Goodman PC, PH15 Installation Instructions Manual

Page 1
I
NSTALLATION INSTRUCTIONS
F
OR
S
ELF
H
-C
EAT
ONTAINED
P
UMP
U
P
NITS
ACKAGE
*PC/*PH15 “M” SERIES
Affix this manual and Users Information Manual adjacent to the unit.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During
installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
These installation instructions cover the outdoor installation of self contained package air conditioners and heating units. See the Specification Sheets applicable to your model for information regarding accessories.
Goodman Manufacturing Company , L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
IO-394 8/10
© 2010 Goodman Manufacturing Company, L.P.
*NOTE: Please contact your distributor or our
website for the applicable
Specification Sheets referred to in this manual.
Page 2
INDEX
TO THE INSTALLER .............................................................................................................................................. 4
I
MPORTANT NOTE TO THE HOMEOWNER REGARDING PRODUCT WARRANTY ..................................................................... 4
SHIPPING INSPECTION ...................................................................................................................................................... 4
REPLACEMENT P ARTS ....................................................................................................................................................... 4
ORDERING PARTS .............................................................................................................................................. 4
SAFETY INSTRUCTIONS..................................................................................................................................................... 4
CODES AND REGULATIONS ............................................................................................................................................... 5
EP A REGULA TIONS ............................................................................................................................................ 5
N
ATIONAL CODES ............................................................................................................................................... 5
MAJOR COMPONENTS ....................................................................................................................................................... 5
PRE-INSTALLA TION CHECKS ............................................................................................................................................. 5
CLEARANCES AND ACCESSIBILITY........................................................................................................................... 5
U
NIT LOCATION ................................................................................................................................................... 5
G
ROUND LEVEL PRE-INSTALLATION DET AILS............................................................................................................ 5
R
OOF TOP PRE-INSTALLATION DETAILS .................................................................................................................. 6
R
OOF CURB INSTALLATIONS ONLY ......................................................................................................................... 6
R
IGGING DETAILS ............................................................................................................................................... 6
CIRCULA TING AIR AND FILTERS ....................................................................................................................................... 7
AIR FLOW CONVERSION ....................................................................................................................................... 7
D
UCT WORK ....................................................................................................................................................... 7
F
ILTERS ............................................................................................................................................................ 7
PIPING ................................................................................................................................................................................. 8
CONDENSA TE DRAIN ........................................................................................................................................... 8
WIRING ................................................................................................................................................................................ 8
HIGH VOL TAGE WIRING........................................................................................................................................ 8
L
OW VOLTAGE WIRING ........................................................................................................................................ 8
I
NTERNAL WIRING ............................................................................................................................................... 8
ST ARTUP , ADJUSTMENTS, AND CHECKS ......................................................................................................................... 9
COOLING START-UP PROCEDURES ........................................................................................................................ 9
H
EAT PUMP START-UP PROCEDURE ...................................................................................................................... 9
F
INAL SYSTEM CHECKS ...................................................................................................................................... 9
COMPONENTS .................................................................................................................................................................... 9
CONT ACT OR ....................................................................................................................................................... 9
C
RANKCASE HEATER .......................................................................................................................................... 9
C
ONDENSER MOTOR........................................................................................................................................... 9
C
OMPRESSOR ................................................................................................................................................. 10
C
ONTACT OR RELAY........................................................................................................................................... 10
D
EFROST CONTROL .......................................................................................................................................... 10
O
UTDOOR THERMOSTAT ..................................................................................................................................... 10
R
EVERSING VALVE COIL ................................................................................................................................... 10
I
NDOOR BLOWER MOTOR ................................................................................................................................... 10
HEA T PUMP OPERA TION .................................................................................................................................................. 10
COOLING CYCLE .............................................................................................................................................. 10
H
EA TING CYCLE ............................................................................................................................................... 10
D
EFROST CONTROL ...........................................................................................................................................11
A
IR FLOW MEASUREMENT AND ADJUSTMENT .......................................................................................................... 12
A
IR FLOW ADJUSTMENTS FOR INDOOR BLOWER MOTOR .......................................................................................... 12
2
Page 3
APH DIP SWITCH FUNCTIONS ............................................................................................................................ 12
APH CFM D APH T APH H APH T APH T E
XPANSION VALVE (TXV) SYSTEM ..................................................................................................................... 13
H
EAT PUMP - HEATING CYCLE ........................................................................................................................... 14
ELECTRICAL ADJUSTMENTS ........................................................................................................................................... 14
MAINTENANCE .................................................................................................................................................................. 15
SERVICE ............................................................................................................................................................................ 15
ELIVERY AND ADJUSTMENTS ............................................................................................................ 12
HERMOSTAT “FAN ONLY” MODE .............................................................................................................. 12
UMIDITY CONTROL .................................................................................................................................. 12
WO-STAGE HEATING ............................................................................................................................... 12
HERMOSTAT WIRING ................................................................................................................................12
COMMON CAUSES OF UNSATISFACTORY OPERATION OF HEAT PUMP ON THE HEATING CYCLE ........................................ 15
NADEQUATE AIR VOLUME THROUGH INDOOR COIL ............................................................................................... 15
I
OUTSIDE AIR INTO RETURN DUCT ..................................................................................................................... 15
UNDERCHARGE .............................................................................................................................................. 15
OOR “TERMINATING” SENSOR CONTACT........................................................................................................... 15
P
MALFUNCTIONING REVERSING VALVE - THIS MAY BE DUE TO: ................................................................................ 15
APPENDIX ......................................................................................................................................................................... 16
TROUBLESHOOTING CHART ................................................................................................................................. 17
GPH15 B GPC15 B APH15 B APH15 CFM O
CFM O
LOWER PERFORMANCE DATA ............................................................................................................... 18
LOWER PERFORMANCE DATA ............................................................................................................... 20
LOWER PERFORMANCE DATA ............................................................................................................... 21
UTPUT AND DIP SWITCH SETTINGS .............................................................................................. 22
UTPUT FOR DIP SWITCH COMBINATIONS 1-2 (ELECTRIC HEAT).................................................................. 22
DIP SWITCH SETTINGS FOR SINGLE AND TWO-STAGE THERMOSTATS ...................................................................... 22
CFM OUTPUT FOR DIP SWITCH COMBINATIONS 5-6 (COOLING/HEATING). ............................................................. 22
ADJUSTMENTS THROUGH DIP SWITCH COMBINATIONS 7-8.................................................................................... 22
3
Page 4
TO THE INSTALLER
Carefully read all instructions for the installation prior to installing unit. Make sure each step or procedure is understood and any special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. After deciding where to install unit, closely look the location over - both the inside and outside of home. Note any potential obstacles or problems that might be encountered as noted in this manual. Choose a more suitable location if necessary.
IMPORTANT NOTE: If a crankcase heater is used, the unit should be energized 24 hours prior to compressor start up to ensure crankcase heater has sufficiently warmed the compres­sor. Compressor damage may occur if this step is not fol­lowed.
IMPORTANT NOTE TO THE OWNER REGARDING PRODUCT WARRANTY
Your warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited warranty certificate carefully to determine what is and is not covered and keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate please contact your installing contractor or contact customer service (877­254-4729) to obtain a copy.
To receive the 10-year Parts Limited Warranty for Goodman branded products, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec. Complete warranty details available at your local dealer or at www.goodmanmfg.com.
IMPORTANT: To register your Goodman brand unit, go to www.goodmanmfg.com. Click on the word “Warranty” located on the left side of the home page. Next, click on the word “Product Registration” located on the left side of the Warranty page and complete the forms in the manner indicated on the Product Registration page. Product limited warranty certificates for models currently in production can be viewed at www.goodmanmfg.com. If your model is not currently in production or does not appear on the website, please contact your installing contractor or contact customer service (877-254-4729) to obtain a copy of your warranty certificate. Each product overview page contains a Product Warranty link; by clicking on it you will be able to view the limited warranty coverage for that specific product. T o view warranty registration information, click on the Product Warranty text on the left navigation panel on the home page of each website. The Online Product Registration pages are located in this same section.
Before using this manual, check the serial plate for proper model identification.
The installation and servicing of this equipment must be performed by qualified, experienced technicians only.
SHIPPING INSPECTION
Upon receiving the unit, inspect it for damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. Check the unit model number, specifications, electrical characteristics and accessories to determine if they are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufacturer assumes no responsibility for installation of incorrectly shipped units.
REPLACEMENT PARTS
O
RDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMP ANY, L.P .
7401 SECURITY WA Y
HOUSTON, TEXAS 77040
877-254-4729
SAFETY INSTRUCTIONS
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
4
Page 5
CODES AND REGULATIONS
The *PH/C M-series heat pumps are designed for OUTDOOR USE ONLY. *PH M-Series is available in cooling capacities of 2, 2.5 3, 4 and 5 nominal tons of cooling. The GPC is only available in 2 thru 4 ton. Optional field installed heat kits are available in 5,8,10,15 and 20 kW. The units can be easily installed in manufactured or modular homes with existing high-static duct work. The units can also be easily converted to accommodate a plenum for normal or low-static applications. The *PH/C M-series are self contained packaged units so the only connections needed for installation are the supply and return ducts, the line and low voltage wiring and drain connection. The units are ETL listed and AHRI certified.
The information on the rating plate is in compliance with the FTC & DOE rating for single phase units.
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EP A) HAS ISSUED V ARIOUS REGULATIONS REGARDING THE
INTRODUCTION
AND DISPOSAL OF REFRIGERANTS IN THIS UNIT.
FAILURE TO FOLLOW THESE REGULATIONS MAY HARM THE
ENVIRONMENT
. BECAUSE REGULATIONS MA Y VARY DUE TO PASSAGE OF NEW
FINES
, WE SUGGEST A CERTIFIED TECHNICIAN PERFORM ANY WORK
LAWS
ON THIS UNIT. SHOULD YOU HAVE ANY QUESTIONS PLEASE
DONE CONTAC T
AND CAN LEAD TO THE IMPOSITION OF SUBSTANTIAL
THE LOCAL OFFICE OF THE EPA.
NATIONAL CODES
This product is designed and manufactured to permit installation in accordance with National Codes. It is the installer’s responsibility to install the product in accordance with National Codes and/or prevailing local codes and regulations.
PRE-INSTALLATION CHECKS
Before attempting any installation, the following points should be considered:
Structural strength of supporting members
Clearances and provision for servicing
Power supply and wiring
Air duct connections
Drain facilities and connections
Location may be on any four sides of a home, manufactured or modular, to minimize noise
CLEARANCES AND ACCESSIBILITY
The unit is designed to be located outside the building with unobstructed condenser air inlet and discharge. Additionally, the unit must be situated to permit access for service and installation. Condenser air enters from three sides. Air discharges upward from the top of the unit. Refrigerant gauge connections are made on the right side of the unit as you face the compressor compartment. Electrical connections can be made either on the right, bottom or duct panel side of the unit. The best and most common application is for the unit to be located 10” from wall (4” minimum) with the connection side facing the wall. This “close to the wall” application minimizes exposed wiring.
Close to the wall application assures free, unobstructed air to the other two sides. In more confined application spaces, such as corners provide a minimum 12” clearance on all air inlet sides. Allow 36” minimum for service access to the compressor compartment and controls. The top of the unit should be completely unobstructed. If units are to be located under an overhang, there should be a minimum of 48” clearance and provisions made to deflect the warm discharge air out from the overhang.
UNIT LOCATION
Consider the affect of outdoor fan noise on conditioned space and any adjacent occupied space. It is recommended that the unit be placed so that condenser air discharge does not blow toward windows less than 25 feet away. Consideration should also be given to shade and unit appearance.
Heat pumps require special location consideration in areas of heavy snow accumulation and/or areas with prolonged continu­ous subfreezing temperatures. Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accumu­lation. The unit must be situated to permit free unobstructed drain­age of the defrost water and ice. A minimum 2" clearance under the outdoor coil is required in the milder climates.
GROUND LEVEL PRE-INSTALLATION DETAILS
The unit should be set on a solid, level foundation - preferably a concrete slab at least 4 inches thick. The slab should be above ground level and surrounded by a graveled area for good drainage. Any slab used as a unit’s foundation should not adjoin the building as it is possible that sound and vibration may be transmitted to the structure.
MAJOR COMPONENTS
The unit includes a hermetically sealed refrigerating system (consisting of a compressor, condenser coil, evaporator coil with flowrator), an indoor blower, a condenser fan and all necessary internal electrical wiring. The heat pump also includes a reversing valve, solenoid, defrost thermostat and control and loss of charge protection. The system is factory­evacuated, charged and performance tested. Refrigerant amount and type are indicated on rating plate.
5
Page 6
Ground Level Installation
ROOF TOP PRE-INSTALLATION DETAILS
Ensure that the roof is weather tight and allows proper drainage of condensation. Use steel or treated wood beams as unit support for load distribution.
NOTE: To ensure proper condensate drainage, unit must be installed in a level position.
To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consult a structural engineer to determine the weight capabilities of the roof.
The unit may be installed directly on wood floors or on Class A, Class B, or Class C roof covering material.
To avoid possible personal injury, a safe, flat surface for service personnel should be provided.
ROOF CURB INSTALLATIONS ONLY
NOTE: Sufficient structural support must be determined prior
to locating and mounting the curb and package unit. Curb insulation, cant strips, flashing and general roofing
material are furnished by the contractor. Curbing must be installed in compliance with the National
Roofing Contractors Association Manual. Construct duct work using current industry guidelines. The duct work must be placed into the roof curb before mounting the package unit.
Rooftop Installation
Roof Curb Installation
RIGGING DETAILS
IMPORTANT: If using bottom discharge with roof curb, duct
work should be attached to the curb prior to installing the unit. Lower unit carefully onto roof mounting curb. While rigging
unit, center of gravity will cause condenser end to be lower than supply air end.
6
Page 7
Rigging
CIRCULA TING AIR AND FILTERS
A
IR FLOW CONVERSION
Units can easily be converted from horizontal to down discharge air flow delivery. In down discharge or high static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations it will be necessary to change the blower speed to provide proper air flow.
Horizontal Air Flow
Single phase models are shipped without horizontal duct covers. If needed, these kits may be ordered through Goodman’s Service Parts department.
Return
Supply
Remove these panels for downflow duct applications
Duct Cover Installation
Down Discharge Applications
Cut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place.
NOTE: Single phase models require installation of horizontal duct kit #20464501PDGK (medium chassis) and #20464502PDGK (large chassis).
DUCT WORK
Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the unit. Duct work should be designed in accordance with the recommended methods of Air Conditioning Contractors of America Manual D (Residential) or Manual Q (Commercial). All duct work exposed to the outdoors must include a weatherproof barrier and adequate insulation.
A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems. Pamphlets No. 90A and 90B.
The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances as shown in the Appendix must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks.
For duct flange dimensions on the unit refer to the Unit Dimension illustration in the Appendix.
For down discharge applications, the duct work should be attached to the roof curb prior to installing the unit. Duct work dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
FILTERS
Filters are not provided with unit and must be supplied and externally installed in the return duct system by the installer . A field-installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning. When installing filters, ensure the air flow arrows on the filter are pointing toward the circulator blower.
Refer to the unit filter size chart below for filter size information.
MINIMUM FILTER SIZE
NOMINAL SIZE (INCHES) NOMINAL AREA (SQ. FT.)
10x20 1.4 14x20 1.9 14x25 2.4 15x20 2.1 16x20 2.2 16x25 2.8 20x20 2.8 20x25 3.5
25x25 4.3
NOTE: Filters must have adequate face area for the rated quantity of the unit. See the air delivery table below for recommended filter size. Size the filters in accordance with their manufacturer recommendations. Throwaway filters must be sized for a maximum face velocity of 300 feet per minute.
7
a e
r
6
t
A
e
r
e
e
t
F
l
5
i
e
F
r
l
a
a
u
n
4
q
i
S
m o N
3
B
A
S
O
P
S
I
D
2
500 1000 1500 2000 2500 3000 3500
R
E
T
L
I
F
E
L
M
R
E
P
Airflow - SCFM
R
E
T
L
I
F
T
N
E
N
A
7
Page 8
PIPING
(
C
ONDENSATE DRAIN
The condensate drain connection of the evaporator is a half coupling of ¾” N.P.T. A trap must be provided to have proper condensate drainage.
Unit
Drain Connection
Flexible Tubing-Hose Or Pipe
Install condensate drain trap as shown. Use ¾ “ drain connection size or larger. Do not operate without trap. Unit must be level or slightly inclined toward drain.
A Positive Liquid Seal Is Required
2" Minimum
3" Minimum
WIRING
NOTE: All wiring should be made in accordance with the
National Electrical Code. Consult your local Power Company to determine the
availability of sufficient power to operate the unit. Check the voltage, frequency, and phase at the power supply to ensure it corresponds to the unit’s RA TED VOL T AGE REQUIREMENT .
In accordance with the N.E.C. or local codes, install a branch circuit fused disconnect near the unit. Determine wire sizes and overcurrent protection from the unit nameplate ampacity and in accordance with the Minimum Filter Size or the N.E.C. The wiring should never be sized smaller than is recommended by either of these two sources.
Fuses smaller than that recommended on the rating plate could result in unnecessary fuse failure or service calls. The use of protective devices of larger size than indicated could result in extensive damage to the equipment. The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices.
All units have undergone a run test prior to packaging for shipment. This equipment has been started at minimum rated voltage and checked for satisfactory operation. Do not attempt to operate this unit if the voltage is not within the minimum and maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit. The unit must be permanently grounded in accordance with local codes, or in absence of local codes, with N.E.C. ANSI/ NFP A NO. 70-1984 or latest edition by using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where codes permit.
IMPORTANT NOTE: Some single phase units are equipped with a single-pole contactor. Exercise caution when servicing as only one leg of the power supply is broken with the contractor.
LOW VOLTAGE WIRING
Heat Pumps. Connect 24V wires from the thermostat to the corresponding wires in the control box using No. 18 AWG as follows:
GPC15
Terminal
Re d
24 - 60
Thermostat
R (24V)
Green G (fan)
White
Brown W2
Yellow
W1 (heat*)
heat*)
Y (cool)
Blue C (24V Common)
[A/G]PH15
Terminal
Red R (24V) R (24V)
Green G (fan) G (fan)
Orange O (rev. valve) O (rev. valve)
White W1 (heat, 2nd) W1 (heat. 2nd)*
Brown W2 (heat, 3rd) W2 (heat, 3rd)* Purple Not used Y1 (Low cool) Yellow Y (cool) Y2 (Hi cool)
Blue C (24V Common) C (24V Common)
Thermostats must be set to energize "G" during cooling. This is default on most all thermostats.
*Optional field installed heat connections.
*PH1549 - *PH1560 have two-stage cooling and require two-stage heat/cool with optional third stage electric heat thermostat.
24 - 4 3
Thermostat
49 - 60
Thermostat
INTERNAL WIRING
A diagram detailing the internal wiring of this unit is located on the electrical box cover. If any of the original wire supplied with the appliance must be replaced, the wire gauge and insulation must be the same as the original wiring.
Transformer is wired for 230 volts on the 208/230 models. See wiring diagram for 208 volt wiring.
1. For branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of run can be determined using the circuit ampacity found on the unit rating plate and the table below. From the unit disconnect to the unit, the smallest wire size allowable may be used for the ampacity , as the disconnect must be
in sight of the unit.
BRANCH CIRCUIT AMPA CITY
SUPPLY WIRE LENGTH -
FEET
200 64443322 150 86644433 100 108866644
50 141210108866
15 20 25 30 35 40 45 50
HIGH VOLTAGE WIRING
Single Phase. Connect two leads to terminals L1 & L2 in the electrical control section, using wire sizes specified in wiring table.
2. Wire size based on 60°C rated wire insulation and 30°C Ambient Temperature (86°F).
3. For more than three conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor.
8
Page 9
STARTUP, ADJUSTMENTS, AND CHECKS
COOLING START-UP PROCEDURES
With power turned off at all disconnects:
1. Turn thermostat system switch to “COOL” and fan switch to “AUTO”. Next, turn the temperature setting as high as it will go.
2. Inspect all registers and set them to the normal open position.
3. Turn on the electrical supply at the disconnect.
4. Turn the fan switch to the “ON” position. The blower should begin ramping up immediately.
5. Turn the fan switch to “AUTO” position. The blower should begin ramping down after an approximate 60-second delay.
6. Slowly lower the cooling temperature until the unit starts. The compressor, blower and fan should now be operating. Allow the unit to run 10 minutes, make sure cool air is being supplied by the unit.
7. Turn the temperature setting to the highest position, stopping the unit. The indoor blower will continue to run for approximately 60-seconds.
8. Turn the thermostat system switch to “OFF” and disconnect all power when servicing the unit.
HEAT PUMP START-UP PROCEDURE
1. Check the cooling mode for the heat pump in the same manner as above. The reversing valve is energized when the thermostat is placed in the cooling position. A clicking sound should be noticeable from the reversing valve. By lowering the temperature setting to call for cooling, the contractor is energized. The compressor, blower and fan should then be running. Af ter the cooling mode is checked out, turn the thermostat system switch to “OFF”.
2. Turn the thermostat system switch to “HEA T” and fan switch to “AUTO”.
3. Slowly raise the heating temperature setting. When the heating first stage makes contact, stop raising the temperature setting.. The compressor, blower and fan should now be running with the reversing valve in the de­energized (heating) position. After giving the unit time to settle out, make sure the unit is supplying heated air.
4. If the outdoor ambient is above 80°F, the unit may trip on its high pressure cut out when on heating. The compressor should stop. The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable. DO NOT FAIL TO TEST.
5. If the outdoor ambient is low and the unit operates properly on the heating cycle, you may check the pressure cutout operation by blocking off the indoor return air until the unit trips.
6. If unit operates properly in the heating cycle, raise the temperature setting until the heating second stage makes contact. Supplemental resistance heat, if installed should now come on. Ensure all heaters energize.
NOTE: *PH1542-60 have two stages of compressor heat. During resistance heat test, increase temperature setting until third stage heat is energized.
If outdoor thermostats are installed, the outdoor ambient must be below the set point of these thermostats for the heaters to operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild.
7. THERMOSTA TS WITH EMERGENCY HEA T . For thermostats with an emergency heat switch, raise the temperature setting until the heating second stage makes contact. The emergency heat switch is located at the bottom of the thermostat. Move the switch to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat emergency heat light will come on.
8. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely.
FINAL SYSTEM CHECKS
1. Ensure all supply and return air grilles are adjusted and the air distribution system is balanced for the best compromise between heating and cooling.
2. Ensure there are no air leaks in the duct work.
3. Check air flow and refrigerant charge. See Sections on
Air Flow Measurement and Adjustment and Checking Charge.
4. Ensure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. The tubes or lines should not rub against sheet metal surfaces, edges or each other.
5. Ensure the Owner is instructed on the unit operation, filter, servicing, correct thermostat operation, etc.
Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.
NOTE: The “Cooling Start-up Procedure” is a recommended step as it serves as an system indicator that the unit will operate normally.
COMPONENTS
Contactor
This control is activated (closed) by the room thermostat for both heating and cooling. The contactor has a 24V coil and supplies power to the compressor and outdoor fan motor.
Crankcase Heater
This item is “ON” whenever power is supplied to the unit and the crankcase heater thermostat is closed. Crankcase heater thermostat closes at 67° and opens at 85°. It warms the compressor crankcase thereby preventing liquid migration and subsequent compressor damage. The insert type heater is self regulating. It is connected electrically to the contactor L1 and L2 terminals.
Condenser Motor
This item is activated by the contactor during heating and cooling, except during defrost and emergency heat operation. On 460V heat pumps, the condenser motor is activated by the CMR.
9
Page 10
Compressor
This item is activated by the contactor for heating and cooling, except during emergency heat. It is protected by an internal overload.
Contactor Relay
This control is activated by the thermostat (24V coil) and supplies power to the contactor.
Defrost Control
The Defrost Control provides time/temperature initiation and termination of the defrost cycle. When a defrost cycle is initiated, the Defrost Control shifts the reversing valve to “COOLING” mode, stops the outdoor fan and brings on supplemental heat. Normally, a defrost cycle will take only 2­3 minutes unless system is low on refrigerant charge or outdoor conditions are severe (i.e. windy and cold). The defrost control also provides for a 3 minute off cycle compressor delay.
Outdoor Thermostat
These optional controls are used to prevent full electric heater operation at varying outdoor ambient (0°F to 45°F). They are normally open above their set points and closed below to permit staging of indoor supplement heater operation. If the outdoor ambient temperature is below 0°F (-18°C) with 50% or higher RH, an outdoor thermostat (OT) must be installed and set at (0°) on the dial. Failure to comply with this requirement may result in damage to the product which may not be covered by the manufacturer’s warranty.
Reversing Valve Coil
This coil is activated by the thermostat, in the cooling mode and during defrost. It positions the reversing valve pilot valve for cooling operation.
Indoor Blower Motor
This is activated by the room thermostat by COOLING or FAN ON position. For GPC/GPH models, the motor is energized directly by the room thermostat for X-13 motors. X-13 motors are constant torque motors with very low power consumption. For APH models, the motor is energized by the fan control board for ECM motors. ECM motors are constant CFM motors with very low power consumption. This motor is energized by a 24V signal from the thermostat. (See Air Flow Measurement and Adjustment for speed adjustment instructions).
The following figures show a schematic of a heat pump on the cooling cycle and the heating cycle. In addition to a reversing valve, a heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equipment for the outdoor coil. It is also provided with a defrost control system.
The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle. The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow.
When the heat pump is on the heating cycle, the outdoor coil is functioning as an evaporator. The temperature of the refrigerant in the outdoor coil must be below the temperature of the outdoor air in order to extract heat from the air. Thus, the greater the difference in the outdoor temperature and the outdoor coil temperature, the greater the heating capacity of the heat pump. This phenomenon is a characteristic of a heat pump. It is a good practice to provide supplementary heat for all heat pump installations in areas where the temperature drops below 45°F. It is also a good practice to provide sufficient supplementary heat to handle the entire heating requirement should there be a component failure of the heat pump, such as a compressor, or refrigerant leak, etc.
Since the temperature of the refrigerant in the outdoor coil on the heating cycle is generally below freezing point, frost forms on the surfaces of the outdoor coil under certain weather conditions of temperature and relative humidity. Therefore, it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor coil to melt the frost accumulation. This is accomplished by reversing the heat pump to the cooling cycle. At the same time, the outdoor fan stops to hasten the temperature rise of the outdoor coil and lessen the time required for defrosting. The indoor blower continues to run and the supplementary heaters are energized.
HEAT PUMP OPERATION
C
OOLING CYCLE
When the heat pump is in the cooling cycle, it operates exactly as a Air Conditioner unit.
HEATING CYCLE
The heat pump operates in the heating cycle by redirecting refrigerant flow through the refrigerant circuit external to the compressor. This is accomplished with through the reversing valve. Hot discharge vapor from the compressor is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes through the expansion device to the outdoor coil (condenser on the cooling cycle) where the liquid is evaporated, and the vapor goes to the compressor.
When the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pressure) reverse positions in the reversing valve.
10
Page 11
COOLING
SERVICE VALVE
SERVICE PORT
REVERSING VALVE
R O
T A R O P
A V E
INDOOR
CHECK VALVE
COIL
HEATING
SERVICE VALVE
R E S N
E D N O C
INDOOR
CHECK VALVE
COIL
SERVICE PORT
COMPRESSOR
DISTRIBUTOR
EXPANSION DEVICE
ORIFICE
DISTRIBUTOR
ORIFICE
SERVICE
VALVE
COMPR ESSOR
SERVICE
VALVE
SERVICE PORT
ACCUMULATOR
SERVICE PORT
CHECK VALVE
ORIFICE
ACCUMULATO R
SERVICE PORT
CHECK VALVE
ORIFICE
OUTDOOR
REVERSING VALVE
DISTRIBUTOR
OUTDOOR
DEFROST CONTROL
During operation the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of 30, 60 and 90 minutes may be selected by setting the circuit board jumper to 30, 60 and 90 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately 34°F), and when the wall thermostat calls for heat. At the end of the timing period, the unit’s defrost cycle will be initiated provided the sensor remains closed. When the sensor opens (approximately 60°F), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor temperature, a twelve minute override interrupts the unit’s defrost period.
COIL
COIL
R
E S N E D N O C
R O
T
A R O
P A V
E
Suggested Field Testing/Trouble Shooting
1. Run unit in the heating mode (room thermostat calling for heat).
2. Check unit for proper charge. NOTE: Bands of frost on the
condenser coil indicate low refrigerant charge.
3. Shut off power to unit.
4. Disconnect outdoor fan by removing the outdoor fan motor wire from “DF2” on defrost control.
5. Restart unit and allow frost to accumulate.
6. After a few minutes of operation, the unit’s defrost thermostat should close. To verify this, check for 24 volts between “DFT” and “C” on board. If the temperature at the thermostat is less than 28°F and the thermostat is open, replace the unit’s defrost thermostat, as it is defective.
7. When the unit’s defrost thermostat has closed, short the test pins on the defrost board until the reversing valve shifts, indicating defrost. This should take up to 21 seconds depending on what timing period the control is set on. After defrost initiation, the short must instantly be removed or the unit’s defrost period will only last 2.3 seconds.
8. The control is shipped from the factory with the compressor delay option selected. This will de-energize the compressor contactor for 30 seconds on defrost initiation and defrost termination. If the jumper is set to Normal, the compressor will continue to run during defrost initiation and defrost termination. The control will also ignore the low pressure switch connected to R-PS1 and PS2 for 5 minutes upon defrost initiation and 5 minutes after defrost termination.
9. After the unit’s defrost thermostat has terminated, check the defrost thermostat for 24 volts between “DFT” and “C”. The reading should indicate 0 volts (open sensor).
10. Shut off power to unit.
11. Replace outdoor fan motor lead to terminal “DF2” on defrost board and turn on power.
11
Page 12
AIR FLOW MEASUREMENT AND ADJUSTMENT
Please review the Duct Work section before proceeding with the airflow measurements and adjustments in this section.
Unit blower curves (see Specification Sheets) are based on external static pressure (ESP per in/W .C.). The duct openings on the unit are considered internal static pressure. As long as ESP is maintained, the unit will deliver the proper air up to the maximum static pressure listed for the CFM required by the application (i.e. home, building, etc.)
In general, 400 CFM per ton of cooling capacity is a rule of thumb. Some applications depending on the sensible and latent capacity requirements may need only 350 CFM or up to 425 CFM per ton. Check condition space load requirements (from load calculations) and equipment expanded ratings data to match CFM and capacity.
After unit is set and duct work completed, verify the ESP with a 1-inch inclined manometer with pilot tubes or a Magnahelic gauge and confirm CFM to blower curves in the Specification Sheets.
NOTE: Never run CFM below 350 CFM per ton, evaporator freezing or poor unit performance is possible.
AIR FLOW ADJUSTMENTS FOR INDOOR BLOWER MOTOR
X-13 Motor
Adjust the CFM by changing the 24V low voltage lead at the speed terminal block on the motor. (T1-Low Speed, T2 and T3-Medium Speed, T4 and T5-High Speed).
NOTE: Factory set T1 (G , fan), T2 (cool/Hi cool), T3 (W2 electric heat), T4 and T5 reserved for high static (cool/Hi cool) and W2. GPH1548M41 and GPH1560M41 low cool Y1 will run at G speed.
ECM Motor
The ECM control board is factory set with the dip switch #4 in the “ON” position for single stage units and to the "OFF" position for the 2 stage units. All other dip switches are factory set in the “OFF” position. For most applications, the settings
are to be changed according to the electric heat size.
The ECM motor provides many features not available on the traditional PSC motor. These features include:
Improved Efficiency
Constant CFM
Soft Start and Stop
Improved Humidity Control
ECM Motor Speed Adjustment
Each ECM blower motor has been preprogrammed for operation at 4 distinct air flow levels when operating in Cooling/ Heat Pump mode or Electric Heat mode. These 4 distinct levels may also be adjusted slightly lower or higher if desired. The adjustment between levels and the trim adjustments are made by changing the dip switch(s) either to an "OFF" or "ON" position.
APH DIP SWITCH FUNCTIONS
The ECM motor has an electronic control that contains eight (8) 2-position dip switches. The function of these dip switches is shown in Table 1.
DIP SWITCH NUMBER FUNCTION
1 2 3N/A 4 Indoor Thermostat 5 6 7 8
Table 1
For APH1524-43 models, dip switch 4 must be set to ON. Dip switch 4 must be set to OFF for two-stage compressor models APH1549-60. Dip switch 4 ON energizes Y1 signal to the ECM motor anytime Y/Y2 is energized. The indoor motor will not operate properly if switch is not set correctly for the model.
Electric Heat
Cooling & Heat Pump CFM
CFM Trim Adjust
APH CFM DELIVERY AND ADJUSTMENTS
See Appendix for CFM Output, Adjustments and DIP switch settings.
APH THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 50% of the high stage cooling setting.
APH HUMIDITY CONTROL
When using a Humidistat (normally closed), cut jumper PJ6 on the control board. The Humidistat will only affect both low stage and high stage cooling air flow by adjusting the Air flow to 85%.
APH TWO-STAGE HEATING
When using staged electric heat, cut jumper PJ4 on the control board.
APH THERMOSTAT WIRING
Use thermostat wiring diagrams provided with the thermostat when making these connections.
See Appendix for Blower Performance tables.
SUPERHEAT CAN BE DETERMINED AS FOLLOWS:
1. Read suction pressure. Determine Saturated Suction Temperature from tables or pressure gauge saturated temperature scale (R-410A).
2. Read suction line temperature.
3. Use the following formula:
SUPERHEAT = SUCTION LINE TEMP - SAT. SUCTION TEMP
See Appendix for Blower Performance Data tables.
12
Page 13
p
SATURATED SUCTION PRESSURE
p
TEMPERATURE CHART
Suction
Pressure
Saturated Suction
Tem
erature °F
PSIG R-410A
50 1 52 3 54 4 56 6 58 7 60 8 62 10 64 11 66 13 68 14 70 15 72 16 71 17 76 19 78 20 80 21
SUBCOOLING = SAT. LIQUID TEMP. - LIQUID LINE TEMP.
SATURATED LIQUID PRESSURE
TEMPERATURE CHART
Liquid
Pressure
Saturated Liquid
Tem
erature °F
PSIG R-410A
200 70 210 73 220 76 225 78 235 80 245 83 255 85 265 88 275 90 285 92 295 95 305 97 325 101 355 108 375 112 405 118
EXPANSION VALVE (TXV) SYSTEM
Single Speed Application (*PH1524/43 and GPC15)
1. Purge gauge lines. Connect service gauge manifold to access fittings. Run system at least 10 minutes to allow pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near liquid line access fitting with adequate contact and insulate for best possible reading.
3. Check subcooling and superheat. Systems with TXV application should have a subcooling of 10 + 2°F and superheat of 15 to 18ºF.
a. If subcooling and superheat are low, adjust TXV to 15
- 18ºF then check subcooling.
b. If subcooling is low and superheat is high, add charge
to raise subcooling to 10 ± 2ºF then check superheat.
c. If subcooling and superheat are high, adjust TXV valve
to 15 - 18ºF then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV
valve to 15 to 18ºF superheat and remove charge to lower the subcooling to 10 ± 2ºF.
The TXV should NOT be adjusted at light load conditions 55º to 60ºF, under such conditions only the subcooling can be evaluated. This is because suction pressure is dependent on indoor air flow, and wet bulb temperature.
NOTE: Do NOT adjust charge based on suction pressure unless there is a gross undercharge.
4. Disconnect manifold set. Installation is complete.
Two Speed Application (*PH1549/60)
Run the unit on low stage cooling for 10 minutes until refrigerant pressures stabilize. Follow the guidelines and methods below to check unit operation and ensure that the refrigerant charge is within limits. Charge the unit on low stage.
1. Purge gauge lines. Connect service gauge manifold to access fittings. Run system at least 10 minutes to allow pressure to stabilize.
2. Temporarily install thermometer on liquid (small) line near liquid line access fitting with adequate contact and insulate for best possible reading.
3. Check subcooling and superheat. Two stage systems running on low stage with TXV application should have a subcooling of 5 to 7 ºF and superheat of 15 to 18ºF.
a. If subcooling and superheat are low, adjust TXV to 15
to 18ºF superheat, then check subcooling. NOTE: To adjust superheat, turn the valve stem
clockwise to increase and counter clockwise to decrease.
b. If subcooling is low and superheat is high, add charge
to raise subcooling to 5 to 7 ºF then check superheat.
c. If subcooling and superheat are high, adjust TXV valve
to 15 to 18ºF superheat, then check subcooling.
d. If subcooling is high and superheat is low, adjust TXV
valve to 15 to 18ºF superheat and remove charge to lower the subcooling to 5 to 7 ºF.
NOTE: Do NOT adjust the charge based on suction pressure unless there is a gross undercharge.
4. Disconnect manifold set, installation is complete.
Refrigerant Charge Check (Units with Fixed Orifice Devices)
After completing airflow measurements and adjustments the unit’s refrigerant charge must be checked. The unit comes factory charged, but this charge is based on 325 CFM per ton and minimum ESP per ARI test conditions (generally between .15 -.25 ESP). When air quantity or ESP is different than above, the refrigerant charge must be adjusted to the proper amount. All package units with fixed orifice devices are charged using the super heat method at the compressor suction line.
For charging in the warmer months, 8 ± 3ºF superheat at the compressor is required at conditions 95ºF outdoor ambient (dry bulb temperature), 80ºF dry bulb / 67ºF wet bulb indoor ambient, approximately 50% humidity. This superheat varies when conditions vary from the conditions described.
13
Page 14
After superheat is adjusted it is recommended to check unit sub-cooling at the condenser coil liquid line out. In most operating conditions 10 - 15ºF of sub-cooling is adequate.
HEAT PUMP - HEATING CYCLE
The proper method of charging a heat pump in the heat mode is by weighing the charge according to the total charge listed on the rating plate.
ELECTRICAL ADJUSTMENTS
This series of electric cooling and, heat pump package equipment is designed to accept a field installed electric heat kit. The unit is equipped to easily install the HKR Series Electric Heat Kit. Full Installation Instructions are included in this kit. Please use this document for guidance in field equipping the package unit with electric heat.
Choose the heat kit that fits the application for the specific installation. Permanently mark the unit’s nameplate with the model being installed. High and low voltage connections are detailed in the heat kit instructions.
Indoor Blower motor speed tap selection may need to be modified to accommodate normal continuous operation to prevent a nuisance trip. See tables below.
EL EC T R I C H EA T kW
ELECTRIC HEAT kW
5
MODE L
GPC1524M41 3 3 3 x x GPC1530M41 3 3 3 3 x
GPC1536M41 3 3 3 3 x GPC1542M41 3 3 3 3 x GPC1548M41 3 3 3 3 3
All mod el s are fac tory shipped at T3 speed
8 10 1 5
20
MODEL
GPH1524M41 GPH1530M41 GPH1536M41 3333x GPH1543M41 GPH1549M41 GPH1560M41 33333
All models are factory shippe d at T3 speed
5 8 10 15 20
333xx 3333x
3333x 33333
MODEL
APH1524M41 APH1530M41
APH1536M41 APH1543M41 APH1549M41
APH1560M41
ELEC TR IC H EA T k W
5 8 10 15 20
XXX XXXX
XXXX XXXX
XXXXX XXXXX
14
Page 15
MAINTENANCE
The Self Contained Package Air Conditioner and Heat Pump should operate for many years without excessive service calls if the unit is installed properly. However it is recommended that the homeowner inspect the unit before a seasonal start up. The coils should be free of debris so adequate air flow is achieved. The return and supply registers should be free of any obstructions. The filters should be cleaned or replaced. These few steps will help to keep the product up time to a maximum. The Troubleshooting Chart (see Appendix) should help in identifying problems if the unit does not operate properly.
Refer to Blower Performance section in the Appendix - Higher
air flow lowers temperature rise.
Lower air flow raises temperature rise.
SERVICE
THE FOLLOWING INFORMA TION IS FOR USE BY
QUALIFIED SERVICE AGENCY ONLY : OTHERS SHOULD
NOT A TTEMPT TO SERVICE THIS EQUIPMENT .
COMMON CAUSES OF UNSATISFACTORY OPERATION OF HEAT PUMP ON THE HEATING CYCLE
INADEQUATE AIR VOLUME THROUGH INDOOR COIL
When a heat pump is in the heating cycle, the indoor coil is func­tioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure, and high pressure cut out.
OUTSIDE AIR INTO RETURN DUCT
Do not introduce cold outside air into the return duct of a heat pump installation. Do not allow air entering the indoor coil to drop below 65°F. Air below this temperature will cause low discharge pressure, thus low suction pressure, and excessive defrost cy­cling resulting in low heating output. It may also cause false de­frosting.
UNDERCHARGE
An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost accumulation on the outdoor coil.
POOR “TERMINATING” SENSOR CONTACT
The unit’s defrost terminating sensor must make good thermal contact with the outdoor coil tubing. Poor contact may not termi­nate the unit’s defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure.
MALFUNCTIONING REVERSING VALVE - THIS MAY BE DUE TO:
1. Solenoid not energized - In order to determine if the solenoid is energized, touch the nut that holds the solenoid cover in place with a screwdriver. If the nut magnetically holds the screwdriver, the solenoid is energized and the unit is in the cooling cycle.
2. No voltage at unit’s solenoid - Check unit voltage. If no voltage, check wiring circuit.
3. Valve will not shif t:
a. Undercharged - check for leaks; b. Valve Body Damaged - Replace valve; c. Unit Properly Charged - If it is on the heating cycle,
raise the discharge pressure by restricting air flow through the indoor coil. If the valve does not shift, tap it
lightly on both ends with a screwdriver handle. DO NOT T AP THE V ALVE BODY. If the unit is on the cooling cycle,
raise the discharge pressure by restricting air flow through the outdoor coil. If the valve does not shift after the above attempts, cut the unit off and wait until the discharge and suction pressure equalize, and repeat above steps. If the valve does not shift, replace it.
15
Page 16
APPENDIX
16
Page 17
TROUBLESHOOTING CHART
g
g
g
g
g
HIGH VOLT AGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
SYMPTOM
High head - low suction a. Restriction in liquid line or
High head - high or normal suction a. In Cooling: Dirty condenser coil a. Clean coil
Low head - high suction
Unit will not r un
Condenser f an runs, compressor doesn't
Low suction - cool compressor a. In Cooling: Low indoor airflow a. Iced evaporator coil In Heating: Dirty outdoor coil, de fective
Com pressor short cycle s
Registers sweat Low airflow
High suction pressure
Insufficient cooling
TXV not functioning
In Heating: Dirty filter, Dirty indoor coil b. Overchar c. In Coolin
c. In Heating: Indoor blower not running c. Repair or Replace a. Incorrect TXV. a. Replace with correct TXV b. Defective compressor valves b. Replace compressor c. TXV not functioning properly c. Check for debris in TXV or deformed TXV.
d. Incorrect TXV setting d. Check Super Heat a. Power off or loose electrical connection a. Check for unit voltage at contactor in unit
b. Thermostat out of calibration set too high b. Reset c. Defective contactor c. Check for 24 volts at contactor coil replace if
d. Blown fuses or tripped breaker d. Replace fuse or reset breaker e. Transformer defective
f. High or low pressure control open
(Optional)
g. Compressor overload contacts open g. Replace compressor
a. Loose connection a. Check for unit voltage at compressor check &
b. Compressor stuck, grounded or open
winding open internal overload c. Low voltage connection c. At compressor terminals, voltage must be within
d. Capacitor weak, open, or shorted d. Check capacitor. If defective, replace.
defrost thermostat, defective defrost
control board, outdoor fan not runnin
refrigerant charge. b. Low airflow b. Check - should be approximately 400 CFM per
c. Low refrigerant charge c. Properly charge unit d. Operatin
outdoor temperature a. Defective overload protector a. Replace - check for correct voltage b. Unit cycling on low pressure control b. Check refrigerant charge and / or airflow
c. High pressure switch cuts out c. Check airflow (indoor & outdoor),
a. a. Increase speed of blower or reduce restriction
a. Excessive load a. Recheck load calculation b. Defective compressor b. Replace c. Reversing valve not seating properly. c. Replace a. Improperly sized unit a. Recalculate load b. Improper airflow b. Check - should be approximately 400 CFM per ton
ed b. Correct System charge
: Condenser fan not runnin
unit in cooling mode below 65°F
a. Remove or replace with proper size TXV.
Remove debris or replace TXV.
contacts are open
e.
Check wiring - replace transformer
f. Check high pressure control or check unit
charge High pressure control opens at 610 psig Low pressure control opens at 22 psig
NOTE: Wait at least 2 hours for overload to reset
t ighten all conn ec tions
b. Wait at least 2 hours for overload to reset If still
open, replace the compressor.
10 % of nameplate volts when unit is operating
Increase speed of blower or reduce restriction ­replace air filters
, low
ton, dirty air filters, all duct outlets open
d. Install or check low ambient control, should be
open below 65°F outdoor temperature
check expansio n device
replace air filters
REMEDYPOSS IBLE CAUSE
c. Incorrect refrigerant charge. c. Charge per procedure attached to unit service
panel
d. Incorrect voltage d. At compressor terminals, voltage must be within
10% of nameplate volts when unit is operating
17
Page 18
GPH15 BLOWER PERFORMANCE DATA
Model Spe ed Volts
GPH 1524M41*
T1 (G)
T2 / T3
(W2)
T4 / T5 (Y)
230
230
230
T1 (G) 230
T2 / T3
(W2)
GPH1530M41*
T4 / T5 (Y) 230
T1 (G)
T2 / T3
(W2)
GPH1536M41*
T4 / T5 (Y)
230
230
230
230
E. S.P (In. of H
O)
2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 882 808 727 649 545 --- --- - --
WATTS 82 86 92 102 108 --- -- - ---
CFM 933 873 810 733 637 584 --- ---
WATTS 93 103 109 120 126 135 --- ---
CFM 1058 1012 945 896 816 723 672 ---
WATTS 124 136 142 153 168 172 179 - --
CFM 893 824 752 665 575 --- --- ---
WATTS 87 95 101 111 115 --- --- ---
CFM 1132 1070 1011 959 889 827 733 669
WATTS 153 162 168 179 184 195 206 208
CFM 1287 1236 1165 1123 1066 1012 958 857
WATTS 211 217 228 239 244 255 265 272
CFM 852 764 711 592 545 --- --- ---
WATTS 80 82 86 95 99 --- -- - ---
CFM 1232 1190 1131 1082 1023 966 889 819
WATTS 202 214 221 229 235 246 258 264
CFM 1267 1213 1162 1120 1058 1009 932 841
WATTS 218 226 236 245 247 260 272 275
NOTES:
• Dat a sh ow n is dry coil . Wet coil pres su r e drop is approxi mately 0.1" H
0.2" H
0, for three- row indoor coil ; and 0.3" H20, for four-row indoor coil.
2
2
• Data shown does not incl ude filter pressure drop, approximately 0.08" H
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON .
• Reduce airflow by 2% for 208-volt operation.
0 , fo r two-row i ndoor c oi l;
0.
2
18
Page 19
GPH15 BLOWER PERFORMANCE DATA
Model Spe ed Volts
T1 (G) 23 0
GPH1543M41*
T2 (Y) / T3
(W2)
T4 / T5
(HS)
230
230
T1 (G) 23 0
T2 (Y) 23 0
T3 (W2) 2 30
GPH1549M41*
T4 (YHS)
T5
(W2HS)
230
230
E. S.P (In. of H
O)
2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 1199 1138 1085 1017 957 889 820 755
WA TTS 162 173 185 1 93 211 219 232 245
CFM 1359 1322 1262 1214 1165 1119 1080 1039
WA TTS 200 214 218 2 33 243 254 267 283
CFM 1598 1559 1525 1483 1441 1398 1353 1314
WATTS 332 343 360 365 384 385 404 414
CFM 1199 1138 1085 1017 957 889 820 755
WA TTS 162 173 185 1 93 211 219 232 245
CFM 1 418 1383 1349 1312 1275 1228 1178 1141
WATTS 242 258 273 282 299 308 320 338
CFM 1799 1745 1698 1658 1610 1560 1522 1450
WA TTS 480 493 508 5 21 531 545 550 547
CFM 1799 1745 1698 1658 1610 1560 1522 1450
WA TTS 480 493 508 5 21 531 545 550 547
CFM 1 921 1865 1818 1780 1719 1667 1579 1483
WATTS 582 585 602 625 627 621 595 569
T1 (G)
230
CFM 1390 1325 1282 1223 1180 1134 1066 1011
WATTS 231 240 253 262 277 292 300 316
CFM 1900 1843 1801 1762 1723 1672 1577 1482
WATTS 543 559 569 583 600 603 577 554
CFM 2094 2039 1981 1907 1819 1731 1628 1497
GPH1560M41*
T2 / T3
(W2)
T4 / T5 (Y)
230
230
WATTS 724 727 720 701 671 653 611 569
NOTES:
• Dat a sh ow n is dry coil. Wet co i l pres su r e drop is approxi mately 0.1" H20 , fo r two-r ow in door c oi l ; 0, for three- row indoor coil ; and 0.3" H20, for four-row indoor coil.
0.2" H
2
• Data shown does not include filter pressure drop, approximately 0.08" H
0.
2
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM /TON.
• Reduce airflow by 2% for 208-volt operat i on.
19
Page 20
GPC15 BLOWER PERFORMANCE DATA
Model Speed Volts
230
230
230
GPC1524M41*
T1 (G)
T2 / T3
T4 / T5
T1 (G) 230
T2 / T3 230
GPC 1530M41*
T4 / T5 230
230
230
230
GPC1536M41*
T1 (G)
T2 / T3
T4 / T5
T1 (G) 230
T2 / T3 230
GPC1542M41*
T4 / T5 230
T1 (G)
T2 / T3
GPC 1548M41*
T4 / T5
230
230
230
E.S.P (In. of H
O)
2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 882 808 727 649 545 --- --- ---
WATTS 82 86 92 102 108 --- --- ---
CFM 933 873 810 733 637 584 --- ---
WATTS 93 103 109 120 126 135 --- ---
CFM 1058 1012 945 896 816 723 672 ---
WATTS 124 136 142 153 168 172 179 ---
CFM 893 824 752 665 575 --- --- ---
WATTS 87 95 101 111 115 --- --- ---
CFM 1132 1070 1011 959 889 827 733 669
WATTS 153 162 168 179 184 195 206 208
CFM 1287 1236 1165 1123 1066 1012 958 857
WATTS 211 217 228 239 244 255 265 272
CFM 852 764 711 592 545 --- --- ---
WATTS8082869599---------
CFM 1232 1190 1131 1082 1023 966 889 819
WATTS 202 214 221 229 235 246 258 264
CFM 1267 1213 1162 1120 1058 1009 932 841
WATTS 218 226 236 245 247 260 272 275
CFM 1123 1070 1025 984 942 894 839 774
Watts 162 170 182 193 204 216 229 242
CFM 1437 1390 1354 1318 1281 1243 1204 1165
Watts 310 317 331 342 355 366 377 389
CFM 1528 1490 1450 1410 1383 1348 1312 1267
Watts 372 379 391 403 416 427 439 451
CFM 1199 1138 1085 1017 957 889 820 755
WATTS 162 173 185 193 211 219 232 245
CFM 1799 1745 1698 1658 1610 1560 1522 1450
WATTS 480 493 508 521 531 545 550 547
CFM 1921 1865 1818 1780 1719 1667 1579 1483
WATTS 582 585 602 625 627 621 595 569
NOTES:
• Data shown is dry coil. Wet c o il pressure drop is approximately 0.1" H20 , fo r two-r ow i ndoor c oi l ;
0.2" H
0, for three- row indoor coil ; and 0.3" H20, for four-row ind oor coil.
2
• Dat a sh ow n do es not include fi l ter pres sure d r op, app r ox ima tely 0.08" H
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON . See Repair Parts list.
• Reduce airflow by 2% for 208-volt operatio n.
20
0.
2
Page 21
APH15 BLOWER PERFORMANCE DATA
APH1530 M41APH1524M41
Cooling/HP
Speed
D Minus 630 D Minus 630 D Minus 720 D Minus 720 D Normal 700 D Normal 700 D Normal 800 D Normal 800
D Plus770 D Plus770 D Plus880 D Plus880 C Minus 743 C Minus 743 C Minus 900 C Minus 900 C Normal 825 C Normal 825 C Normal 1,000 C Normal 1,000 C Plus 908 C Plus 908 C Plus 1,100 C Plus 1,100 B Minus 855 B Minus 855 B Minus 990 B Minus 990 B Normal 950 B Normal 950 B Normal 1,100 B Normal 1,100 B Plus 1,045 B Plus 1,045 B Plus 1,210 B Plus 1,210 A Minus 945 A Minus 945 A Minus 1,125 A Minus 1,125 A Normal1,050 A Normal1,050 A Normal1,250 A Normal1,250 A Plus 1,155 A Plus 1,155 A Plus 1,375 A Plus 1,375
* @ 0.1 - 0.5 ESP * @ 0.1 - 0.5 ESP
Cooling/HP
Speed
D Minus 720 D Minus 720 D Minus 1,103 D Minus 1,103 D Normal 800 D Normal 800 D Normal 1,225 D Normal 1,225 D Plus 880 D Plus 880 D Plus*** 1,348 D Plus 1,348 C Minus 900 C Minus 900 C Minus** 1,260 C Minus** 1,260 C Normal1,000 C Normal1,000 C Normal1,400 C Normal1,400 C Plus 1,100 C Plus 1,100 C Plus 1,540 C Plus 1,540 B Minus 990 B Minus 990 B Minus 1,530 B Minus 1,530 B Normal1,100 B Normal1,100 B Normal1,700 B Normal1,700 B Plus 1,210 B Plus 1,210 B Plus 1,870 B Plus 1,870 A Minus 1,125 A Minus 1,125 A Minus 1,620 A Minus 1,620 A Normal1,250 A Normal1,250 A Normal1,800 A Normal1,800 A Plus 1,375 A Plus 1,375 A Plus 1,980 A Plus*** 1,980
* @ 0.1 - 0.5 ESP * @ 0.1 - 0.5 ESP
Adjust
Tap
Adjust
Tap
CFM*
APH1536M41
CFM*
Electric
Heat
Electric
Heat
Adjust
Tap
Adjust
Tap
CFM*
CFM*
Cooling/HP
Speed
Cooling/HP
Speed
** DENO TES FACTO RY SETTING FOR APH1543M4 1
*** DENOTES FA CTORY SETTING FOR APH1549M41
Adjust
Tap
APH1543M41 APH1549M41
Adjust
Tap
CFM *
CFM *
Electric
Heat
Electric
Heat
Adjust
Tap
Adjust
Tap
CFM*
CFM*
APH1560M41
Cooling/HP
Speed
D Minus 1,260 D Minus 1,260 D Normal1,400 D Normal1,400 D Plus1,540 D Plus1,540 C Minus 1,440 C Minus 1,440 C Normal1,600 C Normal1,600 C Plus1,760 C Plus1,760 B Minus 1,620 B Minus 1,620 B Normal1,800 B Normal1,800 B Plus1,980 B Plus1,980 A Minus 1,800 A Minus 1,800 A Normal2,000 A Normal2,000 A Plus2,200 A Plus2,200
* @ 0.1 - 0.5 ESP
Adjust
Tap
CFM*
Electric
Heat
Adjust
Tap
CFM*
21
Page 22
APH15 CFM OUTPUT AND DIP SWITCH SETTINGS
CFM Output for DIP Switch Combinations 1-2
(Electric Heat)
MODEL
APH1524
APH1530
APH1536
APH1543
APH1549
APH1560
(F)
Factory Setting
SPE ED
TAP
SWITCH1SWITCH2 ELECTRIC
A B
C D A B C D A B C D A B C D A B C D A B C D
Off Off On Off 950 Off On 825 On On 700 Off Off On Off 110 0
Off On 1000 On On 800 Off Off On Off 110 0 Off On 1000 On On 800 Off Off 1800
On Off 170 0 Off On On On 1225 Off Off On Off 170 0 Off On 1400 On On 1225 Off Off On Off 180 0 Off On 1600 On On 1400
HE AT (CFM)
1050
1250
1250
1400
1800
2000
(F)
(F)
CFM Output for DIP Switch Combinations 5-6
(Cooling/Heating).
MODEL
APH1524
(F)
APH1530
(F)
APH1536
APH1543
(F)
APH1549
(F)
APH1560
(F)
Factory Setting
SPE ED
TAP
SWITCH5SWITCH6COOLING/HP
A B
C D A B C D A B C D A B C D A B C D A B C D
Off Off On Off 950 Off On 825 On On 700 Off Off On Off 110 0
Off On 1000 On On 800 Off Off On Off 110 0 Off On 1000 On On 800 Off Off 1800
On Off 170 0 Off On On On 1225 Off Off 1800 On Off 170 0 Off On 1400 On On Off Off On Off 180 0 Off On 1600 On On 1400
CFM
1050
1250
1250
1400
1225
2000
(F)
(F)
(F)
(F)
(F)
(F)
DIP Switch Settings for Single and Two-Stage
Thermostats
MODEL
APH15**
SWITCH3SWITCH
4
N/A ON Single Stage N/A OFF Two- Stage
THERMOSTAT
Adjustments Through Dip Switch Combinations
7-8
CFM
+10% On Off
Normal Off Off
-10% Off On
22
SWITCH7SWITCH
8
Page 23
THIS PAGE LEFT INTENTIONALLY BLANK
23
Page 24
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com www.amana-hac.com
Goodman Manufacturing Company , L.P.
© 2010 Goodman Manufacturing Company, L.P.
24
Loading...