Goodman LPM-07 Installation Manual

Page 1
LPM-07 NATURAL GAS TO LP GAS CONVERSION KIT
INSTALLATION INSTRUCTIONS
ATTENTION INSTALLING PERSONNEL
As a professional installer, you have an obligation to know the product better than the customer. This includes all safety precautions and related items. Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair, it is possible to place yourself in a position which is more hazardous than when the unit is in operation. Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use. Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specic good safety
practices...follow them. The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a
direct conict between existing practices and the content of
this manual, the precautions listed here take precedence.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION
DESCRIPTION
This natural gas to L.P. gas conversion kit allows the 36G22 [B1282628, 36J22 (0151M00037)] and VR-8215 (0151M00013) series gas valves to be used on L.P. gas applications. This conversion kit is for use on all single stage maximum regulation valves.
Required Tools for Kit Installation
2 Pipe wrenches, properly sized to accommodate the
gas piping and connectors
1 7/16” box wrench or socket wrench
1 1/4” nut driver
1 1/4” regular (atblade) screwdriver
1 Manometers to read inlet & outlet pressure of the gas value
(minimum range: 0” - 20” W.C.)
1 3/16” Allen wrench
2 1/8” NPT hose barb
Pipe joint compound or pipe thread tape that is approved for use with L.P. gas
Gas leak detection solution, like a soap and water solution. Always wipe the solution from the joints when testing is complete.
WARNING
To avoid The possibiliTy of explosion or fire, never use a
maTch or open flame To TesT for leaks.
Prior to performing this conversion refer to the National Fuel Gas Code (ANSI Z223.1) or in Canada, CAN/CGA­B149.2-M91 to ensure that the installation is in compliance with those and all local codes.
PLEASE READ AND FOLLOW THESE INSTRUCTIONS CAREFULLY.
WARNING
To avoid The possibiliTy of explosion or fire, never use a
maTch or open flame To TesT for leaks.
WARNING
The manufacTurer will noT be responsible for any
injury or properTy damage arising from improper service or service procedures. This l.p. (liquid peTroleum) conversion kiT musT be insTalled by a qualified service person oragency in accordance wiTh The manufacTurers insTrucTions and all applicable codes and requiremenTs of The auThoriTy having jurisdicTion.
failure To follow These insTrucTions expliciTly may cause
a fire, explosion or The producTion of carbon monoxide, which can cause properTy damage, personal injury or deaTh.
if you insTall or perform service on This uniT, you assume
responsibiliTy
may resulT. many jurisdicTions require a license To
which insTall
for any personal injury or properTy damage
or service heaTing and air condiTioning equipmenT.
KIT CONTENTS
Using the following parts list, ensure that all parts included in this list are present and in an undamaged condition.
Quantity Part Number Description
1 B10259108 Conversion Label
1 B1880007 Spring Kit for White-Rodgers
36G22 & 36J22 valves
1 0163M00078 Spring Kit for Honeywell
VR8215 Value
1 B40899125 1.25mm Burner Orice
1 IO-817 Installation Instructions
1 0151K00000S Pressure Check Kit Value
IO-817 01/2014
Page 2
CONTENTS
CARBON MONOXIDE POISONING HAZARD
B10259-216
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
Special Warning for Installation of Furnaces or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Important Information ......................................................... 2
Conversion Instructions - WR 36G22 or 36J22 Valves ...... 3
Conversion Instructions - HW VR8215 Valve ..................... 5
NOx Screen Removal ......................................................... 6
Non-Condensing Furnaces & Package Gas-Electric.......... 6
IMPORTANT INFORMATION
WARNING
To avoid personal injury, properTy damage or deaTh, due
To leaking gas, conTacT your propane supplier abouT insTalling a gas deTecTing warning device. iron oxide
(rusT) can reduce The level of odoranT in propane gas. a gas deTecTing device is The only reliable meThod To
deTecT a propane gas leak.
WARNING
“This conversion kiT shall be insTalled by a qualified service
agency in accordance wiTh The manufacTurers insTrucTions and all applicable codes and requiremenTs of The auThoriTy having jurisdicTion. if The informaTion in These insTrucTions is noT followed exacTly, a fire, explosion or producTion of carbon monoxide may resulT causing properTy damage, personal injury or loss of life. The qualified service agency is responsible for The proper insTallaTion of This kiT. The insTallaTion is noT proper and compleTe unTil The operaTion of The converTed appliance is checked as specified in The manufacTurers insTrucTions supplied wiTh The kiT.”
CAUTION
To avoid The risk of properTy damage, personal injury or
fire, shuT off gas supply firsT, Then disconnecT The elec- Trical supply before proceeding wiTh conversion.
BEFORE BEGINNING CONVERSION:
VALVE IDENTIFICATION
Before beginning conversion, the type valve you have
must be identied. Compare the gas valve presently on the
equipment to the drawing below to identify the correct valve you are working with. Page numbers for the instructions for that valve are below each drawing.
White-Rodgers 36G22 and 36J22
Instructions for these valves start on page 3.
Honeywell VR8215
Instructions for this valve start on page 5.
2
Page 3
WHITE-RODGERS 36G22 AND 36J22
CONVERSION INSTRUCTIONS
CAUTION
To prevenT unsaTisfacTory furnace operaTion, The
proper gas conversion kiT musT be used for The gas valve. use The whiTe-rodgers spring kiT only wiTh The
whiTe-rodgers gas valves.
NOTE: For low NOx models, see page 6 for NOx screens.
1. Turn off gas supply to the furnace.
2. Turn off the electrical power to the furnace.
3. Remove the furnace control access panel.
4. Separate the gas supply union and remove associated downstream piping.
NOTE: Always use a backup wrench when removing or
replacing piping to avoid any undue strains or rotation of controls.
5. Remove the wires from the gas valve.
6. Remove the 4 sheet metal screws that fasten the manifold/ gas valve assembly to the burner box.
7. Visually inspect orices for damage and drill size (marked
on face with 1.25mm) before installation. Using the 7/16”
wrench, remove all existing natural gas orices and re­place with the appropriate 1.25mm L.P. gas orices con­tained in this kit. Tighten the orices to prevent gas leaks, but do not overtighten. Retain the natural gas orices for
future reconversion.
8. Install water manometer using Valve Pressure Check Kit P/N 0151K00000S included with this kit. Using the includ­ed 3/32” hex wrench, rotate outlet pressure tap screw one revolution counterclockwise. Attach the included 5/16” hose to the inlet and outlet pressure boss of the valve. Hose should overlap boss 3/8”. Connect 5/16” side of in­cluded connector to the hose on the outlet boss. Connect 1/4” side of the connector to the manometer hose. The manometer must have a scale range of at least 0” to 20” of water column.
9. Using a at blade screwdriver, remove the regulator cover
screw.
10. Using a at blade screwdriver, remove plastic regulator
adjustment screw located beneath the cover screw.
11. Remove the natural gas regulator spring from the regulator sleeve.
12. Insert the kit (P/N B1880007, WR F92-0999) provided L.P. regulator spring into the regulator sleeve.
13. Replace the regulator adjustment screw.
14. Reinstall the manifold/gas valve assembly into the appli­ance. Rewire the gas valve.
15. Apply a liberal amount of pipe joint compound or pipe thread tape to the threads and reassemble the piping previously removed. NOTE: the pipe joint compound or pipe thread tape must be resistant to L.P. gas.
16. Turn on the gas supply and check for leaks.
WARNING
To avoid The possibiliTy of explosion or fire, never use a
maTch or open flame To TesT for leaks.
17. Turn on the electrical supply.
18. Adjust the room thermostat to allow for constant operation.
19. If you have the correct manifold pressure and the
burners do not light, there may be air trapped in the lines. Follow these instructions:
To check for air trapped in the supply line: Verify line
pressure is in the correct range. If manifold pressure is indicated during the ignition trial, the valve is opening and air may be in the line.
Units with hot surface ignitors: The valve will not open
until the ignitor is at the proper temperature (glowing brightly).
Units with spark ignition: The valve will open as soon
as the spark starts. If no manifold pressure is indicated during the trial for ignition, please return to step 13 to ensure the correct spring was used and to ensure the regulator adjustment is near the bottom of the adjustment range.
20. If gas inlet pressure falls outside the range of 11” and 13” W.C. after the unit has been in operation for 15 minutes, adjust the gas supply pressure (not manifold pressure), check piping size, etc., and/or consult with local utility.
NOTE: Any other gas-red equipment should be ON
before any adjustments are made.
21. Check manifold pressure. For propane gas, the manifold pressure must be between 9.7” and 10.3” W.C.
3
Page 4
22. Turn adjustment screw out (counterclockwise) to decrease pressure, turn in (clockwise) to increase
pressure. Only small variations in gas ow should be
made by means of the pressure regulator adjustment.
In no case should the nal manifold pressure vary more than plus or minus 0.3” water column from the specied nominal pressure. Any major changes in ow should be made by changing the size of the burner orices. The
measured input rate to the furnace must not exceed the
rating specied on the unit rating plate.
23. Reset all other appliances so they function normally.
24. Turn off gas and electrical supply to the furnace, remove the manometer hose from the pressure tap bosses, and tighten the inlet and outlet pressure tap screws using the 3/32” Allen wrench (clockwise 7 in-lb minimum).
25. If regulator adjustment screw (removed in step 11) is white, the gasket supplied with the kit must be installed on the regulator cover screw. The gasket is not required if the regulator adjustment screw is black.
26. Replace the regulator cover screw on the regulator sleeve.
27. Attach the kit provided WARNING label to the gas valve where it can be readily seen. Also attach the small round L.P. label to the top of the regulator cover screw.
28. Turn on the gas and electrical supply, energize the appliance and recheck for leaks.
29. Observe at least 3 ignition cycles to assure quick and smooth ignition and burner operation.
30. Reinstall the access panels.
36G22 and 36J22 Model
CAUTION
To avoid The risk of properTy damage, personal injury
or fire, shuT off gas supply firsT, Then disconnecT The elecTrical supply before proceeding wiTh conversion.
NOTE: Conversion instructions for the Honeywell VR8215 gas valve begin on the following page.
4
Page 5
HONEYWELL VR8215
CONVERSION INSTRUCTIONS
CAUTION
To prevenT unsaTisfacTory furnace operaTion, The proper
gas conversion kiT musT be used for The gas valve. use The honeywell spring kiT only wiTh The honeywell gas valve.
NOTE: For low NOx models, see page 6 for NOx screens.
1. Turn off gas supply to the furnace.
2. Turn off the electrical power to the furnace.
3. Remove the furnace control access panel.
4. Separate the gas supply union and remove associated downstream piping.
NOTE: Always use a backup wrench when removing or
replacing piping to avoid any undue strains or rotation of controls.
accompany the manometers into the 1/8” taped holes of the gas valve. Connect the manometers to the barbed
ttings.
10. Using a at blade screwdriver, remove the regulator cover
screw.
11. Using a at blade screwdriver, remove plastic regulator
adjustment screw located beneath the cover screw.
12. Remove the natural gas regulator spring from the regulator sleeve.
13. Insert the kit (P/N 0163M00078, Honeywell P/N 396221) provided L.P. regulator spring into the regulator sleeve.
14. Replace the natural gas regulator adjustment screw with the L.P. regulator adjustment screw included in the kit.
NOTE: The LP regulator should be adjusted near the bot-
tom of the adjustment range. DO NOT OVER-TIGHTEN.
15. Apply a liberal amount of pipe joint compound or pipe thread tape to the threads and reassemble the piping previously removed.
NOTE: the pipe joint compound or pipe thread tape must
be resistant to L.P. gas.
16. Turn on the gas supply and check for leaks.
WARNING
Honeywell VR8215
5. Remove the wires from the gas valve.
6. Remove the 4 sheet metal screws that fasten the manifold/ gas valve assembly to the burner box.
7. Visually inspect orices for damage and drill size (marked
on face with 1.25mm) before installation. Using the 7/16”
wrench, remove all existing natural gas orices and re­place with the appropriate 1.25mm L.P. gas orices con­tained in this kit. Tighten the orices to prevent gas leaks, but do not overtighten. Retain the natural gas orices for
future reconversion.
8. Reinstall the manifold/gas valve assembly into the appli­ance. Rewire the gas valve.
9. Remove both the inlet and outlet plugs on the gas valve,
using the 3/16” Allen wrench. Install the ttings which
To avoid The possibiliTy of explosion or fire, never use a
maTch or open flame To TesT for leaks.
17. Turn on the electrical supply.
18. Adjust the room thermostat to allow for constant operation.
19. To check for air trapped in the supply line: Verify line
pressure is in the correct range. If manifold pressure is indicated during the ignition trial, the valve is opening and air may be in the line.
Units with hot surface ignitors: The valve will not open
until the ignitor is at the proper temperature (glowing brightly).
Units with spark ignition: The valve will open as soon
as the spark starts. If no manifold pressure is indicated during the trial for ignition, please return to step 13 to ensure the correct spring was used and to ensure the regulator adjustment is near the bottom of the adjustment range.
20. If gas inlet pressure falls outside the range of 11” and 13” W.C. after the unit has been in operation for 15 minutes, adjust the gas supply pressure (not manifold pressure), check piping size, etc., and/or consult with local utility.
NOTE: Any other gas-red equipment should be ON
before any adjustments are made.
21. Check manifold pressure. For propane gas, the manifold pressure must be between 9.7” and 10.3” W.C.
5
Page 6
22. Turn adjustment screw out (counterclockwise) to decrease pressure, turn in (clockwise) to increase
pressure. Only small variations in gas ow should be
made by means of the pressure regulator adjustment.
In no case should the nal manifold pressure vary more than plus or minus 0.3” water column from the specied nominal pressure. Any major changes in ow should be made by changing the size of the burner orices. The
measured input rate to the furnace must not exceed the
rating specied on the unit rating plate.
23. Reset all other appliances so they function normally.
24. Turn off the gas and electrical supply to the appliance, remove the pressure taps at the gas valve, reinstall the plugs using pipe joint compound or tape.
WARNING
To avoid The possibiliTy of explosion or fire, never use a
maTch or open flame To TesT for leaks.
25. Replace the regulator cover screw on the regulator sleeve.
26. Attach the kit provided ATTENTION label to the gas valve where it can be readily seen.
27. Turn on the gas and electrical supply, energize the appliance and recheck for leaks.
28. Observe at least 3 ignition cycles to assure quick and smooth ignition and burner operation.
29. Reinstall the access panels.
NON-CONDENSING FURNACES
AND PACKAGE GAS-ELECTRIC
1. Remove the screws securing the burner box to the partition panel. Separate burner box from unit.
2. Remove the screw(s) securing the NOx screen retention plate and remove the plate.
3. Remove and discard NOx screens.
4. Reinstall the NOx screen retention plate and burner box.
Typical NOx Screen Removal
NOx SCREEN REMOVAL
WARNING
remove all meTal screens from The heaT exchanger Tubes
when using propane gas. failure To do so may cause properTy damage, personal injury or deaTh and will void warranTy coverage.
NOTE: To prevent premature heat exchanger failure, follow the instructions in the NON-CONDENSING FURNACES AND PACAKGE GAS-ELECTRIC section to remove all metal screen inserts from the entrance of heat exchanger tubes during propane conversions. Not all models will have metal screen inserts.
6
Page 7
THIS PAGE LEFT INTENTIONALLY BLANK
7
Page 8
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE
®
Quality Makes the Difference!
All of our systems are designed and manufactured with the same high quality standards regardless of size or
efciency. We have designed these units to signicantly reduce the most frequent causes of product failure. They
are simple to service and forgiving to operate. We use quality materials and components. Finally, every unit is run tested before it leaves the factory. That’s why we know. . .There’s No Better Quality.
Visit our website at www.daikincomfort.com, www.goodmanmfg.com or www.amana-hac.com for information on:
• Products
• Warranties
• Customer Services
• Parts
• Contractor Programs and Training
• Financing Options
5151 San Felipe, Suite 500, Houston, TX 77056
© 2014 Goodman Manufacturing Company, L.P.
is a trademark of Maytag Corporation and is used under license. All rights reserved.
8
Loading...