Goodman *PH 16, *PH 15 Service Instructions Manual

Page 1
Service Instructions
*PH 16 PACKAGE HEAT PUMPS
*PC 15 PACKAGE COOLING
HORIZONTAL MODELS
WITH R-410A
RS6334002r1
November 2015
© 2015 Goodman Manufacturing Company, L.P.
1
Page 2
INDEX
IMPORT ANT INFORMA TION ......................................................................................................... 4 - 5
PRODUCT IDENTIFICATION - *PC15/*PH16**H41** ....................................................................... 6
PRODUCT DIMENSIONS ................................................................................................................... 7
ACCESSORIES................................................................................................................................... 8
PCCP101-103 ROOF CURB .......................................................................................................................................... 9
PCP101-103 DOWNFLOW PLENUM ............................................................................................................................ 9
PCEF101-103 ELBOW AND FLASHING KIT ............................................................................................................... 10
PCE101-103 ECONOMIZER ......................................................................................................................................... 10
PCMD101-103 DOWNFLOW MANUAL DAMPER ........................................................................................................11
GPHMD101-103 HORIZONT AL MOTORIZED DAMPER WITH DUCT FLANGE............................................................11
SQRPC SQUARE TO ROUND CONVERTER............................................................................................................... 12
SQRPCH SQUARE TO ROUND CONVERTER ............................................................................................................ 12
PCFR101-103 EXTERNAL FIL TER KIT ....................................................................................................................... 13
PRODUCT DESIGN .......................................................................................................................... 14
ELECTRICAL WIRING ................................................................................................................................................. 15
LINE VOLT AGE WIRING.............................................................................................................................................. 16
SYSTEM OPERATION ...................................................................................................................... 17
*PC15/*PH16**H41**
COOLING .................................................................................................................................................................... 17
COOLING CYCLE........................................................................................................................................................ 17
HEA TING CYCLE......................................................................................................................................................... 17
DEFROST CYCLE ....................................................................................................................................................... 18
FAN OPERA TION ........................................................................................................................................................ 18
SCHEDULED MAINTENANCE ......................................................................................................... 21
ONCE A MONTH ......................................................................................................................................................... 21
ONCE A YEAR............................................................................................................................................................. 21
TEST EQUIPMENT...................................................................................................................................................... 21
SERVICING ....................................................................................................................................... 23
COOLING/HEA T PUMP- SERVICE ANAL YSIS GUIDE ................................................................................................ 23
S-1 CHECKING VOL TAGE ........................................................................................................................................... 24
S-2 CHECKING WIRING .............................................................................................................................................. 24
S-3 CHECKING THERMOST A T , WIRING , AND ANTICIP A TOR.................................................................................... 24
S-3A Thermostat and Wiring ..................................................................................................................................... 24
S-3B Cooling Anticipator ........................................................................................................................................... 25
S-3C Heating Anticipator ........................................................................................................................................... 25
S-4 CHECKING TRANSFORMER AND CONTROL CIRCUIT ....................................................................................... 25
S-7 CHECKING CONT ACTOR AND/OR RELA YS........................................................................................................ 25
S-8 CHECKING CONT ACTOR CONT ACTS .................................................................................................................. 26
S-11 CHECKING LOSS OF CHARGE PROTECT OR ................................................................................................... 26
S-15 CHECKING CAP ACITOR ..................................................................................................................................... 26
S-15A RESIST ANCE CHECK ....................................................................................................................................... 27
S-15B CAP ACITANCE CHECK ..................................................................................................................................... 28
S-16 CHECKING MOTORS .......................................................................................................................................... 28
S-16A CHECKING F AN AND BLOWER MOTOR WINDINGS (PSC MOT ORS) ............................................................ 28
S-16D CHECKING EEM MOTORS ............................................................................................................................... 28
S-17 CHECKING COMPRESSOR WINDINGS ............................................................................................................. 29
S-17A RESIST ANCE TEST .......................................................................................................................................... 29
S-17B GROUND TEST ................................................................................................................................................. 30
2
Page 3
INDEX
S-17D Operation T est ................................................................................................................................................. 30
S-18 TESTING CRANKCASE HEA TER ........................................................................................................................ 31
S-18A CHECKING CRANKCASE HEA TER THERMOST AT........................................................................................... 31
S-21 CHECKING REVERSING V ALVE AND SOLENOID .............................................................................................. 31
S-24 TESTING DEFROST CONTROL .......................................................................................................................... 31
S-25 TESTING DEFROST THERMOST AT.................................................................................................................... 31
S-50 CHECKING HEA TER LIMIT CONTROL(S) ........................................................................................................... 32
S-52 CHECKING HEA TER ELEMENTS ........................................................................................................................ 32
S-100 REFRIGERA TION REPAIR PRACTICE............................................................................................................... 32
S-101 LEAK TESTING ................................................................................................................................................. 33
S-102 EV ACUA TION..................................................................................................................................................... 33
S-103 CHARGING ........................................................................................................................................................ 34
S-104 CHECKING COMPRESSOR EFFICIENCY ......................................................................................................... 35
S-108 SUPERHEA T ...................................................................................................................................................... 35
S-109 CHECKING SUBCOOLING ................................................................................................................................35
S-11 1 FIXED ORIFICE RESTRICTION DEVICES ......................................................................................................... 36
S-112 CHECKING RESTRICTED LIQUID LINE ............................................................................................................ 36
S-113 REFRIGERANT OVERCHARGE ......................................................................................................................... 36
S-114 NON-CONDENSABLES...................................................................................................................................... 37
S-115 COMPRESSOR BURNOUT ................................................................................................................................37
S-122 REVERSING VA LVE REPLACEMENT................................................................................................................ 37
S-125 THERMOST ATIC EXP ANSION V AL VE............................................................................................................... 40
S-200 CHECKING EXTERNAL ST A TIC PRESSURE .................................................................................................... 40
S-201 CHECKING TEMPERA TURE RISE ..................................................................................................................... 41
AIRFLOW........................................................................................................................................... 42
WIRING DIAGRAMS.......................................................................................................................... 44
GPC15[24-48]H41** .................................................................................................................................................... 44
GPC1560H41** ........................................................................................................................................................... 45
APC15[24-48]H41**..................................................................................................................................................... 46
APC1560H41**............................................................................................................................................................ 47
GPH16[24-42]H41** .................................................................................................................................................... 48
GPH1648H41** ........................................................................................................................................................... 49
APH16[24-42]H41**..................................................................................................................................................... 50
APH1648H41**............................................................................................................................................................ 51
OT18-60A OUTDOOR THERMOST A T ........................................................................................................................ 52
OT18-60A OUTDOOR THERMOST A T ........................................................................................................................ 53
SINGLE PHASE HKR/P** HEA T KITS......................................................................................................................... 54
PCE* ECONOMIZER .................................................................................................................................................... 55
SPK* - SINGLE POINT WIRING KIT........................................................................................................................... 56
3
Page 4
IMPORTANT INFORMATION
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
T
HIS UNIT SHOULD NOT BE CONNECTED TO. OR USED IN CONJUNCTION WITH, ANY DEVI CES THAT ARE NOT DESIGN CERTIFI ED FOR US E WITH THI S UNIT OR HAV E NOT BEEN TESTED AND APPROVED BY FROM THE USE OF DEVICES THAT HAVE NOT BEE N APPROVED OR CERTIFED BY
GOODMAN. SERIOUS PROPERTY DAMAGE OR PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITI ONS MAY RESULT
GOODM AN .
WARNING
T
O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, DO NOT STORE COMBUSTIBLE MATE RIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
WARNING
GOODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH
MAY RESU LT.
MANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL OR SERV ICE HEATING AND AIR CONDITIONING EQUIPMENT.
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this product. For further assistance, please contact:
GOODMAN® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at: customerservice@goodmanmfg.com
fax us at: (713) 856-1821
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.) Your telephone company will bill you for the call.
email us at: customerservice@goodmanmfg.com
AMANA® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
fax us at: (713) 856-1821
(Not a technical assistance line for dealers.)
4
is a registered trademark of Maytag Corporation or its related entities and is used under license. All rights reserved.
Page 5
IMPORTANT INFORMATION
SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
WARNING
REFRIGERANTS ARE H EAVIER T HAN AIR. THEY CAN "PUS H OUT" THE
OXYGEN IN YOUR LUNGS OR IN ANY ENCLOSED SPACE. POSSI BLE DIFFI CULTY IN BRE ATHIN G OR DEATH:
EVER PURGE REFRIGERANT INTO AN ENCLOSED ROOM OR SPACE. BY
N
LAW, ALL REFRIGERANTS MUST BE RECLAIMED.
IF AN INDOOR LEAK IS SUSPECTED, THOROUGHLY VENTIL ATE THE AREA
• BEFORE BEGINNING WORK.
IQUID REFRIGERANT CAN BE VERY COLD. TO AVOID POSSIBLE FROST-
L
BITE OR BL INDNESS, AVOID CONTACT W ITH REFR IGERANT AND WEAR
I
GLOVES AND GOGGLES. SKIN OR EYES, SEEK MEDICAL HELP IMMEDIATELY.
A
LWAYS FOLLOW
• AS POIS ONOUS GA S WILL BE PRODUC ED.
F LIQUID REFRIGERANT DOES CONTACT YOUR
EPA
REGULATIONS. NEVER BURN REFRIGERANT,
O AVO ID
T
WARNING
TO AVOID POSSIBLE EXPLOSION:
EVER APPLY FLAME OR S TEAM TO A REFRIGERAN T CYLINDER. IF YOU
N
MUST HEAT A CYLINDE R FOR FASTER CHARGING , PARTIALLY IMMERSE IT IN WARM WATER.
NEVER FILL A CYLINDE R MORE THAN 80% FULL OF LIQUID REFRIGERANT.
NEVER ADD ANYTHING OTHER THAN R-22 TO AN R-22 CYLINDER OR
R-410A TO AN R-410A CYLINDER . THE SERVICE EQUIPMENT USED MUST
BE LISTED OR CERTIF IED FOR THE TYPE OF REF RIGERANT USED.
TORE CYLINDERS IN A CO OL, DRY PLACE. NEVER USE A CYLIND ER
S
AS A PLATFORM OR A ROLLER.
WARNING
TO AVOID POSSIBLE EXPLOSION, USE ONLY RETURNABLE (NOT DISPOSABLE)
SERVICE CYLINDERS WHEN REMOVING REFRIGERANT FROM A SYSTEM.
ENSURE THE CYLINDER IS FREE OF DAMAGE WHICH COULD LEAD TO A
LEAK OR EX PLOS ION.
ENSURE THE HYDROST ATIC TEST DATE DOES NO T EXCEED 5 YEARS.
ENSURE THE PRESSURE RATING MEETS OR EXCEEDS 400 LBS.
WHEN IN DOUBT, DO NOT USE CYLINDER.
WARNING
WARNING
SYSTEM CONTAMINANTS, IMPROPER SERVICE PROCEDURE AND/OR PHYSICAL
ABUSE AFFECTING HERMETIC COMPRESSOR ELE CTRICAL TERMINALS MAY CAUSE DANGEROUS SYSTEM VENTING.
The successful development of hermetically sealed refrig­eration compressors has completely sealed the compressor's moving parts and electric motor inside a common housing, minimizing refrigerant leaks and the hazards sometimes as­sociated with moving belts, pulleys or couplings.
Fundamental to the design of hermetic compressors is a method whereby electrical current is transmitted to the com­pressor motor through terminal conductors which pass through the compressor housing wall. These terminals are sealed in a dielectric material which insulates them from the housing and maintains the pressure tight integrity of the her­metic compressor. The terminals and their dielectric em­bedment are strongly constructed, but are vulnerable to care­less compressor installation or maintenance procedures and equally vulnerable to internal electrical short circuits caused by excessive system contaminants.
T
O AVOID POSSIBLE INJURY, EXPLOSION OR DEATH, PRACTICE SAFE
HANDLING OF REFRIGERANTS.
In either of these instances, an electrical short between the terminal and the compressor housing may result in the loss of integrity between the terminal and its dielectric embed­ment. This loss may cause the terminals to be expelled, thereby venting the vaporous and liquid contents of the com­pressor housing and system.
A venting compressor terminal normally presents no danger to anyone, providing the terminal protective cover is properly in place.
If, however, the terminal protective cover is not properly in place, a venting terminal may discharge a combination of
(a ) hot lubricating oil and refrigerant (b ) flammable mixture (if system is contaminated
with air)
in a stream of spray which may be dangerous to anyone in the vicinity. Death or serious bodily injury could occur.
Under no circumstances is a hermetic compressor to be elec­trically energized and/or operated without having the terminal protective cover properly in place.
See Service Section S-17 for proper servicing.
5
Page 6
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information.
PC1524 H 41 * *G / A
BRAND:
G: Goodm an
Brand or Distinctions
A: Ama n a
®
®
®
PRODUCT
TYPE:
Package
Cooling/Heating
15: 15 SEER Rat ing 16: 16 SEER Rat ing
PRODUCT
FAMILY:
C: Co ol i n g H: He at Pump
PRODUCT
SERIES:
24: 24, 000 BTUH 30: 30, 000 BTUH 36: 36, 000 BTUH 42: 42, 000 BTUH 48: 48, 000 BTUH 49: 48, 000 BTUH 60: 60, 000 BTUH
NOMINAL
CAPACITY:
MINOR
REVISION:
CONFIGURATION:
H: Horiz ont al
MAJOR
REVISION:
REFRIGERANT:
4: R-410A
VOLTAGE:
1: 208-230V /1ph/60Hz 3: 208-230v/3ph/60Hz 4: 460v/3ph/60Hz
MODEL # PACKAG E COOLING/ HEATING D ESCR IPTION
*PC1524-60H41AA
*PH1624-48H41AA
*PC1524-60H41AB
*PH1624-48H41AB
6
mana® Br and/Goodman
A
15 Seer 20 8- 2 30/1/ 60 S in gle-Phase Elec tric Cooling Unit with R-410A.
Initial release of the 15 SE ER H model cooling units to meet Ready 15 requirements.
mana® Br and/Goodman
A
16 Seer 20 8- 2 30/1/60 Single-Phase Heat Pump with R- 410 A.
Initial release of the 15 SE ER H model cooling units to meet Ready 15 requirements.
mana® Br and/Goodman
A
15 Seer 20 8- 2 30/1/ 60 S in gle-Phase Elec tric Cooling Unit with R-410A.
R e lease of models wi th ac cess box remo ved.
mana® Br and/Goodman
A
16 Seer 20 8- 2 30/1/60 Single-Phase Heat Pump with R- 410 A.
R e lease of models wi th ac cess box remo ved.
®
Bran d or D istinct ions
®
Bran d or D istinct ions
®
Bran d or D istinct ions
®
Bran d or D istinct ions
®
Package Cooling -
®
Package Heat Pump -
®
Package Cooling -
®
Package Heat Pump -
Page 7
PRODUCT DIMENSIONS
(
)
A
BACK EW
DUCT OPENINGS
VI
Chassis Model A B
*PC1524 22 30
Small
*PC1530 22 30 *PC1536 22 30 *PC1542 22 30
Medium
Dimensions in inches
*PC1548 24 35 *PC1560 24 35
B
Chassis Model A B
Medium
Dimensions in inches
Small
*PH162441** 22.000 29.932 *PH163041** 22.000 29.932 *PH163641** 24.000 34.932 *PH164241** 24.000 34.932 *PH164841** 24.000 34.932
7
Page 8
ACCESSORIES
Part Numb er D escr iption
OT18-60A OT/ HE R- 60A Outdoo r Thermost at wit h Emergenc y Heat Relay
HKR05A, 08, 10, CA Heater K it for all *PC/ *P H ( H) S er ies HKP05C, 10C Heater Kit for all *PC/*PH (H) Series HKP15* Heater k it f or *P C/*PH13/ 14 ( 30- 60) ( H) S er ie s HKP20* Heater K it for *PC/ *P H1 3/14 (42- 60) ( H) S er ies PCCP101- 103 Roof Curb PCP101-103 Downflow Plenum Kit PCP101-103R8 Downflow Plenum Kit w/ R-8 Insulation GP CE D101- 103 Downflow E c onomizer for H Ser ies Pac k age Units (A/ C) - To Be Use d W ith PCP101-103 GP HE D101- 103 Downflow E c onomizer for H Se r ies Pack age Units (Heat Pump) - To Be Used With PCP101- 103 GP CE H101- 103 Horizontal Economizer for H S er ies Pack age Un its (A /C) GP HE H101- 103 Horizontal Economizer for H S er ies Pack age Units (Heat P ump) PCMD101-103 Manual Damper - To Be Used With PCP101- 103 PCMDM101- 10 3 Motorized Damper - To B e Used With PCP101-103 GP HMD101-103 Manual Damper for Hor izontal Applications SPK* Single Point Wiring Kit SQ RP CH101 Square to Round Adapters 16"& 14 " SQ RP CH102- 103 Square to Round Adapters 18"&14" SQ RP C101 Square to Round Adapter - For Use Wit h P CCP 101- 103 Cur b 16" Rounds SQ RP C102- 103 Square to Round Adapter For Use Wit h PCCP101- 103 Cur b 18" Rounds PCF R101- 103 External Horizontal F ilter Rack PCEF101-103 Elbow & Flashing w/ R- 8 Li ner CDK36 Flush Mount Concent ric Duct K it CDK36515 Flush Mount Concent ric Duct K it w/ Filt er CDK36530 Ste p Down Conc entric Duc t Kit CDK36535 Ste p Down Conc entric Duc t Kit w/ Filter CDK4872 Flush Mount Concent ric Duct Kit CDK4872515 Flush Mount Concent r ic Duc t Kit w/ Filter CDK4872530 St ep Down Conc entric Duct K it CDK4872535 St ep Down Conc entric Duct K it w/ Filt er
*PC15/*PH16**H41*
ACCES SO RIES *PC/* PH H SERIES
Outdoor Thermostat ( Requ ir ed for heat pumps with 0° outdoor ambient and 50% or higher r e lative humidity.
GOODMAN® BRAND THERMOSTAT S
CH70TG Manual Changeover
CHSATG Man ua l Cha ng eover Mechanical, Nonprogram m a bl e 1 Heat - 1 Cool
CHT18-60 Manual Changeover
CHT90-120 Manual Changeover
CHTP18- 60HD Manual Changeover
CT18-60 Manual Changeover
1213401 White Manual Changeover 1213402 White Manual Changeover 1213403 White Manual Changeover 1213404 White Manual Changeover 1213406 1213407 1213408 1213410 1213411 1213412 1213431
Beige White
White White White White
White
Manual/Auto Changeover
Manual/Auto Changeover
Manual/Auto Changeover Manual/Auto Changeover
8
Digital, Nonprogrammab le 1 Heat - 1 Cool
Mechanical, Nonprogram m a bl e 1 Heat - 1 Cool Mechanical, Nonprogram m a bl e 2 Heat - 2 Cool
Digital, Nonprogrammab le 2 Heat - 1 Cool
Mechanical, Nonprogr am m a bl e Cool Only
AMANA® BRAND THERMOSTATS
5 + 2 Programming Digital 1 Heat - 1 Cool
Nonprogrammable Digital 1 Heat - 1 Cool
7 Day Programming Digital 2 Heat - 1 Cool
Nonprogrammable Digital 2 Heat - 1 Cool
5 + 2 Programming Digital 3 Heat - 2 Cool
Manual Changeover
Manual Changeover Manual Changeover
5 + 2 Programming Digital 2 Heat - 2 Cool
7 Day Programming Digital 1 Heat - 1 Cool
5 + 2 Programming Digital 2 Heat - 1 Cool
Nonprogrammable Digital 2 Heat - 2 Cool 7 Day Programming Digital 3 Heat - 2 Cool 7 Day Programming Digital 3 Heat - 2 Cool
Page 9
ACCESSORIES
33"
*PC15/*PH16H41*
PCCP101-103 ROOF CURB
64"
59"
29 3/8"
29 3/4"
33"
28 3/4"
31"
26"
PCP101-103 DOWNFLOW PLENUM
(Use with PCCP Roof Curb)
14"
1" Flange
Roof Curb
13"
37"
25 1/2"
33"
13"
9
Page 10
ACCESSORIES
*PC15/*PH14641*
PCEF101-103 ELBOW AND FLASHING KIT
28"
35"
25"
33"
3"
4"
20 3/8"
17 3/4"
4"
25"
8"
PCE*101-103 ECONOMIZER*
(DOWNFLOW APPLICATIONS)
5"
27 3/4"
16 1/2"
17 3/4"
20" x 17 1/2"
10
Filter
3"
31 1/4"
Model Used With
PCEC101-103* *PC HORIZONTAL A/C PCEH101-10 3* *P H HO RIZONTAL HP
*Must be used with PCP101-103
Page 11
ACCESSORIES
PCMDM101-103 DOWNFLOW MOTORIZED DAMPER*
2
1
PCMD101-103 DOWNFLOW MANUAL DAMPER*
*USED WITH PCP101-103 DOWNFLOW PLENUM
"
8
/
1
*PC15/*PH16H41*
6"
10"
29 3/4"
MODEL DESCRIPTION
PCM DH 101 - 103 Ma nua l Dampe r
PCMDM101-103 Motorzie d Damper
GPHMD101-103 HORIZONTAL MANUAL DAMPER WITH DUCT FLANGE
18"
8
1
/
4
"
18"
25 1/4"
2"
12"
6"
17"
17 1/4"
11
Page 12
ACCESSORIES
"
A
*PC15/*PH16H41*
SQRPC SQUARE TO ROUND CONVERTER
(DOWNFLOW APPLICATIONS)
1" FLANGES
1 1/2
SA
RA
OUTER FLANGE
29 1/2"
29 1/4"
SA 16" 18" RA 16" 18"
SQRPCH SQUARE TO ROUND CONVERTER
(HORIZONTAL APPLICATIONS)
SQUARE TO ROUND DUCT CONVERTER PANEL
BEAD
A
SQR PC101 SQRP102-103
C
2"
RETURN
STARTER FLANGE
SQRPCH-101 SQRPCH-102 SQRPCH-103 SQRPCH102-14 SQRPCH103-14
15" 17" 17" 15" 15"
B 15" 17" 17" 15" 15" C 17" 17" 19" 15" 15" D 22 1/2" 24 1/2" 24 1/2" 24 1/2" 24 1/2"
SUPPLY 14" 16" 16" 14" 14"
RETURN 16" 16" 18" 14" 14"
12
2"
SUPPLY
B
D
Page 13
ACCESSORIES
*PC15/*PH16H41*
PCFR101-103 EXTERNAL FILTER KIT
(HORIZONTAL APPLICATIONS)
14" x 25" x 2" FILTER
13
Page 14
PRODUCT DESIGN
LOCATION & CLEARANCES
NOTE: To ensure proper condensate drainage, unit must be in­stalled in a level position.
In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top installations) the installer must provide a service platform for the service person with rails or guards in accordance with local codes or ordinances.
48” MIN.
10"
36"
36"
*PC15/*PH16**H41*
WALL
UNIT
36"
NOTE: Roof overhang should be no more than 36" and provisions made to deflect the warm discharge air out from the overhang.
Minimum clearances are required to avoid air recirculation and keep the unit operating at peak efficiency.
WARNING
TO PREVENT POSSIBLE DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERA TIONS. TO F ACILITATE LIFTING AND MOVING IF A CRANE IS USED, PLACE THE UNIT IN AN ADEQUA TE CABLE SLIDE.
Refer to Roof curb Installation Instructions for proper curb in­stallation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.
Roof Curb and Platform
*PC15/*PH16**H41*
*PC15/*PH16 Package Units are designed for outdoor installa­tions only in either residential or light commercial applications.
NOTE: To ensure proper condensate drainage, unit must be in­stalled in a level position.
The connecting ductwork (Supply and Return) can be connected for horizontal discharge airflow. In the down discharge applica­tions, a matching Platform/Roof Curb (PCCP101-103) and Downflow Plenum (PCP101-103) is recommended for horizon­tal models only.
A return air filter must be installed behind the return air grille(s) or provision must be made for a filter in an accessible location within the return air duct. The minimum filter area should not be less than those sizes listed in the Specification Section. Under no circumstances should the unit be operated without return air filters.
A 3/4" - 14 NPT drain connector is provided for removal of con­densate water from the indoor coil. In order to provide proper condensate flow, do not reduce the drain line size.
Refrigerant flow control is achieved by use of restrictor orifices. These models use the FasTest Access Fitting System, with a saddle that is either soldered to the suction and liquid lines or is fastened with a locking nut to the access fitting box (core) and then screwed into the saddle. Do not remove the core
from the saddle until the refrigerant charge has been removed. Failure to do so could result in property dam­age or personal injury.
The single phase units use permanent split capacitors (PSC) design compressors. Starting components are therefore not required. A low MFD run capacitor assists the compressor to start and remains in the circuit during operation.
The outdoor fan motor is a single phase capacitor type motors.
14
Page 15
PRODUCT DESIGN
Air for condensing (cooling) is drawn through the outdoor coil by a propeller fan, and is discharged vertically out the top of the unit. The outdoor coil is designed for .0 static. No addi­tional restriction (ductwork) shall be applied.
Conditioned air is drawn through the filter(s), field installed, across the evaporator coil and back into the conditioned space by the indoor blower.
COMPRESSORS
Some H series package units use the Compliant Scroll com­pressor, instead of traditional reciprocating compressors. Still other models use reciprocating compressors.
A scroll is an involute spiral which, when matched with a mat­ing scroll form as shown, generates a series of crescent shaped gas pockets between the two members.
During compression, one scroll remains stationary (fixed scroll) while the other form (orbiting scroll) is allowed to orbit (but not rotate) around the first form.
INDOOR BLOWER MOTOR
All *PC15/*PH16 model package units use a EEM blower mo­tor. The EEM motor is a 3 Phase brushless DC (single phase AC input), ball bearing construction motor with an integral con­trol module with an internal FCC B EMI filter.
The EEM motor is continuously powered with line voltage. The switched 24 volt control signal is controlled by the thermostat in the cooling and heat pump mode.
ELECTRICAL WIRING
The units are designed for operation at the voltages and hertz as shown on the rating plate. All internal wiring is complete. Ensure the power supply to the compressor contactor is brought to the unit as shown on the supplied unit wiring diagram. The 24V wiring must be connected between the unit control panel and the room thermostat.
WARNING
TO AVOID PERSONAL IN JURY OR D EATH DUE TO ELECTRIC SHOCK, WI RI NG TO THE UNI T MUST BE PROPERLY POLARI ZED AND G ROUNDED.
As this motion occurs, the pockets between the two forms are slowly pushed to the center of the two scrolls while simulta­neously being reduced in volume. When the pocket reaches the center of the scroll form, the gas, which is now at a high pressure, is discharged out of a port located at the center.
During compression, several pockets are being compressed simultaneously, resulting in a very smooth process. Both the suction process (outer portion of the scroll members) and the discharge process (inner portion) are continuous.
Some design characteristics of the Compliant Scroll compres­sor are:
Compliant Scroll compressors are more tolerant of liquid refrigerant.
NOTE: Even though the compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued floodback or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure.
These scroll compressors use POE or polyolester oil which is NOT compatiable with mineral oil based lubricants like 3GS. POE oil must be used if additional oil is required.
Compliant scroll compressors perform "quiet" shutdowns that allow the compressor to restart immediately without the need for a time delay. This compressor will restart even if the system has not equalized.
NOTE: Operating pressures and amp draws may differ from standard reciprocating compressors. This information can be found in the unit's Technical Information Manual.
WARNING
WARNING
TO AVOID THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY OR FIRE, USE ONLY COPPER CONDUCTORS.
LINE VOLTAGE WIRING
Power supply to the unit must be N.E.C. Class 1, and must comply with all applicable codes. The unit must be electrically grounded in accordance with the local codes or, in their ab­sence, with the latest edition of the National Electrical Code, ANSI/NFPA No. 70, or in Canada, Canadian Electrical Code, C22.1, Part 1. A fused disconnected must be provided and sized in accordance with the unit minimum circuit ampacity.
The best protection for the wiring is the smallest fuse or breaker which will hold the equipment on line during normal operation without nuisance trips. Such a device will provide maximum circuit protection.
15
Page 16
PRODUCT DESIGN
WARNING
DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON THE UNI T DATA PLATE.
All line voltage connections must be made through weather proof fittings. All exterior power supply and ground wiring must be in approved weather proof conduit. Low voltage wiring from the unit control panel to the thermostat requires coded cable.
The unit transformer is connected for 230V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram.
If it is necessary for the installer to supply additional line volt­age wiring to the inside of the package unit, the wiring must comply with all local codes. This wiring must have a minimum temperature rating of 105°C. All line voltage splices must be made inside the unit or heat kit control box.
EXPANSION VALVE (TXV) SYSTEM
SINGLE SPEED APPLICATION (APH1624-42)
1. Purge gauge lines. Connect service gauge manifold to access fittings. Run system at least 10 minutes to allow pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near liquid line access fitting with adequate contact and insu­late for best possible reading.
3. Check subcooling and superheat. Systems with TXV ap­plication should have a subcooling and superheat within the range listed on the chart.
a. If subcooling and superheat are low, adjust TXV then
check subcooling.
b. If subcooling is low and superheat is high, add charge
to raise subcooling then check superheat.
c. If subcooling and superheat are high, adjust TXV valve
then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV
valve superheat and remove charge to lower the subcooling.
The TXV should NOT be adjusted at light load conditions 55º to 60ºF, under such conditions only the subcooling can be evaluated. This is because suction pressure is dependent on indoor air flow, and wet bulb temperature.
TWO SPEED APPLICATION (APH1648 / APC1560)
Run the unit on low stage cooling for 10 minutes until refrigerant pressures stabilize. Follow the guidelines and methods below to check unit operation and ensure that the refrigerant charge is within limits. Charge the unit on low stage.
1. Purge gauge lines. Connect service gauge manifold to access fittings. Run system at least 10 minutes to allow pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near liquid line access fitting with adequate contact and insu­late for best possible reading.
3. Check subcooling and superheat. Two stage systems run­ning on low stage with TXV application should have a subcooling and superheat within the range listed on the chart.
NOTE: Do NOT adjust charge based on suction pressure unless there is a gross undercharge.
4. Disconnect manifold set. Installation is complete.
16
Page 17
PRODUCT DESIGN
SATURATED
SUCTION PRESSURE
TEMPERATURE CHART
SATURATED
SUCTION
PRESSURE
PSIG R-410A PSIG R-410A
50 1 200 70
52 3 210 73
54 4 220 76
56 6 225 78
58 7 235 80
60 8 245 83
62 10 255 85
64 11 265 88
66 13 275 90
68 14 285 92
70 15 295 95
72 16 305 97
74 17 325 101
76 19 355 108
78 20 375 112
80 21 405 118
85 24 415 119
90 26 425 121
95 29 435 123
100 31 445 125
110 36 475 130
120 41 500 134
130 45 525 138
140 49 550 142
150 53 575 145
160 56 600 149 170 60 625 152
Suction Pressure
SUCTION
TEMPERATURE
ºF
PRESSURE
TABLE 6
SATURATED
LIQUID PRESSURE
TEMPERATURE CHART
SATURATED
LIQUID
LIQUID
TEMPERATURE
Liquid Pressure
GPC15
Design Superheat @ 95°F Outdoor Ambient
Tempe rature
ºF
Model #
Superheat
±2°F
Supercooling ±2°F
GPC1524H41 ---
GPC1530H41 ---
GPC1536H41 12° ---
GPC1542H41 ---
GPC1548H41 10° ---
GPC1560h41 12° 12°
GPH16
Design Superheat @ 95°F Outdoor Ambient
Tempe rature
Model #
Superheat
±2°F
Supercooling ±2°F
GPH1524H41 15°
GPH1530H41 15°
GPH1536H41 10° 13°
GPH1542H41 12° 13°
GPH1548H41 15° 15°
SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION
TEMP.
17
Page 18
SYSTEM OPERATION *PC15/*PH16**H41*
SYSTEM OPERATION
COOLING
The refrigerant used in the system is R-410A. It is a clear, colorless, non-toxic and non-irritating liquid. R-410A is a 50:50 blend of R-32 and R-125. The boiling point at atmospheric pressure is -62.9°F.
A few of the important principles that make the refrigeration cycle possible are: heat always flows from a warmer to a cooler body. Under lower pressure, a refrigerant will absorb heat and vaporize at a low temperature. The vapors may be drawn off and condensed at a higher pressure and tempera­ture to be used again.
The indoor evaporator coil functions to cool and dehumidify the air conditioned spaces through the evaporative process taking place within the coil tubes.
Heat is continually being transferred to the cool fins and tubes of the indoor evaporator coil by the warm system air. This warming process causes the refrigerant to boil. The heat re­moved from the air is carried off by the vapor.
As the vapor passes through the last tubes of the coil, it becomes superheated. That is, it absorbs more heat than is necessary to vaporize it. This is assurance that only dry gas will reach the compressor. Liquid reaching the compressor can weaken or break compressor valves.
The compressor increases the pressure of the gas, thus add­ing more heat, and discharges hot, high pressure superheated gas into the outdoor condenser coil.
In the condenser coil, the hot refrigerant gas, being warmer than the outdoor air, first loses its superheat by heat trans­ferred from the gas through the tubes and fins of the coil. The refrigerant now becomes saturated, part liquid, part vapor and then continues to give up heat until it condenses to a liquid alone. Once the vapor is fully liquefied, it continues to give up heat which subcools the liquid, and it is ready to repeat the cycle.
COOLING CYCLE
COOLING ONLY MODELS
When the contacts of the room thermostat close, making terminals R to Y and R to G, the low voltage circuit to the contactor is completed starting the compressor and outdoor fan motor. This also energizes the indoor blower through the 24V signal from the thermostat.
When the thermostat is satisfied, breaking the circuit be­tween R to Y and R to G, the compressor and outdoor fan motor will stop. The indoor blower will stop after the fan off delay.
If the room thermostat fan selector switch should be set to the "on" position then the indoor blower would run continu­ous rather than cycling with the compressor.
HEAT PUMP MODELS
Any time the room thermostat is switched to cool, the O terminal is energized. This energizes the 24 volt coil on the reversing valve and switches it to the cooling position.
When the contacts of the room thermostat close, this closes the circuit from R to Y and R to G in the unit.
This energizes the compressor contactor and will energize the indoor blower instantly on models equipped with EEM blower motor.
When the thermostat is satisfied, it opens its contacts break­ing the low voltage circuit causing the compressor contactor to open and indoor fan to stop after the programmed 60 sec­ond off delay on models equipped with EEM blower motors.
If the room thermostat fan selector switch should be set to the "on" position then the indoor blower would run continu­ous rather than cycling with the compressor.
HEATING CYCLE
COOLING ONLY UNITS
NOTE: The following only applies if the cooling only unit has an approved electric heat kit installed for heating. If auxiliary electric heaters should be used, they may be controlled by outdoor thermostats (OT18-60A or OT/EHR18-60A).
*PC MODELS EQUIPPED WITH EEM BLOWER MO­TORS
With the thermostat set to the heat position and a call for heat, R to W will be energized. This will energize the electric heat sequencers and the EEM motor. The electric heat will be energized through the normally open contacts of the elec­tric heat sequencers. The indoor blower will be energized through W from the thermostat.
When the thermostat is satisfied, this breaks the circuit from R to W. This will turn off the electric heaters, and the indoor blower after the programmed 60 second off delay.
HEAT PUMP UNITS
On a call for first stage heat, the contacts of the room ther­mostat close. This energizes terminals R to Y and R to G, the low voltage circuit to the contactor is completed starting the compressor and outdoor fan motor. This also energizes the indoor blower instantly on models equipped with EEM blower motors.
When the thermostat is satisfied, breaking the circuit be­tween R to Y and R to G, the compressor and outdoor fan motor will stop after the programmed 60 second off delay on models equipped with EEM blower motors .
When auxiliary electric heaters are used, a two stage heat­ing single stage cooling thermostat would be installed.
Should the second stage heating contacts in the room ther­mostat close, which would be wired to W1 at the unit low voltage connections, this would energize the coil(s) of the electric heat relay(s). Contacts within the relay(s) will close, bringing on the electric resistance heaters.
If auxiliary electric heaters should be used, they may be con­trolled by outdoor thermostats (OT18-60A or OT/EHR18-60A).
EMERGENCY HEAT MODE (HEAT PUMPS)
NOTE: The following only applies if the unit has an approved electric heat kit installed for auxiliary heating.
18
Page 19
SYSTEM OPERATION
*PH MODELS EQUIPPED WITH EEM BLOWER MO­TORS
With the thermostat set to the emergency heat position, R to W1 will be energized. This will energize the electric heat se­quencers and the EEM gized through the normally open contacts of the electric heat sequencers. The indoor blower will be energized through W from the thermostat.
DEFROST CYCLE
PACKAGE HEAT PUMPS
The defrosting of the outdoor coil is jointly controlled by the defrost control board and the defrost thermostat.
SOLID STATE DEFROST CONTROL
During operation the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of 30, 60, or 90 minutes may be selected by setting the circuit board jumper to 30, 60, or 90 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately 32
motor. The electric heat will be ener-
+ 2° F), and when the room thermostat
*PC15/*PH16**H41*
calls for heat. At the end of the timing period, the unit’s defrost cycle will be initiated provided the sensor remains closed. When the sensor opens (approximately 60° F), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor tem­perature, a twelve minute override interrupts the unit’s defrost period.
FAN OPERATION
CONTINUOUS FAN MODE MODELS EQUIPPED WITH EEM BLOWER MOTORS
If the thermostat calls for continuous fan, the indoor blower will be energized from the G terminal of the thermostat to the EEM blower motor.
If a call for heat or cool occurs during a continuous fan call, the EEM motor will always recognize the call for the highest speed and ignore the lower speed call.
If the thermostat is not calling for heat or cool, and the fan switch on the thermostat is returned to the automatic posi­tion, the fan will stop after the programmed 60 second off delay on units with the EEM motor.
ECM MOTOR
SPEED ADJUSTMENT
Each ECM blower motor has been preprogrammed for operation at 4 distinct air flow levels when operating in Cooling/Heat Pump mode or Electric Heat mode. These 4 distinct levels may also be adjusted slightly lower or higher if desired. The adjustment between levels and the trim adjustments are made by changing the dip switch(s) either to an "OFF" or "ON" position.
DIP SWITCH FUNCTIONS
The ECM motor has an electronic control that contains eight (8) 2-position dip switches. The function of these dip switches is shown in Table 6, Airflow charts pages 42 and 43.
For APC15 / APH16 [24-36] models, dip switch 4 must be set to ON. Dip switch 4 must be set to OFF for two-stage compressor models APC15 / APH16 [48-60]. Dip switch 4 ON energizes Y1 signal to the ECM motor anytime Y/Y2 is energized. The indoor motor will not operate properly if switch is not set correctly for the model.
THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 50% of the high stage cooling setting.
HUMIDITY CONTROL
When using a Humidistat (normally closed), cut jumper PJ6 on the control board. The Humidistat will only affect both low stage and high stage cooling air flow by adjusting the Air flow to 85%.
TWO-STAGE HEATING
When using staged electric heat, cut jumper PJ4 on the control board.
THERMOSTAT WIRING
Use thermostat wiring diagrams provided with the thermostat when making these connections.
DIP SWITCH NUMBER FUNCTION
1 2 3N/A 4Indoor Thermostat 5 6 7 8
TABLE 6
Electric Heat
Coo l i ng & He a t Pump CFM
CFM Trim Ad just
19
Page 20
SYSTEM OPERATION
TYPICAL PACKAGE COOLING
Indoor
Coil
RESTRICTOR ORIFICE ASSEMBLY IN COOLING OPERATION
Outdoor
Coil
Chatleff
Orifice
Assy
In the cooling mode the orifice is pushed into its seat forcing refrigerant to flow through the metered hole in the center of the orifice.
20
Page 21
SYSTEM OPERATION
TYPICAL HEAT PUMP SYSTEM IN COOLING
Reversing Valve
(Energized)
Indoor
Coil
Accumulato r
TYPICAL HEAT PUMP SYSTEM IN HEATING
Outdoor
Coil
Indoor
Coil
Accumulato r
Reversing Valve
(De-Energized)
Outdoor
Coil
21
Page 22
SCHEDULED MAINTENANCE
The owner should be made aware of the fact, that, as with any mechanical equipment the Package Cooling and Heat Pump units require regularly scheduled maintenance to preserve high performance standards, prolong the service life of the equip­ment, and lessen the chances of costly failure.
In many instances the owner may be able to perform some of the maintenance; however, the advantage of a service con­tract, which places all maintenance in the hands of a trained serviceman, should be pointed out to the owner.
WARNING
ONCE A MONTH
1. Inspect the return filters of the evaporator unit and clean or change if necessary.
NOTE: Depending on operation conditions, it may be necessary to clean the filters more often. If permanent type filters are used, they should be washed with warm water, dried and sprayed with an adhesive according to manufacturers recommendations.
2. When operating on the cooling cycle, inspect the conden­sate line piping from the evaporator coil. Make sure the piping is clear for proper condensate flow.
ONCE A YEAR
Qualified Service Personnel Only
1. Clean the indoor and outdoor coils.
2. Clean the casing of the outdoor unit inside and out .
3. Motors are permanently lubricated and do not require oil­ing. TO AVOID PREMATURE MOTOR FAILURE, DO NOT OIL.
4. Manually rotate the outdoor fan and indoor blower to be sure they run freely.
5. Inspect the control panel wiring, compressor connections, and all other component wiring to be sure all connections are tight. Inspect wire insulation to be certain that it is good.
6. Check the contacts of the compressor contactor. If they are burned or pitted, replace the contactor.
7. Using a halide or electronic leak detector, check all piping and etc. for refrigerant leaks.
8. Check the combustion chamber (Heat Exchanger) for soot, scale, etc. Inspect all burners for lint and proper position­ing.
9. Start the system, using the proper instrumentation check gas inlet and manifold pressures, burner flame and microamp signal. Adjust if necessary.
10.Start the system and run both a Cooling & Heating Perfor­mance Test. If the results of the test are not satisfactory, see the "Service Problem Analysis" Chart of the possible cause.
TEST EQUIPMENT
Proper test equipment for accurate diagnosis is as essential as regular hand tools.
The following is a must for every service technician and service shop:
1. Thermocouple type temperature meter - measure dry bulb temperature.
2. Sling psychrometer- measure relative humidity and wet bulb temperature.
3. Amprobe - measure amperage and voltage.
4. Volt-Ohm Meter - testing continuity, capacitors, and motor windings.
5. Accurate Leak Detector - testing for refrigerant leaks.
6. High Vacuum Pump - evacuation.
7. Electric Vacuum Gauge, Manifold Gauges and high vacuum hoses - to measure and obtain proper vacuum.
8. Accurate Electronic Scale - measure proper refrigerant charge.
9. Inclined Manometer - measure static pressure and pres­sure drop across coils.
Other recording type instruments can be essential in solving abnormal problems, however, in many instances they may be rented from local sources.
Proper equipment promotes faster, more efficient service, and accurate repairs with less call backs.
22
Page 23
SERVICING
SERVICING
COOLING /HEAT PUMP- SERVICE ANALYSIS GUIDE
Com p laint
POSSIBLE CAUSE
DOTS I N ANALYS I S
GUIDE I NDI CAT E
"PO S S IBL E CAUS E"
Pow er Failure Blow n Fuse Unbalanced Power, 3PH Loose Connection Shorted or Broken Wires Open Fan Overload Faulty Thermostat Faulty Transformer Shorted or Open Capacitor Internal Compressor Overload Open Shorted or Grounded Compressor Compressor Stuck Faulty Compress or Contactor Faulty Fan Control Open Control Circuit Low Voltage Faulty Evap. Fan Motor Shorted or Grounded Fan Motor Improper Cooling Anticipator Shortage of Refrigerant Restricted Liquid Line Open Element or Limit on Elec. Heater Dirty Air Filte r Dirty Indoor Coil Not enough air across Indoor Coil Too much air across Indoor Coil Overcharge of Refrigerant Dir ty O utdoor Coil Noncondensibles Recirculation of Condensing Air Infiltration of Outdoor Air Improper ly Located Thermostat Air Flow Unbalanced System Undersized Broken Internal Parts Broken Valves Inefficient Compressor Loose Hold-dow n Bolts Faulty Reversing Valve Faulty Defros t Control Faulty Defros t Thermostat Flow rator Not Seating Properly
No Coolin g
SYMPTOM
System wil l not start
Compressor will not start - fan runs
Comp. and Cond. Fan will not start
Evaporator fan will not start
Condenser fan will not start
Comp ressor runs - goes off on overload
Compressor cycles on overload
••
••
••
••••••
••
••
••
••
••
••
••
••
••
••
••
••
•• ••
••
••
••
••
••
Cooling or Heating Cycle (Heat Pump) Heating Cycle Only (Heat Pump)
Unsatisfactory
Cooling/He ating
System runs continuously - little cooling/htg
Too cool and then too warm
Not cool enough on warm days
Certain area s too cool, others too warm
Compressor is noisy
System runs - blows cold air in heating
♦♦
••
••
••
••
••
••
••
♦♦♦ ♦♦♦
♦♦♦♦♦
♦♦♦♦♦♦♦
••
Unit will not terminate defrost
Pressures
Unit will not defrost
Low suction pressure
••
System
Operating
Low head pressure
High suction pressure
••
••
Test Method
Remedy
High head pressure
Test Voltage S-1 Inspect Fuse Size & Type S-1 Test Voltage S-1 Inspect Connection - Tighten S-2, S-3 Test Circuits With Ohmmeter S- 2, S-3 Test Continuity of Overload S-17A Test continuity of Thermostat & Wiring S-3 Check control circuit w ith voltmeter S-4 Test Capacitor S-15 Test Continuity of Overload S-17A Test Motor Windings S-17B Use Test Cord S-17D Test continuity of Coil & Contacts S- 7, S-8 Test continuity of Coil And Contacts S-7, S-9 Test Control Circuit with Voltmeter S-4 Test Voltage S-1 Repair or Replace S-16
Test Motor Windings S-16A,D Check resistance of Anticipator S-3B Test For Leaks, Add Refrigerant S-101,103 Remove Restriction, Replace Restricted Part S-112 Test Heater Element and Controls S-26,S-27 Inspect Filter-Clean or Replace
Inspect Coil - Clean
Check Blower Speed, Duct Static Press, Filter S-200
Reduce Blower Speed S-200 Recover Part of Charge S-113 Inspect Coil - Clean
Recover Charge, Evacuate, Recharge S-114
Remove Obstruction to Air Flow Check Windows, Doors, Vent Fans, Etc. Relocate Thermostat Readjust Air Volume Dampers Refigure Cooling Load Replace Compressor S-115 Test Compressor Efficiency S-104 Test Compressor Efficiency S-104 Tighten Bolts Replace Valve or Solenoid S-21, 122 Test Control S-24 Test Defrost Thermostat S-25 Check Flowrator & Seat or Replace Flowrator S-111
See S ervice Procedu re Ref.
23
Page 24
SERVICING
S-1 CHECKING VOLTAGE
WARNING
1. Remove doors, control panel cover, etc. from unit being tested.
With power ON:
WARNING
LINE VOLTAGE NO W PRESENT.
2. Using a voltmeter, measure the voltage across terminals L1 and L2 of the contactor for single phase units, and L3, for 3 phase units.
3. No reading - indicates open wiring, open fuse(s) no power or etc. from unit to fused disconnect service. Repair as needed.
4. With ample voltage at line voltage connectors, energize the unit.
5. Measure the voltage with the unit starting and operating, and determine the unit Locked Rotor Voltage.
Locked Rotor Voltage is the actual voltage available at the compressor during starting, locked rotor, or a stalled condition. Measured voltage should be above minimum listed in chart below.
To measure Locked Rotor Voltage attach a voltmeter to the run "R" and common "C" terminals of the compres­sor, or to the T1 and T2 terminals of the contactor. Start the unit and allow the compressor to run for several sec­onds, then shut down the unit. Immediately attempt to restart the unit while measuring the Locked Rotor Volt­age.
6. Should read within the voltage tabulation as shown. If the voltage falls below the minimum voltage, check the line wire size. Long runs of undersized wire can cause low voltage. If wire size is adequate, notify the local power company in regards to either low or high voltage.
Unit Supply Voltage
Voltage Min. Max.
460 437 506
208/230 198 253
S-2 CHECKING WIRING
WARNING
1. Check wiring visually for signs of overheating, damaged insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected open wires.
3. If any wires must be replaced, replace with comparable gauge and insulation thickness.
S-3 CHECKING THERMOSTAT, WIRING, AND ANTICIPATOR
S-3A THERMOSTAT AND WIRING
WARNING
LINE V OLT AG E NOW PR ES ENT .
With power ON and thermostat calling for cooling.
1. Use a voltmeter to verify 24 volts present at thermostat wires C and R.
2. If no voltage present, check transformer and transformer wiring. If 24 volts present, proceed to step 3.
3. Use a voltmeter to check for 24 volts at thermostat wires C and Y.
4. No voltage indicates trouble in the thermostat, wiring or external transformer source.
5. Check the continuity of the thermostat and wiring. Repair or replace as necessary.
INDOOR BLOWER MOTOR
With power ON:
WARNING
LINE VOL TAG E NOW PRE S ENT.
1. Use a voltmeter to verify 24 volts present at thermostat wires C and R.
2. If no voltage present, check transformer and transformer wiring. If 24 volts present, proceed to step 3.
24
Page 25
SERVICING
3. Set fan selector switch at thermostat to "ON" position.
4. With voltmeter, check for 24 volts at wires C and G.
5. No voltage, indicates the trouble is in the thermostat or wiring.
6. Check the continuity of the thermostat and wiring. Repair or replace as necessary.
S-3B COOLING ANTICIPATOR
The cooling anticipator is a small heater (resistor) in the ther­mostat. During the "off" cycle it heats the bimetal element helping the thermostat call for the next cooling cycle. This prevents the room temperature from rising too high before the system is restarted. A properly sized anticipator should main­tain room temperature within 1 1/2 to 2 degree range.
The anticipator is supplied in the thermostat and is not to be replaced. If the anticipator should fail for any reason, the ther­mostat must be changed.
WARNING
1. Remove control panel cover or etc. to gain access to trans­former.
With power ON:
WARNING
LINE VOL TAG E NOW PRE S ENT.
S-3C HEATING ANTICIPATOR
The heating anticipator is a wire-wound adjustable heater, which is energized during the "ON" cycle to help prevent overheating of the conditioned space.
The anticipator is a part of the thermostat and if it should fail for any reason, the thermostat must be replaced. See the follow­ing for recommended heater anticipator setting.
To determine the proper setting, use an amp meter to measure the amperage on the "W" wire going to the thermostat.
Use an amprobe as shown below. Wrap 10 turns of thermostat wire around the stationary jaw of the amprobe and divide the reading by 10.
10 TURNS OF THERMOSTAT WIRE (From "W" on thermostat)
STATIONARY JAW OF AMPROBE
2. Using a voltmeter, check voltage across secondary voltage side of transformer (R to C).
3. No voltage indicates faulty transformer, bad wiring, or bad splices.
4. Check transformer primary voltage at incoming line voltage connections and/or splices.
5 If line voltage is present at the primary voltage side of the
transformer and 24 volts is not present on the secondary side, then the transformer is inoperative. Replace.
S-7 CHECKING CONTACTOR AND/OR RELAYS
The compressor contactor and other relay holding coils are wired into the low or line voltage circuits. When the control circuit is energized the coil pulls in the normally open contacts or opens the normally closed contacts. When the coil is de­energized, springs return the contacts to their normal position.
WARNING
DISCONNECT PO WER SUPPLY BEFORE SERVICING.
READS 4 AMPS CURRENT DRAW WOULD BE .4 AMPS
Checking Heat Anticipator Amp Draw
S-4 CHECKING TRANSFORMER AND CONTROL CIRCUIT
A step-down transformer (208/240 volt primary to 24 volt sec­ondary) is provided with each package unit. This allows ample capacity for use with resistance heaters.
1. Remove the leads from the holding coil.
2. Using an ohmmeter, test across the coil terminals.
If the coil does not test continuous, replace the relay or con­tactor.
25
Page 26
SERVICING
S-8 CHECKING CONTACTOR CONTACTS
S-12 CHECKING HIGH PRESSURE CONTROL
WARNING
DISCONNECT POWER SUP PLY BEFORE SERVICING.
SINGLE PHASE
1. Disconnect the wire leads from the terminal (T) side of the contactor.
2. With power ON, energize the contactor.
WARNING
LINE VOLTAGE NO W PRESENT.
T2
VOLT/OHM
METER
Ohmmeter for te sting holding co il Voltmeter for testing contacts
T1
CC
L1L2
HIGH VOLTAGE! Disconnect ALL power before servicing or insta llin g th is un it. M ult iple powe r sources may be present. Failure to do so may cause property damage, personal injury or death.
The high pressure control senses the pressure in the liquid line. If abnormally high discharge pressures develop, the con­tacts of the control open, breaking the control circuit before the compressor motor overloads. This control is automatically re­set.
1. Using an ohmmeter, check across terminals of high pres­sure control, with wire removed. If not continuous, the con­tacts are open.
2. Attach a gauge to the access fitting on the liquid line.
With power ON:
WARNING
LINE V OLTAG E NO W PRES EN T.
3. Start the system and place a piece of cardboard in front of the condenser coil, raising the condensing pressure.
4. Check pressure at which the high pressure control cuts­out.
TESTING COMPRESSOR CONTACTOR
(Single Phase)
3. Using a voltmeter, test across terminals. A. L1 to L2 - No voltage. Check breaker or fuses on main
power supply. If voltage present, proceed to step B.
B. T1 to T2 - Meter should read the same as L1 to L2 in
step A. If voltage readings are not the same as step A, replace contactor.
S-11 CHECKING LOSS OF CHARGE PROTECTOR
(Heat Pump Models)
The loss of charge protector senses the pressure in the liquid line and will open its contacts on a drop in pressure. The low pressure control will automatically reset itself with a rise in pressure.
The low pressure control is designed to cut-out (open) at ap­proximately 22 + 7 PSIG. It will automatically cut-in (close) at approximately 50 + 7 PSIG.
Test for continuity using a VOM and if not as above, replace the control.
If it cuts-out at 610 PSIG ± 10 PSIG, it is operating normally (See causes for high head pressure in Service Problem Analy­sis Guide). If it cuts out below this pressure range, replace the control. The control should reset at 420 PSIG ± 25 PSIG.
S-15 CHECKING CAPACITOR
CAPACITOR, RUN
A run capacitor is wired across the auxiliary and main wind­ings of a single phase permanent split capacitor motor. The capacitors primary function is to reduce the line current while greatly improving the torque characteristics of a motor. This is accomplished by using the 90° phase relationship between the capacitor current and voltage in conjunction with the motor windings so that the motor will give two phase operation when connected to a single phase circuit. The capacitor also re­duces the line current to the motor by improving the power factor.
26
Page 27
SERVICING
CAPACITOR, START SCROLL COMPRESSOR MODELS
Hard start components are not required on Scroll compressor equipped units due to a non-replaceable check valve located in the discharge line of the compressor. However hard start kits are available and may improve low voltage starting characteris­tics.
This check valve closes off high side pressure to the compres­sor after shut down allowing equalization through the scroll flanks. Equalization requires only about one or two seconds during which time the compressor may turn backwards.
Your unit comes with a 180-second anti-short cycle to prevent the compressor from starting and running backwards.
S-15A RESISTANCE CHECK
WARNING
1. Discharge capacitor and remove wire leads.
MODELS EQUIPPED WITH A HARD START DEVICE
A start capacitor is wired in parallel with the run capacitor to increase the starting torque. The start capacitor is of the elec­trolytic type, rather than metallized polypropylene as used in the run capacitor.
A switching device must be wired in series with the capacitor to remove it from the electrical circuit after the compressor starts to run. Not removing the start capacitor will overheat the capacitor and burn out the compressor windings.
These capacitors have a 15,000 ohm, 2 watt resistor wired across its terminals. The object of the resistor is to discharge the capacitor under certain operating conditions, rather than having it discharge across the closing of the contacts within the switching device such as the Start Relay, and to reduce the chance of shock to the servicer. See the Servicing Section for specific information concerning capacitors.
RELAY, START
A potential or voltage type relay is used to take the start ca­pacitor out of the circuit once the motor comes up to speed. This type of relay is position sensitive. The normally closed contacts are wired in series with the start capacitor and the relay holding coil is wired parallel with the start winding. As the motor starts and comes up to speed, the increase in volt­age across the start winding will energize the start relay hold­ing coil and open the contacts to the start capacitor.
Two quick ways to test a capacitor are a resistance and a capacitance check.
WARNING
DISCHARGE CAPACITOR THROUGH A 20 TO 30 OHM RESISTOR BEFORE HANDLING.
Volt / Ohm Meter
r
o
Capacit
TESTING CAPACITOR RESISTANCE
2. Set an ohmmeter on its highest ohm scale and connect the leads to the capacitor -
A. Good Condition - indicator swings to zero and slowly returns to infinity. (Start capacitor will bleed resistor will not return to infinity. It will still read the resistance of the resistor).
B. Shorted - indicator swings to zero and stops there ­replace.
C. Open - no reading - replace. (Start capacitor would read resistor resistance).
27
Page 28
SERVICING
S-15B CAPACITANCE CHECK
WARNING
DISCHARGE CAPACITOR THROUGH A 20 TO 30 OHM RESISTOR BEFORE HANDLING.
Using a hookup as shown below, take the amperage and volt­age readings and use them in the formula:
Capacitance (MFD) = 2650 X Amperage
Voltage
WARNING
1. Remove the motor leads from its respective connection points and capacitor (if applicable).
2. Check the continuity between each of the motor leads.
3. Touch one probe of the ohmmeter to an unpainted end of the motor frame (ground) and the other probe in turn to each lead.
If the windings do not test continuous or a reading is obtained from any lead to ground, replace the motor.
VOLTMETER
15 AMP
FUSE
AMMETER
CAPACITOR
TESTING CAPACITANCE
S-16 CHECKING MOTORS S-16A CHECKING FAN AND BLOWER MOTOR
WINDINGS (PSC MOTORS)
Applies only to units with PSC Motors
The auto reset fan motor overload is designed to protect the motor against high temperature and high amperage conditions by breaking the common circuit within the motor, similar to the compressor internal overload. However, heat generated within the motor is faster to dissipate than the compressor, allow at least 45 minutes for the overload to reset, then retest.
S-16D CHECKING EEM (ENERGY EFFICIENT MOTOR) MOTORS
Applies only to units with EEM Motors
The EEM Motor is a one piece, fully encapsulated, 3 phase brushless DC (single phase AC input) motor with ball bearing construction. Unlike the ECM 2.3/2.5 motors, the EEM fea­tures an integral control module.
Note: The GE TECMate will not currently operate the EEM motor.
1. Using a voltmeter, check for 230 volts to the motor connec­tions L and N. If 230 volts is present, proceed to step 2. If 230 volts is not present, check the line voltage circuit to the motor.
2. Using a voltmeter, check for 24 volts from terminal C to either terminal 1, 2, 3, 4 or 5, depending on which tap is being used, at the motor. If voltage present, proceed to step 3. If no voltage, check 24 volt circuit to motor.
3. If voltage was present in steps 1 and 2, the motor has failed and will need to be replaced.
Note: When replacing motor, ensure the belly band is between the vents on the motor and the wiring has the proper drip loop to prevent condensate from entering the motor.
28
Page 29
SERVICING
C
123
Low Voltage Connections
High Voltage Connections
3/16"
LGN
4
1/4”
5
Therefore, proper evacuation of a hermetic system is essen­tial at the time of manufacture and during servicing.
To reduce the possibility of external ignition, all open flame, electrical power, and other heat sources should be extinguished or turned off prior to servicing a system.
If the following test indicates shorted, grounded or open wind­ings, see procedure S-19 for the next steps to be taken.
S-17A RESISTANCE TEST
Each compressor is equipped with an internal overload. The line break internal overload senses both motor amperage
and winding temperature. High motor temperature or amper­age heats the disc causing it to open, breaking the common circuit within the compressor on single phase units. The three phase internal overload will open all three legs.
Heat generated within the compressor shell, usually due to recycling of the motor, high amperage or insufficient gas to cool the motor, is slow to dissipate, allow at least three to four hours for it to cool and reset, then retest.
WARNING
EEM MOTOR CONNECTIONS
S-17 CHECKING COMPRESSOR WINDINGS
WARNING
HERMETIC COMPRESSOR ELECTRICAL TERMINAL VENTING CAN BE DANGEROUS. WHEN INSULATING MATERIAL WHICH SUPPORTS A HERMETIC COM­PRESSOR OR ELECTRICAL TERMINAL SUDDENLY DISINTEGRATES DUE TO PHYSICAL ABUSE OR AS A RESULT OF AN EL ECTR ICAL SH ORT BE TWEEN THE TERMINAL AND THE COMPRESSOR HOUSING, THE TERMINAL MAY B E EXPEL LED, V ENTING THE VAPOR AND LIQUID CONTENTS OF THE COMPRES­SOR HOUSING AND SYSTEM.
If the compressor terminal PROTECTIVE COVER and gasket (if required) is not properly in place and secured, there is a remote possibility if a terminal vents, that the vaporous and liquid discharge can be ignited, spouting flames several feet, causing potentially severe or fatal injury to anyone in its path.
This discharge can be ignited external to the compressor if the terminal cover is not properly in place and if the discharge impinges on a sufficient heat source.
Ignition of the discharge can also occur at the venting terminal or inside the compressor, if there is sufficient contaminant air present in the system and an electrical arc occurs as the ter­minal vents.
Ignition cannot occur at the venting terminal without the pres­ence of contaminant air, and cannot occur externally from the venting terminal without the presence of an external ignition source.
1. Remove the leads from the compressor terminals.
WARNING
SEE WARNINGS S-17 BEFORE REMOVING COMPRES­SOR TERMINAL COVER.
2. Using an ohmmeter, test continuity between terminals S­R, C-R, and C-S, on single phase units or terminals T1, T2 and T3, on 3 phase units.
C
OHMMETER
TESTING COMPRESSOR WINDINGS
If either winding does not test continuous, replace the com­pressor.
NOTE: If an open compressor is indicated allow ample time for the internal overload to reset before replacing compressor.
S
COMP
R
29
Page 30
SERVICING
S-17B GROUND TEST
If fuse, circuit breaker, ground fault protective device, etc., has tripped, this is a strong indication that an electrical problem exists and must be found and corrected. The circuit protective device rating must be checked and its maximum rating should coincide with that marked on the equipment nameplate.
With the terminal protective cover in place, it is acceptable to replace the fuse or reset the circuit breaker ONE TIME ONLY to see if it was just a nuisance opening. If it opens again, DO NOT continue to reset.
Disconnect all power to unit, making sure that are open.
1. DO NOT remove protective terminal cover. Disconnect the three leads going to the compressor terminals at the near­est point to the compressor.
all power legs
WARNING
DAMAGE CAN OCCUR TO THE GLASS EMBEDDED TERMINALS IF THE LEADS ARE NOT P ROPERLY REMOVED. THIS CAN RESULT IN TERMINAL AND HOT OIL DISCHARGING.
S-17D OPERATION TEST
If the voltage, capacitor, overload and motor winding test fail to show the cause for failure:
WARNING
1. Remove unit wiring from disconnect switch and wire a test cord to the disconnect switch.
NOTE: The wire size of the test cord must equal the line wire size and the fuse must be of the proper size and type.
2. With the protective terminal cover in place, use the three leads to the compressor terminals that were disconnected at the nearest point to the compressor and connect the common, start and run clips to the respective leads.
3. Connect good capacitors of the right MFD and voltage rat­ing into the circuit.
4. With power ON, close the switch.
HI-POT
COMPRESSOR GROUND TEST
2. Identify the leads and using a Megger, Hi-Potential Ground Tester, or other suitable instrument which puts out a volt­age between 300 and 1500 volts, check for a ground sepa­rately between each of the three leads and ground (such as an unpainted tube on the compressor). Do not use a low voltage output instrument such as a volt-ohmmeter.
3. If a ground is indicated, then carefully remove the compres­sor terminal protective cover and inspect for loose leads or insulation breaks in the lead wires.
4. If no visual problems indicated, carefully remove the leads at the compressor terminals.
Carefully retest for ground, directly between compressor terminals and ground.
5. If ground is indicated, replace the compressor.
WARNING
LINE VOLTAGE NOW PRESENT.
A. If the compressor starts and continues to run, the
cause for failure is somewhere else in the system.
B. If the compressor fails to start - replace.
The condition of the scroll flanks is checked in the following manner.
1. Attach gauges to the high and low side of the system.
2. Start the system and run a “Cooling Performance Test. If the test shows:
a. Below normal high side pressure. b. Above normal low side pressure. c. Low temperature difference across coil. d. L ow amp draw at compressor.
and the charge is correct, test the reversing valve if equipped (heat pump models only. See-S-21). If the reversing valves test good, the compressor is faulty - replace the compressor.
30
Page 31
SERVICING
S-18 TESTING CRANKCASE HEATER
(OPTIONAL ITEM)
Note: Not all compressors use crankcase heaters.
The crankcase heater must be energized a minimum of twenty­four (24) hours before the compressor is operated.
Crankcase heaters are used to prevent migration or accumula­tion of refrigerant in the compressor crankcase during the off cycles and prevents liquid slugging or oil pumping on start up. On some models, the crankcase heater is controlled by a crank­case heater thermostat that is wired in series with the crank­case heater.
A crankcase heater will not prevent compressor damage due to a floodback or over charge condition.
WARNING
DISCONNECT POWER SUPPLY BEFORE SERVICING.
1. Disconnect the heater lead wires.
2. Using an ohmmeter, check heater continuity - should test continuous, if not, replace.
S-18A CHECKING CRANKCASE HEATER THERMOSTAT
Note: Not all models with crankcase heaters will have a
crankcase heater thermostat.
1. Install a thermocouple type temperature test lead on the discharge line adjacent to the crankcase heater thermo­stat.
2. Check the temperature at which the control closes its con­tacts by lowering the temperature of the control. The crank­case heater thermostat should close at 67°F ± 5°F.
3. Check the temperature at which the control opens its con­tacts by raising the temperature of the control. The crank­case heater thermostat should open at 85°F ± 5°F.
4. If not as above, replace control.
S-21 CHECKING REVERSING VALVE AND SOLENOID
Occasionally the reversing valve may stick in the heating or cooling position or in the mid-position.
When stuck in the mid-position, part of the discharge gas from the compressor is directed back to the suction side, resulting in excessively high suction pressure. An increase in the suc­tion line temperature through the reversing valve can also be measured. Check operation of the valve by starting the sys­tem and switching the operation from COOLING to HEATING cycle.
If the valve fails to change its position, test the voltage (24V) at the valve coil terminals, while the system is on the COOLING cycle.
If no voltage is registered at the coil terminals, check the op­eration of the thermostat and the continuity of the connecting wiring from the "O" terminal of the thermostat to the unit.
If voltage is registered at the coil, tap the valve body lightly while switching the system from HEATING to COOLING, etc. If this fails to cause the valve to switch positions, remove the coil connector cap and test the continuity of the reversing valve solenoid coil. If the coil does not test continuous - replace it.
If the coil test continuous and 24 volts is present at the coil terminals, the valve is inoperative - replace it.
S-24 TESTING DEFROST CONTROL
NOTE: PCBDM133 defrost controls have a three (3) minute compressor off cycle delay.
NOTE: The PCBDM133 defrost controls are shipped from the
factory with the compressor delay option selected. This will de-energize the compressor contactor for 30 seconds on defrost initiation and defrost termination. If the jumper is set to Normal, the compressor will continue to run during defrost initiation and defrost termination. The control will also ignore the low pressure switch connected to R-PS1 and PS2 for 5 minutes
upon defrost initiation and 5 minutes after defrost termination. To check the defrost control for proper sequencing, proceed as follows: With power ON; unit not running.
1. Jumper defrost thermostat by placing a jumper wire across the terminals "DFT" and "R" ("R-DFT" on PCBDM133) at defrost control board.
2. Connect jumper across test pins on defrost control board.
3. Set thermostat to call for heating. System should go into defrost within 21 seconds.
4. Immediately remove jumper from test pins.
5. Using VOM check for voltage across terminals "C & O" ("O-RV" on PCBDM133). Meter should read 24 volts.
6. Using VOM check for voltage across fan terminals DF1 and DF2 on the board. You should read line voltage (208­230 VAC) indicating the relay is open in the defrost mode.
7. Using VOM check for voltage across "W2" (W on PCBDM133) & "C" terminals on the board. You should read 24 volts.
8. If not as above, replace control board.
9. Set thermostat to off position and disconnect power before removing any jumpers or wires.
NOTE: Remove jumper across defrost thermostat before re­turning system to service.
31
Page 32
SERVICING
S-25 TESTING DEFROST THERMOSTAT
1. Install a thermocouple type temperature test lead on the tube adjacent to the defrost control. Insulate the lead point of contact.
2. Check the temperature at which the control closes its con­tacts by lowering the temperature of the control. It should close at approximately 32°F ± 2°F.
3. Check the temperature at which the control opens its con­tacts by raising the temperature of the control. It should open at approximately 60°F.
4. If not as above, replace control.
S-50 CHECKING HEATER LIMIT CONTROL(S)
(OPTIONAL ELECTRIC HEATERS)
Each individual heater element is protected with an automatic rest limit control connected in series with each element to prevent overheating of components in case of low airflow. This limit control will open its circuit at approximately 150°F. to 160°F and close at approximately 110°F.
WARNING
DISCONNECT ELECTRI CAL PO WER SUPPLY.
S-100 REFRIGERATION REPAIR PRACTICE
DANGER
ALWAYS REMOVE THE REFRIGERANT CHARGE IN A PROPER MANNER BEFORE APPLYING HEAT TO THE SYSTEM.
These models use the FasTest Access Fitting System, with a saddle that is either soldered to the suction and liquid lines or is fastened with a locking nut to the access fitting box (core) and then screwed into the saddle. Do not remove the core
from the saddle until the refrigerant charge has been removed. Failure to do so could result in property dam­age or personal injury.
When installing a new core or reinstalling the core after re­moval, it is very important to note that before inserting the core into the saddle, the core and saddle must be free of debris and the “O” Ring must have a thin coating of refrigerant oil applied to it. The oil is to prevent the “O” Ring from being deformed when the core is tightened completely. The core should be torqued to 8 ft. lb.
When repairing the refrigeration system:
1. Remove the wiring from the control terminals.
2. Using an ohmmeter test for continuity across the normally closed contacts. No reading indicates the control is open
- replace if necessary. Make sure the limits are cool before testing.
IF FOUND OPEN - REPLACE - DO NOT WIRE AROUND.
S-52 CHECKING HEATER ELEMENTS
Optional electric heaters may be added, in the quantities shown in the spec sheet for each model unit, to provide electric resis­tance heating. Under no condition shall more heaters than the quantity shown be installed.
WARNING
1. Disassemble and remove the heating element(s).
2. Visually inspect the heater assembly for any breaks in the wire or broken insulators.
3. Using an ohmmeter, test the element for continuity - no reading indicates the element is open. Replace as neces­sary.
32
WARNING
DISCONNECT ELECTRI CAL PO WER SUPPLY.
1. Never open a system that is under vacuum. Air and mois­ture will be drawn in.
2. Plug or cap all openings.
3. Remove all burrs and clean the brazing surfaces of the tubing with sand cloth or paper. Brazing materials do not flow well on oxidized or oily surfaces.
4. Clean the inside of all new tubing to remove oils and pipe chips.
5. When brazing, sweep the tubing with dry nitrogen to pre­vent the formation of oxides on the inside surfaces.
6. Complete any repair by replacing the liquid line drier in the system, evacuate and charge.
At any time the system has been open for repair, the factory installed liquid line filter drier must be replaced.
BRAZING MATERIALS
Copper to Copper Joints - Sil-Fos used without flux (alloy of 15% silver, 80% copper, and 5% phosphorous). Recommended heat 1400°F.
Copper to Steel Joints - Silver Solder used without a flux (alloy of 30% silver, 38% copper, 32% zinc). Recommended heat - 1200°F.
Aluminum to Aluminum and Copper to Aluminum Joints
- ZA-1 Brazing Rods use Flux System Cesium-Based Poly-
mer System (alloy of 78% Zinc and 22% Aluminum); Melting point 826°F - Flow point 905°F.
Page 33
SERVICING
S-101 LEAK TESTING
(NITROGEN OR NITROGEN-TRACED)
WARNING
WARNING
This is the most important part of the entire service procedure. The life and efficiency of the equipment is dependent upon the thoroughness exercised by the serviceman when evacuating air (non-condensable) and moisture from the system.
Air in a system causes high condensing temperature and pres­sure, resulting in increased power input and reduced perfor­mance.
Moisture chemically reacts with the refrigerant and oil to form corrosive hydrofluoric and hydrochloric acids. These attack motor windings and parts, causing breakdown.
The equipment required to thoroughly evacuate the system is a high vacuum pump, capable of producing a vacuum equiva­lent to 25 microns absolute and a thermocouple vacuum gauge to give a true reading of the vacuum in the system
NOTE: Never use the system compressor as a vacuum pump or run when under a high vacuum. Motor damage could occur.
Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant then use nitrogen to finish charging the system to working pressure, then apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation.
For a system that contains a refrigerant charge and is sus­pected of having a leak, stop the operation and hold the explor­ing tube of the detector as close to the tube as possible, check all piping and fittings. If a leak is detected, do not attempt to apply more brazing to the joint. Remove and capture the charge, unbraze the joint, clean and rebraze.
For a system that has been newly repaired and does not con­tain a charge, connect a cylinder of refrigerant, through a gauge manifold, to the liquid and suction line dill valves and/or liquid line dill valve and compressor process tube.
NOTE: Refrigerant hoses must be equipped with dill valve de­pressors or special adaptor used. Open the valve on the cylin­der and manifold and allow the pressure to build up within the system. Check for and handle leaks, as described above. After the test has been completed, remove and capture the leak test refrigerant.
WARNING
SCROLL COMPRESSORS DO NOT FRONT SEAT TH E SERVIC E VALV E(S) WITH THE COMPRESSOR OPERATING IN AN ATTEMPT TO SAVE REFRIGERANT. WITH THE SUCTION LINE OF THE COMPRESSOR CLOSED OR SEVERLY RESTRICT­ED, THE SCROLL COMPRESSOR WILL DRAW A DEEP VACUUM VERY QUICKLY. THIS VACUUM CAN CAUSE INTERNAL ARCING OF THE FUSITE RESULTING IN A DAMAGED OR FAILED COMPRESSOR.
LOW SIDE
GAUGE
AND VALVE
HIGH SIDE
GAUGE
AND V ALVE
S-102 EVACUATION
WARNING
1. Connect the vacuum pump, vacuum tight manifold set with high vacuum hoses, thermocouple vacuum gauge and charg­ing cylinder as shown.
2. Start the vacuum pump and open the shut off valve to the high vacuum gauge manifold only. After the compound gauge (low side) has dropped to approximately 29 inches of vacuum, open the valve to the vacuum thermocouple
33
Page 34
SERVICING
gauge. See that the vacuum pump will blank-off to a maxi­mum of 25 microns. A high vacuum pump can only pro­duce a good vacuum if its oil is non-contaminated.
3. If the vacuum pump is working properly, close the valve to the vacuum thermocouple gauge and open the high and low side valves to the high vacuum manifold set. With the valve on the charging cylinder closed, open the manifold valve to the cylinder.
4. Evacuate the system to at least 29 inches gauge before opening valve to thermocouple vacuum gauge.
5. Continue to evacuate to a minimum of 250 microns. Close valve to vacuum pump and watch rate of rise. If vacuum does not rise above 1500 microns in three to five minutes, system can be considered properly evacuated.
6. If thermocouple vacuum gauge continues to rise and levels off at about 5000 microns, moisture and non-condensables are still present. If gauge continues to rise a leak is present. Repair and re-evacuate.
7. Close valve to thermocouple vacuum gauge and vacuum pump. Shut off pump and prepare to charge.
S-103 CHARGING
WARNINGWARNING
CAUTION
0
For charging in the warmer months, 10 pressor is required at conditions: 95 bulb temperature), 800F dry bulb / 670F wet bulb indoor ambi­ent, approximately 50% humidity. This superheat varies when conditions vary from the conditions described.
A superheat charge chart is available for other operating condi­tions. Use it to provide the correct superheat at the conditions the unit is being charged at.
After superheat is adjusted it is recommended to check unit sub-cooling at the condenser coil liquid line out. In most oper­ating conditions 12 + 40F of sub-cooling is adequate.
An inaccurately charged system will cause future problems.
1. Using a quality set of charging scales, weigh the proper amount of refrigerant for the system. Allow liquid refrigerant only to enter the high side.
2. After the system will take all it will take, close the valve on the high side of the charging manifold.
3. Start the system and charge the balance of the refrigerant through the low side.
NOTE: R410A should be drawn out of the storage con­tainer or drum in liquid form due to its fractionation proper­ties, but should be "Flashed" to its gas state before enter­ing the system. There are commercially available restric­tion devices that fit into the system charging hose set to accomplish this. DO NOT charge liquid R410A into the compressor.
4. With the system still running, close the valve on the charg­ing cylinder. At this time, you may still have some liquid refrigerant in the charging cylinder hose and will definitely have liquid in the liquid hose. Slowly open the high side manifold valve and transfer the liquid refrigerant from the liquid line hose and charging cylinder hose into the suction service valve port. CAREFUL: Watch so that liquid refrig­erant does not enter the compressor.
Final Charge Adjustment
F superheat at the com-
0
F outdoor ambient (dry
Charge the system with the exact amount of refrigerant. Refer to the specification section or check the unit nameplates
for the correct refrigerant charge. After completing airflow measurements and adjustments, the
unit’s refrigerant charge must be checked. The unit comes factory charged, but this charge is based on 400 CFM per ton at minimum ESP per AHRI test conditions (generally between .15 - .25 ESP). When air quantity or ESP is different than above, charge must be adjusted to the proper amount.
All package units are charged to the superheat method at the compressor suction line (these are fixed orifice devices).
34
The outdoor temperature must be 60°F or higher. Set the room thermostat to COOL, fan switch to AUTO, and set the tem­perature control well below room temperature.
After system has stabilized per start-up instructions, compare the operating pressures and outdoor unit amp draw to the num­bers listed in the technical manual. If pressures and amp draw are too low, add charge. If pressures and amp draw are too high, remove charge. Check subcooling and superheat as de­tailed in the following section.
5. With the system still running, remove hose and reinstall both access fitting caps.
6. Check system for leaks.
Due to their design, Scroll compressors are inherently more tolerant of liquid refrigerant.
Page 35
SERVICING
NOTE: Even though the compressor section of a Scroll com-
pressor is more tolerant of liquid refrigerant, continued flood­back or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure. S-104 CHECK-
ING COMPRESSOR EFFICIENCY The reason for compressor inefficiency is broken or damaged
suction and/or discharge valves, or scroll flanks on Scroll com­pressors, reducing the ability of the compressor to pump re­frigerant vapor.
The condition of the valves or scroll flanks is checked in the following manner.
1. Attach gauges to the high and low side of the system.
2. Start the system and run a Cooling Performance Test. If the test shows-
Below normal high side pressure.
Above normal low side pressure. Low temperature difference across coil. Low amp draw at compressor.
-and the charge is correct. The compressor is faulty - replace the compressor.
S-104 CHECKING COMPRESSOR EFFICIENCY
The reason for compressor inefficiency is broken or damaged suction and/or discharge valves, or scroll flanks on Scroll com­pressors, reducing the ability of the compressor to pump re­frigerant vapor.
During the "OFF" cycle, the high side pressure bleeds to the low side through the fixed orifice restriction device. Check equalization time as follows:
1. Attach a gauge manifold to the suction and liquid line ac­cess fittings.
2. Start the system and allow the pressures to stabilize.
3. Stop the system and check the time it takes for the high and low pressure gauge readings to equalize.
If it takes more than seven (7) minutes to equalize, the restrictor device is inoperative. Replace, install a liquid line drier, evacu­ate and recharge.
CAUTION
To prevent personal injury, carefully connect and discon nect manifold gauge hoses. Escaping liquid refrigerant can cause burns. Do not vent refrigerant to atmosphere. Recover during system repair or final unit dispo sal.
1. Run system at least 10 minutes to allow pressure to sta­bilize.
2. Temporarily install thermometer on suction (large) line near compressor with adequate contact and insulate for best possible reading.
3. Refer to the superheat table provided for proper system superheat. Add charge to lower superheat or recover charge to raise superheat.
Superheat Formula = Suct. Line Temp. - Sat. Suct. Temp.
Ambient Condenser
Inlet Temp (°F
Drybulb)
100 - - - 10 10
95 90 85 80 75 10 13 17 25 29 70 10 17 20 28 32 65 13 19 26 32 35 60 17 25 30 33 37
EXAMPLE:
a. Suction Pressure = 143 b. Corresponding Temp. °F. = 50 c. Thermometer on Suction Line = 59°F.
To obtain the degrees temperature of superheat, subtract 50.0 from 59.0°F.
The difference is 9° Superheat. The 9° Superheat would fall in the ± range of allowable superheat.
Return Air Temp. (°F Drybulb)
65 70 75
- - 10 10 10
- - 12 15 18
- 10 13 17 20
- 10 15 21 26
80 85
S-108 SUPERHEAT
CHECKING SUPERHEAT
Refrigerant gas is considered superheated whenever its tem­perature is higher than the saturation temperature correspond­ing to its pressure. The degree of superheat equals the de­grees of temperature increase above the saturation tempera­ture at existing pressure. See Temperature - Pressure Chart.
S-109 CHECKING SUBCOOLING
Refrigerant liquid is considered subcooled when its tempera­ture is lower than the saturation temperature corresponding to its pressure. The degree of subcooling equals the degrees of temperature decrease below the saturation temperature at the existing pressure.
1. Attach an accurate thermometer or preferably a thermo­couple type temperature tester to the liquid line close to the pressure switch.
35
Page 36
SERVICING
2. Install a high side pressure gauge on the liquid access fitting.
3. Record the gauge pressure and the temperature of the line.
4. Compare the hi-pressure reading to the "Required Liquid Line Temperature" chart. Find the hi-pressure value on the left column. Follow that line right to the column under the design subcooling value. Where the two intersect is the required liquid line temperature.
Alternately you can convert the liquid line pressure gauge reading to temperature by finding the gauge reading in Tem­perature - Pressure Chart and reading to the left, find the temperature in the °F. Column.
5. The difference between the thermometer reading and pres­sure to temperature conversion is the amount of subcooling.
Subcooling Formula = Sat. Liquid Temp. - Liquid Line Temp.
EXAMPLE:
a. Liquid Line Pressure = 417 b. Corresponding Temp. °F. = 120° c. Thermometer on Liquid line = 109°F.
To obtain the amount of subcooling, subtract 109°F from 120°F. The difference is 11° subcooling. See the specification sheet
or technical information manual for the design subcooling range for your unit.
See R410A Pressure vs. Temperature chart.
S-111 FIXED ORIFICE RESTRICTION DEVICES
The fixed orifice restriction device (flowrator) used in conjunc­tion with the indoor coil is a predetermined bore (I.D.).
It is designed to control the rate of liquid refrigerant flow into an evaporator coil.
The amount of refrigerant that flows through the fixed orifice restriction device is regulated by the pressure difference be­tween the high and low sides of the system.
In the cooling cycle when the outdoor air temperature rises, the high side condensing pressure rises. At the same time, the cooling load on the indoor coil increases, causing the low side pressure to rise, but at a slower rate.
Since the high side pressure rises faster when the tempera­ture increases, more refrigerant flows to the evaporator, increas­ing the cooling capacity of the system.
When the outdoor temperature falls, the reverse takes place. The condensing pressure falls, and the cooling loads on the indoor coil decreases, causing less refrigerant flow.
If a restriction should become evident, proceed as follows:
1. Recover refrigerant charge.
2. Remove the orifice assembly and clean or replace.
3. Replace liquid line drier, evacuate and recharge.
CHECKING EQUALIZATION TIME
During the "OFF" cycle, the high side pressure bleeds to the low side through the fixed orifice restriction device. Check equalization time as follows:
1. Attach a gauge manifold to the suction and liquid line dill valves
2. Start the system and allow the pressures to stabilize.
3. Stop the system and check the time it takes for the high and low pressure gauge readings to equalize.
If it takes more than seven (7) minutes to equalize, the restric­tion device is inoperative. Replace, install a liquid line drier, evacuate and recharge.
S-112 CHECKING RESTRICTED LIQUID LINE
When the system is operating, the liquid line is warm to the touch. If the liquid line is restricted, a definite temperature drop will be noticed at the point of restriction. In severe cases, frost will form at the restriction and extend down the line in the direction of the flow.
Discharge and suction pressures will be low, giving the ap­pearance of an undercharged unit. However, the unit will have normal to high subcooling.
If a restriction is located, replace the restricted part, replace drier, evacuate and recharge.
S-113 REFRIGERANT OVERCHARGE
An overcharge of refrigerant is normally indicated by an exces­sively high head pressure.
An evaporator coil, using an expansion valve metering device, will basically modulate and control a flooded evaporator and prevent liquid return to the compressor.
An evaporator coil, using a fixed orifice restrictor device (flowrator) metering device, could allow liquid refrigerant to re­turn to the compressor under extreme overcharge conditions.
Also with a fixed orifice restrictor device (flowrator) metering device, extreme cases of insufficient indoor air can cause icing of the indoor coil and liquid return to the compressor, but the head pressure would be lower.
There are other causes for high head pressure which may be found in the "Service Problem Analysis Guide."
If other causes check out normal, an overcharge or a system containing non-condensables would be indicated.
If this system is observed:
1. Start the system.
2. Remove and capture small quantities of refrigerant as from the suction line access fitting until the head pressure is reduced to normal.
3. Observe the system while running a cooling performance test. If a shortage of refrigerant is indicated, then the sys­tem contains non-condensables.
36
Page 37
SERVICING
S-114 NON-CONDENSABLES
If non-condensables are suspected, shut down the system and allow the pressures to equalize. Wait at least 15 minutes. Compare the pressure to the temperature of the coldest coil since this is where most of the refrigerant will be. If the pres­sure indicates a higher temperature than that of the coil tem­perature, non-condensables are present.
Non-condensables are removed from the system by first re­moving the refrigerant charge, replacing and/or installing liquid line drier, evacuating and recharging.
S-115 COMPRESSOR BURNOUT
When a compressor burns out, high temperature develops caus­ing the refrigerant, oil and motor insulation to decompose form­ing acids and sludge.
If a compressor is suspected of being burned-out, attach a refrigerant hose to the liquid line dill valve and properly remove and dispose of the refrigerant.
NOTICE
Now determine if a burn out has actually occurred. Confirm by analyzing an oil sample using a Sporlan Acid Test Kit, AK-3 or its equivalent.
Remove the compressor and obtain an oil sample from the suction stub. If the oil is not acidic, either a burnout has not occurred or the burnout is so mild that a complete clean-up is not necessary.
If acid level is unacceptable, the system must be cleaned by using the clean-up drier method.
CAUTION
DO NOT ALLOW THE SLUDGE OR OIL TO CONTACT THE SKIN, SEVERE BURNS MAY RESULT.
NOTE: GOODMAN DOES NOT APPROVE THE FLUSHING METHOD USING R-11 REFRIGERANT.
SUCTION LINE DRIER CLEAN-UP METHOD
The POE oils used with R410A refrigerant is an excellent sol­vent. In the case of a burnout, the POE oils will remove any burnout residue left in the system. If not captured by the refrig­erant filter, they will collect in the compressor or other system components, causing a failure of the replacement compressor and/or spread contaminants throughout the system, damag­ing additional components.
Install a suction line filter drier. This drier should be installed as close to the compressor suction fitting as possible. The filter must be accessible and be rechecked for a pressure drop after the system has operated for a time. It may be necessary to use new tubing and form as required.
NOTE: At least twelve (12) inches of the suction line immedi­ately out of the compressor stub must be discarded due to burned residue and contaminates.
1. Remove the liquid line drier and expansion valve.
2. Purge all remaining components with dry nitrogen or car­bon dioxide until clean.
3 Install new components
4. Braze all joints, leak test, evacuate, and recharge system.
5. Start up the unit and record the pressure drop across the drier.
6. Continue to run the system for a minimum of twelve (12) hours and recheck the pressure drop across the drier. Pres­sure drop should not exceed 6 PSIG.
7. Continue to run the system for several days, repeatedly checking pressure drop across the suction line drier. If the pressure drop never exceeds the 6 PSIG, the drier has trapped the contaminants. Remove the suction line drier from the system.
8. If the pressure drop becomes greater, then it must be re­placed and steps 5 through 9 repeated until it does not exceed 6 PSIG.
NOTICE: Regardless, the cause for burnout must be deter­mined and corrected before the new compressor is started.
including liquid line drier.
S-122 REVERSING VALVE REPLACEMENT
Remove the refrigerant charge from the system. When brazing a reversing valve into the system, it is of ex-
treme importance that the temperature of the valve does not exceed 250°F. at any time.
Wrap the reversing valve with a large rag saturated with water. "Re-wet" the rag and thoroughly cool the valve after each braz­ing operation of the four joints involved. The wet rag around the reversing valve will eliminate conduction of heat to the valve body when brazing the line connection.
The use of a wet rag sometimes can be a nuisance. There are commercial grades of heat absorbing paste that may be sub­stituted.
After the valve has been installed, leak test, evacuate and re­charge.
37
Page 38
SERVICING
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98
°F
-37.7
-34.7
-32.0
-29.4
-36.9
-24.5
-22.2
-20.0
-17.9
-15.8
-13.8
-11.9
-10.1
-8.3
-6.5
-4.5
-3.2
-1.6
0.0
1.5
3.0
4.5
5.9
7.3
8.6
10.0
11.3
12.6
13.8
15.1
16.3
17.5
18.7
19.8
21.0
22.1
23.2
24.3
25.4
26.4
27.4
28.5
29.5
30.5
31.2
32.2
33.2
34.1
35.1
35.5
36.9
PSIG
100 102 104 106 108 110 112
PSIG
114.0
116.0
118.0
120.0
122.0
124.0
126.0
128.0
130.0
132.0
134.0
136.0
138.0
140.0
142.0
144.0
146.0
148.0
150.0
152.0
154.0
156.0
158.0
160.0
162.0
164.0
166.0
168.0
170.0
172.0
174.0
176.0
178.0
180.0
182.0
184.0
186.0
188.0
190.0
192.0
194.0
196.0
198.0
200.0
202.0
204.0
206.0
208.0
210.0
212.0
214.0
Pressure vs. Temperature Chart
R-410A
°F
37.8
38.7
39.5
40.5
41.3
42.2
43.0
43.8
44.7
45.5
46.3
47.1
47.9
48.7
49.5
50.3
51.1
51.8
52.5
53.3
54.0
54.8
55.5
56.2
57.0
57.7
58.4
59.0
59.8
60.5
61.1
61.8
62.5
63.1
63.8
64.5
65.1
65.8
66.4
67.0
67.7
68.3
68.9
69.5
70.1
70.7
71.4
72.0
72.6
73.2
73.8
PSIG
216.0
218.0
220.0
222.0
224.0
226.0
228.0
230.0
232.0
234.0
236.0
238.0
240.0
242.0
244.0
246.0
248.0
250.0
252.0
254.0
256.0
258.0
260.0
262.0
264.0
266.0
268.0
270.0
272.0
274.0
276.0
278.0
280.0
282.0
284.0
286.0
288.0
290.0
292.0
294.0
296.0
298.0
300.0
302.0
304.0
306.0
308.0
310.0
312.0
314.0
316.0
°F
74.3
74.9
75.5
76.1
76.7
77.2
77.8
78.4
78.9
79.5
80.0
80.6
81.1
81.6
82.2
82.7
83.3
83.8
84.3
84.8
85.4
85.9
86.4
86.9
87.4
87.9
88.4
88.9
89.4
89.9
90.4
90.9
91.4
91.9
92.4
92.8
93.3
93.8
94.3
94.8
95.2
95.7
96.2
96.6
97.1
97.5
98.0
98.4
98.9
99.3
99.7
PSIG
318.0
320.0
322.0
324.0
326.0
328.0
330.0
332.0
334.0
336.0
338.0
340.0
342.0
344.0
346.0
348.0
350.0
352.0
354.0
356.0
358.0
360.0
362.0
364.0
366.0
368.0
370.0
372.0
374.0
376.0
378.0
380.0
382.0
384.0
386.0
388.0
390.0
392.0
394.0
396.0
398.0
400.0
402.0
404.0
406.0
408.0
410.0
412.0
414.0
416.0
418.0
°F
100.2
100.7
101.1
101.6
102.0
102.4
102.9
103.3
103.7
104.2
104.6
105.1
105.4
105.8
106.3
106.6
107.1
107.5
107.9
108.3
108.8
109.2
109.6
110.0
110.4
110.8
111.2
111.6
112.0
112.4
112.6
113.1
113.5
113.9
114.3
114.7
115.0
115.5
115.8
116.2
116.6
117.0
117.3
117.7
118.1
118.5
118.8
119.2
119.6
119.9
120.3
PSIG
420.0
422.0
424.0
426.0
428.0
430.0
432.0
434.0
436.0
438.0
440.0
442.0
444.0
446.0
448.0
450.0
452.0
454.0
456.0
458.0
460.0
462.0
464.0
466.0
468.0
470.0
472.0
474.0
476.0
478.0
480.0
482.0
484.0
486.0
488.0
490.0
492.0
494.0
496.0
498.0
500.0
502.0
504.0
506.0
508.0
510.0
512.0
514.0
516.0
518.0
520.0
°F
120.7
121.0
121.4
121.7
122.1
122.5
122.8
123.2
123.5
123.9
124.2
124.6
124.9
125.3
125.6
126.0
126.3
126.6
127.0
127.3
127.7
128.0
128.3
128.7
129.0
129.3
129.7
130.0
130.3
130.7
131.0
131.3
131.6
132.0
132.3
132.6
132.9
133.3
133.6
133.9
134.0
134.5
134.8
135.2
135.5
135.8
136.1
136.4
136.7
137.0
137.3
PSIG
522.0
524.0
526.0
528.0
530.0
532.0
534.0
536.0
538.0
540.0
544.0
548.0
552.0
556.0
560.0
564.0
568.0
572.0
576.0
580.0
584.0
588.0
592.0
596.0
600.0
604.0
608.0
612.0
616.0
620.0
624.0
628.0
632.0
636.0
640.0
644.0
648.0
652.0
656.0
660.0
664.0
668.0
672.0
676.0
680.0
684.0
688.0
692.0
696.0
°F
137.6
137.9
138.3
138.6
138.9
139.2
139.5
139.8
140.1
140.4
141.0
141.6
142.1
142.7
143.3
143.9
144.5
145.0
145.6
146.2
146.7
147.3
147.9
148.4
149.0
149.5
150.1
150.6
151.2
151.7
152.3
152.8
153.4
153.9
154.5
155.0
155.5
156.1
156.6
157.1
157.7
158.2
158.7
159.2
159.8
160.3
160.8
161.3
161.8
*Based on ALLIED SIGNAL Data
38
Page 39
SERVICING
LIQUID PRESSURE
LIQUID PRESSURE
AT ACCESS FITTING (PSIG)
AT SERVICE VALVE (PSIG) 8 10 12 14 16 18
REQUIRED LIQUID LINE TEMPERATURE
REQUIRED SUBCOOLING TEMPERATURE (°F)
189 585654525048 195 605856545250 202 626058565452 208 646260585654 215 666462605856 222 686664626058 229 706866646260 236 727068666462 243 747270686664 251 767472706866 259 787674727068 266 807876747270 274 828078767472 283 848280787674 291 868482807876 299 888684828078 308 908886848280 317 929088868482 326 949290888684 335 969492908886 345 989694929088 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96 94 384 106 104 102 100 98 96 395 108 106 104 102 100 98 406 110 108 106 104 102 100 416 112 110 108 106 104 102 427 114 112 110 108 106 104 439 116 114 112 110 108 106 450 118 116 114 112 110 108 462 120 118 116 114 112 110 474 122 120 118 116 114 112 486 124 122 120 118 116 114 499 126 124 122 120 118 116 511 128 126 124 122 120 118
39
Page 40
SERVICING
S-125 THERMOSTATIC EXPANSION VALVE
The expansion valve is designed to control the rateof liquid refrigerant flow into an evaporator coil in exact proportion to the rate of evaporation of the refrigerant in the coil. The amount of refrigerant entering the coil is regulated since the valve responds to temperature of the refrigerant gas leaving the coil (feeler bulb contact) and the pressure of the refrigerant in the coil. This regulation of the flow prevents the return of liquid refrigerant to the compressor.
The illustration below shows typical heatpump TSV/check valve operation in the heating and cooling modes.
COOLING HEATING
TXV VALVES
Some TXV valves contain an internal check valve thus eliminat­ing the need for an external check valve and bypass loop. The three forces which govern the operation of the valve are: (1) the pressure created in the power assembly by the feeler bulb, (2) evaporator pressure, and (3) the equivalent pressure ofthe su­perheat spring in the valve.
0% bleed type expansion valves are used on indoor and out­door coils. The 0% bleed valve will not allow the system pres­sures (high and Low side) to equalize during the shut down period. The valve will shut of completely at approximately 100 PSIG.
30% bleed valves used on some other models will continue to allow some equalization even though the valve has a shut-off completely because of the bleed holes within the valve. This type of valve should not be used as a replacement for a 0% bleed valve, due to the resulting drop in performance.
The bulb must be securely fastened with two straps to a clean straight section of the suction line. Application of the bulb to a horizontal run of line is preferred. If a vertical installation cannot be avoided, the bult must be mounted so that the capillary tubing comes out at the top.
THE VALVES PROVIDED ARE DESIGNED TO MEET THE SPECIFICATION REQUIRMENTS FOR OPTIMUM PRODUCT OPERATION. DO NOT USE SUBSTITUTES.
S-200 CHECKING EXTERNAL STATIC PRESSURE
The minimum and maximum allowable duct static pressure is found in the Technical Information Manual.
Too great of an external static pressure will result in insuffi­cient air that can cause icing of the coil, whereas too much air can cause poor humidity control, and condensate to be pulled off the evaporator coil causing condensate leakage. Too much air can cause motor overloading and in many cases this con­stitutes a poorly designed system. To determine proper air movement, proceed as follows:
1. Using a draft gauge (inclined manometer) measure the static pressure of the return duct at the inlet of the unit, (Negative Pressure).
Supply
Return
Total External Static
2. Measure the static pressure of the supply duct, (Positive Pressure).
3. Add the two readings together.
NOTE: Both readings may be taken simultaneously and read directly on the manometer as shown in the illustration above, if so desired.
4. Consult proper table for quantity of air.
If the external static pressure exceeds the minimum or maxi­mum allowable statics, check for closed dampers, dirty filters, undersized or poorly laid out ductwork.
40
Page 41
SERVICING
S-201 CHECKING TEMPERATURE RISE
Temperature rise is related to the BTUH output of the unit and the amount of air (CFM) circulated over the indoor coil.
All units are designed for a given range of temperature increase. This is the temperature of the air leaving the unit minus the temperature of the air entering the unit.
The more air (CFM) being delivered through a given unit the less the rise will be; so the less air (CFM) being delivered, the greater the rise. The temperature rise should be adjusted in accordance to a given unit specifications and its external static pressure.
1. Take entering and leaving air temperatures.
2. Select the proper speed tap from the unit's blower perfor­mance data in the Technical Manual for the specific unit.
3. Take motor amperage draw to determine that the motor is not overloaded during adjustments.
T
SUPPLY
T
RETURN
RISE = SUPPLY -TRETURN
T
Checking Temperature Rise
41
Page 42
AIRFLOW
ADJUSTING SPEED TAP FOR INDOOR BLOWER MOTOR
Evaporator Blower Specifications with ECM Motors
APH1624H41 / APC1524H41 APH1630H41 / APC1530H41
Cooling/HP
Speed
D Minus 721 D Minus 721 D Minus 969 D Minus 969 D Normal 909 D Normal 909 D Normal 985 D Normal 985 D Plus 953 D Plus 953 D Plus 1,073 D Plus 1,073
C Minus 800 C Minus 800 C Minus 930 C Minus 930 C Normal 905 C Normal 905 C Normal 1,032 C Normal 1,032 C Plus 986 C Plus 986 C Plus 1,135 C Plus 1,135 B Minus 743 B Minus 743 B Minus 834 B Minus 834 B Normal 847 B Normal 847 B Normal 984 B Normal 984 B Plus 939 B Plus 939 B Plus 1,101 B Plus 1,101 A Minus 714 A Minus 714 A Minus 833 A Minus 833 A Normal 815 A Normal 815 A Normal 937 A Normal 937 A Plus 903 A Plus 903 A Plus 1,036 A Plus 1,036
* @ 0.1 - 0.9 ESP * @ 0.1 - 0.9 ESP
Cooling/HP
Speed
D Minus 1,135 D Minus 1,135 D Minus 1,289 D Minus 1,289 D Norma l 1,270 D Normal 1,270 D Nor mal 1,392 D Normal 1,392 D Pl us 1,3 71 D P lus 1,371 D Pl us 1,440 D Plus 1,4 40
C Minus 1,042 C Minus 1,042 C Minus 1,219 C Minus 1,219 C Norma l 1,178 C Normal 1 ,178 C Normal 1,323 C Normal 1,323 C Pl us 1,307 C Plus 1,307 C Plus 1,4 19 C Plus 1,4 19 B Minus 932 B Minus 932 B Minus 1,182 B Minus 1,182 B Norma l 1,065 B Nor mal 1,065 B Normal 1,294 B Normal 1,2 94 B Pl us 1,181 B Plus 1,181 B Pl us 1,3 84 B Plus 1,3 84 A Minus 823 A Minus 823 A Minus 1,105 A Minus 1,105 A Normal 952 A Normal 952 A Normal 1,219 A Normal 1,219 A P lus 1,080 A P lus 1,080 A Pl us 1,304 A Plus 1,304
* @ 0.1 - 0.9 ESP * @ 0.1 - 0.9 ESP
Adjust
Tap
APH1636H41 / APC1536H41 APH1642H41 / APC1542H41
Adjust
Tap
CFM*
CFM*
Elect ric
Heat
Elect ric
Heat
Adjust
Tap
Adjust
Tap
CFM*
CFM*
Cooling/HP
Spee d
Cooling/HP
Spee d
Adjust
Tap
Adjust
Tap
CFM*
CFM*
Electr ic
Heat
Electr ic
Heat
Adjust
Tap
Adjust
Tap
CFM*
CFM*
APH1648H41 / APC15[48-60]H41
Cooling/HP
Speed
D Minus 1,506 D Minus 1,506 D Normal 1,699 D Normal 1,699 D Plus 1,872 D Plus 1,872
C Minus 1,420 C Minus 1,420 C Normal 1,596 C Normal 1,596 C Plus 1,764 C Plus 1,764 B Minus 1,323 B Minus 1,323 B Normal 1,491 B Normal 1,491 B Plus** 1 ,642 B Pl us ** 1,642 A Minus 1,217 A Minus 1,217 A Normal 1,385 A Normal 1,385 A Plus 1,537 A Plus 1,537
* @ 0.1 - 0.9 ESP
** Denotes factory settings for APC156041
Adjust
Tap
CFM*
Elect ric
Heat
42
Adjust
Tap
CFM*
Page 43
AIRFLOW
MOD EL
APC152 4
APH1 624
APC153 0
APH1 630
APC153 6
APH1 636
APC154 2
APH1 642
APC154 8
APH1 648
APC156 0
(F)
Factory Setting
SPEED
TAP
SWITCH1SWITCH2 ELECTRIC
HEAT (CFM)
A Off Off
B On Off 850 C Off On 907
D On On 955
A Off Off
B On Off 987 C Off On 1034
D On On 1,073
A Off Off
B On Off 1067 C Off On 1179
D On On 1273
A Off Off 1222 B On Off 1298
C Off On
D On On 1395
A Off Off
B On Off 1499 C Off On 1605
D On On 1708
A Off Off
B On Off 1600 C Off On 1700
D On On 1800
816
940
954
1327
1394
1500
MODEL
(F)
SPEED
TAP
APC1524
APH1624
SWITCH5SWITCH6COOLING/HP
CFM
A Off Off
B On Off 850
C Off On 907
816
(F)
D On On 955
(F)
APC1530
APH1630
A Off Off
B On Off 987
C Off On 1034
940
(F)
D On On 1,073
(F)
APC1536
APH1636
A Off Off
B On Off 1067
C Off On 1179
954
(F )
D On On 1273 A Off Off 1222
(F)
APC1542
APH1642
B On Off 1298
C Off On
1327
(F)
D On On 1395
(F)
APC1548
APH1648
(F)
APC1560
A Off Off
B On Off 1499
C Off On 1605
D On On 1708
A Off Off
B On Off 1600
C Off On 1700
1394
1500
(F)
(F)
D On On 1800
(F)
Fa ctory Setting
DIP Switch Settings
for Single & Two-Stage Thermostats
MODEL
SWITCH
3
N/A O N Si ngle Stage
APC15/H16**
N/A OFF Two-Stage
SWITCH
4
THERMOSTAT
Adjustments Through DIP Switch Combinations
7 - 8
CFM
SWITCH
7
Plus10% ON OFF
Normal OFF OFF
Minus10% OFF ON
SWITCH
8
43
Page 44
WIRING DIAGRAMS
GPC15[24-48]H41**
PU
BK
BK
PU
BL
GR
YL
GR
4
T1
NOTE #2
EM
G
5
WH
EM
IF USED
WH
COMP
C
S.A.
SUPPLY VOLTAGE
R
S
NOTE #3
C L G N
1
2 3
SEE NOTE 2
L1
C
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
N
YL
SA (IF USED) SEE NOTE 4
208-240/1/60
T2
C
RCCF
H
F
NOTE #4
L
208-240
2
3 1
24V
RD
C
CM
TR
BK
1
2
208
C
TR
24V
BL
YL
RD
BR
H
C
F
RCCF
PU
L2
NOTE #3
T2
T1
GR
RD
RD
YL
CR
PU
BK
L2
C
L1
SEE NOTE 5
LVJB
YL RD GR
WH
BR
BL
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
IGNITER
GND
Y R G
W1
W2 C
++
CONTROL BOX
HPS
F
ACTORY WIRING LINE VOLTAGE LOW VOLTAGE
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE LOW VOLTAGE
WIRE CODE
BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
2 0 8
­2 4 0
/
1
/
60
T H E R M O S T A T
PU
3
240
BL
RD
GR
WH
WH
BL
PLF
9
3
8
562
41
BR
7
BR
BK
BR
PU
BK
CM
COMPONENT
LEGEND
BR
BLOWER INTERLOCK RELAY
C
CONTACTOR
CH
CRACKCASE HEATER
CM
CONDENSER MOTOR
COMP
COMPRESSOR
EBTDR
ELECTRONIC BLOWER TIME DELAY RELAY
EM
EVAPORATOR MOTOR
FC
FAN CAPACITOR
GND
EQUIPMENT GROUND
LVJB
LOW VOLTAGE JUNCTION BOX
PLF
FEMALE PLUG / CONNECTOR
RCCF
RUN CAPACITOR FOR COMPRESSOR AND FAN
SA
START ASSIST
TR
TRANSFORMER
HPS
HIGH PRESSURE SWITCH
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
BL
RD
RD
BK
BK
YL
RD
BK
YL
S
COMP
4
5
6
PLF
R W2 W1 Y G C
THERMOSTAT
++
44
1
EM
2 3
HPS
C
SEE NOTE #2
OTES:
N
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED REPLACE LEAD ON EBTDR "COM" WITH LEAD ON EBTDR "M1" OR "M2"
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM TERMINAL 3 TERMINAL 2 ON TRANSFORMER.
4. START ASSIST FACTOR EQUIPED WHEN REQUIRED
C
5. USE COPPER CONDUCTORS ONLY ++ USE N.E.C. CLASS 2 WIRE
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
208-240/1/60 0140G00871-C
Page 45
WIRING DIAGRAMS
NOTE #2
WH
NOTE #3
EM
TR
24V
208-230
3
240
208-230/1/60
SUPPLY VOLTAGE
C
COMP
C
S.A.
S
T1
R
L1
C
NOTE #4
H
F
RCCF
CM
T2
C
L2
H
RCCF
F
C
YL
BR
PU
2
24V
208
TR
C
BK
1
PU
COMP
CM
BR
BR
41
PLF
PU
BK
YL
S
BK
RD
BK
562
3
CR
LVJB
RD
BL
BR
WH
GR
PU
R
C
W2
W1
G
Y
A T
O
T
S
M
R
E
H
T
T2
T1
RD
BL
NOTE #3
PU
L1
GND
C
L2
PU
BK
60
/
/
1
0
3
2
-
8
0
2
7
8
9
BL
BR
208-230/1/60 0140G03702-A
RD
RD
BK
BK
RD
C L G N
1
2
3
BL
BL
RD
RD
GR
GR
GR
EM
GR
SEE NOTE 2
L
3 1
2
R W2 W1 Y G C
4
5
6
PLF
SEE NOTE #2
IF USED
THERMOSTAT
N
G
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
EM
1
C
2 3
SEE
NOTE 5
YL
RD SA (IF USED) SEE NOTE 4
PU
WH
BK
PU
4
5
WH
WH
BK
HPS
CONTROL BOX
C
HPS
COMPONENT
LEGEND
C
CM COMP
EM
GND LVJB PLF RCCF
SA TR HPS CSR SOL
CONTACTOR
CONDENSER MOT OR COMPRESSOR
EVAPORATOR MOTOR
EQUIPMENT GROUND LOW VOLTAGE JUNCTION BOX FEMALE PLUG / CONNECTOR RUN CAPACI TOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER HIGH PRESSURE SWITCH COMPRESSOR SOLENOID RELAY HI STAGE SOLENOID
F
ACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
OPTIONAL HIGH
VOLTAGE
FIELD WIRING
HIGH VOLTAGE
LOW VOLT AGE
WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
NOT
ES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOT OR SPEED MOVE YELLOW AND WHITE LEADS FROM EM "2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE ENERIZED, THE HIGHER SPEED SETTING IS USED.
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRE S FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. START ASSIST FACTOR EQUIPED WHEN REQUIRED
5. USE COPPER CONDUCTORS ONLY
++
USE N.E.C. CLASS 2 WIRE
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
IGNITER
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
1
2
4
3
YL
YL
YL
BL
BL
YL
YL
YL
YL
Y2YL
YL
YL
YL
YL
YL
YL
SOL
BL
BL
BL
CSR
Y2
SOL
GR
CSR
BL
BL
GPC1560H41**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
45
Page 46
WIRING DIAGRAMS
APC15[24-48]H41**
RD
BK
BK
1
2
208
C
TR
24V
BK
RD
YL
RD
BR
H
YL
SA (IF USED) SEE NOTE 3
C
F
RCCF
PU
RD
GR
VSM
3
240
BL
NOTE #2
PU
BL
GR
RD
PLF
3
562
41
WH
T2
T1
RD
RD
CR
WH
PU
BK
L2
C
L1
SEE NOTE 4
GND
YL
BL
2 0 8
­2 3 0 / 1 /
60
LVJB
W1 W2
C
R
G Y
++
CONTROL BOX
T H E R M O S T A T
OFF
ON
12
DIP SWITCH
43
6 75 8
24 VAC
HEATER
CR
W2
W1
Y1
THERMOSTAT
HUM
Y1/Y2
C RY1G
HUMIDIST A T
WH
VSTB
BR
W2ED
BL
COM
O
R
YCON
CONDENSER
HEATPUMP
OUTDOOR
W/W2
O
CTO1TO2TO
E/W1
RD
GR
YL
BL
BL
RD
BL
RD
BK
BK
BL
RD
WH
9
BR
8
7
BR
BK
BK
PU
BR
CM
YL
BK
S
COMP
L1
SUPPLY VOLTAGE
208-230/1/60
T2
H
N
RCCF
NOTE #3
208-230
C
C
F
CM
2
T1
G
C
IF USED
S.A.
COMP
NOTE #2
R
S
3 1
C
L
VSM
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
L2
TR
24V
4
5
6
PLF
C
COMPONENT LEGEND
BLOWER INTERLOCK RELAY
BR C
CONTACTOR
CH
CRACKCASE HEATER
CM
CONDENSER MOTOR
COMP
COMPRESSOR
EBTD
ELECTRONIC BLOWER TIME DELAY RELAY
R
EVAPORATOR MOTOR
EM
FAN CAPACITOR
FC
EQUIPMENT GROUND
GND
LOW VOLTA GE JUNCTION BOX
LVJB
FEMALE PLUG / CONNECTOR
PLF
RUN CAPACITOR FOR
RCCF
COMPRESSOR AND FAN
SA
START ASSIST
TR
TRANSFORMER
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. START ASSIST FACTOR EQUIPED WHEN REQUIRED
4. USE C OPPER CONDUCTOR S ONLY
+ +
USE N.E.C. CLASS 2 WIRE
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
IGNITER
FA
CTORY WIRING LINE VOLTAGE LOW V OLTAGE OPTIONAL HIGH VOLTAGE
FIELD WIRING HIGH VOLTAGE LOW V OLTAGE
WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH W HITE YL YELLOW
YCON
W1
W2
R
O
VSTB
W/
R
W2
Y\
E/
O
Y2
W1
THERMOSTAT
++
Y1
Y1
46
COM
G
C
G
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
208-230/1/60 0140G03703-A
Page 47
WIRING DIAGRAMS
NOTE #2
VSM
TR
24V
208-230
3
CONTROL BOX
240
208-230/1/60
SUPPLY VOLTAGE
C
COMP
C
S.A.
S
T1
R
L1
C
NOTE #3
H
F
RCCF
CM
T2
C
L2
H
RCCF
F
C
YL
BR
RD
2
24V
208
TR
C
BK
1
RD
COMP
CM
BR
BR
41
PLF
PU
BK
YL
S
BK
RD
BK
562
3
CR
T2
T1
RD
BL
NOTE #2
PU
BL
L1
GND
C
L2
PU
BK
60
/
/
1
0
3
2
-
8
0
2
7
8
9
BL
208-230/1/60 0140G03704-A
RD
RD
BK
BK
RD
RD
RD
GR
N
3 1
2
4
5
6
PLF
C
IF USED
L
G
SEE
NOTE 4
YL
RD SA (IF USED) SEE NOTE 3
PU
BK
PU
BK
COMPONENT LE GEND
C
CM COMP
EM
GND LVJB PLF RCCF
SA TR HPS CSR SOL
CONTACTOR
CONDENSER MOTOR COMPRESSOR
EVAPORATOR MOTOR
EQUIPMENT GROUND LOW VOLT AGE JUNCTION BOX FEMALE PLUG / CONNECTOR RUN CAPACITOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER HIGH PRESSURE SWITCH COMPRESSOR SOLENOID RELAY HI STAGE SOLENOID
FACTORY
WIRING
LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLT AGE
FIELD WIRING HIGH V OLTAGE LOW VOLTAGE
WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTEC TION
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SI ZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE W IRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. START ASSIST FACTOR EQUIPED W HEN REQUIRED
4. USE COPPER CONDUCTORS ONLY
+ +
USE N.E.C. CLASS 2 WIRE
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
IGNITER
SWITCH (PRESS .)
OVERCURRENT
PROT. DEVICE
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
R
C
W2
W1
G
A T
O
T
S
M
R
E
H
T
++
OT2
OT1OTC
O
W/W2
E/W1
R
YCON
COM
O
W2
ED
OUTDOOR
CONDENSER
HEATPUMP
VSTB
C RY1G
Y1/Y2
HUMIDIST A T
W2
24VAC
CR
Y1
431
2
875
6
DIP SWITCH
ON
OFF
HUM
W1
HEATER
THERMOSTAT
WH
BR
BL
RD
GR
YL
Y2
LVJB
VSM
R
W2Y2W1
Y1
G
COM
YCON
R
W/
W2
Y2
E/
W1
Y1
G
C
THERMOSTAT
Y\ Y2
VSTB
++
BL
BL
BL
BL
WH
WH
WH
BR
HPS
CSR
SOL
HPS
12
4
3
SOL
BL
BL
BL
BL
BL
YL
YL
YL
YL
BL
YL
YL
YL
YL
YL
YL
YL
PU
PU
PU
PU
PU
PU
PU
GR
APC1560H41**
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
47
Page 48
WIRING DIAGRAMS
GPH16[24-42]H41**
48
SEE NOTE 8
SEE NOTE 7
BK
PU
L2
C
L1
P
U
B
K
SEE NOTE 5
P
U
B
K
GND
LVJB
YL
RD GR WH
OR
BR
BL
P
U
R
D
B
K
R
C
S
H
B
K
Y R G W1
O W2 C
++
SEE NOTE 6
D
2 0 8
­2 4 0 / 1 /
60
T H E R M O S T
A T
C
H
B
K
G
R
SEE NOTE 6
FACTORY WIRING LINE VOLTAGE LOW VOL TAGE OPTIONAL HIGH VOLTAGE
FIELD WIRING HIGH VOLTAGE LOW VOL TAGE
WIRE CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
0140G01640-C
BK
3
2
208
240
TR
24V
SA SEE NOTE 4
/
B
L
2
T
E
SEE NOTE 3
PU
BL
T2
RD
T1
BK
BK
PU
OR
RD
GR
Y
L
RD
BK
S
CR
COMP
BL
P
HPS
B
K
B
L
BL
RD
GR
H
W
H
W
PLF
9
3
8
562
41
7
P
U
Y
L
P
K
/
L
COMPONENT LEGEND
C CCR CH CHS CM COMP DC DFT EM GND HVDR LPS LVDR LVJB PLF RVC RCCF
SA TR HPS
PU
RD
RD
P
U
BR
BR
BK
PU
BR
BK
PU
CM
YL
CONTACTOR COMPRESSOR CONTACTOR RE LAY CRACKCASE HEATER CRACKCASE HEATER SW ITCH CONDENSER MOTOR COMPRESSOR DEFROST CONTROL DEFROST THERMOSTAT EVAPORATOR MOTOR EQUIPMENT GROUND HIGH VOLTAGE DEFROST RELAY LOW PRESSURE SWITCH LOW VOLTAGE DEFROST RELAY LOW VOLTAGE JUNCTION BOX FEMALE PLUG / CONNECTO R REVERSING VALVE COIL RUN CAPACITOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER HIGH PRESSURE SWI TCH
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
IGNITER
SWITCH (PRESS.)
OVERCURRENT PROT. DEVICE
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE WHITE AND YELLOW LEADS FROM EM"2" AND "3" TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED. 3 FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED
5. USE COPPER CONDUCTO RS ONLY
++
USE N.E.C. CLASS 2 WIRE
6. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY EQUIPPED WHEN REQUIRED.
7. DOUBLE POLE CO NTACTOR SHOWN. SINGLE POLE CONTACT OR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.
8. COMMON SIDE OF CONTACTOR CAN NOT BE GROUNDED OR CONNECTED TO ANY OTHER COMMON (24V).
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
B
L
H
H
W
RCCF
CONTROL BOX
DF2
T
F
P
2
S
3
C
M
PU
1
C
BL
P
U
O
R
Y
L
RD
BR
H
C
F
RDYL
R
D
L2
D
T
F
C
C
N
T
N
S
E
O
E
C
LPS
P
K
Y
/
L
YL/PK
Y
L
Y
L
R
D
R
D
B
C
R
CCR
LVDR
DFT
DF2
H
W
T1
C
S.A.
SEE NOTE 4
G
SEE NOTE 3
R
L
C
C
CNT
0
0
0-RV
C-RV
W
Y
Y
PS2
R-PS1
R-DFT
R
D
D
R
R
D
GR
DFT
SUPPLY VOLTAGE
208-240/1/60
R
COMP
S
H
CHS
L
1 3
C
R
V
O
-
O
W
R
O
2
W
H
T
E
O
R
B
K
W
H
P
U
R
D
T2
C
RCCF
F
SEE NOTE 6
208-240
2
V
4
2
V
R
­D
C
Y
H
P
S
Y
1
W
R
M
O
S
T
++
P
U
P
U
W
B
K
B
K
Y
L
B
K
B
K
RVC
C
DF1
HVDR
CM
CH
TR
D
D
R
T
F
-
P
1
S
R
-
P
L
S
2
E
1
G
C
A
T
BK
PU
G
R
R
C D
BL
HVDR
GR
DF1
Y
L
YL
Y
L
C
L G N
1
2
3
4 5
2 S
E
C
P
O
L N
E
N
4 5
6
P
F
L
EM
O
N
E
Y
L
O
7
T
E
SEE NOTE 2
EM
R
V
C
SEE NOTE 2
L1
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
R
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Page 49
WIRING DIAGRAMS
SEE NOTE 2
SEE NOTE 3
EM
TR
208-230
3
240
208-230/1/60
SUPPLY VOLTAGE
C
COMP
C
S.A.
S
T1
R
L1
DF1
C
SEE NOTE 4
H
F
RCCF
CM
HVDR
T2
C
DF2
L2
H
RCCF
F
C
BR
PU
2
24V
208
TR
C
BK
1
PU
COMP
CM
BR
BR
PU
41
PLF
PU
BK
YL
S
BK
RD
BK
5
6
2
3
CR
LVJB
RD
OR
BL
BR
WH
GR
PU
R
O
C
W2
W1
G
Y1
A T
O
T
S
M
R
E
H
T
T2
T1
RD
BL
SEE NOTE 3
PU
BL
L1
GND
C
L2
BK
60
/
/
1
0
3
2
-
8
0
2
7
8
9
BL
BR
0140G03658-A
RD
RD
BK
BK
RD
PU
C
L
G
N
1
2 3
BL
BL
RD
GR
GR
RD
EM
GR
SEE NOTE 2
DFT
RVC
++
N
1 3
2
L
G
N
OTES:
1. REPLACEMENT W IRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE YELLOW AND W HITE LEADS FROM EM"2" AND "3" TO "4" AND "5". IF BOTH LEA DS ARE ENERGIZED, THE HIGHER SPEED SETTING IS USED. 3 FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
4. START ASSIST FACTORY EQUIPPED WHEN REQUIRED
5. USE COPPER CONDUCTORS ONLY
++
USE N.E.C. CLASS 2 WIRE
6. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY EQUIPPED WHEN REQUIRED.
7. DOUBLE POLE CONTACTOR SHOW N. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.
8. COMMON SIDE OF CONTACTOR CAN NOT BE GROUNDED OR CONNECTED TO ANY OTHER COMMON (24V).
SEE NOTE 5
SA SEE NOTE 4
RD
YL
BK
OR
GR
4 5
HPS
CH
CHS
LPS
YL/PK
PU
R
D
R
D
C
H
S
C
H
G
R
B
K
B
K
B
K
B
K
P
U
B
K
P
U
P
U
B
L
/
P
K
B
L
/
P
K
P
U
R
W
2
O
W
1
Y
1
G
C
4 5
6
P
L
F
E
M
1
C
H
P
S
C
T
H
E
R
M
O
S
T
A
T
2
3
S
E
E
N
O
T
E
2
2
4
V
D
C
D
F
T
Y
C
R
R
V
C
L
P
S
C
N
T
R
-
P
S
1
P
S
2
R
W
O
R
-
D
F
T
D
F
T
O
-
R
V
C
-
R
V
P
U
2
P
O
L
E
O
N
L
Y
S
E
E
N
O
T
E
7
P
U
P
U
B
L
SEE NOTE 6
SEE NOTE 6
SEE NOTE 6
R
D
R
D
P
U
W
H
B
L
O
R
CONTROL BOX
Y
L
SEE NOTE 7
SEE NOTE 8
Y
L
W
H
W
H
W
H
B
K
B
K
B
K
P
U
P
U
P
U
Y
L
R
D
B
L
Y
L
O
R
Y
L
/
P
K
PS2
C
C
R
C
Y
Y
R-PS1
R-DFT
DFT
0
CNT
CCR
HVDR
LVDR
W
C-RV
0-RV
0
DF2
DF1
R
D
C
G
R
R
D
R
D
R
D
W
H
R
D
Y
L
Y
L
W
H
B
K
B
K
CO
M
PONENT LEGEND
C CCR CH CHS CM COMP DC DFT EM GND HVDR LPS LVDR LVJB PLF RVC RCCF
SA TR HPS CSR SOL
CONTACTOR COMPRESSOR CONTACTOR RELAY CRACKCASE HEATER CRACKCASE HEATER SWITCH CONDENSER MOTOR COMPRESSOR DEFROST CONTROL DEFROST THERMOSTAT EVAPORATOR MOTOR EQUIPMENT GROUND HIGH VOLTAGE DEFROST RELAY LOW PRESSURE SWITCH LOW VOLTAGE DEFROST RELAY LOW VOLTAGE JUNCTION BOX FEMALE PLUG / CONNECTOR REVERSING VALVE COIL RUN CAPACITOR FOR COMPRESSOR AND FAN START ASSIST TRANSFORMER HIGH PRESSURE SWITCH COMPRESSOR SOLENOID RELAY HI STAGE SOLENOID
FACTORY
WIRING LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE
FIELD W
IRING HIGH VOLTAGE LOW VOLTAGE
WIRE
CODE BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
EQUIPMENT GROUND
FIELD GROUND
FIELD SPLICE
SWITCH (TEMP)
IGNITER
SWITCH (PRESS.)
OVERCURRENT PROT. DEVICE
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
++
Y
2
S
O
L
C
S
R
3
1
4
2
Y
L
Y
L
Y
L
Y
L
Y
L
Y
L
Y
L
Y
2
Y
L
Y
L
B
L
B
L
B
L
B
L
Y
L
Y
L
Y
L
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
GPH1648H41**
49
Page 50
WIRING DIAGRAMS
APH16[24-42]H41**
B
16 PIN PLUG
SEE NOTE 9
SEE NOTE 8
BK
PU
SEE NOTE 4
P
U
B
K
GND
B
L
P
U
VSTB
ED
W2
OT1
OT2
WH
BR
OR
BL
COM
O
YCON
R
CONDENSER
HEATPUMP
OUTDOOR
O
W/W2
OTC
E/W1
OFF
ON
DIP SWITCH
4213 8756
24 VAC
HEATER
CR
W2
W1
Y1
THERMOSTAT
RY1G
C
Y1/Y2
RD
GR
YL
U
S
E
E
N
7
O
E
T
D
C
H
BK
R
D
S
BK
CH
BK
SEE NOTES 5 & 6
LVJB
W1 W2
O C R
G
Y1/Y2
++
SEE NOTE 7
GR
2 0 8
­2 3 0
/
1
/
60
T
H
E R M O
S
T
A
T
BK
2
3
240
BL
F
SA SEE NOTE 3
BL/PK
SEE NOTE 2
BL
RD
P
U
WH
WH
PLF
3
562
41
P
K
/
B
L
HPS
PU
B
L
RD
RD
BK
BK
PU
T2
L2
C
T1
L1
PU
RD
OR
9
8
7
BR
P
U
B
P
U
HUM
HUMIDISTAT
K
P
PU
BR
BK
PU
RD
BK
YL
S
R
CR
CM
COMP
RD
B
O
P
YL
H
RCCF
YL
RD
CONTROL BOX
1 C
208
TR
24V
L
R
U
RD
BR
C
RD
LPS
K
YL/PK
P
K
L
/
Y
Y
L
C
R
R
L
Y
CCR
LVDR
DC
HVDR
RD
DFT
DF2
DF1
R
D
R
D
RD
R
D
R
D
C
C
CNT
0
0
0-RV
C-RV
W
Y
Y
PS2
R-PS1
R-DFT
B
K
B
K
PU
VSM
DFT
B
BK
K
RVC
COMPO
NT LEGEND
L1
SUPPLY VOLTAGE
208-230/1/60
SEE NOTE 7
CHS
C
P
O
E
N
O
2
L
L
S
N
8
E
E
O
T
E
R
T1
C
COMP
S
Y
S.A.
CH
T2
C
DF1
C
RCCF
H
HVDR
F
CM
L2
DF2
SEE NOTE 3
1
L
208-230
2
SEE NOTE 2
3
N
VSM
G
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
TR
V
2
4
R
V
R
C
R
O
4 5 6
R
V
C
-
O
R
V
-
W
HPS
PLF
YCON
W1
W2
R
R
W2
O
W/
Y\
O
E/
Y2
W1
THERMOSTAT
+
+
VSTB
D
T
F
D
F
F
D
R
T
-
D
C
P
S
Y
R
-
L
P
S
T
C
P
S
1
2
N
C
T
C
COM
G
Y1
C
G
Y1
NE
C
CONTACTOR
CCR
COMPRESSOR CONTACTOR RELAY
CH
CRANKCASE HEATER
CHS
CRANKCASE HEATER SWITCH
CM
CONDENSER MOTOR
COMP
COMPRESSOR
CSR
COMPRESSOR SOLENOID RELAY
DC
DEFROST CONTROL
DFT
DEFROST THERMOSTAT
GND
EQUIPMENT GROUND
HPS
HIGH PRESSURE SWITCH
HVDR
HIGH VOLTAGE DEFROST RELAY
LPS
LOW PRESSURE SWITCH
LVDR
LOW VOLTAGE DEFROST RELAY
LVJB
LOW VOLTAGE JUNCTION BOX
PLF
FEMALE PLUG / CONNECTOR
RVC
REVERSING VALVE COIL
RCCF
RUN CAPACITOR FOR COMPRESSOR AND FAN
SA
START ASSIST
SOL
HI STAGE SOLENOID
TR
TRANSFORMER
VSM
VARIABLE SPEED MOTOR
VSTB
VARIABLE SPEED TERM BLOCK
FIELD GROUND
EQUIPMENT GROUND
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
S:
NOTE
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) USE COPPER CONDUCTOR ONL Y.
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE AND RED WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. START ASSIST FACTOR EQUIPPED WHEN REQUIRED
4. USE COPPER CONDUCTORS ONLY
USE N.E.C. CLASS 2 WIRE
++
5. SET DIP SWITCH 4 ON VSTB TO OFF POSITION
6. REFER TO IO FOR FAN SPEED SETTINGS
7. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY EQUIPPED WHEN REQUIRED.
8. DOUBLE POLE CONTACTOR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.
9. COMMON SIDE OF CONTACTOR CAN NOT BE GROUNDED OR CONNECTED TO ANY OTHER COMMON (24V).
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
FIELD SPLICE
SWITCH (TEMP)
IGNITER
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
FA
LINE VOLTAGE LOW VOLTA GE OPTIONAL HIGH VOLTAGE
HIGH VOLTAGE LOW VOLTA GE
BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
CTORYW
FIELD
W
IRE CO
IRING
WIRING
DE
0140G03659-A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
50
Page 51
WIRING DIAGRAMS
LPS
BK
YL/PK
YL/PK
YL
C
R
R
DC
HVDR
DF1
RD
RD
DFT
SUPPLY VOLTAGE
208-230/1/60
SEE NOTE 7
R
C
COMP
S
S.A.
O-RV
R
O
W2
R
W/
R
W2
CCR
LVDR
DF2
DFT
RD
RD
RCCF
H
N
208-230
1 3
24V
C-RV
W
YCON
W1
O
Y\
O
E/
Y2
W1
THERMOSTAT
++
YL
RD
VSM
16 PIN PLUG
L1
CHS
C
T1
2 POLE ONLY SEE NOTE 8
L
VSM
G
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
R
RVC
4 5 6
PLF
VSTB
C
C
CNT
0
0
0-RV
C-RV
W
Y
Y
PS2
R-DFT
R-PS1
RVC
CH
T2
C
DF1
C
F
SEE NOTE 3
SEE NOTE 2
2
TR
R-DFT
DC
R-PS1 PS2
Y
LPS
HPS
Y1
Y1
KBKB
HVDR
S0L
G
G
APH1648H41**
CSR
3
4
RD
1 C
208
TR
24V
SEE NOTE 2
BK
3
2
240
BL
BL
BL
RD
OR
PU
RD
YL
H
C
BK
PU
CONTROL BOX
RCCF
RD
BK
BR
F
RDYL
RD PU
WH
BL
PLF
3
SA SEE NOTE 3
BL/PK
BL/PK
WH
9
562
8
41
7
PU
HPS
YL
PU
BL
RD
RD
BK
BK
PU
RD
OR
BR
PU
PU
BR
BK
PU
BK
YL
CM
BL
SOL
12
BL
T2
T1
BK
RD
S
CR
COMP
YL
YL
PU
L2
C
L1
YL
YL
PU
HUM
Y1/Y2
HUMIDISTAT
PU
R
CHS
YL
L2
DF2
CM
COMPONENT LEGEND
C
CONTACTOR
CCR
COMPRESSOR CONTACTOR RELAY
CH
CRANKCASE HEATER
CHS
CRANKCASE HEATER SWITCH
CM
CONDENSER MOTOR
COMP
COMPRESSOR
CSR
COMPRESSOR S OLENOID RELAY
DC
DEFROST CONTROL
DFT
DEFROST THERMOSTAT
GND
EQUIPMENT GROUND
HPS
HIGH PRESSURE SWITCH
HVDR
HIGH VOLTAGE DEFROST RELAY
LPS
LOW PRESSURE SWITCH
LVDR
LOW VOLTAGE DEFROST RELAY
LVJB
LOW VOLTAGE JUNCTION BOX
PLF
FEMALE PLUG / CONNECTOR
RVC
REVERSING VALVE COIL
RCCF
RUN CAPACITOR FOR COMPRESSOR AND FAN
SA
START ASSIST
SOL
HI STAGE SOLENOID
TR
TRANSFORMER
VSM
VARIABLE SPEED MOTOR
VSTB
VARIABLE SPEED TERM BLOCK
FIELD GROUND
DFT
DFT
C
CNT
CSR
C
COM
C
EQUIPMENT GROUND
JUNCTION
TERMINAL
INTERNAL TO
INTEGRATED CONTROL
PLUG CONNECTION
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE INSULATION AS ORIGINAL (AT LEAST 105C) US E COPPER CONDUCTOR ONLY.
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE PURPLE AND RED WIRES FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. START ASSIST FACTOR EQUIPPED WHEN REQUIRED
4. USE COPPER CONDUCTORS ONLY
++
USE N.E.C. CLASS 2 WIRE
5. SET DIP SWITCH 4 ON VSTB TO OFF POSITION
6. REFER TO IO FOR FAN SPEED SETTINGS
7. CRANKCASE HEATER AND CRANKCASE HEATER SWITCH FACTORY EQUIPPED WHEN REQUIRED.
8. DOUBLE POLE CONTACT OR SHOWN. SINGLE POLE CONTACTOR COULD BE FACTORY EQUIPPED AS AN ALTERNATE CONFIGURATION.
9. COMMON SIDE OF CONTACTOR CAN NOT B E GROUNDED OR CONNECTED TO ANY OTHER COMMON (24V).
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTE CTION
FIELD SPLICE
SWITCH (TEMP)
IGNITER
SWITCH (PRESS.)
OVERCURRENT
PROT. DEVICE
BK
PU
SEE NOTE 4
PU
BK
BL
YL
OFF
ON
VSTB
13
DIP SWITCH
2
4
6
875
24 VAC
HEATER
CR
W2
W1
Y1
ED
W2
COM
O
HEATPUMP
THERMOSTAT
OUTDOOR
O
C RY1G
OT1
OTC
OT2
RD
PU
SEE NOTE 7
D
RD
BK
FA
LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE
HIGH VOLTAGE LOW VOLT AGE
BK BLACK BL BLUE BR BROWN GR GREEN OR ORANGE PU PURPLE RD RED WH WHITE YL YELLOW
SEE NOTE 9
SEE NOTE 8
GND
WH
BR OR
BL
R
YCON
CONDENSER
W/W2
E/W1
GR
YL
BK
CH
CTORY WIRING
FIELD WIRING
W
IRE CODE
60
SEE NOTES 5 & 6
LVJB
W1 W2
O C R Y1
G
Y2
++
SEE NOTE 7
GR
BK
0140G03657-A
2 0 8
­2 3 0
/
1
/
YL
T H E R M O S T A T
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
51
Page 52
WIRING DIAGRAMS
PACKAGE SYSTEM WIRING DIAG RA M - 1 STAGE ELECTRIC HEAT
SEE NOTE 1
#18 GAUGE 7 WIRE
REQUIRED FOR
HEAT PUMP S
ROOM THERMOSTAT
YO
CW1GRE
BR
PACKAGE UNIT LOW VOLTAGE JUNCTION BOX
W
R Y
G
O
YELLOW
GREEN
ORANGE
WHITE
R
Y
G O
R
TYPICAL HP
BL
BL
BLUE
BL
12
OUTDOOR THERMOSTAT
CLOSE ON TEMPERATURE FALL
PACKAGE SYSTEM WIRING DIA GRA M - 2 STAGE ELECTRIC HEAT
ABOVE 10 KW
RED
SEE NOTE 1
#18 GAUGE 8 WIRE
FOR HEAT PUMPS
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
SEE NOTE 2
ROOM THERMOSTAT
W2 C RYO W1G E
PACKAGE UNIT LOW VOLTAG E JUNCTION BOX
RED
R
Y
G O
BR
W
R
BL
R Y
G
O
W
BR
BL
YELLOW GREEN ORANGE
WHITE
BROWN
BLUE
12
OUTDOOR T HERMOSTAT
CLOSE ON TEMPERATURE FALL
TYPICAL HP
NOTES:
1) "O" and "E" used on heat pumps only.
2) Connect wire from terminal #1 on outdoor thermostat to the white wire on package units if single stage indoor thermostat is used.
Color Codes
R - Red Y - Yellow BL - Blue BR - Brown O - Orange W - White G - Green
OT18-60A OUTDOOR THERMOSTAT
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
52
Page 53
WIRING DIAGRAMS
PACKAGE SYSTEM WIRING DIAGRAM - HEAT PUMPS ONLY!
TWO-STAGE ELECTRIC HEAT ABOVE 10 kW
TYPICAL H/P
ROOM THERMOSTAT
#18 GAUGE 8 WIRE
OUTDOOR THERMOSTAT #2 (IF US ED, SEE NOTE 1)
R
BL
12
Y
3
12
OUTDOOR THERMOSTAT #1
CLOSE ON TEMPERATURE FALL
W2 C RYO W1G E
BL
W
BR
BL
G O
R
Y
PACKAGE HEAT PUMP
R Y
G
O
W
BR
BL
LOW VOLTAGE JUNCTION BOX
RED
YELLOW
GREEN
ORANGE
WHITE
BROWN
BLUE
For outdoor temperatures below 0° F with 50% or higher relative humidity, set outdoor thermostat at 0° F
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
NOTE 1: OT18 #2 CAN BE CONNECTED BETWEEN W2 OF THERMOSTAT AND BROWN WIRE IF DESIRED.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
COLOR CODES R --RED Y --YELLOW BL-BL UE BR-BROWN O --ORANGE W -WHIT E G --GREEN
OT18-60A OUTDOOR THERMOSTAT
53
Page 54
WIRING DIAGRAMS
*PC15/*PH16H41*
BK
L1 L2
FL
BK
HTR1
M1
R
M2
BK
FL
TL
R
BK
BL
W
PU
BK
R
PLM
1
2 3 4 5 6 7 8
FL
TL
HTR1
R
BK
BK
R
R
M2
M1
M3
M4
PU
BL
W
R
BK
BK
TL
HTR2
R
9
ONE (1) ELEMENT ROWS TWO (2) ELEMENT ROWS
L2L1
BK
R
PLM
1 2 3
4 5 6 7 8 9
5 KW
10 KW
FL
FL
FL FL FL
BL
Y
BK
BK
BK
R
PLM
BK
1
R
BL BR
2 3
4
5 6
R
BK
Y
PU
BL
M1
M2
R2
W
7 8 9
TL
HTR1
FL
TL
HTR2
FL
HTR3
TL
R
Y
BK
M1
R
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BK
BK
M2
M3
M4
R1
R
Y
R
HTR1
HTR2
HTR3
HTR4
BK
M1 M2
R
TL TL TL
TL
R
M3
M4
R1
Y
R
PU
BL
BK
M5 M6
BL
BK
Y
R
PLM
BK
1 2
BL
M7
M8 R2
W
3
R
BL
4
BR
5
6
7
8 9
L1
L2 L1 L2
THREE (3) ELEMENT ROWS FOUR (4) ELEMENT ROWS
15 KW
SINGLE PHASE HKR/P** HEAT KIT
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
54
L2L1 L1 L2
20 KW
Page 55
WIRING DIAGRAMS
*PC15/*PH16H41*
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PCE* ECONOMIZER FOR *PC/*PH****H41*
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
55
Page 56
WIRING DIAGRAMS
GR
B
A
TO CONTROL BOX
SEE NOTES 1 & 2
BK
PU/BK-3
CCB
GR
B
B
A
TO ELECTRIC HEAT
A
BK
BK
BK-3
BK-3
BK
BK
BK
BK
GR
GR
COLOR CODE
BK --------------- BLACK
GR---------------- GREEN
BR --------------- BROWN
PU ---------- ----- PURPLE
WH -------------- WHITE
WIRING CODE
FACTORY WIRING
HIGH VOLTAGE
OPTIONAL HIGH VOLTAGE
FIELD WIRING
HIGH VOLTAGE
0140G02544- A
YL --- - ----------- YELL O W
A
HIGH VOLTAGE!
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT . FAILURE TO
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
B
208 / 240 / 1 / 60
SPB
SPK* - SINGLE POINT WIRING KIT
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
56
GR
BK
BK
GR
D
LEGEN
CCB - COM PRESSOR
CIRCUIT BREAK ER
NOTES:
1. FOR APC & GPC UNITS: A = L1 / B = L2
FOR APH & GPH UNITS: A = L2 / B = L1
2. 45, 40, 35, & 30 AMP BREAKERS WILL
HAVE A PURPLE WIRE. 50 AND 60
AMP BREAKERS WILL HAVE BLACK
WIRE LABELED WITH A #3
SPB - SINGLE POINT BLOCK
Loading...