•Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information.
•All safety information must be followed as provided in the Service Manual.
•Refer to the appropriate Parts Catalog for part number information.
•Models listed on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians only.
Goodman does not assume any responsibility for property damage or personal injury due to
improper service procedures or services performed by an unqualified person.
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
DSZC160241AA
BRAND:
D: Deluxe
Goodman ®
Brand
A: Amana®
Brand
PR ODUCT
FAMILY:
S: Split System
CO MMUNICATION
FEATURE:
C: 4 -wire
Communication
Ready
PRODUCT TYPE:
C: Condenser R-22
H: Heat Pump R-22
X: Condenser R-410A
Z: He at P ump R-4 1 0A
is registered trademark of Maytag Corporation or its related entities and is used under license. All rights reserved.
HIGH VOLTAGE!
WARNING
WARNING
WARNING
WARNING
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.
2
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
WARNING
WARNING
individuals meeting the requirements of an "entry level
technician", at a minimum, as specified by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI). Attempting to install or repair this unit without such background may result in product damage, personal injury or
death.
Installation and repair of this unit
should be performed
ONLY by
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by
Goodman for use with this unit.
WARNING
WARNING
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
To prevent the risk of property
damage, personal injury, or death,
3
PRODUCT DESIGN
Models covered by this manual come with a new 4-wire communicating PCB. When paired with a compatible communicating indoor unit and a communicating thermostat, these
models can support 4-wire communication protocol and provide more troubleshooting information. These models are also
backward compatible with the legacy thermostat wiring.
*SZC16 models are available in 2, 3, 4 and 5 ton sizes and
use R-410A refrigerant. They are designed for 208/230 volt
single phase applications.
The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then discharged out of the top of the cabinet.
These units are designed for free air discharge, so no additional resistance like duct work shall be attached.
The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type copper. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal installation is factory installed in the condensing unit. *SZC
units are charged for the matching evaporator coil and a 15
foot refrigerant line set.
Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Conditioning Contractors Association (ACCA) or equivalent. It is
the contractors responsibility to ensure the system has adequate capacity to heat or cool the conditioned space.
*SZC models use high-efficiency Copeland® scroll "Ultratech"
compressors which are specifically desgined for R-410A refrigerant. There are a number of design characteristics which
are different from the scroll compared to the traditional reciprocating compressor.
"Ultratech" Series scroll compressors with Copeland
ComfortAlert diagnostics will not have a discharge thermostat. Some of the early model scroll compressors required
discharge thermostats.
Due to their design Scroll compressors are inherently more
tolerant of small quantities of liquid refrigerant.
NOTE: Even though the compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.
"Ultratech" Series scroll compressors use "POE" or
polyolester oil which is NOT compatible with mineral oil based
lubricants like 3GS. "POE" oil must be used if additional oil
is required.
WARNING
To avoid possible injury, explosion or death, practice
safe handling of refrigerants.
This unit is for outdoor installation only. Refer to figure for
minimum clearances from the sides of the unit to full walls
and other objects.
NOTE: This unit cannot be completely enclosed. At least
one side must be unrestricted.
These clearances will help avoid air recirculation. If installing
two or more units at the same location, allow at least 24
inches between units. If only one side is restricted (for example, against the outside wall of a house), the unit may be
placed as close as 8" to that one wall.
DO NOT locate the unit:
* Directly under a vent termination for a gas appliance.
* Within 3 feet of a clothes drier vent
* Where the refreezing of defrost water would create
a hazard
* Where water may rise into the unit.
NOT
RECOMMENDED
BBB
AAAAA
C
AA
®
A
Model TypeABCAA
Residential
Light Commercial
AA
Minimu m Airflow Clearance
C
AA
AA
CC
10"10"18"20"
12"12"18"24"
B
AA
OK!
OK!
OK!
ModelDimensions - W x D x H
*SZC160241A*29 x 29 x 38¼
*SZC160361A*35½ x 35½ x 38¼
*SZC160481A*35½ x 35½ x 38¼
OK!
OK!
OK!
Operating pressures and amp draws may differ from standard reciprocating and/or scroll compressors. This information may be found in the "Cooling Performance Data" section.
610 PSIG610 PSIG610 P S IG610 PSIG
420 PSIG420 PSIG420 P S IG420 PSIG
1/61/61/61/6
1.01.21.01.2
3/8"3/8"3/8"3/8"
*SZC160241AE
*SZC160361A*
*SZC160361AE
Suct i on Li n e, Inc hes O.D. *
Refrigerant Charge
Power Supply
Minimum Circuit Ampac ity
Maximum Overcurrent Device
(1)
(2)
3/4"3/4"7/8"7/8"
153.0153.0203.0203.0
208/230-60-1208/230-60-1208/230-60-1208/230-60-1
13.915.821.920.3
20253535
Elec t rical Conduit Siz e
Power Supply (Inches)
Approximat e Shipping Weight
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the serial plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and
wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general
and electrical information.
1/2 or 3/41/2 or 3/41/2 or 3/41/2 or 3/4
208208255255
5
HEAT PUMP SPECIFICATIONS
*SZC160481A*-*SZC160601A*
Cooling Capacit y, BTUH
Compressor
R.L. A mps
L.R. A mps
Low Pressure Switch
Open
Close
High Pressure Switch
Open
Close
Condenser Fan Motor
Horsepower
F.L. Am ps
Liquid Line, Inc hes O.D.*
Suc t i on Line, Inc hes O.D.*
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the serial plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and
wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general
and electrical information.
1/2 or 3/41/2 or 3/ 41/2 or 3/4
327327296
6
HEAT PUMP SPECIFICATIONS
*SZC160601B*
Cooling Capac i ty, B TUH
Compressor
R.L. A m ps
L.R. A m ps
Low Pressure Switch
Open
Close
High Pressure Switch
Open
Close
Condenser Fan M o tor
Horsepower
F.L. Am ps
Liquid Li ne, Inc hes O.D.*
Suc tion Li ne, Inc he s O. D. *
*SZC160601B*
60,00060,000
23.028.8
118.0152.9
22 PSIG22 PSIG
50 PSIG50 PSIG
610 PSIG610 PSIG
420 PSIG420 PSIG
1/61/6
1.01.2
3/8"3/8"
1-1/8"1-1/8"
*SZC160601BC
Refrigerant Charge
Power Suppl y
Mini m um Ci rc uit Ampacit y
Maximum Overc urrent Device
(1)
(2)
273.0273.0
208/230-60-1208/230-60-1
29.837.2
5060
Elect ri c al Condui t S i ze
Power Suppl y (Inc hes)
Approx i m ate Shi pp i ng Weight
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the serial plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and
wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general
and electrical information.