Goodman WCC113 User Manual

Centrifugal Compressor Water Chillers Catalog 605-5
Models WSC, WDC, WCC, HSC
Contents
Modbus
Contents
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Overview of Water-Cooled Product Line . . . . . . . . 3
World-Class Design Leader . . . . . . . . . . . . . . . 4
Design Features. . . . . . . . . . . . . . . . . . . . . . . . 4
Dual Compressor Centrifugal Chillers . . . . . . . . . . 6
Heat Recovery Models . . . . . . . . . . . . . . . . . . . . . . . 9
Templifier Heat Pump Water Heaters . . . . . . . 9
Heat Recovery Models . . . . . . . . . . . . . . . . . . . . . . 10
Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
MicroTech® II Controls . . . . . . . . . . . . . . . . . 11
Application Considerations. . . . . . . . . . . . . . . . . . 14
Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Starters and VFDs . . . . . . . . . . . . . . . . . . . . . . . . . 26
Motor Starters . . . . . . . . . . . . . . . . . . . . . . . . 26
Variable Frequency Drives (VFD) . . . . . . . . . 26
Selection Procedures . . . . . . . . . . . . . . . . . . . . . . 28
IPLV/NPLV Defined . . . . . . . . . . . . . . . . . . . 29
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . 49
Options and Accessories . . . . . . . . . . . . . . . . . . . 52
Refrigerant Recovery Units and Monitors . . . . . 54
Pump Out Units. . . . . . . . . . . . . . . . . . . . . . . 54
Refrigerant Monitors . . . . . . . . . . . . . . . . . . . 54
Retrofit Disassembly (Knockdown Options) . . . 55
Specifications (WSC) . . . . . . . . . . . . . . . . . . . . . . 59
Specifications (WDC) . . . . . . . . . . . . . . . . . . . . . . 65
Specifications (WCC) . . . . . . . . . . . . . . . . . . . . . . 71
Starter Types and Descriptions . . . . . . . . . . . 26
Hazard Identification
DANGER
Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.
WARNING
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.
On the cover: WSC 087, 600 Tons, with Compressor VFD
Document: Issue Date: October 1999 Revision Date: Replaces:
CAT 605-5
September 2015 August 2015
© 2015 Daikin Applied. Illustrations and data cover the Daikin product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: LEED is a registered trademark of the U.S. Green Building Council; BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a license granted by Echelon Corporation; Modbus from Schneider Electric; MicroTech II, Open Choices from Daikin.
2 Cat 605-5
Engineered for flexibility and performance
Centrifugal Compressor Water Chillers Catalog 605-2
Models WSC, WDC, WCC, HSC Includes Higher Voltage (10/11kV) WDC/WCC models
Introduction
Overview of Water-Cooled Product Line
Introduction
Included in this manual:
Centrifugal Products included in separate manuals:
Model WSC
Capacity: 200-1250 tons (AHRI conditions)
Excellent full load performance
Model WDC
Capacity: 400-2500 tons (AHRI conditions)
Outstanding part load performance
Redundancy for increased reliability
Some sizes available with 10/11kV50Hz power option
Model WCC
Capacity: 1200-2700 tons (AHRI conditions)
Two refrigerant circuits for true counterflow
Outstanding full load performance
Some sizes available with 10/11kV50Hz power option
Magnitude™ Magnetic Bearing Compressor Chillers
Magnitude™ Model WMC
• Capacity: 145-400 tons
• Oil-free, frictionless compressor
• Excellent part-load performance
• See CAT 602 for more information
Magnitude™ Model WME
Capacity: 400-1500 tons
• Oil-free, frictionless compressor
• Outstanding efficiency
• See CAT 604 for more information
Templifier™ Model TSC Water Heater
• Recovers waste heat from process applications
• 5,000 - 19,000 MBH
Model HSC
Recycles heat normally lost in cooling towers
• Hot water - 140
See Templifier CAT 614 for more information
o
; COP as high as 7
Produces simultaneous heating and cooling
Cat 605-5 3
Features and Benefits
Features and Benefits
World-Class Design Leader
As part of Daikin Industries, a Fortune 1000 company, Daikin is the second largest air conditioning, heating, ventilating and refrigeration company in the world. We have earned a worldwide reputation for providing a full line of quality products and expertise to meet the demands of our customers. The engineered flexibility of our products allows you to fine tune your HVAC system to meet the specific requirements of your application. You benefit from lower installed and operating costs, high energy efficiency, quiet operation, superior indoor air quality (IAQ) and low cost maintenance and service.
Daikin Centrifugal Compressor Water Chillers are engineered for flexibility and performance - offering choices, options and features that provide the
right solution for your specific application-and have been doing so for over fifty years. Some highlights of our world-class centrifugal design are:
Design Features
Excellent Performance
Daikin offers a wide range of centrifugal vessel and component combinations to provide the right solution for your specific application. The single compressor WSC offers excellent full load performance, however, in most applications, chillers spend about 99% of their operating hours at part-load condidtions. Our dual compressor WDC chillers offer many attractive benefits, including outstanding part-load efficiency, and system redundancy similar to two separate chillers, with a lower total installed cost. WCC models also offer the dual compressor advantage but with counterflow vessels, and a separate refrigerant circuit for each compressor. WCC chillers excel at full load efficiency. Contact your Daikin representative for detailed information to decide which model is right for your job requirements.
Table 1: Centrifugal Models & Possible Applications
Application
Cooling <1250 tons, most hours at full load WSC Cooling >1250 tons, most hours at full load WCC Cooling, most hours at part load WDC Heating Application TSC Templifier™ Simultaneous Cooling and Heating HSC Optimized Part Load Performance Optional VFD
Positive Pressure Design
Positive pressure systems offer numerous advantages over
ve pressure design. In a negative pressure system, leaks
negati allow air, moisture, and other contaminants to seep into system, which will gradually decrease performance, as well as cause corrosion which must be removed. The Daikin positive pressure design eliminates this worry, providing sustainable performance and trouble-free ownership for the life of the unit under normal operation.
Daikin Model
Gear Driven Advantage
Daikin’s precision-engineered gear driven design allows for lighter components, less vibration, and ability to
select gear ratios that will provide the optimum impeller speed for your application. Older direct-drive designs must use large, heavy impellers to reach similar tip speeds, which cause more vibration and greater stress on shaft and motor during unexpected electrical interruptions.
The compact design and lighter weight components allow for efficient hydrodynamic bearings to be used. This means that
operation, the shaft is supported on a film of lubricant,
during with no shaft-to-bearing contact, providing theoretical infinte life bearings under normal circumstances. The design simplicity of the Daikin centrifugal compressors provides increased durability and reliable performance.
Smart Refrigerant
HFC-134a refrigerant contains no chlorine and has zero Ozone Depletion Potential (ODP), making it an environmentally superior alternative to other refrigerants such as HCFC-123. It also has an A1 ASHRAE Safety Classificiation - the lowest toxicity and flammability rating. R-134a provides the assurance of a safe, smart, and sustainable solution.
R-123 requires about 6 times the gas flow rate (cfm/ton) of R­134a, which means that the suction and discharge
piping must also be six times larger. Using R-134a allows Daikin to provide you with a smaller footprint chiller.
Table 2: Refrigerant Comparison
HFC-134a HCFC-123
No Ozone Depletion
Potential
No Refrigerant Phase Out
Date
ENVIRONMENTAL
Physically smaller, requiring
less mechanical room space.
In the event of a small leak,
refrigerant escapes, allowing
easy detection and repair
No purge unit required
No oil change is required
INSTALLATION AND MAINTENANCE
A1 ASHRAE Safety
Classification -
lowest
toxicity/flammability
SAFETY
RefrigerantResourceCenter for references and more information.
rating
See www.DaikinApplied.com /Daikin/DesignSolutions/
Ozone-depleting substance
Montreal Protocol requires
phase out in new equipment by
2020; production cease by 2030
Requires larger refrigerant flow
rate, with subsequent increase in
component and unit size.
In the event of a small leak, air
leaks into the chiller, making
detection and repair difficult. Can
degrade efficiency
Added cost and additional space
for a purge unit. Must
periodically purge unit to remove
contaminants
Annual oil change is
recommended
B1 ASHRAE Safety
Classification- higher toxicity
level
4 Cat 605-5
Features and Benefits
Unmatched Unloading
Daikin pioneered the use of moveable discharge geometry to lower the surge point of centrifugal which the compressor enters a stall or surge condition generally limits compressor unloading. Chillers with a fixed discharge will experience stall or surge at low loads due to refrigerant re-entering the impeller. When in a stall condition, the refrigerant gas is unable to enter the volute due to its low velocity and remains stalled in the impeller. In a surge condition the gas rapidly reverses direction in the impeller causing excessive vibration and heat. Daikin compressors reduce the discharge area as load decreases to maintain gas velocity and greatly reduce the tendency to stall or surge.
Figure 1: Fixed vs. Movable Discharge Geometry
In Figure 1, above, the drawing on the left shows a cross­section view of the operation at full load of a unit with a fixed compressor discharge. At full load, a large quantity of gas is discharged with a fairly uniform discharge velocity as indicated by the arrows.
The center drawing shows a fixed compressor discharge at reduced capacity. Note that the velocity is not uniform and the refrigerant tends to reenter the impeller. This is caused by low velocity in the discharge area and the high pressure in the condenser, resulting in unstable surge operation and with noise and vibration generated.
The following cutaway picture shows the unique Daikin movable discharge geometry. As the capacity reduces, the movable unloader piston travels inward, reducing the discharge cross section area and maintaining the refrigerant velocity. This mechanism capacity reduction.
allows our excellent unloading
compressors. The point at
Figure 2: Movable diffuser closes impeller discharge area as load decreases.
Controls Flexibility
MicroTech II® controls with our Open ChoicesTM feature allow easy integration with the BAS of choice using LonTalk®, BACnet® or Modbus® protocol
Retrofit Flexibility
Easy to retrofit with flexible knock-down options. See page 55 for details.
Trouble-Free Startup
All Daikin chillers are factory tested on AHRI qualified computer-controlled test stands. Each chiller is run-tested under load conditions for a minimum of one hour with evaporator and condenser water flow at job conditions (excluding glycol applications). Operating controls are checked and adjusted, and the refrigerant charge is adjusted for optimum operation and recorded on the unit nameplate. Units operating with 50-Hz power are tested with a 50-Hz power supply. The testing helps ensure correct operation prior to shipment, and allows factory calibration of chiller operating controls.
All domestic Daikin centrifugal chillers are commissioned by Daikin Factory Service personnel, or by authorized and experienced ensure that proper starting and checkout procedures are employed and helps in a speedy commissioning process, giving you confidence that your chiller is operating as expected.
Lubrication System
A separately driven electric oil pump assembly supplies lubrication at controlled temperature and pressure to all bearing surfaces and is the source of hydraulic pressure for the capacity control system.
Daikin startup technicians. This procedure helps
The control system will not allow the compressor to start until oil pressure, at the proper temperature, is established. It also allows the oil pump to operate after compressor shutdown to provide lubrication during coast-down. Lubricant from the pump is supplied to the compressor through a water-cooled, brazed-plate heat exchanger and single or dual five-micron oil filters internal to the compressor. All bearing surfaces are
Cat 605-5 5
Dual Compressor Centrifugal Chillers
pressure lubricated. Drive gears operate in a controlled lubricant mist atmosphere that efficiently cools and lubricates them.
Lubricant is made available under pressure from the compressor oil filter to the unit capacity control system and is used to position the inlet guide vanes in response to changes in leaving chiller water temperature.
If a power failure occurs, an emergency oil reservoir provides adequate lubrication flow under pressure, and prevents damage that could occur during the coast-down period with the oil pump stopped.
Since the Daikin chillers are positive pressure, there is no need to change the lubricant or filter on a regular basis. As with any equipment of
this type, an annual oil check is
recommended to evaluate the lubricant condition.
Figure 3: Lubrication System Schematic
is gas rapidly reversing direction through the impeller). A number of things can contribute to this condition including inadequate maintenance of condenser tube cleanliness, a cooling tower or control malfunction, or unusual ambient temperatures among others.
For these abnormal conditions, Daikin compressor designers have developed a protective control system that senses the potential for a surge, looks at the entire chiller system operation and takes corrective action if possible;
or stops the compressor, to help prevent any damage from occurring. This protection is provided as standard on all Daikin centrifugal compressors.
Dual Compressor Centrifugal Chillers
Dual Compressor Experience
Daikin is the expert when it comes to dual centrifugal compressor technology. We
have been successfully building dual compressor centrifugal chillers since 1971. Daikin is the only company that builds them with either a single refrigerant circuit (Model WDC) or two refrigerant circuits (Model WCC).
Benefits of Dual Compressor Chillers
Superior Efficiency
When coupled with a variable frequency drive, the extremely efficient Dual Compressor Chillers are considerably more efficient than single compressor chillers in the same size range, with IPLVs (Integrated Part Load Value) as low as 0.3 kW per ton. IPLV conditions are set by AHRI and subject to stringent testing. Insist on AHRI-certified IPLV efficiency when making efficiency comparisons.
Enhanced Surge Protection
When centrifugal compressors operate at part load, the volume of refrigerant gas entering the impeller is reduced. At the reduced flow, the impeller's capacity to develop the peak load head is also reduced. At conditions of low refrigerant flow and high compressor head (pressure difference), stall and/or surge can occur (a stall is gas static in the impeller, a surge condition
The Redundancy Feature
Daikin dual centrifugal chillers have two of everything connected to the evaporator and condenser - two compressors, two lubrication systems, two control systems, and two starters.
If any component on a compressor system fails, the component can be removed or repaired without shutting down the other compressor; providing an automatic back-up with at least 60 percent of the chiller design capacity available on WDC units and 50 percent on WCC units.
Redundancy is also built into the distributed control system, which consists of a unit controller, a compressor controller for each compressor and an operator interface touch screen. The chiller will operate normally without the touch screen being functional. If a compressor controller is unavailable, the other compressor will operate normally and handle as much of the load as possible.
Lower Installed Costs
The redundancy feature pays off in lower installed costs. An example of how to incorporate dual compressor chillers into a system requiring redundancy:
6 Cat 605-5
Dual Compressor Centrifugal Chillers
WSC Single Compressor Chillers WDC Dual Compressor Chillers
(2)
600 ton (2100 kW) On Line Units
(2)
750 ton (2100 kW) Units with
+(1)
600 (2100 kW ) t on Standby Unit 1,200 (4200 kW ) On Line tons
*
1,800 ton (6300 kW) Installed Capacity 1500 ton (52 50 kW ) Ins ta lled Capacit y
Job requirement: 1,200 tons (4200 kW), 50% Backup
*One 750-ton (2100 kW) dual chiller running on two compressors for 750 tons (2100 kW), plus one 750-ton (2100 kW) dual chiller running on one compressor for 60% of 750 tons (2100 kW) = 450 tons (1575 kW), for a total of 1200 tons (4200 kW) on any 3 of the 4 total compressors.
The elimination of the extra pumps, valves, piping, controls, rigging, and floor space can result in as much as a 35% reduction in the installation cost for a chiller plant, plus the savings on the chillers themselves.
Dual Compressor Chiller Overview
There are subtle but important differences between the single circuit WDC and two circuit WCC chillers.
Dual Circuit WCC Counterflow Chillers
These chillers have a separate refrigerant circuit for each compressor. They are available in single pass only. They provide the high full load efficiency advantage of two separate chillers arranged for counterflow operation in a single, compact unit.
Single Circuit WDC Chillers
These chillers have a single-refrigerant circuit for the evaporator and condenser with two compressors running in parallel and are available in one, two or three-pass configurations. Their salient feature is that at single­compressor, part load operation, the running compressor can utilize the entire chiller's heat transfer surface, providing outstanding part load performance.
Application of Dual Compressor Chillers
Designers and owners must decide which chiller type, or combination of chiller types, is best for their installation. Considerations include first cost, system efficiency, system reliability, space requirements, and total owning costs.
Use WCC chillers when:
Project requirement is lowest kW per ton performance at full load with high electrical demand charges.
Project has a large central plant where cycling chillers for system capacity reduction is expected (three or more chillers).
High chilled water delta-T and low water pressure drops are desired.
Built-in redundancy is required. A single compressor will provide 50% of the unit's full load capacity.
High efficiency and large capacity is required with series flow. Use two WCC units in series-counterflow in the 3,000 to 4,000 ton range.
Use WDC chillers when:
Project requirement is overall lowest energy consumption with best part load performance.
Project has smaller chilled water plant where unit unloading is expected versus cycling of chillers associated with large multi-chiller plants.
Floor space is limited (16-foot vessel length compared to 20­foot for WCC).
Two or three pass vessels are required, typical of retrofit applications.
Built-in redundancy is required. A single compressor will provide 60% of the unit's full load capacity.
Use a combination of WDC and WCC chillers when:
Peak overall system efficiency is important; for example, use three WCC and one WDC chiller, all in parallel. The WCC units are optimized for running at full load and the WDC is optimized for part load operation. The WCC units cycle on and off and the WDC unit (consider variable frequency drives on this unit) trims the load, running between five and one hundred percent capacity.
Why a Compressor Motor Failure Will Not Contaminate the Common Refrigerant Circuit on WDC dual chillers
Some people are concerned with the result of a motor burnout on a single-circuit dual compressor chiller. This is not a problem on the Daikin WDC chillers because of compressor construction and chiller layout.
The compressor motor is isolated from the main refrigerant flow circuit so that any contaminants generated by a motor failure will not pass into the main refrigerant circuit. Moisture, acid and/or carbon particles will be automatically trapped within the compressor's dedicated coolant feed and exit lines.
Internally, the compressor motor compartment is separated and sealed from the main refrigerant compression chamber. A double shaft seal on the motor side of the gear housing prevents cross flow of refrigerant along the motor shaft. The motor coolant feed line is equipped with both a solenoid valve and a check valve. These mechanical components, plus the higher pressure of the liquid refrigerant, prevent back feed into the main refrigerant system. Refrigerant vapor exiting the motor compartment must pass through a high pressure drop filter-drier, sized to immediately plug up and seal off the motor compartment. Both the coolant feed and return lines are equipped with manual shutoff valves to permit component service.
Cat 605-5 7
Dual Compressor Centrifugal Chillers
Over 30 years of field experience have proven the reliability of these compressor motors. Despite the reliability inherent in the motor design and the protective control, electrical distribution system faults and lightning strikes can occur that are beyond the control of the most conscientious designer. The coolant protective system protects the unit charge from being contaminated.
Special WDC Warranty: In the unlikely event of a motor burnout, the chiller refrigerant charge will not be
Figure 4: Motor Cooling
contaminated. This is so well proven that it is guaranteed for five years. In areas supported by Daikin Factory Service, if a motor burnout occurs in one compressor and contaminates the refrigerant circuit, any resultant damage to the other compressor will be repaired and the refrigerant charge replaced at no cost to the customer for parts and labor. The terms of the original chiller warranty apply to the original burned out compressor.
Efficiency
Chillers usually spend 99% of their operating hours under part load conditions, and most of this time at less than 60% of design capacity. One compressor of a dual WDC chiller operates with the full heat transfer surface of the entire unit. For example, one 500-ton (1,750 kW) compressor on a 1,000 ton (3,500 kW) dual chiller utilizes 1,000 tons (3500 kW) of evaporator and condenser surface. This increases the compressor's capacity and also results in very high efficiency.
Typical efficiencies for a WDC dual chiller, taken from a selection computer run, look like this:
Full load efficiency: 0.550 kW per ton (6.5 COP)
60% load, one compressor: 0.364 kW per ton (9.6 COP)
IPLV: 0.415 kW per ton (8.5 COP)
The addition of VFDs to the WDC dual produces an astonishing AHRI certified IPLV of 0.340 for the above case. Specific selections can vary up or down from this example. IPLV is defined in the Selection section of this manual beginning on page 28 .
8 Cat 605-5
compressor chiller
WCC chillers, with their counterflow design, excel at full load efficiency. Each of the two compressors operates at a lower head (pressure differential) than single compressor chillers in parallel. With any pump or compressor, lower head means lower power for a given flow. As shown on the right, the #2 (downstream compressor) makes 42 F water but has only 89 F condenser water leaving instead of 95 F typical of a single compressor unit. The #1 compressor has 95 F condenser water leaving, but only has to make 47.6 F chilled water.
The Replacement Market Advantage
Bolt-together construction on single and dual compressor chillers along with factory disassembly available as an option simply the tough entrance situations.
Put 20% or more tons in the same footprint.
Add dual compressor redundancy.
Greatly reduce chiller energy consumption.
Install a refrigerant with no phase-out date.
Opens many options for multiple chiller plants using WSC,
WDC and WCC combinations.
Heat Recovery Models
EVAPORATOR
TOW E R
COND ENSER
RE COV E RY
COND E N SE R
AUXILI ARY
HE ATER
HEAT L OAD
TCTCCOO LI N G
LOAD
OPEN CI RC UI T TOWER
HEAT REC OVERY
CHI LLER
LEGEND
TC TEMPERATURE CONTROL POINT
PUMP
Typical Building Types
Hotels/Motels Health Care Athletic Facilities Resorts Schools Food Service Nursing Homes
Typical Applications
Space Heating Outside Air Heating Reheat Service Hot Water Laundries Kitchens
G
TOWER
)
G
HEATER
R
R
CONDENSER
R
COOLING
R
90° F
(35°C)
F
CHILLER
TC
TC
C
Heat Recovery Models
Heat Recovery Models
For decades, Daikin has pioneered the use of heat recovery chillers and the unique Daikin Water Heater to reduce energy costs. These products have become more important than ever with the current emphasis on total building efficiency. ASHRAE Efficiency Standard
90.1 mandates the use of heat recovery equipment of this type in a wide range of buildings.
Heat Recovery Chillers
Model HSC heat recovery chillers, with a single compressor, have a single condenser with split bundles, i.e., two separate water passages divided by separate water heads as shown in the photograph to the right. The inboard water connections are connected to the cooling tower, the other water side is connected to the heating system.
The economic feasibility of hot water generated with these units depends on heating and cooling load profiles and on the relative cost of the available energy sources. A compressor's kW per ton is heavily influenced by the pressure head it is pumping against. During heat recovery operation, the entire cooling load is operating against the high head required by the
Templifier Heat Pump
hot water temperature. For this reason, it is desirable to maximize the percentage of the
total rejected heat used for the heating load. Daikin's economic evaluation program, Energy Analyzer , available on CD from your local Daikin sales office, is the perfect tool to determine the economic feasibility of using this proven technology.
Figure 5: Heat Recovery Chiller Piping Schematic
Templifier Heat Pump Water Heaters
Model TSC: 5,000 to 19,000 MBH
The Model TSC Templifier was developed in the 1970s, after the 1973 oil embargo, as a device to replace fossil-fired water heaters with electric heaters. The concept was simple; direct a stream of warm waste heat to the evaporator of a refrigeration unit, amplify the temperature of the heat through the compression cycle, and then deliver the heat from the condenser, at a higher useful temperature, to a heating load.
The flow diagram shown to the left illustrates just how the Templifier unit is placed decision to include a Templifier water heater is almost always a financial one. Evaluation of load profiles, energy costs, and owning costs is made simple by using the Daikin Energy Analyzer evaluation program to determine if the return on investment meets the owner's requirements.
When there is sufficient waste heat available, Templifier units can be very attractive where fossil fuels are not available, or where their use is restricted due to pollution problems or other reasons. Compared to electric resistance heating, the energy cost for a Templifier unit to heat domestic water, for example, could be 7 to 8 times less!
Where to Use Templifier Water Heaters:
in a chilled water system. The
Table 3: Typical COP’s
Hot Water
Temperatures
COP (Based on 85F off Chiller to Templifier)
110F 120F130F 140F
8.3 6.8 6.0 4.5
Figure 6: Templifier Heat Pump Water Heater Schematic
COOLI N
85°
(29°C)
55°F
(13°C)
EVAPO RATO
12 5°F (52°C
45°F (7 ° C )
95 °F
HEATIN
LOAD
TEMPLI FI ER HEAT
PUMP WAT ER HEATE
T
SUPPLE-
MENTAL
CONDE NSE
EVAPORAT O
TEMPE RATURE CONTRO L
13 5°F (57°C)
(32° )
Cat 605-5 9
LOA D
Heat Recovery Models
Intermediate Heat Exchanger
Ground Water Heat Source
Service Hot Water Piping
CONDENSER
EVAPORATOR
ST OR AG E
TA N K
140°F (60°C)
TEMPLIFIER
HEAT
SOURCE
140°F
(60°C)
140°F
(60°C)
RETURN /
MAKEUP
OUTP UT
STANDBY /
A UXI LI AR Y HE AT
T- C
Figure 7: Typical Templifier Applications
Heat Recovery Models
10 Cat 605-5
Controls
Controls
MicroTech® II Controls
Daikin Centrifugal chillers are equipped with the proven reliability of the MicroTech® II controls system with touch­screen interface. The control system is designed for easy and intuitive operation, and configured for efficient and reliable operation. Plus, Daikin's Open Choices™ feature allows integration with your building automation system (BAS) through an optional communication module (see Options and Accessories section, page 52).
Designed with the System Operator in Mind
Reliable, economic use of any chiller depends on an easy operator interface. That's why operation simplicity was one of the primary considerations MicroTech® II controller and Operator Interface Touch-Screen (OITS). The 15-inch color touch-screen is mounted on a fully adjustable arm. The chiller is graphically displayed, with key operating parameters viewable on the screen. Alarm history and operation setpoints are easily accessed through intuitive touch-screen buttons. The chiller operating manual is also viewable on the touch screen and can be downloaded via USB.
MicroTech® II Controls Enhance Operating Economy
Many features have been integrated into MicroTech II controls to ensure optimum operating economy. In addition to replacing normal relay logic circuits, we've enhanced the controller's energy saving capabilities with the following features:
• Direct control of water pumps Optically isolated, digital output relays provide automatic lead-lag of the evaporator and condenser pumps, permitting pump operation only when required.
• User-programmable compressor soft loading Prevents excessive power draw during pull down from high chilled water temperature conditions.
in the development of the
• Chilled-water reset Reset the leaving water temperature based on the return water temperature. Raising the chilled water setpoint during periods of light loads dramatically reduces power consumption.
• Demand limit control Maximum motor current draw can be set on the panel, or can be adjusted from a remote 4-20ma or 1-5 VDC BAS signal. This feature controls maximum demand charges during high usage periods.
• Condenser water temperature control Capable of four stages of tower fan control, plus an optional analog control of either a three-way tower-bypass valve or variable speed tower-fan motor. Stages are controlled from condenser-water temperature. The three-way valve can be controlled to a different water temperature or track the current tower stage. This allows optimum chilled water plant performance based on specific job requirements.
• Staging Options (Multiple Chiller Installations) The MicroTech® II controller is capable of compressor staging decisions and balancing compressor loads between up to four WSC,WDC or WSC Daikin chillers using defaults or operator-defined staging.
• Plotting Historic Trends Past operation of the chiller can be plotted as trend lines and even downloaded to a spreadsheet for evaluation and analysis.
Proactive Controls
MicroTech® II controls constantly monitor chiller status, and automatically take
proactive measures to relieve abnormal conditions or shut the unit down if a fault occurs. For example, if a problem occurs in the cooling tower and discharge pressure starts to rise, the controller will automatically hold the load point and activate an alarm signal. A further rise in pressure will initiate compressor unloading in an effort to maintain the setpoint pressure. If the pressure continues to rise, the unit will shut off at the cutout pressure setting to protect the unit.
Table 4: Daikin MicroTech® II Controls Features and Benefits
FEATURE BENEFIT
Open Choices™ Option
Touch-screen Interface
Alarm/Fault History and Trend Logging Historical trend data can be downloaded from an onboard USB port
Precise 0.2 F chilled water controls Provides stability in chilled water system
Proactive Controls
Integrated lead/lag pump control
Condenser Water Temperature Control Provides tower fan control /modulation based on system conditions
Multiple language capability -
Metric or IP units of measure
Cat 605-5 11
Easy integration into a building management system via a factory or field-installed
module communicating with BACnet , LONMARK or Modbus protocols.
Easy to read, adjustable, large 15-inch, color touch screen;
See chiller operation at a glance; easily view and change setpoints
Proactive correction of “unusual conditions” allows chiller to stay online; activates
alarm and modifies chiller operation to provide maximum possible cooling
Automatic control of chilled water and condenser water pumps; permits pump
operation only when required
Great asset for world-wide applications
Controls
Alarm History for Easy Troubleshooting
The controller memory can retain and display the cause of the current fault and the last twenty-five fault conditions. This feature is extremely useful for troubleshooting and maintaining an accurate record of unit performance and history.
The Home Screen shown below is the primary viewing screen on the Operator Interface Touch Screen (OITS). It gives real­time data on unit status, water temperatures, chilled water setpoint and motor amp draw.
Figure 8: OITS Home Screen
Trend Logging
Ever wonder how your chiller performed last night? Were you holding the correct chilled water temperature? What kind of cooling load did the chiller have? The Daikin MicroTech® II controller can provide the answers, thanks to its huge memory, and plot water temperatures, refrigerant pressures, and motor load data. These values can also be downloaded through a convenient USB port (located on the unit control panel) into a spreadsheet for detailed evaluation and analysis.
Figure 10: OITS Trend History Screen
If an alarm occurs, a red button appears on the screen that leads to the Active Fault Screen whichgives complete fault information so that the fault can be corrected and cleared.
Changing Setpoints
Changing setpoints is easy with the MicroTech II control. For example, to change the chilled water setpoint, press SET button from any screen, then press WATER and this screen appears, now press button #1, Leaving Water Temperature, and you are ready to input a password and a new value. (The controller features a three-level password security system to provide protection against unauthorized use.)
Figure 9: OITS Setpoint Screen
WDC/WCC Chiller Controls
Dual compressor model centrifugal chillers feature a MicroTech® II unit controller and a separate controller for each compressor. This distributed control scheme allows the operation of each compressor in Performance data for each compressor is monitored separately by each controller, and can be controlled and monitored on the interface panel.
Compressor staging and the load balance function are standard features the compressor with the fewest number of starts first, and will only start remaining compressors when sufficient load has been established. The staging function will stop the compressor with the most run-hours as the load decreases to single compressor range. During two-compressor operation, the load balance function will equalize the load between each compressor, providing optimum unit efficiency.
Versatile Communications For Even More Control
For flexibility there are three ways to interface with the MicroTech® II controller:
Direct entry via Operator Interface Touch-Screen.
Direct entry as above, plus remote digital and analog input/
of MicroTech® II controllers. Smart scheduling starts
output signals for certain functions such as enable run input, alarm signal output, chilled water reset and load limiting, outputs for pump and tower fan control, for variable speed tower fan and/or tower bypass valve.
dependently from the other.
12 Cat 605-5
Controls
Interface with a building automation system (BAS) with optional modules, communicating directly with BACnet,
have received LONMARK certification with the optional LONWORKS communication module.
LONMARK or Modbus protocols.
Protocol Options
Building Automation Systems
All MicroTech II®
controllers are capable of communication with BAS, providing seamless integration and comprehensive monitoring, control, and two-way data exchange with industry standard protocols such as LONMARK , Modbus or BACnet .
•BACnet MS/TP
•BACnet IP
• BACnet Ethernet
• LONWORKS (FTT-10A)
• Modbus RTU
Open Choices Benefits
• Easy to integrate into your building automation system
• Factory- or field-installed communication modules
The BAS communication module can be ordered factory­mounted with your chiller, or can be field-installed at any time after the chiller is installed.
• Comprehensive point list for system integration, equip­ment monitoring and alarm notification
• Comprehensive data exchange
Electric Power Options
In order for the BAS to read the full complement of power data on low and medium voltage solid state, across-the-line, and
Integration Made Easy
Daikin unit controllers strictly conform to the interoperability guidelines of the LONMARK Interoperability Association and the BACnet Manufacturers Association. They
Table 5: Typical BAS Read/Write Data Points
Typical Data Points Active Setpoint R Cond EWT R Evap Water Pump Status R Actual Capacity R Cond Flow Switch Status R Heat Recovery EWT R Capacity Limit Output R Cond LWT R Heat Recovery LWT R Capacity Limit Setpoint W Cond Pump Run Hours R Heat Setpoint W
Chiller Enable W Cond Refrigerant Pressure
Chiller Limited R Cond Sat. Refrigerant Temp
Chiller Local/Remote R Cond Water Pump Status R Liquid Line Refrigerant Temp R Chiller Mode Output R Cool Setpoint W Maximum Send Time W Chiller Mode Setpoint W Current Alarm R Minimum Send Time W Chiller On/Off R Default Values W Network Clear Alarm W Chiller Status R Evap EWT R Oil Feed Pressure R Compressor Discharge Temp R Evap Flow Switch Status R Oil Feed Temp R Compressor Percent RLA R Evap LWT for Unit R Oil Sump Pressure R Compressor Run Hours R Evap LWT for Compressor R Oil Sump Temp R Compressor Select W Evap Pump Run Hours R Outdoor Air Temp Compressor Starts R Evap Refrigerant Pressure R2 Pump Select W Compressor Suction Line Temp R Evap Sat. Refrigerant Temp R2 Run Enabled R
1.) Data points available are dependent upon options selected
2.) Per compressor
wye-delta starters, the optional Field Metering Package must be ordered with the chiller. Otherwise the BAS will only read the average unit amps. This power data is not available to a
BAS on all other starter voltages and types.
1
(W = Write, R = Read)
2
Ice Setpoint W
R
2
Liquid Line Refrigerant Pressure
R
Cat 605-5 13
Application Considerations
Application Considerations
Location
These chillers are intended only for installation in an indoor or weather protected area consistent with the NEMA 1 rating on the chiller, controls, and electrical panels. If indoor sub­freezing temperatures are possible, special precautions must be taken to avoid equipment damage. Equipment room temperature for operating and standby conditions is 40°F-
122°F (4.4°C-50°C)
CAUTION
Daikin Centrifugal Chillers are intended only for installation in indoor areas protected from temperature extremes. Failure to comply may result in equipment damage and may void the manufacturer warranty.
Operating/Standby Limits
Table 6: Operating/Standby Limits
Equipment room operating temperature: 40°-104°F (4.4°-40°C)
Equipment room temperature, standby, with water in vessels and oil cooler:
Equipment room temperature, standby, without water in vessels and oil cooler:
Maximum entering condenser water temperature, startup:
Maximum entering condenser water temperature, operating:
Minimum entering condenser water temperature, operating:
Minimum leaving chilled water temperature:
Minimum leaving chilled fluid temperature with correct anti-freeze fluid:
Maximum entering chilled water temperature, operating:
Maximum oil cooler entering temperature:
Minimum oil cooler entering temperature:
Piping
Piping must be adequately supported to remove weight and strain on the chiller's fittings and connections. Do not use PVCor CPVC piping. Be sure piping is adequately insulated. Install a cleanable 20-mesh water strainer upstream of the evaporator and condenser. Install enough shutoff valves to permit draining water from the evaporator or condenser
without draining the complete system.
CAUTION
Freeze Notice: The evaporator and condenser are not self­draining. Both must be blown out to completely remove water to help prevent freeze-up
.
Include thermometers and pressure gauges at the chiller inlet and outlet connections and air vents at the high points of piping. The water heads can be interchanged (end for end), allowing water connections to be made at either end of the
40°-104°F (4.4°-40°C)
0°F-122F (-18°C-50°C)
design + 5°F (2.7°C)
job-specific design temperature
see this page.
38°F (3.3°C)
15°F (9.4°C)
90°F (32.2°C)
80°F (26.7°C)
42°F (5.6°C)
unit. Use new head gaskets when interchanging water heads. When water pump noise is objectionable, use rubber isolation sections at both the inlet and outlet of the pump. Vibration eliminator sections in the condenser inlet and outlet water lines are not normally required. Where noise and vibration are critical and the unit is mounted on spring isolators, flexible piping and conduit connections are necessary. If not factory installed, a flow switch or pressure differential switch must be installed in the leaving chilled water line in accordance with the flow switch manufacturer's instructions.
Note: Victaulic connections are AWWA C-606. Field supply
transitions if Victaulic brand AGS® (Advanced Groove System) type grooves are used on the field piping.
Optimum Water Temperatures and Flow Rates
A key to improving energy efficiency for any chiller is minimizing the lift, or pressure difference, between the compressor suction and discharge pressures. Reducing the lift reduces the compressor work, and hence its energy consumption per unit of output. The chiller typically has the largest motor of any component in a chilled water system.
Higher leaving chilled water temperatures
Warmer leaving chilled water temperatures will raise the compressor's suction pressure and decrease the lift, improving efficiency. Using 45 F (7.0 C) leaving water instead of 42 F (5.5 C) will make a significant improvement.
Evaporator temperature drop
The industry standard has been a ten-degree temperature drop in the evaporator. Increasing the drop to 12 or 14 degrees will improve the evaporator heat transfer, raise the suction pressure, and improve chiller efficiency. Chilled water pump energy will also be reduced.
Condenser entering water temperature
As a general rule, a one-degree drop in condenser entering water temperature will reduce chiller energy consumption by two percent. Cooler water lowers the condensing pressure and reduces compressor work. One or two degrees can make a noticeable difference. The incremental cost of a larger tower can be small and provide a good return on investment.
Minimum Condenser Water Temperature Operation
When ambient wet bulb temperatures are lower than design, the condenser water temperature can be allowed to fall. Lower temperatures will improve chiller performance.
Up to 600 Tons
Daikin centrifugal chillers up to 600 Tons are equipped with electronic expansion valves (EXV) and will start and run with entering
condenser water temperatures as low as shown in Figure 11 (based on a 10 degree F condenser Delta-T) or as calculated from the following equation on which the curves are based
14 Cat 605-5
Application Considerations
LChWT
42 LChWT
Min. ECWT = 5.25 + 0.88*(LWT) - DT
FL*
(PLD/100) + 22 *(PLD/1 00)2
ECWT = E nt erin g c ond en ser water te mperat ur e LWT = Leaving chilled water temperature DT
FL
= Ch ille d Wate r D elta -T at full l oad
PL D = The pe rc ent ch ille r load poin t to b e chec ked
For example; at 44F LWT, 10 degree F Delta-
water temperature could be as low as 44.5F. This provides excellent operation with water­economizer systems.
Figure 11: Minimum Entering Condenser Water Temperature (With Electronic Expansion Valve)
Minimum Entering Condenser Water Temperature - 10 F Range
65.0
60.0
55.0
50.0
F ,
T W C
E
45.0
40.0
35.0
30.0 0 10 20 30 40 50 60 70 80 90 100 110
44
Percent Load
T, and 50% full load operation, the entering condenser
Cat 605-5 15
side
Application Considerations
44 LChW T
Over 600 Tons
Chillers over approximately 600 Tons are equipped with thermal expansion valves (TXV) and will start and run with entering condenser water temperatures as low as calculated by the following equation and shown in the chart following.
"ECWT = Entering condenser water temperature
"LWT = Leaving chilled water temperature
"DTFL = Chilled Water Delta-T at full load
"PLD = The percent chiller load point to be checked
Min. ECWT = 7.25 + LWT- 1.25* DTFL(PLD/100) +
65. 0
60. 0
55. 0
50. 0
45.0
40. 0
2
Minimu m Ent er ing C ond ens er Wate r Temp er atur e - 10 F R an ge
42
LChWT
22*(PLD/100)
Figure 12: Minimum Entering Condenser Water Temperature (Thermal Expansion Valve)
F ,
T W C
E
35. 0
30. 0 0 102030405060708090100110
Percen
t Load
For example; at 44 F LWT, 10 degree F Delta-T, and 50% full load operation, the entering condenser water temperature could be as low as 50.5 F. This provides excellent operation with water-side economizer systems.
Depending on local climatic conditions, using the lowest possible entering condenser water temperature may be more costly in total system power consumed than the expected savings in chiller power would suggest, due to the excessive fan power required.
Cooling tower fans must continue to operate at 100% capacity at low wet bulb temperatures. As chillers are selected for lower kW per ton, the cooling tower fan motor power becomes a higher percentage
of the total peak load chiller power. Daikin's Energy Analyzer program can optimize the chiller/ tower operation for specific buildings in specific locales.
Even with tower fan control, some form of water flow control, such as tower bypass, is recommended.
Condenser water temperature rise
The industry standard of 3 gpm/ton or about a 9.5-degree delta-T works well for most applications. Reducing condenser water flow to lower pumping energy will increase the water temperature rise, resulting in an increase in the compressor's
condensing pressure and energy consumption. This is usually not a productive strategy.
System analysis
Although Daikin is a proponent of analyzing the entire system, it is generally effective to place the
chiller in the most efficient mode because it is, by far, a larger energy consumer than pumps. The Daikin Energy Analyzer program is an excellent tool to investigate the entire system efficiency, quickly and accurately. It is especially good at comparing different system types and operating parameters. Contact your local Daikin sales office for assistance on your particular application.
For Best Chiller Efficiency
The designer must determine the proper chiller efficiency for a given application. The most efficient chiller is not always the best. A life cycle analysis (as performed by Daikin's Energy Analyzer program, for example) is the only way to be sure of the best selection. Utility costs, load factors, maintenance costs, cost of capital, tax bracket; in other words, all the factors affecting owning cost, must be considered.
Generally, the attempts to save the last few full load kW are very costly. For example, the cost to go from 0.58 to 0.57 kW/
16 Cat 605-5
Application Considerations
ton could be very costly because of the large number of copper tubes that would have to be added to the heat exchangers.
Table 7:
Vessel Activity Example
Evaporator
Evaporator
Evaporator Lower flow rates
Condenser
Condenser
Higher leaving water Temperatures
Higher water temperature drops
Lower entering water temperature
Higher flow rates (3.0 gpm/ ton or higher)
44F instead of 42F
12°F instead of 10°F
2.4 gpm/ton instead of
3.0 gpm/ton
84F instead of 85F
3.0 gpm/ton instead of
2.5 gpm/ton
Mixing Single and Dual Compressor Chillers
WDC dual compressor chillers excel at part load operation, while single compressor chillers usually have better full load efficiency. A good chiller plant strategy is to install one dual and one or more single compressor units. Run the dual until it is fully loaded, then switch to the single compressor unit and run it only at full load, using the dual to trim the load.
Series Counterflow and Series Parallel Chillers
The design of piping systems can greatly impact chiller performance. A popular system is to place the evaporators in series with the chilled water flowing from one evaporator to the next as shown in Figure 13 and Figure 14. Two different condenser water piping arrangements can be used. Parallel flow (Figure 13) divides the total condenser flow between the two condensers. The counterflow system (Figure 14) puts all of the condenser water through the condenser of the lag chiller (chiller producing the coldest evaporator leaving water) and then through the lead chiller (chiller seeing the warmest evaporator water temperatures).
tons) combines counterflow design into one unit. See page 6 for details.
Figure 13: Series Parallel Flow
Figure 14: Series Counterflow Flow
Typically, since the lead machine will see the warmest evaporator water, it will have the greater capacity and larger portion of the total system evaporator temperature drop. Again referring to Figure 13 and Figure 14, the lead machine has an
8.4 degree drop (56.0 degree drop (47.6
°F-47.6°F) and the lag machine has a 5.6
°F - 42.0°F).
Condenser water flow is important to overall system efficiency. With parallel flow (Figure 13), the condensers have identical flow conditions (95 to 85 degrees in this example) with the compressor lift shown. With counterflow arrangement the lift on the lead machine is significantly lower, reducing compressor work and making the overall system efficiency about 2% better. Even though the chiller performance is different, it is good practice to use the same chiller models.
Both the WSC and WDC chillers are suitable for series counterflow arrangement and include controls specifically designed for series chillers. For more information, please refer to Application guide AG -31-003: Chiller Plant Design. Daikin's model WCC dual compressor chiller (1200 to 2700
Cat 605-5 17
Application Considerations
CHILLER
OIL COOLER
STOP VALVE
STRAI NER
MAX. 40 MESH
SOLENO ID
VA LV E
DRA IN VALVE OR PLUG
PUMP
OPEN
DRAIN VALVE
OR PLUG
SOL EN OID
VA LVE
OIL COOLE R
STRAINE R
MAX. 40
MESH
DISCHARGE ABOVE HI GH EST POSSIBLE WATER LEVEL
Oil Coolers
Daikin centrifugal chillers have a factory-mounted, water­cooled oil cooler with a temperature controlled water regulating v Cooling water connections are located at the rear of the unit, near the compressor and are shown on the specific unit certified drawings. Models WDC 063 through 087 and all WCC have the cooling water connections in the lower portion of one tube sheet.
WDC 063, 079, 087, 100 and 126 dual compressor chillers are equipped as above, but the water piping for the two oil coolers is factory piped to a common inlet and outlet connection.
Field water piping to the inlet and outlet connections must be installed according to good piping practices and must include stop valves to isolate the cooler for servicing. A 1" minimum cleanable filter (40 mesh maximum) and drain valve or plug must also be field installed. The water supply for the oil cooler must be from the chilled water circuit, or from an independent clean source such as city water. When using chilled water, it is important that the water pressure drop across the evaporator is greater than the pressure drop across the oil cooler or insufficient oil cooler flow will result. If the pressure drop across the evaporator is less than the oil cooler, the oil cooler must be piped across the chilled water pump, provided that its pressure drop is sufficient. The water flow through the oil cooler will be adjusted by the unit's regulating valve so that the temperature of oil supplied to the compressor bearings (leaving the oil cooler) is between 90
C).
43
NOTE: The system must be designed for the highest cooling water temperature possible, which may occur for a short time during startup.
alve and solenoid valve for each compressor.
F and 110F (32C and
Table 9: WSC with VFD Oil Cooler Data
Hot Side POE Lub.
Cold Side Water
WSC/HSC 063 - 087
Flow, gpm 9.9 13.4 4.0 2.9 2.3 Inlet Temperature, F 118.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 90.3 99.6 103.1 105.6 Pressure Drop, ft. - 30.5 6.7 4.8 3.6
WSC/HSC 100 - 126
Flow, gpm 15.8 24.4 7.0 5.0 4.0 Inlet Temp., F 120.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 89.8 100.1 103.6 106.2 Pressure Drop, ft. - 30.6 15.7 11.4 9.3
NOTES:
1WDC and WCC units have twice the cooling water flow rate
of the comparable WSC chiller.
2
Pressure drops include valves on the unit.
When supplied with city water, the oil piping must discharge through a trap into an open drain to prevent draining the cooler by siphoning. The city water can also be used for cooling tower makeup by discharging it into the tower sump from a point above the highest possible water level.
Note: Particular attention must be paid to chillers with variable
chilled water flow through the evaporator. The pressure drop available at low flow rates can very well be insufficient to supply the oil cooler with enough water. In this case an auxiliary booster pump can be used or city water employed.
Cooling Water Connection Sizes: WDC/WCC 100/126 have 1­1/2 in. FPT connections, all other WDC and WSCs are 1 in. FPT.
Figure 15: Oil Cooler Piping Across Chilled Water Pump
Compressors using chilled water for oil cooling will often start with warm "chilled water" in the system until the chilled water loop temperature is pulled down. With cooling water in the
F to 55F (4C to 13C) range, considerably less water will
40
R
S
be used and the pressure drop will be greatly reduced. The following table contains oil cooler data at various inlet water temperatures.
Table 8: WSC Oil Cooler Data
Hot Side POE
Lube
Cold Side Water
WSC 063 - 087
Flow, gpm 9.9 11.9 2.9 2.0 1.54 Inlet Temperature, F 118.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 87.3 94.5 98.3 101.4 Pressure Drop, psi - 4.3 0.3 0.14 0.09
WSC 100 - 126
Flow, gpm 15.8 21.9 5.11 3.5 2.7 Inlet Temperature, F 120.0 80.0 65.0 55.0 45.0 Outlet Temp., F 100.0 87.0 95.0 99.0 102.3 Pressure Drop, psi - 3.78 0.23 0.11 0.07
18 Cat 605-5
Figure 16: Figure 17, Oil Cooler Piping With City Water
R
S
COOLING TOWER
COOLING TOWER MAKEUP
DRA IN
STOP VALU E
Application Considerations
5.0
2
....
2
2
2
1
 
 
n
DDD
Common
D
Pumps
Model WSC, WDC and WCC chiller compressor motors operate at 3600 rpm on 60 Hz power (3000 rpm on 50 Hz). When VFDs are employed, the hertz/speed can be reduced by 70%. To avoid the possibility of objectionable harmonics in the system piping, 4-pole, 1800/1500 rpm system pumps should be used. The condenser water pump(s) must be cycled off when the last chiller of the system cycles off. This will keep cold condenser water from migrating refrigerant to the condenser. Cold liquid refrigerant in the condenser can make start-up difficult. In addition, turning off the condenser water pump(s) when the chillers are not operating will conserve energy.
Include thermometers and pressure gauges at the chiller inlet and outlet connections and air vents at the high points of piping. The water heads can be interchanged (end for end), allowing water connections to be made at either end of the unit. Use new head gaskets when interchanging water heads. When water pump noise is objectionable, use rubber isolation sections at both the inlet and outlet of the pump. Vibration eliminator sections in the condenser inlet and outlet water lines are not normally required. Where noise and vibration are critical and the unit is mounted on spring isolators, flexible piping and conduit connections are necessary. If not factory installed, a flow switch or pressure differential switch must be installed in the leaving chilled water line in accordance with the flow switch manufacturer's instructions.
Victaulic connections are AWWA C-606 on 14-inch and larger sizes. Field supply transitions if Victaulic brand AGS® (Advanced Groove System) type grooves are used on the field piping.
Filtering and Treatment
Owners and operators must be aware that if the unit is operating wit cooling tower is required. Make sure tower blow-down or bleed-off is operating. Atmospheric air contains many contaminants, which increases the need for water treatment. The use of untreated water will result in corrosion, erosion, slime buildup, scaling, or algae formation. A water treatment service should be used. Daikin is not responsible for damage or faulty operation from untreated or improperly treated water.
Machine Room Ventilation
In the market today, centrifugal c either hermetic or open type motors. Hermetic motors are cooled with refrigerant and dissipate their heat through the cooling tower. On the other hand, open motors circulate equipment room air across themselves for cooling and reject the heat to the equipment room. Daikin chillers have hermetic motors and DO NOT require additional ventilation.
For chillers with open-drive type, air-cooled motors, good engineering practice dictates that the motor heat be removed to
h a cooling tower, cleaning and flushing the
hillers are available with
prevent high equipment room temperatures. In many applications this requires a large volume of ventilation air, or mechanical cooling to properly remove this motor heat.
EXAMPLE: 1000 tons x 0.6 kW/Ton x 0.04 motor heat loss x
0.284 Tons/kW = 7 tons (24 kW) cooling
The energy and installation costs of ventilation or mechanical cooling equipment must be considered when evaluating various chillers. For a fair comparison, the kW used for the ventilation fans, or if mechanical cooling is required, the additional cooling and fan energy must be added to the open motor compressor energy when comparing hermetic drives. Additionally, significant costs occur for the purchase, installation, and maintenance of the ventilation or air handling units.
Equipment room ventilation and safety requirements for various refrigerants is a complex subject and is updated from time to time. The latest edition of ASHRAE 15 should be consulted.
Thermal Storage
Daikin chillers are designed for use in thermal storage systems. The chillers must be considered. The first is normal air-conditioning
The second condition occurs during the ice making process when leaving fluid temperatures are in the 22
(-5.6
°C to -3.3°C) range.
The MicroTech II control system will accommodate both operating points. The ice mode can be started or stopped by an input signal to the microprocessor from a BAS or through a chilled water reset signal. When a signal is received to change from the ice mode to the normal operating mode, the chiller will shut down until the system fluid temperature rises to the higher setpoint. The chiller will then restart and continue operation at the higher leaving fluid temperature. When changing from normal cooling to the ice mode, the chiller will load to maximum capacity until the lower setpoint is reached.
Computer selections must be made to check that the chiller will operate at both conditions. If the "ice mode" is at night, the pressure differentials between the evaporator and condenser are usually similar to normal cooling applications. The leaving fluid temperature is lower, but the condensing temperature is also lower because the cooling tower water is colder. If the ice mode can also operate during the day, when cooling tower water temperatures are high, a proper selection becomes more difficult because the two refrigerant pressure differentials are significantly different.
A three-way condenser water control valve is always required.
have two operating conditions that
duty where leaving evaporator fluid temperatures range from 40 (4.4
°F to 45°F
°C to 7.2°C).
°F to 26°F
Cat 605-5 19
Application Considerations
Variable Speed Pumping
Variable speed pumping involves changing system water flow relative to cooling load change chillers are designed for this duty with two limitations.
First, the rate of change in the water flow needs to be slow, not greater than 10% of the change per minute. The chiller needs time to sense a load change and respond.
Second, the water velocity in the vessels must be 3 to 10 fps (0.91 and occurs which reduces heat transfer. Above 10 fps (3.0 m/sec), excessively high pressure drops and tube erosion occur. These flow limits can be determined from the Daikin selection program.
We recommend variable flow only in the evaporator because there is virtually no change in chiller efficiency compared to constant flow. In other words, there is no chiller energy penalty. Although variable speed pumping can be done in the condenser loop, it is usually unwise. The intent of variable flow is to reduce pump horsepower. However, reducing condenser water flow increases the chiller's condensing pressure, increasing the lift that the compressor must overcome which, in turn, increases the compressor's energy use. Consequently, pump energy savings can be lost because the chiller operating power is significantly increased.
Low condenser flow can cause premature tube fouling and subsequent increased compressor power consumption. Increased cleaning and/or chemical use can also result.
Vibration Mounting
Every Daikin chiller is run tested and compressor vibration is measured and limited to a maximum rate second, which is considerably more stringent than other available compressors. Consequently, floor-mounted spring isolators are not usually required. Rubber mounting pads are shipped with each unit. It is wise to continue to use piping flexible connectors to reduce sound transmitted into the pipe and to allow for expansion and contraction.
AHRI Standard 575 Sound Ratings
Sound data in accordance with AHRI Standard 575 for individual units are available from your local Daikin representative. Due to the large number of combinations and variety of applications, sound data is not included in this catalog.
3.0 m/sec). Below 3 fps (0.91 m/sec), laminar flow
s. Daikin centrifugal
of 0.14 inches per
component
Discharge Line Sound Packages
For extremely sensitive projects, an optional discharge line sound package is offered consisting of sound insulation installed on the unit's discharge line. An additional 2 to 4 dbA reduction normally occurs.
System Water Volume
All chilled water systems need adequate time to recognize a load change, respond to that load change and stabilize, without undesirable short cycling of the compressors or loss of control. In air conditioning systems, the potential for short cycling usually exists when the building load falls below the minimum chiller plant capacity or on close-coupled systems with very small water volumes.
Some of the things the designer should consider when looking at water volume are the minimum cooling load, the minimum chiller plant capacity during the low load period and the desired cycle time for the compressors.
Assuming that there are no sudden load changes and that the chiller plant has reasonable turndown, a rule of thumb of "gallons of water volume equal to two to three times the chilled water gpm flow rate" is often used.
A properly designed storage tank should be added if the system components do not provide sufficient water volume.
Relief Valves
Relief valve connection sizes are 1-inch quantity shown in Table 10 for the evaporator and condenser. In addition, there is a relief valve (3/8 inch flare) on the top of the oil sump of all units.
All relief valves (including the oil sump) must be piped to the outside of the building in accordance with ANSI/ASHRAE 15-
2001. The new 2001 standard has revised the calculation method compared to previous issues.
Twin relief valves, mounted on a transfer valve, are used on the condenser so that one relief valve can be shut off and removed for testing or replacement, leaving the other in operation. Only one of the two valves is in operation at any time. Where 4 valves are shown, on some large vessels, they consist of two relief valves mounted on each of two transfer valves. Only two relief valves of the four are active at any time.
FPT and are in the
20 Cat 605-5
Application Considerations
Figure 17: Typical Vent Piping
Vent piping is sized for only one valve of the set since only one can be in operation at a time.
Relief Pipe Sizing (ASHRAE Method)
Daikin centrifugal chillers have the following relief valve settings and discharge capacity:
WSC/WCC evaporator (1 valve) and condenser (2 valves piped together to common vent pipe) = 200 psi, 75.5 lb of air/min
WDC evaporator (1) = 180 psi, 68.5 lb of air/min
WDC condenser(2) = 225 psi, 84.4 lb of air/min
Note: some large condensers have 4 relief valves
Since the pressures and valve size are fixed for Daikin chillers, the ASHRAE equation can be reduced to the simple tabl
e shown below.
Table 10: Relief Valve Piping Sizes
Pipe Size inch
(NPT)
Moody Factor
Equivalent length (ft)
Note: A 1-inch pipe is too small to handle these valves. A pipe
increaser must be installed at the valve outlet.
1.25 1.5 2 2.5 3 4
0.0209 0.0202 0.0190 0.0182 0.0173 0.0163
2.2 18.5 105.8 296.7 973.6 4117.4
Per ASHRAE Standard 15, the pipe size cannot be less than the relief device. The discharge from more than one relief valve can be run into a common header, the area of which shall not be less than the sum of the areas of the connected pipes. For further details, refer to ASHRAE Standard 15.
The above information is a guide only. Consult local codes and/or latest version of ASHRAE Standard 15 for sizing data.
Relief valve pipe sizing is based on the discharge capacity for the given evaporator or condenser and the length of piping to be run.
Cat 605-5 21
Application Considerations
MODEL CODE EXAM PLE: W S C - 063M - AQ - 18S / E2012- E - 2 * A / C1812- B L Y Y - 2 * A Y Y Y R / 134B
Packaged Water Cooled Centrifugal Chiller
S = Single Compressor D = D ual Compressor C = Dual Counterflow
Hermet ic Co mpressor Model
Compressor/Impeller Code
Gear Ratio
Motor/Voltage Code
Evaporator Shell Description [Diameter (in.), Length (ft.)]
Tube Count Code
Tube Type Code
Number of Passes (1, 2, 3)
Water Inlet Location (R = Right Inlet; L = Left Inlet)
Connection Type
Condenser Shell Description [Diameter (in.), Length (ft.)]
Tube Count Code
Type Type Code
Tube Count Code (Heat Recovery Condenser)
Tube Type Code (Heat Recovery Conderser)
Number of Passes (1, 2, 3)
Water Inlet Location (R = Right Inlet; L = Left Inlet)
Connection Type
Number of Passes (Heat Recovery Condenser)
Water Inlet Location (Heat Recovery Condenser)
Connection Type (Heat Recovery Condenser)
Motor Manufacturer
Refrigeration Type (134 = HFC-134a)
COMPRESSOREVAPORATOR
CONDENSER
R
Figure 18: Chiller Identification (Code String Index)
22 Cat 605-5
Electrical Data
Wiring and Conduit
Wire sizes must comply with local and state electrical codes. Where total amperes require larger conductors than a single conduit would permit, limited by dimensions of motor terminal box, two or more conduits can be used. Where multiple conduits are used, all three phases must be balanced in each conduit. Failure to balance each conduit will result in excessive heating of the conductors and unbalanced voltage.
An interposing relay can be required on remote mounted starter applications when the length of the conductors run between the chiller and starter is excessive.
Note: On WDC and WCC dual compressor units, dual power leads are standard, requiring separate power leads properly sized and protected to each compressor starter or VFD. Separate disconnects must be used.
Use only copper supply wires with ampacity based on 75°C conductor rating. (Exception: for equipment rated over 2000 volts, 90°C or 105°C rated conductors shall be used).
Power Factor Correction Capacitors
Do not use power factor correction capacitors with centrifugal chillers with a compressor VFD. Doing so can cause harmful electrical resonance in the system. Correction capacitors are not necessary since VFDs inherently maintain high power factors.
Control Power
The 115-volt control power can be supplied from the starter or a transformer (meeting the
requirements of Daikin Starter
Electrical Data
Specification 359999 Rev 29) separate from the starter. Either source must be properly fused with 25-amp dual element fuses or with a circuit breaker selected for motor duty. If the control transformer or other power source for the control panel is remote from the unit, conductors must be sized for a maximum voltage drop of 3%. Required circuit ampacity is 25 amps at 115 volts. Conductor size for long runs between the control panel and power source, based upon National Electrical Code limitations for 3% voltage drop, can be determined from the table below.
Control Power Line Sizing
Maximum Length, ft (m)
0 (0) to 50 (15.2) 12 120 (36.6) to 200 (61.0) 6
50 (15.2) to 75 (22.9) 10 200 (61.0) to 275 (83.8) 4
75 (22.9) to 120 (36.6) 8 275 (83.8) to 350 (106.7) 3
Wire Size
(AWG)
Maximum Length, ft (m)
Notes:
1 Maximum length is the distance a conductor will traverse
between the control power source and the unit control panel.
2 Panel terminal connectors will accommodate up to
number 10 AWG wire. Larger conductors will require an intermediate junction box.
Starters and VFDs
Information on starters and VFDs can be found in Daikin Catalog CAT 608.
Wire Size
(AWG)
Cat 605-5 23
Electrical Data
NOTES for Following Wiring Diagram
1 Compressor motor starters are either factory mounted
and wired, or shipped separate for field mounting and wiring. If provided
by others, starters must comply with Daikin specification 359999 Rev 29. All line and load side power conductors must be copper.
2 If starters are freestanding, then field wiring between the
starter and the control panel is required. Minimum wire size for 115
Vac is 12 GA for a maximum length of 50 feet. If greater than 50 feet, refer to Daikin sales office for recommended wire size minimum. Wire size for 24 Vac is 18 GA. All wiring to be installed as NEC Class 1 wiring system. All 24 Vac wiring must be run in separate conduit from 115 Vac wiring. Main power wiring between starter and motor terminal is factory­installed when units are supplied with unit-mounted starters. Wiring of free-standing starter must be wired in accordance with NEC and connection to compressor motor terminals must be made with copper wire and copper lugs only. Control wiring on free-standing starters is terminated on a terminal strip in the motor terminal box (not the unit control panel). Wiring from the unit control panel to the motor terminal is done in the factory.
3 For optional sensor wiring, see unit control diagram. It is
recommended that dc wires be run separately from 115 Vac wiring.
4 Customer furnished 24 or 120 Vac power for alarm relay
coil can be connected between UTB1 terminals 84 power and 51 neutral of the control panel. For normally open contacts, wire between 82 & 81. For normally closed contacts, wire between 83 & 81. The alarm is operator programmable. The maximum rating of the alarm relay coil is 25 VA.
5 Remote on/off control of unit can be accomplished by
installing a set of dry contacts between terminals 70 and
54.
6 Evaporator and condenser flow switches are required and
must be wired as shown. If field supplied pressure differential switches are used then these must be installed across the vessel and not the pump.
7 Customer supplied 115 Vac, 20 amp power for optional
evaporator and condenser water pump control power and tower fans is supplied to unit control terminals (UTBI) 85 power / 86 neutral, PE equipment ground.
8 Optional customer supplied 115 Vac, 25 VA maximum
coil rated chilled water pump relay (EP 1 & 2) can be wired as shown. This option will cycle the chilled water pump in response to building load.
9 The condenser water pump must cycle with the unit. A
customer supplied 115 Vac 25 VA maximum coil rated
condenser water pump relay (CP1 & 2) is to be wired as shown.
10 Optional customer supplied 115 Vac, 25 VA maximum
coil rated cooling tower fan relays (CL - C4) can be wired as shown. This option will cycle the cooling tower fans in order to maintain unit head pressure.
11 Auxiliary 24 Vac rated contacts in both the chilled water
and condenser water pump starters can be wired as shown for additional protection.
12 For VFD, Wye-Delta, and solid state starters connected
to six (6) terminal motors, the conductors between the starter and motor carry phase current and their ampacity must be based on 58 percent of the motor rated load amperes (RLA) times 1.25. Wiring of free-standing starter must be in accordance with the NEC and connection to the compressor motor terminals shall be made with copper wire and copper lugs only. Main power wiring between the starter and motor terminals is factory-installed when chillers are supplied with unit­mounted starters.
13 Optional Open Choices BAS interfaces. The locations
and interconnection requirements for the various standard protocols are found in their respective installation manuals, obtainable from the local Daikin sales office and also shipped with each unit: Modbus IM 743-0LonWorks IM 735-0BACnet IM 736-0.
14 The "Full Metering" or "Amps Only Metering" option
will require some field wiring when free-standing starters are used. Wiring will depend on chiller and starter type. Consult the local Daikin sales office for information on specific selections.
24 Cat 605-5
Loading...
+ 56 hidden pages