Goodman LPLP03 Installation Manual

Page 1
LPLP03
p
LOW PRESSURE PROPANE KIT
INSTALLATION INSTRUCTIONS
Description
This kit is designed for gas-fired units converted to propane gas use. The Propane Low Pressure (LPLP03) Kit monitors the gas line pressure with a pressure switch and disables the unit gas valve if the line pressure drops below acceptable lev­els.
As a professional installer you have an obligation to know the product better than the customer. This includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
Fie l d Suppl ied
1 1/2" x 1-1 / 2" Nippl e 11/2" Tee 1 90 Degree S treet E l b ow
1
NOTE:
installations. See figures inside this IO for application needs.
1/2" P i pe (length dependent on model and applic ation)
Field supplied parts are not required for all
1 Propane Low Pressure Switch
1 1/8" Close Nipple 1 1/ 8" Te e Pi pe 1 1/2" x 1/ 8" Bushing
1 Sho r t Singl e-Stage H arness 1 Long S i ngle - Stage Harness 1 Long Jum per Wire 1 Two-Stag e Harness 1 Modulating Wire Harness 1 Propane Low Pressure Kit Label 1Wiring Diagram
1 1
IO-775C
August 2014
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION
Switch to Gas Valve Piping
Low Pressure Switch Wiring
Honeywell t o White-Ro dgers Wire Harness Ada
White-Rodgers to Honeywell Wire Harness Adaptor
tor
Figure 1
Page 2
CONTENTS
Important Information.......................................................... 2
Models Using White-Rodgers 36F & 36E Gas V alves with 1/8” NPT
Inlet Pressure Port ............................................................. 3
White-Rodgers 36F & 36E V alves
Right Facing Gas Inlet............................................. 3
White-Rodgers 36F & 36E V alves
Left Facing Gas Inlet............................................... 4
White-Rodgers 36G/36J V alve
Right Facing Gas Inlet (Left Facing Similar) ............ 4
Honeywell VR82 and VR9205Q Valves
or VR9205R Modulating V alve on 90%+ models ..... 4
80% Models Using Honeywell VR82, VR92
or White-Rodgers 36G/36J gas valves...................... 4
Honeywell VR82 or VR92 V alve on 80% models ..... 5
LP Low Pressure Switch Wiring
(Single-Stage Models) ............................................. 5
LP Low Pressure Switch Wiring
(T wo-Stage Models White-Rodgers Gas V alve
and Wire Harness Connection) ............................... 5
LP Low Pressure Switch Wiring
(Two-S tage Models with White-Rodgers Gas Valve
with Honeywell Wire Harness Connection) .................. 6
90% Models Using Honeywell VR82, VR9205Q V alves or
VR9205R Modulating V alve or White-Rodgers 36G ..... 6
Short 90% Models Using Honeywell VR82, VR9205Q
V alves or VR9205R Modulating Valve or
White-Rodgers 36J V alve ............................................ 6
Troubleshooting.................................................................. 8
IMPORTANT INFORMA TION
This kit provides control over the unit gas valve by routing the gas valve wiring through the supplied pressure switch. To en­able proper fit-up, the pressure switch kit must be installed before connecting the gas supply line to the gas valve. For new unit installations, the kit hardware may be fitted to the gas valve while the gas manifold is removed for LP gas orifice conversion. For existing installations, the gas valve line must be disconnected from the gas valve to allow fitting of kit hard­ware. Refer to Figures 2, 3, 4, 5 or 6 for a view of kit hardware as installed in unit. Before proceeding, shut off gas supply
at manual shutoff and turn off power to unit.
Contact a local propane gas supplier
about installing a gas detecting warning device.
2
Page 3
NOTE: T o ensure proper operation, install, operate and main- tain the unit in accordance with these installation instruc­tions, all local building codes and ordinances. In their ab­sence, follow the latest edition of the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or CAN/CSA B149.1 Installa­tion Codes.
MODELS USING WHITE-RODGERS 36F & 36E GAS V ALVES WITH 1/8” NPT INLET
PRESSURE PORT
(Alternate method on page 4 may also be used.) NOTE: All threaded connections must be sealed with Teflon
tape or pipe dope. Pipe sealant must be approved for use with propane gas.
1. Remove plug from the gas valve inlet pressure tap port. Save plug.
2. Install the supplied close nipple into the open inlet pres­sure tap port.
3. Thread the provided tee onto free end of the nipple. Orient the tee as shown in figure(s).
NOTE: On some models, tee orientation depends on which side the gas supply line enters.
4. Install pressure switch into the tee.
5. Temporarily fit a field-supplied pressure tap into the re­maining leg of the tee. This pressure tap will allow gas supply line pressure measurement during installation check out.
6. Attach the pressure tap to a manometer or pressure mea­surement device before opening gas supply.
7. With gas valve and manifold installed in the unit, connect gas supply line to the gas valve.
8. Perform installation check out procedure (piping leak check, line pressure measurement, manifold pressure adjustment, etc.) as outlined in the unit installation instructions.
9. Turn OFF gas supply .
10. Remove field-supplied pressure tap from tee and insert plug removed in step 1.
1 1. Turn ON gas supply and leak check inserted plug.
12. Turn OFF power to furnace. Connect jumper harness be­tween LPLP switch and gas valve and gas valve wiring as indicated in Figure 7 (single-stage models) or Figures 6, 8 or 9 (two-stage models).
13. Turn ON power to furnace. V erify proper unit operation.
14. Remove backing from kit label. Fold label around jumper harness wire to indicate kit installation.
15. Adhere kit wiring diagram adjacent to existing unit wiring diagram.
IMPORTANT NOTE: Secure all wires to avoid their contact with any hot surfaces or moving parts.
White-Rodgers 36F Valve White-Rodgers 36E Valve
Right Facing Gas Inlet
Figure 2
3
Page 4
White-Rodgers 36F V al ve White-Rodgers 36E V alv e
Left Facing Gas Inlet
Figure 3
Honeywell VR82, V 9205Q Valves or
VR9205R (Mo dulating ) Valve
Used on 90%+ Models
UPFLOW
R
COUNTERFLOW
White-Rodgers 36G/36J Valve
Right Facing Gas Inlet
(Left Facing Similar)
*If there is interference with the Pressure Switch position,
rotate Pressure Switch 90 degrees.
Figure 4
Figure 5
80% MODELS USING HONEYWELL VR82, VR9205Q OR WHITE-RODGERS 36G/36J
GAS VALVES
NOTE: All threaded connections must be sealed with Teflon tape or pipe dope. Pipe sealant must be approved for use with propane gas.
1. Install field-supplied 90 degree street elbow into gas valve.
2. Install field-supplied 1/2” x length required to exit wrapper into 90 degree street elbow for left side gas outlet. Install field supplied 1/2” x length required to exit wrapper on the right side of the gas outlet (See Figure 6).
3. Place 1/2” tee on pipe.
4. With gas valve and manifold installed in the unit, connect the gas supply line into 1/2” tee as required (typically op­posite of gas valve side).
5. Install 1/2” x 1/8" bushing into 1/2” tee in the remaining opening.
4
Page 5
6. Install pressure switch in bushing. Pressure switch will be installed outside of the wrapper (see Figure 6.)
NOTE: Ensure that the switch is upright in all applica­tions.
7. Perform installation check out procedure (piping leak check, line pressure measurement, manifold pressure adjustment, etc.) as outlined in the unit installation instructions.
8. Turn OFF gas supply .
9. Turn OFF power to furnace. Connect jumper harness be­tween LPLP switch and gas valve and gas valve wiring as indicated in Figure 7 (single-stage models - some models may require the use of long single-stage harness) or Fig­ures 8-1 1 (two-stage models). Some two-stage models may require the use of long jumper wires to accommodate con­nection of the switch. (2nd long jumper wire can be taken from long single stage harness.)
NOTE: Do not run wires through the gas pipe opening if gas piping is present. Pipe could easily cause damage to the wires.
10. Turn ON power to furnace. V erify proper unit operation.
1 1. Remove backing from kit label. Fold label around jumper
harness wire to indicate kit installation.
12. Adhere kit wiring diagram adjacent to existing unit wiring diagram.
IMPORTANT NOTE: Secure all wires to avoid their contact with any hot surfaces or moving parts.
Honeywell VR82 or Valves
Used on 80% Models
V 9205QR
Honeywell or White-Rodgers Gas Valves
LP Low Pressure Switch Wiring
Single-Stage Models
Gas Valve Wiring
from
Furnace Wiring
Harness
Gas Valve
Brown or Gray Wire
Single-Stage
Jumper Ha rness
White-Rodgers Valve Shown
Figure 7
White-Rodgers Gas Valve
&
Wiring Harness Connection
LP Low Pressure Switch Wiring
Two-Stage Models
Gas Valve Wiring
from
Furnace Wiring
Harness
Kit
Label
LP Low
Pressure
Switch
Figure 6
Two-Stage
Jumper Harness
Gas Valve
Figure 8
Kit
Label
LP Low
Pressure
Switch
5
Page 6
White-Rodgers Gas V alve
With Honeywell
Wiring Harness Connection
LP Low Pressure Switch Wiring
Two-Stage Models
Honeywell Gas Valv e VR9205Q
With White-Rodgers
Wiring Harness Connection
LP Low Pressure Switch Wiring
Two-Stage Models
Two-Stage
Jumper Harness
Gas Valve
Gas Valve Wiring
from
Furnace Wiring
Harness
Kit
Label
Figure 9
Honeywell Gas Valv e VR920 5Q
And
Wiring Harness Connection
LP Low Pressure Switch Wiring
Two-Stage Models
LP Low
Pressure
Switch
Two-Stage
Jumper Harness
Gas Valve Wiring
Gas Valve
from
Furnace Wiring
Harness
Kit
Label
Figure 11
LP Low
Pressure
Switch
Two-Stage
Jumper Harness
Gas Valve
Gas Valve Wiring
from
Furnace Wiring
Harness
Kit
Label
Figure 10
LP Low
Pressure
Switch
6
Page 7
SHORT 90 FURNACES USING VR82, VR92 and 36J GAS VALVES
NOTE: All threaded connections must be sealed with Teflon tape or pipe dope. Pipe sealant must be approved for use with propane gas.
Gas plumbed out the r ight side of the furnace
Gas Valve
X
Figure 13
1. Install field-supplied ½” x length required to exit wrapper , when the inlet is on left side.
2. For installing the pressure switch, in case of a right side inlet, install field-supplied ½”x 1 ½” required for “C and D” size cabinet models. “B” cabinet models require a field supplied ½” x length sufficient enough to be clear from any interfer­ence from other components. The pressure switch can be installed within or outside the cabinet in case of right side in­let.
3. Place ½” tee on pipe.
4. With gas valve and manifold installed in the unit, connect the gas supply line into 1/2" tee as required (typically opposite of gas valve side).
5. Install ½” x 1/8" bushing into ½” tee in the remaining opening.
6. Install pressure switch in bushing (See Figure 13). NOTE: Ensure that the switch is upright in all applications.
7. Perform installation check out procedure (piping leak check, line pressure measurement, manifold pressure adjustment, etc.) as outlined in the unit installation instructions.
8. Turn OFF gas supply .
9. Turn OFF power to furnace. Connect jumper harness between LPLP switch and gas valve and gas valve wiring as indi­cated in Figure 7 (single-stage models - some models may require the use of long single-stage harness) or Figures 8-1 1 (two-stage models). Some two-stage models may require the use of long jumper wires to accommodate connection of the switch. (2nd long jumper wire can be taken from long single stage harness.)
NOTE: Do not run wires through the gas pipe opening if gas piping is present. Pipe could easily cause damage to the wires.
10. Turn ON power to furnace. V erify proper unit operation.
1 1. Remove backing from kit label. Fold label around jumper harness wire to indicate kit installation.
12. Adhere kit wiring diagram adjacent to existing unit wiring diagram. IMPORTANT NOTE: Secure all wires to avoid their contact with any hot surfaces or moving parts.
Gas plumbed out the l eft side of the furnace
Gas Valve
X
7
Page 8
®
TROUBLESHOOTING
If the furnace fails to light after installation of the LP low pressure switch kit, proceed as follows:
Remove jumper harness from gas valve and gas valve wiring. Reconnect furnace wiring harness to gas valve.
Problem does not involve the LP low pressure switc h.
With gas supply on, measure resistance between terminals of LP low pressure switch.
Are
switch contacts
closed?
Check jumper harness circuits fo r continuity.
NO
Reconnect LP low pressure switch jumper harness.
Check gas supply gas val ve wiring, etc.
NO NO
Is line
pressure above
9.0" w.c.?
Replace faulty LP low pressure switch.
Reconnect jumper harness.
Correct insufficient ga s line pressure problem.
Reconnect jumper harness.
Continuity
checks OK on
jumper harness?
NO
Jumper ha rness pro blem.
Reconnect jumper harness . Chec k jump er harness connections.
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE
Visit our website at www.daikincomfort.com, www.goodmanmfg.com or www.amana-hac.com for information on:
Products Parts Customer Services
Warranties Financing Options Contractor Programs and Training
Goodman Manufacturing Company, L.P.
5151 San Felipe, Suite 500, Houston, TX 77056
© 2012 - 2014 Goodman Manufacturing Company, L.P.
is a trademark of Maytag Corporation and is used under license. All rights reserved.
8
Loading...