Goodman PG 15 User Manual

G
AS
I
NSTALLATION INSTRUCTIONS
F
OR
S
-E
LECTRIC
INGLE
H
EATING
P
ACKAGE
& C
*PG 15 SEER “M” SERIES
Affix this manual and Users Information Manual adjacent to the unit.
OOLING
U
NITS
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During
installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
These installation instructions cover the outdoor installation of single package gas electric heating and cooling units. See the Specification Sheet applicable to your model* for information regarding accessories.
Goodman Manufacturing Company, L.P.
IO-324H 11/12
5151 San Felipe, Suite 500, Houston, TX 77056
© 2006 - 2009, 2012 Goodman Manufacturing Company, L.P.
This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National Standard of Canada Shown Below.
ANSI Z21.47•CSA-2.3 Central Furnaces
*NOTE: Please contact your distributor or
our website for the applicable
Specification Sheet referred to in this
manual.
www.goodmanmfg.com
INDEX
REPLACEMENT PARTS ....................................................................................................................................................... 4
ORDERING PARTS .............................................................................................................................................. 4
SAFETY INSTRUCTIONS ..................................................................................................................................................... 4
UNIT LOCATION .................................................................................................................................................................. 5
ALL INSTALLATIONS: ............................................................................................................................................ 5
ROUND LEVEL INSTALLATIONS ONLY:.................................................................................................................... 5
G
OOFTOP INSTALLATIONS ONLY: ............................................................................................................................ 5
R
OOF CURB I NSTALLATIONS ONLY: ........................................................................................................................ 6
R
GENERAL INFORMATION .................................................................................................................................................... 6
TRANSPORTATION DAMAGE ................................................................................................................................... 6
RIGGING DETAILS ............................................................................................................................................................... 7
GAS PIPING......................................................................................................................................................................... 7
HIGH A LTITUDE DERATE (U.S. INSTALLATIONS ONLY) ............................................................................................... 7
IPING ............................................................................................................................................................. 7
P
AS PIPING CHECKS .......................................................................................................................................... 8
G
PROPANE GAS INSTALLATIONS ........................................................................................................................................ 8
TANKS AND PIPING ............................................................................................................................................. 8
ELECTRICAL WIRING .......................................................................................................................................................... 9
THERMOSTAT LOCATION ....................................................................................................................................... 9
INGLE STAGE THERMOSTAT ................................................................................................................................9
S
NIT VOLTAGE ................................................................................................................................................. 10
U
EAT ANTICIPATOR SETTING ................................................................................................................................10
H
CIRCULATING AIR AND FILTERS ..................................................................................................................................... 10
AIRFLOW CONVERSION ...................................................................................................................................... 10
UCTWORK ...................................................................................................................................................... 10
D
ILTERS ...........................................................................................................................................................11
F
VENTING .............................................................................................................................................................................11
INSTALLATION - FLUE HOOD EXHAUST ...................................................................................................................11
NSTALLATION - COMBUSTION AIR INTAKE HOOD ....................................................................................................... 11
I
CONDENSATE DRAIN .........................................................................................................................................................11
CONDENSATE DRAIN CONNECTION ........................................................................................................................ 11
NORMAL SEQUENCES OF OPERATION ........................................................................................................................... 12
HEATING ......................................................................................................................................................... 12
OOLING ........................................................................................................................................................ 12
C
AN ONLY ...................................................................................................................................................... 12
F
STARTUP, ADJUSTMENTS, AND CHECKS ....................................................................................................................... 12
HEATING STARTUP ............................................................................................................................................ 12
OOLING STARTUP ........................................................................................................................................... 15
C
TROUBLESHOOTING ........................................................................................................................................................ 15
IGNITION CONTROL ERROR CODES ...................................................................................................................... 15
AULT RECALL ................................................................................................................................................. 15
F
BNORMAL OPERATION - HEATING ....................................................................................................................... 16
A
NTERNAL CONTROL F AILURE ............................................................................................................................ 16
I
EXTERNAL LOCKOUT ....................................................................................................................................... 16
PRESSURE SWITCH STUCK OPEN ..................................................................................................................... 16
PRESSURE SWITCH STUCK CLOSED .................................................................................................................. 16
OPEN THERMAL PROTECTION DEVICE ............................................................................................................... 16
PRIMARY LIMIT .............................................................................................................................................. 16
AUXILIARY/SECONDARY LIMIT .......................................................................................................................... 16
ROLLOUT LIMIT ............................................................................................................................................. 16
FLAME DETECTED WITH GAS VALVE CLOSED ..................................................................................................... 16
LOW FLAME SIGNAL ....................................................................................................................................... 16
A
BNORMAL OPERATION - COOLING ...................................................................................................................... 17
HORT CYCLE COMPRESSOR DELAY ................................................................................................................ 17
S
HIGH PRESSURE S WITCH/LOSS OF CHARGE SWITCH ........................................................................................... 17
2
INDEX
MAINTENANCE .................................................................................................................................................................. 17
FILTER REPLACEMENT OR CLEANING .................................................................................................................... 17
ABINET FINISH MAINTENANCE ........................................................................................................................... 17
C
LEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY) ............................................................................................. 17
C
ONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS ..................................................................................... 17
C
LAME SENSOR (QUALIFIED SERVICER ONLY) ...................................................................................................... 17
F
LUE PASSAGES (QUALIFIED SERVICER ONLY) ..................................................................................................... 17
F
LEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY) ...................................................................................... 17
C
AIN BURNER FLAME (QUALIFIED SERVICER ONLY) .............................................................................................. 18
M
LEANING BURNERS ......................................................................................................................................... 18
C
ACCESSORIES AND FUNCTIONAL PARTS ...................................................................................................................... 18
SHEET METAL A CCESSORIES .............................................................................................................................. 18
UNCTIONAL PARTS .......................................................................................................................................... 18
F
ENERAL INFORMATION ..................................................................................................................................... 18
G
APPENDIX ......................................................................................................................................................................... 19
IGNITION CONTROL DIAGNOSTIC I NDICATOR CHART .................................................................................................. 21
EATING TIMING CHART .................................................................................................................................... 21
H
OOLING TIMING CHART ................................................................................................................................... 21
C
NIT DIMENSIONS ............................................................................................................................................ 22
U *PG15*****41A* W *PG15*****41B* W
INIMUM CLEARANCES ..................................................................................................................................... 27
M
ECOMMENDED FILTER SIZES ............................................................................................................................ 27
R
LOWER PERFORMANCE DATA ............................................................................................................................ 28
B
IRING DIAGRAM .................................................................................................................. 23
IRING DIAGRAM ................................................................................................................. 23
3
REPLACEMENT PARTS
ORDERING P ARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMPANY, L.P.
7401 SECURITY WAY
HOUSTON, TEXAS 77040
(713) 254-4729
SAFETY INSTRUCTIONS
TO THE INSTALLER
Before installing this unit, please read this manual to familiarize yourself on the specific items which must be adhered to, including maximum external static pressure to unit, air temperature rise, minimum or maximum CFM and motor speed connections.
TO THE OWNER
A warranty certificate is provided with the unit. Read the warranty carefully and note what is covered. Keep the warranty certificate in a safe place so you can find it when necessary.
Keep this literature in a safe place for future reference.
4
CARBON MONOXIDE POISONING HAZARD
Special Warning for Installation of Furnaces or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
B10259-216
To avoid possible illness or death of the building occupants,
do NOT locate outside air intake device (economizer, manual fresh air intake, motorized fresh air intake) too close to an exhaust outlet, gas vent termination, or plumbing vent outlet. For specific distances required, consult local codes.
Allow minimum clearances from the enclosure for fire
protection, proper operation, and service access (see appendix). These clearances must be permanently maintained.
The combustion air inlet and flue outlet hoods on the unit
must never be obstructed. If used, do not allow the economizer/manual fresh air damper/ motorized fresh air damper to become blocked by snow or debris. In some climates or locations, it may be necessary to elevate the unit to avoid these problems.
When the unit is heating, the temperature of the return air
entering the unit must be between 50° F and 100° F.
GROUND L EVEL I NSTALLATIONS O NLY:
When the unit is installed on the ground adjacent to the
building, a level concrete (or equal) base is recommended. Prepare a base that is 3” larger than the package unit footprint and a minimum of 3” thick.
The base should also be located where no runoff of water
from higher ground can collect in the unit.
UNIT LOCATION
IMPORTANT NOTE: Remove wood shipping rails prior to instal-
lation of the unit.
ALL I NSTALLATIONS:
For proper flame pattern within the heat exchanger and
proper condensate drainage, the unit must be mounted level.
The flue outlet hood must be at least 12 inches from any
opening through which flue gases could enter a building, and at least three feet above any forced air inlet located within ten feet. The economizer/manual fresh air intake/ motorized fresh air intake and combustion air inlet mounted on the unit are not affected by this restriction.
To avoid possible corrosion of the heat exchanger, do
not locate the unit in an area where the outdoor air (i.e. combustion air for the unit) will be frequently contaminated by compounds containing chlorine or fluorine. Common sources of such compounds include swimming pool chemicals and chlorine bleaches, paint stripper, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various commercial and industrial processes may also be sources of chlorine/ fluorine compounds.
Outside Slab Installation
ROOFTOP I NSTALLATIONS O NLY:
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
To avoid possible property damage or personal injury, the
roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.
5
Rooftop Installation
The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
ROOF C URB I NSTALLATIONS O NLY:
Sufficient structural support must be determined prior to
locating and mounting the curb and package unit.
Ductwork must be constructed using industry guidelines.
The duct work must be placed into the roof curb before mounting the package unit.
Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor.
GENERAL INFORMATION
This unit is approved for outdoor installation ONLY. Rated performance is achieved after 72 hours of operation. performance is delivered at the specified airflow. See outdoor unit specification sheet for split system models or product specification sheet for packaged and light commercial models. Specification sheets can be found at
www.goodmanmfg.com for Goodman® brand products or www.amana-hac.com for Amana® brand products. Within
either website, please select the residential or commercial products menu and then select the submenu for the type of product to be installed, such as air conditioners or heat pumps, to access a list of product pages that each contain links to that model’s specification sheet.
To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installation Codes.
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America.
Obtain from:
American National Standards Institute
1430 Broadway
New York, NY 10018
Rated
Roof Curb Installation
TRANSPORTATION D AMAGE
Check the carton upon arrival for external damage. If damage is found, a request for inspection by carrier agent should be made in writing immediately.
Carefully inspect the unit for damage including damage to the cabinetry. Any bolts or screws which may have loosened in transit must be re-tightened. In the event of damage, the receiver should:
1. Make notation on delivery receipt of any visible damage to shipment or container.
2. Notify carrier promptly and request an inspection.
3. In case of concealed damage, carrier should be notified as soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:
a. Original Bill of Lading, certified copy, or indemnity bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.
d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage.
NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes.
6
RIGGING DETAILS
p
)
g
)
IMPORTANT NOTE: If using bottom discharge with roof curb,
ductwork should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in roof curb installation instructions.
Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.
Rigging
GAS PIPING
IMPORTANT NOTE: This unit is factory set to operate on natural
gas at the altitudes shown on the rating plate.
burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure.
HIGH A LTITUDE DERATE (U.S. INSTALLATIONS O NLY)
IMPORTANT NOTE: The gas/electric units naturally derate with
altitude. Do not attempt to increase the firing rate by changing orifices or increasing the manifold pressure. This can cause poor combustion and equipment failure. At all altitudes, the manifold pressure must be within 0.3 inches W.C. of that listed on the nameplate for the fuel used. At all altitudes and with either fuel, the air temperature rise must be within the range listed on the unit nameplate.
Refer to the Installation Manual provided with the LP kit for conversion from natural gas to propane gas and for altitude adjustments.
Use HA02 for installations above 2000’.
PIPING
IMPORTANT NOTE: To avoid possible unsatisfactory operation
or equipment damage due to under firing of equipment, do not undersize the natural/propane gas piping from the meter/ tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously.
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ ANSI Z223.1.
Natural Gas Connection
Natural Gas Capacity of Pipe
in Cubic Feet of Gas Per Hour (CFH)
Length of
Pipe in Feet
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based
Nominal Black Pipe Size (inches)
1/2 3/4
on 0.60 S
1
ecific Gravity Gas
1 1/4 1 1/2
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to LP gas is permitted with the use of the factory authorized conversion kit LPM-05.
INLET GAS PRESSURE
Natural Min. 5 .0" W.C., Max. 10.0" W.C.
Propane Min . 11.0" W.C. , Max. 13.0" W.C.
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above.
The minimum supply pressure should not vary from that shown in the table above because this could prevent the unit from having dependable ignition. In addition, gas input to the
CFH =
Heatin
BTUH Furnace Input
Value of Gas (BTU/Cubic Foot
Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply:
1. Use black iron pipe and fittings for the supply piping. The use of a flex connector and/or copper piping is permitted as long as it is in agreement with local codes.
2. Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.
5. Use two pipe wrenches when making connection to the gas valve to keep it from turning.
6. Install a manual shut-off valve in a convenient location (within six feet of unit) between the meter and the unit.
7. Tighten all joints securely.
7
8. The unit must be connected to the building piping by one of the following methods:
• Rigid metallic pipe and fittings
• Semirigid metallic tubing and metallic fittings (Aluminum alloy tubing must not be used in exterior locations)
• Listed gas appliance connectors used in accordance with the terms of their listing that are completely in the same room as the equipment
• In the prior two methods above the connector or tubing must be protected from physical and thermal damage. Aluminum alloy tubing and connectors must be coated to protect against external corrosion when in contact with masonry, plaster or insulation or are subject to repeated wettings by liquids (water - not rain water, detergents or sewage)
DRIP LEG
GROUND JOINT UNION (INSTALLED AHEAD OF GAS VALVE)
GROMMET
Proper Piping Practice
NOTE: The unit gas supply entrance is factory sealed with
plugs. Keep plugs in place until gas supply is ready to be installed. Once ready, replace the plugs with the supplied grommets and install gas supply line.
GAS PIPING CHECKS
MANUAL SHUT-OFF VALVE
There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.
PROPANE GAS INSTALLATIONS
IMPORTANT NOTE: Propane gas conversion kits must be
installed to convert units to propane gas. Refer to the gas piping section for the correct LP kit for conversion.
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58).
For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, which depends on (a) temperature of the liquid, and (b) wetted surface area of the container or containers.
2. Proper pressure regulation.
3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size required will depend on length of pipe run and total load of all appliances.
TANKS AND PIPING
Complete information regarding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.
See below for typical propane gas piping.
First Stage Regulator
200 PSIG Maximum
5 to 15 PSIG (20 PSIG Max.)
Continuous
Second Stage Regulator
11" W.C.
Typical Propane Gas Piping
8
R
C
Sizing Between First and Second Stage Regulator Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10 PSIG Setting. Capacities in 1,000 BTU/HR
PIPE OR
TUBING
LENGTH,
FEET
30 309 700 1,303 2,205 3,394 1,843 3,854
40 265 599 1,115 1,887 2,904 1,577 3,298
50 235 531 988 1,672 2,574 1,398 2,923
60 213 481 896 1,515 2,332 1,267 2,649
70 196 446 824 1,394 2,146 1,165 2,437
80 182 412 767 1,297 1,996 1,084 2,267
90 171 386 719 1,217 1,873 1,017 2,127
100 161 365 679 1,149 1,769 961 2,009
150 130 293 546 923 1,421 772 1,613
200 111 251 467 790 1,216 660 1,381
250 90 222 414 700 1,078 585 1,224
300 89 201 378 634 976 530 1,109
350 82 185 345 584 898 488 1,020
400 76 172 321 543 836 454 949
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130 To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance* Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Dr op at 11" W.C. Setting. Capacities in 1,000 BTU/HR
PIPE OR TUBING
LENGTH,
FEET
10 49 110 206 348 539 291 608 1,146 2,353 3,525
20 34 76 141 239 368 200 418 788 1,617 2,423
30 27 61 114 192 296 161 336 632 1,299 1,946
40 23 52 97 164 253 137 284 541 1,111 1,665
50 20 46 86 146 224 122 255 480 985 1,476
60 19 42 78 132 203 110 231 436 892 1,337
80 16 36 67 113 174 94 198 372 764 1,144
100 14 32 59 100 154 84 175 330 677 1,014
125 12 28 52 89 137 74 155 292 600 899
150 11 26 48 80 124 67 141 265 544 815
200 10 22 41 69 106 58 120 227 465 697
250 9 19 36 61 94 51 107 201 412 618
300 8 18 33 55 85 46 97 182 374 560
350 7 16 30 51 78 43 89 167 344 515
400 7 15 28 47 73 40 83 156 320 479
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54
TUBING SIZE, O.D., TYPE L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 1" 1-1/4" 1-1/2"
TUBING SIZE, O.D., TYPE L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4"
NOMINAL PIPE SIZE,
NOMINAL PIPE SIZE,
SCHEDULE 40
SCHEDULE 40
Propane Gas Pipe Sizing
cooling. Units which will have economizers may use thermostats with two or three stages of cooling. All units can use single stage or multi-stage thermostats. Refer to figures later in this section for wiring.
The units are designed for operation on 60 hertz current and at voltages as shown on the rating plate. All internal wiring in the unit is complete. It is necessary to bring in the power supply to the contactor as shown on the unit wiring diagram which is supplied with each unit. The low voltage wiring must be connected between the unit control panel and the room thermostat.
Thermostat
R
CY1
W1
W2
W1W2
Y2
G
GY1Y2
Two-Stage Heating
(
Furnace Integrated Control Module
with
Two-Stage Cooling
Two-Stage Heating with Two-Stage Cooling
Thermostat Diagram
SINGLE STAGE T HERMOSTAT
To use a single stage thermostat, move jumper located to the left of the terminal strip labeled “Stage Delay” from NONE to “5” or “10” minutes. This selection will cause the control to run on low stage for the selected time (5 or 10 minutes) then shift to HIGH STAGE. This option controls both cooling and heating modes. If the jumper is not moved, only low-stage cool and low-stage heat will operate.
(
5 MINUTE DELAY PERIOD WITH JUMPER IN THIS POSITION
10 MINUTE DELAY
ELECTRICAL WIRING
THERMOSTAT LOCATION
PERIOD WITH JUMPER IN THIS POSITION
Mount the thermostat approximately five feet above the floor, in an area that has an inside, vibration-free wall and has good air circulation.
Movement of air must not be obstructed by furniture, door, draperies, etc. The thermostat must not be mounted where it will be affected by drafts, hot or cold water pipes or air ducts in walls, radiant heat from fireplace, lamps, the sun, television, etc. Consult the Instruction Sheet packaged with thermostat for mounting instructions.
NOTE: *PG1524, *PG1530, *PG1537, and *PG1549 units have one stage of mechanical cooling and two stages of heat. All other
Two-Stage Heating (timed) and Two-Stage Cooling (timed)
with Single Stage Thermostat Diagram
Refer to the unit wiring diagram for electrical connections. When installed, the unit must be electrically grounded in accordance with local codes or in the absence of local codes, with the National Electrical Code, ANSI/NFPA No. 70, and/or the CSA C22.1 Electrical Code. Ensure low voltage connections are waterproof.
units have two stages of heating and two stages of mechanical
9
For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weatherproof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit. Low voltage wiring from the unit control panel to the thermostat requires coded cable. See below for ground level and rooftop wiring.
Note:Junction box location shown is optional and is for illustration purposes only.
JUNCTION BOX
UNIT VOLTAGE
The unit transformer is factory connected for 230V operation. If the unit is to operate on 208V, reconnect the transformer primary lead as shown on the unit wiring diagram. The induced draft blower on some models is equipped with a low speed 230V lead (blue) and a low speed 208V lead (black). If equipped, connect the induced draft blower low speed 208V lead (black) in place of the low speed 230V lead (blue). Place the unused 230V lead on the “PARK” terminal located on ignition control.
HEAT A NTICIPATOR S ETTING
The heat anticipator is to be set by measuring the load (amperage) at the “R” circuit. Follow the instructions provided with the thermostat for more details.
CIRCULATING AIR AND FILTERS
AIRFLOW C ONVERSION
Units can easily be converted from horizontal to down­discharge airflow delivery. In down-discharge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations it will be necessary to change the blower speed to provide proper air flow.
Horizontal Air Flow
Single phase models are shipped without horizontal duct covers. If needed, these kits may be ordered through Goodman’s Service Parts department.
Electrical Power Directly To Junction Box
Electrical Power Routed Through Bottom of Unit
Typical Electrical Wiring Unit Voltage
Duct Cover Installation
Down Discharge Applications
Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place.
NOTE: Single phase models require installation of horizontal duct kit #20464501PDGK (medium chassis) and #20464502PDGK (large chassis).
DUCTWORK
Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial).
10
All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.
For duct flange dimensions on the unit refer to the Unit Dimension illustration in the appendix.
For down-discharge applications, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
FILTERS
HOOD
LOWER FLUE HOOD
LIP
SCREEN
INSTALLATION - COMBUSTION AIR INTAKE HOOD
1. Locate the second hood.
2. Using the three screws provided, attach the hood (with the opening facing down) to the heat exchanger access door.
Even though a return air filter is not supplied with this unit, there must be a means of filtering all return air. All units may be externally filtered.
Refer to the unit filter size chart in the appendix for filter size information.
Filters installed external to the unit should be sized in accordance with their manufacturer recommendations. A throwaway filter must be sized for a maximum face velocity of 300 feet per minute.
Filter Installation
IMPORTANT NOTE: When installing a filter, the air flow arrows
on the filter must point toward the circulator blower.
VENTING
NOTE: Venting is self-contained. Do not modify or block.
INSTALLATION - FLUE H OOD E XHAUST
1. Locate the flue hood assembly box from the blower compartment.
2. Slide screen over flanges on the lower flue hood.
3. Slide screen into hood.
4. Using the three screws provided, attach the hood (with the opening facing down) over the flue exhaust opening in the utility panel.
CONDENSATE DRAIN
CONDENSATE D RAIN C ONNECTION
A 3/4” NPT drain connection is supplied for condensate piping. An external trap must be installed for proper condensate drainage.
DRAIN CONNECTION
UNIT 2" MINIMUM
FLEXIBLE TUBING-HOSE OR PIPE
3" MINIMUM
11
A POSITIVE LIQUID SEAL IS REQUIRED
Drain Connection
NORMAL SEQUENCES OF OPERATION
HEATING
This unit is equipped with an ignition control that automatically lights the main burner. DO NOT attempt to light the main burners by any other method.
1. Thermostat calls for low or high stage heating.
2. Induced draft blower energizes for 15-second pre-purge.
3. The spark igniter and low and high stage gas valve are energized for 7 seconds. NOTE: The igniter produces a very intense electrical spark that ignites the gas.
4. Main burners light and control detects presence of flame.
5. If the call is for low stage heat, the induced draft blower switches to low speed and the high stage gas valve closes 5 seconds after the main burners light. If call is for high stage heat, induced draft blower remains at high speed and high stage gas valve remains open. NOTE: If a single stage thermostat is used, the control will step to low stage after the main burners light and remain at low stage for 5 or 10 minutes, depending on jumper position. If the call for HEAT remains after the transition delay time expires, the control will transition from low stage to high stage.
6. The 30-second HEAT FAN ON delay time begins after the main burners light.
7. The unit delivers heat to the conditioned space until the thermostat is satisfied.
8. Gas valve(s) de-energizes. The induced draft blower continues operation for a 30-second post-purge.
9. Induced draft blower remains at low speed (or switches from high to low if operating at high stage heat) for the 30­second post purge.
10. Ignition control begins timing the HEAT FAN OFF delay. There is an adjustable HEAT FAN OFF delay of approximately 90/120/150/180 seconds (factory set at
150). If the unit is operating at high stage when the call for heat is removed, the blower will operate for 30 seconds at high heat speed then switch to low heat speed for the remainder of the selected HEAT FAN OFF delay. NOTE: After the HEAT FAN OFF delay time has elapsed, the blower will de-energize. This allows any additional heat in the heat exchanger to be transferred to the conditioned space.
COOLING
1. Thermostat calls for low or high stage cooling.
2. If the thermostat call is for low stage cooling, the compressor and outdoor fan are energized at low stage. If the thermostat call is for high stage cooling, the compressor and outdoor fan are energized at high stage.
3. The indoor blower will energize approximately 6 seconds later.
4. The unit delivers cooling to the conditioned space until the thermostat is satisfied.
5. The compressor and outdoor fan will be de-energized when the thermostat opens.
6. The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is satisfied. This allows additional cooling from the indoor coil to be transferred to the conditioned space. Then, the indoor blower is de-energized.
NOTE: A 180-second anti-short cycle is integral to the control and prevents recycling of the compressor.
FAN ONLY
1. Thermostat calls for FAN ONLY by energizing “G”.
2. The indoor blower is immediately energized at the low heat speed.
3. The indoor blower is immediately de-energized once thermostat call for FAN is removed.
STARTUP, ADJUSTMENTS, AND CHECKS
HEATING S TARTUP
This unit is equipped with an electronic ignition device to automatically light the main burners. It also has a power vent blower to exhaust combustion products.
On new installations, or if a major component has been replaced, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and check for wiring errors, or obstructions in or near the blower motors. Duct covers must
be removed before operating unit.
Heat Anticipator Setting
Set the heat anticipator on the room thermostat to 0.4 amps to obtain the proper number of heating cycles per hour and to prevent the room temperature from overshooting the room thermostat setting.
Rollout Protection Control
The rollout protection device opens, cutting power to the gas valve, if the flames from the burners are not properly drawn into the heat exchanger. The rollout protection device is located on the burner bracket. The reason for elevated temperatures at the control must be determined and repaired prior to resetting this manual reset control.
Rollout Protection
Rollout Protection on Burner Bracket
Secondary Limit Control
The secondary limit control is located on the top of the blower scroll assembly. This control opens when elevated temperatures are sensed. Elevated temperatures at the control are normally caused by blower failure. The reason for the opening should be determined and repaired prior to resetting.
12
If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower compartment temperature drops below the limit reset temperature, the limit will automatically reset.
Secondary
Control Lim it
Back of Unit
Gas Supply And Manifold Check
Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.
Gas Inlet Pressure Check
Gas inlet pressure must be checked and adjusted in accordance to the type of fuel being consumed.
With Power And Gas Off:
1. Connect a water manometer or adequate gauge to the inlet pressure tap of the gas valve. Inlet gas pressure can also be measured by removing the cap from the dripleg and installing a predrilled cap with a hose fitting.
With Power And Gas On:
2. Put unit into heating cycle and turn on all other gas consuming appliances.
INLET GAS PRESSURE
Secondary Limit Control
Pre-Operation Checks
1. Close the manual gas valve external to the unit.
2. Turn off the electrical power supply to the unit.
3. Set the room thermostat to its lowest possible setting.
4. Remove the heat exchanger door on the side of the unit by removing screws.
5. This unit is equipped with an ignition device which automatically lights the main burner. DO NOT try to light burner by any other method.
6. Move the gas control valve switch to the OFF position. Do not force.
7. Wait five minutes to clear out any gas.
8. Smell for gas, including near the ground. This is important because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the warnings on page 4 of this manual. If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position.
9. Replace the heat exchanger door on the side of the unit.
10. Open the manual gas valve external to the unit.
11. Turn on the electrical power supply to the unit.
12. Set the thermostat to desired setting.
Open to
Atmosphere
n
o
a
m
M
Pressure Boss
r
e
t
e
o
n
m
a
M
e
o
s
H
Pressure Boss
Inlet
t
r
e
e
Outl et
On/Off Switch
High Fire Regulator
High Fi re
Coil Terminal (HI)
Terminal (C)
Adjust
A
Common
Regu lator
Vent
Low Fire
Regulat or Adju st
Coaxial Coil
Terminal (M)
Natural Min. 5 .0" W.C., Max. 10.0" W.C.
Propane Min . 11.0" W.C. , Max. 13.0" W.C.
NOTE: Inlet Gas Pressure Must Not Exceed the Maximum Value Shown.
If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or consult with local utility.
Gas Line
Gas Shutoff Valve
Gas Line To Furnace
Open To
Drip Leg Cap With Fitting
Manometer Hose
Atmosphere
Manometer
Measuring Inlet Gas Pressure
Alternate Method
Manifold Pressure Check
1 Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.
2. Turn off all electrical power to the system.
3. Back outlet pressure test screw (inlet/outlet pressure boss) out one turn (counterclockwise, not more than one turn).
4. Attach a hose and manometer to the outlet pressure boss of the valve.
5. Turn ON the gas supply.
6. Turn on power and energize main (M) solenoid. Do not energize the HI solenoid.
7. Measure gas manifold pressure with burners firing. Adjust manifold pressure using the Manifold Gas Pressure table shown below.
White-Rodgers Model 36G54 connected to Manometer
13
Manifold Ga s P res sure
Gas
Natural Lo w Stage 1.6 - 2.2" w.c. 2.0" w.c.
High Stage 3.2 - 3.8" w.c. 3.5" w.c.
Propane Lo w St age 5.7 - 6.3" w.c. 6. 0" w.c.
High Stage 9.7 - 10.3" w.c. 10.0" w.c.
Range Nominal
8. Remove regulator cover screw from the low (LO) outlet pressure regulator adjust tower and turn screw clockwise to increase pressure, or counterclockwise to decrease pressure.
9. Energize main (M) solenoid as well as the HI terminal.
10. Remove regulator cover screw from the HI outlet pressure regulator adjust tower and turn screw clockwise to increase pressure, or counterclockwise to decrease pressure.
11. Turn off all electrical power and gas supply to the system.
12. Remove manometer hose from outlet pressure boss.
13. Turn outlet pressure test screw in to seal pressure port (clockwise, 7 in-lb minimum).
14. Turn on electrical power and gas supply to the system.
15. Turn on system power and energize valve.
16. Using a leak detection solution or soap suds, check for leaks at pressure boss screw. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.
NOTE: For gas to gas conversion, consult your dealer for appropriate conversion.
Gas Input (Natural Gas Only) Check
To measure the gas input use a gas meter and proceed as follows:
1. Turn off gas supply to all other appliances except the unit.
2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit.
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT
Example: Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step 2, then:
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate.
4. Relight all other appliances turned off in step 1. Be sure all pilot burners are operating.
Main Burner Flame Check
Flames should be stable, soft and blue (dust may cause orange tips but they must not be yellow) and extending directly outward from the burner without curling, floating or lifting off.
Temperature Rise Check
Check the temperature rise through the unit by placing thermometers in supply and return air registers as close to the unit as possible. Thermometers must not be able to sample temperature directly from the unit heat exchangers, or false readings could be obtained.
1. All registers must be open; all duct dampers must be in their final (fully or partially open) position and the unit operated for 15 minutes before taking readings.
2. The temperature rise must be within the range specified on the rating plate.
NOTE: Air temperature rise is the temperature difference between supply and return air.
With a properly designed system, the proper amount of temperature rise will normally be obtained when the unit is operated at rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blower speed will increase the temperature rise.
NOTE: Blower speed MUST be set to give the correct air temperature rise through the unit as marked on the rating plate.
External Static Pressure Check
The total external static pressure must be checked on this unit to determine if the airflow is proper.
Blower Speed Adjustments
WARNING
O AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE
T
ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE
BLOWER MOTOR.
Refer to the wiring diagram in the appendix to verify speed tap settings.
Depending upon the model, blower speeds are changed at the indoor blower. The ignition control board has four blower speeds: LOW HEAT, HI HEAT, LOW COOL and HIGH COOL.
NOTE: FAN ONLY energizes at LOW HEAT speed. The *PG15 models are equipped with EEM motors. EEM motors
are constant torque motors with very low power consumption. This motor is energized by 24VAC. Adjust the CFM for the unit by changing the 24VAC leads to the speed terminal block on the motor.
HEATING COOLING
Speed
Tap
T1
T2
Definition
Low
Speed Heat
High
Speed Heat
NOTE: Heating airflow must be adjusted to provide the temperature rise shown on rating plate. A higher speed tap may not provide more airflow. Blower speeds are programmed to deliver adequate airflow at rated external static pressure (ESP). Refer to airflow table provided in the Appendix for details.
Limit Check
Check limit control operation after 15 minutes of operation by blocking the return air grille(s).
1. After several minutes the main burners must go OFF. Blower will continue to run.
2. Remove air restrictions and main burners will relight after a cool down period of a few minutes.
Adjust the thermostat setting below room temperature.
1. Main burners must go OFF.
2. Circulating Air Blower will continue to run for 90, 120, 150 or 180 seconds, depending on the setting.
Lead
Color
White T3
Brown T4
Spee d
Tap
T5
Definition
Low Speed
Cool
High Speed
Cool
High Speed
Cool Hi-Static
Lead
Color
Purple
Yellow
14
space. It is the installing contractors responsibility to ensure
LO COOL
HI COOL
LO HEAT
HI HEAT
U6
U7
U4
U3
U5
P1
K2
K1
the proper refrigerant sub-cooling at the condenser is adjusted for each application. As the outdoor ambient temperature rises the sub-cooling decreases and as the outdoor ambient temperature lowers, the sub-cooling increases. NOTE: Proper sub-cooling adjustment optimizes cooling performance. Models equipped with thermostatic expansion valve, charge the system to sub-cooling, range shown on chart, when necessary, adjust expansion valve stem for superheat setting.
SPEEDUP
SW1
FAULT
BLOWER
RECALL
OFF DELAY
F1
STAGE
ECON
DELAY
RCW1W2
GY1Y2
NOTE: The expansion valve will not need adjustment for most applications. Ensure system superheat is set within range listed on chart.
Control Board (Top)
NOTE: If necessary, adjust fan OFF delay settings to obtain satis-
factory comfort level.
Unit Shutdown
1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the unit.
3. Remove the heat exchanger door on the side of the unit by removing screws.
4. Move the gas control valve switch to the OFF position. Do not force.
5. Close manual gas shutoff valve external to the unit.
6. Replace the heat exchanger door on the unit.
7. If cooling and/or air circulation will be desired, turn ON the electrical power.
COOLING S TARTUP
NOTE: Check all manual reset limit controls in heating circuit if
cooling mode does not operate.
Compressor Protection Devices
The compressor includes components which are designed to protect the compressor against abnormal operating conditions.
Designsuperhe at&subcooling@95°Fout doorambienttemperature
Models# Superheat°F Subcooling°F
GPG152407041
GPG153009041 GPG153709041 GPG154211541
GPG154911541
GPG156014041
8‐12 ‐‐‐
8‐12 ‐‐‐
5‐9 ‐‐‐
5‐9 ‐‐‐
5‐9 ‐‐‐
5‐912‐18
Superheat Adjustment
To adjust superheat, remove the control box cover and locate the expansion valve on the liquid line of the evaporator. Unscrew the cover from the expansion valve, locate the adjustment screw, and turn it clockwise (in) to increase superheat or counterclockwise (out) to decrease superheat. Replace adjustment cap. Wait a minimum of 10 minutes between adjustments to allow time for the TXV and pressures to stabilize.
Cooling Operation
NOTE: Mechanical cooling cannot be reliably provided at
ambient temperatures below 50° F.
1. Turn on the electrical power supply to the unit.
2. Place the room thermostat selector switch in the COOL position (or AUTO if available, and if automatic changeover from cooling to heating is desired).
3. Set the room thermostat to the desired temperature.
Refrigerant Charge Check (Units with Fixed Orifice Devices)
After completing airflow measurements and adjustments the unit’s refrigerant charge must be checked. All package units with fixed orifice devices are charged using the super heat method at the compressor suction line.
For charge adjustments, see superheat and charts shown for each model.
Cooling Refrigerant Charging (Models with TXV)
Check unit charge before putting the cooling section into full operation. The unit has a thermostatic expansion valve metering device. To ensure the unit is properly charged for the intended application, check the unit refrigerant sub-cooling at the condenser. The refrigerant sub-cooling is a function of outdoor ambient temperature and return air temperature of the conditioned
TROUBLESHOOTING
IGNITION CONTROL ERROR CODES
The following presents probable causes of questionable unit operation. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation.
Remove the control box access panel and note the number of diagnostic LED flashes. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation.
FAULT R ECALL
The ignition control is equipped with a momentary push-button switch that can be used to display on the diagnostic LED the last five faults detected by the control. The control must be in Standby Mode (no thermostat inputs) to use the feature. Depress the push­button switch for approximately 2 seconds. NOTE: Do not hold
for longer than 4 seconds. Holding the button for 4 seconds or higher will erase the memory! Release the switch when the
LED is turned off. The diagnostic LED will then display the flash codes associated with the last five detected faults. The order of display is the most recent fault to the least recent fault.
15
ABNORMAL O PERATION - HEATING
INTERNAL C ONTROL F AILURE
If the integrated ignition control in this unit encounters an internal fault, it will go into a “hard” lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring. Disconnect electric power for five seconds. If LED remains off after restoring power, replace control.
EXTERNAL L OCKOUT
An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be established within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for ignition, the gas valve is de-energized, 30 second inter-purge cycle is completed, and ignition is re-attempted. The control will repeat this routine three times if a measurable combustion is not established. The control will then shut off the induced draft blower and go into a lockout state.
If flame is established but lost, the control will energize the circulator blower at the heat speed and then begin a new ignition sequence. If flame is established then lost on subsequent attempts, the control will recycle the ignition sequence.
The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts. The integrated control will automatically reset after one hour, or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic red LED indicates an external lockout, perform the following checks:
Check the supply and manifold pressures
Check the gas orifices for debris
Check gas valve for proper operation
Check flame sensor A drop in flame signal can be caused by nearly invisible coating on the sensor. Remove the sensor and carefully clean with steel wool.
Check wiring Check wiring for opens/shorts and miswiring.
IMPORTANT NOTE: If you have to frequently reset your gas/ electric package unit, it means that a problem exists that should be corrected. Contact a qualified servicer for further information.
PRESSURE SWITCH STUCK OPEN
A pressure switch stuck open can be caused by a faulty pressure switch, faulty wiring, a disconnected or damaged hose, a blocked or restricted flue, or a faulty induced draft blower.
If the control senses an open pressure switch during the pre­purge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is de-energized, the circulator blower heat off cycle begins, and the induced draft blower remains on. The diagnostic LED (red) code is two (2) flashes.
PRESSURE SWITCH STUCK CLOSED
A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring. If the control encounters a pressure switch stuck closed, the induced draft blower remains off. The diagnostic red LED code for this fault is three (3) flashes.
OPEN THERMAL PROTECTION DEVICE
If a limit switch opens, the gas valve is immediately de­energized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch re-closes. The diagnostic LED (red) code for an open limit is four (4) flashes.
PRIMARY LIMIT
A primary limit will open due to excessive supply air temperatures. This can be caused by a dirty filter, excessive duct static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see wiring diagram), and limit. This limit will automatically reset once the temperature falls below a preset level.
AUXILIARY/SECONDARY LIMIT
A dirty filter, excessive duct static, insufficient air flow, a faulty limit, or a failed circulator blower can cause this limit to open. Check filters, total external duct static, circulator blower motor, blower motor speed tap (see wiring diagram), and limit. An interruption in electrical power during a heating cycle may also cause the auxiliary limit to open. The automatic reset secondary limit is located on top of the circulator blower assembly.
ROLLOUT LIMIT
If the burner flames are not properly drawn into the heat exchanger, the flame rollout protection device will open. Possible causes are restricted or blocked flue passages, blocked or cracked heat exchanger, a failed induced draft blower, or insufficient combustion air. The rollout protection device is a manual reset limit located on the burner bracket. The cause of the flame rollout must be determined and corrected before resetting the limit.
FLAME DETECTED WITH GAS VALVE CLOSED
If flame is detected with the gas valve de-energized, the combustion and air circulator blowers are energized. The diagnostic fault code is five (5) flashes (red LED) for this condition. The flame diagnostic LED (amber) will flash (2) times to indicate this condition. The control can be reset by removing the power supply to the unit or it will automatically reset after one hour. Miswiring is the probable cause for this fault.
LOW FLAME SIGNAL
Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator causing a drop in the flame signal. If the flame signal drops below a predetermined value, the ignition control will display an error code of (1) flash on the amber diagnostic LED. The unit will continue to operate until the control can no longer detect flame.
ABNORMAL OPERATION - COOLING
SHORT CYCLE COMPRESSOR DELAY
The automatic ignition control has a built-in feature that prevents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent thermostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored or thermostat call for cooling is restored. (Compressor is off a total of three minutes). The diagnostic red LED will flash six (6) times to indicate the compressor contactor output is being delayed.
16
NOTE: Some electronic thermostats also have a built-in compressor short cycle timer that may be longer than the three minute delay given above. If you are using an electronic thermostat and the compressor has not started after three minutes, wait an additional five minutes to allow the thermostat to complete its short cycle delay time.
HIGH PRESSURE S WITCH/LOSS OF CHARGE SWITCH
Some models include a high pressure cutout switch and/or a loss of charge cutout switch. The high pressure cutout switch protects the refrigeration system from excessive operating pressures. The loss of charge cutout switch protects the refrigeration system from very low operating pressures due to a loss of refrigerant. Compressor operation will be disabled if either of these devices opens. If either devices opens, the diagnostic red LED will flash (9) times to indicate that a refrigeration system pressure switch is open.
MAINTENANCE
CONDENSER, EVAPORATOR, AND INDUCED D RAFT MOTORS
Bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated. No additional oiling is required.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
A drop in the flame current can be caused by a nearly invisible coating on the flame sensor. This coating, created by the fuel or combustion air supply, can be removed by carefully cleaning the flame sensor with steel wool.
NOTE: After cleaning, the microamp signal should be stable and in the range of 4 - 6 microamps DC.
Flame Sensor
Have the gas heating section of the unit checked at least once a year before the heating season begins, to be sure that the combustion air inlet and flue outlet hoods are not blocked by debris, which would prevent adequate combustion air and a properly operating vent system.
FILTER R EPLACEMENT OR C LEANING
A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. The filter(s) may be located in the return air duct(s), or return air filter grille(s). Consult with your installing dealer for the actual location of the return air filter(s) for your unit.
Dirty filters are the most common cause of inadequate heating or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local conditions and usage.
Dirty throwaway filters should be discarded and replaced with a new, clean filter. Dirty permanent filters should be washed with water, thoroughly dried and sprayed with a filter adhesive before being reinstalled. (Filter adhesives may be found at many hardware stores.) Permanent filters should last several years. However, should one become torn or uncleanable, it should be replaced.
CABINET F INISH M AINTENANCE
Use a fine grade automotive wax on the cabinet finish to maintain the finish’s original high luster. This is especially important in installations with extended periods of direct sunlight.
Flame Sensor
FLUE PASSAGES (QUALIFIED SERVICER ONLY)
At the start of each heating season, inspect and, if necessary, clean the unit flue passage.
CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)
1. Shut off electric power and gas supply to the unit.
2. Remove burner assembly by disconnecting the gas line and removing the manifold bracket from the partition panel.
3. Remove the flue from the induced draft blower and the collector box cover from the partition panel.
4. The primary heat exchanger tubes can be cleaned using a round wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the spring cable. Slowly rotate the cable with the drill and insert it into one of the primary heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Use a large cable for the large tube, and then repeat the operation with a small cable for the smaller tube. Repeat for each tube.
5. When all heat exchanger tubes have been cleaned, replace the parts in the reverse order in which they were removed.
6. To reduce the chances of repeated fouling of the heat exchanger, perform the steps listed in “Startup, Adjustments, and Checks”.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris.
17
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)
Flames should be stable, soft and blue (dust may cause orange tips but must not be yellow). The flames must extend directly outward from the burner without curling, floating or lifting off.
Check the burner flames for:
1. Good adjustme nt
2. Stable, soft and blue
3. Not curling, floating, or lifting off.
Burner Flame
At least once a year, prior to or during the heating season, make a visual check of the burner flames.
NOTE: This will involve removing and reinstalling the heat exchanger door on the unit, which is held by two screws. If you are uncertain about your ability to do this, contact a qualified servicer. If a strong wind is blowing, it may alter the airflow pattern within the unit enough that an inspection of the burner flames is not pos­sible.
CLEANING B URNERS
1. Shut off electric power and gas supply to the unit.
2. Remove the screws securing the manifold to the burner retention bracket. Remove the manifold and rotate each burner counterclockwise to remove.
Burner
Burner Bracket
For further information on the yearly inspection, consult the User Manual. It is recommended that a qualified servicer inspect and service the unit at least once each year.
Turn the unit on at the thermostat. Wait a few minutes, since any dislodged dust will alter the normal flame appearance. Flames should be predominantly blue and directed into the tubes. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports.
ACCESSORIES AND FUNCTIONAL PARTS
SHEET M ETAL A CCESSORIES
Additional accessories can be purchased to fit specific application needs. Parts and instructions are available from your distributor.
FUNCTIONAL P ARTS
FUNCTIONAL PARTS
Auxiliary Limit Switch Flame Rollout Switch
Blower Housing Flame Sensor
Circulator Blower Motor Gas Orifice
Blower Wheel Gas Valve
Burner Heat Exchanger
Capacitor High Limit Switch
Compressor Igniter
Condenser Coil Ignition Control
Condenser Fan Blade Induced Draft Blower
Condenser Fan Motor Pressure Switch
Contactor Pressure Switch Hose
Gas Manifold Thermostatic Expansion Valve
Evaporator Coil Transformer
Manifold
Manifold Assembly
3. Remove the burners.
4. Use a bottle brush to clean burner insert and inside of the burners.
5. Replace burners and manifold, inspect the burner assembly for proper seating of burners in retention slots.
6. Reconnect electrical power and gas supply.
Functional Parts List
GENERAL I NFORMATION
1. Refer to the description in Functional Parts List when ordering any of the listed functional parts. Be sure to provide the unit model and serial numbers with the order.
2. Although only functional parts are shown, all sheet metal parts, doors, etc. may be ordered by description.
3. Parts are available from your distributor.
18
APPENDIX
19
Amber Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual
Circulator Blower
Gas Valve
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART
Red Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual
Off Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch Stuck Open 3 Flashes Pressure Switch Stuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay (Cooling Only) 7 Flashes Limit Opened Five (5) Times Within The Same Call For Heat 8 Flashes Indoor/Outdoor Thermostat Open (Cooling Only; Devices Not present On All Models) 9 Flashes High Pressure/Loss of Charge Switch Open (Cooling Only; Devices Not Present On All Models)
Off No Flame Present On Normal Flame 1 Flash Low Flame Current 2 Flashes Flame Detected with Gas Valve De-energized.
HEATING TIMING CHART
HIGH
LOW
OFF
HIGH
LOW
OFF
Igniter
Induced Draft Blower
Thermostat
Seconds
Circulator Blower
Compressor
Outdoor Fan
ON
OFF
HIGH
LOW
OFF
HIGH
LOW
OFF
0 15 22 27 52 0 30
COOLING TIMING CHART
HIGH
LOW
OFF
HIGH
LOW
OFF
HIGH
LOW
OFF
90, 120, 150, 180
20
UNIT DIMENSIONS
SUCTION/LIQUID PRESSURE PORTS
BEHIND COMPRESSOR ACCESS PANEL
COMBUSTION AIR INTAKE
HEAT EXCHANGE ACCESS PANEL
CONDENSATE DRAIN CONNECTION
F
O
R
E
Y
T
T
I
N
V
E
A
C
R
G
20
24
47
GAS SUPPLY ENTRANCE
3/4" NPT FEMALE
FLUE EXHAUST
HOOD
C
4 3/4
16 1/8
19 1/8
7 5/16
7 7/8
POWE R WIRE ENT RANCE
CONTROL WIRE ENTRANCE
18 7/16
FLUE EXHAUST
7 15/16
51
16
1 3/8
5 1/2
16
B
RETURN
LARGE
B
DIMENSION
(INCHES)
SUPPLY
MEDIUM
3
EVAPORATOR/CONTROL PANEL ACCESS PANEL
A3240 B1618
C9 1/214
A
2 3/4
5 1/4
COMBUSTION AIR INTAKE
SUPPLY
EXHAUST FLU E HOOD
BLOWER ACCESS PANEL
11
5 3/4
22
11
RETURN
22
21
*PG15*****41A* WIRING DIAGRAM
BR
LPS
HPS
WH
PU
BR
BL
BR
YL
BL/PK
PU
YL
ALS
PS
RS
W. R.
GAS VALV E
M
GV
H C
COMP
C
RS
CM
EM
OR
PU
BL
YL/BK
C
NGL
OR
OR
YL
YL
OR
BR
SOL
PU
BK
HIGH VOLTAGE!
M. F
ULTIPLE POWER SOURCES MAY BE PRESENT AILURE TO DO
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
D ALL .
ISCONNECT POWER BEFORE SERVICING
.
YL/BK
BL/PK
YL
SEE NO TE 6
BL
BK
RD
PU
RD
T2T1
GND
PU
YL
CC
L2L1
BL
BK
GR
PU
PU
BK
208
TR
24V
3
2
240
BK
RD
1
C
BL
POWER SUPPLY 208-230/1/60 SEE NOTE 3
3
2
1
YL
PU
GR
BL
6
5
4
PU
PU
RD
YL
PU
FS
IGN
LS
YL
RD
PU
BR
BL
OR
WH
PU
PU
PU
FS
LO COOL
5
4
24VAC COM
HI COOL
3
2
HI HEAT
1
LO HEAT
OR
OR
180
NONE
150
5 MIN
120
10 MIN
90
BLOWER
STAGE
OFF DELAY
DELAY
L2
T1
1
2
3
F
ECON
BK
BL
LOW
INDUCER
SEE NOT E 7
4
7
5
8
6
9
BR
BL
BL
L1HIGH
PU
YL
LOW
ODF
YL
BK
RD
BK
HI
PARK
BK
YL
PU
63
5
YL
124
YL
YL
Y2Y1GW2W1CR
YL/BK
BL/PK
VM
BL
BL BK
RD
BR
PU
YL
PU
BR
RD
PU
HCF
RCCF
BK
RD
YL
0140G00533 REV A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
22
*PG15*****41A* WIRING DIAGRAM
A
A
R
W1
W2
Y2
C
Y1
G
L1
L1
INTEGRATED IGNITION CONTROL
TO
MICRO
MICRO
HIGH VOLTAGE!
M. F
ULTIPLE POWER SOURCES MAY BE PRESENT AILURE TO DO
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
SUPP LY VO LTAGE
C
F
PS
LPS
SEE NOTE 8
1
ECO N
ECON
2
3
ECON
208-230/1/60
R
S
HPSHP S
SOL
SOL
CM
VM
EM
LSALS
M
HI
C
5
5
4
H
F
SEE NOTE 2
TR
RS
GV
SEE NO TE 7
CC
EM C
T2
CC
C
L2
L2
L2
L2
T1
CC
LO
HI
LO
HI
L1
L1
P1
TH
2
HLO
1
HLI
3
PSW
6
PSW
8
MVL
9
MVH
7
MVC
5
COM
P2
1
4
5
3
6
2
INTERGRATED IGNITION CONTROL
ECO N
LO HEAT HI HEAT
TO
LO COOL
HI COOL
D ALL .
ISCONNECT POWER BEFORE SERVICING
L2
OMPONENT LEGEND
C
AUX ILLARY LIMIT SWI TCH
LS
COMP
L2
INTEGRATED IGNITION CONTROL
COMPRESSOR CONDENSER MOTOR
CM
CONTACTOR
CC ECON ECONOMIZER EM
EVAPOR ATOR MOT OR FUSEF
FS
FLAME SE NSOR
GND
EQUIPMENT GROUND
EQUIPMENT GROUND GAS VALVEGV
IIC
INTEGRATED IGNITION CONTROL
IGNITOR
IGN LS
LIMIT SWITCH
PS
PRESSURE SWIT CH
RCCF
RUN CAPACITOR FOR COMPRESSOR/FAN
ROLLOUT SWITCHRS SOLENOID (2ND STAGE COOL)SOL
TR TRANSFORMER
VENT MOTORVM
N
OTES
NOTES
1. REP LACEMENT WIRE MUST BE THE SAME SIZ E AND TYPE OF INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.
3. USE COPPER CONDUCTORS ONLY.
4. FOR 20 8V OPERATION, REMOVE BLU E LEAD FRO M INDUCER LOW
TERMINAL. MOVE BLACK LEAD FROM PARK TERMINAL ONTO INDUCER LOW TERMINAL. PLACE BLUE LEAD ON PARK TERMINAL.
5. USE N EC CLASS 2 WIRE FOR THERMOS TAT FIELD WIRING .
6. COMPRESSOR 2 ND STAGE SOLENOID NOT PRESENT ON ALL MODELS.
7. OP TIONAL RE FRIGERANT S WITCHES
8. FOR ECO NOMIZER, REMOVE PLU G FROM ECONO MIZER HARN ESS.
CONNECT PLUG FR OM ECONOM IZER TO HAR NESS.
LINE VOLTAGE LOW VOLTAGE OPTIONAL HIGH VOLTAGE
HIGH VOLTAGE LOW VOLTAGE
.
FACTORY WIRING
CTORY WIRING
F
FI
ELD WIRING
IRE CODE
W BK BLACK BL BLUE
BR BROWN GR GREEN OR ORANGE PK PINK PU PURPLE RD RED WH WHITE YL YELLOW
DIA GNOS TIC
LED - RED
ON
OFF
1 FLA SH
2 FLA SHES
3 FLASH ES
4 FLASHES
5 FLA SHES
6 FLASHES
STATUS
NO RMAL OPER ATI ON
NO POWER OR
INTERNAL CONTROL
FAU LT
IGNITION FAILURE
PRESSURE SWITCH OPEN
WITH OUT INDUCER ON
OPEN L IMIT S WITC H
FALSE FLAME DE TECTED
COM PR. SH ORT CYCLE DELAY
CHECK
CHECK
-
-
CHECK INPUT POWER
CHECK FUSE(S)
GAS FL OW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
CHECK PRESSURE SWITCH
CHECK TUBING
CHECK VENT MOTOR
CHECK PRESSURE SWITCHPRESSURE SWITCH CLOSED
CHECK WIRI NG FOR SHORTS
CHECK MAIN LIMIT SWITCH
CHECK AUXILIARY LIMIT SW.
CHECK RO LLOUT LIMIT SW.
CHECK G AS VALVE CHECK FOR SHORTS IN FLAME SENSOR WIRING
3 MIN COMP. SHORT
CYCL E DELAY
DIA GNOS TIC
LED - RED
7 FLASH ES
DIAGNOSTIC LED - AMBER
OFF
ON
1 FLASH
2 FLASH ES
STATUS
SAME CA LL FOR HEAT
PSW/LOC OPEN9 FLA SHES
STATUS
NO FLAME PRESENT
LOW FLAME SIGNAL
FAL SE FL AME D ETEC TE D
CHECK
CHECK MAIN LIMIT SWITCHLIMIT OPEN 5 TIMES IN
CHECK AUXILIARY LIMIT SW.
CHECK JUMPER BETWEEN
1 AND 4 ON 6 -CIRCU IT
CONN ECTO RIDT/ODT OPEN8 FLASH ES
CHECK OPTIONAL
REFRIGERANT SWITCHES
CHECK REFRIGERANT
SWITCHES FOR LOSS OF
CHARGE OR HIGH HEAD
PRESSURE
CHECK
-
-NORMAL FLAME PRESENT
GAS FLOW
GAS PRESSURE
GAS VALVE
FLAME SENSOR
CHECK GAS VALVE
CHECK FOR SHORTS IN
FLAME SENSOR WIRING
0140G00533 REV A
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
23
*PG15*****41B* WIRING DIAGRAM
HIGH VOLTAGE!
M. F
ULTIPLE POWER SOURCES MAY BE PRESENT AILURE TO DO
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
D ALL .
ISCONNECT POWER BEFORE SERVICING
.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
24
*PG15*****41B* WIRING DIAGRAM
HIGH VOLTAGE!
M. F
ULTIPLE POWER SOURCES MAY BE PRESENT AILURE TO DO
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
D ALL .
ISCONNECT POWER BEFORE SERVICING
.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
25
MINIMUM CLEARANCES
48" MIN
12" MIN
3"
.
MIN
12" MIN
36" MIN
(FOR SERVICE)
NOTE: Roof overhang should be no more than 36".
RECOMMENDED FILTER SIZES
UNIT 2 Ton 2 1/2 Ton 3 Ton 3 1/2 / 4 Ton 5 Ton
Min. Filter Size (1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x1 (2)20 x 20 x 1 (2)20 x 25 x 1
-
26
BLOWER PERFORMANCE DATA
*PG152407041** - Rise Range: 35° - 65° F
E.S.P
CFM W ATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
0.1 729 55 52 913 103 57 897 99 897 99 1047 139
0.2 680 63 57 864 111 61 848 107 848 107 998 146
0.3 631 71 62 815 119 64 799 115 799 115 948 154
0.4 582 79 X 766 127 X 750 123 750 123 899 162
0.5 532 87 X 717 135 X 701 131 701 131 850 170
0.6 --- --- --- 667 143 X 652 139 652 139 801 178
0.7 --- --- --- --- --- --- --- --- --- --- --- ---
0.8 --- --- --- --- --- --- --- --- --- --- --- ---
*PG153009041** - Rise Range: 45° - 75° F
E.S.P
0.1 1050 139 49 1256 220 55 1123 168 1123 168 1326 248
0.2 1006 147 52 1211 228 57 1079 176 1079 176 1282 256
0.3 961 154 54 1167 236 59 1034 183 1034 183 1237 263
0.4 916 162 57 1122 243 62 989 191 989 191 1192 271
0.5 872 170 60 1077 251 64 945 199 945 199 1148 279
0.6 827 178 63 1033 259 68 900 206 900 206 1103 287
0.7 782 185 69 988 267 70 855 214 855 214 --- ---
0.8 738 193 72 --- --- --- 811 222 811 222 --- ---
ST
1
CFM W ATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
T1 T2 T3 T4 T5
T1
Stage Heating
2nd Stage Heating Spe ed
T2
T3
Cooling Speed
Cooling Speed
T4
Cooling Speed
T5
*PG153709041** - Rise Range: 45° - 75° F
ST
E.S.P
0.1 1053 143 49 1257 236 55 1184 203 1184 203 1408 304
0.2 1007 151 52 1211 243 57 1138 210 1138 210 1362 311
0.3 961 158 54 1165 250 59 1092 217 1092 217 1315 319
0.4 915 165 57 1119 258 62 1046 225 1046 225 1269 326
0.5 869 173 60 1073 265 64 1000 232 1000 232 1223 334
0.6 823 180 63 1027 273 68 954 240 954 240 1177 341
0.7 777 188 69 980 280 70 908 247 908 247 --- ---
0.8 731 195 72 --- --- --- 862 255 862 255 --- ---
1
CFM W ATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
T1
Stage Heating
Speed
nd
2
Stage Heating Spe ed
T2
T3
Cooling Speed
Cooling Speed
T4
Cooling Speed
T5
*PG154211541** - Rise Range: 45° - 75° F
ST
E.S.P
0.1 1090 150 52 1286 231 57 1354 260 1354 260 1609 365
0.2 1025 158 57 1225 239 61 1296 267 1296 267 1556 373
0.3 960 166 62 1165 247 64 1237 275 1237 275 1504 381
0.4 895 174 X 1105 255 X 1178 283 1178 283 1451 388
0.5 830 181 X 1045 262 X 1120 291 1120 291 1399 396
0.6 765 189 --- 984 270 X 1061 299 1061 299 1347 404
0.7 699 197 --- 924 278 --- 1002 306 1002 306 1294 412
0.8 634 205 --- --- --- --- 944 314 944 314 1242 420
1
CFM W ATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
T1
Stage Heating
Speed
nd
Stage Heating Spe ed
2
T2
T3
Cooling Speed
Cooling Speed
T4
Cooling Speed
T5
*PG154911541** - Rise Range: 45° - 75° F
ST
E.S.P
0.1 1164 180 56 1435 293 61 1477 310 1477 310 1709 407
0.2 1100 188 59 1378 301 63 1421 318 1421 318 1659 414
0.3 1037 196 62 1322 309 65 1365 326 1365 326 1609 422
0.4 974 204 65 1265 316 68 1310 334 1310 334 1559 430
0.5 910 212 70 1208 324 70 1254 342 1254 342 1509 438
0.6 847 220 75 1152 332 73 1198 349 1198 349 1459 446
0.7 784 227 X 1095 340 X 1143 357 1143 357 1409 453
0.8 720 235 X 1038 348 X 1087 365 1087 365 --- ---
1
CFM W ATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
T1
Stage Heating
Speed
nd
2
Stage Heating Spe ed
T2
T3
Cooling Speed
Cooling Speed
T4
Cooling Speed
T5
*PG156014041** - Rise Range: 45° - 75° F
ST
E.S.P
0.1 1792 514 X 1792 514 58 1366 257 1939 603 2108 704
0.2 1743 522 45 1743 522 61 1317 265 1889 611 2058 713
0.3 1693 530 45 1693 530 61 1267 273 1840 619 2009 721
0.4 1644 538 46 1644 538 63 1218 281 1791 627 1960 729
0.5 1595 546 48 1595 546 65 1169 290 1742 635 1911 737
0.6 1546 554 50 1546 554 68 1120 298 1693 643 --- ---
0.7 1496 563 52 1496 563 70 1071 306 1643 651 --- ---
0.8 --- --- --- --- --- --- --- --- --- ---
1
CFM W ATTS RISE CFM WATTS RISE CFM WATTS CFM WATTS CFM WATTS
T1
Stage Heating
Speed
nd
2
Stage Heating Spe ed
T2
T3
Cooling Speed
Cooling Speed
T4
Cooling Speed
T5
X = Outside of Temperature Rise Range - Not Recommended.
NOTE:
The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,
external static pressure should not exceed 0.5" w.c.
27
PACKAGE UNITS - DUAL FUEL & GAS
HOMEOWNER’S ROUTINE MAINTENANCE RECOMMENDATIONS
We strongly recommend a bi-annual maintenance checkup be performed
by a
qualified service agency before the heating and cooling seasons begin.
REPLACE OR CLEAN FILTER
IMPORTANT NOTE: Never operate unit without a filter installed as
dust and lint will build up on internal parts resulting in loss of efficiency, equipment damage and possible fire. A return air filter is not supplied with this unit; however, there must be a means of filtering the return air. An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort system clean. A dirty coil could cause poor operation and/or severe equipment damage. The installer of your unit can tell you where your filter(s) are and how to clean or replace them. Check your return filter(s) at least once every two months. When they are dirty, replace or clean as required. Disposable type filters should be replaced. Reusable type filters may be cleaned. NOTE: Reusable type filters should be washed with warm water, dried completely and sprayed with an adhesive according to the manufacturers recommendations. You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic types. These filters can do a better job of catching small airborne particles. Improper filter maintenance is the most common cause of inad­equate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as re­quired. When replacing a filter, it must be replaced with a filter of the same type and size and always make certain the air flow arrows on the filter point in the proper direction.
CONDENSER, EVAPORATOR AND INDUCED D RAFT MOTORS
The bearings on the air circulating blower motor, condenser motor and the combustion fan motor are permanently lubricated and require no further lubrication.
COMPRESSOR
The compressor motor is hermetically sealed and does not re­quire additional oiling.
ANNUAL INSPECTION (QUALIFIED SERVICER ONLY)
Your package unit should be inspected by a qualified installer, or service agency at least twice every year. This check should be performed before the heating and cooling seasons begin. This will ensure that adequate combustion air is being drawn and the vent system is working properly. Particular attention should be paid to the following items. Repair as necessary.
Check physical support of the unit. Ensure it is sound without any sagging, cracks, or gaps, around the base.
Check for obvious signs of deterioration of the unit.
• Flue Hood and Combustion Air Inlet. Check for blockage (wasp nest, etc.) and corrosion.
FLUE HOOD (QUALIFIED SERVICER ONLY)
Return Air Connection. Check for physical soundness and ensure that the connection is firmly sealed to the package unit casing.
Heat exchanger. Check for corrosion and/or obstructions within the heat exchanger passageways.
Burners. Check for proper ignition, burner flame, and flame sense.
Wiring. Check wires for damage.Check electrical connections for tightness and/or corrosion.
Filters. Check that filters are clean and in the proper placement in the unit or duct system.
Louvers. Inspect air inlet louvers inside the heat exchanger compartments. Ensure the area is clean and free of dirt and debris.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The outdoor coil should be inspected annually. It is important to keep the outdoor coil clean. Dirt, leaves, or debris could restrict the airflow. If cleaning of the outdoor coil becomes necessary, hire a qualified servicer. Inexperienced people could easily puncture the tubing in the coil.
BEFORE CALLING YOUR SERVICER
Check the thermostat to confirm that it is properly set.
Check the disconnect switch near the unit to confirm that it is closed.
Check the electrical panel for tripped circuit breakers or failed fuses . Reset the circuit breakers or replace fuses as necessary.
Check for blockage of the indoor air inlets and outlets. Confirm that they are open and have not been blocked by objects (rugs, curtains or furniture).
Check for obstructions on the unit . Confirm that it has not been covered on the sides or the top. Remove any obstruction that can be safely removed. If the unit is covered with dirt or debris, call a qualified servicer to clean it.
Check the filter. If it is dirty, clean or replace it.
28
Loading...