design, performance criteria, refrigerants,
controls, and installation requirements for water-cooled centrifugal chillers.
1.2 REFERENCES
A Comply with the following codes and standards
1 AHRI 550/590
2 NEC
3 ANSI/ASHRAE 15
4 OSHA as adopted by the State
5 ASME Section VIII
Specifications (WCC)
1.6 WARRANTY
A The refrigeration equipment manufacturer’s warranty shall
be for a period of (one) -- OR -- (two) --Or-- (five) years from date of equipment start up or 18 months from shipment whichever occurs first. The warranty shall include parts and labor costs for the repair or replacement of defects in material or workmanship. [WDC: The refrigerant charge shall be warranted against contamination from a motor burnout for five years.]
1.7 MAINTENANCE
A Chiller maintenance shall be the responsibility of the owner
with the following exceptions:
1 The manufacturer shall provide the first year scheduled
oil and filter change if required.
2 The manufacturer shall provide first year purge unit
maintenance if required.
1.3 SUBMITTALS
A Submittals shall include the following:
1 Dimensioned plan and elevation view drawings,
including motor starter cabinet, required clearances, and location of all field piping and electrical connections.
2 Summaries of all auxiliary utility requirements such as:
electricity, water, air, etc. Summary shall indicate quality and quantity of each required utility.
3 Diagram of control system indicating points for field
interface and field connection. Diagram shall fully depict field and factory wiring.
4 Manufacturer’s certified performance data at full load
plus IPLV or NPLV.
5 Before shipment, submit a certification of satisfactory
completion of factory run test signed by a company officer. The test shall be performed on an AHRI­qualified test stand and conducted according to AHRI Standard 550/590.
6 Installation and Operating Manuals.
1.4 QUALITY ASSURANCE
A Qualifications: Equipment manufacturer must specialize in
the manufacture of the products specified and have five years experience with the equipment and refrigerant offered.
B Regulatory Requirements: Comply with the codes and
standards in Section 1.2.
C Chiller manufacturer plant shall be ISO Registered.
1.5 DELIVERY AND HANDLING
A Chillers shall be delivered to the job site completely
assembled and charged with refrigerant and oil.
B Comply with the manufacturer’s instructions for rigging
and transporting units. Leave protective covers in place until installation.
PART 2 — PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
A Daikin
B (Approved Equal)
2.2 UNIT DESCRIPTION
A Provide and install as shown on the plans a factory
assembled, charged water-cooled packaged chiller. Each unit shall be complete with two single-stage hermetic centrifugal compressors each having independent lubrication and control systems. Each compressor shall have a dedicated circuit in the evaporator and condenser, and its own refrigerant control device. The chiller unit shall be capable of running on one compressor with the other compressor or any of its auxiliaries inoperable or removed. Each chiller shall be factory run-tested under load condi­tions for a minimum of one hour on an AHRI qualified test stand with evaporator and condenser waterflow at job con­ditions (excluding glycol applications). Operating controls shall be adjusted and checked. The refrigerant charge shall be adjusted for optimum operation and recorded on the unit nameplate. Units operating with 50-Hz power shall be tested with a 50-Hz power supply. Any deviation in perfor­mance or operation shall be remedied prior to shipment and the unit retested if necessary to confirm repairs or adjust­ments. Manufacturer shall supply a certificate of comple­tion of a successful run-test upon request.
2.3 DESIGN REQUIREMENTS
A General: Provide a complete water-cooled dual centrifugal
water chiller as specified herein. Machine shall be provided according to standards, Section 1.2. In general, the unit shall consist of two compressors, two circuited refrigerant condenser and evaporator, two lubrication systems, and two control systems. The vessels shall be single pass with a counterflow water arrangement.
Cat 605-5 72
Specifications (WCC)
Sound Pressure (at 30 feet)
63
Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA
Sound Power
63 Hz
125
Hz
250
Hz
500
Hz
1000
Hz
2000
Hz
4000
Hz
8000
Hz
Overall
dBA
75% Load
dBA
50% Load
dBA
25% Load
dBA
One-third Octave Band Sound Power
50Hz63Hz80Hz100HZ125Hz160Hz200Hz250Hz315Hz400Hz500Hz630Hz800Hz1000Hz1250Hz1600Hz2000Hz2500Hz3150Hz4000Hz5000Hz6300Hz8000Hz10
kHz
Note: Chillers shall be charged with a refrigerant such as HFC-134a, not subject to the Montreal Protocol and the U. S. Clean Air Act.
B Performance: Refer to schedule on the drawings. The
chiller shall be capable of stable operation to five percent of full load with standard AHRI entering condensing water relief without hot gas bypass.
C Acoustics: Sound pressure for the unit shall not exceed the
following specified levels. Provide the necessary acoustic treatment to chiller as required. Sound data shall be measured according to
D AHRI Standard 575 and shall be in dB. Data shall be the
highest levels recorded at all load points. Test shall be in accordance with AHRI Standard 575.
2.4 CHILLER COMPONENTS
A A.Compressors:
1 The chiller shall have two single-stage hermetic
centrifugal compressors. Casing design shall ensure major wearing parts, main and thrust bearings are accessible for maintenance and replacement.
2 The impeller shall be statically and dynamically
balanced. The compressor shall be vibration tested and not exceed 0.14 IPS.
3 Movable inlet guide vanes actuated by an internal oil
pressure driven piston shall accomplish unloading. Compressors using an unloading system that requires penetrations of the compressor housing or linkages, or both, that must be lubricated and adjusted are acceptable provided the manufacturer provides a five-year inspection agreement consisting of semi-annual inspection, lubrication, and annual change out of compressor seals. A statement of inclusion must accompany any quotations.
4 If compressors are not equipped with guide vanes for
each stage and movable discharge diffusers, then furnish hot gas bypass and select chillers at 5% lower kW/ton than specified to compensate for bypass inefficiency at low loads.
5 For air-cooled motors the chiller manufacturer shall be
responsible for providing the cooling of the refrigeration machinery room. The sensible cooling load shall be based on the total heat rejection to the atmosphere from tow refrigeration units.
6 For open motor unit, an oil reservoir shall collect any oil
and refrigerant that leaks past the seal. A float device shall be provided to open when the reservoir is full, directing the refrigerant/oil mixture back into the compressor housing. Manufacturer shall warrant the shaft seal, reservoir, and float valve system against leakage of oil and refrigerant to the outside of the refrigerating unit for a period of 5 years from the initial start-up including parts and labor to replace a defective seal and any refrigerant required to trim the charge original specifications.
B Lubrication System: Each compressor shall have an
independent lubrication system to provide lubrication to all parts requiring lubrication. Provide a heater in the lubricant sump to maintain lubricant at sufficient temperature to minimize affinity of refrigerant, and a thermostatically controlled water-cooled oil cooler. Coolers located inside the evaporator or condenser are not acceptable due to inaccessibility. A positive displacement submerged lubricant pump shall be powered through the unit control transformer.
C Refrigerant Evaporator and Condenser:
1 Evaporator and condenser shall be of the shell-and-tube
type, designed, constructed, tested and stamped according to the requirements of the ASME Code, Section VIII. Regardless of the operating pressure, the refrigerant side of each vessel will bear the ASME stamp indicating compliance with the code and indicating a test pressure of 1.1 times the working pressure but not less than 100 psig. Provide intermediate tube supports at a maximum of 18 inch spacing.
73 Cat 605-5
Specifications (WCC)
2 Each vessel shall have two refrigerant circuits, separated
by an intermediate tube sheet.
3 Tubes shall be enhanced for maximum heat transfer,
rolled into steel end and intermediate tube sheets and sealed with Locktite or equal sealer. The tubes shall be individually replaceable.
4 The water sides shall be designed for a minimum of 150
psig or as specified elsewhere. Vents and drains shall be provided.
5 Chilled water minimum refrigerant temperature shall be
33F.
6 An electronic or thermal refrigerant expansion valve
shall control refrigerant flow to the evaporator. Fixed orifice devices or float controls with hot gas bypass are not acceptable because of inefficient control at low load conditions. The liquid line shall have a moisture indicating sight glass.
7 The evaporator and condenser shall be separate shells. A
single shell containing both vessel functions is not acceptable because of the possibility of internal leaks.
8 Interstage economizers shall be used between each
compressor stage on multi-stage compressors for increased efficiency.
9 Reseating type spring loaded pressure relief valves
according to ASHRAE-15 safety code shall be furnished. The evaporator shall be provided with single or multiple valves. The condenser shall be provided with dual relief valves equipped with a transfer valve so one valve can be removed for testing or replacement without loss of refrigerant or removal of refrigerant from the vessel. Rupture disks are not acceptable.
10 The evaporator, suction line, and any other component or
part of a component subject to condensing moisture shall be insulated with UL recognized 3/4 inch closed cell insulation. All joints and seams shall be carefully sealed to form a vapor barrier.
11 Provide a factory-installed, thermal dispersion, water
flow switches on each vessel to prevent unit operation with no flow.
D Prime Mover: Squirrel cage induction motor of the
hermetic type of sufficient size to efficiently fulfill compressor horsepower requirements. Motor shall be liquid refrigerant cooled with internal thermal overload protection devices embedded in the winding of each phase. Motor shall be compa
tible with the starting method specified hereinafter. If the Contractor chooses to provided an open drive motor or compressor, verify in the submittal that the scheduled chiller room ventilation system will
accommodate the additional heat and maintain the equipment room at design indoor temperature based on 95 degree F outdoor ambient ventilation air available. If additional cooling is required, manufacturer shall be responsible for the installation, wiring and controls of a cooling system.
Chiller selection shall compensate for tons and efficiency loss to make certain the owner is not penal-ized.
E Motor Starters:
The main motor starters are to be furnished by the chiller manufacturer and shipped loose for floor mounting and field wiring to the chiller package. They shall be free-stand­ing with NEMA-1 enclosure designed for top entry and bottom exit and with front access. The starters must comply with the codes and standards in Section 1.2 as required.
1 Low Voltage (200 through 600 volts) controllers are to
be continuous duty AC magnetic type constructed according to NEMA standards for Industrial Controls and Systems (ICS) and capable of carrying the specified current on a continuous basis. The starters shall be:
Wye-Delta Closed Transition
- The starter shall be equipped with properly sized resistors to provide a smooth transition. The resistors shall be protected with a transition resistor protector, tripping in a maximum of two seconds, locking out the starter, and shall be manually reset. A clearly marked transition timer shall be adjustable from 0 to 30 seconds or a current sensing device shall initiate transi­tion when the starting current drops to 90% of the unit RLA.
-- OR --
Solid-State Reduced Voltage
- Starter shall be furnished with silicon controlled rectifiers (SCR) connected for start­ing and include a bypass contactor. When operating speed is reached, the bypass contactor shall be energized remov­ing the SCRs from the circuit during normal running.
All Low Voltage starters shall:
a Be coordinated with the chiller package(s) making
certain all terminals are properly marked according to the chiller manufacturer’s wiring diagrams.
b The starters shall be equipped with a motor control
relay (MCR). The relay shall interconnect the starter with the unit control panel and directly operate the main motor contactor. The MCRs shall constitute the only means of energizing the motor starter.
c The main contactors shall have a normally-open
auxiliary contact rated at 125VA pilot duty at 115 VAC. An additional set of normally open contacts shall be provided on the MCR.
d There shall be electronic overloads in each phase,
which will permit continuous operation at 107% of the rated load amps of each motor. The overloads shall have a must-trip setting at 125% of the RLA. Overloads shall be manual reset and shall de-energize the main contactors when the overcurrent occurs. The overloads shall be adjustable, have manual reset, be ambient compensated, and set for Class 10 operation.
Cat 605-5 74
Specifications (WCC)
e Each starter shall have a current transformer and
adjustable voltage dropping resistor(s) to supply a 5.0 VAC signal at full load to the unit control panels.
f Each starter shall be equipped with a line to 115 VAC
control transformer, fused in both the primary and secondary, to supply power to the control panels, oil heaters and oil pumps.
g Each starter shall include the following protective
devices:
• Phase failure and reversal protection
• Under/over voltage protection
• Stall protection
-- OR --
2 Variable Frequency Drive
a The chiller shall be equipped with a Variable Frequency Drive
(VFD) to automatically regulate each compressor speed in response to cooling load and compressor pressure lift. The chiller control shall coordinate compressor speed and guide vane position to optimize chiller efficiency. b The VFD and options are UL options are designed
to comply with the applicable requirement
tm
508A listed. The drive and
of the latest standards of ANSI, NEMA, National Electric Code NEC, and FCC Part 15 Subpart J. c The VFD shall have 110% continuous overload of continuous amp rating with no time limit, PWM (pulse width modulated) output, IGBT (insulated gate bipolar transistors) power technology and full power rating at 2kHz, DC bus inductor (choke), and wireless construction. d The VFD has the following basic features:
i. An overload circuit to protect an AC motor operated by the VFD output from extended overload operation on an inverse time basis.
ii. 0.98 power factor at full load and provides power factor correction at lighter loads
iii. An LCD Keypad display
1. Frequency output
2. Voltage output
3. Motor Current
4. % current
5. Output kW
6. Fault log of 16 most recent faults
iv. 3% minimum impedance AC line reactor
v. Fan cooled drives and cabinet
vi. Molded case disconnect with fusing or CB disconnect with fusing
vii. 100,000 amp interrupting capacity e. The VFD includes the following protective circuits and features:
i. Output phase-to-phase short circuit condition.
ii. Total ground fault protection under any operating condition.
iii. High input line voltage detection.
iv. Low input line voltage detection.
v. Loss of input or output phase.
vi. External fault. (This protective circuit shall permit wiring of remote a NC safety contact to shut down the drive).
vii. Metal oxide varistors for surge suppression at the VFD input terminals.
viii. Maintenance counters (6)
ix. External Start Interlocks
x. Communication loss
xi. Keypad Communication loss
xii. Motor Stall Detection
xiii. Auto Fault Reset
-- OR --
3 Medium Voltage (601 through 7200 volts). The starters
shall be:
Solid-State Reduced Voltage.
Starter shall be furnished with silicon controlled rectifiers (SCR) connected for start­ing and include a bypass contactor. When operating speed is reached, the bypass contactor shall be energized remov­ing the SCRs from the circuit during normal running.
a The starter shall be coordinated with the chiller
package(s) making certain all terminals are properly marked according to the chiller manufacturer’s wiring diagrams.
b The starters shall be equipped with a redundant motor
control relay (MCR), which interconnects the starter with the unit control panel and directly operates the main motor contactors. The MCRs shall constitute the only means of energizing the motor starter.
75 Cat 605-5
Specifications (WCC)
c The main contactors shall have a normally open
auxiliary contact rated at 125VA pilot duty at 115 VAC. An additional set of normally open contacts shall be provided on the MCR.
d There shall be electronic overloads in each phase,
which will permit continuous operation at 107% of the rated load amps of each motor. The overloads shall have a must-trip setting at 125% of the RLA. Overloads shall be manual reset and shall de-energize the main contactors when the overcurrent occurs. The overloads shall be adjustable, have manual reset, be ambient compensated, and set for Class 10 operation
e Each starter shall have a current transformer and
adjustable voltage dropping resistor(s) to supply a 5.0 VAC signal at full load to the unit control panels.
f Each starter shall be equipped with a line-to-115 VAC
control transformer, fused in both the primary and secondary, to supply power to the control panels, oil heaters and oil pumps.
g Each starter shall include the following:
•Phase failure and reversal protection
•Under/over voltage protection
•Load break disconnect switch on solid state or across-the-line starters Isolating safety switch on autotransformer or pri­mary reactor starters
•Current limiting power fuses
-- OR -­Across-the-Line
type with primary contactor allowing locked rotor amps to reach the motor when energized including items a through g above.
-- OR -­Autotransformer
type factory wired to the 65% tap with drawout magnetic, three-pole, vacuum break shorting con­tactor, drawout magnetic, two-pole, vacuum break starting contactor, and open delta starting auto-transformer factory set at 65% including items a through g above.
-- OR -­Primary Reactor
type with drawout magnetic, three-pole, vacuum break shorting assembly, and three-phase starting reactor, factory set at the 65% tap including items a through g above. All medium and higher voltage starters shall have the fol­lowing components:
Main Control Relays
A motor control relay shall be provided to interlock the starter with the chiller. The two relay shall constitute the only means of energizing the motor starter. No other devices (manual or automatic) with the capability of ener­gizing the starter can be used. The starter is to be controlled by the unit microprocessor.
Motor Protection and Overloads
The starter shall include overload protection functions. These controls include:
• Solid state overload (overcurrent) protection
• Phase unbalance protection
• Phase reversal and phase loss protection.
• Adjustable overload to closely match motor performance
• Three current transformers to measure motor current and a fourth current transformer for input to the chiller microprocessor.
Undervoltage (UV) Relay
The undervoltage relay is an adjustable three-phase protec­tion system that is activated when the voltage falls below a predetermined safe value and is factory set at 85% of nomi­nal.
Control Voltage Transformer
The starter is provided with a 3KVA control transformer with both secondary and primary fuses to supply control power to the chiller.
Additional Standard Components
• Mechanical type solderless connectors to hand
le wire
sizes indicated by the NEC.
• Three vertically mounted current limiting power fuse blocks (fuses included)
• Magnetic three-pole, vacuum break contactor
• Single phase control circuit transformer
• Vertically mounted control circuit primary current limit­ing fuses
• Current transformers
• Load terminals
• Control circuit terminal blocks and secondary fuses
• Phase failure and reversal relay
F CHILLER CONTROLLER
Chiller control shall be done through unit controller (micro­processor) and a controller for each compressor, all of which shall have a 4-by-20-character display to view sys­tem parameters, denote alarms and input setpoints. In conjunction with these controllers, the primary operator interface shall be a state-of-the-art super VGA color touch screen monitor and USB port. The control system shall have inherent trend logging capa­bilities, which are transferable to other PC management systems such as an Excel spread sheet via a USB port. Active trend logging data shall be available for viewing in 20 minute, 2 hour or 8 hour intervals. A full 24 hours of history shall be downloadable via the USB port. The fol­lowing trended parameters shall be displayed:
• Entering and leaving chilled water temps
• Entering and leaving condenser water temps
• Evaporator saturated refrigerant pressure
• Condenser saturated refrigerant pressure
• Net oil pressure for each compressor
• % rated load amps for entire unit
In addition to the trended items above, other real-time oper­ating parameters shall also be shown on the touch screen.
76
Cat
605-5
Specifications (WCC)
These items can be displayed in two ways: by chiller graphic showing each component or from a color-coded, bar chart format. At a minimum, the following critical areas must be monitored:
• Oil sump temperature per compressor
• Oil feed line temperature per compressor
• Evaporator saturated refrigerant temperature for unit
• Suction temperature for unit
• Condenser saturated refrigerant temperature for unit
• Discharge temperature for unit
• Liquid line temperature for unit The unit operating and maintenance instructions shall be viewable on the touch screen and downloadable via the onboard USB port. Complete fault history shall be displayed using an easy to decipher, color coded set of messages that are date and time stamped. The last 20 faults shall be downloadable from the USB port. Automatic corrective action to reduce unnecessary cycling shall be accomplished through pre-emptive control of low evaporator or high discharge pressure conditions to keep the unit operating through ancillary transient conditions. System specific, chiller plant architecture software shall be employed to display the chiller, piping, pumps and cooling tower. Chiller interconnection softw for up to 4 WCC, WDC or WSC chillers shall be included also providing automatic control of: evaporator and condenser pumps (pri­mary and standby), up to 4 stages of cooling tower fans and a cooling tower modulating bypass valve or cooling tower variable frequency drives. There shall be five possible tower control strategies:
• Tower fan staging only – up to 4 stages controll
ed by either the entering condenser water temperature or lift dif
ferential temperature between the conden
ser and
evaporator saturated temperatures.
• Tower fan staging plus low limit - controlled as in # 1 plus tower bypass valve set at a minimum entering con­denser water temperature.
• Tower staging with staged bypass control – similar to # 2 with additional control of the bypass valve between fan staging to smooth control and minimize fan staging.
• VFD staging only – in this mode, a variable
speed drive controls the first fan with up to 3 more fans to be staged on and off and there is no bypass valve.
• VFD and Valve Staging – same as # 4 plus bypass valve control.
Factory mounted DDC controllers shall support operation on a BACnet, Modbus or LONWORKS network via one of the data link / physical layers listed below as speci­fied by the successful Building Automation System sup­plier.
• BACnet MS/TP master (Clause 9)
• BACnet IP, (Annex J)
• BACnet ISO 8802-3, (Ethernet)
•LONWORKS FTT-10A The information communicated between the building auto­mation system and the factory mounted unit controllers shall include the reading and writing of data to allow unit monitoring, control and alarm notification as specified in the unit sequence of operation and the points list.
2.5. MISCELLANEOUS ITEMS
A Pumpout System: The unit shall be equipped with a
pumpout system complete with a transfer pump, condensing unit, and storage vessel constructed according to ASME Code for Unfired Pressure Vessels and shall bear the National Boards stamp. If the design of the unit allows the charge to be transferred to and isolated in the main condenser, then a pumpout system is not required. Transfer of refrigerant charge shall be accomplished by either main compressor operation, migration, or gravity flow. Isolation shall be accomplished with valves located at the inlet and exit of the condenser. The main condenser shall be sized to contain the refrigerant charge at 90F according to ANSI­ASHRAE 15.A.
B Purge System (negative pressure chillers only):
1 The chiller manufacturer shall provide a separate high
efficiency purge system that operates independently of the unit and can be operated while the unit is off. The system shall consist of an air-cooled condensing unit, purge condensing tank, pumpout compressor and control system.
2 A dedicated condensing unit shall be provided with the
purge system to provide a cooling source whether or not the chiller is running. The condensing unit shall provide a low purge coil temperature to result in a maximum loss of 0.1 pounds of refrigerant per pound of purged air.
3 The purge tank shall consist of a cooling coil, filter-drier,
water separation tube, sight glass, drain, and air discharge port. Air and water are separated from the refrigerant vapor and accumulated in the purge tank.
4 The pumpout system shall consist of a small compressor
and a restriction device located at the pumpout compressor suction connection.
C Vacuum Prevention System (Negative pressure chillers
only): Chiller manufacturer shall supply and install a vacuum prevention system for each chiller. The system shall constantly maintain 0.05 psig inside the vessel during non-operational periods. The system shall consist of a precision pressure controller, two silicon blanket heaters, a pressure transducer, and solid-state safety circuit.
D Refrigerant Detection Device (negative pressure chillers
only): Chiller manufacturer shall supply and install a refrigerant detection device and alarm capable of monitoring refrigerant at a level of 10 ppm. Due to the critical nature of this device and possible owner liability, the chiller manufacturer shall guarantee and maintain the
Cat 605-5 77
Specifications (WCC)
detection monitor for five years after owner acceptance of the system.
E Waffle type vibration pads for field mounting under unit
feet.
F IBC Certification: The chiller shall be certified to the
following codes and standards; 2009 IBC, 2010 CBC, ICC­ES AC-156, ASCE 7-05. The chiller must be mounted to a rigid base and may use neoprene waffle vibration pads.
G OSHPD Certification: The chiller shall be OSHPD Pre-
Approved per OSP-0116-10 and be so labeled. The chiller shall meet a minimum seismic design spectral response acceleration of 1.60 S
rigid base and may use neoprene waffle vibration pads.
PART 3 — EXECUTION
3.1 INSTALLATION
A Install per manufacturer’s requirements, shop drawings,
and Contract Documents.
B Adjust chiller alignment on foundations, or subbases as
called for on drawings.
C Arrange piping to allow for dismantling to permit head
removal and tube cleaning.
D Furnish and install necessary auxiliary water piping for oil
cooler.
E Coordinate electrical installation with electrical contractor.
F Coordinate controls with control contractor.
G Provide all materiel required for a fully operational and
functional chiller.
. The chiller must be mounted to a
DS
3.2 START-UP
A Units shall be factory charged with the proper refrigerant
and lubricant.
B Factory Start-Up Services: Provide for as long a time as is
necessary to ensure proper operation of the unit, but in no case for less than two full working days. During the period of start-up, The Start-up Technician shall instruct the Owner’s representative in proper care and operation of the unit.
78 Cat 605-5
Daikin Training and Development
When you make an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on training, or call 540-248-9646 to speak to the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Representative
for warranty details. To find your local Daikin
Representative, go to www.DaikinApplied.com .
This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com .
© 2015 Daikin Appliedwww.DaikinApplied.com • 800-432-1342 CAT 605-5, 9/15
Loading...