Affix this manual and Users Information Manual adjacent to the unit.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During
installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
These installation instructions cover the outdoor
installation of self contained package air conditioners
and heating units. See the Specification Sheets
applicable to your model for information regarding
accessories.
REPLACEMENT P ARTS ....................................................................................................................................................... 4
ORDERING PARTS .............................................................................................................................................. 4
CODES AND REGULATIONS ............................................................................................................................................... 5
EP A REGULA TIONS ............................................................................................................................................ 5
MAJOR COMPONENTS ....................................................................................................................................................... 5
CIRCULA TING AIR AND FILTERS ....................................................................................................................................... 7
CONDENSA TE DRAIN ........................................................................................................................................... 8
HIGH VOL TAGE WIRING........................................................................................................................................ 8
L
OW VOLTAGE WIRING ........................................................................................................................................ 8
ST ARTUP , ADJUSTMENTS, AND CHECKS ......................................................................................................................... 9
INAL SYSTEM CHECKS ...................................................................................................................................... 9
CONT ACT OR ....................................................................................................................................................... 9
ONTACT OR RELAY........................................................................................................................................... 10
D
EFROST CONTROL .......................................................................................................................................... 10
NDOOR BLOWER MOTOR ................................................................................................................................... 10
HEA T PUMP OPERA TION .................................................................................................................................................. 10
EA TING CYCLE ............................................................................................................................................... 10
D
EFROST CONTROL ...........................................................................................................................................11
SERVICE ............................................................................................................................................................................ 15
ADJUSTMENTS THROUGH DIP SWITCH COMBINATIONS 7-8.................................................................................... 22
3
Page 4
TO THE INSTALLER
Carefully read all instructions for the installation prior to installing
unit. Make sure each step or procedure is understood and any
special considerations are taken into account before starting
installation. Assemble all tools, hardware and supplies needed to
complete the installation. Some items may need to be purchased
locally. After deciding where to install unit, closely look the location
over - both the inside and outside of home. Note any potential
obstacles or problems that might be encountered as noted in this
manual. Choose a more suitable location if necessary.
IMPORTANT NOTE: If a crankcase heater is used, the unit
should be energized 24 hours prior to compressor start up to
ensure crankcase heater has sufficiently warmed the compressor. Compressor damage may occur if this step is not followed.
IMPORTANT NOTETOTHE OWNER REGARDING PRODUCT
WARRANTY
Your warranty certificate is supplied as a separate document
with the unit installed by your contractor. Read the limited
warranty certificate carefully to determine what is and is not
covered and keep the warranty certificate in a safe place. If
you are unable to locate the warranty certificate please contact
your installing contractor or contact customer service (877254-4729) to obtain a copy.
To receive the 10-year Parts Limited Warranty for Goodman
branded products, online registration must be completed within
60 days of installation. Online registration is not required in
California or Quebec. Complete warranty details available at
your local dealer or at www.goodmanmfg.com.
IMPORTANT: To register your Goodman brand unit, go to
www.goodmanmfg.com. Click on the word “Warranty” located
on the left side of the home page. Next, click on the word
“Product Registration” located on the left side of the Warranty
page and complete the forms in the manner indicated on the
Product Registration page.
Product limited warranty certificates for models currently in
production can be viewed at www.goodmanmfg.com. If your
model is not currently in production or does not appear on the
website, please contact your installing contractor or contact
customer service (877-254-4729) to obtain a copy of your
warranty certificate.
Each product overview page contains a Product Warranty link;
by clicking on it you will be able to view the limited warranty
coverage for that specific product. T o view warranty registration
information, click on the Product Warranty text on the left
navigation panel on the home page of each website. The Online
Product Registration pages are located in this same section.
Before using this manual, check the serial plate for proper
model identification.
The installation and servicing of this equipment must be
performed by qualified, experienced technicians only.
SHIPPING INSPECTION
Upon receiving the unit, inspect it for damage from shipment.
Claims for damage, either shipping or concealed, should be filed
immediately with the shipping company. Check the unit model
number, specifications, electrical characteristics and accessories
to determine if they are correct. In the event an incorrect unit is
shipped, it must be returned to the supplier and must NOT be
installed. The manufacturer assumes no responsibility for
installation of incorrectly shipped units.
REPLACEMENT PARTS
O
RDERING PARTS
When reporting shortages or damages, or ordering repair
parts, give the complete unit model and serial numbers as
stamped on the unit’s nameplate.
Replacement parts for this appliance are available through
your contractor or local distributor. For the location of your
nearest distributor, consult the white business pages, the
yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMP ANY, L.P .
7401 SECURITY WA Y
HOUSTON, TEXAS 77040
877-254-4729
SAFETY INSTRUCTIONS
The following symbols and labels are used throughout this
manual to indicate immediate or potential safety hazards. It
is the owner’s and installer’s responsibility to read and comply
with all safety information and instructions accompanying
these symbols. Failure to heed safety information increases
the risk of personal injury, property damage, and/or product
damage.
4
Page 5
CODES AND REGULATIONS
The *PH/C M-series heat pumps are designed for OUTDOOR
USE ONLY. *PH M-Series is available in cooling capacities of
2, 2.5 3, 4 and 5 nominal tons of cooling. The GPC is only
available in 2 thru 4 ton. Optional field installed heat kits are
available in 5,8,10,15 and 20 kW. The units can be easily
installed in manufactured or modular homes with existing
high-static duct work. The units can also be easily converted
to accommodate a plenum for normal or low-static
applications. The *PH/C M-series are self contained packaged
units so the only connections needed for installation are the
supply and return ducts, the line and low voltage wiring and
drain connection. The units are ETL listed and AHRI certified.
The information on the rating plate is in compliance with the
FTC & DOE rating for single phase units.
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION
AGENCY (EP A) HASISSUEDV ARIOUSREGULATIONSREGARDINGTHE
INTRODUCTION
ANDDISPOSALOFREFRIGERANTSINTHISUNIT.
FAILURETO FOLLOWTHESEREGULATIONSMAYHARMTHE
ENVIRONMENT
. BECAUSEREGULATIONSMA YVARYDUETOPASSAGEOFNEW
FINES
, WESUGGESTACERTIFIEDTECHNICIANPERFORMANYWORK
LAWS
ONTHISUNIT. SHOULDYOUHAVEANYQUESTIONSPLEASE
DONE
CONTAC T
ANDCANLEADTOTHEIMPOSITIONOFSUBSTANTIAL
THELOCALOFFICEOFTHE EPA.
NATIONAL CODES
This product is designed and manufactured to permit
installation in accordance with National Codes. It is the
installer’s responsibility to install the product in accordance
with National Codes and/or prevailing local codes and
regulations.
PRE-INSTALLATION CHECKS
Before attempting any installation, the following points should be
considered:
•Structural strength of supporting members
•Clearances and provision for servicing
•Power supply and wiring
•Air duct connections
•Drain facilities and connections
•Location may be on any four sides of a home,
manufactured or modular, to minimize noise
CLEARANCESAND ACCESSIBILITY
The unit is designed to be located outside the building with
unobstructed condenser air inlet and discharge. Additionally,
the unit must be situated to permit access for service and
installation. Condenser air enters from three sides. Air
discharges upward from the top of the unit. Refrigerant gauge
connections are made on the right side of the unit as you face
the compressor compartment. Electrical connections can be
made either on the right, bottom or duct panel side of the unit.
The best and most common application is for the unit to be
located 10” from wall (4” minimum) with the connection side
facing the wall. This “close to the wall” application minimizes
exposed wiring.
Close to the wall application assures free, unobstructed air
to the other two sides. In more confined application spaces,
such as corners provide a minimum 12” clearance on all air
inlet sides. Allow 36” minimum for service access to the
compressor compartment and controls. The top of the unit
should be completely unobstructed. If units are to be located
under an overhang, there should be a minimum of 48”
clearance and provisions made to deflect the warm discharge
air out from the overhang.
UNITLOCATION
Consider the affect of outdoor fan noise on conditioned space
and any adjacent occupied space. It is recommended that
the unit be placed so that condenser air discharge does not
blow toward windows less than 25 feet away. Consideration
should also be given to shade and unit appearance.
Heat pumps require special location consideration in areas of
heavy snow accumulation and/or areas with prolonged continuous subfreezing temperatures. Heat pump unit bases have holes
under the outdoor coil to permit drainage of defrost water accumulation. The unit must be situated to permit free unobstructed drainage of the defrost water and ice. A minimum 2" clearance under
the outdoor coil is required in the milder climates.
GROUND LEVEL PRE-INSTALLATION DETAILS
The unit should be set on a solid, level foundation - preferably
a concrete slab at least 4 inches thick. The slab should be
above ground level and surrounded by a graveled area for
good drainage. Any slab used as a unit’s foundation should
not adjoin the building as it is possible that sound and
vibration may be transmitted to the structure.
MAJOR COMPONENTS
The unit includes a hermetically sealed refrigerating system
(consisting of a compressor, condenser coil, evaporator coil
with flowrator), an indoor blower, a condenser fan and all
necessary internal electrical wiring. The heat pump also
includes a reversing valve, solenoid, defrost thermostat and
control and loss of charge protection. The system is factoryevacuated, charged and performance tested. Refrigerant
amount and type are indicated on rating plate.
5
Page 6
Ground Level Installation
ROOF TOP PRE-INSTALLATION DETAILS
Ensure that the roof is weather tight and allows proper
drainage of condensation. Use steel or treated wood beams
as unit support for load distribution.
NOTE: To ensure proper condensate drainage, unit must be
installed in a level position.
•To avoid possible property damage or personal injury,
the roof must have sufficient structural strength to carry
the weight of the unit(s) and snow or water loads as
required by local codes. Consult a structural engineer to
determine the weight capabilities of the roof.
•The unit may be installed directly on wood floors or on
Class A, Class B, or Class C roof covering material.
•To avoid possible personal injury, a safe, flat surface for
service personnel should be provided.
ROOF CURB INSTALLATIONS ONLY
NOTE: Sufficient structural support must be determined prior
to locating and mounting the curb and package unit.
Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor.
Curbing must be installed in compliance with the National
Roofing Contractors Association Manual. Construct duct work
using current industry guidelines. The duct work must be
placed into the roof curb before mounting the package unit.
Rooftop Installation
Roof Curb Installation
RIGGING DETAILS
IMPORTANT: If using bottom discharge with roof curb, duct
work should be attached to the curb prior to installing the unit.
Lower unit carefully onto roof mounting curb. While rigging
unit, center of gravity will cause condenser end to be lower
than supply air end.
6
Page 7
Rigging
CIRCULA TING AIR AND FILTERS
A
IRFLOW CONVERSION
Units can easily be converted from horizontal to down
discharge air flow delivery. In down discharge or high static
installations, the installer should measure the total external
static and review the blower performance charts before
performing the installation. In some installations it will be
necessary to change the blower speed to provide proper air
flow.
Horizontal Air Flow
Single phase models are shipped without horizontal duct
covers. If needed, these kits may be ordered through
Goodman’s Service Parts department.
Return
Supply
Remove these panels
for downflow duct
applications
Duct Cover Installation
Down Discharge Applications
Cut insulation around bottom openings and remove panels
from the bottom of the unit, saving the screws holding the
panels in place.
NOTE: Single phase models require installation of horizontal
duct kit #20464501PDGK (medium chassis) and
#20464502PDGK (large chassis).
DUCTWORK
Duct systems and register sizes must be properly designed
for the C.F.M. and external static pressure rating of the unit.
Duct work should be designed in accordance with the
recommended methods of Air Conditioning Contractors of
America Manual D (Residential) or Manual Q (Commercial).
All duct work exposed to the outdoors must include a
weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with
Standards of the National Board of Fire Underwriters for the
Installation of Air Conditioning, Warm Air Heating and
Ventilating Systems. Pamphlets No. 90A and 90B.
The supply duct from the unit through a wall may be installed
without clearance. However, minimum unit clearances as
shown in the Appendix must be maintained. The supply duct
should be provided with an access panel large enough to
inspect the air chamber downstream of the heat exchanger. A
cover should be tightly attached to prevent air leaks.
For duct flange dimensions on the unit refer to the Unit
Dimension illustration in the Appendix.
For down discharge applications, the duct work should be
attached to the roof curb prior to installing the unit. Duct work
dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may
be made with flexible connections to reduce possible unit
operating sound transmission.
FILTERS
Filters are not provided with unit and must be supplied and
externally installed in the return duct system by the installer . A
field-installed filter grille is recommended for easy and
convenient access to the filters for periodic inspection and
cleaning. When installing filters, ensure the air flow arrows
on the filter are pointing toward the circulator blower.
Refer to the unit filter size chart below for filter size information.
NOTE: Filters must have adequate face area for the rated
quantity of the unit. See the air delivery table below for
recommended filter size. Size the filters in accordance with
their manufacturer recommendations. Throwaway filters must
be sized for a maximum face velocity of 300 feet per minute.
7
a
e
r
6
t
A
e
r
e
e
t
F
l
5
i
e
F
r
l
a
a
u
n
4
q
i
S
m
o
N
3
B
A
S
O
P
S
I
D
2
500 1000 1500 2000 2500 3000 3500
R
E
T
L
I
F
E
L
M
R
E
P
Airflow - SCFM
R
E
T
L
I
F
T
N
E
N
A
7
Page 8
PIPING
(
C
ONDENSATE DRAIN
The condensate drain connection of the evaporator is a half
coupling of ¾” N.P.T. A trap must be provided to have proper
condensate drainage.
Unit
Drain
Connection
Flexible
Tubing-Hose
Or Pipe
Install condensate drain trap as shown. Use ¾ “ drain
connection size or larger. Do not operate without trap. Unit
must be level or slightly inclined toward drain.
A Positive Liquid Seal
Is Required
2" Minimum
3" Minimum
WIRING
NOTE: All wiring should be made in accordance with the
National Electrical Code.
Consult your local Power Company to determine the
availability of sufficient power to operate the unit. Check the
voltage, frequency, and phase at the power supply to ensure
it corresponds to the unit’s RA TED VOL T AGE REQUIREMENT .
In accordance with the N.E.C. or local codes, install a branch
circuit fused disconnect near the unit. Determine wire sizes
and overcurrent protection from the unit nameplate ampacity
and in accordance with the Minimum Filter Size or the N.E.C.
The wiring should never be sized smaller than is
recommended by either of these two sources.
Fuses smaller than that recommended on the rating plate
could result in unnecessary fuse failure or service calls. The
use of protective devices of larger size than indicated could
result in extensive damage to the equipment. The
manufacturer bears no responsibility for damage caused to
equipment as result of the use of larger than is recommended
size protective devices.
All units have undergone a run test prior to packaging for
shipment. This equipment has been started at minimum rated
voltage and checked for satisfactory operation. Do not attempt
to operate this unit if the voltage is not within the minimum
and maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof
conduit. The unit must be permanently grounded in
accordance with local codes, or in absence of local codes,
with N.E.C. ANSI/ NFP A NO. 70-1984 or latest edition by using
ground lug in the control box.
Fuses or HACR type circuit breakers may be used where
codes permit.
IMPORTANT NOTE: Some single phase units are equipped
with a single-pole contactor. Exercise caution when servicing
as only one leg of the power supply is broken with the contractor.
LOW VOLTAGE WIRING
•Heat Pumps. Connect 24V wires from the thermostat to
the corresponding wires in the control box using No. 18
AWG as follows:
GPC15
Terminal
Re d
24 - 60
Thermostat
R (24V)
Green G (fan)
White
Brown W2
Yellow
W1 (heat*)
heat*)
Y (cool)
BlueC (24V Common)
[A/G]PH15
Terminal
Red R (24V) R (24V)
Green G (fan) G (fan)
Orange O (rev. valve) O (rev. valve)
White W1 (heat, 2nd) W1 (heat. 2nd)*
Brown W2 (heat, 3rd) W2 (heat, 3rd)*
Purple Not used Y1 (Low cool)
Yellow Y (cool) Y2 (Hi cool)
BlueC (24V Common)C (24V Common)
Thermostats must be set to energize "G" during cooling.
This is default on most all thermostats.
*Optional field installed heat connections.
*PH1549 - *PH1560 have two-stage cooling and require
two-stage heat/cool with optional third stage electric heat
thermostat.
24 - 4 3
Thermostat
49 - 60
Thermostat
INTERNAL WIRING
A diagram detailing the internal wiring of this unit is located
on the electrical box cover. If any of the original wire supplied
with the appliance must be replaced, the wire gauge and
insulation must be the same as the original wiring.
Transformer is wired for 230 volts on the 208/230 models.
See wiring diagram for 208 volt wiring.
1. For branch circuit wiring (main power supply to unit
disconnect), the minimum wire size for the length of run
can be determined using the circuit ampacity found on the
unit rating plate and the table below. From the unit
disconnect to the unit, the smallest wire size allowable
may be used for the ampacity , as the disconnect must be
in sight of the unit.
BRANCH CIRCUIT AMPA CITY
SUPPLY WIRE LENGTH -
FEET
20064443322
15086644433
100108866644
50141210108866
15 20 25 30 35 40 45 50
HIGH VOLTAGE WIRING
•Single Phase. Connect two leads to terminals L1 & L2 in
the electrical control section, using wire sizes specified
in wiring table.
2. Wire size based on 60°C rated wire insulation and 30°C
Ambient Temperature (86°F).
3. For more than three conductors in a raceway or cable, see
the N.E.C. for derating the ampacity of each conductor.
8
Page 9
STARTUP, ADJUSTMENTS, AND CHECKS
COOLING START-UP PROCEDURES
With power turned off at all disconnects:
1. Turn thermostat system switch to “COOL” and fan switch
to “AUTO”. Next, turn the temperature setting as high as it
will go.
2. Inspect all registers and set them to the normal open
position.
3. Turn on the electrical supply at the disconnect.
4. Turn the fan switch to the “ON” position. The blower should
begin ramping up immediately.
5. Turn the fan switch to “AUTO” position. The blower should
begin ramping down after an approximate 60-second
delay.
6. Slowly lower the cooling temperature until the unit starts.
The compressor, blower and fan should now be operating.
Allow the unit to run 10 minutes, make sure cool air is
being supplied by the unit.
7. Turn the temperature setting to the highest position,
stopping the unit. The indoor blower will continue to run
for approximately 60-seconds.
8. Turn the thermostat system switch to “OFF” and disconnect
all power when servicing the unit.
HEAT PUMP START-UP PROCEDURE
1. Check the cooling mode for the heat pump in the same
manner as above. The reversing valve is energized when
the thermostat is placed in the cooling position. A clicking
sound should be noticeable from the reversing valve. By
lowering the temperature setting to call for cooling, the
contractor is energized. The compressor, blower and fan
should then be running. Af ter the cooling mode is checked
out, turn the thermostat system switch to “OFF”.
2. Turn the thermostat system switch to “HEA T” and fan switch
to “AUTO”.
3. Slowly raise the heating temperature setting. When the
heating first stage makes contact, stop raising the
temperature setting.. The compressor, blower and fan
should now be running with the reversing valve in the deenergized (heating) position. After giving the unit time to
settle out, make sure the unit is supplying heated air.
4. If the outdoor ambient is above 80°F, the unit may trip on
its high pressure cut out when on heating. The compressor
should stop. The heating cycle must be thoroughly
checked, so postpone the test to another day when
conditions are more suitable. DO NOT FAIL TO TEST.
5. If the outdoor ambient is low and the unit operates properly
on the heating cycle, you may check the pressure cutout
operation by blocking off the indoor return air until the unit
trips.
6. If unit operates properly in the heating cycle, raise the
temperature setting until the heating second stage makes
contact. Supplemental resistance heat, if installed should
now come on. Ensure all heaters energize.
NOTE: *PH1542-60 have two stages of compressor heat.
During resistance heat test, increase temperature setting
until third stage heat is energized.
If outdoor thermostats are installed, the outdoor ambient
must be below the set point of these thermostats for the
heaters to operate. It may be necessary to jumper these
thermostats to check heater operation if outdoor ambient
is mild.
7. THERMOSTA TS WITH EMERGENCY HEA T . For thermostats
with an emergency heat switch, raise the temperature
setting until the heating second stage makes contact. The
emergency heat switch is located at the bottom of the
thermostat. Move the switch to emergency heat. The heat
pump will stop, the blower will continue to run, all heaters
will come on and the thermostat emergency heat light will
come on.
8. If checking the unit in the wintertime, when the outdoor coil
is cold enough to actuate the defrost control, observe at
least one defrost cycle to make sure the unit defrosts
completely.
FINAL SYSTEM CHECKS
1. Ensure all supply and return air grilles are adjusted and
the air distribution system is balanced for the best
compromise between heating and cooling.
2. Ensure there are no air leaks in the duct work.
3. Check air flow and refrigerant charge. See Sections on
Air Flow Measurement and Adjustment and Checking
Charge.
4. Ensure the unit is free of “rattles”, and the tubing in the unit
is free from excessive vibration. The tubes or lines should
not rub against sheet metal surfaces, edges or each other.
5. Ensure the Owner is instructed on the unit operation, filter,
servicing, correct thermostat operation, etc.
Set the thermostat at the appropriate setting for cooling and
heating or automatic changeover for normal use.
NOTE: The “Cooling Start-up Procedure” is a recommended
step as it serves as an system indicator that the unit will operate
normally.
COMPONENTS
Contactor
This control is activated (closed) by the room thermostat for
both heating and cooling. The contactor has a 24V coil and
supplies power to the compressor and outdoor fan motor.
Crankcase Heater
This item is “ON” whenever power is supplied to the unit and
the crankcase heater thermostat is closed. Crankcase heater
thermostat closes at 67° and opens at 85°. It warms the
compressor crankcase thereby preventing liquid migration
and subsequent compressor damage. The insert type heater
is self regulating. It is connected electrically to the contactor
L1 and L2 terminals.
Condenser Motor
This item is activated by the contactor during heating and
cooling, except during defrost and emergency heat operation.
On 460V heat pumps, the condenser motor is activated by the
CMR.
9
Page 10
Compressor
This item is activated by the contactor for heating and cooling,
except during emergency heat. It is protected by an internal
overload.
Contactor Relay
This control is activated by the thermostat (24V coil) and
supplies power to the contactor.
Defrost Control
The Defrost Control provides time/temperature initiation and
termination of the defrost cycle. When a defrost cycle is
initiated, the Defrost Control shifts the reversing valve to
“COOLING” mode, stops the outdoor fan and brings on
supplemental heat. Normally, a defrost cycle will take only 23 minutes unless system is low on refrigerant charge or
outdoor conditions are severe (i.e. windy and cold). The defrost
control also provides for a 3 minute off cycle compressor
delay.
Outdoor Thermostat
These optional controls are used to prevent full electric heater
operation at varying outdoor ambient (0°F to 45°F). They are
normally open above their set points and closed below to
permit staging of indoor supplement heater operation. If the
outdoor ambient temperature is below 0°F (-18°C) with 50%
or higher RH, an outdoor thermostat (OT) must be installed
and set at (0°) on the dial. Failure to comply with this
requirement may result in damage to the product which may
not be covered by the manufacturer’s warranty.
Reversing Valve Coil
This coil is activated by the thermostat, in the cooling mode
and during defrost. It positions the reversing valve pilot valve
for cooling operation.
Indoor Blower Motor
This is activated by the room thermostat by COOLING or FAN
ON position. For GPC/GPH models, the motor is energized
directly by the room thermostat for X-13 motors. X-13 motors
are constant torque motors with very low power consumption.
For APH models, the motor is energized by the fan control
board for ECM motors. ECM motors are constant CFM motors
with very low power consumption. This motor is energized by
a 24V signal from the thermostat. (See Air Flow Measurementand Adjustment for speed adjustment instructions).
The following figures show a schematic of a heat pump on
the cooling cycle and the heating cycle. In addition to a
reversing valve, a heat pump is equipped with an expansion
device and check valve for the indoor coil, and similar
equipment for the outdoor coil. It is also provided with a defrost
control system.
The expansion devices are flowrator distributors and perform
the same function on the heating cycle as on the cooling
cycle. The flowrator distributors also act as check valves to
allow for the reverse of refrigerant flow.
When the heat pump is on the heating cycle, the outdoor coil
is functioning as an evaporator. The temperature of the
refrigerant in the outdoor coil must be below the temperature
of the outdoor air in order to extract heat from the air. Thus, the
greater the difference in the outdoor temperature and the
outdoor coil temperature, the greater the heating capacity of
the heat pump. This phenomenon is a characteristic of a
heat pump. It is a good practice to provide supplementary
heat for all heat pump installations in areas where the
temperature drops below 45°F. It is also a good practice to
provide sufficient supplementary heat to handle the entire
heating requirement should there be a component failure of
the heat pump, such as a compressor, or refrigerant leak, etc.
Since the temperature of the refrigerant in the outdoor coil on
the heating cycle is generally below freezing point, frost forms
on the surfaces of the outdoor coil under certain weather
conditions of temperature and relative humidity. Therefore, it
is necessary to reverse the flow of the refrigerant to provide
hot gas in the outdoor coil to melt the frost accumulation. This
is accomplished by reversing the heat pump to the cooling
cycle. At the same time, the outdoor fan stops to hasten the
temperature rise of the outdoor coil and lessen the time
required for defrosting. The indoor blower continues to run
and the supplementary heaters are energized.
HEAT PUMP OPERATION
C
OOLING CYCLE
When the heat pump is in the cooling cycle, it operates exactly
as a Air Conditioner unit.
HEATING CYCLE
The heat pump operates in the heating cycle by redirecting
refrigerant flow through the refrigerant circuit external to the
compressor. This is accomplished with through the reversing
valve. Hot discharge vapor from the compressor is directed to
the indoor coil (evaporator on the cooling cycle) where the
heat is removed, and the vapor condenses to liquid. It then
goes through the expansion device to the outdoor coil
(condenser on the cooling cycle) where the liquid is
evaporated, and the vapor goes to the compressor.
When the solenoid valve coil is operated either from heating
to cooling or vice versa, the piston in the reversing valve to the
low pressure (high pressure) reverse positions in the
reversing valve.
10
Page 11
COOLING
SERVICE VALVE
SERVICE PORT
REVERSING VALVE
R
O
T
A
R
O
P
A
V
E
INDOOR
CHECK VALVE
COIL
HEATING
SERVICE VALVE
R
E
S
N
E
D
N
O
C
INDOOR
CHECK VALVE
COIL
SERVICE PORT
COMPRESSOR
DISTRIBUTOR
EXPANSION DEVICE
ORIFICE
DISTRIBUTOR
ORIFICE
SERVICE
VALVE
COMPR ESSOR
SERVICE
VALVE
SERVICE PORT
ACCUMULATOR
SERVICE PORT
CHECK VALVE
ORIFICE
ACCUMULATO R
SERVICE PORT
CHECK VALVE
ORIFICE
OUTDOOR
REVERSING VALVE
DISTRIBUTOR
OUTDOOR
DEFROST CONTROL
During operation the power to the circuit board is controlled
by a temperature sensor, which is clamped to a feeder tube
entering the outdoor coil. Defrost timing periods of 30, 60 and
90 minutes may be selected by setting the circuit board jumper
to 30, 60 and 90 respectively. Accumulation of time for the
timing period selected starts when the sensor closes
(approximately 34°F), and when the wall thermostat calls for
heat. At the end of the timing period, the unit’s defrost cycle
will be initiated provided the sensor remains closed. When
the sensor opens (approximately 60°F), the defrost cycle is
terminated and the timing period is reset. If the defrost cycle
is not terminated due to the sensor temperature, a twelve
minute override interrupts the unit’s defrost period.
COIL
COIL
R
E
S
N
E
D
N
O
C
R
O
T
A
R
O
P
A
V
E
Suggested Field Testing/Trouble Shooting
1. Run unit in the heating mode (room thermostat calling for
heat).
2. Check unit for proper charge. NOTE: Bands of frost on the
condenser coil indicate low refrigerant charge.
3. Shut off power to unit.
4. Disconnect outdoor fan by removing the outdoor fan motor
wire from “DF2” on defrost control.
5. Restart unit and allow frost to accumulate.
6. After a few minutes of operation, the unit’s defrost
thermostat should close. To verify this, check for 24 volts
between “DFT” and “C” on board. If the temperature at the
thermostat is less than 28°F and the thermostat is open,
replace the unit’s defrost thermostat, as it is defective.
7. When the unit’s defrost thermostat has closed, short the
test pins on the defrost board until the reversing valve
shifts, indicating defrost. This should take up to 21
seconds depending on what timing period the control is
set on. After defrost initiation, the short must instantly be
removed or the unit’s defrost period will only last 2.3
seconds.
8. The control is shipped from the factory with the compressor
delay option selected. This will de-energize the
compressor contactor for 30 seconds on defrost initiation
and defrost termination. If the jumper is set to Normal, the
compressor will continue to run during defrost initiation
and defrost termination. The control will also ignore the
low pressure switch connected to R-PS1 and PS2 for 5
minutes upon defrost initiation and 5 minutes after defrost
termination.
9. After the unit’s defrost thermostat has terminated, check
the defrost thermostat for 24 volts between “DFT” and “C”.
The reading should indicate 0 volts (open sensor).
10. Shut off power to unit.
11. Replace outdoor fan motor lead to terminal “DF2” on defrost
board and turn on power.
11
Page 12
AIRFLOW MEASUREMENTAND ADJUSTMENT
Please review the Duct Work section before proceeding
with the airflow measurements and adjustments in this
section.
Unit blower curves (see Specification Sheets) are based on
external static pressure (ESP per in/W .C.). The duct openings
on the unit are considered internal static pressure. As long as
ESP is maintained, the unit will deliver the proper air up to the
maximum static pressure listed for the CFM required by the
application (i.e. home, building, etc.)
In general, 400 CFM per ton of cooling capacity is a rule of
thumb. Some applications depending on the sensible and
latent capacity requirements may need only 350 CFM or up to
425 CFM per ton. Check condition space load requirements
(from load calculations) and equipment expanded ratings data
to match CFM and capacity.
After unit is set and duct work completed, verify the ESP with a
1-inch inclined manometer with pilot tubes or a Magnahelic
gauge and confirm CFM to blower curves in the Specification
Sheets.
NOTE: Never run CFM below 350 CFM per ton, evaporator
freezing or poor unit performance is possible.
AIR FLOW ADJUSTMENTS FOR INDOOR BLOWER MOTOR
X-13 Motor
Adjust the CFM by changing the 24V low voltage lead at the
speed terminal block on the motor. (T1-Low Speed, T2 and
T3-Medium Speed, T4 and T5-High Speed).
NOTE: Factory set T1 (G , fan), T2 (cool/Hi cool), T3 (W2 electric
heat), T4 and T5 reserved for high static (cool/Hi cool) and
W2. GPH1548M41 and GPH1560M41 low cool Y1 will run at G
speed.
ECM Motor
The ECM control board is factory set with the dip switch #4 in
the “ON” position for single stage units and to the "OFF"
position for the 2 stage units. All other dip switches are factory
set in the “OFF” position. For most applications, the settings
are to be changed according to the electric heat size.
The ECM motor provides many features not available on the
traditional PSC motor. These features include:
•Improved Efficiency
•Constant CFM
•Soft Start and Stop
•Improved Humidity Control
ECM Motor Speed Adjustment
Each ECM blower motor has been preprogrammed for
operation at 4 distinct air flow levels when operating in Cooling/
Heat Pump mode or Electric Heat mode. These 4 distinct
levels may also be adjusted slightly lower or higher if desired.
The adjustment between levels and the trim adjustments are
made by changing the dip switch(s) either to an "OFF" or "ON"
position.
APH DIP SWITCH FUNCTIONS
The ECM motor has an electronic control that contains eight
(8) 2-position dip switches. The function of these dip switches
is shown in Table 1.
DIP SWITCH NUMBERFUNCTION
1
2
3N/A
4Indoor Thermostat
5
6
7
8
Table 1
For APH1524-43 models, dip switch 4 must be set to ON. Dip
switch 4 must be set to OFF for two-stage compressor models
APH1549-60. Dip switch 4 ON energizes Y1 signal to the
ECM motor anytime Y/Y2 is energized. The indoor motor will
not operate properly if switch is not set correctly for the model.
Electric Heat
Cooling & Heat Pump CFM
CFM Trim Adjust
APH CFM DELIVERYAND ADJUSTMENTS
See Appendix for CFM Output, Adjustments and DIP switch
settings.
APH THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 50% of the high
stage cooling setting.
APH HUMIDITY CONTROL
When using a Humidistat (normally closed), cut jumper PJ6 on the
control board. The Humidistat will only affect both low stage and
high stage cooling air flow by adjusting the Air flow to 85%.
APH TWO-STAGE HEATING
When using staged electric heat, cut jumper PJ4 on the control
board.
APH THERMOSTAT WIRING
Use thermostat wiring diagrams provided with the thermostat
when making these connections.
See Appendix for Blower Performance tables.
SUPERHEAT CAN BE DETERMINED AS FOLLOWS:
1. Read suction pressure. Determine Saturated Suction
Temperature from tables or pressure gauge saturated
temperature scale (R-410A).
1. Purge gauge lines. Connect service gauge manifold to
access fittings. Run system at least 10 minutes to allow
pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near
liquid line access fitting with adequate contact and insulate
for best possible reading.
3. Check subcooling and superheat. Systems with TXV
application should have a subcooling of 10 + 2°F and
superheat of 15 to 18ºF.
a. If subcooling and superheat are low, adjust TXV to 15
- 18ºF then check subcooling.
b. If subcooling is low and superheat is high, add charge
to raise subcooling to 10 ± 2ºF then check superheat.
c. If subcooling and superheat are high, adjust TXV valve
to 15 - 18ºF then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV
valve to 15 to 18ºF superheat and remove charge to
lower the subcooling to 10 ± 2ºF.
The TXV should NOT be adjusted at light load conditions 55º
to 60ºF, under such conditions only the subcooling can be
evaluated. This is because suction pressure is dependent
on indoor air flow, and wet bulb temperature.
NOTE: Do NOT adjust charge based on suction pressure
unless there is a gross undercharge.
4. Disconnect manifold set. Installation is complete.
Two Speed Application (*PH1549/60)
Run the unit on low stage cooling for 10 minutes until
refrigerant pressures stabilize. Follow the guidelines and
methods below to check unit operation and ensure that the
refrigerant charge is within limits. Charge the unit on low
stage.
1. Purge gauge lines. Connect service gauge manifold to
access fittings. Run system at least 10 minutes to allow
pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near
liquid line access fitting with adequate contact and insulate
for best possible reading.
3. Check subcooling and superheat. Two stage systems
running on low stage with TXV application should have a
subcooling of 5 to 7 ºF and superheat of 15 to 18ºF.
a. If subcooling and superheat are low, adjust TXV to 15
to 18ºF superheat, then check subcooling.
NOTE: To adjust superheat, turn the valve stem
clockwise to increase and counter clockwise to
decrease.
b. If subcooling is low and superheat is high, add charge
to raise subcooling to 5 to 7 ºF then check superheat.
c. If subcooling and superheat are high, adjust TXV valve
to 15 to 18ºF superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV
valve to 15 to 18ºF superheat and remove charge to
lower the subcooling to 5 to 7 ºF.
NOTE: Do NOT adjust the charge based on suction
pressure unless there is a gross undercharge.
4. Disconnect manifold set, installation is complete.
Refrigerant Charge Check (Units with Fixed Orifice Devices)
After completing airflow measurements and adjustments the
unit’s refrigerant charge must be checked. The unit comes
factory charged, but this charge is based on 325 CFM per ton
and minimum ESP per ARI test conditions (generally between
.15 -.25 ESP). When air quantity or ESP is different than above,
the refrigerant charge must be adjusted to the proper amount.
All package units with fixed orifice devices are charged using
the super heat method at the compressor suction line.
For charging in the warmer months, 8 ± 3ºF superheat at the
compressor is required at conditions 95ºF outdoor ambient
(dry bulb temperature), 80ºF dry bulb / 67ºF wet bulb indoor
ambient, approximately 50% humidity. This superheat varies
when conditions vary from the conditions described.
13
Page 14
After superheat is adjusted it is recommended to check unit sub-cooling at the condenser coil liquid line out. In most operating
conditions 10 - 15ºF of sub-cooling is adequate.
HEAT PUMP - HEATING CYCLE
The proper method of charging a heat pump in the heat mode is by weighing the charge according to the total charge listed on the
rating plate.
ELECTRICAL ADJUSTMENTS
This series of electric cooling and, heat pump package equipment is designed to accept a field installed electric heat kit. The unit
is equipped to easily install the HKR Series Electric Heat Kit. Full Installation Instructions are included in this kit. Please use this
document for guidance in field equipping the package unit with electric heat.
Choose the heat kit that fits the application for the specific installation. Permanently mark the unit’s nameplate with the model
being installed. High and low voltage connections are detailed in the heat kit instructions.
Indoor Blower motor speed tap selection may need to be modified to accommodate normal continuous operation to prevent a
nuisance trip. See tables below.
The Self Contained Package Air Conditioner and Heat Pump
should operate for many years without excessive service calls
if the unit is installed properly. However it is recommended
that the homeowner inspect the unit before a seasonal start
up. The coils should be free of debris so adequate air flow is
achieved. The return and supply registers should be free of
any obstructions. The filters should be cleaned or replaced.
These few steps will help to keep the product up time to a
maximum. The Troubleshooting Chart (see Appendix) should
help in identifying problems if the unit does not operate
properly.
Refer to Blower Performance section in the Appendix - Higher
air flow lowers temperature rise.
Lower air flow raises temperature rise.
SERVICE
THE FOLLOWING INFORMA TION IS FOR USE BY
QUALIFIED SERVICE AGENCY ONLY : OTHERS SHOULD
NOT A TTEMPT TO SERVICE THIS EQUIPMENT .
COMMON CAUSESOF UNSATISFACTORY OPERATIONOF HEAT
PUMPONTHE HEATING CYCLE
INADEQUATE AIR VOLUME THROUGH INDOOR COIL
When a heat pump is in the heating cycle, the indoor coil is functioning as a condenser. The return air filter must always be clean,
and sufficient air volume must pass through the indoor coil to
prevent excessive discharge pressure, and high pressure cut out.
OUTSIDE AIRINTO RETURN DUCT
Do not introduce cold outside air into the return duct of a heat
pump installation. Do not allow air entering the indoor coil to drop
below 65°F. Air below this temperature will cause low discharge
pressure, thus low suction pressure, and excessive defrost cycling resulting in low heating output. It may also cause false defrosting.
UNDERCHARGE
An undercharged heat pump on the heating cycle will cause low
discharge pressure resulting in low suction pressure and frost
accumulation on the outdoor coil.
POOR “TERMINATING” SENSORCONTACT
The unit’s defrost terminating sensor must make good thermal
contact with the outdoor coil tubing. Poor contact may not terminate the unit’s defrost cycle quickly enough to prevent the unit from
cutting out on high discharge pressure.
MALFUNCTIONING REVERSING VALVE - THISMAYBEDUETO:
1. Solenoid not energized - In order to determine if the
solenoid is energized, touch the nut that holds the solenoid
cover in place with a screwdriver. If the nut magnetically
holds the screwdriver, the solenoid is energized and the
unit is in the cooling cycle.
2. No voltage at unit’s solenoid - Check unit voltage. If no
voltage, check wiring circuit.
3. Valve will not shif t:
a. Undercharged - check for leaks;
b. Valve Body Damaged - Replace valve;
c. Unit Properly Charged - If it is on the heating cycle,
raise the discharge pressure by restricting air flow
through the indoor coil. If the valve does not shift, tap it
lightly on both ends with a screwdriver handle. DO NOT
T AP THE V ALVE BODY. If the unit is on the cooling cycle,
raise the discharge pressure by restricting air flow
through the outdoor coil. If the valve does not shift after
the above attempts, cut the unit off and wait until the
discharge and suction pressure equalize, and repeat
above steps. If the valve does not shift, replace it.
15
Page 16
APPENDIX
16
Page 17
TROUBLESHOOTING CHART
g
g
g
g
g
HIGH VOLT AGE!
Disconnect ALL power before servicing or installing this unit. Multiple
power sources may be present. Failure to do so may cause property
damage, personal injury or death.
SYMPTOM
High head - low suctiona. Restriction in liquid line or
High head - high or normal suctiona. In Cooling: Dirty condenser coila. Clean coil
Low head - high suction
Unit will not r un
Condenser f an runs,
compressor doesn't
Low suction - cool compressora. In Cooling: Low indoor airflowa.
Iced evaporator coilIn Heating: Dirty outdoor coil, de fective
Com pressor short cycle s
Registers sweatLow airflow
High suction pressure
Insufficient cooling
TXV not functioning
In Heating: Dirty filter, Dirty indoor coil
b. Overchar
c. In Coolin
c. In Heating: Indoor blower not runningc. Repair or Replace
a. Incorrect TXV.a. Replace with correct TXV
b. Defective compressor valvesb. Replace compressor
c. TXV not functioning properlyc. Check for debris in TXV or deformed TXV.
d. Incorrect TXV settingd. Check Super Heat
a. Power off or loose electrical connectiona. Check for unit voltage at contactor in unit
b. Thermostat out of calibration set too highb. Reset
c. Defective contactorc. Check for 24 volts at contactor coil replace if
d. Blown fuses or tripped breakerd. Replace fuse or reset breaker
e. Transformer defective
f. High or low pressure control open
(Optional)
g. Compressor overload contacts openg. Replace compressor
a. Loose connectiona. Check for unit voltage at compressor check &
b. Compressor stuck, grounded or open
winding open internal overload
c. Low voltage connectionc. At compressor terminals, voltage must be within
d. Capacitor weak, open, or shortedd. Check capacitor. If defective, replace.
defrost thermostat, defective defrost
control board, outdoor fan not runnin
refrigerant charge.
b. Low airflowb. Check - should be approximately 400 CFM per
c. Low refrigerant chargec. Properly charge unit
d. Operatin
outdoor temperature
a. Defective overload protectora. Replace - check for correct voltage
b. Unit cycling on low pressure controlb. Check refrigerant charge and / or airflow
c. High pressure switch cuts outc. Check airflow (indoor & outdoor),
a.a. Increase speed of blower or reduce restriction
a. Excessive loada. Recheck load calculation
b. Defective compressorb. Replace
c. Reversing valve not seating properly.c. Replace
a. Improperly sized unita. Recalculate load
b. Improper airflowb. Check - should be approximately 400 CFM per ton
edb. Correct System charge
: Condenser fan not runnin
unit in cooling mode below 65°F
a. Remove or replace with proper size TXV.
Remove debris or replace TXV.
contacts are open
e.
Check wiring - replace transformer
f. Check high pressure control or check unit
charge
High pressure control opens at 610 psig
Low pressure control opens at 22 psig
NOTE: Wait at least 2 hours for overload to reset
t ighten all conn ec tions
b. Wait at least 2 hours for overload to reset If still
open, replace the compressor.
10 % of nameplate volts when unit is operating
Increase speed of blower or reduce restriction replace air filters
, low
ton, dirty air filters, all duct outlets open
d. Install or check low ambient control, should be
open below 65°F outdoor temperature
check expansio n device
replace air filters
REMEDYPOSS IBLE CAUSE
c. Incorrect refrigerant charge.c. Charge per procedure attached to unit service
panel
d. Incorrect voltage d. At compressor terminals, voltage must be within
10% of nameplate volts when unit is operating
17
Page 18
GPH15 BLOWER PERFORMANCE DATA
ModelSpe edVolts
GPH 1524M41*
T1 (G)
T2 / T3
(W2)
T4 / T5 (Y)
230
230
230
T1 (G)230
T2 / T3
(W2)
GPH1530M41*
T4 / T5 (Y)230
T1 (G)
T2 / T3
(W2)
GPH1536M41*
T4 / T5 (Y)
230
230
230
230
E. S.P (In. of H
O)
2
0.10.20.30.40.50.60.70.8
CFM882808727649545------- --
WATTS828692102108----- ----
CFM933873810733637584------
WATTS93103109120126135------
CFM10581012945896816723672---
WATTS124136142153168172179- --
CFM893824752665575---------
WATTS8795101111115---------
CFM113210701011959889827733669
WATTS153162168179184195206208
CFM128712361165112310661012958857
WATTS211217228239244255265272
CFM852764711592545---------
WATTS8082869599----- ----
CFM12321190113110821023966889819
WATTS202214221229235246258264
CFM126712131162112010581009932841
WATTS218226236245247260272275
NOTES:
• Dat a sh ow n is dry coil . Wet coil pres su r e drop is approxi mately 0.1" H
0.2" H
0, for three- row indoor coil ; and 0.3" H20, for four-row indoor coil.
2
2
• Data shown does not incl ude filter pressure drop, approximately 0.08" H
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON .
• Reduce airflow by 2% for 208-volt operation.
0 , fo r two-row i ndoor c oi l;
0.
2
18
Page 19
GPH15 BLOWER PERFORMANCE DATA
ModelSpe edVolts
T1 (G) 23 0
GPH1543M41*
T2 (Y) / T3
(W2)
T4 / T5
(HS)
230
230
T1 (G) 23 0
T2 (Y) 23 0
T3 (W2) 2 30
GPH1549M41*
T4 (YHS)
T5
(W2HS)
230
230
E. S.P (In. of H
O)
2
0.10.20.30.40.50.60.70.8
CFM 1199113810851017957889820755
WA TTS 1621731851 93211219232245
CFM 13591322126212141165111910801039
WA TTS 2002142182 33243254267283
CFM 15981559152514831441139813531314
WATTS 332343360365384385404414
CFM 1199113810851017957889820755
WA TTS 1621731851 93211219232245
CFM 1 4181383134913121275122811781141
WATTS 242258273282299308320338
CFM 17991745169816581610156015221450
WA TTS 4804935085 21531545550547
CFM 17991745169816581610156015221450
WA TTS 4804935085 21531545550547
CFM 1 9211865181817801719166715791483
WATTS 582585602625627621595569
T1 (G)
230
CFM13901325128212231180113410661011
WATTS231240253262277292300316
CFM19001843180117621723167215771482
WATTS543559569583600603577554
CFM20942039198119071819173116281497
GPH1560M41*
T2 / T3
(W2)
T4 / T5 (Y)
230
230
WATTS724727720701671653611569
NOTES:
• Dat a sh ow n is dry coil. Wet co i l pres su r e drop is approxi mately 0.1" H20 , fo r two-r ow in door c oi l ;
0, for three- row indoor coil ; and 0.3" H20, for four-row indoor coil.
0.2" H
2
• Data shown does not include filter pressure drop, approximately 0.08" H
0.
2
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM /TON.
• Reduce airflow by 2% for 208-volt operat i on.
19
Page 20
GPC15 BLOWER PERFORMANCE DATA
ModelSpeedVolts
230
230
230
GPC1524M41*
T1 (G)
T2 / T3
T4 / T5
T1 (G)230
T2 / T3230
GPC 1530M41*
T4 / T5230
230
230
230
GPC1536M41*
T1 (G)
T2 / T3
T4 / T5
T1 (G)230
T2 / T3230
GPC1542M41*
T4 / T5230
T1 (G)
T2 / T3
GPC 1548M41*
T4 / T5
230
230
230
E.S.P (In. of H
O)
2
0.10.20.30.40.50.60.70.8
CFM882808727649545---------
WATTS828692102108---------
CFM933873810733637584------
WATTS93103109120126135------
CFM10581012945896816723672---
WATTS124136142153168172179---
CFM893824752665575---------
WATTS8795101111115---------
CFM113210701011959889827733669
WATTS153162168179184195206208
CFM128712361165112310661012958857
WATTS211217228239244255265272
CFM852764711592545---------
WATTS8082869599---------
CFM12321190113110821023966889819
WATTS202214221229235246258264
CFM126712131162112010581009932841
WATTS218226236245247260272275
CFM112310701025984942894839774
Watts162170182193204216229242
CFM14371390135413181281124312041165
Watts310317331342355366377389
CFM15281490145014101383134813121267
Watts372379391403416427439451
CFM1199113810851017957889820755
WATTS162173185193211219232245
CFM17991745169816581610156015221450
WATTS480493508521531545550547
CFM19211865181817801719166715791483
WATTS582585602625627621595569
NOTES:
• Data shown is dry coil. Wet c o il pressure drop is approximately 0.1" H20 , fo r two-r ow i ndoor c oi l ;
0.2" H
0, for three- row indoor coil ; and 0.3" H20, for four-row ind oor coil.
2
• Dat a sh ow n do es not include fi l ter pres sure d r op, app r ox ima tely 0.08" H
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON . See Repair Parts list.
DPlus770 D Plus770DPlus880 D Plus880
CMinus743CMinus743CMinus900CMinus900
CNormal825CNormal825CNormal1,000CNormal1,000
CPlus908CPlus908CPlus1,100CPlus1,100
BMinus855BMinus855BMinus990BMinus990
BNormal950BNormal950BNormal1,100BNormal1,100
BPlus1,045BPlus1,045BPlus1,210BPlus1,210
AMinus945AMinus945AMinus1,125AMinus1,125
ANormal1,050 A Normal1,050A Normal1,250 A Normal1,250
APlus1,155APlus1,155APlus1,375APlus1,375
* @ 0.1 - 0.5 ESP* @ 0.1 - 0.5 ESP
Cooling/HP
Speed
DMinus720DMinus720DMinus1,103DMinus1,103
DNormal800DNormal800DNormal1,225DNormal1,225
DPlus880DPlus880DPlus***1,348DPlus1,348
CMinus900CMinus900CMinus**1,260CMinus**1,260
CNormal1,000 C Normal1,000CNormal1,400 C Normal1,400
CPlus1,100CPlus1,100CPlus1,540CPlus1,540
BMinus990BMinus990BMinus1,530BMinus1,530
BNormal1,100 B Normal1,100B Normal1,700 B Normal1,700
BPlus1,210BPlus1,210BPlus1,870BPlus1,870
AMinus1,125AMinus1,125AMinus1,620AMinus1,620
ANormal1,250 A Normal1,250A Normal1,800 A Normal1,800
APlus1,375APlus1,375APlus1,980APlus***1,980
* @ 0.1 - 0.5 ESP* @ 0.1 - 0.5 ESP
Adjust
Tap
Adjust
Tap
CFM*
APH1536M41
CFM*
Electric
Heat
Electric
Heat
Adjust
Tap
Adjust
Tap
CFM*
CFM*
Cooling/HP
Speed
Cooling/HP
Speed
** DENO TES FACTO RY SETTING FOR APH1543M4 1
*** DENOTES FA CTORY SETTING FOR APH1549M41
Adjust
Tap
APH1543M41 APH1549M41
Adjust
Tap
CFM *
CFM *
Electric
Heat
Electric
Heat
Adjust
Tap
Adjust
Tap
CFM*
CFM*
APH1560M41
Cooling/HP
Speed
DMinus1,260DMinus1,260
DNormal1,400 D Normal1,400
DPlus1,540 D Plus1,540
CMinus1,440CMinus1,440
CNormal1,600 C Normal1,600
CPlus1,760 C Plus1,760
BMinus1,620BMinus1,620
BNormal1,800 B Normal1,800
BPlus1,980 B Plus1,980
AMinus1,800AMinus1,800
ANormal2,000 A Normal2,000
APlus2,200 A Plus2,200