The Daikin brand HKR electric heat kits are for
use with Daikin brand air handlers and modular
blowers. The HKS heat kits are designed for
use with packaged electric/heat pump units.
These versatile heat kits are designed for easy
installation in the field.
HKR / HKA / HKP / HKS
ELECTRIC HEAT KITS FOR AIR HANDLERS
AND PACKAGED ELECTRIC UNITS
Contents
DVPVC .................................... 3
DVPTC .................................... 4
ASPT ...................................... 6
ASUF ...................................... 8
ARPT ..................................... 9
ARUF .................................... 11
MBVC .................................. 13
MBR .................................... 14
DP13CM ............................... 15
DP14CH ................................ 16
DP13CH ................................ 17
DP15HH .............................. 18
DP14HH .............................. 19
DP13HM ............................... 20
DP13HH ............................... 21
Standard Features
• Sequencers for better temperature
control
• Multiple branch circuit capability
• Completely assembled and tested
• Control circuitry arranged to readily
permit staging
• Factory-installed circuit breakers available
on specific models (See Electrical Data)
• Fuse link secondary high-temperature
limit control
• Plug-in wiring harness for ease
of installation into air handler
• Rust-resistant nickel
chromium heat elements
• ETL Listed
* Complete warranty details available from your
local dealer or at www.daikincomfort.com.
SS-DHKRwww.daikincomfort.com4/14
Supercedes 3/14
P
UnitTypeRevisions
HKR
AirHandlers&PackagedUnits
EngineeringRevisions
HKA AirHandlers
HKP PackagedUnitsCircuitBreaker
NoneSingleor3PhaseKit;
PhaseNoCircuitBreaker
None SinglePhaseCSinglePhaseKitw/
3 ThreePhaseCircuitBreaker
Hea8ngCapacity@240Volts
5 4.75kW15 14.25to15.00kW
8 7.00kW20 19.00to19.60kW
10 9.50kW
HKS HeatKitforEngineeringRevisions
AirHandlers
A SinglePhase208V
XNocircuitbreakerB SinglePhase240V
CCircuitBreakerC SinglePhase208/240V
D ThreePhase208V
E ThreePhase240V
03 3.0kWF ThreePhase208/240V
05 4.5kWG ThreePhase460V
06 6.0kW
08 8.0kW
10 9.6kWC CCabinet
15 14.4kWD DCabinet
19 19.2k@wth150Flimit AllCabinetSizes
20
19.2kWwith170Flimit
25 25.0kW
RODUCT SPECIFICATIONS
NOMENCLATURE
HKR*05
1234,511
*A
HEATINGKW CORRECTION FACTOR
Supply Voltage240230220210208
Correction Factor1.000.920.840.770.75
Multiply the 240-volt heating capacity by correction factors.
2www.daikincomfort.comSS-DHKR
AIR HANDLER ELECTRICAL DATA— DVPVC
P
RODUCT SPECIFICATIONS
Model &
Heat Kit Usage
DV24PVCC14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
DV36PVCD14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC20D#*
HKSC15XF*
HKSC20XF*
DV48PVCD14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC20D#*
HKSC15XF*
HKSC20XF*
DV60PVCD14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC20D#*
HKSC15XF*
HKSC20XF*
HKSC25DC*
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps
^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits
* Revision level that may or may not be designated
C = Circuit Breaker Option
--- indicates Not Required
HKA meets the new UL1995 requirements for 15 and 20KW heaters
AmpsMCA¹MOP²AmpsMCA¹MOP²MCA¹MOP²
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
34.7/40.0
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
34.7/40.0
34.7/40.0
0.0/0.0
0.0/0.0
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
34.7/40.0
34.7/40.0
0.0/0.0
0.0/0.0
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
34.7/40.0
34.7/40.0
0.0/0.0
0.0/0.0
52.0/60.0
Circuit 1Circuit 2Single-Point Kit
4.9/4.9
18/21
27/30
32/36
41/47
48/55
48/55
6.5/6.5
20/22
28/32
34/38
43/48
50/57
50/57
50/57
6.5/6.5
6.5/6.5
6.5/6.5
20/22
28/32
34/38
43/48
50/57
50/57
50/57
6.5/6.5
6.5/6.5
8.6/8.6
22/24
30.3/34
36/40
45/50.3
52/59
52/59
52/59
8.6/8.6
8.6/8.6
74/84
15/15
20/25
30/30
35/40
45/50
50/60
50/60
15/15
20/25
30/35
35/40
45/50
50/60
50/60
50/60
15/15
15/15
15/15
20/25
30/35
35/40
45/50
50/60
50/60
50/60
15/15
15/15
15/15
25/25
35/35
40/40
45/60
60/60
60/60
60/60
15/15
15/15
80/90
---
---
---
---
---
---
17.3/20.0
---
---
---
---
---
---
17.3/20.0
34.7/40
30.0/34.6
37.5/43.3
---
---
---
---
---
---
17.3/20.0
34.7/40
30.0/34.6
37.5/43.3
---
---
---
---
---
---
17.3/20
34.7/40.0
30.0/34.6
37.5/43.3
35/40
---
---
---
---
---
---
22/25
---
---
---
---
---
---
22/25
43/50
38/43
47/54
---
---
---
---
---
---
22/25
43/50
38/43
47/54
---
---
---
---
---
---
22/25
43/50
38/43
47/54
43/50
---
---
---
---
---
---
25/25
---
---
---
---
---
---
25/25
45/50
40/45
50/60
---
---
---
---
---
---
25/25
45/50
40/45
50/60
---
---
---
---
---
---
25/25
45/50
40/45
50/60
45/50
---
---
---
---
---
---
70/80
---
---
---
---
---
---
72/82
93/107
---
---
---
---
---
---
---
---
72/82
93/107
---
---
---
---
---
---
---
---
74/84
95/109
---
---
117/134
---
---
---
---
---
---
70/80
---
---
---
---
---
---
80/90
100/110
---
---
---
---
---
---
---
---
80/90
100/110
---
---
---
---
---
---
---
---
80/90
100/110
---
---
125/150
SS-DHKRwww.daikincomfort.com3
P
RODUCT SPECIFICATIONS
AIR HANDLER ELECTRICAL DATA— DVPTC
Model &
Heat Kit Usage
DVPTC24B14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
DVPTC30C14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
DVPTC36C14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC19C#*
HKSC15XF*
DVPTC48C14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC19C#*
HKSC15XF*
DVPTC42D14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC20D#*
HKSC15XF*
HKSC20XF*
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protection Device @ 208 / 240V
^ Heat Kit requires three-phase power supply
* Revision level that may or may not be designated
C = Circuit breaker option
--- indicates Not Required
NOTES
• All HKR ampacities noted above include air handler motor amps, excluding three-phase models.
• HKA meets the new UL1995 requirements for 15 and 20KW heaters; HKR-21C* is Obsolete; no replacement
Heater AmpsMCA¹MOP²Heater AmpsMCA¹MOP²MCA¹MOP²
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
34.7/40.0
34.7/40.0
0.0/0.0
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
34.7/40.0
34.7/40.0
0.0/0.0
0.0/0.0
10.8/12.5
17.3/20.0
21.7/25.0
28.9/33.3
34.7/40.0
34.7/40.0
34.7/40.0
0.0/0.0
0.0/0.0
Circuit 1Circuit 2Single-Point Kit
4.9/4.9
18/21
27/30
32/36
41/47
48/55
4.9/4.9
18/21
27/30
32/36
41/47
48/55
6.5/6.5
20/22
28/32
34/38
43/48
50/57
50/57
50/57
6.5/6.5
6.5/6.5
20/22
28/32
34/38
43/48
50/57
50/57
50/57
6.5/6.5
6.5/6.5
20/22
28/32
34/38
43/48
50/57
50/57
50/57
6.5/6.5
6.5/6.5
15/15
20/25
30/30
35/40
45/50
50/60
15/15
20/25
30/30
35/40
45/50
50/60
15/15
20/25
30/35
35/40
45/50
50/60
50/60
50/60
15/15
15/15
20/25
30/35
35/40
45/50
50/60
50/60
50/60
15/15
15/15
20/25
30/35
35/40
45/50
50/60
50/60
50/60
15/15
15/15
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
17.3/20.0
34.7/40
30.0/34.6
---
---
---
---
---
---
17.3/20.0
34.7/40
30.0/34.6
---
---
---
---
---
---
17.3/20.0
34.7/40
30.0/34.6
37.5/43.3
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
22/25
43/50
38/43
---
---
---
---
---
---
22/25
43/50
38/43
---
---
---
---
---
---
22/25
43/50
38/43
47/54
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
25/25
45/50
40/45
---
---
---
---
---
---
25/25
45/50
40/45
---
---
---
---
---
---
25/25
45/50
40/45
50/60
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
72/82
93/107
---
---
---
---
---
---
---
72/82
93/107
---
---
---
---
---
---
---
72/82
93/107
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
80/90
100/110
---
---
---
---
---
---
---
80/90
100/110
---
---
---
---
---
---
---
80/90
100/110
---
---
4www.daikincomfort.comSS-DHKR
AIR HANDLER ELECTRICAL DATA— DVPTC (CONT.)
P
RODUCT SPECIFICATIONS
Model &
Heat Kit Usage
DVPTC48D14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC20D#*
HKSC15XF*
HKSC20XF*
HKSC25DC*
DVPTC60D14A*
HKS*03XC*
HKS*05XC*
HKS*06XC*
HKS*08XC*
HKS*10XC*
HKSC15*#*
HKSC20D#*
HKSC15XF*
HKSC20XF*
HKSC25DC*
¹ Minimum Circuit Ampacity @ 208 / 240 V
² Maximum Overcurrent Protection Device @ 208 / 240V
^ Heat Kit requires three-phase power supply
* Revision level that may or may not be designated
C = Circuit breaker option
--- indicates Not Required
NOTES
• All HKR ampacities noted above include air handler motor amps, excluding three-phase models.
• HKA meets the new UL1995 requirements for 15 and 20KW heaters; HKR-21C* is Obsolete; no replacement
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps
^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits
* Revision level that may or may not be designated
C = Circuit Breaker Option
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps
^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits
* Revision level that may or may not be designated
C = Circuit Breaker Option
¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25
² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps
^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits
* Revision level that may or may not be designated
C = Circuit Breaker Option
--- indicates Not Required
8www.daikincomfort.comSS-DHKR